1 Supplemental Information for 2 Ultrafine particle removal by residential HVAC filters 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Brent Stephens1,* and Jeffrey A. Siegel2,3 1 Department of Civil, Architectural and Environmental Engineering, Illinois Institute of Technology, Chicago, IL USA 2 Department of Civil, Architectural and Environmental Engineering, The University of Texas at Austin, Austin, TX USA 3 Department of Civil Engineering, The University of Toronto, Toronto, ON Canada Author contact information: Brent Stephens, Ph.D.* Department of Civil, Architectural and Environmental Engineering Illinois Institute of Technology Alumni Memorial Hall Room 212 3201 South Dearborn Street Chicago, IL 60616 Phone: (312) 567-3540 Fax: (312) 567-3519 Email: brent@iit.edu *Corresponding author Jeffrey A. Siegel, Ph.D. Department of Civil Engineering University of Toronto 35 St. George St. Toronto, ON M5S 1A4 Phone: (416) 978-7975 Fax: (416) 978-6813 Email: jeffrey.siegel@utoronto.ca 32 UTest House CO2 CO2 LAUNDRY ROOM E LAUNDRY ROOM LAUNDRY ROOM CO2 CO2 MASTER BATHROOM DINING ROOM CO2 MASTER BATHROOM CO2 MASTER DINING E BATHROOM ROOM CO2 ECO CO2 CO2 CO2 BATHROOMROOM CONTROL CONTROL ROOM CO2 CO2 UP FLOW HVAC E CONTROL ROOM HVAC CO2 CO2 CO2 2 DINING KITCHEN UP ROOM FLOW OPC BATHROOM KITCHEN BATHROOM KITCHEN CO2 E CO2 CO2 E UP FLOW HVACCO2 OPC DOWN FLOW HVAC DOWN FLOW HVAC OPC DOWN FLOW HVAC CO2 COLIVING ROOM 2 LIVING ROOM MASTER BEDROOM SMALL BEDROOM SMALL E BEDROOM E CO2 SMPS LIVING ROOM MASTER BEDROOM SMALL BEDROOM E HEPA HEPA MASTER BEDROOM CO2 33 34 35 36 37 38 39 Figure S1. Photograph and floor plan of the test house. The floor plan includes locations of the AHUs, mixing fans, CO2 instrumentation, incense emission sources (labeled “E”), and the particle instrumentation (labeled “SMPS”). HEPA Airflow Rate Measurement The airflow measurement procedure was performed once using an Energy Conservatory 40 TrueFlow plate and DG-700 digital manometer installed; the airflow rate for each filter condition 41 was then estimated by correcting for the measured operating supply plenum pressure using a 42 procedure in the TrueFlow plate manual (where the airflow rate with a filter installed is equal to 43 the airflow rate with the TrueFlow plate installed multiplied by the square root of the ratio of the 44 supply plenum pressure with the filter installed to the supply plenum pressure with the TrueFlow 45 plate installed). The flow plate has a manufacturer-reported uncertainty of ±7% of its reading, 46 although conversations with the manufacturer suggest lower actual uncertainties for situations 47 where repeated flows in the same system are compared; therefore, ±5% was used in previous 48 work (Stephens et al., 2010a; Stephens et al., 2010b) and was also used here. Indoor temperature 49 and relative humidity were measured upstream of the HVAC system using an Energy 50 Conservatory Automatic Performance Testing System with thermistors and capacitance sensors 51 connected, both logging at 1-minute intervals (manufacturer-reported accuracies were ±0.2°C for 1 52 temperature and ±5% for RH). The same system also measured and logged the pressure drop 53 across the filter (if installed) and the pressure in the supply plenum at the same intervals. 54 Air Exchange Rate Measurement 55 To measure the air exchange rate (AER) during each test condition, CO2 was injected 56 into each room of the house from a cylinder connected to a mass flow controller. Injection 57 occurred during the particle concentration elevation phase and proceeded until the CO2 58 concentration in each room was at least 500 ppm or greater above background. CO2 59 measurements were made at one-minute intervals in 7 locations (6 within the test house and one 60 outdoors, as shown in Figure S1) with dual beam infrared absorption CO2 monitors (GE Telaire 61 Model 7001) connected to a data acquisition system in the control room. Only data from the CO2 62 monitor in the central living room were used to estimate whole-house air exchange rates (AERs) 63 using the subsequent tracer gas decay rate, in accordance with ASTM E 741 (2006). 64 Estimation of Parameters 65 66 The filter test method relies on a well-mixed size-resolved number balance of particles of diameter i in the space, assuming no indoor sources of particles, as shown in Equation S1. dCi ,in Q Pi Ci ,out Ci ,in i Ci ,in i ,HVAC HVAC Ci ,in dt V (S1) 67 where Ci,in is the size-resolved indoor particle concentration (# m-3), t is time (hr), Ci,out is the 68 size-resolved outdoor particle concentration (# m-3), λ is the air exchange rate (AER, hr-1), Pi is 69 the envelope penetration factor (dimensionless), βi is the size-resolved deposition rate of particles 70 to indoor surfaces (hr-1), ηi,HVAC is the size-resolved particle removal efficiency of the HVAC 71 system (dimensionless), QHVAC is the airflow rate through the HVAC system (m3 hr-1), and V is 72 the volume of the building (m3). 2 73 74 The size-resolved indoor particle loss rate was then estimated using the first-order decay model in Equation S2. Ci ,in t Ci ,in,t 0e 75 i , HVAC Q HVAC i V t (S2) All of the loss mechanisms present in Equation S2 (λ, βi, and ηi,HVACQHVAC/V) were 76 combined into one lumped loss term for each particle size in the number balance and the test 77 procedure was repeated for the three basic test conditions: (1) with no filter installed and the 78 HVAC system off (i.e., “background” case), (2) with the HVAC system operating and no filter 79 installed (i.e., “no filter” case), and (3) with the HVAC system operating with a test filter 80 installed (i.e., “filter” case). Because AER was measured simultaneously, λ was subtracted from 81 the total loss rate to determine the “effective” loss rate, Li (hr-1), due to surface, HVAC system 82 component, and duct interactions alone (in the no filter case) or the combined effects of surface, 83 HVAC component, duct, and filter interactions (in the filter installed case). 84 Air exchange rates (AERs) were measured during each test in accordance with ASTM E 85 741. AERs were estimated using a nonlinear least squares regression on the solution to a well- 86 mixed balance on the indoor concentration of tracer gas (CO2), as shown in Equation S3. Ct ,in t Ct ,in,t 0 e t Ct ,o u t 1 e t (S3) 87 where Ct,in is the time-varying indoor tracer gas concentration (ppm of CO2), Ct,in,t=0 is the initial 88 indoor tracer gas concentration (ppm of CO2 at time t = 0), and Ct,out is the mean outdoor tracer 89 gas concentration during each experiment (ppm of CO2). Equation S3 assumes no indoor sources 90 of tracer gas during the decay period, which is reasonable for the unoccupied house. 91 92 A nonlinear least-squares regression was performed on the time-series of concentration data from each aggregate particle size bin to estimate total loss rates using Equation S2. The 3 93 indoor particle concentration [Ci,in(t)] was the dependent variable and time (t) was the 94 independent variable, and two size-resolved parameters were estimated: an initial concentration 95 (Ci,in at time t = 0) and the overall particle loss rate (λ + Li). Similarly, a nonlinear least-squares 96 regression was performed on the CO2 time-series to estimate AER for each test condition using 97 Equation S3. The indoor CO2 concentration [Ct,in(t)] was the dependent variable and time (t) was 98 the independent variable; again, two parameters were estimated: an initial concentration (Ct,in at 99 time t = 0) and the AER (λ). 100 Particle Binning 101 Because there were more bins associated with very small particles in the raw data (e.g., 102 seven bins for 3.11-3.85 nm particles, five bins for 5.14-5.94 particles, and three bins for 9.14- 103 9.82 nm particles, etc.), a greater number of bins were combined for small sizes than for large 104 sizes. Particle binning was also done in this manner because very small particles (i.e., < 8 nm) 105 were not detected in great enough quantity after incense burning to treat those bins individually. 106 This resulted in the following aggregation: 20 bins from 3.11 to 6.15 nm were combined and 107 represented as 4.4 nm particles; 13 bins from 6.38 to 9.82 nm were combined and represented as 108 7.9 nm particles; 11 bins from 10.2 to 14.6 nm were combined and represented as 12.2 nm 109 particles; 8 bins from 15.1 to 19.5 nm and from 20.2 to 25.9 nm were represented as 17.2 nm and 110 22.9 nm particles, respectively; the remaining subsequent aggregate size bins were summed 111 across five sizes until the last size range, represented by 100 nm, was summed over only four 112 bins. 113 UFP Generation and Loss Rates 114 Figure S2 shows mean (± s.d.) values of the initial indoor particle concentration 115 measured across all 40 experiments (i.e., Ci,in at time t = 0 for each experiment), which provides 4 116 an idea of the typical ultrafine particle size distribution resulting from incense burning. Initial 117 particle concentrations generated by incense burning were very low for the smallest geometric 118 mean particle size (< 5 nm), which led to high uncertainties later in the analysis. Therefore, the 119 smallest particle size is excluded from the rest of the analysis; this was not an issue for larger 120 particle sizes because initial concentrations were much greater. -3 ) 5000 1000 500 100 50 10 5 5 121 122 123 124 125 126 127 128 10 50 Particle Diameter (nm) 100 Figure S2. Mean (± s.d.) of indoor particle concentrations measured at the beginning of each of the 40 test runs (when t = 0 in the exponential decay model). Concentrations were intentionally elevated by burning incense, which produced very few particles less than 10 nm in diameter. The rest of this analysis excludes the smallest particle size (with a geometric mean dp of 4.4 nm) because of high uncertainties associated with low concentrations. Table S1 provides estimates of size-resolved effective loss rates (Li, total particle loss 129 rates minus AER) for each of the 8 test conditions. Values represent mean and standard 130 deviations of estimates resulting from five replicates for each particle size and test condition. 131 132 5 133 Table S1. Mean size-resolved effective loss rates (Li) measured during all test conditions Geometric Effective loss rate (hr-1) mean No filter MERV 4 MERV 6 MERV 11 MERV 10 MERV 13 MERV 16 diameter (nm) HVAC off 7.9 2.93 ± 0.95 3.73 ± 0.76 3.26 ± 1.09 4.17 ± 1.21 4.50 ± 0.93 7.06 ± 1.20 9.15 ± 1.50 8.33 ± 3.48 12.2 1.66 ± 0.66 2.50 ± 0.52 2.51 ± 0.65 2.86 ± 0.48 3.54 ± 0.43 3.97 ± 0.78 5.57 ± 1.07 6.28 ± 0.69 17.2 1.14 ± 0.43 1.60 ± 0.49 1.39 ± 0.54 1.77 ± 0.37 2.51 ± 0.41 2.79 ± 0.57 3.86 ± 0.54 5.04 ± 1.51 22.9 0.67 ± 0.30 1.19 ± 0.39 1.13 ± 0.22 1.40 ± 0.28 2.05 ± 0.17 2.14 ± 0.37 3.30 ± 0.33 5.05 ± 0.45 28.9 0.51 ± 0.19 1.07 ± 0.20 1.00 ± 0.16 1.19 ± 0.19 1.82 ± 0.14 1.92 ± 0.56 2.78 ± 0.53 4.66 ± 0.39 34.6 0.43 ± 0.13 0.94 ± 0.13 0.91 ± 0.10 1.06 ± 0.13 1.78 ± 0.11 1.80 ± 0.44 2.70 ± 0.31 4.75 ± 0.35 41.4 0.36 ± 0.11 0.83 ± 0.09 0.81 ± 0.08 0.95 ± 0.09 1.76 ± 0.08 1.76 ± 0.48 2.72 ± 0.28 4.73 ± 0.31 49.6 0.29 ± 0.10 0.74 ± 0.07 0.69 ± 0.08 0.79 ± 0.09 1.67 ± 0.10 1.83 ± 0.27 2.79 ± 0.21 4.82 ± 0.46 59.3 0.22 ± 0.10 0.65 ± 0.06 0.58 ± 0.09 0.69 ± 0.08 1.62 ± 0.15 1.86 ± 0.12 3.04 ± 0.15 5.06 ± 0.69 71.1 0.18 ± 0.09 0.59 ± 0.05 0.50 ± 0.08 0.60 ± 0.07 1.50 ± 0.18 1.85 ± 0.10 3.24 ± 0.13 5.22 ± 0.60 85 0.13 ± 0.08 0.53 ± 0.05 0.44 ± 0.06 0.54 ± 0.07 1.43 ± 0.21 1.77 ± 0.15 3.41 ± 0.17 5.57 ± 0.54 100 0.11 ± 0.08 0.48 ± 0.05 0.41 ± 0.06 0.47 ± 0.07 1.33 ± 0.21 1.66 ± 0.17 3.61 ± 0.18 5.71 ± 0.56 Values represent the mean ± standard deviation of five replicate tests for each condition. MERV 4, 6, and 11 are 2.5 cm filters; MERV 10, 13, and 16 are 12.7 cm filters. 134 135 136 UFP Removal Efficiency Table S2 summarizes mean and absolute uncertainty values of particle removal efficiency 137 measured during seven test cases: one with the HVAC system on without a filter, followed by 138 the six filter test conditions. 139 Table S2. Measured removal efficiency of the duct system and six test filters across 12 particle sizes Geometric mean diameter (nm) Duct removal efficiency No filter Filter removal efficiency MERV 4 MERV 6 MERV 11 MERV 10 MERV 13 MERV 16 7.9 12 ± 5% -5 ± 2% 12 ± 5% 17 ± 5% 54 ± 15% 12.2 12 ± 6% 2 ± 1% 9 ± 3% 20 ± 5% 25 ± 7% 17.2 7 ± 3% -2 ± -1% 5 ± 2% 17 ± 6% 20 ± 7% 22.9 8 ± 4% 0 ± 0% 5 ± 2% 15 ± 5% 16 ± 6% 28.9 8 ± 3% 0 ± 0% 3 ± 1% 13 ± 3% 14 ± 5% 34.6 7 ± 2% 0 ± 0% 3 ± 1% 15 ± 2% 14 ± 4% 41.4 7 ± 2% 0 ± 0% 3 ± 0% 16 ± 2% 15 ± 4% 49.6 7 ± 2% 0 ± 0% 2 ± 0% 16 ± 2% 17 ± 3% 59.3 6 ± 3% -1 ± 0% 2 ± 0% 16 ± 3% 19 ± 3% 71.1 6 ± 3% -1 ± 0% 1 ± 0% 15 ± 2% 20 ± 2% 85.0 6 ± 4% -1 ± 0% 1 ± 0% 15 ± 3% 20 ± 3% 100 5 ± 4% -1 ± 0% 0 ± 0% 14 ± 3% 18 ± 3% Values represent the mean ± absolute uncertainty across five replicate tests. 91 ± 25% 52 ± 15% 38 ± 13% 35 ± 12% 28 ± 8% 29 ± 6% 31 ± 5% 33 ± 5% 39 ± 5% 43 ± 5% 46 ± 6% 50 ± 6% 75 ± 35% 61 ± 15% 55 ± 24% 61 ± 21% 57 ± 12% 60 ± 10% 62 ± 9% 64 ± 10% 70 ± 13% 73 ± 12% 79 ± 12% 82 ± 13% MERV 4, 6, and 11 are 2.5 cm filters; MERV 10, 13, and 16 are 12.7 cm filters 6 140 References in the SI 141 142 143 144 145 146 147 ASTM E 741, (2006). Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution. Stephens, B., Novoselac, A., Siegel, J.A., (2010). The effects of filtration on pressure drop and energy consumption in residential HVAC systems. HVAC&R Research 16, 273–294. Stephens, B., Siegel, J.A., Novoselac, A., (2010). Energy implications of filtration in residential and light-commercial buildings (RP-1299). ASHRAE Transactions 116, 346–357. 7