TECHNICAL REPORT ON RECOMMENDED SUN-SHADING OF EASTERN ELEVATION IN AKURE BY ADANIKIN OLUMIDE AYODEJI (ARC/05/5570) SUBMITTED TO The Department of Architecture School of Post-Graduate studies Federal University of Technology Akure, Ondo State Nigeria Lecturer, Prof.O.O Ogunsote AUGUST2011 TABLE OF CONTENT Abstract 2 1.0 Introduction 3 1.1 Importance of Akure Town 4 1.2 Geographical Location of Akure 4 1.3 Geology and Vegetation 5 1.4 Description of process of Data collection 6 1.4.1 Source 6 1.4.2 Time 2.0 Sunshine in Akure 7 2.1 Solar radiation 7 2.2 Long wave radiation heat loss 8 2.3 Design of sun shading devices 8 2.4 How to shade eastern elevation 9 2.5 Sun control 9 3.0 Sun-shading and design recommendations for eastern elevation in akure. 10 3.1 Landscaping 10 3.2 Roof overhangs 10 3.3 Interior and exterior shading. 11 4.0 Conclusion 13 References 14 LIST OF TABLE Table 1.0 Climatic data sheet Table 2.0 sunshine graph ABSTRACT Historically architectural forms have largely resulted from man struggle with adverse climatic condition. Today, in our technological age, we have been able to make any area of planet habitable since interior and exterior climatic control can be achieved by way of natural/ artificial heating and cooling system. This advancement in construction technology has contributed to worldwide uniformity of architectural and disappearances of district/ regional types of housing. The need for better environmental condition is one of the major reasons for the existence of the building. The apparent human environmental requirements are for lights, air and warmth in addition, sound must be considered since it is indispensable in every activity. For comfort and efficiency, the human body requires a moderate rate of environment condition. This report contains a detailed recommendation of sun shading for eastern elevation Akure; the primary data was collected from the Ondo State Government Agro-climatological. The data was use as bases for analyzing the architectural problems and design recommendation for eastern elevation in Akure. Keywords: Sun-shading, Eastern elevation, Sunshine, Akure, Nigeria CHAPTER ONE. 1.0 INTRODUCTION Akure lies in the tropical zone; solar heat, glare and humidity are its characteristics. The area is particularly noted for dry and wet season, a tropical climate characteristically defined by the wet Southwest and dry Northeast trade wind There is need to control the amount of sunlight that is admitted into a building, in warm, sunny climates excess of heat gain may result to high cooling energy consumption. Well designed sun shading devices can considerable reduce building peak heat gain and requirement and improve the natural lighting quality of building interior depending on the amount and location of fenestration. It can also improve user visual comfort by reducing contrast ratios. Shading devices offer the opportunity of differentiating one building facade from another. 1.1 IMPORTANCE OF AKURE TOWN Akure is the capital city of Ondo State in Nigeria. A state with an area of 20. 555 square kilometer. Osun, Ogun and Ekiti states at the west, Kwara and Kogi at the North, Edo and Delta at the East and at the southern part by the Atlantic Ocean, bound it. Topographically, the land rises steadily from the shores of the Atlantics Ocean to the giant highlands of the Akoko’s in the North. These highlands which are part of the famous Yoruba highlands of western Nigeria constitutes a great water shed from where most of the notable rivers draining Ondo state take their source. River Owena, which supplies water for domestic use to one – third of the inhabitants of the states, is the most prominent amongst the rivers. The importance of this river is seen in its usage in the various government establishments and enterprises which includes, Owena motel, e t c. The latest national population census in 2006 but the figure at 360268 people (Information bulletin Ondo state, Dec 2006). The current population of the city according to GeoNames geographical database 420594 people. The federal ministry of communication, the police headquarters, the federal ministry of trades and industries, the water corporation and the Power Holding Company of Nigeria (PHCN). The establishment of Ondo State in February 1976 has since led to the establishment of many ministries and statutory co- corporations as well as quasi-governmental institutions that had greatly influenced the demographic structure of the city. Religious wise, the city serves the headquarters for many Christian denomination inducing the Catholic Diocese of Ondo, the Anglican Diocese of Akure, a district headquarters for the C.A.C church and the General Headquarter for Agape Christian Assembly etc. Also, Akure is the host city of educational institutions like, the federal University of Technology, State school of Nursing and school of Midwifery as well as the school of Health Technology. 1.2 GEOGRAPHICAL LOCATION OF AKURE 0 1 0 1 Akure lies on latitude 7 15 North of the Equator and on longitude 5 15 east of the Greenwich meridian. It stands on the altitude of about 396 meters above the sea level. The land towards Ado-Ekiti is hilly and studded with granite formations believed to be of volcanic origin spreading over an area of 99,287 square kilometers, Akure is situated 210 kilometers east of Ibadan, the capital of city of Oyo state, 168 kilometers west of Benin the capital of Edo state, 311 kilometers north east of Lagos, capital of Lagos, 189 south East of Ilorin the, capital of Kwara state. In relation to all big towns in state, Akure is centrally located, being surrounded with a 48-kilometer radius by those important towns. It is bounded by Ondo and Idanre to the south, Owo to the east, Iju / Itaogbolu to the north and Ile-oluji to west. 1.3 GEOLOGY AND VEGETATION Geologically, Akure falls into the pre-Cambrian exposed order granite belt. Its formation dates back to as for as 600 to 3500 million years ago. Topographically, the site is generally flat and soil area generally falls into large quantity of red laterite and very little of mangrove swamp soil of Humid tropical Equatorial area. Climatically, Ondo state has a tropical climate and belongs to the equatorial rain forest belts. There are several attractive varieties of vegetations in Ondo state. Numerous creaks and lagoons, bordering the Atlantic Ocean, are naturally separated one from another by mangrove swamps of raffia swamps. After this lies the well-drained rain forest region, which stretchers to about two hundred kilometers inland. This zone provides that most fertile agricultural lands. The major cash is cocoa, which provides about 90% of the annual revenue of Ondo state, Timber is another important source of wealth of the rainforest belt and includes Iroko, Mahogany, Obeche, Danta, and Opepe etc. Lastly there is the Guinea savannah forest, which fringes the northern part of the state. Farmers in this area concentrate more on the cultivation of subsistence crops such as cassava, yams, maize, rice, cocoyam etc. Akure town and neighboring ones like Idanre, Ondo, Ile-Oluji and Owo falls into second group i.e. the equatorial rainforest. 1.4 DESCRIPTION OF PROCESS OF DATA COLLECTION 1.4.1 SOURCE The information in this write up was collected from the Ondo state government Agro climatological and ecological monitoring unit (PMU), Akure. Also other sources of data include textbooks, Journal and Internet. 1.4.2 TIME The data was collected at Automatic weather station of PMU unit Akure. The data was recorded automatic recordable machine at appropriate time interval depending on the sensors setting. CHAPTER TWO 2.0 SUNSHINE IN AKURE Akure being located in the equatorial zone has predominant climatic characteristics of being warn humid, with little seasonal variation with sunshine among the climatic features that affects human comfort others include rainfall, temperature, Relative Humidity and wind. The effect of sunshine is in influenced by the humid-south west trade wind with rate of cloud coverage. Akure lies in latitude 7’14N and Longitude 5, 17’E, the latitude is the factor that determines the level of sunshine. Akure the state capital of Ondo state justifies her name being called the sunshine state, it is called the sunshine capital, the sunshine duration in Akure sometimes spans for almost 8 hours per day, as at last year dry season, the sun rises at 10:00am and sets at 4:50pm, in 2010, this shows clearly that the level of solar radiation in Akure has increased over the years. Akure experience a vertical solar insolative mid day sun with a much concentrated solar insolative, from the table, the month of September records the highest duration of sunshine for 8.7 hours, the implication of this is that the heat during the day is absorbed during the day and during the night there will be emission of heat, the interior becomes unbearable, there is a need for sun shading devices to exclude sun throughout the year and also utilizing landscape design(use of landscaping vegetation, use of building fabric and design in the interior, and the use of passive technologies for cooling,heating,ventilation and lighting) 2.1 SOLAR RADIATION Solar radiation is an electromagnetic radiation from the sun. The wavelength of the solar spectrum on the earth surface ranges from 0.28 microns to 3.0 microns; where a micron is a thousand of a millimeter. The solar spectrum is divided into three; i. The Ultra Violet (U.V) ii. The Visible iii. The Infra – Red (I.R) Only the small section of the spectrum between 0.4 and 0.7 microns is light visible to the eye; waves shorter than 0.4 microns are ultra violet radiation and waves longer than 0.76 microns are infra red. Although the peak intensity of solar radiation is in the visible range, over one half of the energy is emitted as infra red radiation. 2.2 LONGWAVE RADIATION HEAT LOSS Longwave radiation is emitted by the surface of the earth to the atmosphere and to the outer space. According to the Stefan Boltzmann law, the intensity of emitted radiation is proportional to the difference between the fourth powers of the absolute temperature, zero Kelvin of the emitting absorbing points. It therefore depends on the difference between the temperature of the earth’s surface and the absorbing medium atmosphere and outer space. Long wave radiation is also emitted in all direction by the gases in the atmosphere; of this the earth absorbs the downward component 2.3 Design of sun shading devices When are designing shading devices for a structure, especially in the eastern elevation (this is been referred to the side at which sunrise). Therefore in designing the shading device for this elevation, the following steps needs to be put into consideration; We determine the time when shading is required in the year. Position of the sun at the times shading is required must be established. Also the dimension and the proportion of the shading device that will provide shading during the period of shading are also determined. Also the design of the device in terms of its geometry, aesthetics and structural factors is also to be done 2.4 How to shade eastern elevation Since the sun angle in the morning starts at 0 degrees (sunrise), we will be unable to block all sunrise entering the building without blocking the view of the occupants. The best way is to block the sun from 10:00 am – noon in the cooling season, while admitting this sun during the heating season. Use interior blinds or shades to blocks glare for the occupants. This will allow the heat gain to enter the interior space during the heating season thereby gaining the energy benefits. 2.5 SUN CONTROL Sun control or shading is the process of controlling the sunlight entering the building which can be accomplished through a number of methods this depends on the use of space and the climate. The use of sun control and shading devices is an important aspect of many energy efficient building design strategies. In particular, building that employ passive solar heating or daylight often depend on well designed sun control and shading devices. The sun shading includes; vertical, horizontal e.t.c and they perform the following function; ventilation, allowing a view out, protection from rain, protection from direct solar radiation and also from sky glare. CHAPTER THREE 3.0 SUN-SHADING AND DESIGN RECOMMENDATIONS FOR EASTERN ELEVATION IN AKURE. Sun control or shading is the process of controlling the sunlight entering the building which can be accomplished through a number of methods this depends on the use of space and the climate For this technical report, the categories of shading am going to recommend include; Landscaping Roof overhangs Interior and exterior shading. 3.1 Landscaping In cooling and heating climate, deciduous trees works best on the east elevation of the structure. Effective on this location, when they are well placed at a distance from the building and with low crown. Evergreens are also effective in shielding the building from hot winds in the eastern part of the building. Also, deciduous trees with long lasting foliage can be used to shade all windows from direct sun penetration in the east elevation. Also ground covers around the building will helps to reduce glare. All this are useful in the eastern part of the building not only for their geometric form but they are also aesthetically pleasing and can create usable outdoor spaces for occupants. 3.2 Roof overhangs They are more reliable and less expensive form of shading because of they are part of the building shell. They are to be designed to block the sun in heating climates, overhang, when wants to be used to shade the eastern elevation must be designed for the orientation in each months and also when the sun is lower in the sky.(that is when the temperature is higher ) to provide shading on the eastern elevation. 3.3 Interior and exterior shading. Exterior shading provides more effective shading at reducing unwanted solar gain than interior shading because it stops the sun from striking the building. It can be fixed or movable. They include; solar screens, roll down blinds, horizontal louvers, shutters and vertical louvers. Interior shading tends to be less effectives at reducing cooling loads because they allow the sun to enter the building, trapping the heat between the window and the shading devices. The interior are of low cost and easy to operate and design. It can also be effective if designed to provide both sun-shading and insulation during the day in the cooling season and at night in the heating season. Also points to notes when recommending a sun-shading for eastern elevation include; The use of the space Location of the building Orientation Also, to minimize the east glazing of the building Window to be used in the eastern elevation must be of low heat gain coefficient. The heat capacity of the building should be as low as possible in order to prevent accumulation of heat during the daytime, which would elevate the indoor temperature during the night when the external wind speed is usually at its lowest. Thermal resistance of the external walls is advantageous within certain limits in minimizing the heat flow the external surface warmed by the sun. Modern insulating material, which, combine very low weight and heat capacity together with high thermal resistance, may provide the best indoor climatic conditions. Lightweight roofs, covered with tiles or sheets of asbestos cement or aluminum, are preferable in a warm –wet climate owning to their low heat capacity. When concrete roofs of high heat capacity are constructed, it is preferable to provide an insulating lager below the ceiling, thus reducing heat flow during the day and enabling rapid lowering of the ceiling temperature during the night. 4.0 CONCLUSION It is high time for the architects to pay adequate attention to shading; this will go along way in helping to reduce the amount of sun entering into the building and also friendly architectural design for the city of Akure which is the main focus in this term paper. Understanding of the building orientation, the choice of material and when to shade will improves structural stability and functionality of buildings and determines the comfort of the occupants. REFERENCES Fadamiro, J. A. and Ogunsemi, D. R. (1996) “Fundamentals of Building Design, Construction and Materials”. Fancy Publications Ltd. Ile-Ife. Ogunsote O.O (2011), Lecture Note on Applied climatology for Masters Students, Federal University of Technology, Akure. The Nigerian Meteorological Agency Departments of Civil Aviation, Federal Secretariat, Igbatoro, Akure, Ondo State. www.google .com www.ask.com Year ; Lat & Long Location Akure Notes; air velocity assumed Nomogram Normal cloting ET or CET Comfort limits Lower ; 22 C Upper ; 27 C JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Mean air velocity (m/s) Mean maximum DBT ( C ) Mean min RH (%) Mean max WBT ( C ) Maximum ET (C) Mean min DBT ( C ) Mean max RH (% ) Mean min WBT ( C ) Minimum ET (C ) 0.92 0.96 1.25 1.27 1.09 1.15 1.35 1.09 0.91 0.72 0.62 0.52 30.72 33.67 31.53 31.55 30.64 30.55 28.19 28.59 29.76 31.00 30.13 33.27 30.3 30.2 56.2 53.9 55.4 59.5 64.6 65.5 64.6 61 52.7 48.3 23.32 21.72 23.99 22.37 23.65 22.85 21.30 22.28 23.28 24.19 24.05 23.99 26.62 28.34 28.21 27.4 27.18 26.42 23.39 23.71 24.31 27.00 27.88 28.21 73.27 57.84 89.63 74.00 75.29 74.30 84.92 88.17 85.05 79.29 71.97 70.11 15.62 14.85 16.27 15.00 15.45 16.27 17.54 18.00 18.30 20.08 20.70 20.69 Hours of sunshine 7.6 8.3 8.5 7.3 8.3 7.2 8.5 7.9 8.7 7.3 6.4 6.8 Shading stop Table 1.0 CLIMATIC DATA SHEET FOR AKURE IN THE YEAR 2004 Sunshine hours (h/day) TABLE 2.0 SHOWING HOURS OF SUNSHINE IN GRAPH Source: The Nigerian Meteorological Agency, Department of Civil Aviation Federal Secretariat, Igbataro, Akure, Ondo State.