duct manufacturers/assemblers/distributors checklist

advertisement
Flexible Duct AS 4254.1 and AS 4859.1 checklist for
compliance with NCC 2013 as of 1 May 2013
AS 4254 checklist
Duct Manufacturers Name........................................................................
Ducts recognized trade name as sold to market......................................
Material R Values for the insulation used on this duct..........................
Country where duct was manufactured..................................................
AS4254.1
2012
FLEXIBLE DUCT REQUIREMENTS
1.6- TESTING
COMPLIES
(please circle)
CLAUSE
If either insulated or uninsulated flexible duct is required to be subjected to fire and
mechanical tests or thermal tests, all such testing shall be carried out by a registered NATA
testing laboratory as defined in the National Construction Code. Samples submitted for
prototype testing shall be identical to manufactured product supplied to market under the fire,
mechanical and thermal test certificates. In order for supplied manufactured product to be
identified and compared with supplied test certificates, the certificates shall include the
following minimum product data:
a) Manufacturer’s name and product’s recognised trade name.
b) Information required by the ‘Flexible Duct Compliance Report Summary’ (see Clause 2.9
and Appendix A).
A product shall comply with all the requirements of this standard before compliance can be
claimed.
Does the above mentioned product meet all of the requirements of Clause 1.6?
2.4.1- General
2.8- VALIDITY
PERIOD FOR
TEST RESULTS
2.9- FLEXIBLE
DUCT
COMPLIANCE
REPORT
SUMMARY +
Appendix A
YES/NO
The insulated or uninsulated flexible duct (the assembled final product) samples submitted
for testing shall be identical to manufactured product supplied to market under the fire,
mechanical and thermal test certificates..
Does the above mentioned product meet this requirement of Clause 2.4.1?
YES/NO
Are all of the 11 test reports used to determine the product named above compliant to
AS 4254 2002; less than 10 years old?
YES/NO
Original copies of 11 NATA - Test Reports to substantiate claims made in Flexible Duct
Compliance Report Summary for the 2 burn and 9 fit for purpose (mechanical) tests that
comprise AS 4254 2002 are readily available for download from duct manufacturer's website.
YES/NO
2.4.3- Fire
performance
AS/NZS 1530.3 1999 Burning test requires only 2 results of the possible 4 results to comply
with AS 4254 2002. “4 Zero” compliance is NOT required in AS 4254 2002 nor AS 4254.1
2012.
YES/NO
Do the 2 x AS/NZS 1530.3 1999 tests indices results specified in AS 4254 2002 comply?
The 2 specified tests are;
2.4.3
Mechanical
Performance
2.4.2
2.4.2
2.4.2
2.4.2
2.4.2
2.4.2
2.4.2
2.4.2

Test 1, AS1530.3- Smoke developed - indices result not greater than 3
YES/NO

Test 2, AS1530.3- Spread of flame – indices result not greater than 0
YES/NO
UL 181.9 – Burning Test
UL 181.11 - Mechanical - Mould growth and humidity Test
UL 181.12 - Mechanical - Temperature Test
UL 181.13 - Mechanical - Puncture Test
UL 181.14 - Mechanical - Static load Test
UL 181.15 - Mechanical - Impact Test
UL 181.17 - Mechanical - Pressure Test
UL 181.18 - Mechanical - Collapse Test
UL 181.19 - Mechanical - Tension Test
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
2.9- FLEXIBLE
DUCT
COMPLIANCE
REPORT
SUMMARY
Is an individual Flexible Duct Compliance Report Summary for the product named
above readily available for download from duct manufacturer website?
YES/NO
2.6- THERMAL
INSULATION
USED ON
FLEXIBLE
DUCT
Were the Material R Values (R m) claimed for the insulation used in the construction of
the product named above determined by testing conducted in a NATA certified
laboratory as a low density fibrous insulation as per AS/NZS 4859.1 2002 Table 2.1 +
Clause 2.3.2 (c)?
YES/NO
2.7LABELLING
OF FLEXIBLE
DUCT
Is the outer duct sleeve/jacket on the product named above clearly labelled at least
every 1000 mm with all the requirements of this clause including; the duct
manufacturer's name, compliance to AS 4254.1 2012 and the Material R Value of the
insulation used in its construction?
YES/NO
AS4254.1 2012
CLAUSE 2.6
Current insulation supplier's NATA certified test certificates must be readily available upon
request and/or from duct manufacturers website for each Material R Value (R m) claimed by
the duct manufacturer .
+ AS/NZS 4859.1
2002
CLAUSE 4.4 (f)
Demonstration of
Compliance
AS/NZS
4859.1 2002
CLAUSE
4. 2ACCEPTANCE
OF TESTING +
Note 1
Is there a test report available for insulation rated to:
-R m 0.6
-R m 1.0
-R m 1.5
-R m 2.0
-R m 2.4
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
REQUIREMENTS FOR INSULATION USED IN THE
CONSTRUCTION OF FLEXIBLE DUCT
COMPLIES
Is the laboratory used to determine the Material R Values (Rm) claimed on the product
named above a NATA laboratory that has been certified by NATA to conduct AS/NZS
4859.1 2002 testing?
YES/NO
(please circle)
2.3.2(c)Classification +
Table 2.1
Were the Material R Values (Rm) specified for the insulation used in the construction of
the product named above determined by testing as a low density fibrous to ASTM
YES/NO
C 653 and Appendix D?
2.2- VALIDITY
OF TEST
RESULTS
Is each of the NATA certified test reports provided by the current supplier of insulation
to the duct manufacture used to determine each material thermal value for the product
named above less than 5 years old?
3.1 General +
Figure 3.1 +
Note on page 18
Does the distance between the outer duct sleeve and duct core allow the insulation to fit
in an "unrestrained state" snugly between the outer duct sleeve and duct core and allow
the insulation to return to the “average recovered or installed thickness" stated in the
NATA certified test reports?
YES/NO
YES/NO
Fit for purpose:
Insulation supplied by insulation manufacturer to duct manufacturer
Does the insulation when removed from the insulation manufacturer's packaging (as supplied
to the duct manufacturer as standard, i.e. compression packed or non compression packed)
recover to the following;

The nominal stabilized thickness within 24 hours after being conditioned at 45C.
YES/NO
Is this requirement met?

It is a requirement of AS 4859.1 2002 that both nominal stabilised thickness and
declared thermal resistance must be on the insulation manufacturers packaging (as
supplied to the duct manufacturer as standard, i.e. compression packed or non
compression packed). Are both these requirements met?
YES/NO
The following clauses from the thermal standard AS 4859.1 refer to the two ‘fit for purpose’
questions above.
See Appendix to refer to each individual clause.
2.2
2.3.1
2.3.3.7
2.3.3.7
3.1
3.1
3.1.1
7.2.1
7.2.1
7.2.1
Validity of test results
Thermal resistance- General
Thermal resistance- Low density fibrous materials
Note
General
General note
Table- Labelling requirements
Performance criteria and technical provisions- Thermal resistance
Thermal resistance note 1
Thermal resistance note 2
Fit for purpose:
Insulation used within the construction of the insulated flexible duct.
Does the insulation used within the product named above after being removed from its
standard compressed packaged state ( as sold to market) and after being allowed the
nominated days to recover to declared nominal stabilised thickness as purchased from the
insulation manufacturer;

Achieve the declared nominal stabilized thickness as purchased from the insulation
manufacturer.
The following clauses from the thermal standard AS4859.1 refer to the fit for purpose
questions above.
See Appendix to refer to each individual clause.
Thermal Standard Preface
YES/NO
2.2
2.3.1
2.3.3.7
3.1
3.1
3.1.1
7.2.1
7.2.1
Validity of test results
Thermal resistance- General
Thermal resistance- Low density fibrous materials
General
General note
Table- Labelling requirements
Performance criteria and technical provisions- Thermal resistance
Thermal resistance note 2
IF YOU ARE A DUCT MANUFACTURER AND BUY IN INSULATION FROM AN
INSULATION SUPPLIER YOU MUST COMPLY WITH THE FOLLOWING
REQUIREMENTS
On the
label
In the
report
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
Does the NATA certified test reports and the labelling on the packaging provided by your
current insulation supplier which are used to substantiate each different material thermal
value for the product named above sold to market by the duct manufacturer named above
include the following information;
Table 3.1
The products name?
The name and address of the insulation manufacturer where the insulation was produced?
A statement of compliance to AS/NZS 4859.1 2002?
The Declared Material R Values?
The grams per m2 (gsm) of insulation blanket?
The length and width of the product?
The nominated stabilized thickness (or the installed thickness of the insulation at a nominated
period of days after the flexible duct is installed)?
List the material thermal value of each blanket sited that meets the 14 point criteria list
above.
1._____
2._______ 3.________ 4._________ 5.__________ 6._________
IF YOU ARE A DUCT MANUFACTURER AND PRODUCE YOUR OWN
INSULATION YOU MUST COMPLY WITH THE FOLLOWING REQUIREMENTS
Appendix A
A4 Note 2
Table 3.1
Where insulation is produced in-house by a duct manufacturer, irrespective of all internal
management systems applied, the responsibility to conform to the full requirements of
AS/NZS 4859.1 2002 lies with the duct/insulation manufacturer. Appropriate in house
quality management systems are set out in AS/NZS ISO 9001 and AS/NZS ISO 9004.
Are the various Material R values as well as all other properties stated within in-house
quality management systems consistent with the random insulation samples viewed?
YES/NO
Does the NATA certified test reports which are used to substantiate each different material
thermal value for the product named above sold to market by the duct manufacturer named
above include the following information;
In the report
The product name?
The name and address of the insulation manufacturer where the insulation was produced?
A statement of compliance to AS/NZS 4859.1 2002?
The Declared Material R Values?
The grams per m2 (gsm) of insulation blanket?
The length and width of the product?
The nominated stabilized thickness (or the installed thickness of the insulation at a nominated
period of days after the flexible duct is installed)?
List the material thermal value of each blanket sited that meets the 7 point criteria list above.
1._____
2._______ 3.________ 4._________ 5.__________ 6._________
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
APPENDIX TO AS 4254.1-2012 CHECKLIST
INDEX FOR CHECKLIST OF REFERENCED CLAUSES FROM
AUSTRALIAN STANDARDS
AS 4254.1 2012
CLAUSE
1.6
2.4.1
2.4.2
2.4.3
2.6
2.7
2.8
2.9
AS/NZS 4859.1
2002
CLAUSE
Preface
2.2
2.3.1
2.3.2
2.3.3.7
3.1
4.2
4.4
7.2.1
CLAUSE TITLE
APPENDIX
PAGE
NUMBER
Testing
Test criteria- General
Test criteria- Mechanical performance
Test criteria- Fire performance
Thermal insulation used on flexible duct
Labelling of flexible duct
Validity period for test results
Flexible duct compliance report summary
2
2
2
3
3
3
3
4
APPENDIX
CLAUSE TITLE
PAGE
NUMBER
Preface
Validity of test results
Thermal resistance- General
Thermal resistance- Classification
Thermal resistance- Low density fibrous materials
General
Acceptance of testing
Demonstration of compliance
Performance criteria and technical provisionsThermal resistance
4
4
4
4
5
5
6
6
6
ADDITIONAL INFORMATION
PAGE
1. Schedule of referenced Australian Standards in NCC 2013
9
2. Schedule of referenced tests mentioned in Australian Standards
9
3. Testing authorities certified by NATA to conduct the nominated test(s)
9
APPENDIX TO AS 4254.1 2012 CHECKLIST
REFERENCED AUSTRALIAN STANDARDS CLAUSES
AS4254.1 2012
CLAUSE
1.6 TESTING
If either insulated or uninsulated flexible duct is required to be subjected to fire and
mechanical tests or thermal tests, all such testing shall be carried out by a registered
NATA testing laboratory as defined in the National Construction Code. Samples
submitted for prototype testing shall be identical to manufactured product supplied to
market under the fire, mechanical and thermal test certificates. In order for supplied
manufactured product to be identified and compared with supplied test certificates, the
certificates shall include the following minimum product data:
a) Manufacturer’s name and product’s recognised trade name.
b) Information required by the ‘Flexible Duct Compliance Report Summary’ (see Clause
2.9 and Appendix A).
Testing authorities shall keep records of adhesive type, coat weight and all flame
retardants used in the adhesives for all facings and lining materials of a composite nature
that are bonded together with fire-retardant adhesives during inner core and/or sleeve
manufacturer.
A product shall comply with all the requirements of this standard before compliance can
be claimed.
2.4 TEST CRITERIA
2.4.1 General
All insulated and uninsulated flexible duct shall be tested in accordance with UL 181 and
AS/NZS 1530.3 for the mechanical and fire performance requirements of Clauses 2.4.2
and 2.4.3. All tests shall be carried out on 300 mm internal diameter flexible duct. All
tests shall be carried out on the flexible duct system, i.e the insulated or uninsulated
assembled final product, as opposed to individual layers. Samples submitted for testing
shall be identical to manufactured product supplied to market under the fire, mechanical
and thermal test certificates.
2.4.2 Mechanical
Performance
All insulated and uninsulated flexible duct shall be tested in accordance with UL 181 for
the following mechanical properties:
a) Mould growth and humidity.
b) Temperature- The low temperature test shall be carried out at -10°C and the high
temperature test at 78° for both interior and exterior surfaces. High temperature tests
shall be carried out for a minimum period of seven days.
c) Puncture.
d) Static load.
e) Impact- The impact test does not apply to metal duct as defined in Clause 2.3.
f) Pressure- The pressure test shall be carried out at 1000 Pa.
g) Collapse- The collapse test shall be carried out at 200 Pa.
h) Tension.
Where an uninsulated flexible duct (flexible duct core) passes the pressure, collapse,
impact and tension tests, it need not be retested as an insulated flexible duct for these
tests only, provided an identical flexible duct core construction is used.
2.4.3 Fire
performance
The tests for fire performance are applicable to flexible duct only, not joining materials.
All insulated and uninsulated flexible duct shall be tested for fire performance as
follows:
a) The flexible duct system, tested in accordance with AS/NZS 1530.3, shall have a
smoke developed index not greater than ‘3’ and spread the flame index not greater than
‘0’.
b) The flexible duct system shall pass the UL 181 burning test. The UL 181 burning test
shall be carried out with the following qualifications:
i) Gas shall be propane with a fuel content of approximately 93 MJ/m
.
ii) The Bunsen burner shall have a 9.5±0.1 mm inside diameter.
iii) Fuel/Air mixture shall be such that a half blue/half yellow flame is produced.
iv) The flame height shall be approximately 63 mm and half of the flame shall impinge
on the duct.
v) The sample shall be fully extended, uncompressed and conditioned for 24 h at 20±2°C
and 65±5%RH.
vi) Ambient conditions in the laboratory shall be between 10°C and 30°C, and 15% and
80% RH.
2.6 THERMAL
INSULATION USED
ON FLEXIBLE DUCT
The insulation of flexible duct shall be achieved by integrating the insulation material
into the construction of the flexible duct (i.e. the flexible duct system).
To determine the flexible duct’s R value, only the insulation material shall be thermally
tested as low density fibrous insulation as per AS/NZS 4859.1:2002, Clause 2.3.2(c) and
Tale 2.1 (as amended by Amd.1 (2006)). The insulation material shall not be tested as a
formed shape as described in AS/NZS 4859.1:2002, Clause 2.3.2(a).
2.7 LABELLING OF
FLEXIBLE DUCT
Labelling of the outer jacket/sleeve of all insulated flexible duct shall comply with the
following:
a) Labelling shalli) be repeated along with the total length of the duct at 1000 mm intervals.
ii) be legible for the flexible duct’s service life; and
iii) have characters at least 10 mm high.
NOTE: Spiral labelling of the outer jacket/sleeve is permitted as long as it complies with
Clause 2.7.
b) The label on the outer jacket /sleeve of all insulated flexible ductwork shall include
the following information:
i) Name of manufacturer.
ii) Compliance with AS 4254.1.
iii) The R value of the flexible duct.
2.8 VALIDITY
PERIOD FOR TEST
RESULTS
For insulated and uninsulated flexible duct tested to this Standard, flexible duct that has
no change in raw material and/or component supplier and/or formulation and/or design,
the test results shall be valid for a maximum period of ten years from the date of NATA
certified laboratory test.
Any changes made by the flexible duct manufacturer to raw material and/or component
supplier and/or formulation and/or design shall invalidate the test results, and retesting
shall be required.
2.9 FLEXIBLE DUCT
COMPLIANCE
REPORT SUMMARY
NOTE: THIS SUMMARY
CAN BE FOUND AT THE
END OF THIS
DOCUMENT.
All manufacturers and suppliers of flexible duct shall supply the Flexible Duct
Compliance Report Summary to substantiate compliance with this Standard upon
request. The Flexible Duct Compliance Report Summary shall comply with Appendix A.
A separate Flexible Duct Compliance Report Summary shall be used for each different
branded product line, but not for each different thermally-rated product that utilizes the
same type of insulation material within each product line.
AS/NZS 4859.1
2002
CLAUSE
PREFACE
The objective of this Standard is to address the standardization and performance
verification requirements of all thermal insulation materials that may be used in
buildings. Insulation materials or assemblies are broadly classified into groups, having
different testing requirements over a number of aspects of performance. Particular
emphasis has been given to the development of clear and concise requirements for
determination and labelling of thermal performance, a primary performance requirement
for these materials.
2.2 VALIDITY OF
TEST RESULTS
For materials that do not change in formulation or design, the test results shall be valid
for a maximum period of 5 years from the date of measurement, computation or test.
Any changes made by the manufacturer to formulation or design, which may affect the
performance, shall invalidate test results, and retesting shall be required.
2.3 THERMAL
RESISTANCE
2.3.1 General
Thermal resistance of insulation materials may be highly dependant on boundary
conditions and other environmental factors encountered in buildings and common
insulation delivery systems. Thermal resistance (material, system or total) refers to the in
situ or in-service condition. It is the intent of the methods and procedures contained in
this Standard that the measured and/or declared thermal resistance shall reflect as
accurately as possible the performance encountered within buildings.
NOTES:
-Some materials may achieve a thermal resistance that is lower in the long term than
at the time of installation. Common causes include the settlement of dust on
reflective insulations, outgassing of blowing gasses in foam insulations and
settlement of loose fill insulations. The declared thermal resistance should be the
value achieved in the long term (see ISO 10456).
-Some compression-packaged materials may take time to achieve their stabilized
thickness and R-value. When the declared R-value is not expected to be achieved
until some time after installation, that time should be stated on the label.
-The moisture content of materials will affect their thermal resistance.
2.3.2 Classification
c) Low density fibrous Pre-formed insulation, including blanket, commonly
compressible, that may be supplied cut into pieces and usually supplied compression
packaged, e.g., rock wool, glass wool, polyester fibre, wool and like materials. Materials
of this type are expected to exhibit substantial variation in density, thickness, resiliency,
and thickness regain, after compressed packaging.
2.3.3 Determination of
R-value
TABLE 2.1
STANDARD METHODS FOR DETERMINATION OF THERMAL
PROPERTIES
Classification
Test Methods
Low density fibrous
ASTM C 653 and Appendix D
2.3.3.7
Low density fibrous
materials
The declared thermal resistance (material R-value) of any lot (as described in ASTM C
653) of low density fibrous insulation shall not be greater than the actual average thermal
resistance of the lot as determined in accordance with Clause 2.2.
The declared thermal resistance of the lot (material R-value) shall be a value such that
not less than 95% of individual packs of low-density fibrous insulation shall have an
average thermal resistance, as determined in accordance with Clause 2.2, that is not less
than 90% of this declared thermal resistance.
The declared thermal resistance (material R-value) shall apply to the material-
a) in an unrestrained state; and
b) in a dry (ambient) state.
NOTE: Thickness reduction due to compression, or the presence of free water, will
reduce the thermal resistance of the material.
3.1 GENERAL
The insulation material or assembly shall be packaged by the manufacturer or agent in
such a way as to provide adequate protection during handling, transport and storage.
Type of material
Information required
Packaging shall be adequate to provide reasonable expectation that performance will be
maintained through normal storage and handling, with particular regard to the possible
effects of excessive compression.
Labelling shall include the terms; ‘R-value’ and/or ‘Thermal Resistance’ to describe
thermal resistance values. These terms shall be qualified with the term ‘declared’
together with the term ‘material’.
The declared R-value shall be the long-term value and shall take into account the
derating that may arise through aging or environmental factors (see Clause 2.3.1).
Labelling shall comply with Table 3.1. Additional information may be provided by the
manufacturer or agent. The required information shall be conspicuous.
Where the product is supplied for retail sale in packaged quantities, labelling in
accordance with Table 3.1 shall be provided with each package.
Where the product is not supplied in packaged quantities with labelling in accordance
with Table 3.1, the manufacturer shall supply documentation that conveys the same
information as Table 3.1.
NOTE: Formed shapes and low-density fibrous materials may be used in situations
where space is limited. In order to ascertain that the material will fit within an available
space without being compressed, the product thickness, as stated on the label, should be
noted. Loss of material R-value due to compression is less than the loss in thickness.
Typically 5% loss of material R-value may occur for a 10% loss in thickness, depending
on the initial density and the type of material.
All types
-Product name
-Description of contents
-Name and address of manufacturer
-Batch identification or other traceability information
-Safety instructions
-A statement of compliance with this Standard, i.e., AS/NZS
4859.1
-One declared R-value (m2.K/W), accompanied by a clear
statement as to the conditions under which it applies and
preceded by the qualifier ‘Material’.
TABLE 3.1
LABELLING
REQUIREMENT
Low-density fibrous
-The statement ‘This pack complies with AS/NZS 4859.1 for a
net weight of xx kg, a total area or yy m2 and a mean thickness
or zz mm’ where xx, yy and zz appear on a valid and current
report of measurement of thermal resistance in accordance with
this standard.
-Declared material R-value (2006 amendment)
- Number of pieces
-Nominal total area (m2)
-Nominal length and width of each piece
-Nominal stabilized thickness
-A statement of the time after installation to achieve nominal
stabilized thickness and R-value
- A statement ‘the performance of this product may be reduce if
stored for too long in its compression packaging’
-A statement ‘the total R-value depends on installation and may
be greater than or less than the R-value of the product’
4.2 ACCEPTANCE OF
TESTING
Where a performance is measured by testing, it shall be performed by a recognized
laboratory (see note 1).
NOTES:
1.
2.
A recognized laboratory should have accreditation or recognition for testing to
the relevant standards and procedures, either to ISO 17025 or to the
requirements of a recognized national laboratory accreditation scheme.
It is expected that the application and levels of all factors affecting the thermal
resistance would be standardized by agreement between recognized
laboratories.
4.4
DEMONSTRATION
OF COMPLIANCE
f) Copies of test and calculation reports to be made available upon request.
7.2 PERFORMANCE
CRITERIA AND
TECHNICAL
PROVISIONS
As polyester can exhibit slow loft recovery after compression packaging, the product
shall be conditioned at 45±1°C for 24h to accelerate relofting prior to thermal testing.
The thermal resistance shall be determined at the lesser of the relofted thickness and the
declared thickness.
7.2.1 Thermal
resistance
NOTES:
1. If the artificially lofted thickness is less than the label declared thickness, the product
may be tested for thermal resistance using ASTM C653 to determine the R-value of the
pack at the artificially lofted thickness. If the thickness is less than the declared value, the
thermal resistance will probably also be lower. For example, a 10% shortfall in thickness
is likely to result in a 5% lower thermal resistance.
2. Polyester typically recovers to a stable thickness within a month after installation
depending on the degree of packaging compression and the ambient environmental
conditions. The label is required to carry a declaration of the time interval after
installation that the product will achieve the declared thickness and, therefore, R-value.
The conditioning requirements of this Standard are to expedite product thermal testing,
and the ability of the product to naturally loft to its declared thickness has to be proven in
addition to the thermal resistance measurement.
7.2.1 Thermal
resistance
APPENDIX A
NOTE 2
If the above methods are considered inappropriate, determination of compliance with the
requirements of this Standard may be assessed by being based on the results of testing
coupled with the manufacturer’s guarantee of product conformance. Irrespective of
acceptable quality levels or test frequencies, the responsibility remains with the
manufacturer or supplier to supply products that conform with the full requirements of
the Standard.
SCHEDULE OF REFERENCED AUSTRALIAN STANDARDS IN NCC 2013

AS/NZS 4859.1 2002 inc. AMMENDMENT No. 1/2006 12-28
Materials for thermal insulation used in buildings

AS 4254.1 2012
Ductwork for air handling systems in buildings, Part 1 Flexible Duct.

AS/NZS1530.3 1999
Method for fire tests on building components: Simultaneous determination of flame
propagation and smoke release
SCHEDULE OF REFERENCED TESTS IN THE ABOVE MENTIONED AUSTRALIAN
STANDARDS
Where AS/NZS 4859.1 2002 inc. AMMENDMENT No. 1/2006 12-28 is specified;
ASTM 653 C and Appendix D is the only test recognized to determine material R value (R m) of
insulation blanket used in the construction of insulated flexible duct
AS 4254.1 2012
UL 181.9 - Burning Test
UL 181.11 - Mechanical - Mould growth and humidity Test
UL 181.12 - Mechanical - Temperature Test
UL 181.13 - Mechanical - Puncture Test
UL 181.14 - Mechanical - Static load Test
UL 181.15 - Mechanical - Impact Test
UL 181.17 - Mechanical - Pressure Test
UL 181.18 - Mechanical - Collapse Test
UL 181.19 - Mechanical - Tension Test
AS/NZS 1530.3 1999
The 2 AS/NZS 1530.3 1999 test indices results that are a requirement of AS/NZS 4254.1.2012 are;
1. Smoke developed indices - result not greater than 3
2. Spread of flame indices – result not greater than 0
TESTING AUTHORITES CERTIFIED BY NATA TO CONDUCT THE NOMINATED
TEST(S)
NOTE: Not all NATA accredited laboratories are certified to conduct the nominated testing to the
requirements of AS/NZS 4859.1 2002, AS 4254.1 2012 and AS 1530.3 1999.
BRANZ
AS/NZS 4859.1 2002 inc. AMMENDMENT No. 1/2006 12-28
ASTM 653 C and Appendix D
|AWTA
AS 4254.1 2012
UL 181.9 - Burning Test
UL 181.11 - Mechanical - Mould growth and humidity Test
UL 181.12 - Mechanical - Temperature Test
UL 181.13 - Mechanical - Puncture Test
UL 181.14 - Mechanical - Static load Test
UL 181.15 - Mechanical - Impact Test
UL 181.17 - Mechanical - Pressure Test
UL 181.18 - Mechanical - Collapse Test
UL 181.19 - Mechanical - Tension Test
AS/NZS 1530.3 1999
The 2 AS/NZS 1530.3 1999 test indices results that are a requirements of AS/NZS 4254.1.2012 are;
1. Smoke developed indices -result not greater than 3
2. Spread of flame indices –result not greater than 0
CSIRO
AS 4254.1 2012
UL 181.9 – Burning Test
AS/NZS 1530.3 1999
The 2 AS/NZS 1530.3 1999 test indices results that are a requirements of AS/NZS 4254.1.2012 are;
1. Smoke developed indices -result not greater than 3
2. Spread of flame indices –result not greater than 0
VIPAC
None
Download