KENYA PORTS AUTHORITY TENDER NO. KPA/169/2010-11/EE UPGRADING OF INCOMING POWER FROM 11KV TO 132KV SUPPLY, INSTALLATION AND COMMISSIONING OF 132KV/11KV SUBSTATION AND ASSOCIATED EQUIPMENT TENDER DOCUMENT June 2011 2 TABLE OF CONTENTS TABLE OF CONTENTS TABLE OF CONTENTS........................................................................................... 2 ABBREVIATIONS AND ACRONYMS .................................................................. 4 SECTION I: INVITATION FOR TENDERS (IFT) .................................................. 5 VISION, MISSION, & CORE VALUES ..................................................................... 7 HEALTH, SAFETY AND ENVIRONMENT POLICY STATEMENT .............. 8 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) ................................... 9 1. 2. 3. 4. 5. 6. 7. Scope of Tender ................................................................................................. 10 Source of Funds ................................................................................................ 10 Eligible Tenderers ............................................................................................. 10 One Tender per Tenderer ............................................................................... 11 Alternative Tenders by Tenderers ............................................................... 11 Cost of Tendering.............................................................................................. 11 Site Visit and Pre-Tender Meeting............................................................... 11 A. Tendering Documents ............................................................................ 12 B. Preparation of Tenders .......................................................................... 13 C. Submission of Tenders .......................................................................... 17 8. Content of Tendering Documents ............................................................... 12 9. Clarification of Tendering Documents ....................................................... 13 10. Amendments of the Tendering Documents .............................................. 13 11. Language of Tender.......................................................................................... 13 12. Documents Constituting the Tender .......................................................... 13 13. Documents Establishing Eligibility and Qualifications of the Tenderer ....................................................................................................................... 14 14. Form of Tender .................................................................................................. 15 15. Tender Prices ..................................................................................................... 15 16. Tender Currencies ............................................................................................ 15 17. Tender Validity Period ..................................................................................... 15 18. Tender Security and Tender Securing Declaration ............................... 16 19. Format and Signing of Tender ...................................................................... 17 20. 21. 22. 23. Sealing and Marking of Tenders .................................................................. 17 Deadline for Submission of Tenders .......................................................... 18 Late Tenders ....................................................................................................... 18 Modification, Substitution and Withdrawal of Tenders ....................... 18 D. Opening and Evaluation of Tenders .................................................. 19 E. Award of Contract ................................................................................... 22 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. Opening of Tenders .......................................................................................... 19 Confidentiality ................................................................................................... 19 Clarification of Tenders .................................................................................. 20 Preliminary Examination of Tenders .......................................................... 20 Correction of Errors ......................................................................................... 21 Conversion to Single Currency..................................................................... 21 Comparison of Tenders ................................................................................... 21 National Preference .......................................................................................... 22 Determination of the winning evaluated Tender .................................... 22 Post-qualification of Tenderer ...................................................................... 22 34. Criteria of Award ............................................................................................... 22 35. Clarifications ...................................................................................................... 22 36. Procuring Entity’s Right to Accept any Tender and to Reject any or all Tenders ................................................................................................................... 23 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 2 of 270 3 TABLE OF CONTENTS 37. 38. 39. 40. 41. 42. F. Procuring Entities Right to Vary Quantities at the Time of Award .. 23 Notification of Award ....................................................................................... 23 Signing of Contract .......................................................................................... 23 Performance Security ...................................................................................... 24 Advance Payment ............................................................................................. 24 Adjudicator ......................................................................................................... 24 Review of Procurement Decisions ...................................................... 24 43. Right to Review .................................................................................................. 24 44. Time Limit on Review ...................................................................................... 25 45. Submission of Applications for Review by the Public Procurement Administrative Review Board ................................................................................ 25 46. Decision by the Public Procurement Administrative Review Board . 25 47. Appeal on the decision of the Review Board ............................................ 25 SECTION III: TENDER DATA SHEET ............................................................ 26 SECTION IV: GENERAL CONDITIONS OF CONTRACT ............................ 36 PART I – GENERAL CONDITIONS.................................................................... 37 PREAMBLE TO GENERAL CONDITIONS .......................................................... 38 PART II – SPECIAL CONDITIONS OF CONTRACT ...................................... 41 SECTION V: TECHNICAL SPECIFICATIONS ............................................... 44 SECTION VII: DRAWINGS ............................................................................... 235 SECTION VIII: BILLS OF QUANTITIES ....................................................... 241 SECTION IX: TENDER FORMS ..................................................................... 249 A. Form of Tender ....................................................................................... 250 B. Tender-Securing Declaration (Mandatory) .................................... 254 C. Confidential Business Questionnaire ............................................. 255 ntegrity Declaration ......................................................................................... 258 D. Letter of Acceptance ............................................................................. 260 E. Contract Data Sheet ............................................................................. 261 SECTION X: FORMS OF SECURITY ............................................................ 265 A. Tender Security (Bank or Insurance Guarantee) ........................ 266 B. Performance Bank or Insurance Guarantee [Unconditional] . 267 C. Bank or Insurance Guarantee for Advance Payment ................ 268 SECTION XI: APPLICATION TO PUBLIC PROCUREMENT ADMINISTRATIVE REVIEW BOARD ....................................................... 269 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 3 of 270 4 ABBREVIATIONS AND ACRONYMS ABBREVIATIONS AND ACRONYMS CDS Contract Data Sheet GCC General Conditions of Contract IFT Invitation for Tender ITT Instruction to Tenderers PE Procuring Entity PM Project Manager PPDA 2005 Public Procurement and Disposal Act, 2005 PPDR 2006 Public Procurement and Disposal Regulations, 2006 PPOA Public Procurement Oversight Authority STD Standard Tender Documents SOR Statement of Requirements SP Service Provider TDS Tender Data Sheet VAT Value Added Tax KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 4 of 270 SECTION I: 5 INVITATION FOR TENDERS (IFT) SECTION I: INVITATION FOR TENDERS (IFT) KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 5 of 270 SECTION I: 6 INVITATION FOR TENDERS (IFT) Invitation for Tenders Tender No.KPA/169/2010-11/EE Tender Name: UPGRADING OF INCOMING POWER FROM 11KV TO 132KV - SUPPLY, INSTALLATION AND COMMISSIONING OF 132kV/11kV SUBSTATION AND ASSOCIATED EQUIPMENT June 2011 1.1 The Kenya Ports Authority now invites sealed tenders from eligible suppliers of high voltage electrical switchgear and electrical contractors registered with Ministry of Energy’s ERC Class A for carrying out the proposed UPGRADING OF INCOMING POWER FROM 11KV TO 132KV - SUPPLY, INSTALLATION AND COMMISSIONING OF 132kV/11kV SUBSTATION AND ASSOCIATED EQUIPMENT 1.2 The Procuring Entity has set aside funds for use during the financial year(s) [2010-11-12]. It is intended that part of the proceeds of the fund will be used to cover eligible payments under the contract for the PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132KV -SUPPLY, INSTALLATION AND COMMISSIONING OF 132kV/11kV SUBSTATION AND ASSOCIATED EQUIPMENT 1.3 Tendering will be conducted through the National Competitive (NCB) Bidding procedures specified in the Public Procurement and Disposal Act, 2005 and the Public Procurement and Disposal Regulations, 2006 and is open to all Tenderers as defined in the Regulations. 1.4 Interested eligible Tenderers may obtain further information from and inspect the Tendering Documents at the offices of the Procurement & Supplies Manager located on the 4th floor of office Block 3 at the Kenya Ports Authority Headquarters, Kilindini Kipevu from MONDAY TO FRIDAY (BETWEEN 0800 HOURS AND 1600 HOURS inclusive) except on public holidays. 1.5 A complete set of tender documents may be obtained by interested candidates upon payment of non-refundable fees of KShs.5, 000.00 in the form of a Bankers Cheque payable to Kenya Ports Authority. The document can also be viewed and downloaded from the website www.kpa.co.ke and payment evidence MUST be submitted with the tender document. Bidders who download the tender document from the website must forward their particulars immediately for records and communication of any further tender clarifications or addenda and will be required to pay a discounted fee of Kshs 3,000. Enquiries can be made via email address: ctcsecretary@kpa.co.ke fax number +25422 2226721. 1.6 There shall be a pre-planned site visit on Thursday, 23nd June, 2011 starting from 1000 Hours. Interested and eligible candidates shall be required to gather at the Conference room on the 6 th floor of Kipevu Block III HQ at 1000 Hours. All bidders shall be required to sign an attendance register as evidence of having participated in the site visit. Bidders who shall not turn up for the pre – planned site visit shall make their own arrangements to visit the site. 1.7 All Tenders in one original plus [two-2 copies], properly filled in, and enclosed in plain envelopes must be delivered to the address below: Tender Box No. 7 located at the BUS TERMINUS, PORT MAIN PEDESTRIAN GATE NO.8, KILINDINI, MOMBASA BEFORE 0900 HOURS ON TUESDAY, 26TH JULY, 2011 Bulky tenders shall be submitted at the office of Procurement & Supplies Manager located on the 4th floor of office Block III at the Kenya Ports Authority Headquarters, Kipevu, Kilindini Mombasa. 1.8 Tenders will be opened promptly thereafter in the presence of Tenderers’ representatives who choose to attend the opening at the New Conference Room, 6 th Floor Finance Block III Kipevu Headquarters, Kenya Ports Authority, Mombasa. 1.9 Late Tenders, incomplete Tenders, Tenders not opened at the Tender opening ceremony shall not be accepted for evaluation irrespective of the circumstances. 1.10 Canvassing or lobbying for the tender shall lead to automatic disqualification. Yobesh Oyaro PROCUREMENT AND SUPPLIES MANAGER KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 6 of 270 7 VISION, MISSION, & CORE VALUES Vision World class seaports of choice. Mission To facilitate and promote global maritime trade through the provision of competitive port services. Values Customer Focus: Service excellence is key to our operations and we endeavour to exceed customer expectations. Integrity: We uphold fairness, honesty, professionalism and transparency in all our undertakings. Teamwork: We embrace team spirit in all that we do. We Care: We care for our staff, the communities around us and are sensitive to the environment. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 7 of 270 8 HEALTH, SAFETY AND ENVIRONMENT POLICY STATEMENT The Kenya Ports Authority recognizes and appreciates the importance of Health, Safety and Environment in the organization. The Authority therefore places Health, Safety and Environment matters as important Boardroom Agenda. To translate this commitment into actions, the Authority shall adopt a health, safety and environment policy that shall ensure: 1. Compliance with all relevant statutory instruments in all matters of Health, Safety and Environment. 2. Appropriate consideration of relevant international conventions and recommendations. 3. Formulation and compliance with rules, regulations and guidelines on matters of Health, Safety and Environment. 4. All reasonably practicable precautions are taken to safeguard the safety and health of all employees and Port users. 5. Appropriate systems for providing adequate information and instructions to all cadres of employees on risks to their health and safety are in place. 6. That all work places and equipment/plant are safe and regularly inspected. 7. All employees and Port Users assume defined responsibilities in matters of health, safety and environment in conformity with this policy. 8. Appropriate training for all employees to enhance their performance is provided. 9. That all Suppliers comply with Health, Safety and Environment rules, regulations and guidelines. 10. Adequate provision for prevention and control of fires and proper use of Fire fighting appliances. 11. Adequate provision for prevention and control of environmental pollution. 12. That Environmental Impact Assessment is carried out for all projects likely to have an impact on the environment. 13. Provision and promotion of First Aid services and activities. 14. Contravention of the Health, Safety and Environment Management System attracts severe disciplinary action including dismissal and/or prosecution. 15. Review of the Health, Safety and Environment Management System to conform to changing trends. (Signed) GICHIRI NDUA MANAGING DIRECTOR KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 8 of 270 9 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) SECTION II: INSTRUCTIONS TO TENDERERS (ITT) KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 9 of 270 10 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) Introduction 1. Scope of Tender 1.1 The Procuring Entity indicated in the Tender Data Sheet (TDS) invites Tenders for the construction of works as specified in the Tender Data Sheet and Sections V (Technical Specifications) and VII (Drawings). 1.2 The successful Tenderer will be expected to complete the works by the required completion date specified in the Tender Data Sheet. 1.3 The objectives of the works are listed in the Tender Data Sheet. These are mandatory requirements. Any subsequent detail is offered to support these objectives and must not be used to dilute their importance. 2. Source of Funds 2.2 3. Eligible Tenderers 3.1 Payments will be made directly by the Procuring Entity (or by financing institution specified in the Tender Data Sheet upon request of the Procuring Entity to so pay) and will be subject in all respects to the terms and conditions of the resulting contract placed by the Procuring Entity. A Tenderer may be a natural person, private or public company, government-owned institution, subject to sub-Clause 3.4 or any combination of them with a formal intent to enter into an agreement or under an existing agreement in the form of a joint venture, consortium, or association. In the case of a joint venture, consortium, or association, unless otherwise specified in the Tender Data Sheet, all parties shall be jointly and severally liable. 3.2 The Invitation for Tenders is open to all suppliers as defined in the Public Procurement and Disposal Act, 2005 and the Public Procurement and Disposal Regulations, 2006 except as provided hereinafter. 3.3 A Tenderer shall not have a conflict of interest. All Tenderers found to have a conflict of interest shall be disqualified. A Tenderer may be considered to have a conflict of interest with one or more parties in this Tendering process, if they: a) Are associated or have been associated in the past directly or indirectly with employees or agents of the Procuring Entity or a member of a board or committee of the Procuring Entity; b) Are associated or have been associated in the past, directly or indirectly with a firm or any of its affiliates which have been engaged by the Procuring Entity to provide consulting services for the preparation of the design, specifications and other documents to be used for the procurement of the works under this Invitation for Tenders; c) Have controlling shareholders in common; or d) Receive or have received any direct or indirect subsidy from any of them; or e) Have the same legal representative for purposes of this Tender; or f) Have a relationship with each other, directly or through common third parties, that puts them in a position to have access to information about or influence on the Tender of another Tenderer, or influence the decisions of the Procuring Entity regarding this Tendering process; or g) Submit more than one Tender in this Tendering process. However, this does not limit the participation of subcontractors in more than one Tender, or as Tenderer and subcontractor simultaneously. 3.4 A Tenderer will be considered to have a conflict of interest if they KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 10 of 270 11 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) participated as a consultant in the preparation of the design or technical specification of the project and related services that are the subject of the Tender. 3.5 Tenderers shall not be under a declaration of ineligibility for corrupt and fraudulent practices issued by the Government of Kenya in accordance with GCC sub-Clause 3.2. 3.6 Government owned enterprises in Kenya may participate only if they are legally and financially autonomous, if they operate under commercial law, are registered by the relevant registration board or authorities and if they are not a dependent agency of the Government. 3.7 Tenderers shall provide such evidence of their continued eligibility satisfactory to the Procuring Entity, as the Procuring Entity shall reasonably request. 4.1 A firm shall submit only one Tender, in the same Tendering process, either individually as a Tenderer or as a partner in a joint venture pursuant to ITT Clause 5. 4.2 No firm can be a subcontractor while submitting a Tender individually or as a partner of a joint venture in the same Tendering process. 4.3 A firm, if acting in the capacity of subcontractor in any Tender, may participate in more than one Tender but only in that capacity. 4.4 A Tenderer who submits or participates in more than one Tender (other than as a subcontractor or in cases of alternatives that have been permitted or requested) will cause all the Tenders in which the Tenderer has participated to be disqualified. 5.1 Tenderers shall submit offers that comply with the requirements of the Tendering documents, including the basic Tenderer’s technical design as indicated in the specifications and Drawings and Bill of Quantities. Alternatives will not be considered, unless specifically allowed for in the Tender Data Sheet. If so allowed, sub-Clause 5.2 and 5.3 shall govern. 5.2 When alternative times for completion are explicitly invited, a statement to that effect will be included in the Tender Data Sheet as will the method of evaluating different times for completion. 5.3 If so allowed in the Tender Data Sheet, Tenderers wishing to offer technical alternatives to the requirements of the Tendering documents must also submit a Tender that complies with the requirements of the Tendering documents, including the basic technical design as indicated in the specifications. In addition to submitting the basic Tender, the Tenderer shall provide all information necessary for a complete evaluation of the alternative by the Procuring Entity, including technical specifications, breakdown of prices, and other relevant details. Only the technical alternatives, if any, of the winning evaluated tenderer conforming to the basic technical requirements shall be considered by the Procuring Entity. 6. Cost of Tendering 6.1 The Tenderer shall bear all costs associated with the preparation and submission of its Tender, and the Procuring Entity shall in no case be responsible or liable for those costs, regardless of the conduct or outcome of the Tendering process. 7. Site Visit and Pre-Tender Meeting 7.1 The Tenderer, at the Tenderer’s own responsibility and risk, is advised to visit and examine the Site of Works and its surroundings and obtain all information that may be necessary for preparing the Tender and entering into a contract for construction of the Works. The costs of visiting the Site shall be at the Tenderer’s own expense. 4. One Tender per Tenderer 5. Alternative Tenders by Tenderers KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 11 of 270 12 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) 7.2 The Procuring Entity may conduct a site visit and a pre-Tender meeting. The purpose of the pre-Tender meeting will be to clarify issues and to answer questions on any matter that may be raised at that stage. 7.3 The Tenderer’s designated representative is invited to attend a site visit and pre-Tender meeting which, if convened, will take place at the venue and time stipulated in the Tender Data Sheet. 7.4 The Tenderer is requested as far as possible, to submit any questions in writing or by electronic means to reach the procuring Entity before the pre-Tender meeting. It may not be practicable at the meeting to answer all questions, but questions and responses will be transmitted in accordance with sub-Clause 7.5. 7.5 Minutes of the pre-Tender meeting, including the text of the questions raised and the responses given together with any responses prepared after the pre-Tender meeting will be transmitted within the time stated in the Tender Data Sheet to all purchasers of the Tendering documents. Any modification of the Tendering documents listed in sub-Clause 8.1 that may become necessary as a result of the preTender meeting shall be made by the Procuring Entity exclusively through the issue of an Addendum pursuant to ITT sub Clause 10.2 and not through the minutes of the pre-Tender meeting. 7.6 Non attendance during the site visit or pre-Tender meeting will not be a cause for disqualification of a Tenderer unless specified to the contrary in the Tender Data Sheet. A. Tendering Documents 8. Content of Tendering Documents 8.1 The works required, Tendering procedures, and contract terms are prescribed in the Tendering Documents. In addition to the Section I Invitation for Tenders, Tendering documents which should be read in conjunction with any addenda issued in accordance with ITT sub Clause 10.2 include: Section Section Section Section Section Section Section II Instructions to Tenderers III Tender Data Sheet IV General Conditions of Contract V Technical Specifications VII Drawings VIII Bill of Quantities IX Forms of Tender Form of Tender Appendix to Tender Confidential Business Questionnaire Integrity Declaration Letter of Acceptance Contract Data Sheet Section X Forms of Security Tender Security Form Tender Securing Declaration Performance Bank or Insurance Guarantee Advance Payment Guarantee Section XI Form RB 1 Application to Public Procurement Administrative Review Board 8.2 The number of copies to be completed and returned with the Tender is specified in the Tender Data Sheet. 8.3 The Invitation for Tenders (Section I) issued by the Procuring Entity KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 12 of 270 13 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) is not part of the Tendering Documents and is included for reference purposes only. In case of discrepancies between the Invitation for Tenders and the Tendering Documents listed in sub-Clause 8.1 above, the said Tendering Documents will take precedence. 9. Clarification of Tendering Documents 10. Amendments of the Tendering Documents 8.4 The Procuring Entity is not responsible for the completeness of the Tendering Documents and their addenda, if they were not obtained directly from the authorized staff of the Procuring Entity. 8.5 The Tenderer is expected to examine all instructions, forms, terms and specifications in the Tendering documents. Failure to furnish all information required by the Tendering Documents or to submit a Tender substantially responsive to the Tendering documents in every respect will be at the Tenderer’s risk and may result in the rejection of its Tender. 9.1 A prospective Tenderer requiring any clarification of the Tendering documents may notify the Procuring Entity in writing, e-mail or facsimile at the Procuring Entity's address indicated in the Tender Data Sheet. 9.2 The Procuring Entity will within the period stated in the Tender Data Sheet respond in writing to any request for clarification provided that such request is received no later than the period indicated in the Tender Data Sheet prior to the deadline for the submission of Tenders prescribed in sub-Clause 22.1. 9.3 Copies of the procuring entity's response will be forwarded to all Purchasers of the Tendering documents, including a description of the inquiry, but without identifying its source. 9.4 Should the Procuring Entity deem it necessary to amend the Tendering documents as a result of a clarification, it shall do so following the procedure under ITT Clause 10. 10.1 Before the deadline for submission of Tenders, the Procuring Entity may, for any reason, whether at its own initiative or in response to a clarification requested by a prospective Tenderer, modify the Tendering documents by issuing addenda. 10.2 Any addendum issued shall be part of the Tender documents pursuant to sub-Clause 8.1 and shall be communicated in writing, by e-mail or facsimile to all who have obtained the Tendering documents directly from the Procuring Entity. 10.3 In order to allow prospective Tenderers reasonable time in which to take an addendum into account in preparing their Tenders, the Procuring Entity at its discretion shall extend, as necessary, the deadline for submission of Tenders, in accordance with sub-Clause 22.2 B. Preparation of Tenders 11. Language of Tender 11.1 The Tender, and all correspondence and documents related to the Tender exchanged by the Tenderer and the Procuring Entity shall be written in the Tender language stipulated in the Tender Data Sheet. Supporting documents and printed literature furnished by the Tenderer may be in another language provided they are accompanied by an accurate translation of the relevant passages in the above stated language, in which case, for purposes of interpretation of the Tender, the translation shall prevail. 12. Documents 12.1 The Tender submitted by the Tenderer shall consist of the following KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 13 of 270 14 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) Constituting the Tender components: a) The Form of Tender (in the format indicated in Section IX) completed in accordance with ITT Clause 15, 16 and 17; b) Information requested by Instructions to Tenderers ITT subClause 13.2; 13.3 and 13.4; c) Tender Security or Tender Securing Declaration in accordance with Instructions to Tenderers ITT Clause 19; d) Priced Bill of Quantities; e) Qualification Information Form and Documents; f) Alternative offers where invited in accordance with Instructions to Tenderers ITT Clause 5; g) Written confirmation authorizing the signatory of the Tender to commit the Tenderer in accordance with Instructions to Tenderers ITT sub Clause 19.2; and h) Technical schedules duly filled in details as requested. i) And any information or other materials required to be completed and submitted by Tenderers, as specified in the Tender Data Sheet. 13. Documents Establishing Eligibility and Qualification s of the Tenderer 13.1 Pursuant to ITT Clause 13, the Tenderer shall furnish, as part of its Tender, documents establishing the Tenderer’s eligibility to Tender and its qualifications to perform the contract if its Tender is accepted. 13.2 Tenders submitted by a joint venture of two or more firms as partners shall comply with the following requirements, unless otherwise stated in the Tender Data Sheet: a) The Tender shall include all the information listed in the Tender Data Sheet pursuant to sub-Clause 13.3 above for each joint venture partner; b) The Tender shall be signed so as to be legally binding on all partners; c) One of the partners will be nominated as being in charge, and this authorization shall be evidenced by submitting a power of attorney signed by legally authorized signatories of all the partners; d) The partner in charge shall be authorized to incur liabilities and receive instructions for and on behalf of any and all partners of a joint venture and the entire execution of the Contract, including payment, shall be done exclusively with the partner in charge; e) All partners of the joint venture shall be liable jointly and severally for the execution of the contract in accordance with the contract terms and a statement to this effect shall be included in the authorization mentioned under (c) above as well as in the Tender and in the Agreement (in case of a successful Tender); and f) A copy of the joint venture agreement entered into by all partner shall be submitted with the Tender. Alternatively, a Letter of Intent to execute a joint venture agreement in the event of a successful Tender shall be signed by all partners and submitted KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 14 of 270 15 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) with the Tender, together with a copy of the proposed Agreement. g) The Tender Security and Tender Securing Declaration as stated in accordance with ITT Clause 19, and in case of a successful Tender, the Agreement, shall be signed so as to be legally binding on all partners. 14. Form of Tender 14.1 The Tenderer shall fill the Form of Tender furnished in the Tendering Documents. The Form of Tender must be completed without any alterations to its format and no substitute shall be accepted. 15. Tender Prices 15.1 The Contract shall be for the whole Works, as described in subClause 1.1, based on the priced Bill of Quantities submitted by the Tenderer. 15.2 The Tenderer shall fill in rates and prices for all items of the Works described in the Bill of Quantities. Items for which no rate or price is entered by the Tenderer will not be paid for by the Procuring Entity when executed and shall be deemed covered by the other rates and prices in the Bill of quantities. 15.3 All duties, taxes and other levies payable by the Contractor under the Contract, or for any other cause, as of the date 15 days prior to the deadline for submission of Tenders, shall be included in the rates, prices and total Tender price submitted by the Tenderer. 16.1 The unit rates and prices shall be quoted by the Tenderer in the currency as specified in the Tender Data Sheet. 16.2 Tenderers shall indicate details of their expected foreign currency requirements in the Tender, if any. The rates of exchange to be used by the Tenderers in arriving at the local currency equivalent shall be the selling rates for similar transactions established by the authority specified in the Tender Data Sheet prevailing on the date 28 days prior to the latest deadline for submission of Tenders. These exchange rates shall apply for all payments so that no exchange risk will be borne by the Tenderer. In any case, payments will be computed using the rates quoted in the Tender. 16.3 Tenderers may be required by the Procuring Entity to clarify their foreign currency requirements and to substantiate that the amounts included in the rates and prices and in the Contract Data Sheet are reasonable and responsive to sub-Clause 17.1. 17.1 Tenders shall remain valid for the period specified in the Tender Data Sheet after the Tender submission deadline prescribed by the Procuring Entity, pursuant to ITT Clause 22. A Tender valid for a shorter period shall be rejected by the Procuring Entity as non responsive. 17.2 In exceptional circumstances, prior to expiry of the original Tender validity period, the Procuring Entity may request that the Tenderers extend the period of validity for a specified additional period. The request and the Tenderers' responses shall be made in writing or by cable. A Tenderer may refuse the request without forfeiting its Tender Security or causing to be executed its Tender Securing declaration. A Tenderer agreeing to the request will not be required or permitted to otherwise modify the Tender, but will be required to extend the validity of its Tender Security or Tender Securing declaration for the period of the extension, and in compliance with ITT Clause 19 in all respects. 17.3 In the case of fixed price contracts, if the award is delayed by a period exceeding sixty (60) days beyond the expiry of the initial Tender validity period, the contract price will be increased by a factor 16. Tender Currencies 17. Tender Validity Period KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 15 of 270 16 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) specified in the request for extension. The Tender evaluation shall be based on the Tender price without taking into consideration on the above correction. 18. Tender Security and Tender Securing Declaration 18.1 Pursuant to ITT Clause 12, where required in the Tender Data Sheet, the Tenderer shall furnish as part of its Tender, a Tender Security in original form and in the amount and currency specified in the Tender Data Sheet. A Tender Securing Declaration as specified in the Tender Data Sheet in the format provided in section X shall be provided as a mandatory requirement. 18.2 The Tender Security or Tender Securing Declaration is required to protect the Procuring Entity against the risk of Tenderer’s conduct which would warrant the security’s forfeiture, pursuant to ITT subClause 19.9. 18.3 The Tender Security shall be denominated in the currency of the Tender and shall be in one of the following forms: a) Cash; b) A Bank Guarantee; c) An Insurance Bond issued by an insurance firm approved by the PPOA located in Kenya; d) An irrevocable letter of credit issued by a reputable bank. 18.4 The Tender Security shall be in accordance with the Form of the Tender Security included in Section X or another form approved by the Procuring Entity prior to the Tender submission. 18.5 The Tender Security shall be payable promptly upon written demand by the Procuring Entity in case any of the conditions listed in subClause 19.8 are invoked. 18.6 Any Tender not accompanied by a Tender Security in accordance with sub-Clauses 19.1 or 19.3 shall be rejected by the Procuring Entity as non-responsive, pursuant to ITT Clause 28. 18.7 The Procuring Entity shall immediately release any Tender Security if: a) The procuring proceedings are terminated; b) The Procuring Entity determines that none of the submitted Tenders is responsive; c) A contract for the procurement is entered into. 18.8 The Tender Security shall be forfeited and the Tender Securing Declaration executed if the Tenderer: a) Withdraws its Tender after the deadline for submitting Tenders but before the expiry of the period during which Tenders must remain valid; b) Rejects a correction of an arithmetic error pursuant to sub-Clause 29.2; c) Refuse to enter into a written contract in accordance with ITT Clause 40; 18.9 d) Fails to furnish the Performance Security in accordance with ITT Clause 41. The Tender Security and Tender Securing Declaration of a joint venture must be in the name of the joint venture submitting the Tender. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 16 of 270 17 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) 18.1 0 A Tenderer shall be suspended from being eligible for Tendering in any contract with the Procuring Entity for the period of time indicated in the Tender Securing Declaration: a) If the Tenderer withdraws its Tender, except as provided in ITT sub-Clauses 18.2 and 29.2; or b) In the case of a successful Tenderer, if the Tenderer fails within the specified time limit to: (i) Sign the contract; or (ii) Furnish the required Performance Security. 19. Format and Signing of Tender 19.1 The Tenderer shall prepare one original of the documents comprising the Tender as described in ITT Clause 12 of these Instructions to Tenderers, with the Form of Tender, and clearly marked “ORIGINAL”. In addition, the Tenderer shall submit copies of the Tender, in the number specified in the Tender Data Sheet, and clearly marked as “COPIES”. In the event of discrepancy between them, the original shall prevail. 19.2 The original and all copies of the Tenders shall be typed or written in indelible ink and shall be signed by a person or persons duly authorized to sign on behalf of the Tenderer. This authorization shall consist of a written confirmation as specified in the Tender Data Sheet and shall be attached to the Tender. The name and position held by each person signing the authorization must be typed or printed below the signature. All pages of the Tender, except for un-amended printed literature, shall be initialled by the person or persons signing the Tender. 19.3 Any interlineations, erasures, or overwriting shall be valid only if they are initialled by the person or persons signing the Tender. 19.4 The Tenderer shall furnish information as described in the Form of Tender on commissions or gratuities, if any, paid or to be paid to agents relating to this Tender and to contract execution if the Tenderer is awarded the contract C. Submission of Tenders 20. Sealing and Marking of Tenders 20.1 20.2 The Tenderer shall seal the original and each copy of the Tender in separate envelopes, duly marking the envelopes as “ORIGINAL” and “COPY”. The envelopes shall then be sealed in an outer envelope securely sealed in such a manner that opening and resealing cannot be achieved undetected. The inner and outer envelopes shall: a) Be addressed to the Procuring Entity at the address given in the Tender Data Sheet; and b) Bear the Project name indicated in the Tender Data Sheet, the Invitation for Tenders (IFT) title and number indicated in the Tender Data Sheet, and a statement: “DO NOT OPEN BEFORE,” to be completed with the time and the date specified in the Tender Data Sheet, pursuant to ITT sub-Clause 22.1. 20.3 In addition to the identification required in sub-Clause 21.2, the inner envelopes shall also indicate the name and address of the Tenderer to enable the Tender be returned unopened in case it is declared late, pursuant to sub-Clause 22.1 and for matching purpose under ITT Clause 23 20.4 If the outer envelope is not sealed and marked as required by ITT sub clause 21.2, the Procuring Entity shall assume no responsibility for KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 17 of 270 18 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) misplacement or premature opening of the Tender. 21. Deadline for Submission of Tenders 22. Late Tenders 21.1 Tenders shall be received by the Procuring Entity at the address specified under ITT sub-Clause 21.2 no later than the date and time specified in the Tender Data Sheet. 21.2 The Procuring Entity may, in exceptional circumstances and at its discretion, extend the deadline for the submission of Tenders by amending the Tendering documents in accordance with ITT Clause 9, in which case all rights and obligations of the Procuring Entity and Tenderers previously subject to the deadline will thereafter be subject to the new deadline. 21.3 The extension of the deadline for submission of Tenders shall not be made later than the period specified in the Tender Data Sheet before the expiry of the original deadline. 22.1 22.2 23. Modification, Substitution and Withdrawal of Tenders The Procuring Entity shall not consider for evaluation any Tender that arrives after the deadline for submission of Tenders, in accordance with ITT Clause 22. Any Tender received by the Procuring Entity after the deadline for submission of Tenders shall be declared late, rejected and returned unopened to the Tenderer 23.1 A Tenderer may modify or substitute or withdraw its Tender after it has been submitted, provided that written notice of the modification, including substitution or withdrawal of the Tender, is received by the Procuring Entity prior to the deadline prescribed for submission of Tenders prescribed under ITT sub-Clause 22.1. 23.2 The Tenderer’s modification or substitution or withdrawal notice shall be prepared, sealed, marked, and dispatched in accordance with the provisions of ITT Clauses 20 and 21 with the outer and inner envelopes additionally marked “MODIFICATION” or SUBSTITUTION or “WITHDRAWAL” as appropriate. The notice may also be sent by electronic mail and facsimile, but followed by a signed confirmation copy, postmarked not later than the deadline for submission of Tenders. 23.3 No Tender may be withdrawn, replaced or modified in the interval between the deadline for submission of Tenders and the expiration of the period of Tender validity specified by the Tenderer on the Tender Form. Withdrawal of a Tender during this interval shall result in the Tenderer’s forfeiture of its Tender Security or execution of Tender Securing Declaration, pursuant to the ITT sub-Clause 19.9. 23.4 Withdrawal of a Tender between the deadline for submission of Tenders and the expiration of the period of Tender validity specified in the Tender Data Sheet or as extended pursuant to sub-Clause 22.2 shall result in the forfeiture of the Tender Security and execution of Tender Securing Declaration pursuant to ITT subClause 19.9. 23.5 Tenderers may only offer discounts to, or otherwise modify the prices of their Tenders by submitting Tender modifications in accordance with this Clause, or included in the original Tender submission. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 18 of 270 19 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) D. Opening and Evaluation of Tenders 24. Opening of Tenders 25. Confidentiality 24.1 The Procuring Entity will open all Tenders including modifications, substitution or withdraw notices made pursuant to ITT Clause 24, in public, in the presence of Tenderers or their representatives who choose to attend and other parties with legitimate interest and Tender proceedings, at the place on the date and at time specified in the Tender Data Sheet. The Tenderers’ representatives who are present shall sign a register as proof of their attendance. 24.2 Envelopes marked “WITHDRAWAL” shall be opened and read out first. Tenders for which an acceptable notice of withdrawal has been submitted pursuant to ITT Clause 24 shall not be opened but returned to the Tenderer. If the withdrawal envelope does not contain a copy of the “Power of Attorney” confirming the signature as a person duly authorized to sign on behalf of the Tenderer, the corresponding Tender will be opened. Subsequently, all envelopes marked "MODIFICATION" shall be opened and the submissions therein read out in appropriate detail. Thereafter all envelopes marked or "SUBSTITUTION" opened and the submissions therein read out in appropriate detail. 24.3 All other envelopes shall be opened one at a time. The Tenderers' names, the Tender prices, the total amount of each Tender and of any alternative Tender (if alternatives have been requested or permitted), any discounts, the presence or absence of Tender security, and such other details as the appropriate tender opening committee may consider appropriate, will be announced by the Secretary of the Tender Opening Committee at the opening. 24.4 Tenders or modifications that are not opened and not read out at Tender opening shall not be considered further for evaluation, irrespective of the circumstances. In particular, any discount offered by a Tenderer which is not read out at Tender opening shall not be considered further. 24.5 Tenderers are advised to send in a representative with the knowledge of the content of the Tender who shall verify the information read out from the submitted documents. Failure to send a representative or to point out any un-read information by the sent Tenderer’s representative shall indemnify the Procuring Entity against any claim or failure to read out the correct information contained in the Tenderer’s Tender. 24.6 No Tender will be rejected at Tender opening except for late Tenders which will be returned unopened to the Tenderer, pursuant to ITT Clause 23. 24.7 The Secretary of the appropriate tender opening committee shall prepare minutes of the Tender opening. The record of the Tender opening shall include, as a minimum: the name of the Tenderers and whether or not there is a withdrawal, substitution or modification, the Tender price per Lot if applicable, including any discounts and alternative offers and the presence or absence of a Tender Security or Tender Securing Declaration. 24.8 The Tenderers’ representatives who are present shall be requested to sign the record. The omission of a Tenderer’s signature on the record shall not invalidate the contents and affect the record. 24.9 A copy of the minutes of the Tender opening shall be furnished to individual Tenderers upon request. 25.1 Information relating to the examination, clarification, evaluation, KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 19 of 270 20 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) and comparison of Tenders and recommendations for the award of a Contract shall not be disclosed to Tenderers or any other persons not officially concerned with such process until the award to the successful Tenderer has been announced. 26. Clarification of Tenders 27. Preliminary Examination of Tenders 25.2 Any effort by a Tenderer to influence the Procuring Entity’s processing of Tenders or award decisions may result in the rejection of his Tender. 25.3 Notwithstanding sub-Clause 26.2, from the time of Tender opening to the time of Contract award, if any Tenderer wishes to contact the Procuring Entity on any matter related to the Tendering process, it should do so in writing. 26.1 To assist in the examination, evaluation, comparison of Tenders and post-qualification of the Tenderer, the Procuring Entity may, at its discretion, ask a Tenderer for clarification of its Tender including breakdown of prices. Any clarification submitted by a Tenderer that is not in response to a request by the Procuring Entity shall not be considered. 26.2 The request for clarification and the response shall be in writing. No change in the prices or substance of the Tender shall be sought, offered, or permitted except to confirm the correction of arithmetic errors discovered by the Procuring Entity in the evaluation of Tenders in accordance with ITT Clause 29. 26.3 From the time of Tender opening to the time of Contract award if any Tenderer wishes to contact the Procuring Entity on any matter related to the Tender it should do so in writing. 27.1 Prior to the detailed evaluation of Tenders, the Procuring Entity will determine whether: a) The Tender has been submitted in the required format; b) Any Tender Security submitted is in the required form, amount and validity period; c) The Tender has been signed by the person lawfully authorized to do so; d) The required number of copies of the Tender have been submitted; e) The Tender is valid for the period required; f) All required documents and information have been submitted; and g) Any required samples have been submitted. 27.2 The Procuring Entity will confirm that the documents and information specified under ITT Clause 12 and ITT Clause 13 have been provided in the Tender. If any of these documents or information is missing, or is not provided in accordance with the Instructions to Tenderers, the Tender shall be rejected. 27.3 The Procuring Entity may waive any minor informality, nonconformity, or irregularity in a Tender which does not constitute a material deviation, provided such waiver does not prejudice or affect the relative ranking of any Tenderer 27.4 A substantially responsive Tender is one which conforms to all the terms, conditions, and specifications of the Tendering documents, without material deviation or reservation. A material deviation or KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 20 of 270 21 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) reservation is one that: a) Affects in any substantial way the scope, quality, or execution of the Works; b) Limits in any substantial way, inconsistent with the Tendering documents, the Procuring Entity's rights or the Tenderer’s obligations under the Contract; or c) If rectified, would affect unfairly the competitive position of other Tenderers presenting substantially responsive Tenders. 27.5 28. Correction of Errors 28.1 If a Tender is not substantially responsive, it will be rejected by the Procuring Entity, and may not subsequently be made responsive by correction or withdrawal of the non-conforming deviation or reservation. Tenders determined to be substantially responsive will be checked by the Procuring Entity for any arithmetic errors. Errors will be corrected by the Procuring Entity as follows: a) If there is a discrepancy between unit prices and the total price that is obtained by multiplying the unit price and quantity, the unit price shall prevail, and the total price shall be corrected, unless in the opinion of the Procuring Entity there is an obvious misplacement of the decimal point in the unit price, in which the total price as quoted shall govern and the unit price shall be corrected; b) If there is an error in a total corresponding to the addition or subtraction of subtotals, the subtotals shall prevail and the total shall be corrected; and 28.2 c) Where there is a discrepancy between the amounts in figures and in words, the amount in words will govern. The amount stated in the Tender will, be adjusted by the Procuring Entity in accordance with the above procedure for the correction of errors and, with, the concurrence of the Tenderer, shall be considered as binding upon the Tenderer. If the Tenderer does not accept the corrected amount, its Tender will then be rejected, and the Tender Security may be forfeited and the Tender Securing Declaration may be executed in accordance with sub-Clause 19.9. 29. Conversion to Single Currency 29.1 To facilitate the evaluation and comparison, the Procuring Entity will convert all Tender prices expressed in the amounts in various currencies in which the Tender prices are payable to Kenya Shillings at the selling exchange rate established for similar transactions by the Central Bank of Kenya ruling on the date specified in the Tender Data Sheet. 30. Comparison of Tenders 30.1 The Procuring Entity shall evaluate and compare only the Tenders determined to be substantially responsive in accordance with ITT Clause 28. In evaluating the Tenders, the Procuring Entity will determine for each Tender the evaluated Tender price by adjusting the Tender price as follows: Making any correction for errors pursuant to ITT Clause 29; Excluding provisional sums and the provision, if any for contingencies in the Bill of Quantities, but including Day work , where priced competitively ; and Making appropriate adjustments to reflect discounts or other price modifications offered in accordance with sub-Clause 24.5. 30.2 30.3 The Procuring Entity may waive any minor informality or nonconformity, which does not constitute a material deviation, KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 21 of 270 22 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) provided such waiver does not prejudice or affect the relative standing of any Tenderer. Variations, deviations, and alternative offers and other factors, which are in excess of the requirements of the Tendering documents or otherwise result in unsolicited benefits for the Procuring Entity will not be taken into account in Tender evaluation. There will be no national preference except to the effect and substance as contained in the Tender Data Sheet. 31. National Preference 31.1 32. Determination of the winning evaluated Tender 33. Postqualification of Tenderer 32.1 The Tender with the highest combined technical and financial score evaluated from among those which are eligible, compliant and substantially responsive shall be the winning evaluated Tender. 33.1 If specified in the Tender Data Sheet, post-qualification shall be undertaken. 33.2 The Procuring Entity will determine to its satisfaction whether the Tenderer that is selected as having submitted the winning evaluated responsive Tender is qualified to perform the contract satisfactorily, in accordance with the criteria listed in sub-Clause 13.3. The determination will take into account the Tenderer’s financial, technical, and production capabilities. It will be based upon an examination of the documentary evidence of the Tenderer’s qualifications submitted by the Tenderer, pursuant to sub-Clause 13.3, as well as such other information as the Procuring Entity deems necessary and appropriate. Factors not included in these Tendering documents shall not be used in the evaluation of the Tenderer’s qualifications. An affirmative determination will be a prerequisite for award of the contract to the Tenderer. A negative determination will result in rejection of the Tenderer’s Tender, in which event the Procuring Entity will proceed to the next highest evaluated tender to make a similar determination of that Tenderer’s capabilities to perform satisfactorily. 33.3 33.4 E. Award of Contract 34. Criteria of Award 34.1 Subject to ITT Clause 35 and 36, the Procuring Entity will award the Contract to the Tenderer whose Tender has been determined to be substantially responsive to the Tendering documents and who has offered the winning evaluated tender Price, provided that such Tenderer has been determined to be: a) Eligible in accordance with the provisions of ITT Clause 3; b) Is determined to be qualified to perform the Contract satisfactorily; c) Successful negotiations have been concluded. 35. Clarifications 35.1 Clarifications may be undertaken with the winning evaluated tenderer relating to the following areas: a) A minor alteration to the technical details of the statement of requirements; b) Reduction of quantities for budgetary reasons, where the reduction is in excess of any provided for in the Tendering documents; c) A minor amendment to the Contract Data Sheet; d) Finalizing payment arrangements; KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 22 of 270 23 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) e) Mobilization arrangements; f) Agreeing final delivery or work schedule to accommodate any changes required by the Procuring Entity; g) The methodology or staffing; or Clarifying details that were not apparent or could not be finalized at the time of Tendering. 35.2 Clarifications shall not change the substance of the tender. 36.1 Notwithstanding ITT Clause 35, the Procuring Entity reserves the right to accept or reject any Tender, and to cancel the Tendering process and reject all Tenders, at any time prior to the award of Contract, without thereby incurring any liability to the affected Tenderer or Tenderers. 36.2 Notice of the rejection of all Tenders shall be given promptly within 14 days to all Contractors that have submitted Tenders. 36.3 The Procuring Entity shall upon request communicate to any Tenderer the grounds for its rejection of its Tenders, but is not required to justify those grounds. 37. Procuring Entities Right to Vary Quantities at the Time of Award 37.1 38. Notification of Award 38.1 The Procuring Entity reserves the right at the time of contract award to increase or decrease the quantity of goods or related services originally specified in these Tendering documents (schedule of requirements) provided this does not exceed by the percentage indicated in the Tender Data Sheet, without any change in unit price or other terms and conditions of the Tender and Tendering documents. The Tenderer whose Tender has been accepted will be notified of the award by the Procuring Entity prior to expiration of the Tender validity period by e-mail or facsimile confirmed by registered letter. This letter (hereinafter and in the Conditions of Contract called the "Letter of Acceptance") will state the sum that the Procuring Entity will pay the Contractor in consideration of the provision and maintenance of the Work(s) as prescribed by the Contract (hereinafter and in the Contract called the “Contract Price”). The notification of award will constitute the formation of the Contract, subject to the Tenderer furnishing the Performance Security in accordance with ITT Clause 41 and signing the Contract in accordance with sub-Clause 40.2 At the same time as the person submitting the successful Tender is notified, the Procuring Entity will notify each unsuccessful Tenderer, the name of the successful Tenderer and the Contract amount and will discharge the Tender Security and Tender Securing Declaration of the Tenderer pursuant to ITT sub Clause 19.7 If, after notification of award, a Tenderer wishes to ascertain the grounds on which it’s Tender or application for pre-qualification was unsuccessful, it should address its request to the secretary of the Tender Committee that authorized the award of contract. The secretary of the Tender Committee shall, within fourteen days after a request, provide written reasons as to why the Tender, proposal or application to be pre-qualified was unsuccessful. However, failure to take this opportunity to clarify the grounds for rejection does not affect the Tenderer’s right to seek immediate review by the Public Procurement Administrative Review Board under Clause 45. 36. Procuring Entity’s Right to Accept any Tender and to Reject any or all Tenders 38.2 38.4 39. Signing of 39.1 Promptly, and in no case later than 14 days, after notification, Procuring Entity shall send the successful Tenderer the Agreement KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 23 of 270 24 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) Contract 40. Performance Security and Contract Data Sheet, incorporating all agreements between the parties obtained as a result of Contract negotiations. 39.2 Within the period specified in the notification or Tender Data Sheet but not earlier than fourteen (14) days since notification of award of contract, the successful Tenderer shall sign and date the contract and return it to the Procuring Entity. 40.1 Within thirty (30) days but after 14 days after receipt of the Letter of Acceptance, the successful Tenderer shall deliver to the Procuring Entity a Performance Security in the amount and in the form stipulated in the Tender Data Sheet and the Contract Data Sheet, denominated in the type and proportions of currencies in the Letter of Acceptance and in accordance with the Conditions of Contract. If the Performance Security is provided by the successful Tenderer in the form of a Bank Guarantee or Insurance Bond, it shall be issued either: a) At the Tenderer’s option, by a bank or insurance firm located in Kenya, or a foreign bank or insurance firm through a correspondent bank or insurance firm located in Kenya; 40.2 b) With the consent of the Procuring entity, directly by a foreign bank acceptable to the Procuring entity. 40.3 41. Advance Payment 42. Adjudicator 41.1 Failure of the successful Tenderer to comply with the requirement of sub-Clause 41.1 shall constitute sufficient grounds for the annulment of the award and forfeiture of the Tender Security, in which event the Procuring Entity may make the award to the next winning evaluated tenderer or call for new Tenders. The Procuring Entity will provide an Advance Payment as stipulated in the Conditions of Contract, subject to a maximum amount, as stated in the Tender Data Sheet. 41.2 The Advance Payment request shall be accompanied by an Advance Payment Security (Guarantee) in the form provided in Section X. For the purpose of receiving the Advance Payment, the Tenderer shall make an estimate of, and include in its Tender, the expenses that will be incurred in order to commence work. These expenses will relate to the purchase of equipment, machinery, materials, and on the engagement of labour during the first month beginning with the date of the Procuring Entity’s “Notice to Commence” as specified in the Contract Data Sheet. 42.1 The Procuring Entity proposes the person named in the Tender Data Sheet to be appointed as Adjudicator under the Contract. If the Tenderer disagrees with this proposal, the Tenderer should so state in the Tender. If, in the Letter of Acceptance, the Procuring Entity has not agreed on the appointment of the Adjudicator, the Adjudicator shall be appointed by the Appointing Authority designated in the Contract Data Sheet at the request of either party. F. Review of Procurement Decisions 43. Right to Review 43.1 A Tenderer who claims to have suffered or risk suffering, loss or damage or injury as a result of breach of a duty imposed on a Procuring Entity or an Approving Authority by the Public Procurement and Disposal Act, 2005 and the Public Procurement and Disposal Regulations 2006, the procurement proceedings or processes, may seek administrative review as prescribed by the Act. The following matters, however, shall not be subject to the administrative review: a) The choice of procurement method; KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 24 of 270 25 SECTION II: INSTRUCTIONS TO TENDERERS (ITT) b) a decision by the Procuring Entity to reject all Tenders, proposals or quotations; c) Where a contract is signed in accordance to Section 68 of the Public Procurement and Disposal Act,2005; d) Where an appeal is frivolous. 44. Time Limit on Review 44.1 45. Submission of Applications for Review by the Public Procurement Administrative Review Board 45.1 45.2 The Tenderer shall submit an application for review in the number of copies and pay fees as prescribed by the Public Procurement and Disposal Regulations 2006 within fourteen (14) days of the time the Tenderer became or should have become aware of the circumstances giving rise to the complaint or dispute. Any application for administrative review shall be submitted in writing to the Secretary, Public Procurement Administrative Review Board on Form RB 1 at the address shown in the Tender Data Sheet. The secretary to the review board shall immediately after filing of the request, serve a copy thereof on the Procuring Entity or Director-General as the case may be. The application for administrative review shall be in accordance with the requirements of Regulation 73 of the Public Procurement and Disposals Regulations, 2006, including: a) Reasons for the complaint ,including any alleged breach of the Act or Regulations; b) An explanation of how the provisions of the Act and or Regulation has been breached or omitted, including the dates and name of the responsible public officer, where known; c) Statements or other evidence supporting the complaint where available as the applicant considers necessary in support of its request; d) Remedies sought; e) Any other information relevant to the complaint. 46. Decision by the Public Procurement Administrative Review Board 46.1 The Administrative Review Board shall within thirty days after receipt of an application for administrative review deliver a written decision which shall indicate: a) Annulling anything the Procuring Entity has done in the procurement proceedings, including annulling the procurement proceedings in their entirety; b) Giving directions to the Procuring Entity with respect to anything to be done or redone in the procurement proceedings; c) Substituting the decision of the Review Board for any decision of the Procuring Entity in the procurement proceedings; d) Order the payment of costs as between parties to the review. 47. Appeal on the decision of the Review Board 46.2 The decision made by the Review Board shall, be final and binding on the parties unless judicial review thereof commences within fourteen (14) days from the date of the Review Board’s decision. 47.1 Any party to the review aggrieved by the decision of the Review Board may appeal to the High Court and the decision of the High Court shall be final. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 25 of 270 26 SECTION III: TENDER DATA SHEET KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 26 of 270 27 SECTION III: TENDER DATA SHEET Tender Data Sheet (TDS) Instructions to Tenderers Clause Reference TDS Reference Number ITT Clause Number Amendments of, and Supplements Instruction to Tenderers to, Clauses in the A. Introduction 1. 11.1 . 2. 21.1 . 3. 31.2 . 4. 41.3 . 5. 7 3.1 . The Procuring Entity is: The Kenya Ports Authority (KPA). Name of Project is: UPGRADING OF INCOMING KPLC SUPPLY FROM 11KV TO 132KV The expected completion date of the works is 16 months. However bidders may suggest their own timelines The Objectives of the Project are : UPGRADING OF INCOMING KPLC SUPPLY FROM 11KV TO 132KV a) This invitation to tender is open to Registered Electrical Contractors who shall demonstrate the require technical and financial capability to undertake the envisaged project. b) Tender Security shall be in the amount of Kenya Shillings Five Million (Kshs5,000,000) in the form of a Bank Guarantee in the format provided in the tender document 6. 8 5.2 . 7. 7.3 8. 17.5 . 9. 7.6 Alternative time for completion tenderers shall be expected to submit their work programs and may propose alternative completion periods Pre-Tender meeting will take place at KPA Kipevu Headquarter Kilindini Mombasa Venue 6th Floor Finance Block III at 1000hours On Thursday, 23rd June, 2011 Starting at 1000Hours The minutes of the pre-Tender meeting will be transmitted within [five(5 days)] Non-attendance at the pre-tender meeting will not result in disqualification B. Tendering Documents 10. 8.2 The number of copies to be completed and returned with the Tender is 2 i.e. One ORIGINAL and Two (2) COPIES 11. 8.1 Address for clarification of Tendering Document is The Secretary, Corporation Tender Committee, Kenya Ports Authority, Mombasa, KENYA Tel +254 041 2113600/999 Fax: +254-041-2226721 Email: ctcsecretary@kpa.co.ke 12. 8.2 Period to Respond to request for clarification by the Procuring Entity [2- days] Period Prior to deadline for submission of Tenders for Tenderers to request clarification [ten (10) days] C. Preparation of Tenders 13. 14. 11.1 12.1 Language of Tender and all correspondence shall be English Other information or materials required to be completed and submitted by Tenderers : KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 27 of 270 28 SECTION III: TENDER DATA SHEET Tenders shall be submitted in a two envelope systems (Envelope A Technical Submission and Envelope B financial Submission) the two sealed envelopes shall then be sealed in an outer envelope bearing the tender number and name and a statement ‘ DO NOT OPEN BEFORE 0900HOURS ON TUESDAY, 26TH JULY, 2011 Envelope A shall contain the Technical submission and shall be clearly marked “Envelope A – Technical Submission”. Envelope A shall contain NO indication of the tender price or other financial information of the bid and: a. Shall have a table of contents pages clearly indicating Sections and Page Numbers clearly indicated. The various sections shall be highlighted and arranged in the format below b. Shall have pages in the whole document numbered in the correct sequence and all pages MUST be initialed. THIS IS A MANDATORY REQUIREMENT AND TENDERS WITHOUT PAGE NUMBERS SHALL BE DISQUALIFIED. Section 1. Profile Requirements Particulars of Tendering Company including the Company background, statutory registration documents e.g. VAT & PIN Certificate, and a Valid /Current Tax Compliance certificate(TCC3) (MANDATORY) Duly filled and signed Confidential Business questionnaire and Anti-Corruption Declaration Commitment/ Pledge(MANDATORY) A Valid and Current Ministry of Energy, Energy Regulatory Commission (ERC) Class A Certificate (MANDATORY) 2. Manufacturer’s Authorization Original Manufacturer’s Authorization Form in the format provided in the tender document for the transformers and switchgear - where the bidder is not the manufacturer (MANDATORY) 3. Tender Security Original Tender Security of Kshs.5 million in form of a bank Guarantee in the format provided in the Tender Document valid for a period of 120 days from date of tender opening (MANDATORY) The main material and equipment to be supplied must have proven experience of at least five (5) years, up to bid submission, of safe operation in power system network. Provide evidence to demonstrate that the bidder and the bidder’s proposed Sub-contractor(s), if any, have previously erected distribution system of the type specified and have adequate technical knowledge and practical experience. The bidder shall furnish with its bid details of having completed or being in the process of completing the supply and installation of at least one (1) turnkey contract of a similar size and complexity of 7.5 MVA, 132/11 kV Substation or a Substation of a higher Transformer rating and/or higher voltage rating in the last 5 years. The Manufacturer must have minimum 5 years operating experience with transformers 4. Experience KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 28 of 270 29 SECTION III: TENDER DATA SHEET and High Voltage Switchgear systems. Proof including site details, technical brochures must be included with the tender. 5. Technical Specifications and Technical schedules Tenderers Experience In Similar works- List and contact details of sites where the bidder has installed similar equipment. Complete with brief description of project scope, contract value, and Contract period. Site Visit may be requested to prove the same. (use the table format provided) Qualifications and Experience of Key Projects Staff proposed for the Project (Team Leader, Co-Team Leader, other Engineers) Provide a list attach Curriculum Vitae in the format provided and attach certified copies of professional and academic certificates. Key equipment proposed for the works and evidence of ownership or lease (Provide a list and attach evidence of ownership or lease) The Manufacturers of all the major equipment to be supplied must have ISO 9001 or equivalent quality assurance Certification and the tenderer to provide manufacturer’s authorisation The bidder shall return all the Technical schedules duly filled in the format provided Detailed information on the Transformers and high Voltage Switchgear systems including specifications and Manuals, Information Brochures of the items quoted for and details of their country of origin, CE conformity certificate etc. ISO CERTIFICATION for items imported from overseas (MANDATORY) KEBS certification for local items (MANDATORY) *This should be in form of a clause-by-clause commentary on the Procuring Entity’s Technical Specifications demonstrating substantial responsiveness of the transformers and HV Switchgear to those specifications, or a statement of deviations and exceptions to the provisions of the Technical Specifications. Tenderer’s Technical Specifications shall not be a reproduction of the Procuring Entity’s specifications. ( refer to clause 13 of the ITB) The schedule of deviations should be accompanied by a commentary of how they enhance the operational efficiency, cost effectiveness, maintainability, and durability, environmental and economic advantages. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 29 of 270 30 SECTION III: TENDER DATA SHEET Training proposal for KPA Engineers /Technical (provide details of the training areas to be covered)- MANDATORY 6. Methodology and work plan 7. Under-takings Work plan for design, building, shipping, delivery, testing and commissioning in descriptive Gantt chart format. (i) A written undertaking: (a) of ability to supply spares for at least 15 years after handing over which includes upgrading of any software and hardware proposed by the bidder in the Tender (MANDATORY) (b) to supply the Transformers and high Voltage Switchgear accompanied by a Computer based Maintenance Program for execution of maintenance schedules, should the tenderer be awarded the contract(MANDATORY) (c) to supply the Switchgear accompanied by all necessary manuals from the original manufacturer of each major component to be of good quality, plastic covered, and in the English language required to operate and maintain the Transformers and high Voltage Switchgear and in three (3) copies for each of the following categories: -Operation, -Maintenance and Parts (MANDATORY) (ii) Details of how the bidder intends to carry out their part of the obligations during the duration of Warranty (defects liability) period - 24 months after commissioning (MANDATORY) 8. Major Component Manufacturer Documentation Form 9. Defects liability period support plan 10. Spare Parts 11. Financial Capacity This should list the major components used on the installation and their manufacturers’ details to include name, address & location, contacts and name of the contact person and be should be submitted in the format provided in the tender document (MANDATORY) (NOTE: The manufacturer’s engineer shall give a minimum 4 months on site technical support as long as the Procuring entity has given notice to require their presence. Thereafter, the manufacturer’s engineer shall be availed on site within 48 hours of notification) (MANDATORY) Recommended list of Spares to be supplied with the Transformers and high Voltage Switchgear for three year's preventive maintenance consumption after the 24 months Defect Liability period (MANDATORY) That the bidder shall have adequate financial stability and status to meet the financial obligations pursuant to the scope of the works. In KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 30 of 270 31 SECTION III: TENDER DATA SHEET particular the bidder shall submit audited financial statements for the last 4 years i.e. 2007, 2008, 2009 and 2010. The bidder shall demonstrate access to, or availability of financial resources such as liquid Assets, lines of credit, unencumbered real assets, and other financial means other than any contractual advance payments to meet the following cash flow requirement : a) Cash flow Capacity to have a cash flow of amount of Kshs 90,Million and Evidence of access to credit lines (eg letter from Bankers) 12. Accompanying technical documents 13. Information regarding litigation, The overall cash flow for this contract and current commitments. Annual Turnover of Kshs 300Million in the last three(3) year Operator manuals, Maintenance manuals etc Any other item and information which the Tenderer considers may support his technical proposal.(MANDATORY) (Litigation history in the last ten years in the format provided) (MANDATORY) Envelope B shall contain: i. ii. 13.3 Priced Bill Of quantities iii. Cost of spare parts to be used during the provided in the technical specifications iv. Cost of spare-parts to be used for one year’s preventive maintenance after warranty period. v. Priced list of major spare parts, listed tools(clause 1.13 of technical specifications) Accessories and consumables in the format provided in the tender document vi. 15 Form of Tender. warranty period as Optional extras and cost, if any. Minimum qualifying criteria shall be 75% of the marks in the technical evaluation (Envelope A) The marks shall be distributed as follows: Qualification requirements for bidders, including members of joint ventures, subcontractors or vendors:The Bidder and his proposed sub-contractors, if any, shall supply documentary evidence to establish to the Procuring Entity’s satisfaction that the bidder has the Financial, Technical, Production, and capacity necessary to perform the contract, including capacity in terms of personnel for the purpose of performing the services Bidders qualification will be evaluated on the basis of the following criteria: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 31 of 270 32 SECTION III: TENDER DATA SHEET A. TENDERER’S TECHNICAL CAPACITY AND EXPERIENCE A1. Technical Capacity of the Contractor The bidder shall provide evidence of ownership or ability to access tools, test equipments and heavy equipment (age of heavy equipment items should be given) required for timely completion of the Contract. The list of such tools and heavy equipment shall be Listed (verification shall be done where required) Major Construction & Transportation Equipment, for carrying out Civil Works, including loading and unloading equipment Substation Erection Tools & Equipment Test Equipment for Plant and Switchgear and for Protection & Control Equipment and Schemes. - A2. CV of key personnela) The following key staff of the Bidder for the proposed project shall be Registered professionals by the domicile professional National body or a recognized International professional body (Attach Registration certificates of the professionals) with at least 5 years of relevant experience: Project Manager should have completed at least one (1) project of similar complexity of 15 MVA, 132/11 KV Substation or a Substation of a higher Transformer rating and/or higher voltage rating in the last 5 years Construction Engineer (Registered Engineer). The construction Engineer shall have a minimum of five (5) years experience in similar works - (The Construction Engineer shall only be engaged in one Lot for the whole project duration) Safety Officer (Minimum formal Education- a Diploma in Electrical Engineering with training in safety and experience in safety) Detailed CVs (Including the telephone contact and email address) shall be provided listing the projects and relevant roles played in the project (to be verified where necessary) for each of the three (3) key staff shall be provided. A signed letter from the three (3) key staff confirming their commitment and availability to the project if awarded shall also be provided. No replacement of the key staff of the proposed project Organization shall be allowed without prior approval from the Procuring Entity. Where replacement is necessary the staff`s qualification shall be the same as above. B. ADHERENCE TO TECHNICAL SPECIFICATIONS AND TECHNICAL SCHEDULES B1. Performance Guarantees and technical schedules. Bidders’ Satisfactory completion of technical schedules for outdoor switchgear will be assessed. The technical schedules forms are listed under Technical guarantees schedule for outdoor switchgear and will be evaluated as hereunder: a) b) c) d) e) f) g) Schedule Schedule Schedule Schedule Schedule Schedule Schedule 1a 1b 2a 2b 3a 3b 4a KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 32 of 270 33 SECTION III: TENDER DATA SHEET h) i) j) k) l) m) n) Schedule Schedule Schedule Schedule Schedule Schedule Schedule 5 6a 6b 7a 7b 8a 8b B2. Performance Guarantees and technical schedules. Bidders’ Satisfactory completion of technical schedules for 11kV switchgear will be assessed. The technical schedules forms are listed under Technical schedule for 11kV switchgear and will be evaluated as hereunder: i. ii. iii. iv. v. vi. vii. viii. ix. x. xi. xii. xiii. Schedule A Schedule B Schedule C Schedule D Schedule E Schedule F Schedule G Schedule H Schedule I Schedule J Schedule K Schedule L Schedule M B3. Ability to arrange timely Supplies as per the specification & Timely Completion The bidder will provide committal letters from proposed planned suppliers showing that the major materials and equipment in the quantities specified in the contract document will be delivered for timely completion of the Contract on time and as specified in the respective technical specifications and as detailed in the technical schedules: a) 132 kV switchgear. b) 11 kV switchgear. c) Bidders Gantt Chart and Critical Path Method (CPM) Programme for Execution of the Facilities. The Programme provided must be detailed showing all the stages of Execution of the Project from Start to Completion of the project. The Programme should be made using Microsoft Office Projects or any other equivalent programme. C. TRAINING Details of training schedules for KPA engineers and technicians as requied in the technical schedules D. FINANCIAL CAPACITY Evidence of financial capability Audited accounts for the last three(3) year Cash flow as specified Adequate Turnover KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 33 of 270 34 SECTION III: TENDER DATA SHEET EVALUATION SUMMARY Evaluation item A. Adherence to Technical Specifications and technical schedules (55 points) (Only bids that meet a score of 80% in this criteria shall be considered) B. Tenderer’s technical capacity and experience (i) Equipment capacity (10 points) (ii) Personnel capability (10points) (iii) Similar experience- List and evidence of similar contracts i Marks / Points 55 30 n the last 5 years for both manufacturer and bidder (10points) use format provided C. Training D. Financial capacity of the Tenderer: Tenderer’s financial performance based on Certified Audited Accounts for 2007, 2008 and 2009/10 TOTAL MARKS Pass Mark 5 10 100 POINTS 75 points The Authority shall carry out a site visit to the factory/ reference site visits to the reference sites and manufacturing plant prior to opening of financial submission “Envelope B” so as to establish whether the information provided in the technical submission is accurate. Where site visits are conducted, the Evaluation Criteria shall be based on: Quality of workmanship Reliability of the switchgear equipment Availability of spare parts and service response Cost of Maintenance The Bidder(s) whose site(s) is/are visited MUST score a minimum of 15 out of 20 points of the site visit criteria so as to be considered financial opening 16 13.4 17 18 16.4 17.1 19 17.2 20 21 18.1 19.1 22 20.1 23 20.2 In the case of joint venture each partner shall submit information required under Clause ITT Clause 13.4. The price shall be fixed The currency in which the prices shall be quoted shall be: Kenya Shilling or United States Dollars The authority for establishing the rates of exchange shall be Central Bank of Kenya.The applicable date for exchange rates for tendering and evaluation purposes is 28 days earlier than the final deadline for the submission of tenders. The Tender validity period shall be 90 days . The amount of Tender Security shall be KShs 5 Million in the form of a bank Guarantee in the format provided In addition to the original of the Tender, the Tenderer should submit Two copies of the Tender Written confirmation of authorization are Sealed Power of Attorney authorising the signatory to commit the tenderer D. Submission of Tenders 24 21.2 a) Tenders shall be submitted to Tender Box No. 7 located at the BUS TERMINUS, PORT MAIN PEDESTRIAN GATE NO.8, KILINDINI, MOMBASA BEFORE 0900 HOURS ON TUESDAY, 26TH JULY, 2011 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 34 of 270 35 SECTION III: TENDER DATA SHEET 25 21.2 b) 26 22.1 27 22.3 28 24.4 Bulky tenders shall be submitted at the office of Procurement & Supplies Manager ( door no 3.4.3) located on the 4th floor of office Block III at the Kenya Ports Authority Headquarters, Kipevu, Kilindini Mombasa Project name UPGRADING OF INCOMING KPLC SUPPLY FROM 11KV TO 132KV Tender number KPA/169/2010-11/EE Time and date for submission 0900 HOURS ON TUESDAY, 26TH JULY, 2011 The deadline for Tender submission is 0900 HOURS ON TUESDAY, 26TH JULY, 2011 The extension of the deadline for submission of Tenders shall be made not later than 7days; normally not more than seven days] before the expiry of the original deadline. Expiry of Tender validity is 90 days from tender opening date E. Opening and Evaluation of Tenders 29 25.1 33 34.1 35 38.1 The Tender opening shall take place at: New Conference Room, 6th Floor Finance Block III Kenya Ports Authority, Kipevu Headquarters, Kilindini 0900 HOURS ON TUESDAY, 26TH JULY, 2011 Post- qualification will be undertaken where KPA deems it necessary Percentage for quantities increase or decrease is [15 percent] F. Award of Contract 36 41.1 The amount of Performance Security shall be [10% of the contract price]in the form of a Bank guarantee for an equivalent amount in the format provided 37 42.1 38 43.1 The Advance Payment shall be limited to a maximum of fifteen (15) percent of the Contract Price] and in any event shall be covered by a Bank guarantee for an equivalent amount in the format provided. The proposed adjudicator for the project is: The chairman Chartered Institute of Arbitrators Kenya Branch G. Review of Procurement Decisions 39 46.1 The address for submitting appeals to Administrative Review Board : The Secretary, Public Procurement Administrative Review Board , The Public Procurement Oversight Authority, 10th Floor ,National Bank House, P.O. Box 58583-00200, NAIROBI, Kenya. Tel: +254 (0) 20 3244000 Email: info@ppoa.go.ke Website: www.ppoa.go.ke KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 35 of 270 36 SECTION IV: GENERAL CONDITIONS OF CONTRACT SECTION IV: GENERAL CONDITIONS OF CONTRACT KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 36 of 270 PART I – GENERAL CONDITIONS 37 The Conditions of Contract shall be : A: MAIN ELECTROMECHANICAL WORKS CONDITIONS OF CONTRACT (Including erection on site) PART I – GENERAL CONDITIONS PART I – General Conditions, shall be those forming Part I of the “Conditions of Contract for Electrical and Mechanical Works – Including Erection on Site, Third Edition 1987, reprinted 1988 with Editorial Amendments” prepared by the Federation International des Ingenieurs – conseils (FIDIC). The Conditions are subject to variations and additions set out in Part II hereof entitled “Special Conditions”. i. The Special Conditions take precedence over the General Conditions of Contract. ii. Copies of the FIDIC Conditions of Contract can be obtained from: FIDIC Secretariat P.O.Box 86 1000 Lausanne 12 Switzerland Fax: 41 21 653 5432 Telephone 41 21 653 5003 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 37 of 270 PART I – GENERAL CONDITIONS 38 PREAMBLE TO GENERAL CONDITIONS This Preamble, the General Conditions, the Special Conditions, Technical Specification, Employer’s and Contractor’s Drawings and Technical Literature, Schedules and Bills of Quantities and other documents constitute the Contract documents. The clauses and sub-clauses mentioned here are from the FIDIC conditions of Contract for Mechanical and Electrical Works. Commencement Date Sub-Clause 1.1.1 (i) The date for commencement of the works is 14 days from the date of letter of notification by the employer subject to receipt of a letter of acceptance The Employer Sub Clause 1.1.12 The employer is: KENYA PORTS AUTHORITY P.O. Box 95246-80104 Mombasa The Engineer Sub-Clause 1.1.15 Technical Services Manager Kenya Ports Authority P.O. Box 95009-80104 Mombasa The Engineer’s Representative M&E Consulting Engineers P.O. Box 43224-00100 Nairobi Time for Completion Sub-clause 1.1.35 The Time for Completion from the Commencement Date will be agreed at the time of tender award Contractor’s Profit Sub-Clause 1.6 The percentage to cover profit entitlement, where appropriate, is 18%. Ruling Language Sub-Clause 5.1 The version in English language (ruling language) shall prevail. Day to day Communications Sub-Clause 5.2 The language for day to day communications is English. Programme to be Furnished Sub-Clause 12.1 The Programme must be submitted in the form of GANTT Chart and Method Statement. Electricity, Water, Gas and Other Services Sub-Clause 14.3 Supplies on the site are: a. Electricity: Shall be supplied by the Employer b. Water: Shall be supplied by the Employer c. Other Services: The Employer shall not provide any other services. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 38 of 270 PART I – GENERAL CONDITIONS 39 Employer’s Equipment Sub-Clause 14.4 The Employer will not avail for use by the Contractor any equipment Working Hours Sub-Clause 18.3 The normal working hours are 0800Hours to 1700Hours Monday to Friday Delay in Completion Sub-clause 27.1 Failure to meet the Time for Completion entitles the Employer to reduction in Contract Price as follows: Kshs. 100,000.00 per day Maximum Kshs. NO LIMIT Prolonged Delay Sub-Clause 27.2 Maximum amount recoverable from the Contractor by the Employer: 110% of the value of uncompleted work. Terms of Payment Sub-Clause 33.1 In addition to the provisions under Clause 33, the terms of payment shall be on the basis of payment Schedule (if any) annexed to this Preamble. Payment in Foreign Sub-Clause 35.1 Currencies Payment in foreign currencies shall be arranged as follows: Shall be in US DOLLARS or equivalent Rates of Exchange Sub-Clause 35.3 The rates of Exchange for the purpose of the Contract are: Not Applicable. Payment against Provisional Sums Minimum Liability Sub-Clause 36.4 (b) The percentage to be applied to Provisional. Nil Sub-Clause 42.2 The maximum liability of the Contractor to the Employer shall be Contract sum. Insurance of Works Sub-Clause 43.1 The deductible limits in the insurance cover of the Works shall not exceed 10% Sub-Clause 43.1 (a) The additional risks to be insured are: 110% of the value of loss of damage Third Party Liability Sub-Clause 43.3 The amount of insurance against third party liability taken out by the Contractor shall not be less than: Kshs. 200,000.00 Payment on Termination for Employer’s Default Sub-Clause 46.3 The additional amount payable by the Employer on termination shall not exceed : Kshs.100,000.00 Labour, Materials and Transport Sub-Clause 47.1 The method of Calculating adjustments for changes in costs KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 39 of 270 PART I – GENERAL CONDITIONS 40 shall be: Adjustments for changes in the cost of labour, materials, transport or other costs shall not be allowed. Notices to Employer and Engineer Sub-Clause 49.2 The address of the Employer for notices is: THE SECRETARY, CORPORATION TENDER COMMITTEE KENYA PORTS AUTHORITY P. O. BOX 95246-80104 TEL: +254-41-2113999/3600, FAX: +254-41-2226721 E-MAIL: ctcsecretary@kpa.co.ke Applicable Law Procedural Law Arbitration Sub-Clause 51.1 The applicable law is the laws of the Republic of Kenya. for Sub-Clause 51.2 The Procedural Law for arbitration is the laws of the Republic of Kenya. Language and place Sub-Clause 51.3 of Arbitration The language of arbitration is English language. The place of arbitration is Mombasa Kenya. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 40 of 270 PART II – SPECIAL CONDITIONS OF CONTRACT 41 PART II – SPECIAL CONDITIONS OF CONTRACT The Conditions of Contract comprise the “General Conditions of Contract” and the following “Special Conditions of Contract” which include amendments and additions to the “General Conditions of Contract” and the Special Conditions of Contract. The provisions in the “General Conditions of Contract” shall apply unless modified in Sub-Section 3.3: special Conditions of Contract”. (The Clauses referred to in Part II – Section A are those where the provision in the General Conditions (Part I) refer to an alternative solution to be stated in Part II. The provisions in the General Conditions will apply unless an alternative solution is given in Part II – Section A.) Table 3.1 Ser ial No. 01 General Conditions Clause No. 1.1.12 Brief Description Modification Employer 02 1.1.15 Engineer 03 1.1.16 Engineer’s Representative The Employer shall be: Kenya Ports Authority P. O. Box 95009-80104 Tel. No. +245-41-2311867 Fax No. +254-41-2226721 Email: ctcsecretary@kpa.co.ke The Engineer shall be: Technical Services Manager P. O. Box 95246-80104 Tel. No. +245-41-2311867 Fax No. +254-41-2226721 Email: asamatar@kpa.co.ke M&E Consulting Engineers P.O. Box 43224-00100, Nairobi 04 1.1.11 05 4 (Subclause 6.6.) 06 9.0 Defects Notification Period Operation and Maintenance Manuals Price Variation 07 10.1 08 Invitation 09 25.1 Performance Security Tender Validity Period Time completion for The Defects Notification Period shall be 24 months. Operation and Maintenance Manuals shall be in English language. 9.1 Contract price variations shall not be allowed for contracts not exceeding one year (12 months) 9.2 Where contract price variation is allowed, the variation shall not exceed 15% of the original contract price. 9.3 Price variation requests shall be processed by the procuring entity within 30 days of receiving the request. Performance Security shall be 10% of the Contract sum in the form of a bank guarantee in the format provided The Tender shall remain valid for a period of 90 days from the date of submission. The time for completion shall be agreed at the time of Tender Award. The scope of work shall include: 1. This part of the contract shall comprise the supply delivery, erection, testing, commissioning and setting to work of all electrical engineering installation works as detailed in these KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 41 of 270 PART II – SPECIAL CONDITIONS OF CONTRACT 42 specifications and the accompanying contract drawings. 2. The contractor shall include all apparatus and appliances not particularly called for in this specification or on the contract drawings but which are necessary for completion and satisfactory function of the contract works. No claim for extra payment shall be entertained from the contractor due to his failure to adhere to the above requirement. 10 26.3 Earlier Completion Currency of Payments Sufficiency of Contract Prices, Materials, Labour, Programme etc There will be no extra sum paid for partial or full completion earlier than the stated Time for Completion. Shall be Kenya Shillings or US Dollars. 11 - 12 - 13 - Bribery Any commission, advantage, gift, gratuity, reward or bribe given, promised or offered by or on behalf of the contractor or his agent or servant or any other person on his or their behalf to any officer, servant, representative or agent of the Employer shall be in addition to any criminal liability which may be thereby incurred subject to the Contractor to the cancellation of this and all other contracts which he may have entered into with the Employer of any loss or damage resulting from such cancellation The Employer shall be entitled upon a certificate in writing of the Engineer to deduct the amounts so certified from any monies otherwise due to the Contractor recover the said amounts as a debt due or partly the one and partly the other as the Employer shall deem advisable. 14 - First Facilities Aid a) The Contractor shall be deemed to have obtained all necessary information as to the conditions of working at the site in KENYA PORTS AUTHORITY and have obtained all necessary information on all matters and things that may in any way influence them in making his Tender and completing the Schedules and to have satisfied himself as to the risks, obligations and responsibilities to be undertaken in entering into the Contract. b) The Contractor is deemed to have inquired into and satisfied himself as the sources of supply, the sufficiency of and the means of obtaining and transporting all plant, materials, labour, fuel, water, electricity and other things required for or in connection with the work and to have considered all matters as possible contingencies affecting the execution and completion of the work The Contractor shall provide and maintain on the Site adequate and easily accessible first aid facilities for treatment of all personnel and work-people in case of accidents during the execution of the works under the Contract and such equipment as may be required in any relevant laws and regulations for the time being in force. The places where these items are kept shall be prominently marked. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 42 of 270 PART II – SPECIAL CONDITIONS OF CONTRACT 15 - Fire Prevention and Fire Fighting 16 - Regulations and site Discipline 17 - Register Employees 18 - Disorderly Conduct etc 19 - Consent Authorities 20 - Declaration Against Waiver of 43 A sufficient number of the Contractor’s employees shall be fully qualified in first aid so that a person so qualified is immediately available in case of accident at any time and at any place and the persons so designated shall be made known to all employees by the posting of their names and designation in a prominent position on the Site. Any order from the engineer as to extensions of or alterations to such first aid facilities or services shall be promptly carried out. The Contractor shall provide, maintain and at all times carry a suitable first aid kit in each of his supervisory transport vehicles. The Contractor shall take necessary precautions to prevent any damage due to fire. The precautions shall include but not limited to the installation and maintenance of fire extinguishers in key positions in or near the buildings. Such arrangements shall be subject to the approval of the appropriate fire service officer. The Contractor shall obey all Government of Kenya, Local authority and Kenya Ports Authority regulations and all other regulations which may from time to time require his observance and he shall instruct his agents, servants and other employees to obey such regulations; the Contractor shall be responsible for keeping discipline of the Site. The Contractor shall keep on the site a detailed register in the form required by the Engineer of all persons employed upon the Works, including Sub-contractors and their employees, containing the names, usual and temporary address, trade and rate of pay of each such person. The register shall be available for inspection by the Engineer whenever required. The Contractor shall at all times take all reasonable precautions to prevent any unlawful riotous or disorderly conduct by or amongst his employees and for the preservation of peace and protection of persons and property in the neighbourhood of the Works against the same and shall not interfere with members of any authorized Police Force who shall have free and undisputed access at all times to any part of the Works in the performance of their duties. by The contractor shall obtain and fill in all notices and forms required by the Authorities and shall obtain all consents where necessary for the various works being executed and shall pay all fees in connection therewith. The condonation by the Employer of any breach or breaches by the contractor or an authorized SubContractor of any of the stipulations and conditions contained in the Contract shall in no way prejudice, or effect or be construed as a waiver of the Employer’s rights, powers and remedies under the Contract in respect of any breach or breaches aforesaid. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 43 of 270 44 SECTION V: TECHNICAL SPECIFICATIONS SECTION V: TECHNICAL SPECIFICATIONS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 44 of 270 45 SECTION V: TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS FOR 132KV SWITCHGEAR, CONTROL, PROTECTION AND COMMUNICATIONS EQUIPMENT SCOPE OF WORKS: This specification covers: The manufacturing, supplying, testing before shipment, painting, packing for transport, insuring, shipping, delivering to the Port of Mombasa Kenya, landing, customs clearing, transporting from the port to the site, erecting, constructing, installing, site testing and commissioning of the plant as generally described below. Training of KPA personnel so as to equip them with the necessary knowledge for the operation and maintenance of the equipment after installation, and handing over. The proposed substation will be at the Port of Mombasa, adjacent to Substation M and the tee-off will be at Kipevu power generation plant. NB: It is to be noted that these technical specifications and attached drawings are provided as a guideline for the tenderers to be able to quote for the supply of equipment and services necessary to achieve a working substation that meets the specified requirement. Tenderers are expected to perform detailed calculations to arrive at equipment specifications provide detailed designs based on these specifications and to ascertain that equipment supplied will meet the performance requirements as indicated in these specifications. Additionally, they are expected to include any other items not listed in these specifications, but which in their opinion, is necessary to complete the installation and enable the equipment to work successfully and meet these technical specifications. It is the responsibility of the contractor to provide proper designs, materials, workmanship and all the accessories necessary for the proper execution of the project. The works will include but not limited to the following: Tee off at Kipevu Establish a tee-off substation at Kipevu with a) Nine (9 No.) 132 kV cable sealing ends. Two sets (6 No.) 132 kV surge diverters Two (2 No.) 132 kV Air break switches One (1 No.) 132 kV circuit breaker One set (3 No.) 132 kV current transformers. Cabling : One Lot Structures and Civil Works including cable trenches, drainage and landscaping. b) Laying approximately 1.5 km of 3 No. 132 kV S/C copper cables in 400mm 2 from Hilltop substation to KPA HQ site as indicated in the drawings. This will involve: Excavation of cables trench along the trace line Laying the 132kV single core cables plus terminations at both ends Reinstatement of trenches after laying of cable and bottom sand layer. Laying of approximately 1.5 km 48 strand fibre optic cable. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 45 of 270 46 SECTION V: TECHNICAL SPECIFICATIONS KPA Substation at the Port Establish a 132V Substation at Mombasa Port with 1.1 Four (4No.) 132kV circuit breakers- one gang-operated mechanism Three (3No.) 132kV line isolator assembly with an integral earth switch Three (3No.) 132kV isolators(without integral earth switch) Three sets (9 No.) of 132kV current transformers One sets (3No.) of 132kV Line surge arrester One set (3No.) 132kV Capacitive Voltage Transformer Two sets (6No.) of 132kV transformer surge arresters Two sets (3No.) of 11kV transformer surge arresters 2x 15MVA , 132/11kV Transformer Busbar protection panel with high impedance differential numeric relay Line differential protection using OPGW Line distance protection relays (132kV line) Line back up protection, over current & earth fault, over voltage (132 kV line). Line metering cubicle with meters of Cl. 0.2 accuracy (for 1 incomer 132kV line). 1x 200kVA, 11/0.433 kV substation transformer, on the 11kV busbar. Substation and equipment earthing – one lot Cabling : One Lot Structures and Civil Works including cable trenches, drainage and landscaping –One Lot Substation Illumination System- One Lot One Lot of 132kV bus bar materials Safety Appliances Build a new control building of an approved design as given in drawing with a floor area of at least 384m². Provide medium voltage cable of appropriate capacity to link the new substation to existing substation M DETAILED DESCRIPTION KPA 132/11kV SUBSTATION (1) Protection and control The following equipment shall be provided and installed for the purposes of protection, control and monitoring. Line differential protection using OPGW as first main Overcurrent relays as backup protection and independent of the distance relay. Busbar protection covering the 132 kV bays. Annunciator relay (with audible alarm) Transformer differential protection relay Transformer LV overcurrent (independent) Transformer HV overcurrent ( independent) Transformer LV restricted earth fault Transformer tap changer regulating relay(tap changer panel) (2) 132kV protection panel Two 132kV protection panels shall include but not limited to: Line differential protection Overcurrent Other accessories to ensure full protection functionality The other panels shall include Overvoltage Other accessories to ensure full protection functionality (3) 132 kV Metering and control equipment panel. This shall accommodate the controls for 132kV lines, the transformer circuit breaker controls, mimic diagram (with approved colour codes) and shall also incorporate the following but not limited to: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 46 of 270 47 SECTION V: TECHNICAL SPECIFICATIONS Substation control unit Line annunciator relay 1 Ammeter per phase MW and MVAR Meters Energy meter Trip/close control switch Circuit Breaker ON/OFF indication Voltage meter with selector switch. Transducer for MW and MVAR to be interfaced with SCADA. Other accessories to ensure full functionality (4) 132 kV Circuit Breaker Panels The circuit breaker panel shall include but not limited to: Breaker fail protection relay Pole discrepancy Trip circuit supervision (both trip coils) Tripping relay with visible flag Annunciation relay for breaker functions(gas pressure alarm, block, breaker fail, pole discrepancy, dc supply failure) Other accessories to ensure full protection functionality (5) Transformer protection panel Each transformer protection panel shall include but not limited to: Transformer differential Restricted earth fault HV overcurrent Annunciation relay and transformer function Master Trip relay LV trip relay Other accessories to ensure full protection functionality (6) Tap-changer panel Each transformer tap-changer panel shall include but not limited to: Voltage regulation relay Selector switch Auto on/off Manual switch raise/lower Tap-changer function Local /remote Other accessories to ensure full functionality (7) Battery One set of 110 V dc battery and battery charger shall be provided. One set of 48V dc battery and battery charger shall be provided (8) Communications and Scada Fibre optic STM-1 terminal equipment to transmit voice and data to the KPLC Regional control centre at Kipevu. The OLTE shall be equipped with a fast Ethernet port capable of handling at least 10 Mb/s. SCADA data shall be collected and transmitted to the RCC via IEC 60870-5-104 protocol. The contractor shall parameterise offered substation control/RTU to operate seamlessly with existing KPLC system. (9) i.) Control building The new control building shall be of an approved design as given in drawing and shall accommodate the new equipment. It shall house: KPLC metering room housing 132kV Control Panel and KPLC communication centre. 11kV Switchgear and controls (see 11 kV switchgear specifications) 132kV Circuit breaker controls and protection relay panels room Battery room KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 47 of 270 48 SECTION V: TECHNICAL SPECIFICATIONS Battery chargers and distribution boards SCADA and Communication equipment for KPA A washroom, WC, Urinal and Hand Wash Basin Equipment/utility store 2 GENERAL SPECIFICATIONS 2.1 ELECTRICAL CONTROLS AND AUXILIARIES a) Responsibility for electrical control and auxiliaries. The contractor shall provide all control, indication, alarm and protection devices and all auxiliary equipment with wiring and interconnecting cable which are integral parts of or are directly associated with or mounted on the equipment to be supplied under this contract. b) Operation and control. The operations, control procedures, monitoring and protective devices for the plants are described in Equipment Technical Specifications. The Contractor shall take all measures and furnish all requirements necessary for effecting the intended method of operation and control. The station functional control shall be possible in a hierarchic structure as follows: Supervisory Control from a Supervisory Control and Data Acquisition (SCADA) System. This will be connected to KPA Local Control Centre at the Port and to the KPLC Regional Control Centre (RCC) at Kipevu. 132kV equipment at the station shall also be under direct Supervisory Control from the RCC at Kipevu whereas the MV line breakers shall be controlled from the LCC at the Port. Indications shall be available both at LCC and RCC. Local Control from the local relay and protection panels or from the instrument sections on MV switchboards. Direct Control/Emergency Control from the apparatus itself. The stations shall function without interruptions even if connection to higher levels fails. A local/remote switch shall be accommodated on each control position blocking remote operation but not indication. The position of this switch shall be indicated in the higher levels of operation. The control shall include operation of all circuit breakers and motorised disconnectors. Status indication shall be available in the supervisory system for all HV and MV breakers in the system as well as busbar voltages, line and transformer load in MVA (plus MW and MVAr for the 132 kV. For on-load tap changers position indication and raising/lowering of the tap changer position shall be possible supervisory and remotely. Direct control of all station switchgear at the respective switchyards/panels shall be possible. Interlocking devices and automatic change-over systems shall be incorporated in the control circuits in the quantity needed to guarantee non-interruption and correct sequence of operation of the equipment. Protective devices shall be supplied in accordance with the Particular Technical Specifications, and the particular needs of such equipment furnished with the aim of ensuring a safe and reliable operation of the plants in the event of electrical and mechanical disturbances or in case of mal-operation by the plant personnel shall be taken into consideration. The signals and command to be transmitted are given in Particular Technical Specifications. All equipment, instruments and devices in the substation necessary for supervisory, remote and local control as well as for protection, signalling and indication shall be included in the Bid and hence the Contract, it being understood so that the enumeration found in Scope of Works, in this respect is indicative but not limiting. Interlocking devices shall be incorporated in the control circuit to ensure proper sequence and correct operation of the equipment (breaker, isolator and earth switch). KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 48 of 270 49 SECTION V: TECHNICAL SPECIFICATIONS 2.2 DESIGN DATA FOR LOW VOLTAGE EQUIPMENT Low voltage installation shall be in accordance with EMC directives. The rating and design criteria for low voltage equipment shall be as follows: 2.2.1 AC system 1 2 3 4 5 6 7 8 9 Parameter Rated voltage between phase Rated voltage between phase to earth Grounding system Frequency Voltage variation Frequency variation Power frequency Test Voltage Thermal rating of conductors Max short-circuit Current Value 415V 3ph 4wire 240V PME 50hz +/-6% +/-5% 1 min 3 kV 120 % of load 31.5 kA The three-phase supply shall be used for power circuit and the single-phase supply for lighting, indication, motor controls and similar small power circuits. The single phase supply within, cubicles and panels shall be transformed down to 110 Volt AC if necessary. Unless otherwise specified, the equipment provided under this contract is to be capable of reliable operation at voltages as low as 85% of the rated voltage, and to withstand continuously up to 110% supply voltage above the rated value of 240V or 415V AC. AC LV equipment can, after the Principal Electrical Engineer’s approval, be rated for lower short circuit current if calculation demonstrates that lower values are applicable at the place of installation. DC equipment shall be adapted to the actual values at sites as shown in calculations. 2.2.2 DC system 1 2 3 4 Parameter Rated voltage between phase Voltage variation Thermal rating of conductors Max short-circuit Current Value 110V DC- 2 wire +/-6% 120 % of load 31.5 kA DC equipment shall be adapted to the actual values at sites as shown in calculations. The 110Volt, 2-wire will be used for essential controls indication, alarm, protection relays, emergency lighting, circuit breaker tripping and closing circuit. All equipment and apparatus except the electrical protective relays and electronic equipment shall be capable of satisfactory operation at 80% to 125% of the rated supply voltage. The electrical protective relays and electronic equipment shall be capable of satisfactory operation of 85% to 120% of the rated supply voltage. All devices on DC operating circuit for the circuit breakers shall also be capable of satisfactory operation even at 130% of the rated working voltage, considering equalizing charge of storage battery. DC loads to be supplied from battery and/or battery charger shall be calculated by the contractor and lists of those loads shall be submitted. The rating of the Station Auxiliary DC supply will be such that the station DC supply controlled operations will function normally for at least 10 hours following the loss of Auxiliary AC supply to the Battery Charger. 2.2.3 230 V AC Un-interrupted supply (UPS) If specified DC/AC UPS shall supply dedicated computer and measuring equipment. The supply shall be 230 V – IT. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 49 of 270 50 SECTION V: TECHNICAL SPECIFICATIONS 2.3 MOTORS 2.3.1 General As far as possible and if nothing else is specified, motors shall be three phase squirrel cage motors complying with IEC 60034 and with dimensions according to IEC 60072. Such motors shall have the following data: Parameter Value 1 Continuous rating 130 % of mechanical load 2 Frequency band for continuous rated 47 – 57 Hz operation without exceeding temperature class 3 Voltage band for continuous rated -15 % - +10 % operation without exceeding temperature class 4 Maximum start current with direct start:(a) Motors above 75 kW 5 x In (b) Motors between 35 and 75 kW 6x In 5 Insulation class F 6 Temperature rise B 7 Direct starting range 75 – 110 % of Un Motors shall have sealed ball or roller bearings. If the bearing is not sealed for life it shall withstand two years of operation before refill of lubricants. Outdoor motors and motors erected in moist environment shall be equipped with stillstand heaters controlled from the starter. The heater shall be so dimensioned that maximum temperature is not reached even if the heater remains connected under operation. Motors shall withstand three consequent starts without overheating. Motors over 20 kW shall be equipped with thermistor based temperature protection. The three line connections of AC motors shall be brought out to a terminal box sealed from the motor. The terminal arrangement shall be suitable for the reception of aluminium and copper cable. A permanently attached diagram or instruction sheet shall be provided giving the connections for the required direction of rotation. If only one direction of rotation is permitted, this shall be clearly marked. Motors to be connected to variable speed drives shall be specially adapted to this. 2.3.2 Special Motors Other types of motors shall only be used where squirrel cage motors are inconvenient to use (and even then only after approval by the Principal Electrical Engineer) or if DC motors are specified. Such motors shall as far as possible follow the requirements set above. Brushes shall be designed with a constant brush pressure and shall withstand at least 5000 hours of operation before they have to be replaced. It shall always be at least two brushes in parallel and the brush-holders shall not touch the commutators when the brushes wear out. The press fingers shall not carry the current and each brush shall be separately adjustable. Where single phase motors are used the motors shall be grouped so as to form, approximately, a balanced three phase load. 2.3.3 Motor control gear Control gear shall comply with the requirements of IEC 60947, the control gear being rated according to the duty imposed by the particular application. No replacement of equipment shall be necessary after short circuit (ref. IEC 60947) Motor contactors shall comply with IEC 60947 class of intermittent duty 0-3 and utilisation category AC4. The contactors and their associated apparatus shall be capable of switching the stalled current, and shall have a continuous current rating of at least 50% greater than the full load current of the motors they control. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 50 of 270 51 SECTION V: TECHNICAL SPECIFICATIONS The operating currents of overload trips fitted to motor contactors shall be substantially independent of ambient temperature conditions, including the effect of direct sunlight on the enclosure in which the contactors are installed. Where small motors are connected in groups, the group protection shall be arranged so that it will operate satisfactorily in the event of a fault occurring on a single motor. Each motor or group of motors shall be provided with control gear for starting and stopping by hand and automatically. Overload and single-phasing protection shall be provided. Facilities for padlocking the supply in off position shall be provided. 2.4 COMPUTER BASED CONTROLLERS Computer Based Controllers inclusive Programmable Logical Controllers (PLC) can be used for individual control functions. Such equipment shall be designed for industrial environment and application in high voltage plants. The control equipment must be fed from the general station DC supply. The control equipment must be equipped with internal “watchdog” function giving external potential free alarm by internal fault. The operational status shall be frozen by fault or un-normal function so it can be re-established after restart. The process must be shut down to a safe stage if fatal faults occur in the controller. Analogue and digital in- and out puts must be galvanic isolated and potential free and must, together with the enclosure, screen against disturbance from electromagnetic field occurring by short-circuit, switching over voltages or lightning discharges. The control equipment shall be tested according IEC 60255 and fulfil relevant EMC requirements for Industrial Environment. Digital in- and outputs shall be tested and approved for switching of DC voltages supplied by the main plant battery (AC values are irrelevant). Programmes shall be stored in “flash ram” or similar storage medium and shall not be destroyed or changed by power failure (i.e. Separate backup battery shall not be used). The memory shall contain the last program version. All programming of control sequences shall be documented in a self-explanatory way not requiring special program knowledge for understanding (function block programming or similar) Communication between various controllers (and the main control system) can be over fibre optical cable provided agreement between the contractors. Such communication must use open protocols to be approved by the Principal Electrical Engineer (P.E.E). The Bidder shall in any case present a verification of transmission quality. The Controllers shall be delivered with software and software licences needed for testing, setting and reconfiguration. If hardware other than laptop is required for this such shall be included in the supply. 2.5 DESIGN DATA FOR HIGH VOLTAGE EQUIPMENT The rating and design criteria for the HV and MV plant and equipment shall be as follows:Item Parameters SYSTEM PARAMETER 132 kV 11kV 1 System description 50 Hz, 3 phase, 50 Hz, 3 3 wire phase, 3 wire 2 Neutral point earthing Solid earthed Solid earthed 3 Nominal voltage of networks 132 kV 11 kV 4 Highest system voltage as defined by IEC145 kV 12 kV 60038 *1 5 Short circuit and earth fault current, 31.5 kA 31.5 kA symmetrical r.m.s value (main breaking current) not less than *2 6 Thermal short-circuit current, not less 31.5 kA 31.5kA than 1 second 7 Dynamic peak current (min making 80 kA 78 kA current) not less than 8 Rated current of busbars and bus coupler 2,000 A 1500 A if not given in Scope of Works, for each KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 51 of 270 52 SECTION V: TECHNICAL SPECIFICATIONS 9 10 10(a) 10(b) 10(c) 11 11(a) 11(b) 11(c) 11(d) 11(e) 12 13 14 15 individual substation. Minimum rated current of isolating 1,250 A 630A switches and circuit breakers if not given in Scope of Works Insulation level according IEC 60071: *3 Switching surge withstand voltage Phase-to-earth N/A N/A Longitudinal impulse component of N/A N/A combined test Lighting impulse withstand voltage (1.2/50 650 kV 95 kV µs K peak) Test voltage at power frequency 1 min dry 275 kV 38 kV and wet. To earth and between phases. For the design and erection of the conductors in the switchyard the following minimum clearances shall be observed. Phase to earth [mm] 1270 300 Phase to phase [mm] 1475 250 3000 *1 Bus bars phase to phase [mm] 1400 Height to live parts above ground [mm] 5000 2900 Lowest part of insulators above ground 3500 2500 [mm] Maximum temperature rise of conductors 400C 400C above ambient temperature (400C) Maximum wind pressure on conductors 430 N/m2 430 N/m2 and cylindrical objects Maximum wind pressure on flat surfaces 820 N/m2 820 N/m2 Minimum nominal creepage distance as defined in IEC 60815 Table II 25mm kV 25mm/ kV Note *1) Ref IEC 60038) Note *2) For all current carrying parts the permissible short circuit duration shall be at least 1 second. Indoor equipment shall be arc tested in accordance with IEC 60298 amendment 2. The dynamic or momentary short circuit current on which the equipment design shall be based shall be computed by multiplying the r.m.s value of the symmetrical short circuit current by the factor 1.8 x 2^0.5 Note *3) Ref IEC 60071) 2.6 CLIMATIC CONDITIONS Unless otherwise specifically stated in Equipment Technical Specifications or Scope of Works, any equipment, component and assembly shall be designed for the following service conditions: Parameter Ambient air temperature Outdoor Indoor 24 hour average maximum Ambient temperature for cables in the ground Max Min +40°C +40°C +30°C +40 °C -1°C -1°C -1°C -1°C Relative humidity 90% 65% Height above sea level 90% 100 m Cooling water temperature N/A 65% Below 1100m N/A KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 52 of 270 53 SECTION V: TECHNICAL SPECIFICATIONS EMC Class (IEC 61000) Industrial environments Seismic coefficient Wind pressure on project area of conductors and cylindrical objects , N/m² Maximum wind pressure on steel members on 1.5 times projected area 0.16 430 Rainfall conditions Average, mm/year Maximum, mm in 24 Hrs Annual mean isokeraunic level Environmental Pollution Maximum Wind Velocity 383 820 N/m² 1500-2500 160 Max 180 days Medium to High 120 km/hr (33.3 m/s) Wherever any of these maximum or 24 hour average temperatures exceed the normal service condition temperatures of the IEC Recommendations for the relevant equipment, or of such other standard which is approved to be applied, the permissible temperature rises of the IEC Recommendations or the standard shall be reduced by the same amount as the difference between the above figures and the normal service condition temperatures. The Contractor shall guarantee these reduced temperature rises. All air cooled equipment shall be cooled with convection (i.e. without fans) provided other cooling methods are not explicitly allowed for in the specifications. 2.7 SEISMIC COEFFICIENT The seismic coefficient shall be taken as 0.16 2.8 TROPICALIZATION In choosing materials and their finishes, due regard shall be given to the humid tropical conditions under which the plant will be called upon to work. The contractor shall submit details of his usual practice which have proven satisfactory and which he recommends for application to the parts of the work, which may be affected by tropical conditions. The materials and finishes used shall be approved by the Employer. All switchgear and control cubicles shall also be rodent and vermin proof. 2.9 EARTHING The earthing grid comprising earthing bus and stub under the outdoor switchgear and the control building shall be installed by the contractor. The depth shall be 600mm. wiring for earthing and connections from the equipment, including for all ancillary equipment, control boards, steel structures, etc shall be installed under this contract. Conductor size used for main earthing network will be 95mm² copper. Main equipment shall be connected with 95mm² copper wire. Auxiliary equipment shall be connected with at least 35mm² copper wire main to main earthing network. 2.10 UNIT OF MEASUREMENT AND LANGUAGE In all correspondence, in all technical schedules and on all drawings prepared by the Contractor, the metric units of measurement shall be used. On drawings or printed pamphlets where other units have been used, the equivalent metric measurements shall be added. All documents, correspondence, drawings, reports, schedules instructions, and nameplate readings of the equipment shall be in the language stated in the Bid Data sheet. 2.11 WORKING STRESS AND DESIGN (1) General The design, dimensions and materials of all parts shall be such that they will not suffer damage under the most adverse conditions nor result in deflections and vibrations, which KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 53 of 270 54 SECTION V: TECHNICAL SPECIFICATIONS might adversely affect the operation of the equipment. Mechanisms shall be constructed to avoid sticking due to rust or corrosion. The equipment and apparatus shall be designed and manufactured in the best and most substantial and workmanlike manner with materials best suited to their respective purpose and generally in accordance with up-to-date recognized standards of good practice. All parts which will or might have to be dismantled for the purpose of serving or replacement shall be assembled with anti-corrosive fasteners. The type, material and size of all fasteners shall be selected to safely withstand the maximum superimposed direct, alternating, kinetic and all loads induced by workmen when installing or removing the fasteners during the life of the equipment. Suitable structural steel bases or frames shall be provided where necessary to transmit to the concrete foundations all loads imposed by the various parts of the equipment. Such bases or frames shall be supplied complete with suitable anchor bolts and shall be so proportioned that the bearing loads imposed on the concrete foundations will not exceed 50 Kg per square centimetre. The equipment should be designed to cope with 0.16 G acceleration of seismology on the centres of gravity. Whenever possible, all similar parts, including spare parts, shall be made interchangeable. Such parts shall be of the same materials and workmanship and shall be constructed to such tolerances as to enable substitution or replacement by spare parts easily and quickly. All equipment shall be designed to minimize the risk of fire and consequential damage, to prevent ingress of vermin, dust and dirt, and accidental contact with electrically energized or moving parts. The plant shall be capable of continuous operation with minimum attention and maintenance in the exceptionally severe conditions likely to be obtained in a tropical climate. Upon request by the Employer complete information regarding the design assumptions, loading and operating conditions, deflections and unit stresses used in the design shall be provided by the Contractor. The Contractor shall be deemed to have examined the specification and drawings herewith, and unless stated specifically to the contrary in the schedule of proposed conditions and /or deviations from the specification to have concurred with the design and layout of the applicable project features as being sufficient to insure reliability and safety in operation, freedom from undue stresses, adequate drainage and other essentials for a satisfactory working plant. (2) Strength and quality All steel castings and weldings and all site weldings shall be stress-relieved by heat treatment before machining, and castings shall be stress-relieved again after repair by welding. Liberal factors of safety shall be used throughout, especially in the design of all parts subject to alternating stresses or shocks. 2.12 MATERIALS AND WORKMANSHIP Materials shall be new; the best of their respective kinds and such as are usual and suitable for work of like character. All materials shall comply with the latest issues of the specified standard unless otherwise specified or permitted by the Employer. Workmanship shall be of the highest class throughout to ensure reliable and vibrationOperations. The design, dimensions and materials of all parts shall be such that the stresses to which they may be subjected shall not cause distortion, undue wear, or damage under the most severe conditions encountered in service. All parts shall conform to the dimensions shown on and shall be built in accordance with approved drawings. All joints, datum surfaces and meeting components shall be machined and all castings shall be spot faced for nuts. All machined finished shall be shown on the drawings. All screw, KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 54 of 270 55 SECTION V: TECHNICAL SPECIFICATIONS bolts, studs and nuts and threads for pipe shall conform to the latest standards of the International Organization for Standardization covering these components and shall all conform to the standards for metric sizes. The Contractor shall never incorporate any standards or size system by his own account, regardless of that accepted and incorporated in this Contract. All materials and works that have cracks, flaws or other defects or inferior workmanship will be rejected by the Employer. All defective materials shall be promptly removed from the site by the Contractor, and inferior workmanship shall be cut out and replaced. (1) Standard Specifications The design, materials, manufacture, testing, inspection and performance shall, unless otherwise specified in the Special requirements of these Specifications, conform to the authorized standards of the International Electrotechnical Commission (IEC) or equivalent national standards. The Contractor shall include a statement of the standards, intended to be used. (2) Assembly Necessary items of equipment shall be assembled in the factory prior to shipment and type tests shall be performed by the contractor as may be required to demonstrate to the satisfaction of the Employer the adequacy of equipment and its component parts. All tests should simulate normal operating conditions as closely as possible. All dismantled parts shall be properly match marked and doweled to ensure correct assembly in the field. (3) Casting Casting shall be true to pattern, of workmanlike finish and of uniform quality and condition, free from blowholes, porosity, hard spots, shrinkage defects, cracks or other injurious defects, shall be satisfactorily cleaned for their intended purpose. Major defect on castings shall not be repaired, plugged, or welded without permission of the Employer. Such permission will be given only when the defects are small and do not adversely affect the Strength, use or merchantability of the castings. The Contractor will give the distinction between major and minor defects. Excessive segregation of impurities or alloys at critical points in a casting will be a cause for its rejection. The largest fillets compatible with the design shall be incorporated wherever a change in section occurs. All castings shall be stress-relieved before machining and again after repair by welding. Plates to be joined by welding shall be accurately cut to size and rolled by pressure to the proper curvature, which shall be continuous from the edges. Flattening in the curvature along the edges with correction by blows will not be allowed. The dimensions and shape of the edges to be jointed shall be such as to allow thorough fusion and complete penetration, and the edges of plates shall be properly formed to accommodate the various welding conditions. (4) Forging The ingots from which the forgings are made shall be cast in metal moulds. The workmanship shall be first-class in every respect and the forgings shall be free from all defects affecting their strength and durability, including seams, pipes, flaws, cracks, scales, fins, porosity, hard spots, excessive non-metallic inclusions and segregations. The largest fillets compatible with the design shall be incorporated wherever a change in section occurs. All finished surfaces of forgings shall be smooth and free from tool marks. The forging shall be clearly stamped with the heat number in such locations to be readily observed when the forging is assembled in a completed unit. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 55 of 270 56 SECTION V: TECHNICAL SPECIFICATIONS (5) Welding Wherever welding is specified or permitted, a welding process, including stress relieve treatment as required if necessary, conforming to an appropriate and widely recognized professional standard shall be used. All welders and welding operators shall be fully qualified by such a standard. After the welding process has been approved by the Employer, the Contractor shall record it on a special drawing, which shall thereupon become one of the drawings of the Contract. Radiograph inspection shall be carried out by the Contractor when required by the standards, Specifications, or the design criteria employed. All welds which, in the opinion of the Employer, may be subject to the full stress induced in the adjacent plate, or which in the opinion of the Employer, do not appear to conform to the welding standard shall be radiographed when required. All defects in welds shall be chipped out to sound metal and such areas shall be magnetically or ultrasonically tested to ensure that the defect has been completely removed before repair welding. Plates to be joined by welding shall be accurately cut to size and rolled by pressure to the proper curvature, which shall be continuous from the edge. Flattening in the curvature along the edges with correction by blows will not be allowed. The dimensions and shape of the edges to be jointed shall be such as to allow through fusion and complete penetration, and the edges of plates shall be properly formed to accommodate the various welding conditions. The surfaces of the plates adjacent to the edges to be welded shall be thoroughly cleaned of all rust, grease and scale to bright metal. All important weldings shall be stress-relieved by heat treatment before machining. (6) Galvanizing Unless specifically mentioned to the contrary, iron and steel shall be galvanized in the factory after fabrication. The zinc coating shall be uniform, clean, smooth and as free from spangle as possible. Galvanizing shall be applied by the hot dip process for all parts other than steel wires. All steel wires shall be galvanized by a recognized trade standard. The minimum quantities of zinc coating shall be 350 gram/m2 for bolts and nuts and 550 gram/m2 for all other parts except steel wires, unless otherwise specified in the Contract Documents. The uniformity of zinc coating, tested by dipping surface shall not be exposed until the surface has been dipped four times for bolts and nuts, and six times for all parts. The preparation for galvanizing and the galvanizing itself shall not distort or adversely affect the mechanical properties of the materials. Special treatment during galvanizing to prevent the formation of “White rust” during shipment or storage is required. The Tenderer shall state in his Tender the treatment to be used. (7) Colour Standard Each item of equipment shall be painted in accordance with the Clause 3.7.21.The final colour of each item shall be decided by the employer after contract. (8) Nameplate To facilitate operation and maintenance it is very important that all equipment, valves, instruments, switches, pipeline, etc., shall be clearly identified by nameplates showing the function and proper use of each item. Such identification shall be in English and must be intelligently and carefully designed to minimize errors and to avoid mal-operation in operation or maintenance. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 56 of 270 57 SECTION V: TECHNICAL SPECIFICATIONS The nameplates shall be permanently legible, clearly worded, weather proof when outdoors and securely mounted in conspicuous and logical locations. A table showing materials, dimensions, location, mounting and wording shall be submitted to the Employer for approval. (9) Cabling and Wiring The conductor used in substation and switching station shall be continuous between outlets, and no junction shall be made except within outlets or junction boxes. The conductor shall be drawn through ducts or conduits after they have been cleaned. Oil or grease shall not be used as a lubricant for the drawing operation, but an approved compound may be used for this purpose. Joints in wiring shall be compressed and insulated with PVC tape or approved connectors may be used. (10) Conduits Rigid steel conduit shall be galvanized inside and outside, or enamelled inside.It shall be of a minimum thickness of 2.3mm and have a minimum inside diameter of 16mm. (11) Conduits Installation Conduits shall be concealed within the walls, ceilings and floors where possible. Exposed runs of conduit shall be supported within a space of not more than 150cm. It shall be installed perpendicular to walls, structural members and ceilings. Only threaded joints shall be used. Conduit, which were crushed or deformed, shall not be used in the works. Conduit shall be installed in such a manner as to ensure that the inside remains in a dry condition. Conduit shall be securely fastened to all sheet-steel outlets, junction and pull boxes with galvanized locknuts and bushings. Exposed conduits shall be finished with the same colour paints as the finished colour of the wall or ceiling against which the conduits are placed. All joints and terminations shall comply with the weatherproof or explosion proof requirements as applicable. 2.13 (1) BASIC REQUIREMENTS FOR ELECTRICAL EQUIPMENT Corona and radio interference Switchgear shall electrically be designed to avoid local corona formation and discharge likely to cause radio interference, and shall be designed to mechanically endure shortcircuit current without thermal and mechanical failure for one (1) second. The design of all line conductor fittings, vibration dampers, insulator fittings, etc. shall avoid sharp corners or projections which would produce high electrical stress in normal operation. The design of adjacent metal parts and melting surfaces shall be such as to prevent corrosion of the contact surfaces and to maintain good electrical contact under service conditions. Particular care shall be taken during manufacture of conductors and fittings and during subsequent handling to ensure smooth surface free from abrasion. (2) Insulators and Fittings All porcelain insulators and bushings for outdoor equipment shall be brown grazed. The resin insulators for indoor equipment may be of the inherent colour of the resin. All fittings shall be malleable iron hot-dipped galvanized alloy. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 57 of 270 58 SECTION V: TECHNICAL SPECIFICATIONS All the insulators and bushings shall have impressed thereon, before firing the glaze, the name, initial or trade mark of the manufacturer, the year of manufacture and the mechanical strength. (3) Enclosure The enclosures for switchgear, control and relaying equipment shall be dead-front, floorstanding or wall-mounting, rigid welded steel frames, completely enclosed by metal sheets and suitable for indoor or outdoor installation. The completed sections shall have provisions for lifting and ample strength to withstand all stresses incidental to shipping, installation and operation without distortion or other damage. The floor-standing type enclosure shall be bolted at the bottom to suitable steel channel and shall be of vermin-proof construction. Suitable terminal blocks shall be provided for all outgoing power and control cables. All cable terminals shall generally be located for bottom entry and connections. The enclosure shall be painted in conformity with the requirements specified in Clause 3.7.21. The degree of protection of the enclosures shall be IP 41 for indoor switchgear, IP 54 for outdoor switchgear and IP 51 for indoor control and relaying equipment conforming to IEC 529 and IEC 144. Interior illumination lamps operated by door switches shall be provided for each enclosure as much as applicable. At least one 240V convenience outlet of Kenya use shall be provided for each enclosure at convenient location. Space heaters for 240-volt A.C. shall be provided inside the enclosures to prevent moisture condensation. A manual switch to control the heaters shall be provided in the enclosures. (4) Measuring Instruments All measuring instruments shall be of flush-mounted, back-connected, dust-proof and heavy-duty switchboard type. Each measuring instrument shall have a removable cover, either transparent or with a transparent window. Each instrument shall be suitable for operation with the instrument transformers shown on the drawing under both normal and short-circuit conditions. For analog type instruments, scale plates shall be of a permanent white circular or rectangular finish with black pointer and markings. The scale range shall be determined from the current transformer and voltage transformer ratios. All measuring instruments of analog type shall be approximately 110mm² enclosures and shall be provided with clearly readable long scale, approximately 240 degrees. The maximum error shall be not more than one and a half (1.5) percent of full-scale range. (5) Indicating Lamp Assemblies Indicating lamp assemblies for the enclosures shall be of the switchboard type, insulated for 110-volt D.C. service, with appropriately coloured lens and integrally mounted resistors for 110-volt service. The lens shall be made of a material, which will not be softened by the heat from the lamps. Red indicating lamps shall be used for “ON” position and green lamps for “OFF” position. (6) Nameplates and Escutcheon Plates Each cubicle, panel, meter, switch and device shall be provided with a nameplate or escutcheon plate for identification. Each equipment shall be provided with a rating plate containing the necessary information specified in the relevant IEC standards. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 58 of 270 59 SECTION V: TECHNICAL SPECIFICATIONS The plates shall be made of weatherproof and corrosion-proof materials and shall not be deformed under the service conditions at the site. The entries on the plates shall be indelibly marked by engraving to black letter on a white background. The language of all plates shall be English. (7) Wiring (a) General All wiring inside the switchboards shall be done with PVC insulated wire, not less than 2.5mm2 except for electronic devices. A suitable wiring duct system shall be installed for all inter-panel and front-to-rear panel wiring which will provide easy access for inspection and replacement. As far as possible all wiring shall be installed in wiring ducts. All wiring from hinged door panels to the fixed panels shall be done with flexible conductor of equivalent size. All multicore cables shall be steel armoured. Wiring between terminals of the various devices shall be point to point. Splices or tee connection will not be acceptable. Wire runs shall be neatly tucked or clamped. Exposed wiring shall be kept to a minimum, but where used shall be formed into compact groups suitably bound together and properly supported. Instrument transformer secondary circuits shall be grounded only at the first panel entered, and shall not be grounded at any point or outside of the enclosures. Cable supports and clamp type terminal lugs shall be provided for all incoming and outgoing power wiring terminated at each panel. All wire shall be marked near each terminal end with circuit or wire designation. These markers shall be of an approved type and permanently attached to the conductor insulation. (b) Phase arrangement The standard phase arrangement when facing the front of the panel shall be R-S-T-N, and R-N-S from the left to right, from top to bottom, and front to back for A.C three-phase and single-phase circuits and N-P from left to right, P-N from top to bottom and front to back for D.C polarity. All relays, instruments, other devices, buses and equipment involving three-phase circuit shall be arranged and connected in accordance with the standard phase arrangement where possible. (c) Wiring colour code All wires shall have ferrules at all terminations to distinguish each terminal. (d) Phase and polarity colour code Following coloured ferrules shall be provided on each wire in order to identify phase and polarity. Phase and Polarity Colour A.C., three-phase, First phase Red Second phase Yellow Third phase Blue A.C., single-phase, First line Red Second line Yellow Neutral Black Grounded Green with yellow stripe Auxiliary Supply Positive Red Negative Black High and medium voltage versus control and measuring cables 800 mm Low voltage power cables versus control and measuring cables 400 mm Necessary EMC consideration shall be taken in accordance with EMC standards. Additionally, cables for extra low power, i.e. mA and mV circuits and cables connected to low power solid state electronic circuits, shall be laid in separate sheet steel trays with KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 59 of 270 60 SECTION V: TECHNICAL SPECIFICATIONS covers. The DC trip and AC voltage supplies and wiring to main protective gear shall be segregated from those for back-up protection to the greatest extent possible. Single-phase power cables shall be run in trefoil configuration, single-phase DC power cables shall be run in parallel. Special care shall be taken so that closed magnetic circuits do not form around single phase cables. Cables below 25 mm² cross section shall be copper. Larger cross sections may be aluminium. Minimum cross sections shall be as follows: Measuring cables for current 4.0 mm² Control and other measuring cables 2.5 mm² Power cables according 120 % max load current All cross section must be checked against max load current, allowable burden on measuring transformers, short circuit values, voltage drop, protection requirements and selectivity. The cables shall be marked with item designation in both ends as well as by entrances in enclosures. The cable marking shall be fire proof. Cables shall be laid in full runs and not spliced unless approved by Project Manager. Termination of multi-stranded conductor ends shall be with a suitable crimped thimble as specified above. All other cable lugs or similar shall be of crimped type adapted to the cable type and cross-section used. The tools used should be special approved for the lugs and cable type used. The cable supplier’s instructions regarding handling and bending radius shall be followed. Fibre optic cables shall not contain metallic material and be so laid that they have proper mechanical protection. I.e. cables not constructed for embedding shall be laid in protective tubes. 2.14 SAFETY PRECAUTIONS Prior to any of the work being energized, the Contractor shall be responsible for supplying and fixing in prominent positions near to each item of the work concerned, large temporary signs giving clear warning of danger in areas which might previously have been regard as safe. During erection and tests the Contractor shall provide all temporary scaffolding ladders, platforms with toe boards and handrails as required for safe and convenient access of workmen, inspectors and other authorized persons. All dangerous opening or holes shall be provided with handrails or covers. Measures shall be taken to protect workmen from falling. The maximum possible safety shall be afforded to personnel directly engaged on this Contract or to those who frequent the working area or to those who in the normal course of their occupation find it necessary to utilize temporary works erected by the Contractor. The Contractor shall demonstrate that he has facilities for conducting a safety programme commensurate with the works on the site. He shall submit in writing a proposed comprehensive safety programme to the Employer for approval prior to the start of construction operation on the site. The Contractor shall designate a competent supervisory employee to carry out his safety programme. 2.15 PROTECTION, CLEANING AND PAINTING (1) Embedded Steelwork All parts to ultimately be buried in concrete shall be cleaned and protected before leaving the manufacturer’s plant by cement wash or other approved method. Before being installed they shall be thoroughly desiccated and cleared of all rust and adherent matter, or be treated according to a method approved by the Employer. Such cleaning or treatment shall not detrimentally affect the strength or final operation and function of the equipment. (2) Steel exposed to atmosphere All machined parts or bearing surfaces shall be cleaned and protected from corrosion before leaving the manufacturer’s plant by the application of an approved rust preventive KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 60 of 270 61 SECTION V: TECHNICAL SPECIFICATIONS coating, or a peelable plastic film. Where the latter is impracticable, such parts shall be heavily covered with high melting point grease. After erection such parts shall be cleaned with solvent and lapped or polished bright. All parts, other than machined parts, which will be exposed after erection shall be thoroughly cleaned and galvanized or given with two coats of best quality approved primer and one coat of best quality approved finish paint before leaving the manufacturer’s plant and a further one coat of paint of an approved quality and colour after erection and touching up on the site, except such apparatus as panels and instruments which shall be finished painted under approved procedures. All outside panel surfaces shall be primed, filed where necessary, and given not less than two coats of synthetic undercoat. The finishing coat for the outdoor installations shall be gloss paint and for the indoor installations shall be a semi-gloss paint. The inside surface of the enclosures shall have two prime coats and one finishing coat of light cream colour. Primer shall be applied to surfaces prepared in accordance with the plant manufacturer’s instructions. The surface shall be wiped clean immediately prior to applying the paint. The primer and finish coats of paint shall be applied using the methods and equipment recommended by the manufacturer. The internal surface of all pipelines shall be cleaned out by the approved methods before installation and again prior to commissioning, to ensure freedom from dirt, rust, scale, welding slag, etc. All exposed pipes shall be painted with an identifying colour after erection is completed. The colour code system shall be approved by the Employer. All steel surfaces, which are in permanent contact with oil, shall be given three coats of approved oil resistant. No painting or protection is required for finished or unfinished stainless steel parts. The final colour of all equipment, frames for meters and relays, and switch handle shall be approved by the Employer but the Contractor shall propose a colour scheme for the equipment and devices and shall submit colour chips or paint samples. A colour chip shall be included with the approved colour schedule for each type of finish to be applied at the site. The humid and tropical conditions shall be taken into account on selection of the paints and painting procedure. 2.16 EMBEDDED METAL WORK, OPENING, ETC The Contractor shall supply and install all enters, fasteners, embedded metalwork’s, piping, conduit and sleeves associated with and required for the equipment being provided and installed under this Contract, except as otherwise provided in the specifications. The Contractor shall indicate the location and details of foundations, openings, blockout and all embedded components on his drawings and shall be responsible for the completeness and accuracy of his drawings and the information supplied to others. The Contractor shall be responsible for the adequacy and accuracy of location of all embedded components supplied by him. The foundation bolts, embedded steel parts, anchors, braces, posts, supports, shims, etc., and all metal works as may be required for temporary or final support of anchorage of the equipment shall be provided and installed by the Contractor as part of this contract. Any metal work, which is to be built into the concrete foundations, shall not be painted nor coated unless otherwise approved. 2.17 SPARE PARTS The Contractor shall furnish spare parts as listed in the bill of quantities. The spare parts supplied shall be packed or treated in such a manner as to be suitable for storage under the climate conditions at the Site for a period of not less than two years, and each part shall be clearly marked with the description and purpose on the Spare parts so KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 61 of 270 62 SECTION V: TECHNICAL SPECIFICATIONS provided shall be delivered into such stores as may be designated by the Employer. Delivery of spare parts will not be deemed to be complete until the packages have been opened by the Contractor, their contents checked by a representative of the Employer and the articles reprotected and repacked by the Contractor to the satisfaction of the Employer, or assembled into units at the employer’s option. The method of package and package materials shall be suitable for the satisfactory re-package. 2.18 PACKING Each item shall be packed properly or protected for shipment from the place of manufacture to the site. Each crate of package shall contain a packing list in a waterproof envelope and a copy in triplicate shall be forwarded to the Employer prior to dispatch. All items of material shall be clearly marked for easy identification against the packing list. All cases, packages, etc, shall be clearly marked on the outside to indicate the total weight, to show where the weight is bearing and the correct position of the slings and shall bear an identification mark relating them to the appropriate shipping documents. Cases, which cannot be marked as above, shall have metal tags with the necessary marking on them. The metal tags shall be securely attached to the package with strong steel wire or equivalent. Long pieces of steel angles shall be packed in bundles and properly tied together by an approved method and care taken to ensure that they are robust and not of excessive length and weight for handling in transit. Short pieces of steel angles and steel plates shall be bolted or wired together through holes and packed in stout timber cases. Bolts, nuts, washers and fillers shall be bagged in sealed vinyl and packed in steel cans. The cans shall bear the contents and be crated together. Packing together of components of dissimilar metals shall not be acceptable. Conductors and overhead earth wire shall be packed on drums stoutly constructed of good quality steel. Drums shall be securely battened around the perimeter to give maximum protection to the conductor and the earth wire and correct direction of rolling indicated with an arrow in a manner not easily removable. The first layer of conductors or earth wire on drums shall be secured to the hub in manner avoiding damage to subsequent layers. All drums shall be protected from deterioration on site by termite or fungus attack by an approved impregnation treatment at the works before dispatch. The Employer shall reserve the right to inspect and approve the equipment and the packing before the items are dispatched. The Contractor shall be entirely responsible for ensuring that the packing is suitable for transit and such inspection will not relieve the Contractor from responsibility for any loss or damage due to faulty packing. It shall be the responsibility of the Contractor to improve and to reinforce the road facilities when the weight and dimension of the cargo exceed the above specification. All packing materials shall remain the property of the Contractor and shall be removed from the Site at the earliest opportunity and disposed off to the satisfaction of the Employer. The following information must be clearly stencilled or printed on each packing case, crate, cask, drum, bundle or loose piece, care being taken that the number and other particulars on each package agree with those entered in the packing list accompanying the Invoice: Employer's Identity Supplier's Identity Destination Contract No. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 62 of 270 63 SECTION V: TECHNICAL SPECIFICATIONS Package No. Item Code Weight, dimensions Sub-Project (Plant Identity). The marking shall be durable. The marking shall be upon the body of the package. Marking upon a batten fastened on the case, etc. shall not be used. 2.19 DELIVERY The Contractor shall deliver all materials and equipment including Contractor’s equipment supplied under the Contract to the site in adequate time for its preparation and erection according to the Schedule. Each notification shall include a complete shipping list of the contents of each package to be delivered and shall indicate the anticipated date of delivery and the serial number for each component to be used for identification and evidence of the insurance cost arranged for it. The Contractor shall be responsible for the reception on Site of all deliveries for the purpose of the Contract. 2.20 CLEANING AND MATERIAL DISPOSAL The Contractor shall at all times during the course of the work prevent the accumulation on the premises of debris caused by the Works. Whenever it is necessary, in the opinion of the Employer and in all events upon completion of the Works, the Contractor shall remove from the premises all temporary buildings and facilities, tools, scaffolding, surplus materials, debris and all work and materials condemned by the Employer and shall leave the premises in a clean, safe and sanitary condition. The Contractor shall prevent at any time unnecessary accumulation and scattering of debris, materials, tools and equipment around the premises, and shall conduct the work in an orderly manner. In case the Contractor fails to comply with the above provision, or in case of dispute, the employer shall have the right to order removal by others of debris, materials, tools or equipment, and to charge the cost of such removal and/or repairs to the Contractor. 2.21 PROGRAMME AND PROGRESS Within one month after the Date of Commencement, the Contractor shall prepare his construction programme in a Software form covering the design, manufacture, delivery, erection testing and commissioning of the Works, in sufficient detail to define the various sections of the Works, including parts to be supplied by the Contractor. A hard copy shall be submitted to the Employer for approval. Upon approval of the programme by the Employer, it should thereafter be referred to as the approved Construction Programme and shall become a part of the Contract. Monthly progress reports shall be provided by the Contractor, indicating the actual state of progress of all items during the course of manufacture and work at the Site, in the form given by the Employer. A brief weekly report on the construction work at the Site shall also be submitted by the Contractor to the Employer. From time to time during the execution of Contract, the Employer is empowered to call meetings, either in his home office or at the manufacturer’s offices or Employer’s Nairobi office or at the Site, as he deems necessary, for the purpose of co-ordination and control. If required by the Employer, responsible representatives of the Contractor shall attend such meetings at his own expense. In executing the Approved Construction Programme of this Contract, the Contractor shall co-operate with the Employer and other contractors on the Site in order to effect the timely completion of the Project as a whole. The Progress Plans shall at least contain the following milestones: Essential information delivered from Employer KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 63 of 270 64 SECTION V: TECHNICAL SPECIFICATIONS 2.22 Documentation for approval from Contractor to Employer Release of factory documentation Factory Tests Shipment Site ready for erection Start erection Ready for pre-commissioning Ready for commissioning Test run Taking over Submittal of final documentation DRAWINGS AND DATA TO BE SUPPLIED BY THE CONTRACTOR Before starting manufacture of the equipment, dimensioned drawings and data showing all significant details of the equipment and materials to be used shall be submitted to the Employer for approval, at least 2 weeks before the commencement of the manufacturing process. These drawings shall be submitted within the times mentioned hereunder, measured in calendar month from the Date of commencement. The drawings shall be modified as necessary if requested by the Employer, and resubmitted for final approval. When the Contractor prepares his construction schedule, as required herein, he shall make allowance for the drawing approval time and indicate it on the schedule. A period of at least six weeks should be allowed for such approval after receipt by the Employer. Claims or extensions of time will not be approved if they are related to the late submission of drawings to the Employer or if they involve delays caused by drawings not being approved by the Employer. After approval of drawings by the Employer, the Contractor shall supply the approved drawings to the Employer according to the details given below. It is to be understood, however, that approval of the drawings will not relieve the Contractor of any responsibility in connection with the work. All drawings submitted for approval or sent to the Employer for any other reason shall be sent by courier. After items of the work have been manufactured and erected, complete sets of prints and negatives of the finally corrected drawings shall be furnished according to the following table. The following number of drawings to be submitted to the Employer shall be as follows: To the Employer, during the work: Drawing for approval 5 copies Approved drawings 3 copies After completion of the work (final drawings): AutoCAD (latest version) 2 CDs with AutoCAD Licensed software Complete set of bound prints (as built) 6 sets All Protection and Control drawings shall be done on A4 paper. The function of each drawing shall be clearly indicated. Related drawings shall be arranged sequentially, have the same drawing number but different sheet numbers. The drawings shall include the following; AC Schematics DC Schematics Functional Drawings Layout Drawings KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 64 of 270 65 SECTION V: TECHNICAL SPECIFICATIONS Panel equipment wiring and cable terminations and schedules. Relays and accessories list. Protection and Control Software drawings shall be done in the latest AutoCAD release edition. Additional copies of particular drawings are to be provided if required, at the Contractor’s expense. 2.23 OPERATING AND MAINTENANCE INSTRUCTIONS The Contractor shall submit to the Employer for approval, general instructions concerning the correct manner of assembling, operating and maintaining the work. This instruction manual shall be submitted immediately following final approval of the drawings. When finally approved, six (6) copies of the instruction manual shall be furnished to the Employer. The contractor shall ensure that his erection supervisor has a copy in his office at the Site. The instruction manual shall describe in detail the erection procedure and use of all erection equipment and measurement devices. The method for assembling, adjusting, operating and dismantling of each device, system and machine shall be described and illustrated. The maintenance details of each component shall also be described, including the frequency of inspections and lubrication. The instruction manual shall include a separate and complete section describing the normal and emergency operating procedures for the control of the switching equipment, and shall include explanatory diagrammatic drawings of equipment to facilities understanding the description. The Contractor shall, in preparing the instruction manual, take into account the lack of experience and familiarity of the operators with this type of equipment. The manual shall give specific information as to oil, grease, or any other materials needed for maintenance operations. This information shall include brand names and manufacturer’s numbers or designations, for at least two brands available in Kenya, preferably manufactured in Kenya. The manual shall include a complete list of all drawings prepared for the Contract, spare parts list, and a parts list for each component of the equipment. The parts list shall apply only to the equipment supplied and shall not include general reference or description of similar equipment which is of the same model but different only in detail. The manual shall be prepared on the English language. 2.24 TEST PROCEDURE INSTRUCTIONS 2.24.1 Electrical equipment: (1) The manufacturer shall be responsible for performing or for having performed all the required tests specified in this specification. Tenderer shall confirm the manufacturer’s capabilities in this regard when submitting tenders. Any limitations shall be clearly specified. (2) Tender documents shall be accompanied by copies of Type test and Routine test reports & certificates for similar rated equipment for the purpose of tender evaluation. Type test reports & certificates shall be certified by the National Standards and Testing Authority (NSTA) of the country of origin. Where a body other than NSTA is used to certify the type-test reports, a copy of the certificate of accreditation shall be attached. Current contact information of the testing and certification authority shall be provided. Tenderer should note that this requirement is mandatory. (3) Upon completion of the manufacturing process, routine tests shall be carried out as per the specified standard for each equipment. In addition to these tests, Impulse, temperature rise and short-circuit tests (where applicable) shall be carried out and the results endorsed by the NSTA of the country of manufacture. (4) Routine test reports shall be completed for equipment and made available before the inspection by KPA representatives. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 65 of 270 66 SECTION V: TECHNICAL SPECIFICATIONS (5) A detailed list & contact addresses of previous customers shall be submitted with the tender. The manufacturer shall indicate the monthly & annual production capacity and experience in the production of the type and size of equipment he is offering. List of workshop tools and equipment shall also be appended. (6) The Contractor shall prepare and execute a testing program which will establish that specified requirements have been met and that the items furnished and installed will perform as specified and required. (7) The Contractor shall submit to the Employer for approval, during or immediately following the submission of drawings, testing programmes describing each test to be performed during commissioning and performance tests. The programme shall establish the sequence of the test, the equipment preparation and operation procedures to be followed and the detailed procedure for conducting each test. The programme shall also contain performance guarantees, design values, technical particulars, or other criteria and distributed in the same manner as the drawings. (8) A file containing a list of all the Commissioning Tests carried out and the results obtained for all the Protection and Control schemes and the primary equipment, including system balanced and unbalanced fault analysis for relay coordination and scheme settings shall be submitted to the Employer prior to the commissioning of the project. It is mandatory that these group tests shall be witnessed by the Employer’s representative. (9) Three copies of the Commissioning Report shall be submitted to the Employer. 2.25 ATTENDANCE OF EMPLOYER’S REPRESENTATIVE AT FACTORY TEST AND TRAINING The Contractor shall arrange for two Employer’s staff members to witness tests of major items of equipment listed below in the manufacturer’s plant. All routine tests shall be carried out in the presence of the Employer’s representatives. The representatives shall approve shipment of the equipment if they are satisfied that the requirements of the specification are fully met. An engineer from KPLC will also be invited to witness the tests for equipment that will be handed over to KPLC. It is anticipated that the visit shall not exceed five (5) days (1) 132 kV and 11 kV circuit breakers (2) 132 kV and 11kV outdoor isolators and earth switches (3) Control and Protection panels (4) 132 kV Current transformers (5) 132 kV Capacitive Voltage Transformers and 132 kV voltage transformers. (6) 132/11 kV Power Transformers (7) OPGW conductor (8) Communication terminal equipment. During the attendance, the Contractor shall give the Employer’s persons a brief explanation on design, manufacture, operation and maintenance of the materials and equipment. Protection Schemes philosophy and settings shall be explained. TRAINING (1) High voltage switchgear equipment (2) Control and protection equipment (3) Telecommunication Equipment The training on the operation of the high voltage switchgear equipment, control, protection and communication equipment shall be conducted for 2 Employer’s staff for duration of not less than 5 days. 2.26 PHOTOGRAPHS The Contractor shall keep photographic records of the progress of each phase of the work. Upon completion of the work, the Contractor shall submit three sets of colour photographs with explanatory description adequately edited in book form to the Employer’s satisfaction. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 66 of 270 67 SECTION V: TECHNICAL SPECIFICATIONS The Contractor shall provide himself with necessary access to the work and temporary facilities to photograph his part of the work at any stage of construction or manufacture. 3 3.1 TECHNICAL SPECIFICATIONS FOR THE SUBSTATION SWITCHGEAR AND CONTROL EQUIPMENT Scope This subsection covers the design, manufacture, testing before shipment, delivery to site, erection and testing at the site of the following: 3.2 132kV CIRCUIT BREAKERS: 3.2.1 SCOPE This specification is for three pole operated outdoor 132kV circuit breaker together with controls and ancillary equipment. 3.2.2 REFERENCES The following documents were referred to during the preparation of this specification, and may be referred to, in case of conflict, the provision of this specification shall take precedence. Unless otherwise specified, the latest revision, edition and amendments shall apply. IEC 56: High – Voltage alternating current circuit breakers. IEC 144: Degree of protection of enclosures for low – voltage switchgear and control gear. BS 5311: Specification for A.C circuit breakers of rated voltage above 1 kV. 3.2.3 CONSTRUCTION The circuit breakers shall be single pole operated, out-door type, SF6 gas insulated and shall comply with the requirements of IEC 56 and/or BS 5311. The circuit breaker shall be live tank type. All the three poles of circuit breakers shall be operated by local electrical and remote/electrical from the mechanism in the housing. The circuit breaker shall have SF6 gas for electrical interrupting medium. The SF6 gas shall comply with the requirement of IEC 376 and be suitable for use in the circuit breaker when it is operated under the service and system conditions. Sufficient gas shall be provided for filling the circuit breaker at installation with additional 20% for any losses. When the circuit breaker is in closed position a rapid fall in the SF6 gas pressure, to a level below that at which safe operation is possible shall not result in tripping the circuit breaker. A remote alarm indication to signal this condition shall be provided. A second stage drop in gas shall block closing and tripping of the circuit breaker. Insulation creepage distance shall not be less than 25mm per kV of rated voltage between phases. 3.2.4 OPERATING MECHANISM The operating mechanism shall be suitable for mounting at the circuit breaker supporting structure, and below the circuit breaker in a weather-proof, dust-proof, vermin-proof and well ventilated housing. The degree of protection shall be class IP 54 as per the requirement of IEC 144. Operating duty shall be standard and operating mechanism shall be trip free during the entire closing sequence. Operating mechanism shall be provided with either motor wound spring or pressure actuated mechanism with provision for hand charge. Motor operating voltage shall be 110 Volts D.C. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 67 of 270 68 SECTION V: TECHNICAL SPECIFICATIONS A set of at least ten normally closed and ten normally open spare potential free contacts shall be provided for remote electrical indication as well as electrical interlocking and shall be wired to a terminal block in the housing. Potential free contacts shall be provided for alarming spring charge failure or control oil pressure low. Potential free contacts shall be provided for alarms for SF6 gas low and SF6 Trip Block. A minimum of twenty (20) spare terminals shall be provided for connection to the current and voltage transformers. The circuit breaker shall be provided with Local/Remote selector switch. The selection of local operation shall inhibit the operation of the circuit breaker from any remote source and selection of remote inhibits operation from local operation. The circuit breaker shall be provided with a local switch for Open/Neutral/Close Operation. Mechanically operated indication to show the status of the circuit breaker operations (open/close and springs charged/discharged) shall be provided. The circuit breaker shall be provided with suitable terminals for connecting clamps for up to 3” outside diameter copper tubes. The circuit breaker shall be provided with means to prevent contact pumping while the closing circuit remains energized, should be circuit breaker either fail to latch or be tripped during closing due to operation of the protective relays. Mechanical interlock key arrangement shall be provided on the mechanism such that it will not be possible to withdraw the interlock key with circuit breaker in closed position. For the 132 kV line circuit breakers, the mechanical interlock keys from each pole shall be such that they will be closed in a block of 4 keys so that the 4th key only come out when the other three are on in the block. That 4th key will be used to inter lock the 2 separately. For the 132kV transformer circuit breaker, the mechanical interlock key will come out only when the circuit breaker is off and this key will be used to operate the 132kV transformer bay disconnectors. Circuit breaker shall be provided with duplicate trip coils in order to facilitate duplication of protection tripping, where required. The circuit breaker shall have separate operating mechanism for each pole. From local position (only on middle phase) the operation of all the 3 poles should be possible with CLOSE/NEUTRAL/TRIP Switch. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 68 of 270 69 SECTION V: TECHNICAL SPECIFICATIONS 3.2.5 RATINGS The circuit breaker shall be of the following ratings: Nominal System Voltage Highest Voltage of equipment Frequency Rated normal current Rated short-time withstand current Rated duration of short circuit Rated short circuit making current First pole to clear factor Operating sequence Auxiliary D.C Voltage for closing & tripping coils Auxiliary A.C Voltage Impulse withstand voltage One minute power frequency withstand voltage Creepage distance of insulator Minimum clearance between phases Minimum clearance to earth 132 kV 145 kV 50 Hz 2000 Amps 40kA 3 Sec. 80kA 1.5 0-0.3 sec – CO – 3 min - CO 110 V d.c. 415/240 V, 50 Hz 750 kV peak (1.2/50µs, dry) 325 kV r.m.s. (50Hz 60s, wet) 3625 mm 1475mm 1270mm 3.2.5 TESTS The manufacturer shall be responsible for performing or for having performed all the required tests specified in this specification. Tenderers shall confirm the manufacturer’s capabilities in this regard when submitting tenders. Any limitations shall be clearly specified. Type and routine tests shall be carried out as per the requirement of IEC 56. Test certificates issued by a recognized short-circuit testing station, certifying the operation of the circuit breaker at duties corresponding to the rated breaking capacities of the circuit breaker shall be submitted. Tender documents shall be accompanied by copies of Type test and Routine test certificates for similar rated equipment. These certificates shall be certified by the National Testing or the National Standards Institute of the country of origin. A detailed list & contact addresses of previous customers shall be submitted with the tender. The manufacturer shall indicate the monthly & annual production capacity and experience in the production of the equipment he is offering. 3.2.6 DRAWING AND MANUALS Two sets of operational manuals and drawing detailing dimensions, panel layout, wiring and schematic shall be provided. 3.2.7 PACKING AND INFORMATION The circuit breaker and associated components shall be packed in a manner as to protect it from any damage in transportation and repeated handling. Each assembly and package of items associated with the circuit breaker shall be suitably marked. Where an item includes a number of components to form a complete assembly, all component parts shall be included in one composite package which shall be firmly strapped and bound together. Draft design and construction drawings shall be submitted to KPA before the manufacturing of circuit breakers commence. KPA undertake to submit their comments or approval for the drawings within three weeks of receiving the draft copies. Sufficient relevant technical details and drawings shall be submitted for the purpose of Tender Evaluation. Tenders which do not meet this requirement will be considered nonresponsive. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 69 of 270 70 SECTION V: TECHNICAL SPECIFICATIONS To facilitate comprehensive technical evaluation of the tenders, a clause by clause statement of compliance with the specification shall be submitted with relevant manufacturer’s specification sheets, catalogues and brochure. 3.2.8 TECHNICAL SCHEDULES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.3 132 kV THREE POLE DISCONNECTORS: 3.3.1 SCOPE This specification is for 132kV, 1600 Amps Isolator for use on line disconnection, isolation of substation apparatus. This specification covers both the 132 kV isolators with and without earth switch. 3.3.2 REFERENCES The following documents were referred to during the preparation of this specification, and may be referred to in case of conflict; the provision of this specification shall take precedence. Unless otherwise specified, the latest revision, edition and amendments shall apply IEC 129: Alternating current disconnectors (isolators) and earthing switches. IEC 144: gear Degree of protection of enclosures for low - voltage switchgear and control IEC 60273: Characteristic of indoor and outdoor post insulators for systems with nominal voltages greater than 1000V BS 729: Hot dip galvanized coating on iron and steel articles. 3.3.3 CONSTRUCTION 3.3.3.1 The isolator shall be horizontal side opening, double side break rotating post type for use on a 132kV, 50 Hz, 3 - phase system. 3.3.3.2 The isolator shall be complete with supporting base, phase coupling details, operating rod, unions and guides. 3.3.3.3 The operating mechanism shall be provided with a universal joint to allow for a reasonable degree of out-of alignment of the operating rod. 3.3.3.4 The isolator shall be motorised and also fitted with manual operation facility. There should be a remote selection to allow for operation of the isolator from the control room. The remote selection should block any local electrical or manual operation. 3.3.3.5 The supporting under-base shall be hot dip galvanized steel as per the requirement of BS 729. The under-base shall be suitable for mounting on a steel structure. 3.3.3.6 All the three switches shall be arranged so that the phase units are mounted independently and then finally interconnected with coupling tubes so as to ensure simultaneous operation of all switches by drive rods and operating handle for both manual and motor operation. 3.3.3.7 The operating mechanism shall be fixed at the base frame, in a weather proof, vermin proof and dust proof housing. The degree of protection shall be class IP 54 as per IEC 144. 3.3.3.8 Auxiliary dry contacts, five normally open and five normally closed shall be provided for electrical interlocks such that the isolator and associated 132 kV circuit breaker can be interlocked with each other. The contacts shall be rated to continuously carry at least 10Amps at voltages up to 500V dc/ac 3.3.3.9 Each phase shall be mounted on a spiral type solid core post insulator conforming to IEC 60273, and shall be fitted with clamp connector for the suitable conductor/connector. 3.3.3.10 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation between the contacts on all the three switches. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 70 of 270 71 SECTION V: TECHNICAL SPECIFICATIONS 3.3.3.11 All current carrying parts shall be made of electrolytic hard drawn copper with switch contacts silver plated. 3.3.3.12 The earth switch shall consist of a hinged type earthing switch fixed at the base frame. The earth switch shall have the same rating as the isolator. 3.3.3.13 The isolator shall be provided with both mechanical and electrical interlocking devices between the isolator and earth switch so that during operations, it is only possible to operate the earth switch with the isolator in the open position and the isolator with the earth switches in the open position. 3.3.3.14 Ten normally open and ten normally closed auxiliary contacts shall be provided on the switch for future use. 3.3.3.15 Five normally open and five normally closed auxiliary contacts shall be provided on the earth switch for future use. 3.3.3.16 The isolator and earth switch shall be provided with a padlocking facility such that the mechanism can be locked in OPEN or CLOSED position. 3.3.4 RATING The ratings of the isolator, including its operating devices and auxiliary equipments shall be as indicated below. Nominal Voltage and frequency Highest Voltage Normal current Rated short circuit withstand current & time Rated short circuit making current Auxiliary Voltage A.C. D.C. Lightning impulse With contacts closed withstand voltage Across open contacts 132 kV, 50Hz 145 kV 1600 Amps 31.5 kA, 3s 80 kA 415/240 V, 50 Hz 110±10% 750 kV peak One minute power frequency withstand voltage With contacts closed 325 kV r.m.s. Across open contacts 370kV Minimum creepage distance of insulator Minimum clearance phase-to-phase Minimum clearance phase-to-earth Mechanical endurance (number of close-open cycles without using spare parts) 870kV peak 4495mm 2900mm 2900mm 2000 (minimum) 3.3.5 TESTS 3.3.5.1 The isolator shall be inspected and routine tested in accordance with the requirement of IEC 129. 3.3.5.2 Certified type test certificates issued by the relevant National Testing Authority confirming compliance of the isolators on offer with the specifications shall be submitted. 3.3.6 TECHNICAL SCHEDULES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.4 132kV CAPACITOR VOLTAGE TRANSFORMERS (CVTs): 3.4.1 SCOPE 3.4.1.1 This specification is for voltage transformers for use with electrical instruments and electrical protective devices on system with maximum operating voltage up to 145kV. 3.4.2 SYSTEM CHARACTERISTICS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 71 of 270 72 SECTION V: TECHNICAL SPECIFICATIONS 3.4.2.1 The voltage transformers will be connected to overhead system operating at a nominal voltage of 132kV and a maximum voltage of 145kV which are generally of earthed construction. 3.4.2.2 The voltage transformer will be connected between line and earth of a 3-phase 3-wire system with the neutral point solidly earthed. 3.4.3 CONSTRUCTION 3.4.3.1 The voltage transformer shall be out-door oil-immersed capacitor type and shall comply with the requirement of IEC 186. 3.4.3.2 The voltage transformer shall be suitable for installation on steel structure. The voltage transformer shall be fitted with lugs. 3.4.3.3 The porcelain portion of the voltage transformer shall be made of high-grade brown glazed porcelain. All other external parts shall be either inherently resistant to atmospheric corrosion or hot-dip galvanized. 3.4.3.4 The voltage transformer shall have primary, secondary and earth terminals. 3.4.3.5 The primary terminal shall be tin-plated, suitable for both copper and aluminum connectors. The secondary terminal shall be brought out to a separate terminal box, complete with protection MCB. The MCB should have auxiliary contacts for indication, alarm and distance relay input. 3.4.4 RATINGS The voltage transformer shall be capable of continuously carrying 50% burden above the rated capacity without damage. The rating of the voltage transformer shall be as indicated herein:Parameter Value 1 Rated primary voltage 132000/√3 Volts 2 Rated secondary voltage 110/√3 Volts 3 Rated frequency 50 Hz 4 Minimum creepage distance of 3988 mm insulator 5 Lightning impulse withstand voltage 685kV at 1500M above sea level 6 Power frequency withstand voltage 6 290kV 7 Rated burden 100 VA (a) Rated voltage factor 1.5 for 30 seconds (1.2 continuous) (b) Accuracy class 1.0 (c) No. secondary out put 2 (metering, protection) 3.4.5 MARKING The voltage transformer shall be fitted with a rating plate indicating the following: The manufacturer’s name or identification mark. The voltage transformer serial number or designation. The rated primary and secondary voltage. The rated frequency. The burden and accuracy class of each secondary output. The highest system voltage (e.g. 145kV). The insulation level. The rated voltage factor and corresponding rated time. The terminals shall be marked clearly and indelibly. The marking shall be in accordance with IEC 186. 3.4.6 TEST Type and routine tests shall be carried out as per the requirement of IEC 186. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 72 of 270 73 SECTION V: TECHNICAL SPECIFICATIONS 3.4.7 REFERENCES The following documents were referred to during the preparation of this specification, and may be referred to. In case of conflict, the provision of this specification shall take precedence. Unless otherwise specified, the latest revision, edition and amendments shall apply. IEC 186: Voltage transformers. BS 3941: Specification for voltage transformers. 3.4.8 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.5 132 kV CURRENT TRANSFORMERS: 3.5.1 SCOPE This specification is for current transformers for use with electrical instruments and electrical protective devices on systems with maximum operating voltage of 145kV. 3.5.2 SYSTEM CHARACTERISTICS The current transformer will be connected to overhead system operating at a nominal voltage of 132 kV and maximum voltage of 145kV (with aerial earth wire) construction. 3.5.3 CONSTRUCTION The current transformer shall be outdoor, oil-filled, hermetically sealed and shall comply with the requirement of IEC 185. The current transformer shall be suitable for vertical installation on steel structure. 3.5.3.1 The porcelain portion of the current transformer shall be made of high-grade brown-glazed porcelain. All external ferrous portions shall be hot-dip galvanized. 3.5.3.2 The current transformer shall have primary, secondary and earth terminals. The primary terminal shall be tin-plated, suitable for both copper and aluminium connectors. The secondary terminal shall be covered with removable plate. The terminal box shall be capable of accommodating up to 12 secondary terminals suitable for conductor of up to 4.0mm2. 3.5.3.3 The current transformer shall have four cores. The protection cores shall be suitable for conventional over current requirements and for true transformation of the fully asymmetrical fault currents. Measuring cores shall have high accuracy (low loss) and low saturation levels. 3.5.4 RATINGS The short circuit rating of the current transformers shall be 31.5kA. The current transformers shall be capable of passing rated primary current without damage with the secondary open circuited. The rating of the current transformers shall be as indicated herein:Parameter Values 1 Rated primary current (Amps) 600/400/200 2 Rated secondary current 1 AMP 3 Rated frequency 50Hz 4 Minimum Creepage distance of insulator 3988 mm 5 Lightning impulse withstand voltage 685kV 6 Power frequency withstand voltage 290kV 7 Rated burden and accuracy class Core No. 1 20VA, 5P20 Core No. 2 20VA, 0.2 Core No. 3 20VA, X Core No. 4 20VA, 5P20 The knee point voltage shall not be less than 250 Volts at 8mA. 3.5.5 MARKING The current transformers shall be fitted with a rating plate indicating the following:KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 73 of 270 74 SECTION V: TECHNICAL SPECIFICATIONS The The The The The The The manufacturer’s name or identification mark. current transformer serial number or designation. primary and secondary currents. insulation level. highest system voltage (e.g. 145kV). output and accuracy class of the cores. rated frequency. The terminals shall be marked clearly and indelibly. The marking shall consist of letters followed by numbers. The letters shall be in block capitals. 3.5.6 TESTS Type and routine tests shall be carried out as per the requirement of IEC 185. 3.5.6 REFERENCES The following documents were referred to during the preparation of this specification, and may be referred to. In case of conflict, the provision of this specification shall take precedence. Unless otherwise specified, the latest revision, edition and amendments shall apply. IEC 185: Current Transformers. BS 3938: Specification for current transformers. 3.5.7 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.6 132 kV SURGE ARRESTERS: 3.6.1 SCOPE This specification is for 132kV metal-oxide type surge arresters without spark gaps for a.c. system. 3.6.2 CONSTRUCTION 3.6.2.1 The surge arrester shall be metal-oxide type without spark gaps and constructor as per the requirement of IEC 99-4. 3.6.2.2 The metal-oxide used shall be of quality to ensure thermal stability under service duty of the surge arrester. 3.6.2.3 The completed surge arrester shall be housed in a silicone rubber. The silicone rubber insulator shall be dimensioned to provide a leak free interface with the end caps. The housing shall withstand the lighting impulse voltage of the arrester. 3.6.2.4 The surge arrester shall be sealed (end caps) with a controlled permanent seal to ensure no moisture absorption or deterioration of the metal-oxide element for the surge arrester. 3.6.2.5 The surge arrester shall be supplied with fixing accessories and fitted with pad type clamp connectors suitable for both copper and aluminium tubes of up to 76.2mm diameter. The steel plates or straps shall be galvanized as per the requirement of BS 729. The mounting brackets shall be suitable for both horizontal and vertical mounting on a steel channel. 3.6.3 RATING The rating of the surge arrester shall be as indicated herein:Parameter Rating 1 Rated Voltage………………………………. 108 kV 2 Nominal discharge current……………… 10 kA 3 Long duration discharge class……....…. 3 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 74 of 270 75 SECTION V: TECHNICAL SPECIFICATIONS 4 5 6 Creepage distance of insulator………… 3630 mm Continuous operating voltage…………. 84 kV Rated frequency………………………….. 50 Hz 3.6.4 MARKING The surge arrester shall be fitted with a rating plate indicating the following: The manufacturer’s name or identification mark. The surge arrester serial number or designation. The nominal discharge current. The insulation level. The continuous operating voltage The rated voltage The rated frequency. 3.6.5 TESTS Type, routine and acceptance tests shall be carried out as per the requirement of IEC 99-4. 3.6.6 REFERENCES The following documents were referred to during the preparation of this specification. In case of conflict, the provision of this specification shall take precedence. Unless otherwise specified, the latest revision, edition and amendments shall apply. IEC 99: Surge Arrester. Part 4: Metal-oxide surge arresters without gaps for a.c. systems. IEEE Std.:C62.22 – 1991 IEEE Guide for application of metal-oxide surge arresters for alternating – current systems. 3.6.7 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.7 132/11 kV POWER TRANSFOMERS: 3.7.1 SCOPE This specification is for newly manufactured outdoor oil type power transformer as described below: 15 MVA, 132/11kV, 50 Hz, ONAN/ONAF three phase power transformer. The specification also covers inspection and test of the transformer as well as schedule of Guaranteed Technical Particulars to be filled, signed by the manufacturer and submitted for tender evaluation. The specification stipulates the minimum requirements for 15MVA, 132/11kV power transformer acceptable to the Kenya Power and Lighting Co. for use by the Authority and it shall be the responsibility of the manufacturer to ensure adequacy of the design and good engineering practice in the manufacture of the transformer for KPA. The specification does not purport to include all the necessary provisions of a contract. 3.7.2 REFERENCES The following standards contain provisions which, through reference in this text constitute provisions of this specification. Unless otherwise stated, the latest editions (including amendments) apply. ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles – Specifications and test methods. IEC 60076: Power transformers. IEC 60044: Instrument transformers. IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear. IEC 60354: Loading guide for oil – immersed power transformers. BS 171: Power transformers BS 381C: Specification for colours for identification coding and special purposes KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 75 of 270 76 SECTION V: TECHNICAL SPECIFICATIONS 3.7.3 TERMS AND DEFINITIONS The terms and definitions given in the reference standards shall apply. 3.7.4 SYSTEM CHARACTERISTICS a) The primary HV system is 132,000 Volts, 3 phase, 3 wire, 50Hz, with neutral point solidly earthed. b) The secondary MV system is 11,000 Volts, 3 phase, 3 wire, 50Hz, with neutral point solidly earthed. c) The Transformer shall be operated at a high loading factor. 3.7.5 GENERAL REQUIREMENTS 3.7.5.1 The transformer shall be outdoor, oil-immersed, of ONAN/ONAF classification and core type (lamination stackings). All offers shall comply with the requirements of IEC 60076. Any deviations/additional requirements shall be as stated in this specification. 3.7.5.2 The transformer shall be a two winding type three-phase integral unit. 3.7.5.3 The transformer shall be of the free breathing type. A dehydrating cobalt free breather of approved design shall be provided. 3.7.5.4 The transformer and accessories shall be designed to facilitate operation, inspection, maintenance and repairs. All apparatus shall be designed to ensure satisfactory operation under such sudden variations of load and voltage as may be met with under working conditions on the system, including those due to short circuits. 3.7.5.5 The design shall incorporate every reasonable precaution and provision for the safety of all those concerned in the operation and maintenance of the equipment keeping in view the regulatory requirements in Kenya. 3.7.5.6 All material used shall be of the best quality and of the class most suitable for working under the conditions specified and shall withstand the variations of temperatures and atmospheric conditions arising under working conditions without undue distortion or deterioration or the setting up of undue stresses in any part, and also without affecting the strength and suitability of the various parts for the work which they have to perform. 3.7.5.7 Corresponding parts liable to be replaced shall be interchangeable. 3.7.5.8 All outdoor apparatus, including bushings insulators with their mountings, shall be designed so as to avoid pockets in which water can collect. 3.7.5.9 All connections and contacts shall be of ample section and surface for carrying continuously the specified currents without undue heating and fixed connections shall be secured by bolts or set screws of ample size, adequately locked. Lock nuts shall be used on stud connections carrying current. All leads from the winding to the terminals and bushings shall be adequately supported to prevent injury from vibration including a systematical pull under short circuit conditions. 3.7.5.10 All apparatus shall be designed to minimize the risk or accidental short-circuit caused by animals, birds or vermin. 3.7.5.11 In tank on-load-tap changers shall be located such that the space above the diverter switch chamber will be free of inter-connecting pipes etc. for lifting the diverter switch unit for inspection and maintenance purposes. 3.7.5.12 Galvanizing shall be applied by the hot-dipped process to ISO 1461 and for all parts other than steel wires shall consist of a thickness of zinc coating equivalent to not less than 610g of zinc per square meter of surface. The zinc coating shall be smooth, clean and of uniform thickness and free from defects. The preparation of galvanizing and the galvanizing itself shall not adversely affect the mechanical properties of the coated material. The quality will be established by tests as per ISO 1461. 3.7.5.13 All bolts, nuts, and washers exposed to atmosphere and in contact with non-ferrous parts which carry current shall be of phosphor bronze. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 76 of 270 77 SECTION V: TECHNICAL SPECIFICATIONS 3.7.5.14 If bolts and nuts are placed so that they are inaccessible by means of ordinary spanners, suitable special spanners shall be provided by the supplier. 3.7.5.15 Except for hardware, which may have to be removed at site, all external surfaces shall receive at least four coats of paint. The total dry film thickness shall be between 100 and 130 microns. 3.7.5.16 Descriptive labels for mounting indoors or inside cubicles and kiosks shall be of material that will ensure permanence of the lettering. A matt or satin finish shall be provided to avoid dazzle from reflected light. Labels mounted on dark surface shall have white lettering on a black background. Danger notices shall have red lettering on a white background. 3.7.5.17 All interior surfaces of chambers or kiosks that are in contact with air shall receive at least three coats of paint, of which the topcoat shall be of a light shade. 3.7.5.18 The design and all materials and processes used in the manufacture of the transformers shall be such as to reduce to a minimum the risk of the development of acidity in the oil. 3.7.5.19 Every care shall be taken to ensure that the design and manufacture of the transformers and auxiliary plant shall be such to have minimum noise and vibration levels following good modern manufacturing practices. The maximum noise levels shall be stated in the bid 3.7.6 Ratings 3.7.6.1 The windings of the transformer shall be rated at 15MVA (ONAF), with a minimum ONAN rating of 11 MVA. These ratings shall be for the operating conditions stated in clause 2.6.The rating specified in this clause shall be the continuous rating at the maximum ambient temperature and altitude given in clause 2.6 3.7.6.2 (a) The transformer shall be capable of carrying its full normal rating continuously at any tap under the conditions stated in clause 2.6 without undue stress, overheating, or the temperature rise in the hottest region exceeding 55ºC and 60ºC in oil and windings respectively. (b) The loading capabilities shall be demonstrated by a temperature – rise test. This test shall be done in the presence of KPA Representatives during factory visit. 3.7.6.3 The transformer shall be capable of withstanding the maximum fault level at its rated voltage and impedance for 2 seconds. The design should cater for the expected lifetime of the transformer. 3.7.7 Winding and connections 3.7.7.1 The transformer shall be wound Dyn11 with respect to the 132 kV and 11 kV windings as per IEC 60076. 3.7.7.2 The transformers shall be capable of operation without danger on any particular tapping at the rated MVA when the voltage may vary by ± 10% of the voltage corresponding to the tapping. 3.7.7.3 The windings and connections as well as the insulating material shall not soften, ooze, shrink or collapse during service. The materials shall be non-catalytic and chemically inactive in transformer oil during service. 3.7.7.4 No strip conductor wound on edge shall have a width exceeding six times its thickness. The conductors shall be transposed at sufficient intervals to minimize eddy currents and equalize the current and temperature distribution along the windings. 3.7.7.5 The windings and connections shall be properly braced to withstand shocks during transportation or due to short circuit and other transient conditions during service. 3.7.7.6 Adequate pre-shrinkage of the coil assembly using pre-compressed press board material having low moisture content for the radial spacer blocks shall be ensured by the manufacturers so that there is no displacement of the radial spacer blocks due to frequent short circuits on the transformers. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 77 of 270 78 SECTION V: TECHNICAL SPECIFICATIONS 3.7.7.7 All windings after being wound and all fibrous hygroscopic materials used in the construction of the transformer shall be dried under vacuum and impregnated with hot oil. 3.7.7.8 The coil clamping rings wherever used shall preferably be of flat insulated steel laminations. 3.7.7.9 The radial spacer blocks must be made of pre-compressed pressboard material, which will not soften while in contact with oil or fray out into fibres or edges. The slots should be so dimensioned that the blocks will not come out of the slots. 3.7.7.10 All joints shall be brazed/crimped considering the vibrations due to short circuits and load fluctuations. 3.7.7.11 KPA will inspect built-up winding for its quality, weight of copper, insulation and overall weight of coil assembly. The size of conductor used for different windings shall also be checked during stage inspection to check the current density. 3.7.7.12 The transformer shall be designed with particular attention to the suppression of harmonic voltage, especially the third and fifth, so as to eliminate wave-form distortion and from any possibility of high frequency disturbances, inductive effects or of circulating currents between the neutral points at different transforming stations reaching such a magnitude as to cause interference with communication circuits. 3.7.7.13 The windings shall be designed to reduce to a minimum the out-of-balance forces in the transformer at all voltage ratios. 3.7.8 Tapping 3.7.8.1 Tapping Range The transformers shall be provided with tapping on the 132 kV winding for a variation of no load primary voltage for parallel operation, with Tap No. 1 having the highest voltage assignment, as follows: 132000 Volts +8*1.67% -8*1.67% 3.7.8.2 Tapping Method Tapping shall be carried out by means of an on-load tap changer as described in clause 3.7.14 below. 3.7.9 Core and flux density a) Core 3.7.9.1 The core shall be constructed from the laminations of high grade cold rolled non-aging, grain oriented silicon steel known as M4 High B Grade or superior grade CRGO steels of maximum 0.27mm or less lamination thickness especially suitable for transformer core. The grade of CRGO shall be stated in the bid. 3.7.9.2 The design of the magnetic circuit shall be such as to avoid static discharges, development of short-circuit paths within itself or to the earthed or to the clamping structure and the production of flux components at right angles to the plane of the laminations which may cause local heating. 3.7.9.3 Every care shall be exercised in the selection, treatment and handling of core steel to ensure that as far as practicable, the laminations are flat and the finally assembled core is free from distortion. 3.7.9.4 Adequate oil ducts shall be provided in the core for cooling. Tinned copper strip bridging pieces shall be used for maintaining electrical continuity wherever the magnetic circuit is provided into pockets by such ducts or insulating material thicker than 0.25mm. 3.7.9.5 There shall be no movement of the core assembly relative to the tank during transport, installation as well as in service due to sudden jerks caused by short circuits and fluctuating loads. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 78 of 270 79 SECTION V: TECHNICAL SPECIFICATIONS 3.7.9.6 All steel sections used for supporting the core shall be thoroughly sand blasted or shot blasted after cutting, drilling and welding. Any non-magnetic or high resistance alloy shall be of established quality. 3.7.9.7 Adequate lifting lugs shall be provided to enable core and winding to be lifted. 3.7.9.8 Supporting framework of the Cores shall be so designed as to avoid the presence of pockets which would prevent complete emptying of the tank through the drain valve, or cause trapping of air during filling. 3.7.9.9 The insulation structure for the core to bolts and core to clamp plate shall be such as to withstand a voltage of 2kV AC for one minute. (b) Flux Density 3.7.9.10 The primary voltage variation, which may affect the flux density at every tap, shall be kept in view while designing the transformer. 3.7.9.11 The transformer shall be so designed that the working flux density shall not exceed 1.6 Tesla at normal voltage, frequency & ratio. Tenders with higher flux density than specified shall not be considered. 3.7.9.12 Tenderers shall indicate the continuous allowable maximum flux for one minute and five seconds. 3.7.9.13 The limit of flux density at which core material used saturates shall also be stated in the tender. The name and grade of core material shall be stated in the tender. 3.7.9.14 The successful tenderer shall be required to furnish magnetization curve of the core material, design calculations and such other data/documents deemed fit by the purchaser for being satisfied that flux density is as desired. NOTE: The above flux density has been specified to meet with the over fluxing of the core due to temporary over voltage of the orders of 25% for one minute and 40% for five seconds that may appear in abnormal conditions such as the one obtained following sudden loss of large loads. 3.7.10 Losses, Regulation and Impedance 3.7.10.1 Losses of the transformer shall be stated and shall be subject to tolerances in accordance with IEC 60076. The fixed losses shall be as low as is consistent with good design, reliability and economical use of materials. 3.7.10.2 Voltage regulation from no-load to continuous rated output at unity power factor, at 0.8 lagging and 0.8 leading power factor with constant voltage across the higher voltage windings shall be stated in the bid. 3.7.10.3 The impedance voltage at extreme tappings and at principal tapping shall be stated and shall be subject to tolerances in accordance with IEC 60076. 3.7.10.4 Terminals: Arrangement & Bushings 3.7.10.5 The 11kV and 132kV windings shall be brought out separately through open bushings of outdoor, weatherproof design in accordance with the latest IEC standard. 3.7.10.6 Bushings for 132kV terminals shall be of oil-filled condenser type construction, drawout type and shall each have a capacitance test point. Bushings for 11kV terminals shall be of the solid porcelain type. 3.7.10.7 The neutral bushing of the transformer shall be identical to the corresponding phase terminal bushings for 11kV Bushings. 3.7.10.8 Spacing and air clearances shall be so co-ordinated as to render the probability of a flashover from the terminal of one winding to the terminal of another winding negligible. 3.7.10.9 Leakage distance of bushings shall not be less than 25mm/kV, based on operating phase to phase voltage. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 79 of 270 80 SECTION V: TECHNICAL SPECIFICATIONS 3.7.10.10 Bushing terminals shall be clamp type suitable for both copper and aluminium Bus bars of sizes up to 76mm diameter. 3.7.10.11 Each bushing of the 132kV windings shall be mounted on a turret. Each turret shall be suitable for accommodating at least two sets of current transformers. 3.7.10.12 Each bushing of the 11kV windings shall be mounted on a turret. Each turret shall be suitable for accommodating at least three sets of current transformers. 3.7.10.13 Terminal arrangement on the HV and LV sides shall be A, B, C and n, a, b, c respectively. 3.7.11 Current Transformers to be fitted 3.7.11.1 Current transformers shall be installed in the bushing turrets and shall be of the following quantities, ratios, ratings and class: (a) 132 kV Phase Bushings CTs CORE 1 HV side-line - ph 1A ; 15VA, 100/1A, cl.3 - for winding thermocopy. HV side-line - ph 1B ; 15VA, 100/1A, cl.0.5 – for measurements. HV side-line - ph 1C ; 15VA, 100/1A, cl.3 – for winding thermocopy CORE2 HV side-line - ph 1A ; 15VA, 100/1A, Class X, Vk >250V – for differential protection. HV side-line - ph 1B ; 15VA, 100/1A, Class X, Vk >250V – for differential protection. HV side-line - ph 1C ; 15VA, 100/1A, Class X, Vk >250V – for differential protection. CORE 3 HV side-line HV side-line HV side-line CORE 4 HV side-line HV side-line HV side-line - ph 2A ; 15VA, 100/1A, 5P20 – O/C. - ph 2B ; 15VA, 100/1A, 5P20 – O/C. - ph 2C ; 15VA, 100/1A, 5P20 – O/C - ph 2A ; 15VA, 300/1A, 5P20 – Bus prot. - ph 2B ; 15VA, 300/1A, 5P20 – Bus Prot - ph 2C ; 15VA, 300/1A, 5P20 – Bus Prot (b) 11 kV Phase Bushings CTs Core 1 MV side-line - ph 2A ; 15VA, 1000/1A, Class X, Vk >250V – Differential. MV side-line - ph 2B ; 15VA, 1000/1A, Class X, Vk >250V – Differential. MV side-line - ph 2C ; 15VA, 1000/1A, Class X, Vk >250V – Differential. Core2 MV side-line - ph 2A ; 15VA, 1000/1A, cl.3 - for winding thermocopy MV side-line - ph 2B ; 15VA, 1000/1A, cl.3– for AVR supply MV side-line - ph 2C ; 15VA, 1000/1A, cl.3 - for winding thermocopy. Core3 MV side-line - ph 2A ; 15VA, 1000/1A, 5P20 – O/C. MV side-line - ph 2B ; 15VA, 1000/1A, 5P20 – O/C. MV side-line - ph 2C ; 15VA, 1000/1A, 5P20 – O/C Core 4 MV side-line - ph 2A ; 15VA, 1000/1A, CL X – REF MV side-line - ph 2B ; 15VA, 1000/1A, CL X – REF MV side-line - ph 2C ; 15VA, 1000/1A, CL X – REF 33kV NEUTRAL Core 1 Neutral side -; 15 VA 1000/1 cl. X - for Restricted Earth fault. Core 2 Neutral side -; 15 VA 1000/500/1A cl. x - for Earth fault Protection. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 80 of 270 81 SECTION V: TECHNICAL SPECIFICATIONS 3.7.11.2 Current transformers of suitable rating and class for winding temperature indicators shall be installed to adequately cover the transformer as indicated above for guidance. 3.7.11.3 Current transformers shall comply with the requirements of IEC 60044. 3.7.11.4 Full technical particulars of current transformers offered, including type test results from an International reputable Testing Authority or a National Standards and Testing Authority, shall be submitted with tender. 3.7.12 AIR CLEARANCE 3.7.12.1 When totally assembled, as in service, electrical clearances in air shall be adequate to withstand the assigned impulse withstand test voltages. 3.7.12.2 Care shall be taken to ensure that all fittings are suitably positioned so as not to interfere with the external connection to the bushing terminals. 3.7.12.3 Minimum external air clearances shall be as shown under. NOMINAL SYSTEM VOLTAGE BETWEEN PHASES 11 kV 132 kV Minimum clearance phase-to-earth and phase-to-neutral Minimum clearance phase-to-phase between phases of the same winding Minimum clearance between a line terminal of the high voltage winding and a line terminal of a lower voltage winding Minimum clearance from live metal to oil pipework including conservator and pressure relief device mm 485 1270 mm 485 1475 mm 485 1475 mm 480 1630 3.7.13 INSULATION LEVELS The complete transformer arranged for service, shall be capable of withstanding the following voltages and shall comply fully with the requirements of IEC 60076 Part 3, including the latest amendments. Nominal system voltage (kV, rms) Highest system voltage (kV, rms) Lightning Impulse withstand voltage (kV, peak) Power frequency withstand voltage (kV, rms) 11 132 12 145 70 685 63 290 3.7.14 ON LOAD TAP CHANGER AND MECHANISM BOX 3.7.14.1 The transformer shall be complete with vacuum type on-load, electrically driven tap changing mechanism of the high-speed resistor transition type, and shall comply with the requirements of IEC 214 and 512. The equipment shall be suitable for remote operation from a control panel supplied with the transformer as well as `for local operation from the Motor Drive Unit (MDU) mounted on the transformer body. 3.7.14.2 The mechanism shall be so designed as to ensure that when a tap change operation is in progress, it shall be able to complete the task independently irrespective of operation of any relays or switches. 3.7.14.3 Adequate means shall be provided to safeguard the transformer and its auxiliary circuits from damage should a failure of the auxiliary supply or any other mal-operation occur during the progress of tap changing that may prevent it from completing its task. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 81 of 270 82 SECTION V: TECHNICAL SPECIFICATIONS 3.7.14.4 Means shall be provided in the marshalling kiosk for mechanical isolation of the supply to the Motor Drive Unit, and a suitable thermal overload device (details to be submitted with tender) shall be provided in the MDU for the protection of the motor. The possibility of over-running the mechanism at each end of the voltage range shall be prevented by means of limit switches and mechanical stops. Other techniques used to prevent tap changer runaway shall be indicated. 3.7.14.5 A mechanically operated device shall be provided to indicate the tap position locally, and a suitable tap position transmitter shall be provided for the remote tap position indication. 3.7.14.6 A counter shall be provided on the tap changing mechanism box to indicate the total number of operations completed by the equipment. 3.7.14.7 Contactors and associated equipment for the control circuit for local/remote and manual operations of the tap changer mechanism shall be housed in the mechanism box. 3.7.14.8 The tap changer (diverter switch) shall be housed in a separate compartment and shall be Vacuum Type. Sufficient documentation for the vacuum switch in form of manuals, instructions, drawings, technical characteristics, certified type test certificates and reports (from an International Testing/ Standards Laboratory), manufacturing and export experience of the supplier shall be submitted with the tender for technical evaluation. 3.7.14.9 The Motor Drive Unit shall have the following in addition to what has been stated above: (a) Isolating switch in the transformer marshalling box for the supply to the tap changer Motor Drive Unit, (b) Raise/lower contactors for tap changer motor operation, and associated single phase protection/overload relay, (c) Switch for selection of local/remote tap changer control, (d) Switch or switches for local tap changer operation, (e) Provisions shall be made available for hand operation in the mechanism box. 3.7.14.10 The tap changer shall be of internationally reputable manufacture and proven reliability in service. Detailed documentation and copies of certificates shall be submitted with the tender for evaluation. 3.7.15 Remote Tap Changer Control Panel The remote tap changer control panel shall contain the following devices: Automatic Voltage Regulating Relay (to be of proven design and technical details submitted with tender). Off/Manual/Automatic switch for the Relay. Raise /Lower control switch. Raise , Lower, ‘out of step’ and tap change in progress indication lamps Dial type Tap position indicator (technical details to be submitted with the tender). Master/Follower/Independent Scheme and selector switch. The Tap Changer shall employ, negative reactance or circulating current principle scheme for parallel operation with other three similar transformers but of different rating. Local /Remote switch kV meter (technical details to be submitted with the tender) Door operated lamp and anti-condensation heater. Heater switch ON/OFF to control anti-condensation heater Various control circuits controlled by Miniature Circuit Breakers 3.7.16 AUTOMATIC VOLTAGE REGULATING RELAY The relay shall be of proven design and shall incorporate the following features; Rated voltage 110V AC. Rated Current 1 Amp. Initial time delay range 5-100 seconds, and ability to select Integrated delay or Definite time delay. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 82 of 270 83 SECTION V: TECHNICAL SPECIFICATIONS Inter-tap delay 1-80 seconds Relay voltage setting, adjustable in steps of 1V from 85 - 130V Line drop compensation 0-20 V at rated current for both reactive and resistive setting Under voltage inhibit range 70%-90% & over current inhibit range 150%-250% Bandwidth range 0.5-5 % of voltage level Over voltage inhibit The AVR should have a selector switch with OFF/Manual/Auto Should be of Numeric Design. The Relay shall be Designed to employ both Circulating Current Compensation or Negative (Reverse) Reactance compounding to minimize circulating current for Parallel Transformer Operation. Tap changer Maintenance, by maintaining Tap Operation count. Tap Changer Mechanism Failure. Sufficient documentation in form of instruction manuals, drawings, technical characteristics and test certificates from international/national testing/standards laboratory of the country of manufacture shall be submitted with the tender to facilitate technical evaluation. 3.7.17 PARALLEL OPERATION 3.7.17.1 A scheme for operating this transformer in parallel with other similar units of different rating shall be provided and wired in the marshalling kiosk (box) by the manufacturer ready for inter-phasing. 3.7.17.2 scheme shall maintain the transformers in stable parallel operation and limit circulating current to a minimum. 3.7.17.3 In the event of this transformer being disconnected from the system, its reconnection shall not result in its tap changer failing to operate automatically because of tapping discrepancy. 3.7.17.4 Suitable selector switch shall be provided, so that any one transformer of the group can at a time be selected as “Master”, “Follower” or “Independent”. 3.7.17.5 Necessary interlock blocking independent control when the units are in parallel shall be provided. 3.7.17.6 The scheme shall be such that only one transformer of a group can be selected as “Master”. 3.7.17.7 An out –of- step device shall be provided for each transformer which shall be arranged to prevent further tapchanging when transformers in a group operating in “Parallel control” are one tap out-of-step. 3.7.18 MARSHALLING KIOSK (Box) The marshalling kiosk shall be of outdoor, IP 55, weatherproof, vermin-proof type with a hinged, lockable door fitted with a glass panel to facilitate reading of oil and winding temperature gauges without opening the door. The kiosk shall be mounted so that its window is approximately 1600mm above ground level; and shall accommodate at least the following items:a) Winding temperature indicator for both HV and MV with a maximum pointer drag hand type with a resetting knob and three separately adjustable mercury contacts for alarm, trip and operation of cooler control circuits as required. b) Oil temperature indicator with a maximum pointer drag hand type with a resetting knob and two separately adjustable mercury contacts for alarm and trip. c) Mechanical isolating switch for the incoming 3 phase, 4 wire, 415V 50Hz supply to the marshalling kiosk. 415 volts and 240 volts socket outlets (square pins) shall also be provided in the kiosk. d) A mechanical isolating switch for the outgoing 3 phase 4-wire 415V 50Hz supply to the OLTC Motor drive unit. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 83 of 270 84 SECTION V: TECHNICAL SPECIFICATIONS e) f) Suitable starters for the cooling fan motors complete with thermal overload/single phase protection relay and normally-closed electrical auxiliary contacts for motor failure alarm/trip circuits. A selector switch with ‘OFF’, ‘HAND’ and AUTO positions for cooling fan motors g) An internal standard screw type illumination lamp and heater for the kiosk with respective switches. The lamp shall be door switch operated. h) Wiring, fuses, links, terminal boards and cable glands for bottom entry of multicore cables i) Anti-condensation heater with a switch. j) Thermostat for anti-condensation heater control. k) Hygrostat for anti-condensation heater control. l) MCB control for each of the circuits. m) Phase sequence relay for detection of wrong phase rotation for the supply to the fans and the OLTC Motor Drive Unit. Detailed technical details, drawings, and schematics shall be submitted with the tender documents for evaluation. 3.7.19 AUXILIARY SUPPLIES Equipment shall be rated for the following auxiliary power supplies: (a) Cooler control circuits: 240 V, single phase, 50Hz (b) Tap changer control: 240 V, single phase, 50Hz (c) Cooling fan motors: 415 V, three phase, 50Hz (d) Tap changer motor: 415 V, three phase, 50Hz 3.7.20 TRANSFORMER TANK AND TANK COVER 3.7.20.1 The tank shall be constructed of mild steel plates of sufficient thickness and strength and shall be complete with all accessories. It shall be designed so as to allow the complete transformer when filled with oil to be lifted by crane or jacks, transported by road, rail or on water without overstraining any joints and without causing subsequent leakage of oil. 3.7.20.2 The base of the tank shall be so designed that it shall be possible to move the complete transformer unit in any direction without injury when using rollers, and/or plates 3.7.20.3 The tank and its accessories shall be so designed as to prevent collecting or trapping of gases.Where this cannot be avoided, pipes shall be provided to vent the gas into the main expansion pipe. The vent shall have a minimum outside diameter of 19mm except for short pipes which may be 6.35mm minimum inside diameter. 3.7.20.4 All joints, other than those that may have to be broken shall be welded. Caulking of unsatisfactorily welded joints is forbidden. 3.7.20.5 The main tank body shall be pressure tested and a certificate issued by the national standards and testing laboratory ascertaining the soundness of all welded joints. A certified copy of the certificate shall be submitted with the tender for evaluation. 3.7.20.6 Tank shall be provided with lifting lugs suitable for lifting the complete transformer with oil. Furthermore, a minimum of four accessible jacking positions shall be provided to enable the complete transformer to be raised or lowered using jacks. 3.7.20.7 The transformer tank and all attachments normally under oil shall be capable of withstanding full vacuum. The oil conservator shall withstand at least 35% full Vacuum. 3.7.20.8 Tank cover shall be of such a design and construction as to prevent accumulation of water and shall be bolted to the flange on the tank top to form a weatherproof joint. 3.7.20.9 Inspection openings shall be provided as necessary to give easy access to bushings, tapping switch and for testing or general inspection. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 84 of 270 85 SECTION V: TECHNICAL SPECIFICATIONS 3.7.20.10 Tank cover and inspection covers shall be provided with suitable lifting arrangements. Inspection covers shall not weigh more than 25 kg apiece. 3.7.20.11 The tank cover shall be fitted with isolated pockets for oil and winding temperature instrument bulbs. Protection shall be provided where necessary for each capillary tube. The pocket shall be fitted with a captive screwed cap to prevent the ingress of water. Detailed drawings shall be provided. 3.7.20.12 The pocket shall be located in a position of maximum oil temperature at continuous maximum rating and it shall be possible to insert and remove the instrument bulbs without lowering the oil in the tank. 3.7.20.13 Gaskets for weather and oil-tight joint faces shall be of synthetic rubber-and-cork composition and shall have a minimum thickness of 5mm, except that where jointing faces are precision-machined thinner gaskets may be used. 3.7.21 PAINT WORK Cleaning and painting shall be in accordance with the following requirements. Any deviations in methodology shall be stated and may only be those that will produce demonstrably superior results. A test report issued by the national standards and testing laboratory shall be produced at the time of acceptance testing of the transformer. 3.7.21.1 Tanks and Accessories (a) External and internal surfaces of all transformer tanks and chambers and other fabricated steel items shall be cleaned of scale, rust and surface dirt by blast cleaning or other suitable approved method. After cleaning, these surfaces should be immediately covered with paint. (b) The exterior shall be thoroughly cleaned by shot blasting or other approved method and given priming coat followed by two coats of contrasting colours of durable weatherresisting paint. The final coat shall be high gloss of shade No. 632 (Admiralty Grey) according to BS 381C. (c) The interior of all transformer tanks and other oil-filled chambers shall be cleaned of all scale and rust by shot blasting or other approved method. Hot oil resistant varnish on white synthetic enamel/proxy paint is to be used for painting the inside of all oil filled chambers, including transformer tanks. The final coat shall be of a light-coloured anti-condensation finish. 3.7.21.2 Radiators (a) Radiators shall be thoroughly degreased and treated externally by phospating and/or other rust-inhibiting process. (b) Radiators shall be flood-painted with a primer and two coats of durable weather and oil resisting paint. The final external coat shall be high gloss of shade No. 632 (Admiralty Grey) according to BS 381C. The total paint thickness shall not be less than 80μm at any point. 3.7.22 COOLING SYSTEM 3.7.22.1 Radiators shall be supplied in banks as suitable. Each bank shall be fitted with gate valves with legible labelling for OPEN/CLOSED positions and used for full isolation from the main tank. Each radiator shall have a top and bottom isolating butterfly valve. The radiator design shall exclude accumulation of rainwater. 3.7.22.2 Radiator banks shall be mounted directly to the transformer main tank for best use of space. 3.7.22.3 Each radiator shall have a bleeding facility (to allow escape of air) on top. 3.7.22.4 Separately mounted a-c motor driven fans fitted with wire mesh guards shall be provided for the radiators. The fan motors shall be totally enclosed, weatherproof, outdoor type suitable for continuous operation and shall be fitted with terminal boxes and glands to accommodate multicore electric supply cables. Technical details of the fan motor shall be supplied with the tender. 3.7.22.5 Suitable starters, protection/warning devices, contactors and switches for the motors shall be provided as stipulated in clause 2.3.3 above. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 85 of 270 86 SECTION V: TECHNICAL SPECIFICATIONS 3.7.22.6 Suitable lifting lugs shall be provided for removal and assembly of radiators. 3.7.22.7 The complete cooling system and the fittings shall be fully co-ordinated. Where necessary, the cooling fan motors shall be fired in designed groups and in such sequence as to achieve the desired control at maximum efficiency and safety. 3.7.23 FITTINGS 3.7.23.1 Conservator The transformer shall be provided with a conservator having a filling orifice, an isolating valve, a drain valve and a cobalt free dehydrating breather (with oil seal) which shall be accessible from ground level. The drain pipe shall be located at the lowest point in the conservator in its final installed position and welded such that it can drain all the sludge in the conservator. The conservator shall be partitioned proportionately to separate the main tank oil and the tap changer oil. Each compartment to be fitted with a breather and an oil level indicator with electrical contacts for alarms. The conservator complete with drain valve shall be in such a position as not to obstruct the electrical connections to the transformer. An oil gauge shall be provided at one end of the conservator marked with oil levels that can be read by a person standing on the ground. Expansion joints may be provided in the inlet and outlet pipes to the transformer as necessary. 3.7.23.2 Gas and Oil Actuated Relay (Transformer main tank) Transformers shall be provided with a gas and oil actuated relay (Buchholz relay) of double float type with tripping contacts to detect accumulation of gas and sudden changes of oil pressure. Shut off valves and flange couplings shall be provided to facilitate easy removal of the relay without lowering oil level in the main tank. A bleed valve for gas venting, a test valve and a terminal box suitably wired to the marshalling kiosk shall also be provided. The gas venting pipe shall be brought down to a height reachable from ground level and shall be fitted with a gas sampling device at the end. Provision should be made on the relay for simulation of gas and oil surge for testing purposes. 3.7.23.3 Gas and Oil Actuated Relay (Tap changer compartment) Tap changer compartment shall be provided with a gas and oil actuated relay (Buchholz relay) of double float type with tripping contacts to detect accumulation of gas and sudden changes of oil pressure. Shut off valves and flange couplings shall be provided to facilitate easy removal of the relay without lowering oil level in the tap changer compartment. A bleed valve for gas venting, a test valve and a terminal box suitably wired to the marshalling kiosk shall also be provided. The gas venting pipe shall be brought down to a height reachable from ground level and shall be fitted with a gas sampling device at the end. Provision should be made on the relay for simulation of gas and oil surge for testing purposes. 3.7.23.4 Pressure Relief Device A pressure relief device shall be provided for the main tank, complete with trip contacts suitably wired to the marshalling kiosk. The device shall be resettable after an operation. Details of the device shall be submitted with the offer. 3.7.23.5 (a) (i) (ii) (b) Winding Temperature Indicator The transformer shall be provided with winding temperature indicator, maximum indicator and associated current transformer. The temperature indicator shall have a scale ranging from 20°C to 150°C, preferably uniformly divided and its type to be stated in the bid. The indicator shall have two sets of independently adjustable contacts as follows: Alarm Adjustable setting: 70°C to 150°C Fixed differential: Not more than 5°C Trip Adjustable setting: 70° to 150°C Fixed differential: Not more than 5°C All contacts shall be adjustable to a scale and shall be accessible on removal of the cover for dial type devices. For purposes of (i) and (ii) above, the contacts shall be KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 86 of 270 87 SECTION V: TECHNICAL SPECIFICATIONS (c) (d) (e) (f) 3.7.23.6 suitable for making or breaking 150VA between the limits of 30 and 250 V a.c. or d.c., and making 500 VA between the limits of the 110 and 250 V d.c. Isolating and test links shall be provided in a control cubicle to allow for measuring the oil temperature and testing the heater coil. The current transformer providing winding temperature indication shall be located at the discretion of the manufacturer, in the best position for the duty. Calibration of indicator shall be related to the winding having the maximum temperature rise. If the value on the winding temperature indicator varies by more than 3°C from the values derived from the tests specified in clause 5, then adjustments shall be made to the equipment to achieve these limits. Oil Temperature Indicator Transformers shall be provided with an oil temperature indicator with a maximum pointer and contacts for alarm and trip signals, similar to winding temperature indicator above. 3.7.24 ACCESSORIES The following shall be provided: 3.7.24.1 Valves with blank flanges fitted at the top and bottom for oil filtration purposes, having the following features: (a) The valve located at the bottom of the tank shall also be suitable for draining oil from the transformer tank. (b) All valves shall close with a clockwise rotation. The main inlet and outlet valves shall be provided with “open” and “closed” position indicators, visible from ground level. (c) All valves shall have provision for padlocking in the open and closed position for operation purposes. The hole for the padlock shall have a clearance of not less than 8mm and not more than 10mm. Locking pin shall be of anti-rattle design to limit noise emissions. The locking padlocks shall be provided. (d) Closed/Open positions of all valves must be clearly marked. 3.7.24.2 Oil sampling device appropriately located to obtain samples of transformer oil from the top and bottom of the tank. 3.7.24.3 Two earthing terminals located at diagonally opposite corners of the tank. 3.7.24.4 Air release valves or plugs for the main tank, suitably located. 3.7.24.5 Non-deteriorating detailed diagram and rating plates. 3.7.24.6 Other Fittings/accessories Diagram plate Plate of valves and oil piping. Motor drive electrical and protection diagram. Cooling control electrical and protection diagram. Electrical scheme for operating this in parallel with other similar units. Detailed list of the transformer equipment & fittings including their drawings, brochures & instruction manuals. Shipping data Detailed erection, installation, operation and maintenance manuals in English language. Testing Plan. Impact recorder for the whole duration of transit and a report provided afterwards. 2 Sets of keys for padlocking devices. (all control boxes as well as valves to be padlocked) 3.7.25 TRANSFORMER OIL The transformer and all associated oil immersed equipment shall be supplied oil filled. The oil shall comply with all the requirements of IEC 296 (class 1: un-inhibited oil). Tenderer shall provide the chemical composition and properties of the oil and the replacement cycle over the expected life of the transformer. 3.7.26 CAPITALIZATION KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 87 of 270 88 SECTION V: TECHNICAL SPECIFICATIONS 3.7.26.1 Transformer losses shall be capitalized at the following rates to facilitate evaluation and comparison of tenders. Load (copper) losses US$ 2577 per kW No load (Iron) losses US$ 4339 per kW NB:- Where tenders are being compared, losses will be capitalized at the above rate and added to the bid evaluated price of the transformer. 3.7.27 QUALITY MANAGEMENT SYSTEM 3.7.27.1 The supplier shall include a quality assurance programme (QAP) that will be used to ensure that the transformer design, material, workmanship, tests, service capability, maintenance and documentation, will fulfil the requirements stated in the contract documents, standards, specifications and regulations. The QAP shall be based on and include relevant parts to fulfil the requirements of ISO 9001:2000. 3.7.27.2 The Manufacturer’s Declaration of Conformity to reference standards and copies of quality management certifications including copy of valid ISO 9001: 2000 certificate shall be submitted with the tender for evaluation. 3.7.28 TESTS AND INSPECTION 3.7.28.1 The transformer shall be inspected and tested in accordance with the requirements of IEC 60076 and this specification. It shall be the responsibility of the manufacturer to perform or to have performed all the tests specified. Tenderers shall confirm the manufacturer’s capabilities in this regard when submitting tenders. Any limitations shall be clearly specified. 3.7.28.2 Certified true copies of previous Type Test Certificates and Type Test Reports issued by the relevant International or National Testing/ Standards Authority or ISO/IEC 17025/ILAC accredited laboratory shall be submitted with the offer for evaluation (all in English Language). A copy of the accreditation certificate for the laboratory shall also be submitted. Any translations of certificates and test reports into English language shall be signed and stamped by the Testing Authority. Copies of type test certificates and reports for the transformer to be submitted shall include: Dielectric tests to IEC 60076 (Lightning Impulse and Power Frequency Withstand Tests). Short circuit withstand test to IEC 60076. Temperature rise test to IEC 60076. 3.7.28.3 The transformer shall be subject to acceptance tests at the manufactures’ works before dispatch. Acceptance tests shall be witnessed by two Engineers appointed by The Kenya Ports Authority (KPA) and shall include the following: 3.7.28.4 Routine tests to IEC 60076 (to be done during acceptance testing at factory) Measurement of winding resistance Ratio test Vector group Separate source voltage withstand test Induced over-voltage Insulation resistance Oil leakage test on fully assembled transformer for 12 hours Measurement of impedance voltage Magnetic balance Measurement of no-load loss and current Measurement of load loss (at normal & extreme taps) Tests on on-load tap-changer Tests on on-load tap-changer remote control panel Efficiency at 50%, 75%, 100% loading at unity p.f and rated terminal voltage (Corrected to 75°C) Lightning impulse withstand test KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 88 of 270 89 SECTION V: TECHNICAL SPECIFICATIONS 3.7.28.5 Type Tests to IEC 60076 (to be done during acceptance testing at factory) Temperature rise test – To be performed on the two units during acceptance testing. 3.7.28.6 Additional tests (to be done during acceptance testing at factory) Measurement of power taken by the fans Insulation dissipation factor Condenser bushing capacitance and tan delta DGA (dissolved gas analysis) of the insulating oil.- To be performed before and after temperature rise test Acoustic and sound level Sweep Frequency Response Analysis Insulation tests on the auxiliary wiring in the marshalling boxes Measurement of zero sequence impedance Measurement of harmonics no-load current CT ratio and polarity Measurement of zero phase sequence impedance Paint thickness Tank pressure test 3.7.28.7 Testing Facility The manufacture shall provide current e-mail address, fax and telephone numbers and contact person at the International or National Standards and Testing Facility of the country where the transformer is manufactured and tested. 3.7.28.8 Test reports for each transformer (including its individual components) shall be submitted to The Kenya Ports Authority for approval before shipment. 3.7.28.9 On receipt of the transformer KPA will inspect it and may perform or have performed any of the relevant tests in order to verify compliance with the specification. The manufacturer shall replace/rectify without charge to KPA, equipment which upon examination, test or use fail to meet any or all of the requirements in the specification. 3.7.29 MARKING, LABELLING AND PACKING 3.7.29.1 The transformer and associated components shall be packed in a manner as to protect it from any damage in transportation and handling. 3.7.29.2 Each assembly and package of items associated with the transformer shall be suitably marked. 3.7.29.3 In addition to markings and labels required elsewhere in the specification, each equipment and component shall be marked in accordance with the relevant IEC standard. Each transformer shall be provided with a rating plate of weatherproof material, fitted in a visible position, showing the appropriate details listed in IEC 60076. The entries on the plate shall be indelibly marked (either by etching, engraving or stamping). 3.7.29.4 In addition, the name plate shall include load and no load losses for the highest, lowest and principle tap positions, temperature class of insulation, connection diagram and the inscription ‘PROPERTY OF KPA.' all marked indelibly. 3.7.30 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled. 3.8 SUB STATION LOCAL TRANSFORMER 3.8.1 SCOPE KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 89 of 270 90 SECTION V: TECHNICAL SPECIFICATIONS This specification is for a 200kVA, 11000/433 volts three phase distribution transformer for substation auxiliary supply. A changeover control panel shall be installed in the control room to enable supply changeover from either of the station transformer to the distribution boards. 3.8.2 GENERAL 3.8.2.1 The transformer shall be outdoor, oil immersed core type and shall be manufactured and tested as per IEC 76. 3.8.2.2 The complete transformer shall be painted and the final colour shall be Dark Admiralty Grey colour No.632 as per BS 381C. The inside of the tank shall be coated with oil resisting varnish or paint so that oil cannot come into contact with tank or metal at any point. 3.8.2.3 The 200kVA transformers shall be fitted with skids and provided with 40.0mm diameter axle hole for jacking lugs and suitable for concrete plinth mounting. 3.8.3 CONSTRUCTION 3.8.3.1 The transformer tank shall be constructed of corrugated mild steel plates fabricated by pressing or rolling.The transformer tank shall be sealed by means of suitable gasket or welding and be fitted with dial type thermometer and earth terminals. 3.8.3.2 The cores shall be constructed of high quality low loss grain oriented electrical steel laminations. The design shall ensure no hot sections due to overfluxing or circulating currents. The flux density at any point shall not exceed 1.65 tesla. 3.8.3.3 The windings shall be of electrolytic copper wires capable of sustaining short circuit forces on the transformer. 3.8.3.4 The high voltage winding shall have tappings at ±2 X 2.5% operated by an off-circuit switch with marked position indicators. 3.8.3.5 The three-phase transformer shall be wound to IEC vector reference Dyn11. 3.8.3.6 Outdoor weatherproof bushings, provided with screwed stem and nuts shall be mounted on the tank cover, arranged to be changed without opening transformer. The high voltage bushing shall be fitted with adjustable double-gap arcing horns set at 2 X 55mm gaps. The minimum creepage distance of the bushing shall not be less than 990mm for 11kV. 3.8.3.7 Cooling of the transformer shall be by natural circulation of oil and natural circulation of air (ONAN). 3.8.3.8 The transformer shall be filled with oil as per IEC 296. 3.8.3.9 The transformer shall be provided with a metallic name plate giving the required rating and other particulars. 3.8.4 STANDARD SIZES The standard size for the Substation local supply transformers shall be 200kVA; three phase 11000/433 Volts. 3.8.5 RATINGS 3.8.5.1 The transformer shall be capable of carrying its full normal rated current continuously under the tropical conditions stated, and at any tappings without the temperature rise in the hottest region exceeding 60°C and 65°C in oil and winding respectively. 3.8.5.2 Transformer shall be capable for sustaining a three-phase symmetrical short circuit on the low voltage side with power maintained on the high voltage side without damage or distress for 2 seconds. 3.8.5.3 The impedance voltage measured at the normal tap shall not exceed the value indicated in the following table. RATING (kVA) PHASE HIGHEST SYSTEM VOLTAGE (kV) Maximum % IMPEDANCE KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 90 of 270 91 SECTION V: TECHNICAL SPECIFICATIONS 200 3 12 4.0 The guaranteed losses shall be as indicated in the following tables, subject to a tolerance of 10% on total losses. RATING (kVA) PHASE HIGHEST NO LOAD FULL LOAD SYSTEM LOSSES $/kW LOSSES VOLTAGE (kV) $/kW 200 3 12 2577 4339 NB:- Where tenders are being compared, losses will be capitalized at the above rate and added to the bid evaluated price of the transformer. 3.8.6 TESTS 3.8.6.1 Type and routine tests shall be carried out as per IEC 76. 3.8.6.2 All transformers shall be subjected to inspection and routine tests. 3.8.6.3 Test reports shall be completed for each transformer and made available after the tests have been carried out. The following spare parts shall be supplied for the transformer: 1 – bushing of each type with conductor and terminals 1 – set of gaskets 1 – dial type thermometer. All other accessories necessary for full installation and maintenance shall be provided for the Transformer. 3.8.7 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.9 11kV UNIT SPECIFICATIONS (Refer to part B. of this section for the Technical Specifications for 11kV switchgear ) 3.10 CONTROL, MEASURING AND PROTECTIVE RELAYING EQUIPMENT 3.10.1 SCOPE This subsection covers the design, detailing, manufacture testing before shipments, packing, transport to site, erection and tests at the site of the following equipment: Set of Protective relays, controls and accessories for 132kV switchgear 3.10.2 Requirements for Design The equipment for the control system shall be highly reliable, durable and suitable for continuous operation. The equipment shall be designed to be fail – safe for the possible failure of any major circuit during the operation and shall provide a safe guard against possible surges, fail – safe against disrupted surges against disrupted signals due to outside interference that would normally be associated with the cable communication lines and any other provisions necessary for the efficient operation of the equipment. All instrument scales, coils, relay contacts and other features shall be suitable for the apparatus controlled or the purpose intended. The control and relay panels provided under this subsection shall be located in the control rooms of the substation. It shall be the contractor’s responsibility to properly design the electrical control, protective relaying, alarm and indication schemes related to all equipment to be provided under this contract and to co-ordinate with the existing control and relaying system. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 91 of 270 92 SECTION V: TECHNICAL SPECIFICATIONS The Contractor shall prepare arrangement and detailed drawings, equipment lists and wiring diagrams based on the requirements for meters, relays, control switches, indicating lamps and other devices including those to be supplied under other subsections. 3.10.3 Protection and Alarm General Protection against electrical faults and abnormal conditions on 132kV switchgear shall be conducted by the protective relays and switches. 3.11 ELECTRICAL PROTECTIVE RELAYS AND PANELS 3.11.1 General The electrical Measuring protective relays for the 132 kV line shall be of Numeric Design type suitable for operation with the current transformer secondary of 1A and the voltage transformer secondary of 110V, as shown on the single line diagrams. Auxiliary relays of Static or ELECTROMECHANICAL DESIGN are acceptable. The protective relays and their auxiliary relays shall operate successfully for any value of the DC supply voltage between 85% and 120% of the rated voltage of 110V without exceeding the temperature rise limits for the operating coils. The protective relays and necessary auxiliaries shall be housed in the metal – enclosed cubicle. Each protective relay shall be of the flush mounted, back connected, dustproof switch board type with rectangular case. Each relay shall have a removable transparent cover or cover with a transparent window, with provision for sealing. It is preferred that each measuring relay shall be of a withdrawable type from the front of the panel with sliding contacts, without opening the current transformer secondary circuits, disturbing external circuits or requiring disconnection of leads on the rear of the panels. Each protective relay shall be equipped with a red operation indicator and contacts for operation on 110 Volt DC for each phase, and external, front operated, manual-resetting device. Each protective relay shall be equipped with adequate electrically independent contacts of adequate rating for trip and alarm functions. Test facilities shall be provided as an integral part of each protective Switchgear relay panel for testing of current and voltage transformer secondary circuits and trip circuit using secondary injection test equipment. 3.12 DETAILED SPECIFICATIONS FOR RELAYS, ENERGY METER, TRIP BATTERY & CHARGER. These specifications indicate the required performance characteristics. 3.12.1 PROTECTION RELAYS. This must satisfy the requirements for distance, Three Phase Overcurrent and Earth Fault Relay and Sensitive Earth Fault Relay. NB: See detailed specifications for each of the above protection functions, below. Restricted Earth fault relay Relay must be of Numerical type Relay should reject harmonics produced by C.T saturation The offer should include the associated stabilising resistor and voltage dependent resistor (metrosil) Current setting range 0.05-0.8In Operating time < 25ms at 5 times the setting Three phase overcurrent and earth fault relay Should incorporate the following Features; Relay must be of Numerical Type KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 92 of 270 93 SECTION V: TECHNICAL SPECIFICATIONS Current setting range for overcurrent relay 0.5In-2.4In Current setting range for earth fault relay 0.05In-0.8In I.D.M.T characteristics according to BS142 or IEC255 i.e. SI,VI,EI,LTI, including definite time for the high-set Elements. Time setting multiplier 0.05 - 1.0 Broken conductor protection feature Negative sequence Protection Feature High set Element for both overcurrent and earth fault Protection, with a setting range of 1-30In. Thermal Protection Dedicated Breaker Fail Protection. Circuit Breaker Maintenance Fault records, Event Records and disturbance records. Configurable output relays with ability to output starting elements to control Tripping of other upstream Protection relays. Drop off /pickup ratio >90% Low transient overreach < 10% Earth Fault Relay. Should incorporate the following Features; Relay must be of Numerical Type Current setting range 0.05In-0.8In I.D.M.T characteristics according to BS142 or IEC255 i.e. SI, VI, EI, LTI, including definite time for the high-set Elements. Time setting multiplier 0.05 - 1.0 Highset Element with a setting range of 1-30In. Circuit Breaker Maintenance Fault records, Event Records and disturbance records. Configurable output relays with ability to output starting elements to control Tripping of other upstream Protection relays. Drop off /pickup ratio >90% Low transient overreach < 10% Sensitive Earth Fault Relay. Should incorporate the following Features; Relay must be of Numerical Type Current setting range for earth fault relay 0.005In- 0.8In Definite time delay characteristic; setting range, 0- 30 Seconds. Circuit Breaker Maintenance Fault records, Event Records and disturbance records. Drop off /pickup ratio >90% Low transient overreach < 10% Three- Phase Directional Overcurrent and Earth Fault Relay. Should incorporate the following Features; Relay must be of Numerical design. Current setting range for overcurrent relay 0.5In-2.4In Current setting range for earth fault relay 0.05In-0.8In Quadrature connection for polarising voltage (Vn=110) Applicable on the LV side of a Dyn1 transformer High set Element, with a setting range of 1-32In The phase and earth directional elements should be individually selectable. I.D.M.T characteristics according to BS 142 or IEC 255 and Definite time characteristic KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 93 of 270 94 SECTION V: TECHNICAL SPECIFICATIONS Relay equal The normal operating boundary shall be +/-90 degrees from relay characteristic angle sensitivity should be 1% of rated value of current and current polarising voltage at an angle to the relay characteristic angle. Time setting multiplier 0.05 - 1.0 Broken conductor protection feature Negative sequence Protection Feature Highset Element for both overcurrent and earth fault Protection, with a setting range of 130In. Thermal Protection. Dedicated Breaker Fail Protection. Circuit Breaker Maintenance Incorporate Fault records, Event Records and disturbance records. Configurable output relays with ability to output starting elements to control Tripping of other upstream Protection relays. Trip relay High burden tripping relay, immune to capacitance discharge currents and leakage currents At least 8 pairs of outputs contacts two of which should be normally closed (NC) contacts Instantaneous operation, t <12ms Flag or target should be a red L.E.D or bulb and should be electrically reset Trip circuit supervision Relay The relay should have the following features Continuous supervision of trip circuit for circuit breaker in both OPEN& CLOSE position Trip circuit fail - Red L.E.D Trip Circuit Healthy – Green L.E.D Contacts should be available to wired for annunciation and scada Two normally closed and three normally open output contacts NB: The relay L.E.Ds should be visible from the front of the panel without opening the panel door(s). Annunciator unit Should have Silence, Accept and Reset Accommodate 18 alarm Elements Relay output for audible alarm and self supervision Integrated event register to provide analysis of the latest five (5) events Discrepancy switch for circuit breaker control At least 2 pairs of contacts for CB closing At least 2 pairs of contacts for CB tripping For operation up to 110 V dc Semaphore for isolator and earth switch position indication Preferably with Red L.E.D for ON indication and Green L.E.D for OFF Indication. Transducers: MW Transducer: Connection shall be 3-Phase 3or 4-Wire Inputs 110V AC and 1Amp Output shall be 0 - +/- 20 mA Auxiliary power supply shall be 110 V AC, separately connected. MVAr Transducer: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 94 of 270 95 SECTION V: TECHNICAL SPECIFICATIONS Connection shall be 3-Phase 3 or 4-Wire Inputs 110V AC and 1Amp Output shall be 0 - +/- 20 mA Auxiliary power supply shall be 110 V AC, separately connected. Current Transducer: Input 0- 1Amp Output 0 – 20 mA Auxiliary power supply shall be 110 V AC iv)Voltage Transducer: Input 0- 110 Volts Output 0 – 20 mA Auxiliary power supply shall be 110 V AC, separately connected. Breaker Failure Protection Relay The breaker fail protection relay should have the following features: Numeric design Circuit –breaker failure protection, single or three pole with or without current Three phase overcurrent detectors. Earth fault detector. 2 out of 4 check of current detectors Independently settable delay times for operation with and without current “No current” condition control using the circuit-breaker auxiliary contacts Two stage delay, hence two stages of operation Trip command input. Necessary logic to determine breaker fail condition. Operator keypad with display Display of line measured current values Serial Interface Annunciation and storage of previous events. Self monitoring Pole discrepancy Flush mounting LEDs to show phase and stage of operation. Biased Differential protection for a two winding transformer This should incorporate the following Features; Relay Must be of Numerical design Pick up setting range, 0.1 to 0.5In Should incorporate a high-set Element with a setting range of up to 20In. Magnetising current inrush restraint Integral CT ratio compensation(0.1-2) and vector group compensation Measurement and indication on the MMI, of phase (HV&LV) ,differential and bias currents. Storage of Fault records and Event records; the Fault flags should be accessible on the relay LCD screen without opening the relay cover. Separate function that performs ovefluxing protection with alarm and trip functions. 5th harmonic restraint feature on the differential Element. Appropriate Dual Bias characteristic to ensure relay stability for heavy through faults Should incorporate a disturbance recorder feature. Red L.E.D to indicate Tripping Relay Self diagnostic and Alarm feature Ability to Latch output contacts to prevent Transformer re-energisation before carrying out investigations. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 95 of 270 96 SECTION V: TECHNICAL SPECIFICATIONS Other specifications i) TESTING FACILITIES Separate Test facilities for each AC current, voltage and voltage transformer secondary circuit so as to give access for testing of each protective relay and its associated circuits. This may consist of either test terminals blocks for the front of the panel mounting with automatic short circuiting of the current secondary by means of movement of links from their normal operating position, or a relay test block mounted adjacent to each or any other suitable testing arrangement. Each current transformer circuit shall be earthed through a removable link at one point only. The common Protection trip and Alarm circuit for each Panel shall be provided with an isolation link to facilitate Testing and Breakdown Maintenance. ii) RELAYS All measurement relays must be of Numeric design. Static relays can be offered where there are no equivalent relays of Numeric design. Electromechanical relays are acceptable only for use as Auxiliary relays and contactors, NOT as Measuring Relays. Relays contacts shall be suitable for making and breaking the maximum currents, which they may be required to control in normal service. Where contacts of the protective relays are unable to deal directly with the tripping currents, Auxiliary Trip relays shall be provided. Relays contacts shall make firmly without bounce and the whole of the relay mechanism shall be as far as possible unaffected by vibration or external magnetic fields. Relays shall be provided with clearly inscribed labels describing their application and to include the (IEC) Device Function number. To minimize the effects of electrolysis, relay coils operating on DC shall be so connected that the coils are not continuously connected from the positive pole of the battery. Relays shall be suitable for operating on the station 110V DC supply without the use of dropping resistors or diodes. The relay thermal rating should be such that the fault current clearance times on any combination of current and time multiplier setting shall not exceed the thermal withstand capability of the relay (Maximum Fault current=25 KA) The relays must be IEC 60255 and EMC 89/336/EEC compliant. iii) RELAY PROGRAMMING SOFTWARE AND CONNECTION CABLES: Software must be provided for Programming and downloading Data for all Numerical Relays supplied. The software Users Guide shall also be supplied. The Numerical Relays will be equipped with an RS232 Communication Port on the front to facilitate connection to a Laptop. There shall be two extra ports on the back for communication to regional control and National control independently. The relevant communication cable, between the Relay and the Laptop shall also be provided (3 cables). Also communication facilities shall be provided on each Numerical Relay for Remote Interrogation and Programming of the Numerical Relays. The Relays will also have an MMI to facilitate manual Relay programming and Data access. Relay Operation due to system fault, shall be indicated by a Red L.E.D. and the fault details (flags) shall be displayed on the MMI. Both the Relay Fault flags and Red L.E.D will be reset without opening the Relay Cover. 3.12.2 Control Any computer solution proposed shall be based on hardware and software well proven in HV installations. All data storage media shall be checked for internal faults and virus before delivery. All data and parameters specified to the individual distributed control units, shall be stored in a non-volatile memory so no local logic or information will be lost due to power supply failure. Remote and Local Control The substations shall be provided with a microprocessor based substation control and signalling system (SCS). The system shall accommodate control, data acquisition, alarm handling and trend KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 96 of 270 97 SECTION V: TECHNICAL SPECIFICATIONS analysis. The figure below illustrates the main principles. However, the Employer wants to keep a conventional back up control facility with indication at bay level (local control). I.e. control of motorised breakers and switches, status indication of all breakers and switches, analogue or digital indication of measurands (I and Imax all phases), MW and MVAr) and alarm annunciation shall be presented by discrete components. The control of high and medium voltage circuit breakers, isolating switches and tap changers shall take place in a hierarchy with four levels as described in Project Specific Data Section. From each level one may block access from higher levels. The control units shall take auxiliary voltage form the station battery and be equipped with self-supervision systems giving alarm by internal faults. The system shall be fail-safe keeping all equipment in the last status by loss of communication to higher systems. The system shall be of the state-of-art based on IEC 61850 for operation under electrical conditions present in high-voltage substations, follow the latest engineering practice, and ensure long-term compatibility requirements and continuity of equipment supply and the safety of the operating staff. Maintenance, modification or extension of components may not cause a shut-down of the whole substation automation system. Self-monitoring of single components, modules and communication shall be incorporated to increase the availability and the reliability of the equipment and minimize maintenance. For safety and availability reasons the Substation Automation System shall be based on a decentralized architecture and on a concept of bay-oriented, distributed intelligence. Functions shall be decentralized, object-oriented and located as close as possible to the process. The main process information of the station shall be stored in distributed databases. The typical SA layout shall be structured in two levels, i.e. in a station and a bay level. To provide highest reliability the station HMI and the gateways shall work completely independent meaning retrieving the process data directly from the bay level devices. Mombasa Port 132kV Transmission line & substation project KPA Additionally the gateway and the station HMI shall be configured fully redundant to ensure full functionality in case of single point of failure. The data concentrator and the station computer shall be connected to a redundant LAN. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 97 of 270 98 SECTION V: TECHNICAL SPECIFICATIONS 3.12.3 Control Stations Distributed Control Units Outdoor switchgear shall have a control and relay panel in the control room with facilities for Local Control. The local control for indoor breakers can be located in the instrument cabinet. The protection and control functions can also be combined in one unit. Signals from protection equipment can alternatively be hardwired to bay control unit. The bay control unit shall handle position indications from circuit breakers, disconnectors, earthing switches and transformer tap changer. It shall control closing and opening of circuit breakers and receive time tag, store and display alarms and measurements. The position indication from the on load tap changer shall be taken from a potentiometer switch supplied and mounted on the transformer. The alarm handling capacity must be sufficient to handle all normal alarms from the switchgear, the protection, the transformer and the tap changer. All commands from the remote and supervisory control can be given to bay control unit, which execute the commands. Conventional interlocks should be retained. All microprocessor based control equipment such as bay control units shall be galvanic ally isolated from the environments outside panels, using opto couplers or interposing relays for signals, galvanic isolated measuring transducers for measurements and relays or contactors for commands. All data and parameters specified to the individual distributed control units, shall be stored in a non-volatile memory so no local logic or information will be lost due to power supply failure. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 98 of 270 99 SECTION V: TECHNICAL SPECIFICATIONS Editing and input of local data and parameters shall be performed locally by suitable programming equipment to be included in the supply. Preferably it should also be possible to edit any such local data at higher control level and download this information. Interface with Supervisory Control and Data Facilities In order to interface and achieve the desired functionality of the SCADA/EMS system, it should be noted that data concentrators at the substation shall be based on standard IEC 60870- 5-101 protocol. It should be noted that the following SCADA facilities shall be available from the substation. Supervisory control of all circuit breakers and motorized line and bus bar isolators. Remote control of on-load tap changers. Status Indications of all circuit breakers, isolators, positions of on-load tap changers and ‘local/remote’, ‘Automatic/ Manual’, Main/Follower mode of automatic voltage regulators where applicable. These shall be reported by exception, but system shall allow scan by demand. Alarms; Bay alarms, Transformer alarms, Bus bar alarms, station alarms and warning shall be collected by the SCADA. Measurements; bus bar voltages, frequency active & reactive power, 30, 48 & 110 V DC voltages and line currents. Energy measurements, this shall be at interconnection points and feeders. Where data concentrators will capture and process data for transmission to the control centres it is expected that the following functions shall be provided: Single command outputs, double command outputs for supervisory (on/off) control of circuit breakers, isolators etc with check-before-execute function. Regulation command outputs e.g. raise/lower command outputs for transformer tap changer control and set point transmission with validity check before execution. Single and double state digital inputs. Each status (open/closed) of two state devices such as circuit breakers or isolator position should be acquired independent from each other and checked for validity. Undefined states like open and closed or neither open nor closed shall be alarmed with run-time monitoring adapted to the HV equipment operation parameters. Transformer tap changer position indication should be processed as coded signals, by digital measurement input modules. Analogue measured inputs with pre-processing including validity check, local limit supervision and measurement transmission on exception (only if a significant individually selectable change occurs). Measurement transmission with a resolution of at least 10 bit plus sign as this is the most economical way to increase the overall accuracy of the measurements. Metering pulse inputs for acquisition of energy values with internal storage to allow cyclic acquisition of meter readings. Sequential event recording with time stamping of events (time stamp 10ms, resolution 1 ms) Selectable priority levels for data acquisition to speed up the acquisition of circuit breaker status changes and important measurements. The Contractor shall as part of his supply fill in I/O lists for each substation on the format specified by the SCADA supplier. The I/O lists will comprise the name tag, address tag (fitted to the SCADA Contractor's system of addressing the information), ASDU type in accordance with the agreed interoperability list and other information as required. Protocols The Station Controller shall be set up for communication with the Control Centre over a serial interface with protocol IEC 60870-5-101 and network interface with protocol IEC 60870-5-101. Switching between the two must be allowed for at any time by changing software parameters. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 99 of 270 100 SECTION V: TECHNICAL SPECIFICATIONS An international open and defined User Convention must be used (e.g. “Norwegian User Convention or similar) and the Contractor shall inform on which convention he intends to use. Internally between bay controllers and station controller the Contractor may use an open (not proprietary) protocol of his own choice. However, the station controller must be able to receive and transmit information from future extensions on an IEC 60870-5-101 protocol. Communication All communication between bay units and between bay units and station controller/workstation shall be on a bus structure, preferably by fibre optic cable. Indicating and Metering Instruments and Metering Transducers (if used) Remote indication of measurands shall take place on the station controller’s VDU. Local instruments are used they shall be of the dial type which is easily legible, with black graduations and numerals on a white background. The instruments shall have a dimension of 96 x 96 mm. The error of the instruments shall be maximum 1.5% reckoned on the total length of the scale. All instruments shall be of a narrow frame type. Preferably the measurements shall be performed directly in the SCS or in the protection relays. However, if needed, the metering transducers (converters) shall be installed in the boards and shall be suitable for connection to the potential and current transformers. The cases shall be hermetically sealed against moisture and dust. Transducer output shall be an impressed DC current of 0-10 mA output. The maximum meter reading at the receiving end shall be equivalent to 30% overload of the source value. The permitted resistive load shall be Mat least 1000 ohms. The accuracy class shall be minimum 1%. The auxiliary voltage, if required (preferably not) shall be 110 V or 30 V DC. The W and VAr measurements shall be of the three-element (threewattmeter) type when connected to primary systems with grounded neutral. W and VAr measurements for transmission lines, shall be such that the direction of the power flow is indicated by negative direction towards the substation and positive direction out of the substation. The voltage shall be measured phase-phase voltage, one reading is sufficient. The scale on the different types of instruments shall be proposed by the Contractor and be subject to approval by the Project Manager. Programming and Fault Finding Editing and input of local data and parameters shall be performed locally by suitable programming equipment to be included in the supply. Preferably it should also be possible to edit any such local data at higher control level and download this information. The programming equipment shall also be suitable for fault diagnostic. 3.12.4 THE ENERGY METER SPECIFICATIONS FOR CLASS 0.2S ELECTRONIC ENERGY METERS 1 2 3 4 5 6 7 The meters shall conform fully to IEC 687 for class 0.2S Energy Meters and any other relevant specifications. The meters shall be programmable and relevant software and connection cable to laptop shall be provided. Meters complying with IEC 61334-4-4-1(DLMS Standard protocol) shall be preferred. The meters shall have memory and be capable of storage of at least 12 months load profile and other data. The meters shall be capable of bi-directional metering so as to record faithfully, both export and import quantities. The accuracy shall be as per IEC 687 in both directions. The quantities to be displayed shall be determined by the user through use of software that shall be provided. The meters shall be configurable for use in three phase 3 /4-wire networks systems as follows:3x240/415 V, 10 (100) A 3x240/415 V, /5 (1) A 3x /110V, /5 (1) A The meters shall be usable on phase voltages of magnitudes ranging from 100V to 500V, 50 Hz. Meters shall be with voltage-surge protection that meets IEC 687 specifications. The meters shall be for flush panel mounting KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 100 of 270 101 SECTION V: TECHNICAL SPECIFICATIONS 8 The meters shall have a non-volatile memory so as to ensure no loss of data during power failures. Security passwords and switches shall be provided to prevent unauthorized programming of the meter. 9 The meters shall be suitable for operation in any part of the Republic of Kenya where the climate varies largely from temperatures between -5 and 40 Degrees Celsius and relative humidity reaching 95% in some parts. Operating altitudes ranging from sea level to 2200 metres above sea level. 10 The meters shall support multi-tariff metering. 11 The Meters shall incorporate instrumentation for the following measurands: MW, MVAR, MVA, p.f., Phase Currents, Phase voltages and the angle between individual Phase Voltage and corresponding phase current. This measurands shall be visible on the Meter display. 12 The meters MUST have a capability of freezing billing readings on any selected date of the month. 13 The meters will measure maximum demand for MW, MVAR and MVA and these will be accessible on the Meter display. The Demand integration period will be programmable. 14 The CT and VT ratios shall be programmable. 15 The meters shall have an accurate internal quartz controlled clock. It should be possible to reset the clock without loss of billing data. 16 The supplier shall show proof of ISO 9000 and ISO 14000 standards compliance. 17 The meters shall be provided with adequate sealing facilities to prevent tampering. 18 The nameplate and meter details shall be clearly marked using materials and colours that are durable and indelible. 19 In addition to requirements of IEC 687 the name-plate shall carry the following particulars: (a) The inscription “The property of Kenya Ports Authority.” (b) Owner’s serial numbers as directed with a minimum 5mm figure height. (c) Year of manufacture. 20 The meter base cover shall be of non-metallic, non-hygroscopic, flame retardant, polished material having high impact-resilience and low dirt absorption properties.The front cover may be of translucent material with a clear transparent front. 21 The meter shall have a minimum of three sealing - provisions for the meter body, terminal cover and front cover (where applicable). 22 The meter terminal cover shall be the normal short length with provisions of easy bottom breakage for cable entry. The terminals shall be of bottom entry, and the arrangement shall be:L1 L 1: L2 L2: L3 L3: N or I1 V1 I1: I2 V2 I2: I3 V3 I3: N 23 The accuracy shall be Class 0.2 24 The meter errors shall comply with the requirement IEC 687 and shall be adjusted at the manufacturer’s works to be within 0.2% between low and high load and shall exhibit good stability. 25 The meter shall have a warranty against any defects, which may develop due to faulty material, calibration, transportation or workmanship for a period of not less than eighteen months from the date of delivery. All defective meters shall be replaced at the supplier’s cost. 26 The following drawings and information shall be required with the tender: (a) Meter drawing giving all the relevant dimensions. (b) Wiring diagrams. (c) Description leaflet including details of programming of the meters (d) User’s and service manuals. 3.12.5 BATTERIES & CHARGER (110 & 48 Volts) I) PROTECTION AND CONTROL BATTERIES. The Batteries should be Valve Regulated maintenance free with the following Specs: 1. Capacity 400 Ah at 10 hour discharge rate to 1.85V minimum @20°C. 2. Cells should be complete with all corrosive resistant terminals, links fasteners and terminal covers and cell record book and labels. Terminals also clearly indicated positive (+) and negative (-). Specifications data are to be attached to each cell. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 101 of 270 102 SECTION V: TECHNICAL SPECIFICATIONS 3. 4. 5. 6. 2.0 Volts nominal voltage per unit Cells should be capable of delivering 100% capacity at 20°C. Container need not to be transparent. Each cell should be of robust construction all round, having fire and mechanical shock resistant lid/cover assembly. 7. Documentary evidence of the Design Service life at 20°C of the batteries must be attached. Those under 12 years service life will not be considered. 8. All cells of a bank should be of the same dimensions, weight, make,voltage and ampere hour capacity. 9. The Batteries to be used for protection and control in power stations whose standby requirement is 10 hours minimum. 10. The chargers to be used with the batteries are constant potential chargers. 11. Supply should be accompanied by a set of detailed instruction manual on maintenance, Design and operation in English and should include any special instructions. The manuals to include operational curves and data limits. 12. The Units should have low internal resistance which should be indicated in the manuals. 13. The batteries should have low gas emission whose volume should be indicated in the manual. 14. A list of previous supply to power utilities with quantities for the same battery function should be included in the tender as documentary proof. II). BATTERY CHARGER 110 VOLTS Type Automatic constant voltage float/boost battery charger Input i. Input Voltage – 240V Single phase +/- 13% ii. Frequency – 50 Hz +/- 5%. DC Output i. Nominal – 110V ii. Current – 75A min. iii. Float setting – 129V iv. Boost setting – 156V DC Output Voltage Regulation (rms) i. Float mode: +/- 1% ii. Boost mode: +1%; -4% iii. For 0- 100% full load and within the input supply limits iv. 7% of the battery capacity Operation i. Altitude: 0 – 100m a.s.l ii. Temperature: 0 to 40°C iii. Humidity: 20 – 90% iv. Natural air convection Fault Protection i. AC mains input MCB ii. DC output fuse for reverse polarity protection iii. Automatic current-limiting into load fault condition Current Limit i. Set at 100% of full load current Instruments i. DIN 72 flush mounting DC output ammeter scaled 0 – 75A ii. DIN 72 flush mounting DC voltmeter scaled 0 – 160V iii. DIN 72 flush mounting AC voltmeter scale 0 – 250 V Controls i. Illuminated AC on/off mains input MCB fitted on the front panel ii. Manual float/boost selection switch fitted on the front panel iii. Alarm cancellation push button Alarms i. Mains failure ii. DC failure KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 102 of 270 103 SECTION V: TECHNICAL SPECIFICATIONS iii. Positive E/fault iv. Negative E/fault v. All the above to have LED indication fitted on the front panel Distribution i. At least 4 pairs of unfused terminals for the protection circuits. General i. The charger should be of free standing type ii. Technical specifications data, and detailed instruction manual on erection, commissioning, operation, maintenance, trouble shooting, spares catalogue and including any special instructions shall be provided. The manual must be in English. III) BATTERY CHARGER 48 VOLTS Type Automatic constant voltage float/boost battery charger Input i. Input Voltage – 240V Single phase +/- 13% ii. Frequency – 50 Hz +/- 5%. DC Output i. Nominal – 48V ii. Current – 45A min. iii. Float setting – 54V iv. Boost setting – 60V DC Output Voltage Regulation (RMS) i. Float mode: +/- 1% ii. Boost mode: +1%; -4% iii. For 0- 100% full load and within the input supply limits iv. 7% of the battery capacity Operation i. Altitude: 0 – 1500m a.s.l ii. Temperature: 0 to 40°C iii. Humidity: 20 – 90% iv. Natural air convection Fault Protection i. AC mains input MCB ii. DC output fuse for reverse polarity protection ii. Automatic current-limiting into load fault condition Current Limit i. Set at 100% of full load current Instruments i. DIN 72 flush mounting DC output ammeter scaled 0 – 55A ii. DIN 72 flush mounting DC voltmeter scaled 0 – 75V iii. DIN 72 flush mounting AC voltmeter scale 0 – 250 V Controls i. Illuminated AC on/off mains input MCB fitted on the front panel ii. Manual float/boost selection switch fitted on the front panel iii. Alarm cancellation push button Alarms i. Mains failure ii. DC failure iii. Positive E/fault iv. Negative E/fault v. All the above to have LED indication fitted o the front panel Distribution i. At least 4 pairs of unfused terminals for the communication circuits. General iii. The charger should be of free standing type KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 103 of 270 104 SECTION V: TECHNICAL SPECIFICATIONS iv. Technical specifications data, and detailed instruction manual on erection, commissioning, operation, maintenance, trouble shooting, spares catalogue and including any special instructions should be provided. The manual must be in English. 3.12.6 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled 3.13 TELECOMMUNICATION EQUIPMENT It is proposed to have a 48 fibre OPGW on the line its associated Terminal equipment, RTU for SCADA and a telephone extension. 3.13.1 OPGW, COMMUNICATION EQUIPMENT AND SCADA REQUIREMENTS The Scope will include Supply and Installation of communications, telephones, teleprotection and SCADA equipment for the efficient supervision, control, operation and maintenance of the transmission system. 3.13.2 SCOPE OF WORK The Scope will include Supply and Installation of communications, telephones, teleprotection and SCADA equipment for the efficient supervision, control, operation and maintenance of the transmission system. Optical fibre communication link with its associated terminal equipment is required from the Kipevu Substation to the new Mombasa Port Substation. The contractor shall include detailed system design, manufacture, supply, installation, testing, commissioning, remedying of defects, maintaining the works during the defects liability period and any incidental work necessary for the proper completion of the work in accordance with this contract. FATs shall be carried out for fibre, OLTE and RTU as per cls 1.24. Training shall be carried out for RTU and SDH equipment. Detailed requirements are as follows:System design – The system design and preparation of contractor's drawings to approval of the Engineer Supply and installation of fibre optic lead-in cables including mounting hardware and splicing. Supply and installation of lead in cables to the equipment terminals Supply and installation of fibre optic terminal and multiplexing Supply and installation of supervisory management system and cabling to the relevant distribution frame(s) Supply and installation of DC power supplies to the new substation. Factory testing of the terminal equipment and supervisory prior to delivery. Testing and commissioning of the systems up to the terminal equipment and integration to existing SCADA system. The OLTEs shall be incorporated in the existing network management system. Multiplexed signals for permissive and direct inter-trips for the 132 circuits 3.13.3 OPTICAL GROUND WIRE (OPGW) The transmission line earth wire integrating optical fibres shall be of design and construction to ensure long service with high economy and low maintenance costs. It shall be suitable in every respect for continuous operation at nominal parameters as well as in transient operating conditions under the climatic conditions peculiar to the site. The OPGW shall incorporate at least 48 optical fibres. The OPGW constitution shall be of stranded aluminum-clad steel (ACS) wires or Galvanized steel wires (GS). Other OPGW types are acceptable if the required performance characteristics are met. All materials used shall be of the best quality and workmanship, and shall be of the highest class throughout with the designs and dimensions of all parts such that the stresses to which the OPGW are subjected to shall not render them liable to distortion or damage under the most severe conditions encountered during installation as well as in service. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 104 of 270 105 SECTION V: TECHNICAL SPECIFICATIONS Special attention shall be paid to the OPGW stranding process to ensure the necessary tightness between different layers in order to avoid slippage or relative movement of strands or cage formation during stringing Stranding tolerances as well as inspection and testing shall be as per IEC 61089 as far as applicable, and to the respective manufacturing standards. The OPGW manufacturer shall have ISO 9000 quality assurance system certified and shall prove a minimum experience in successful supply of similar OPGW in the last 5 years. The OPGW installation shall include all cable fittings (tension and suspension spirals, vibration dampers, earth connection etc.), joint boxes, termination boxes, fibre connectors and other accessories required for a complete working fibre link. 3.13.3.1 Optical fibre parameter and performance The OPGW, access cables and underground cables shall have at least 48 (forty-eight) single mode optical fibres with following characteristics: Transmission wavelength: 1310 nm and 1550 nm Mode field diameter: 9.0 to 11.5 micrometers (mm), including tolerances Optical cladding diameter: 125 mm ± 2.4% Cable Attenuation: not greater than 0.38 dB/km for every fibre in every drum at optical wavelength of 1310 nm; and not greater than 0.25 dB/km for every fibre in every drum at optical wavelength of 1550 nm Joint attenuation: not greater than 0.1 dB at optical wavelength of 1310 nm and not greater than 0.2 dB at 1550 nm for every fibre, measured on the fully installed joint Total dispersion: not greater than 3.5 ps/km.nm at optical wavelength of 1310 nm and not greater than 19.0 ps/km.nm at optical wavelength of 1550 nm Core numerical aperture: less than 0.23 Life span: greater than 30 years The Contractor is required to supply a graph of attenuation versus wavelength over the range of 1200 nm to 1600 nm No joints shall be allowed in any fibre in any drum length. Discontinuities will be acceptable if: Less than 0.10 dB in magnitude measured at 1310 nm, and OTDR traces from both ends of the cable at 1310 and 1550 nm wavelength show a difference of less than 0.05 dB/km for every fibre in every drum. Power Meter & Light source. The test shall be used to verify that the measured loss is in average equal or less than the calculated link budget. The Contractor shall state the refractive index of the optical fibres at 1310 nm and 1550 nm. 3.13.3.2 Splice Boxes The OPGW shall generally be cut and jointed at angle towers, but not at all angle points. It shall be continuously strung with OPGW sections as long as possible. At all angle points the prescribed minimum bending radius shall be observed. If necessary, special tandem or multiple stringing blocks have to be used for stringing the OPGW at angle points. Bidders shall supply detailed information, including physical dimensions and weights, of joint, gantry and termination boxes that they propose using. Joint boxes shall be used to join sections of the OPGW together along the route. The joint boxes shall be of the 'hood' type with encapsulated cable entry and they shall be mounted within the framework of the transmission towers not less than 8 m above the base. Note: All fibre jointing and testing shall be carried out at ground level, after which the joint box shall be lifted into position and the cable loops carefully secured to the tower members in such a manner that there is no risk of damage to the cable from persons climbing the towers. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 105 of 270 106 SECTION V: TECHNICAL SPECIFICATIONS 3.13.3.3 Cable Accessories Contractors shall provide detailed specifications for all types of cable accessories (anchor and suspension spirals, vibration dampers, earth connections and clamps, etc.) used in the installation of the OPGW. Optical ground wire suspension and tension assemblies shall be based on pre-formed spiral armatures according to the OPGW cable manufacturer's specification so as to assure the required minimum bending radius of the ground wire and to avoid concentrations of mechanical stresses applied to the cable. The suspension assemblies (armor grip suspension) shall be based on helical rods made of high-tensile, corrosion-resistant aluminum alloy. For the tension assemblies the helical rods shall be of aluminum clad steel for the ACS type OPGW. It is understood that all other small parts, for instance for fixing the OPGW along the tower structure from the earth wire peak up to the OPGW joint box and cable accessories are supplied under the contract. The safety factors for the OPGW suspension and tension assemblies shall be at least equal to those prescribed for the earth wire as per VDE 0210. The manufacturer of the spiral armatures shall have experience of at least 5 years successful production of the offered type of fittings. Fibre standard ITU-T G.652 – D 3.13.4 TERMINAL EQUIPMENT The terminal equipment shall be the type SDH STM-1 optical terminal equipment. Communication equipment in Mombasa Port Substation: SDH (STM-1) multiplexer shall be installed in racks that are EMC compatible and suitable to work in HV system environments. The multiplexer shall be based on the SDH technology, working on the basic transmission Bit Rate of 155.520 Mbit/s (STM-1). It shall be in accordance with the latest ITU-T SDH recommendations such as: G.703, G.704, G774, G.783, G.784, G.785, G.811, G.812, G.813, G.823, G.825, G.826 and M.3010. The equipment shall be able to perform both, multiplexing and line terminating functions. The SDH Equipment (Terminal Equipment, Add/Drop Multiplex, Synchronous Digital Cross- Connect) to be offered shall meet the following requirements: It shall have at least all the functions outlined in ITU-T G.783. The PDH electrical tributary interfaces to the SDH equipment shall conform to ITUT G.703. The SDH electrical and optical interfaces shall conform to ITU-T G.703 and G.957. The cross-connect offered shall be capable of providing non-blocking connection between virtual containers. The Optical Power to be offered shall be such that under normal operating condition, the BER of the system at the receiver is better than 1x10-10. Error performance versus the receive signal shall be verified during the factory acceptance tests. The multiplex structure shall conform to ITU-T G.707. Details of the Multiplex structure for the offered equipment including the usage of the overhead bits shall be detailed with the offer. The synchronous optical interface protection shall be achieved by having 1+1 protection. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 106 of 270 107 SECTION V: TECHNICAL SPECIFICATIONS The laser shall automatically cut-off when the link is disturbed. Redundant cross connect, where failure on either one shall not cause link outage, and path protection on the traffic interface and the 2 Mbit/s levels shall also be provided. Timing and synchronization shall conform to ITU-T G. 783, G.811, G.812 and G.813. Timing references, number of timing references available, switching time to a different timing reference, type and level of clocks shall be stated in the offer. The equipment shall automatically switch to another clock if the reference timing is lost and automatically revert back upon restoration. The accuracy of the internal clock as well as the details of the clock signal distribution shall also be stated in the offer. The equipment shall be capable of diverting timing references between the STM-1, 2 Mbit/s and a G.703 tributary interfaces. The SDH equipment shall be wired for the full STM-1 capacity, however equipped under the scope of this specification to receive at least four (4) PCM tributaries as specified below. However, if higher PDH signals other than the 2 Mbit/s are required to be routed through, the same shall be possible just by adding the respective interface cards and no extra wiring needed. It shall have 2 Mbit/s outputs where it can directly be connected to digital telephone exchanges or teleprotection equipment. The jitter and wander tolerance for PDH and SDH interfaces shall conform to ITU-T G.823 and G.825. Jitter and wander characteristics of SDH multiplex and line equipment shall conform to ITU-T G.783. The Contractor shall submit the details of the power budget calculations stating the following (based on 0.25 dB/km optical fibre attenuation at 1550 nm): Transmitter Power Minimum receive Signal @ BER 1x10-10 Connector Loss Repair Splice Loss Power Penalty (Chromatic dispersion and LD reflection Loss) Maintenance Margin (> 2dB) Other Loss System Margin The SDH equipment to be offered shall provide the followings: A data communication channel to the Telecommunication Management Network, in accordance with ITU-T G.773 for the purpose of integration of the new equipment into the Telecommunication Network Management System. A Craft interface in accordance with ITU-T G.773 to allow a local terminal to access the network element. An engineer order–wire which shall have conference and selective calling features. Performance monitoring in accordance with ITU-T G.784 and G.826. Optical safety as per ITU-T G.783. The alarm functions shall include but not limited to: Alarms classified as critical, major, minor, and information. Indications of loss of incoming signal. Visual and audible indication of alarms. Test function of alarm indicators to ensure workability of alarm indicators. Alarm functions shall be detailed by the Contractor, e.g. if implemented in Telecommunication Network Management System. Test functions of the equipment shall include as a minimum: Transmit output Receive Sensitivity BER Protection switching Engineer Order-wire KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 107 of 270 108 SECTION V: TECHNICAL SPECIFICATIONS Alarms Supply Voltages Test loops The Contractor shall give details of all other functions available on the equipment / system. The equipment shall have a proven record by submitting a reference list, that it has been installed and operated in similar environment. The power supply voltage and range shall comply with the characteristics of the DC system, the rated voltage being 48 Volt DC ±15.SCADA and voice communications, including all necessary interface cards. This will provide for new protection. SCADA and voice signals installed under this project as well as any existing services which the client required to be carried on the optical fibre. Lead in cable shall be provided at the new Substation to connect the OPGW to the terminal equipment. DC power supplies will be provided at the new substation. Optical Distribution Flames (ODF) Each Optical Line Terminal Equipment (OLTE) or SDH multiplexer shall include an optical distribution frame, installed in a own wall mounted fixed cubicle. Assignment between station fibre cable and OLTE's shall be made by using patch cords between the termination box and the optic distribution frame. Capacity of the optic distribution frame shall allow free assignment between each individual fibre of the station fibre optic cables and the relevant optical I/O ports of the OLTE's. The optic distribution frame shall be equipped with low loss optical connectors (< 0.3 Db including the loss in the bulk head, loss in the connector splice & the loss in the pig tail) of the screw-on type. Auxiliary connectors shall be provided to facilitate testing and maintenance of the fibres/equipment. All spare fibres shall be properly terminated and spliced on connectors of the same type within the frame. 3.13.5 SPEECH EQUIPMENT It’s proposed to connect two remote extensions from this exchange to each of the new substation through the proposed communication Link. Seller shall provide the Telephone sets at the new substations 3.13.6 REMOTE TERMINAL UNITS Remote Terminal Units (RTUs) shall be installed at the new substation, purposes of Control/supervisory of the substation. New RTUs shall be equipped with a 25% spare capacity. The following signals if available, shall be collected via SCADA Control of circuit breakers and isolators Supervisory control of all 132 kV, Circuit Breakers (CBs) Supervisory control of all 132 kV motorised line and busbar isolators. Voltage control / voltage regulation: Remote control of all on-load tap changers for all 132/11 kV transformers Status Indications: Status indication of 132 kV circuit breakers at substations equipped with RTUs. For acquisition of and 132 kV CB status indications the auxiliary contracts of only one pole shall be wired for CB closed position and for open position. · Status indication of all 132 kV and line and busbar isolators Position indication of on-load tap changers of 132/11 kV transformers, Status indication of "Local / Remote", "Automatic / Manual" and "Master / Follower" mode of automatic voltage regulators where applicable Alarms: Bay Alarms: For each bay, the following protection signals shall be acquired individually if available: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 108 of 270 109 SECTION V: TECHNICAL SPECIFICATIONS "Main Protection 1 Trip" (MP1) "Main Protection 2 Trip" (MP2) "Backup Protection Trip" (BPT) "Permissive Trip Signal A Send" (PAS) "Permissive Trip Signal A Received" (PAR) "Permissive Trip Signal B Send" (PBS) "Permissive Trip Signal B Received" (PBR) "Blocking Signal Send" (BSS) "Blocking Signal Received" (BSR) "Direct Transfer Trip Send" (DTS) "Direct Transfer Trip Received" (DTR) "PT Fail A" (PTA) "PT Fail B" (PTB) "Trip Circuit Faulty" (TCF) "Protection A Faulty" (PAF) "Protection B Faulty" (PBF) "SF6 Low 1st Step (SF1) "SF6 Low 2nd Step (SF2) "CB Failure Protection Operated" (FPO) "CB Spring Charging Failure" (SCF) "Local Control Position of Selector Switch" (LCP) "CB Pole discrepancy protection" (CBD) Depending on the type of bay (line, transformer, bus coupler), the voltage level and the respective protection philosophy, the Main and Back-up Protection Alarms may be a "Distance Protection 1 trip", "Distance Protection 2 trip", "Differential Protection trip", "Overcurrent Protection trip", "Overload protection trip", "Directional earth fault protection trip" etc. Other alarms generated for the individual bays or circuit breakers shall be grouped at the station level and then transmitted to the respective Control Centre· "Circuit Breaker Faulty" (CBF) as one common (grouped) alarm for other failures that do affect the operation of the circuit breaker and need immediate attention / repair. · "Bay faulty" (BFY) as one common (grouped) alarm for all other failures that do not affect the operation of the circuit breaker. Transformer alarms: "Temperature Alarm" (TTA) oil and winding temperature as grouped alarm "Temperature Trip" (TTT) oil and winding temperature as grouped alarm· "Buchholz Alarm" (TBA) tank and OLTC as grouped alarm "Buchholz Trip" (TBT) tank and OLTC as grouped alarm "Transformer Oil Level (Low and High)" (TOL) "Transformer Cooling fan Trouble" (TCT) "Transformer Bank out of Step" (TBS) "Transformer Bank Independent" (TBI) "Transformer OLTC Control/Supply Failure" (TCC) "Transformer OLTC Loss of Sensing to HS" (TCS) "General Alarm" (TGA) all other alarms except the above as one grouped alarm "General Trip" (TGT) all other trip signals except the above as one grouped alarm Busbars Alarms: Busbar differential protection trip (BDT) Busbar voltage status (BVS) Busbar supervision operated KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 109 of 270 110 SECTION V: TECHNICAL SPECIFICATIONS Station alarms and warnings: 110 V DC alarm (DA1) 110 V Battery Charger Trouble (BCT) 48 V DC alarm 48 V Battery Charger B Trouble Protection Panel Under voltage (PPU) Protection Panel DC Supply Trip (PPS) Auxiliary supply fault (AUX) Smoke detected in Control room (SCR) Station Control Disabled (SCD) RTU alarm (RTU) Communication alarm (COM) The RTU shall be synchronised by use of a GPS. The new RTU shall be programmable, with real time clock, synchronised by an external source, process Input and Output (I/O) modules, CPU, memory and data transmission equipment. The new RTU to be supplied and installed under the project shall provide at least the following functions: single command outputs, double command outputs regulation command outputs e.g. raise/lower command outputs for transformer tap changer control analog setpoint transmission and output single, double and multiple state digital inputs analogue measured inputs metering pulse inputs for acquisition of energy meter values Sequential Event Recording (SER) with time stamping of events at the RTU RTU time synchronization self testing and diagnostic functions for detection and reporting of any error automatic re-starting function Mombasa Port 132kV Transmission line & substation project KPA database and parameter setting by menu-controlled dialogues from a local PC and remotely from the corresponding control centre with downloading function. Bidders shall with their offer inform about the different types of data transmission protocols available and for the proposed type of RTU. Telecontrols The RTU shall have the capability for the SCADA system master station to select and control specified power system devices. The following power system devices will be controlled by the RTU: two-state devices such as circuit breakers and isolators multi-state devices such as transformer tap changers Telecommands The RTU shall ensure that only the correct output is selected for two state devices before command execution. Operation of control outputs shall be via a select-check-execute command sequence. The control sequence shall include the following: The SCADA system shall transmit a command message addressing the proper RTU and the control point within the RTU, and indicate the control action desired. The RTU shall initialize its control logic, reassemble the command message, and transmit the reassembled message to the SCADA system. The message sent to the SCADA system shall be generated by the RTU's point selection logic. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 110 of 270 111 SECTION V: TECHNICAL SPECIFICATIONS The SCADA system shall check the returned message for validity and, if valid, shall issue an execute command to the RTU. The RTU shall operate the control point selected only after the execute command has been received. The control action shall be executed only if the select-check-execute sequence is performed without error or interruption. The RTU shall reset its control logic upon any error in the sequence or if the execute command is not received within a pre-defined time after the command message is received at the RTU. The impedance of the output circuit shall be measured to detect jammed contacts. The point selection logic for the control output shall be designed to preclude operation of an unselected output under single component failure conditions. That is, no single component shall be capable of selecting and operating an output point by itself. In no case, any unwanted telecommand shall be given to the process in case of an RTU power failure. The RTU communications protocol shall also support "immediate execute" contact outputs (where an operation can be commanded without the validity check and execute message exchange) for control output types such as On Load Tap Changer (OLTC) raise / lower command outputs. Teleindications Teleindication refers to status information of operational equipment monitored by the system. Such teleindications include status information of switching devices, event information, alarms, etc. The RTU shall report teleindications by exception but shall also allow the SCADA system to demand - scan status data even if the data has not changed. Status indications The status (open / closed) of two state devices such as circuit breakers or isolators shall be acquired by 2 independent, potential - free contacts or by 2 interposing relays, one for each position. Position indications shall be checked for validity and undefined states like open and closed (1 | 1) or neither open nor closed (0 | 0) shall be alarmed. The RTU shall provide for run-time-monitoring, adjustable to the HV equipment operation parameters, to avoid alarming of undefined states while the equipment (e.g. isolator) is operating. Alarms Alarms shall be acquired as single indications via potential - free contacts which are either available at the initiating equipment or to be generated by paralleling relays to be provided under the project. Digital parallel input The RTUs shall have the ability to handle digital measurands, e.g. four digits BCD. Transformer tap position shall be coded by means of a diode matrix to a BCD code before connecting to the digital parallel inputs of the RTU. The Tender shall include complete functional and electrical specifications of possible input codes and input circuits in the tendered system. Telemeasurements In analogue measurands the information to the RTU is given in the form of an analogue current supplied by the output of an analog measuring transducer. The analog signals shall be converted to digital mode by an analog-to-digital converter, to which the inputs are connected. All inputs of a module shall be measured within one cycle, regardless of the number of inputs in use. Thus new points can be added to the RTU without reprogramming. Analog measurements shall be transmitted to the master station with 12 bits or 11 bits + sign bit. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 111 of 270 112 SECTION V: TECHNICAL SPECIFICATIONS Telemetering The transmission of integrated totals refers to the transmission of measurable quantities which are integrated over a specified period of time. The integration shall take place before transmission. The measured quantity such as active or re-active energy (kWh, kVarh), which is presented as defined pulses which are read into an integrating register of the RTU from a pulse output or a closing contact of an energy meter. Transfers of the accumulated counts into a storage area shall be initiated every 1 minute by the RTU clock. In case of a failure to scan, e.g. due to failure of the telecommunication system, 1-minutes integrated totals over a period of not less than 1 day shall be stored at the RTU Pulse accumulator data shall be assigned to a scan group for scanning of the accumulated values from the SCADA system. Sequence of Event Recording (SER) The RTU shall be capable of Sequence-of-Events (SER) data collection at a time resolution less than the operating speeds of the power system devices. Any digital input points in the RTU may be assigned, programmable as an SER data point. In general, a breaker position change and any alarm from a protection device that has initiated a trip signal is defined as an event for SER. Multiple transitions of a device, such as the tripping and subsequent reclosing of a breaker, shall be considered as a series of separate events. Each time an event is detected, the RTU shall time-tag the event and store it together with the time-tag of the event for transmission to the SCADA system with the next scan. The buffer shall be sized to store, as a minimum, a number of events equal to three times the number of SER points implemented in the RTU. The time-tag recorded with each event shall be generated from a clock internal to the RTU. Separating capability The RTU shall be capable of correctly determining the sequence of events for which their occurrence is separated by >= 1 ms (separating capability class SP4 of IEC 60870-4) Time resolution The resolution of the time tag shall be 10 ms. Common time base The internal clock of each RTU shall be synchronized either from an internal, Contractor supplied and installed time synchronization source, such as a Global Positioning System (GPS) or an omega synchronizing signal. The synchronization shall be done periodically such that the time-tags in each RTU shall be within five milliseconds (5 ms) accuracy between all RTUs. Tenderers shall clearly indicate the method used for time synchronization and describe in detail how the required accuracy is achieved. In the RTU there shall be a digital output from which time synchronization messages can be forwarded to external devices. The frequency of the activation of the message shall be adjustable. Data transmission The data transmission network will consist of dedicated data channels and/or TCP/IP network utilizing fibre optic transmission media, power line carrier and radio transmission. The new RTUs shall be capable of “dual port function”, utilizing different protocols on at minimum 2 separate RTU communication ports simultaneously. Communication protocols shall be implemented by modifiable firmware in the RTU. Reconfiguration of the RTU database may be necessary when an RTU's communications protocol is changed due to the difference in the functions supported by the protocol. The Contractor shall provide and implement RTUs with standard IEC 60870-5-101 communications protocol as well as IEC 60870-5-104 communications protocol. Both protocols shall be included and shall be selectable for each of the RTUs by parameterization. The interfaces to the different communication media for IEC 60870-5-101 and IEC 60870-5104 shall be provided by the RTU hardware. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 112 of 270 113 SECTION V: TECHNICAL SPECIFICATIONS The RTU protocol shall be non-proprietary for use within KPA. The Contractor shall provide all details and parameter settings used under the IEC 60870-5-101 and IEC 60870-5- 104 protocols. KPA shall be authorized to disclose the RTU protocol to third party suppliers. 3.13.6.1 Functional requirements for adaptation works This Section is dealing with the interfacing equipment and works to be performed at substations and power stations. Analogue and digital input data to RTU Power system analogue and digital input data shall be collected from the substation field instrumentation and provided to the RTUs. Interfacing shall be designed to minimize electromagnetic and electrostatic interference. Analogue measurements The interfacing shall consist of analogue transducers, isolating/test devices, wiring, cabling and terminations to the secondary PT/CT circuit in the control or relay cabinets. The output signal from the analogue transducer shall be transmitted to the appropriate input at the RTU. This refers i.e. to MW/MVAr, Current and Voltage measurements. Status indications The interfacing shall use spare potential free contacts where available or auxiliary paralleling relays to be provided under the Contract, (one independent contact / relay for each position) actuated by the switchgear equipment, isolating and test devices, wiring, cabling and terminations to the digital input point at the RTU. Alarms Input wiring to the RTU from alarm points shall use spare contacts available on the actuating device wherever possible. Where spare contacts are unavailable, auxiliary "contact multiplying" relays shall be supplied and wired to provide the required digital input signal to the RTU. Pulse accumulation The pulse accumulation interfacing shall utilize potential-free pulse contacts or pulse outputs of electronic meters if available, isolation and test devices, wiring, cabling and terminations to the RTU. Where potential free pulse contacts or pulse outputs are not available, new meters shall be provided under the Contract. Supervisory control interface The outstation adaptation works for device control will be required to take an output signal from the RTU, actuate an auxiliary control relay, and have a contact from the control relay to initiate a control action such as breaker trip/close, etc. on the substation equipment by the appropriate connections to the substations equipment control circuits. The supervisory control interface shall consist of outputs from the RTU, interposing relays, isolating/test devices, and wiring, cabling and terminations to the appropriate control circuits and control relays and switches in control cabinets. Each RTU control output shall drive an auxiliary control relay, which shall be located in the control panel or locally. The interposing relay shall be normally de-energized during normal operation. A normally open contact of these interposing control relays shall actuate a breaker tripping/closing coil. In no cases shall the relay contacts supplied in the RTU directly control any equipment. In no case shall the closing commands for circuit breakers by-pass any station internal interlocking. For OLTC devices, appropriate latching relays shall be utilized. A key type selector switch shall be installed for each feeder equipped for remote control from the corresponding Control centre. The switch shall allow selection of control from the KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 113 of 270 114 SECTION V: TECHNICAL SPECIFICATIONS Control centre or from the substation and its position shall be indicated at the corresponding Control centre. The Contractor shall provide and install suitable test switches or isolating devices for all control points, to allow for proper control isolation, testing, safety procedures. Remote terminal units hardware Enclosures The Contractor shall provide enclosures meeting the following requirements: Swing racks supported by heavy gauge hinges shall be provided so that only access to components and wiring is required for routine maintenance troubleshooting. Provisions for top and bottom cable entry. Cable entries shall be provided protection against insect and animal entry, and sealed to prevent dust and contamination. Protection class of the enclosures shall be for indoor cabinets IP52 minimum for outdoor cabinets IP64 minimum. Suitable signal and safety ground networks within the enclosure. Convenience outlets at 230 V AC, shall be provided. front and with sand Power supply The Contractor shall supply any hardware required to convert the 48 V battery voltage to the required internal voltages for the RTU hardware. The RTUs shall be capable of operating with ungrounded or grounded (either polarity) input power. In RTU DC distribution, Miniature Circuit Breakers (MCBs) with alarm contact shall be used, i.e. fuses are not accepted. Interconnections All connections between the RTU's termination facilities and signal wiring shall be through barrier-terminal blocks with knife-switch isolation, mounted in the RTU panel or an adjacent marshalling cabinet, if not already exist in the Substation. Terminal blocks shall be screwtype, with full depth insulating barriers. Distributed RTUs RTUs shall have the capability to gather data from other smaller or distributed RTUs or local intelligent substation instrumentation using directly connected RS-232C- or RS 485channels with or without modems. The distance between the different control locations may reach up to 500 m. Digital inputs The digital inputs shall be opto-isolated, signal voltage 48 V DC. Other voltages shall also be possible by changing the matching resistor in the input circuit. Contact bouncing of the interposing relays shall be filtered. The bounce filtering time shall be 7 ms. Input circuits with selectable bounce filtering time setting are preferred. The indications shall preserve the chronological order of events inside the RTU. Oscillating inputs as a result of e.g. a faulty relay chattering shall be blocked locally at the RTU. Analogue inputs In analogue measurements, the information to the analog input modules of the RTU is given in the form of analog current supplied by the output of measuring transducers. Measuring transducers shall normally be installed in the switch/control gear. In analog input modules, the following current input ranges shall be available: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 114 of 270 115 SECTION V: TECHNICAL SPECIFICATIONS unipolar 0-5 mA, 0-10 mA, 4-20 mA bipolar +/- 5 mA. +/-10 mA, 4-20 mA. It shall be possible to change the input range for each individual input, preferably by software means, instead of changing the input resistor. The analog input circuit shall have a precise DC impedance less than 200 ohms for current inputs. This impedance must not vary more than half of the accuracy of the Analog to Digital Converter (ADC) with influence values such as temperature, etc. In the input circuit galvanic isolation shall be provided from mechanical earth and electrical earth, and, preferably, between different inputs. The circuits of the analog input module shall be protected against disturbances caused by switching transients and against disturbances from power and radio frequencies present at outstations. The scanning of each input shall not introduce any error on the analog information. For each input it must be possible, without disturbing the other inputs, to isolate the input from the ADC and close the analog circuit, to connect, on the ADC side, a test set for maintenance or adjustments, to measure the analog input value without disturbing the measurement (addition of an mA meter over a link which is then disconnected). The analog information shall be converted into digital value by the ADC which can be common for all inputs. Analog measurements shall be transmitted to the master station with at least 11 bits plus sign bit. The total accuracy must be better than 0.5% of the nominal range of a measurement calculated from RTU's analog input up to Control Centre. A calculation of the total accuracy in the wide sense as well as in the restricted sense as per IEC 870 - 4 shall be included in the Tender. The input circuits must withstand a permanent overload of 30% without any damage. In case of input overload the output message shall be either the exact value corresponding to the input or the maximum value that is possible to code (with the correct sign). Pulse inputs The counter register shall be 16 bit. The maximum input frequency shall be 25 Hz. In practice, the pulses will be dimensioned in a way that max. frequency is less than 5 Hz. Interposing relays will not be used. RTU firmware requirements The RTUs shall meet the following characteristics of the firmware to support the functions of the RTUs. The Contractor shall use standard firmware as much as possible. All firmware shall be completely and consistently documented. It shall not be necessary to perform modification to firmware, logic, or data for expansion within the sizing parameters defined for the RTU. At the time the RTU is accepted, all firmware delivered must be up to date and in final form, including all standard firmware changes and field changes initiated by the Contractor or the Contractor's suppliers prior to acceptance. The firmware documentation must reflect these changes. Firmware shall be loadable by service notebook locally at minimum, download of firmware and parameter sets through SCADA system, using the data communication links will be KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 115 of 270 116 SECTION V: TECHNICAL SPECIFICATIONS referable. In any case changing of EPROMs or similar devices shall not be necessary when updating RTUs firmware. Initialization / restart program Firmware shall be provided to enable the RTU to restart itself upon manual request and automatically under the conditions of power restoration, memory parity errors, and hardware failures. The firmware shall initialize the RTU and begin execution of the RTU functions without intervention by the SCADA system. All RTU restarts shall be reported to the SCADA system. Fail safe processing In the case of irrecoverable faults such as power supply failures, firmware malfunctions, or any other detected condition that may affect the security of indications and controls, the RTU shall place itself in a secure state that prohibits the transmission of false indications or the execution of erroneous control outputs. The detection of these error conditions shall be the responsibility of the RTUs self-test and operations monitoring firmware. Database maintenance The Contractor shall supply software to configure each RTU's database where this information is located in software and/or firmware at the RTU. The software shall completely generate or modify the database of the RTUs. The database software shall have error detection services and shall produce a printed listing of the input data and the resulting RTU database configuration. Down loading of database from SCADA system The RTU shall support the change of the RTU's configuration and processing parameters by messages from the SCADA system. These changes shall include, but not be limited to scan group definitions, analog limits, SER point allocation and buffer definitions. Diagnostic firmware The Contractor shall supply diagnostic firmware for both off-line local tests and on-line selfdiagnostic capability built into the RTU. The RTU shall enter an off-line state during the execution of off-line diagnostics, and this off-line state shall be reported to the SCADA system. The RTU shall include a remote diagnostics communication port and shall be capable of executing off-line diagnostics from an external computer terminal connected to this remote diagnostics port. A SCADA interface Marshalling cubicle shall be supplied to interface all power system data i.e. status indication alarms, analogues, interposing relays for control outputs etc. to the RTU. This cubicle shall also house transducers for analogue inputs and interposing relays for control outputs. 48 volts DC power supplies shall be supplied to power the RTU, interposing relays, telephones equipment Special Tools and Measuring Equipment Special tools and measuring equipment which are used to set up the equipment properly and which are essential for maintenance shall be provided. This includes service laptops Fibre Optic and RTU. 3.13.7 TECHNICAL GUARANTEES The appropriate Technical guarantees in appropriate Technical schedule section shall be completely filled KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 116 of 270 117 SECTION V: TECHNICAL SPECIFICATIONS 3.14 MISCELLANEOUS MATERIALS 3.14.1 SCOPE This subsection covers the design, manufacture, testing before shipment, delivery to Site and erection and testing at Site of the following materials. (a) Electrical conductors, cables and fittings (b) Insulators and fittings (c) Steel structures (d) Earthing materials (e) Other material (f) Lighting facilities for outdoor switchyard. 3.14.2 CABLES 3.14.2.1 600V Cables Low-tension circuit from station local transformer to AC distribution panel: 600V cable shall be copper conductor, polyvinyl chloride insulated PVC sheathed, 600V 300sqmm x 4cores. Low-tension motor circuit from AC distribution panel to each motor: The sectional area of the 600V cables shall be ample for each motor capacity and shall be decided by the Contractor taking into account the voltage drop for starting current. 3.14.2.2 Control Cables Control cables shall be copper conductor, of jacket type, 600V, polyvinyl chloride insulated PVC sheathed, multi-cores copper. The cross-sectional area of core shall not be less than 2.5 mm². and the cables shall be armoured.The cross-sectional area of core for current transformer circuit control cables shall not be less than 4 sq mm and shall be armoured. 3.14.2.3 Insulated Wire 600V PVC insulated wire shall be considered stranded copper conductors and used for power and heater for indoor wirings. 3.14.2.4 Cables Drawn into Ducts Unless otherwise specified, the Contractor shall provide ducts and pipes. Immediately before pulling the cables, the Contractor is to remove any loose material from the ducts and prove them by drawing through a material of slightly less diameter than the duct. The ducts shall be water and vermin proof sealed and for indoor installations fireproof. 3.14.2.5 Cables Installed in Concrete Trenches In substations concrete trenches and cable ducts shall be provided and installed by the Contractor. These trenches shall not be filled with sand. All cable duct entries to buildings, whether or not for cables, shall be protected against entry of water, oil and vermin with a suitable filling material supplied and installed by the Contractor on the approval of the Employer. All cable routes in concrete trenches shall be suitably supported by means of cleats or racks and raised from the trench floor by means of suitable spacers. All cables shall be run in a neat and orderly manner and the crossing of cables within the trench shall be avoided as far as possible. The Contractor shall be responsible for removing and replacing the trench covers free of charge during the execution of his work as directed by the Engineer. 3.14.2.6 Bus Conductors Following conductors shall be provided as outdoor bus and jumper conductors: For 132 kV bus bar and jumper (i) Pipe bus: Copper pipe – 75mm (diameter) x 5mm (thickness) (ii) Jumper and droppers: AAC. 400 mm2 3.14.2.7 Galvanized Steel Wires Galvanized steel wires of 55 mm2 (7/3.2 mm) shall be used for overhead ground wires, of which ultimate tensile strength shall be more than 90 kg/.mm². 3.14.2.8 Fittings Suitable compression clamps and spacers for conductors, suitable terminals for the equipment to conductor, and suitable clamps for galvanized steel wire shall be supplied and installed. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 117 of 270 118 SECTION V: TECHNICAL SPECIFICATIONS Connecting clamps shall be free from electrolytic corrosion and designed for bi-metal against the connection between aluminium and copper. The following tests, as applicable, shall be carried out at the Contractor’s plant: (a) Construction test (b) Tensile strength test (c) Elongation test (d) Resistance test (e) Insulation resistance test (f) Withstand voltage test (g) Characteristics 3.14.3 INSULATORS AND FITTINGS 3.14.3.1 Substation Disc Insulator Units Each suspension and strain insulator string shall be of 12 units for 132kV circuits without arcing horn. The insulator unit shall be standard 254 mm porcelain, with ball and socket, and have a spacing of 146 mm between discs, complying with IEC publication 3051974. The connection between units shall be such as to allow sufficient flexibility for freedom of movement, and to prevent the possibility of becoming separated accidentally either during or after the erection. The interlocking sockets shall be designed to allow easy passage of the ball into the socket and retaining or locking devices required to keep in the socket under all service conditions. The dimensions of socket and pin shall be in accordance with IEC. Recommendation 120, 16mm socket and pin. The insulator units shall be brown glazed porcelain. Each insulator unit shall have the following characteristics: Withstand voltage: Power frequency, dry 70kV Power frequency, wet 40kV Impulse voltage 110kV Puncture voltage 110kV Minimum breaking load 70 kN Minimum creepage per unit 295mm Minimum creepage for insulator string shall be 3988mm Minimum breaking load of insulator string with fittings shall be 70 kN. 3.14.3.2 Station Post Insulators Station post insulators shall be provided for supporting the connecting lead wires of switchgear equipment to bus. The insulator shall be of brown coloured porcelain rated as follows: System voltage 145kV AC withstand voltage (wet, 1 min.) 290kV Impulse withstand voltage 685kV The station post insulator shall comply with IEC.273-1968, IEC 720. 3.14.3.3 Fittings All fittings shall be malleable iron hot dip galvanized to BS 729. Suspension and tension clamps shall be as light as possible and of approved types. All clamps shall be designed to avoid any possibility of deforming the stranded conductors and separating the individual strands. Tension clamps shall be bolted type, and shall not permit slipping off or damage to conductors or any part thereof. Suspension clamps shall be free to pivot in the vertical plane containing the conductor. Clamps shall not exhibit excessive heating by magnetization or otherwise. U-bolts, ball hooks, socket-eyes and other necessary fittings required for the above insulators and clamps shall be provided. The following tests shall be carried out before shipment: (a) With stand and flashover voltage KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 118 of 270 119 SECTION V: TECHNICAL SPECIFICATIONS (b) Mechanical strength (c) Dimensions of insulators and fittings (d) Galvanizing 3.14.4 STEEL STRUCTURES 3.14.4.1 General The Contractor shall furnish all steel structures required, including framework of outdoor equipment. 3.14.4.2 Details of Design The steel structures shall be designed in accordance with the following requirements: (a) Vertical loading The weight of the conductors, ground wires, insulator strings, workers, the structures themselves and equipment to be supported, if any, shall be considered. (b) Wind pressure: (i) On conductors and earth wires: 385 N/m² on projected area (ii) On insulators and all other circular: 385 N/m² on projected area section (iii) On lattice structures or beam structure: 590 N/m² on projected area (c) Working tensions of conductor and wire: (i) Conductors for 132kV buses-700kg per conductor and for 132kV lines 700kg per conductor (ii) Overhead ground wire- 500kg per wire (d) Seismic co-efficient: 0.16 (e) Factor of safety: 2.5 The structures shall be designed so that no failure or permanent distortion shall occur when the load equivalent to 2.5 times the maximum simultaneous working loads are applied. (f) Slenderness ratio: The slenderness ratio shall not exceed 200 for main and web members and 250 for nominal members. (g) Member size No leg members less than 5mm in thickness and 60mm in width of flange for main, and 4mm in thickness and 45mm in width of flange for web and nominal members shall be used. (h) Bolts and nuts All the members shall be connected by bolts and nuts. The size of the connection bolts shall be not less than 16mm for leg member. The suitable anchor bolts shall be provided. The size of step bolts shall be 16mm. The Contractor shall submit full details and drawings for the steel structures to the Employer for approval prior to commencing fabrication. 3.14.4.3 Foundation The Contractor shall place the concrete foundation for steel structures and switchgear equipment on the switchyard. The Contractor shall supply installations drawing giving erection particulars. The foundation shall be anchor bolt type. Such members as to be buried in the foundation concrete block shall not be provided. Size of block-out hole for anchor bolts shall be indicated on the drawing so that the concerning work can be performed prior to the erection of supports. Safety factor of concrete for up lifting force shall not be less than 2.5. The allowable bearing strength of earth will be assumed to be 2.0 ton/m², however, it shall be confirmed by the Contractor. The weight of earth shall be assumed to be 1.6 ton/m³ and weight of concrete to be 2.3 ton/m³. If required, pile foundation shall be provided, and the cost of piling shall be deemed to be included in the Bid Price. The angle of repose will be reckoned as 10 degree. 3.14.4.4 Materials All steel employed for the structures have high yield point and high ultimate tensile strength and shall be subject to the approval of the Employer. Diameter of both holes shall not be more than 1.5mm larger than the diameter of the bolts. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 119 of 270 120 SECTION V: TECHNICAL SPECIFICATIONS All members shall be stamped or marked in an approved manner with numbers and/or letters corresponding to number and/or letters on drawings or material list approved by the Employer. The erection marks shall be stamped before galvanizing and shall be clearly legible after galvanizing. The following tests shall be carried out before delivery to site. (a) Mechanical strength of materials (b) Galvanized test (c) Shop assembly 3.14.5 EARTHING MATERIALS In addition to the conductors and fittings to be used for the works to be erected under the contract, the Contractor shall supply and install the following materials for the grounding system of each substation and complete the grounding system. The Contractor shall submit full details and drawings for grounding systems to the Employer for approval. Grounding resistance shall be 1-ohm at the maximum or the value calculated and the Contractor shall be responsible for preparing the specified value. (a) Bare annealed high conductivity copper stranded wire: 95mm² for main grounding mesh, local transformer, arresters, etc. And 35.mm² for other equipment and materials. (b) Copper plates of 3mm thick, 1 meter by 1 meter size, equipped with copper lead conductor 95 mm², 3 meter long (c) Grounding rod of 25mm diameter, 3 meter long, copper clad steel rod equipped with copper led conductor, 35.mm², 3 meter long. (d) Clamps needed for connecting each conductor shall be provided. 3.14.6 OTHER MATERIALS All other miscellaneous materials, such as conduct pipes, steel plates, fabricated cable ducts, cables supporting brackets sand/or cable racks, pipe hangs, angle steels, channels steels, bolts and nuts and other items, required for putting into service the works to be covered under this Contract, shall be supplied and installed by the Contractor as required. These materials shall comply with the highest grade specified in the relevant standards. Coloured phase mark plates and bus identification marks shall be fitted on each beam of steel structures of incoming feeders, outgoing feeders, main buses and transformers buses. Colour of phase marks shall be red, yellow and blue. 3.14.7 LIGHTING SYSTEM A complete lighting system for the switchyard at the KPA substation shall be supplied and installed by the Contractor. Station lighting components of approved type shall be supplied and installed. These shall include but not limited to: (a) Lighting Fixtures (i) Outdoor type mercury lighting fixtures for AC 240V shall be equipped with screwed base lamp holders, and shall be of high-power factor suitable for stable operation in tropical climate and weatherproof type. (ii) Outdoor type incandescent lighting fixtures for DC 110V for emergency use shall be complete with all fittings. (iii) The type of lighting fixtures used should be available locally. (b) Lighting supports Lighting supports shall be steel poles painted with suitable colour, which will be instructed by the Employer. Ballast, cut out, and terminals shall be equipped in the pole and other attachments necessary for wiring and fixing of the lighting fixtures shall also be provided with the pole. The ground level shall be marked on the support for easy installation. 600-volt PVC insulated wires of 2.5 mm² in size shall be laid in the lighting pole for connection from the terminal box to the lighting fixtures. (c) Cabling and wiring shall be of approved type as well as all required installation materials. (d) Lighting panel for outdoor lighting system shall be installed in each station or extended in the relevant stations. The lighting panel shall be indoor metal enclosed, wall mounting type, dust and vermin proof construction and shall contain the following equipment. Identification name plate KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 120 of 270 121 SECTION V: TECHNICAL SPECIFICATIONS Twenty single pole moulded case circuit breakers 600 V, 30A Pole moulded case circuit breakers 600V, 100 A Magnet contactor for emergency lighting Internal wirings Neutral links Terminal boards (e) Spare Parts. The following spare parts shall be supplied for the station- 3 sets of each type of complete lighting fixtures with all accessories. Lighting for outdoor switchyard and access roads constructed under this contract shall also be provided by the Contractor. The Contractor shall prepare and submit to the Employer for approval the calculation sheets, the facilities drawings, the installation drawings and wiring diagram. The power shall be supplied from the low tension AC distribution panel in the control building. The mean illumination level of each location for AC power shall be as follows: Outdoor operating area 30 lux Outdoor switchyard 5 lux Street lighting 10 lux 3.14.8 MARSHALLING BOXES Marshalling boxes shall be used for outdoor switch bays and control building for the stations. The boxes shall be of outdoor or indoor, metal enclosed, air insulated, self standing type, dust and vermin-roof construction and containing the terminal blocks, internal wiring, space heater with thermostat for moisture protection, and other necessary equipment. Those for outdoor use shall be of weather-proof construction. 3.14.9 AC POWER OUTLETS An AC power outlet shall be installed in the adjacent place of local service transformer. The AC power outlet shall be of outdoor, metal enclosed, air insulated, self standing or structure mounted type and dust, vermin and weather proof construction and containing a 3 pole moulded case circuit breaker, 600V, 100A power plug cable gland, and other necessary accessories. 3.15 CIVIL ENGINEERING AND BUILDING WORKS 3.15.1 GENERAL The works comprise the topographical survey of site, subsoil investigations, detailed design, production of working drawings, provision of labour, plant and materials, and construction of the civil engineering and building works. The works include site clearance and earthworks; Cabro (Minimum 80mm or 49N/mm²) paved Substation and access road, surfaced water drainage, switchgear and structures, Drained indoor/outdoor cable trenches, perimeter fencing with 750mm razor wire on top and gates, etc. The framed structure control buildings will be completed with control and relay room, communications equipment room, office, washroom, drainage infiltration tanks, septic tank, water supply with minimum head 3m tower tank and ground storage tank with pumping boost . The new Control building at the KPA Substation shall have a minimum floor area shall be 384m². 3.15.2 SITE SURVEY AND SUBSOIL INVESTIGATION The Bidder shall visit the site to satisfy himself that information given in the Bid Document is accurate and also to collect additional data, which he may require for preparation of his bid. (A)Site Survey The Contractor shall survey the site of the switchyard associated with control building, to obtain the following: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 121 of 270 122 SECTION V: TECHNICAL SPECIFICATIONS (1) Accurate volume of ground to be cut and levelled. (2) Accurate positions of switchgears, structures, ducts, drainage, buildings, fences, etc. (3) Drainage pattern of the site A site survey plan shall be prepared in the scale of 1:500 showing the survey results and proposed layout of the work. (B) Sub-soil Investigation The Contractor shall ascertain for himself the nature of the sub-soil conditions over the sites of the works for his design purposes, by means of sounding tester and trial excavations, etc. The following should be considered as a minimum requirement, but should be extended if many inconsistencies are encountered: (1) Depth of sounding tests shall be less than 5 metres unless rock is encountered; in which case the thickness shall be proved to be greater than 1.5 metres on two boreholes. Where weak soils are encountered, the test shall be taken down to a load bearing stratum and adequate thickness. (2) Test records shall describe and indicate level of all soils encountered and indicate the natural water table level. Rock core records should specify total core recovery, solid core recovery and quality of the rock cored. (3) Electrical resistivity of the soil shall be verified on four samples, in accordance with approved practice. (e.g. British Standard Code of Practice CP 1013-1965): 3.15.3 DESIGN OF WORKS a) Design and Drawings The Contractor shall design the civil engineering and building works and prepare design report complete with working drawings in size A3 as necessary for the construction of the works. The Contractor is required to produce full design calculations for the foundations, building structures, etc. and detailed working drawings. He shall be responsible for the detailed designs, strength and safety of the structures, to meet the structural, acoustic and environmental requirements of the buildings and other works. He shall be responsible for ensuring that the design satisfies the requirements of all authorized local and natural bodies. Design calculations and detailed drawings must be submitted to the Employer for approval before the relevant construction work is carried out. Design calculations shall be in accordance with an approved method of computation and should take into account the most unfavourable combination of dead load, live load and wind load. b) Detail Requirements for Design (1) Calculations Calculations shall clearly identify the subject of the calculations and shall include but not be limited to providing the following information: (2) (a) Assumption used for design purposes (b) Codes or standards used (c) Loading used (d) Calculation (e) Technical specification section and paragraph number (2) Drawings Drawings and data sheets prepared by the Contractor shall include complete construction details. The drawings shall include but not be limited to the following information or detail as applicable: construction joints, reinforcement details and bar bending schedules, details for unusual or special items of architectural, form work, trenching, structural steel details, etc. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 122 of 270 123 SECTION V: TECHNICAL SPECIFICATIONS 3.15.4 GENERAL SITE WORKS A. Setting-out The Contractor shall be responsible for all setting-out, irrespective of any checking by the Employer. The accuracy of all setting-out is to be better than ±1part in 3,000. The Contractor shall advise the Employer within 24 hours whenever a new setting-out peg is established or an existing one destroyed, and shall regularly furnish the engineer with layout plans showing all current setting-out and survey stations. The tolerances shown below shall rule on site unless otherwise agreed upon by the Employer and the Contractor. Block work (1) Position in plan Fair-faced or specified side from the designed position ±15mm (2) Length Up to and including 5m ±15mm Over 5m up to and including 10m ±20mm Over 10m ±25mm (3) Height Up to and including 3m ±15mm Over 5m up to and including 6m ±20mm Over 6m ±25mm (4) Thickness More than one block ±15mm (5) Level of bed joints Length up to but not exceeding 5m ±10mm Over 5m but not exceeding 10m ±15mm Over 10m but not exceeding 20m ±20mm Add for every 5m ±5mm (6) Straightness In any 5m (not cumulative) ±10mm max (7) Verticality In any 3m ±15mm Permissible Deviation on In-site Concrete (1) Plant and other foundations (a) Position of centre line on plan from nearest building grid line ±10mm (b) Dimensions on plan -5mm + 20mm (c) Formation level ±25mm (d) Surface level -5mm + 0mm (e) Sleeved bolt location ±15mm (f) Sleeved bolt vertically 1 in 100 (g) Cast-in bolt location ±2mm (h) Cast-in bolt vertically 1 in 300 (i) Bolt levels 0mm + 20mm NB: Where tolerances (e) and (f) conflict with (g) and (h) the latter shall govern. (2) Components above foundation (excepting items in (c) below) (a) Position of centre line on plan from Nearest building grid line ±19mm (b) Verticality: Plumbers in height of up to 0.5m ±5mm Over 1.5m to 1.5m inclusive ±10mm Over 1.5m to 3m inclusive ±15mm Over 3m to 30m inclusive ±20mm (c)Cross section and linear dimensions of beams, slabs, columns and walls. Up to 300mm ±5mm Over 300 to 600mm ±10mm Over 600mm to 1.5m ±15mm KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 123 of 270 124 SECTION V: TECHNICAL SPECIFICATIONS Over 1.5mm to 3m ±20mm Over 3m ±30mm (d) Level of specified surface relative to the nearest Bench Mark ±10mm (3) Overall dimensions of a concrete framed building (a) Length and width measured at external ground level For dimensions up to and including 15m ±15mm For dimensions over 15m up to 30m ±50mm For each subsequent 30m ±20mm (b) Height of structural roof level with reference to the transferred Bench mark ±40mm The Employer may at his discretion alter or specify new tolerances as necessary. The Contractor shall submit for the Employer’s approval, his proposed finished site levels, road levels and building floor levels. Following approval by the Employer the Contractor shall level the sites to suit. B. Drainage Drainage shall be designed in accordance with relevant Codes for Practice published by authoritative Standards Organization such as the British Institution, e.g. BS 8301, BS 6031 and CP 2005. A surface water drainage system covering the switchyard shall be installed. The number of runs and outfalls and pipe sizing must be sufficient to cope with the severest precipitation, with a factor of safety of 1.2. Within switchyard and other areas in which maintenance will be carried out the drainage must allow uninterrupted access. Embankments and cuttings are to have drainage facilities at their top or bottom. The formation level of switchyard areas is to be formed with uniform cross-falls of about 1 in 300 in the same direction as the natural drainage path of the surrounding country. Surface water from roofs of buildings shall be drained to down pipes, which connect with the site drainage system. C. Cable Ducts and Trenches The Contractor is responsible for all civil engineering works required for the cable runs between switchgear and buildings, in concrete cable trenches. Cable entries into buildings shall be through ducts or in concrete cable trenches. Trench covers outside buildings shall be of reinforced concrete, designed for the maximum likely imposed loads appropriate to their location. Concrete cable trenches shall be adequately drained to underground infiltration tanks of adequate capacity. Power cables and control cables shall be laid on suitable cable racks in trenches. Cable entries into buildings shall be sealed to prevent the entry of dust, vermin, etc., using suitable materials. D. Perimeter Security fencing and Gates The perimeter of the site is to be fenced with galvanized chain link or equivalent fencing, 2.4 meters high above ground level, attached to reinforced concrete supporting posts and struts. The posts shall have three strands of galvanized barbed wire attached to cranked tops. Double leaf gates shall be provided at the entrance to the site. E. Station Building The reinforced concrete framed structure control buildings will be completed with control and relay room, communications equipment room, furnished office , washroom, drainage infiltration tanks, . Control building minimum floor area shall be 384m² and a minimum height of 3.5m. Walls and partitions shall be dressed stone masonry with minimum compressive strength of 12N/mm². Control building floor layout shall be approved by the employer before detailed drawings production. The buildings shall have prefabricated steel roof, with walls of concrete block-work, rendered outside and plastered inside. All walls and roofs shall be fully insulated, to produce maximum thermal transmittance (U.) values of 1.14 (watts/m².) for walls and 0.57 for roofs. Architectural treatment of the buildings shall be in accordance with the Employer’s usual standard or preference. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 124 of 270 125 SECTION V: TECHNICAL SPECIFICATIONS The buildings will have been designed with ease of operation and maintenance as a major factor. Materials, workmanship and finish must be of an appropriately high standard. In considering the various materials, details, and construction methods, Contractors must investigate the availability, delivery and transportation to the site of all materials, plant, and labour, to enable the programme to be maintained. Internal partition walls shall be generally for concrete block work with emulsion painted smooth plastered finish. The equipment areas shall have screened floors finished with a surface hardener. All finishes shall be fireproof or flame retarding. Floor shall be sand-cement screed throughout. Room heights shall be governed by the criteria that there should be 1-meter clearance between the top of cubicles or panels and ceilings. Particularly, attention must be given in the design of the building to fire prevention and safety of the personnel at all times. Access doors and escape doors shall be provided and fitted with panic bolts where necessary, so that operating and maintenance staff can always exit safely from the buildings in fire emergencies of any nature or location. All windows shall be dustproof. A number of opening lights shall be provided in all rooms, including air-conditioned rooms. Internal doors shall be flush-faces, solid-core, timber doors, with painted timber frames and architraves. External doors shall be made of steel as appropriate. F. Site Clearance and Excavation The Contractor shall clear from all areas required for the works all unwanted materials, debris, etc., but shall take all reasonable precautions to prevent damage to existing road construction and to existing surfaces, buildings and other facilities in the area which do not need to be demolished. The whole of the excavations shall be carried out to the widths, lengths and depths shown on the approved drawings. No unlicensed or indiscriminate digging will be permitted. The Contractor may excavate by any method he considers suitable, subject to the Employer’s approval, and shall allow for the use of types of plant most suited for excavation in any location and at any time. The Contractor shall allow for risk of meeting and having to excavate through any sort of material, which may be encountered, including rock. Materials from the excavation may, if approved by the Employer, be used by the Contractor in the construction of the Works. Other excavated material shall be backfilled where required or deposited where directed anywhere on site. Surplus materials shall be removed from the site by the Contractor to the approved place. Backfill material shall not be borrowed from the site, site deterioration due to backfill borrowing on site shall be restored to Employer satisfaction with no additional cost. Whereas Employer acquired plot might be bigger than Substation site requirement, the Contractor shall only use the Substation site as will be in the approved Substation layout drawing, use of land outside this area will require Employer approval. The Contractor shall at all times keep the site free from all surplus materials, rubbish and offensive matter. In excavations for foundations, a bottom layer of excavation 150mm in thickness shall be left undisturbed and subsequently removed only when the concrete is about to be placed in order that softening or deterioration of the surfaces of the bottom of the excavated area by exposure may be avoided as far as possible. The bottom of all excavated areas shall be trimmed, levelled and well rammed. Concrete shall not be deposited thereon until the bottom has been inspected and approved by the Employer. All excavation works are to be kept dry and clean, in order that work is not affected or interfered with by water entering the excavations. The arrangements made for dealing with water in excavations must be approved by the Employer, and they must ensure that the de-watering of excavations can continue during the placing of concrete or the execution of any other works that could be affected by water in excavations. Adequate precautions must be taken against washing out of cement and concrete or to prevent KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 125 of 270 126 SECTION V: TECHNICAL SPECIFICATIONS the work being disturbed in any way. No concrete, masonry, brickwork or other materials shall be placed or built until the surfaces are properly drained. G. Filling and reinstatement Filling for trenches, excavations and leveling for the Site shall be deposited in layers not exceeding 250mm uncompacted thickness. Where excavations, whether in rock or other material, are made to a greater depth than detailed, the intervening space shall be brought up to the proper level in plain concrete. The Contractor shall be responsible for the stability of the embankments where formed either by cutting or filling, and precautions taken to protect the earthworks from deterioration under adverse weather conditions. Wherever applicable the recommendations contained in the following codes of practice shall be followed in calculations, detailing and performance of the earthworks and drainage: (1) Earthworks – British Standard Code of Practice BS 6031 – 1981 (2) Civil Engineering Code of Practice No.2 on Earth Retaining Structures, Issued by institute of Structural Engineers, U.K. (3) Soils - British Code for Civil Engineering Soils BS 1377. Embankments shall not be formed over inclined ground surfaces without previously forming the founding surface, on which the fill material will be placed, to a benched profile. All earthwork top surfaces shall be finished off level and regular and the sides of cuttings and embankments shall be properly trimmed to the detailed slopes as they become consolidated. The Contractor is to allow for embankments and cutting slopes to be well forked, raked and stabilized as protection from erosion. H. Explosives Explosives may only used when specified. Their use shall comply with the following: (1) Approvals required by CAP 115 Laws of Kenya on Mining. (2) Blasting design to ensure controlled blasting as an excavation method. (3) All local bylaws and regulations. (4) The Contractor shall store explosives in a licensed store or magazine provided with a separate compartment for detonators. (5) Explosives shall be used in the quantities and manner recommended by the manufacturers. The written approval of the Employer shall be obtained for each location or series of locations where the Contractor wishes to use. Such approval shall not in any way relieve the Contractor of his liabilities under the Conditions of Contract. (6) When blasting is carried out, the Contractor shall ensure, by adherence to proper safety distances and by the use of heavy blasting mats where necessary, to prevent the dispersal of material, that no damage is caused to persons, animals or property on or off the Site. Special care shall be taken when blasting in wet ground to ensure that individual explosions are reduced to such a size as to preclude damage to any buildings or structures. 3.15.5 CONCRETING WORK SPECIFICATIONS GENERAL Authoritative Standards and Codes Practice The following authoritative standards are referred to hereinafter: B. S. Date Title A 12 1989 Portland Cement (Ordinary and rapid hardening). B 812 Methods for sampling and testing of mineral aggregates, sand and fillers C 882 1983 Aggregates from natural source for concrete (including granolithic) D 1881 Methods of testing concrete E 5328 1981 Method of specifying concrete F 2499 1973 Hot applied joint sealants for concrete pavements (4) G 3148 1980 Tests for making concrete H 3921 1985 Clay bricks A 4251 1974 (1980) Trunk type concrete mixers B 4449 1988 Carbon steel bars for the reinforcement of concrete KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 126 of 270 127 SECTION V: TECHNICAL SPECIFICATIONS C 4466 1981 Bending dimensions and scheduling of bars for the reinforcement of concrete (old edition ) D 4483 1985 Steel fabric for the reinforcement of concrete E 5075 Concrete Admixture F 6073:Pt.1 1981 Precast concrete blocks G 8810.Pt. 1&2 1985 The structural use of concrete H 5950 The use of structural steel in buildings I KS 95 2003 Specification for Natural Aggregates for use in Concrete J 8007 1987 The structural use of concrete for retaining aqueous liquids K 3110 1972 Safe use of cranes (cranes, tower cranes and derrick cranes) MATERIALS AND SPECIFICATIONS (a) Concrete for concrete foundation and pile shall have the minimum required breaking strengths as specified in the technical schedules. (b) Cement used shall be Portland or other approved composition obtained from an approved maker. Portland cement shall conform in all respects to BS-12. (c) Aggregates shall be clean and free from dust, earthy or organic matter or salt. Coarse aggregate shall be of approved grading to be retained on a mesh not less than 5mm², and of a maximum size to pass a mesh not more than 40mm², subject to KS 95:2003. Where specially approved in writing by the Employer, coarse aggregate of uniform size not larger than will pass a 25mm mesh may be used throughout. Fine aggregate shall be coarse, sharp, clean and free from dust, salt, clay, vegetable matter or other impurity and shall be screened through a mesh not more than 5mm in the clear. It shall be a well-graded mixture of coarse and fine grains from 5-mm gauge downwards. (d) Water shall be clean and free from all earth, vegetable or organic matter, salt, soil, oil acid and alkaline substances either in solution or in suspensions. Quality shall be confirmed by lab test. (e) At least four weeks before commencing any concreting work; the Contractor shall make trial mixes using samples of cement and fine and coarse aggregates. The test specimens for the trial mixes shall be of cube type. Preliminary test specimens shall be taken from the proposed mixes as follows: For each proposed mix a set of 6 specimens shall be made from each of 3 consecutive batches. Three from each set of six shall be tested at an age of seven (7) days and three (3) at an age of 28 days. The test shall be carried out in a laboratory approved. Neither the mix proportions nor the source of supply of materials shall be altered without the prior approval of the Employer except that the Contractor shall adjust the proportions of mix as required, to take account of permitted variations in the materials, such approval shall be subject to the execution, to the Engineer’s satisfaction, of trial mix procedures set out herein. (f) Concrete cubes are to be taken and tested to verify the concrete strength during the concreting works. The Contractor shall provide the cube moulds at site for the purpose, accordingly. The test specimens shall be 150mm cube and the mould shall be of metal with inner faces accurately machined in order that opposite sides of the specimen are plane and parallel. Each mould shall be provided with the metal base having a smooth machined surface. The interior surfaces of the mould and base should be lightly oiled before concrete is placed in the mould. (g) Concrete strength Grade ‘35’, ‘30’, ‘25’, and ’20’ concrete shall have the minimum strengths as given by Works Cubes Tests shown below. The grade of concrete stated is concrete characteristic strength below which not more than 5% of the test results may fall, Concrete target mean strength Fcu.o = Grade in N/mm²+ 1.645ơ where Ơ = standard deviation of the strength tests, 1.645 is the probability factor and 1.645ơ is the design margin. Target mean strength shall exceed required characteristic strength by the design margin value, and concrete production shall aim to attain this mean, KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 127 of 270 128 SECTION V: TECHNICAL SPECIFICATIONS 7 Days 28 days Minimum Crushing Strengths Grade 35 Grade 30 23.5 N/ mm² 20.0 N/ mm² 35.0 N/ ² mm 30.0 N/ mm² Grade 25 16.5 N/ mm² 25.0 N/ mm² Grade 20 13.5 N/ mm² 20.0 N/ mm² The average strength obtained from cube tests shall be 10 per cent higher than the Strength shown above. Subject to design the minimum grade for structural concrete shall be Grade 25, Grade 15 will be allowed for blinding concrete, precast concrete minimum grade shall be Grade 30. (h) Tests required and Sampling Sampling of materials Approved sources, graded aggregates, sampling and testing to BS 812, Workability Fresh concrete slump test. Slump range 25 – 50mm, - mechanical vibration and maximum 1.5m fall method of placing. Strength/durability Compression/cube (150mm) test, three after seven days and three at twenty-eight days. Test to BS 1881. Works cubes are to be made at intervals as required by the Employer. The cubes shall provide a continuous record of concrete work. The cubes shall be made in approved 150mm moulds in strict accordance with code of practice. Three cubes shall be made on each occasion from different batches, the concrete being taken from the point of deposit. Each cube shall provide a distinguishing number (numbers to run consecutively and the date, and a record shall be kept on site, giving the following particulars:(I) Cube number (II) Date made (III) Location in work (IV) 7 –day Test Date; …………… Strength ……………… 28 –day Test………….. Strength…………… Cubes shall be forwarded, carriage paid for, to an approved Testing Authority in time to be tested two at 7 days and one at 28 days and the remaining one at the discretion of the Employer. No cube shall be dispatched within 3 days of casting. Copies of all work Cube Test results shall be forwarded to the Employer within one week after test and one shall be retained on site office file. If the strength required above are not attained, and maintained throughout the carrying out of the contract, the contractor will be required to increase the proportion of cement and/or substitute better aggregate so as to give concrete which does comply with the requirements of the contract .The contractor may be required to remove and replace at his own cost any concrete which fails to attain the required strength as ascertained by Work Cube Tests. The contractor must allow in his rates for concrete test cubes for all expenses in connection with the preparation and conveyance to the Testing Laboratory and of test cubes and no claim in respect of his failure to do so will be entertained. Piling and Other Special works. Piling will be carried out using an approved procedure throughout. The actual length and numbers of piles required at any location will be approved by the Employer on the basis of the final agreed design data; and payment made for departures form the assumed tender design quantities on the basis of the difference of quantities times the schedule variation rates. Tender Prices shall include for all necessary casings, pumping, depreciation of piling machines, materials, transportation and others. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 128 of 270 129 SECTION V: TECHNICAL SPECIFICATIONS Where special ground conditions exist which do not allow for any of the designs in an original or modified form special types of foundations may be employed which will be paid for on the basis of schedule rates where applicable. To this extent the schedule variation rates for concrete, steel and excavations shall apply throughout irrespective of special conditions. Where ordered by the Employer, the contractor shall carry out pile bearing and uplift test for all types of pile generally in accordance with the method given in the BSCP-2004. Such tests shall be carried out to determine the ultimate uplift and bearing values. Following special requirement shall additionally be considered: (A)Construction Joints Construction joints shall be permitted only at the position predetermined on the Drawings or as instructed on the site by the Employer. In general they shall be perpendicular to the lines of principal stresses and shall be located at points of minimum shear, viz. vertically at or near, mid-span of slabs, ribs and beams. Suspended concrete slabs are generally to be cast using alternate bay construction in bays not exceeding 15.000M in length. No two adjacent bays are to be cast within a minimum period of 48 hours of each other. The joints between adjacent bays are to positions agreed with the Employer. Joints shall be water tight and use of water bars and appropriate sealant shall be specified in all cases. (B)Construction Bays The Contractor shall agree with the Employer, prior to the commencement of concreting, upon the sequence of placing concrete and the positions of vertical and horizontal joints, whether shown or not on the drawings. In general, slabs in excess of 6 meters in length and/or width and walls exceeding 6 meters in length shall not be poured in one operation and subsequent adjacent shall not be concreted within 7 days. The maximum are of any pour shall be 100- mm². In the light of experience the Employer may consider the above pour size limits to be excessive and will have the authority to reduce them. Expansion joints shall be fully detailed on construction drawings for approval. Expansion joints shall be filled with bitumen-impregnated fiberboard to full depth and width. The infilling will be permitted to be used as permanent formwork only for the second casting. Where the fibreboard is exposed it shall be cutback for a depth of at least 2cm from the chambered edge, filled and pointed with a resilient liquid polysulfide polymer sealant to the manufactures instructions. Where dowel bars are indicated on the Drawings forming part of a joint, they shall be held securely horizontal and perpendicular to the joint during concreting. (C) Formwork All, “forms, falsework or shuttering” shall include all temporary moulds forming the concrete to the required shape and size together with any special lining that may be required to produce the concrete finish specified. A. All timber for formwork, falsework and shuttering shall be sound wood, well seasoned and free from lose knots, shakes, large cracks, warping and other defects. Before use on the work, it shall be properly stacked and protected from injury from any source.Any timber which becomes badly warped or cracked prior to the placing of concrete shall be rejected. B. If the contractor proposes to use steel shuttering, he shall submit to the Employer dimensioned drawings of all the component parts, and give details of the manner in which he proposes to assemble or use them. Steel shuttering will only be permitted if it is sturdy in construction and if the manner of its use is approved by the Employer. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 129 of 270 130 SECTION V: TECHNICAL SPECIFICATIONS C. Struts and props shall, where required by the Employer, be fitted with double hardwood wedges or other approved devices so that the moulds may be adjusted as required and eased gradually when required. Wedges shall be spiked in to position and any adjusting devices locked before the concrete is cast. D. All forms shall be wood and shall be built grout- tight and of sufficient rigidity to prevent distortion due to the pressure of the concrete and other loads incidents to the construction operations. Forms shall be constructed and maintained so as to prevent warping and the opening of joints due to shrinkage of the timber. E. All formwork shall be approved by the Employer before concrete is placed within it. The contractor shall if required by the Employer provide the latter with copies of his calculations of strength and stability of the formwork or false work but not withstanding the Employer’s approval of these calculations, nothing shall relieve the contractor of his responsibilities for the safety or adequacy of the formwork. Form of construction joints F. Where permanent or temporary joints are to be made in horizontal or inclined members, stout stopping off boards shall be securely fixed across the mould to form a grouting joint The form of the permanent construction joints shall be as shown on the Drawings. G. Where reinforcement or water stops pass through the face of construction joint the stopping off boards shall be drilled so that the bars or water stop can pass through or the board shall be made in section with a half round indentation in the joint faces for each bar so that when placed, the board is neat and accurate fit and not grout leaks from the stops. H. The forms shall be restrained and unyielding and shall be so designed that the finished concrete will conform to the proper dimensions and contours. The design of the forms shall take into account the effect of vibration of concrete as it is placed. I. All sharp edges inside the forms shall be provided with 25mm triangular fillets, unless otherwise shown on the drawings or directed by the Employer. J. Openings for the inspection and cleaning of the inside of shuttering for walls, piers and columns shall be formed in such a way that they can be closed conveniently before commencing. K. When concrete is to be deposited to a steeper slope than 45 deg. to the horizontal, top forms shall be used to enable the concrete to be properly compacted. L. Form, clamps, tie bolts and anchors shall be used to fasten forms. The use of wire ties to hold forms in position during placing of concrete will not be permitted. Tie bolts and clamps shall be positive in action and of sufficient strength and number to prevent spreading or springing of the forms. They shall be of such type that no metal part shall be left within the specified concrete. M. The cavities shall be filled with grout mortar and the surface left sound, smooth, even and uniform in colour, All forms form for outside surfaces shall be constructed with stiff wales at right angles to the studs and all form clamps shall extend through and fasten such wales. N. The shapes, strength, rigidity, water tightness, and surface smoothness of re-used forms shall be maintained at all times. Any warped or bulged timber must be replaced. Forms, which are unsatisfactory in any respect, shall not be re-used. O. All forms shall be treated with approved mould or similar oil or be soaked with water immediately before placing concrete to prevent adherence of concrete. Any materials which adhere to or discolour concrete shall not be used. P. All forms shall be set and maintained true to the line designed until the concrete is sufficiently hardened. Forms shall remain in place for periods which shall be as specified hereinafter. When forms appears to be unsatisfactory in any way, either before or during KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 130 of 270 131 SECTION V: TECHNICAL SPECIFICATIONS the placing of concrete, the Employer shall order the work stopped until the defect have been corrected. Release Agent Q. Only approved chemical release agents, mould creams (emulsions of water in oil) or oils containing a proportion of surfactant not exceeding 2% will be permitted. Water-soluble emulsion and oils without surfactant shall not be used. Oil based release agents shall be applied at a ratio of 7m²/litre, 24 hours in advance of concreting, preferably by spray or roller. Chemical release agents shall be applied in accordance with the manufacturer’s recommendations. R. The greatest care must be taken that all sawdust shavings, ships and debris is removed from the formwork before concrete is placed in position and the necessary arrangements must be made by leaving out a board in the bottom of the formwork or otherwise required. S. The erection, easing, striking and removal of all formwork must be done under the personal supervision of a competent foreman, and any damage occurring through fault formwork or its incorrect removal shall be made good by the contractor at his own expense. T. All projecting fins on the concrete surfaces after removal of formwork shall be chipped off, and any voids or honey combing to any surface made good to the requirements of the Employer. U. No patching of the concrete is to be done before inspection of the concrete surfaces as stripped. V. Traffic or loading must not be allowed on the concrete until the concrete is sufficiently matured and in no case shall traffic or loading be of such magnitude as to cause deflection or other movement in the formwork or damage to the concrete members. Where directed by the Employer props may be required to be left in position under slabs and other members for greater period than those specified hereinafter. W. It shall be the Contractor’s responsibility that no distortion, damage overloading or undue deflection is caused to the structure by the striking of formwork, but the Employer reserves the right to delay the time of striking in the interest of the work. Formwork shall not be struck until the concrete has sufficiently hardened. Approval of the Employer shall not relieve the Contractor of his liability to make good any concrete damage by premature removal or collapse of forms. In no circumstances shall forms be struck until the concrete reaches cube strength of at least twice the stress to which the concrete may be subjected at the time of striking. The following times given in days (24 hours) are the absolute minimum that will permitted:Striking Times Forms Walls, Columns (unloaded Beam sides Slabs – props left under Beams soffits – props left under Slabs – props Beams – props Ordinary Cement 2 7 14 14 18 Portland Rapid Hardening Cement 2 2 5 5 8 The time for removal of forms as set out shall not apply to slabs and beams spanning more than 10 metres. For such spans appropriate times shall be recommended or advised by the Employer. The periods given above are based on the removal of all props and formwork using ordinary Portland Cement under average weather conditions. Adverse weather conditions or different cement may cause the above periods to be increased. Should the contractor wish to make use of reduced striking time then he must satisfy the Employer that the strength of the concrete at such time and the structural system is adequate to withstand the dead and imposed loads applied to it. Before making use of reduces striking times the Employer’s agreement must be obtained in writing. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 131 of 270 132 SECTION V: TECHNICAL SPECIFICATIONS Finishes Saw finish- The shuttering shall consist of saw boards, sheet metal or other materials to give a support to the concrete. Appearance is not of primary importance for this class of formwork. It shall be used for surface against which backfill or further concrete is to be placed. The treatment of the shuttering or concrete to provide a bond for the further surface treatment of the concrete shall be directed or approval by the Employer. Masonry or similar material used for facing concrete shall only be used as shuttering where directed by the Employer. The Employer’s approval shall be obtained to the use of blocks or slabs when used as permanent forms in foundation and other similar location. A. Wrought finish. The shuttering shall be wrought with boards arranged in a uniform pattern. Alternatively, plywood, metal panels or other approved materials may be used, subject to the Employer’s approval. Joints between boards or panel shall be horizontal or vertical unless otherwise directed. This shuttering shall give a good finish to the concrete and will normally be used for all faces where a high-class finish is not necessary. B. Fair-faced finishing. Standard steel panels, hardboard and boarding will not be permitted for the face of this shuttering. The shuttering shall be faced with resin-bonded plywood, faced with matt finished plastic or equivalent material in large sheets, which shall be arranged in an approved uniform pattern. Whenever possible, joints between sheets shall be arranged to coincide with features such as stills, jambs or changed in direction or the surface areas of formwork between features in walls, between beams in horizontal surface or other similar arrangement, shall where possible, be divided into panels of uniform dimensions, without the use of make-up pieces. All joint between panels on vertical or inclined surfaces shall be vertical or horizontal unless otherwise directed by the Architect; those on horizontal surfaces shall be at right angles and wherever possible they shall be parallel to walls and beams. The shuttering shall give a high class finish to the concrete with no lips, fins, or irregularities, and shall give a completely true and even surface, which will be prominently exposed to view where good alignment is of special importance. It is for use in both in-situ and pre-cast concrete. C. Texture finish. This is an all-over finish of high quality as may be directed by the Employer. Sample panels may be constructed on site prior to commencement of the works, to compare different textures. The shuttering shall be such that the concrete finish give a surface that will be prominently exposed to view a good appearance and alignment are of special importance. D. Where other finishes, apart from the above are specified, the contractor shall provide a sample panel at least 2.4m x 1.2m in vertical surface area including a typical horizontal and vertical joint in the shuttering. The sample panel shall be construction techniques that the contractor proposes for the actual works. This sample when approved will form the standard for the entire works. All unsuccessful samples shall be removed from the site. Floor Finish E. Where “tamped finish” is specified it will be obtained by an edge board to the Employer’s approval. Board works are so be made to a true pattern and will generally be at right angles to the traffic flow. Haphazard or diagonal tamping will not be accepted. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 132 of 270 133 SECTION V: TECHNICAL SPECIFICATIONS 3.15.6 STRUCTURAL STEEL QUALITY OF MATERIALS AND WORKMANSHIP (A) The quality of all materials and workmanship used in the execution of this contract shall comply with the requirements of the most recent issues of the following British Standards and code of practice, including all amendments. B.S 4 (part 1) Hot Rolled Sections B.S 4 (part 2) Hot Rolled Hollow Sections B.S 449 The use of Structural Steel in Buildings B.S 638 Arc welding plant equipment and accessories B.S 639 Covered Electrodes for manual Metal Arch Welding of Mild Steel and Medium tensile steel B.S 916 Black Bolts, Screws and Nuts B.S 1449 Steel plate, sheet and strip B.S 1775 Steel Tubes for mechanical, structural and General Engineering Purposes B.S 2994 Cold rolled Steel Sections B.S 4190 ISO metric black hexagon bolts, screws and nuts B.S 4320 Metal washers for general engineering purposes B.S 4360 Weldable structural steel B.S 4848 Hot rolled structural steel sections B.S 4872 Approved testing of welds when welding Procedures approval is not required B.S 5135 General requirements for the Metal Arc Welding of Structural steel B.S 5493 Protection of iron and steel structures from Corrosion BS 729 Specification for hot dip galvanized coatings on iron and steel. TOLERANCES All members shall be fabricated with a tolerance in length of + 0mm and -3 mm, all shall not deviate from straightness by more than 1 in 400. The allowance for angular twist shall be (3 + 0.6L) in the length of the member under consideration in metres. Twist shall be measured by placing the member as fabricated against a flat surface measuring the differences between the two corners of the opposite end. The above tolerances shall be adhered to unless otherwise specified on the Engineer’s drawing. (A) Materials All metals and metal work components whether fabricated on or offsite shall conform to the requirements of the relevant British Standards and other standards to the approval by the Employer. Metalwork articles shall have a first class finish, and be free from scale, rust, damage or other defects. Components shall be properly assembled and joined in a neat and functional manner. Welded connections shall be ground off as necessary to present a clean smooth finish without detriment to the strength of the connection. Particular attention shall be given to the protection of metalwork from degradation caused by the environment in which it is to be used. This shall be accomplished by galvanizing, surface coating or such other treatment suitable for the metalwork under consideration. (1) Mild Steel Mild steel shall comply with the relevant standard and shall be galvanized for parts, which are not accessible, or in open air, or come in contact with moisture. All other parts, except reinforcement to concrete, shall be primed as described under the Clause for painting. (2) Copper Copper and copper alloys shall comply with the British Standards and approved standards and approved standards relevant to the form and use for which the material is intended. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 133 of 270 134 SECTION V: TECHNICAL SPECIFICATIONS Copper components shall be placed so that in no case shall they come in direct contact with aluminium nor shall it be possible for water or condensation to pass off copper on to aluminium. (3) Zinc Zinc sheet shall be of good colour, free from cracks, dross, overlaps, scales and any other defects, which might be detrimental to its working properties. All zinc shall be at least 0.8 mm thick. No iron or copper shall be used in contact with zinc. (4) Aluminium Sheeting Aluminium for profiled roof sheeting and flashing shall be manufactured from alloy in hard temper conforming to BS 1470 Ns3 Specification not less than 0.7 mm thickness and with a colour coasted surface finish. Profiled sheeting shall conform to BS CP 5427. Fastenings shall be by means of aluminium hook bolts or other approved fixes in accordance with BS CP 143 Part 1 and recommendations of the manufacturer. Laps shall be sealed as necessary. (5) Galvanizing Where steel members are specified to be galvanized they shall be so treated after all cutting, drilling, punching and removal of burrs has been carried out. Galvanizing shall be applied by the hot dip process and shall consist of a coating of zinc weighing not less than 610 g/m² of surface. The zinc coating shall be smooth, clean, of uniform thickness and free from defects. The preparation for galvanizing itself shall not adversely affect the mechanical properties of the steel. The testing of the zinc coating on galvanized articles shall be carried out in accordance with BS 729. (B) Steel External Doors Steel external doors shall be fabricated from steel sheet covering a framework of steel angles and galvanized after fabrication. Door frames shall also be galvanized steel. All external doors shall be insulated and fitted with panic latches, which are lockable from outside. External doors shall be effectively sealed to reduce the ingress of dust as far as practicable, using heavy duty seals which shall be guaranteed for a minimum period of five years from date of commissioning. Doors and seals shall be designed so that replacement of worn seals can be achieved easily on site. (C) Workmanship All plates and sections shall be true to form, free from twist and straightened before any fabrication work is started on them. Each piece of work shall be distinctly marked before dispatch in accordance with a marking diagram to be provided by the Contractor. 3.15.7 BLOCK WORK A) Materials (1) Cement Cement shall be Sulphate–resisting and of a quality as described in the section for concrete. The clause in that section referring to cement storage shall also apply. (2) Sands an aggregates Fine and course aggregates for forming blocks shall be aggregates from natural sources of hard, durable material or other approved, free from deleterious substances. Sand shall be graded 2 mm down and coarse aggregate shall be as specified for concrete. (3) Lime Lime for mortar shall be hydrated gray-stone lime in accordance with BS 890 for hydrated calcium limes. Magnesia lime shall both be used in mortar for brickwork below the dampproof course. The Contractor shall forward copies of Manufacturers certificates to the Employer, which in addition to certifying compliance with BS 890 shall give details of the type of lime. If lime is delivered as lime putty, the certificate shall state whether quicklime or hydrated lime was used in its manufacture. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 134 of 270 135 SECTION V: TECHNICAL SPECIFICATIONS All lime shall be efficiently protected against deterioration during transport and whilst stored on site. Different type or brands of lime shall be stored separately in dry conditions in a manner that allows it to be used in the order of delivery. When lime putty is to be used the Contractor shall obtain the approval of the Employer of his arrangement for transport handling and storage. Precautions shall be taken to prevent contamination and drying out of lime putty stored on site. Lime putty made from quicklime should mature for at least 14 days before being used. Where it is made from hydrated lime (powder), lime putty should stand for at least sixteen hours before use. (4) Concrete Blocks Concrete blocks shall be solid or hollow blocks to comply with the relevant standard as previously mentioned and shall be solid hard, true to size and shape and sharp arises in accordance with Ministry of Works Standard Specification for Metric sized concrete block for building dated September, 1972. They shall be obtained from an approved manufacturer or manufactured on site in approved block making machines. The mix used shall be less than (1:9) by volume and maximum size of aggregate shall be 12mm size. The blocks on removal from the machine shall be laid on edge or racks under sheds erected by the Contractor and left for 3 days during which period they shall be kept constantly wet. After this initial period they shall be placed on edge in the open racks and protected by sacking or other approved covering and kept wet for further 5 days. Thereafter the blocks shall be left in the same position without wetting for a further 20 days. No blocks shall be used in the works until 28 days old and until samples have been tested approved by the Employer. The Contractor shall ensure that the blocks are stocked separately in their respective categories in the structure in the position shown on the drawings. Any stone for walling shall be good hard local stone equal in standard and quality. Stone shall be squared, dressed and joints chisel dressed on the face. Stone to receive render, shall be so dressed to reduce dubbing-out to a minimum. The coursed stone shall both be less than 150mm deep and 305 mm long. All stone shall be laid on their natural or quarry bed lines. Block Laying All blocks shall be kept completely filled with mortar. The thickness of the horizontal mortar joints shall not exceed 40mm to every four joints. Where block work is to be plastered or rendered, joints shall be struck off and left rough to provide a key. Movement joints shall be provided where required. They shall incorporate a joint filling strip and sealant Gaps in movement joints shall be left free from debris and shall not be pointed with mortar. Block work shall be built with three courses to 600 mm in a uniform manner, in truly level courses and truly vertical or battered. Corners and other advanced work shall be racked back and not raised above the general level more than one meter. Toothing shall be used only where provision has to be made for a future extension. Both leaves of cavity shall be built up simultaneously. Galvanized flat twist wall ties of an approved pattern shall be bedded with a slight fall towards the outer face and shall be provided in alternate courses at intervals of 900mm and staggered horizontally. Additional ties shall be used near the sides of all openings at the rate of one for each 300mm of opening height. The cavity shall be kept clear of mortar droppings and rubbish, and the inside mortar joints shall be finished flush as the work proceeds. Cavities shall be 50-75 mm in width. Both holes shall be built into the external skin of cavity walls in the form of sand filled vertical joints at 1m centres and are to be racked out on completion. Weep holes shall be laced over all lintels. Walls shall be constructed with an approved metal reinforcement every second course. Additional horizontal reinforcement shall be provided in bed joints in walls for each 2courses above and below all openings greater than 300mm wide. The reinforcement shall extend a minimum of 900mm beyond the opening on both sides. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 135 of 270 136 SECTION V: TECHNICAL SPECIFICATIONS Below ground level and at the jambs of all openings, the hollow concrete blocks shall be filled with weak concrete, well taped down and carried from base slab to top of such openings. Cavities shall be kept clear of mortar droppings or other debris, by the use of lifting batters or other suitable means. Where external block work abuts concrete surfaces and where indicated elsewhere, the blocks shall be tied to the concrete every second course with adjustable galvanized steel ties fixed in slots cast into the concrete. Concrete abutting external block work shall be coated with two coats of bitumen paint. Holes and chases shall be cut out or left in the walls as required and provision shall be made for making good to the satisfaction of the Employer. On completion, all block work shall be cleaned down and mortar dropping and other marks removed. Defective blocks or workmanship shall be made good. (6) Reinforcement When required, vertical reinforcement for hollow concrete blocks shall be high yield deformed steel conforming to BS 4449 requirements. The minimum to be provided shall be 10mm diameter bars at 150mm centres. Lap lengths for vertical reinforcement shall be a minimum of 50 diameters. Horizontal bed joint reinforcement shall be made from hard drawn steel wire to BS4482 consisting of two wires with diameter a minimum of 5 mm and separated by cross wires welded at 304-mm centers. The main wires shall be at 50 mm centers and 160mm centers for 100 and 200mm block work respectively. Alternatively, approved expanded mesh reinforcement may be used. (7) Lintels The block work over all openings in walls shall be supported on reinforced concrete grade 25 lintels. All lintels shall be the same width as the block work into which they are being built. Building in Frames Openings in masonry for doors, widows, air conditioning units’ ventilators and fans etc. shall be properly marked out and built in as the work proceeds with approved anchors. The fittings shall be propped and strutted where required. The back surface of steel and galvanized fittings shall be coated with a bituminous paint before fixing. All fittings shall be bedded in 1:3 sand cement mortar 12mm thick. Precautions during Inclement Weather Newly laid masonry work shall be protected from the harmful effects of sunshine, rain, drying wind, running or surface water and shocks. Any work that may be damaged shall be taken out and pointed as directed by the Employer. Any costs incurred in carrying out such remedial work shall be borne by the Contractor. Damp Proof Course (DPC) A damp proof course shall be laid in walls, above ground level so as to exclude rising moisture. Damp-proof courses shall be from one of the following materials: (1) Lead and copper DPC complying with the requirements of BS 743. (2) Asbestos base bitumen DPC complying with the requirement of BS 743 Type C. (3) Asbestos base lead cored bitumen DPC complying with requirements of BS 743 Type F. Damp-Proof Membrane An approved bitumen/PVC waterproof membrane shall be placed on the blinding under concrete floor slabs, to exclude rising moisture. The membrane shall be taken up walls and lapped with the wall DPC. All floor finishes shall be protected from damage by following trades and other causes and any damage, howsoever caused, shall be made good by the Contractor at his own expense to the satisfaction of the Employer. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 136 of 270 137 SECTION V: TECHNICAL SPECIFICATIONS 3.15.8 FLOOR LAYING (A) Screeded Beds Concrete floors, which are required to be surfaced with screed, shall have a roughened surface, produced by hacking and wire brushing. The roughened concrete floor shall be cleaned, wetted preferably overnight, the surplus water removed and 1:1 cement/sand grout brushed into the surface, keeping just ahead of the screeded bed. The screeded bed shall be 40mm thick and shall be well compacted and leveled with a screeding board and steel trowelled smooth. If the screed is the finished surface, it should be treated with an approved silicate of soda solution hardener to prevent dusting. The screed shall be mixed in the proportions of 1:2:4 (cement, sand, and 10mmpea shingle) by volume with the minimum quantity of water necessary to give a good hard smooth, steel trowelled finish. The section hereof concerning concrete applies, but the sand shall satisfy the requirements of BS 1199. Rigid screed battens shall be fixed on continuous beds of mortar to prevent movement when screeds are being laid and compacted. The screed batten shall be fixed to true lines and levels. The bay sizes shall not exceed 15 square meters and the length of any one bay shall be limited to 1.5 times the width. The bays shall be laid alternately, ie. in chequerboard fashion, a minimum of 24 hours being allowed to elapse between the laying of adjacent bays. The bays shall be separated by strips of hard plastic or other suitable material. Screeded beds shall be cured for at least seven days, using polythene sheeting or other approved method. Floor finish shall be terrazzo, granito tiles and ceramic tiles mixture as approved. 3.15.9 CABLE DUCTS, DRAINAGE AND SEWERAGE DISPOSAL (A) Cable Ducts Cable ducts may be constructed of in-situ concrete or pre-cast concrete duct. In each case, the material shall be in accordance with relevant sections of this Specification. All cable ducts shall be laid in straight lines and regular gradients between cable pits, as directed. All ducts shall be kept clear from earth, debris and other obstructions during and after laying. (B) Drainage All drainage shall be designed for common use with cable ducts, in accordance with approved standards and Codes of Practice. All drains shall be laid in straight lines and regular gradients as described or directed. Great care shall be exercised in setting out and determining the level of the drains. All drains shall be kept clear from earth, debris, superfluous cement and other obstructions during and after laying. Underground drains shall be provided with inspection well at appropriate sections and connected to common underground infiltration tank. C) Sanitary Fittings Wash hand basins shall be supported on cantilever brackets cut and pinned to the walls or screwed to 30mm timber chambered backboards, which shall be plugged and screwed to the walls. They shall be provided with 35mm bottle traps with brass cleaning eye and lining soldered on, or alternatively, a similar PVC fitting. Cistern supporting brackets shall be screwed to 30mm timber chambered backboards, which shall be plugged and screwed to the walls. Overflow pipes from WC cisterns shall be 20mm bore. Glazed ware shall be of best quality and type and manufacture approved by the Employer. Fittings shall be securely fixed in an approved manner. Cisterns shall be plastic wherever possible. D) Overhead Reservoir water tank The contractor shall provide for an overhead plastic water tank with a capacity of not less than 2,500 litres. 3.15.10 PAINTING AND DECORATING Paints for priming, undercoat and finishing shall be ready mixed paints of the best quality for the intended use and comply with BS 6150. Paint for use on concrete or block work shall be of a type specially prepared for this purpose. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 137 of 270 138 SECTION V: TECHNICAL SPECIFICATIONS All work shall be properly cleaned and rubbed won between each coat in a way, and using materials, recommended by the manufacturers of the paints concerned. No coat shall be commenced until the Employer has passed the previous coat a dry, hard and satisfactory. Each coat shall be of a distinct colour from the preceding one and all colours shall be approved by the Employer. Spray painting will not be permitted except for internal faces of walls and ceiling. All other paint shall be thoroughly brushed into and completely cover the surface. All timber required to be built into bedded or fixed against brickwork, masonry or concrete shall be given two priming coats and one undercoat on the concealed surfaces. All woodwork shall have knots treated with two coats of a knotting solution and then painted with aluminium priming paint prior to priming the complete surface. The wood shall then be primed, stopped and painted with two undercoats and one high glossfinishing coat. Hard wood, which is not required to be painted, shall be made perfectly smooth, prepared and oiled twice with linseed oil. Alternatively, it shall be stained and wash-polished, or treated with two coats of an approved varnish. Bitumastic painted surfaces and coated pipes shall be thoroughly cleaned to remove grease, dirt or other deleterious matter, and then painted with one coat of sealer, one coat of leafing aluminium, one coat of undercoating paint and one coat of high gloss finish. When so described or directed, internal surfaces of fair-faced block work, plastered walls and the soffits of concrete roofs shall be prepared and painted with one coat of antisuction primer, followed by one undercoat and two finishing coat of PVA based plastic emulsion paint. Exterior surfaces for fair faced block work walls and concrete columns at the new buildings shall be prepared and painted with two coats of an approved stone paint. At the completion of all works, the Contractor shall clean down the premises; wash paving and steps; wash and leather down wall tiling, etc. Clean all sanitary fittings; touch up paint work; examine all roofs and leave watertight; clean out all pipes and leave the whole of the premises in a clean, sound and perfect condition ready for immediate occupation. 3.15.11 (A) SECURITY FENCING AND GATES Security Fencing Chain link gauge 8 or equivalent fences shall be constructed in accordance with BS 1722, Part 10 and shall be of such manufacture that when any one segment is cut, remaining segments within the pattern retain their rigidity. Overall height of the fencing shall be 2.4metrs above ground level, excluding barbed wire. Posts of the fences shall be of steel structure with concrete block foundations. The perimeter fences shall be earthed independently of the main switchyard earthing with an adequate earthing rod at every 5 supporting posts of the fences. The posts shall have cranked tops set at 45° to the posts, to which shall be attached three stands of galvanized barbed wire to BS 4102. Barbed wires shall be strained between straining posts with eyebolts and fixed to intermediate posts with stirrup wires. Intermediate posts shall be provided at centres not exceeding 3 meters. Corner posts and struts shall be provided at all ends, corners, adjacent to gate posts and at intervals not exceeding 35 meters. All fence fittings shall be galvanized. (B) Gate A gate shall comply with BS 1722, Part 10 and shall be constructed of galvanized chain link mesh on galvanized extension arms. Separate man gate shall be provided beside the main gate. The gate shall be fitted with a vertical drop bolt on each leaf, a sliding bar lock with padlock eyes and a padlock to prevent movement of the sliding bar lock. All these fittings shall be galvanized. The vertical drop bolts are to drop into galvanized steel tubes cast into KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 138 of 270 139 SECTION V: TECHNICAL SPECIFICATIONS the road, to secure the gate when in both closed and open positions. Gateposts shall be made from galvanized steel RHS or tubular section shall be capped and set in concrete in the ground. Gate hinges (pivots) shall be heavily galvanized. 3.15.12 ANCILLARY CIVIL ENGINEERING AND BUILDING WORKS General The ancillary civil engineering and building works for the Project are classified as follows:(1) Air conditioning and ventilating works. (2) Fire safety facilities, and (3) Control room at KPA. (1) Air Conditioning and Ventilating services Air Conditioning Supervisors’ office, Control room, Library, Communications equipment and battery room shall be air-conditioned. Air conditioning shall be provided in the form of self-contained air conditioning units, in a designed capacity for proper operation and maintenance of communications equipment proposed by the Contract. The air conditioning units shall be individually thermostatically controlled to maintain internal conditions at 20 to 22 degrees centigrade. Mechanical Ventilation Supply and extract ventilation shall be provided to serve the toilet/wash rooms. Supply air handling plants shall consist of a fresh air intake louvers, insect screen, filter and fan. Extract ventilation shall be provided by means of wall mounted fans, roof extract units or ducted systems with louvered discharges to atmosphere. Design All air conditioning and ventilation systems shall be designed for continuous operation. Plant shall be arranged to facilitate maintenance and future replacement of equipment. The Contractor shall calculate heat gains and losses under the local conditions, taking into account solar radiation, thermal transmittance through roofs, walls, floors and windows, fresh air requirements, heat emission from installed electrical equipment and lighting, personnel, infiltration and any other sources. The Contractor shall be responsible for determining the heat transfer coefficients for all materials used in building construction. In the event of any change in materials, design or method of building construction, the Contract shall at all times be responsible for rechecking the design of all system to ensure that they are capable of meeting the specified design requirements. Self contained room air conditioners shall be of the through-the-wall pattern and complete with adjustable grilles, heavy gauze zinc coated stove enamelled sheet steel casing with single or two colour decorative finish. The casing and position shall be such as to protrude not more than 250mm into the conditioned space and not external projection beyond the building line will be permitted other than the fixing of the condenser cooling air grille. Compressors shall be of the fully hermetic type, fitted with resilient mountings and complete with thermal overload protection and starting relays. Evaporators shall be manufactured of copper tube with copper or aluminium fins mechanically bonded. The evaporator fan shall be of double inlet double width type and complete with continuously rated totally enclosed electric motor. Filters shall be of the washable type, suitably positioned for easy access for cleaning. Automatic control by means of an integral thermostat shall be provided together with the safety controls to prevent excessive cooling. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 139 of 270 140 SECTION V: TECHNICAL SPECIFICATIONS (2) (3) 3.16 (A) Fire Safety Facilities Portable fire extinguishers shall be provided under this Contract. Portable, wall mounted, hand held extinguishers shall be 5.5 Kg pressurized control discharge BCF units. The body of the extinguisher shall be seamless, welded and brazed as appropriate. The extinguisher shall be capable of being released by means of a lever-operated valve provided with a safety pin. Extinguishers shall be capable of controlled partial discharge. The type shall be of that recharge unit that is locally available. The extinguishers shall be wall mounted and attached in a manner affording quick release from the supporting bracket. They shall be installed so that the top of the extinguisher is not more than 1.5 meters above the floor. In no case shall the clearance between the bottom of the extinguisher and the floor be less than 0.1 meter. The extinguishers shall be positioned so that the instructions for operation face outwards. Automatic control by means of an integral thermostat shall be provided together with the safety controls to prevent excessive cooling. Control room At the new KPA Substation, the control room shall be at least 240m², and shall house the following; 11kV switchgear Circuit breaker control and protection relay panels room Battery room Battery chargers and distribution boards Communication equipment Fully furnished Office A washroom ,WC, Urinal and Bath Equipment/Utility store Library/Records room TESTS AT THE SITE During the construction and after the installation of each item of equipment under the Section 2, tests shall be performed, as specified herein, to establish the accuracy of the assembly and to prove the adequacy of the materials and the workmanship. All tests and tests procedures shall be approved by the Employer. The Contractor shall perform the following tests of each subsection, for all items where applicable, to ensure that the equipment has been correctly installed, all necessary adjustments and settings made, and that the item is in sound condition to run under load. Inspection during erection of equipment (a) Appearance check of all equipment (b) Calibration of pressure gauges (c) Protective relay check (d) Oil tightness check and gas leakage tests (e) Measurement of the resistance of the main circuit (B) Test after the installation of equipment 1. Substation Switchgear. a. Circuit breakers i. Closing and opening operation test ii. Trip-free operation test iii. Manual operation test iv. Remote operation test v. Main Contact resistance test vi. Breaker timing (closing time and opening time) vii. Measurement of insulation resistance b. Disconnecting switches i. Operation test (manual and remote) ii. Check of interlock mechanism iii. Measurement of insulation resistance KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 140 of 270 141 SECTION V: TECHNICAL SPECIFICATIONS (3) (C) iv. Main Contact resistance c. Lightning arresters i. Measurement of insulation resistance d. Current transformers i. Measurement of insulation resistance ii. Ratio test iii. Polarity check iv. Magnetisation curve to confirm knee point e Voltage transformers i. Measurement of insulation resistance ii. Ratio and Polarity check. 2. Control, measuring and protective equipment a. Control and measuring equipment i. Relay tests ii. Measurement of insulation resistance iii. Sequential operation check iv. Calibration of meters b. Protective relaying equipment i. Individual relay calibration and Functional tests ii. Residual voltage (current) measurement iii. Measurement of burden iv. Current and voltage transformer circuits grounding point check v. Sequential operation test at each station by primary and secondary injection to check sensitivity and stability vi. Station to station operation performance tests (transmission line protective relaying equipment only). vii. Test on Trip and alarm circuits viii. Stability, Operation, and Sensitivity of transformer unit schemes . ix. Calibration Tests on all Instruments x. Calibration Test on Energy meter Miscellaneous materials a. Outdoor bus i. Measurement of insulation resistance b. Power cables i. High voltage test ii. Insulation resistance measurement c. Control cables i. Insulation resistance measurement ENVIRONMENTAL REQUIREMENTS The Contractor shall undertake to complete all works in accordance with statutory requirements including those of: i) The Kenya Agricultural Act - Concerning protection against soil erosion. ii) Public Health Act – Concerning with noise, water and air quality as they relate to human health. iii) Chief Authority Act – Concerning the regulation of timber cutting and wasteful destruction of trees and avoidance of damage to the public road or other community facilities. iv) The Local Government Act – Section 145 for preservation or protection of wildlife and Section 163 regarding noise disturbance controls. v) Environment Management and Coordination Act - EMCA”99, Kenya Environmental Law and accompanying gazetted regulations. vi) Energy Act 2007 Environmental provisions. vii) Forest and Wildlife Act viii) Clearance and disturbance of natural vegetation shall be kept to a minimum to prevent habitat loss and to keep soil erosion in check. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 141 of 270 142 SECTION V: TECHNICAL SPECIFICATIONS 3.17 SITE VISIT In practising due diligence, the contractor is specifically advised to inspect the site & terrain and be well acquainted with the actual working and other prevalent conditions, facilities available, position of material and labour. The bidder is advised to visit and examine the site where the plant is to be installed and its surroundings and obtain for itself on its own responsibility all the information that may be necessary for preparing the bid. The bidders shall ask for necessary clarifications required for clearly understanding the scope & technical /commercial requirements of the tender from KPA before submitting their offer. B. TECHNICAL SPECIFICATIONS FOR 11kV SWITCHGEAR These specifications lay down requirements for 11kV metal clad switchgear panels. They are intended for use by Kenya Ports Authority in purchasing the equipment. They must be read together with the accompanying Technical Specifications for 132 KV Switchgear, Control, Protection and Communications Equipment. NOTE: These specifications have been derived from the standards of the Kenya Power and Lighting Company (K.P.L.C) and the tenderer is therefore advised to get acquainted with the said standards. 1. GENERAL SPECIFICATIONS 1.1 SCOPE These Specifications cover the Design and Engineering, Manufacture, Testing at the Manufacture’s Factory, painting, packing for transport, insuring, shipping, delivering to the port of Kenya, landing, customs clearing, transporting and Delivery to KPA stores of 11 KV Indoor Metal Clad Switchgear Panels . Subsequent paragraphs will give detailed descriptions and requirements for the Switchgear Panels, including Circuit Breakers, Current, Transformers, Voltage Transformers, Protection relays, metering, measuring, indicating and control devices and other equipment / devices, specified herein. 1.2 STANDARDS Rating, characteristics, tests and test procedures, etc, for the 11kV metal-clad switchgear panels and all the protection relays, measuring and indicating instruments and the control and monitoring devices and accessories, including current transformers and voltage transformers shall comply with the provisions and requirements of the standards of the International Electro-technical Commission (IEC), and also relevant ANSI standards where specified. The last revision or edition in effect at the time of bid invitation shall apply. Where references are given to numbers in the old numbering scheme from IEC it shall be taken to be the equivalent number in the new five-digit numbers scheme. The bidder shall specifically state the precise standard, complete with identification number, to which the various equipment and materials are manufactured and tested. The bid document may not contain a full list of standards to be used, as they only are referred to where useful for clarification of the text. 1.3 UNIT OF MEASUREMENT AND LANGUAGE In all correspondence, in all technical schedules and on all drawings prepared by the manufacturer, the metric units of measurement shall be used. On drawings or printed pamphlets where other units have been used, the equivalent metric measurement shall be added. All documents, correspondence, drawings, reports, operating and maintenance instructions/manuals and nameplate details of the equipment shall be in English language. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 142 of 270 143 SECTION V: TECHNICAL SPECIFICATIONS 1.4 SERVICE CONDITION From the geographical condition, the area where the switchgear panels shall be installed is categorized into the tropical climate zone. In choosing materials and their finishes, due regard shall be given to the humid tropical conditions under which the switchgear panels shall be called upon to work. The manufacturer of the switchgear panels shall submit details of his usual practice of tropicalization which have proven satisfactory for application to the switchgear panels and associated equipments to prevent rusting and ageing in the tropical climate zone. The applicable standards for tropicalization shall be listed. 1.4.1 Climatic Conditions Unless otherwise specifically stated in particular technical specifications any equipment or component or assembly shall be designed for the following service conditions: Parameter Max Min Ambient air temperature Outdoor +400C -10C 0 Indoor +40 C -10C 0 24 hours average +30 C -10C maximum Relative humidity 90-100% Height above sea level EMC Class (IEC 6100) Seismic coefficient Rainfall condition Average Maximum Annual mean isokeraunic level Pollution (IEC 60815) Creepage 2200m Industrial environments 1.5 800-1700 mm/year 160mm in 24 hours Max 180 thunderstorm days Heavy: class II 25mm/KV 1.4.2 Switchgear Room Temperature The switchgear should be suitable for installation in a room without air conditioning but with ventilation to allow natural cooling. Therefore all the protection and control devices employed shall be capable of operating in this environment without failure for their designed life time. Particularly the power supply modules of the protection and control devices shall be designed for minimum heat generation and effective heat dissipation to ensure that the temperature of these devices enclosed in the relay panels at the above listed ambient temperature shall not exceed the maximum operating temperature of the device. 1.4.3 Tropicalization (a) All equipment must be designed for operations in the service tropic climate conditions and fully comply with climatic aging tests as per IEC 60932 – class 2. In choosing materials and their finishes, due regard shall be given to the humid tropical conditions under which the switchgear will be called upon to work. The manufacturer shall submit details of his usual practice which have proven satisfactory for application to the parts of the switchgear panels, which may be affected by tropical conditions. (i) Metals Iron and steel are generally to be painted or galvanized as appropriate. Indoor parts may alternatively have chromium or copper-nickel plates or other approved KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 143 of 270 144 SECTION V: TECHNICAL SPECIFICATIONS (ii) (iii) protective finish. Small iron and steel parts (other than rustless steel) of all instruments and electrical equipment, the cores of electromagnets and the metal parts of relays and mechanisms shall be treated in an appropriate manner to prevent rusting. Screws, Nuts, Springs, Etc The use of iron and steel shall be avoided in instruments and electrical relays wherever possible. Steel screws shall be zinc, cadmium or chromium plated or where plating is not possible owing to tolerance limitations, shall be of corrosion resisting steel. Instrument screws (except those forming part of a magnetic circuit) shall be of brass or bronze. Springs shall be of non-rusting material, e.g., phosphor-bronze or nickel silver, as far as possible. Rubbers: Neoprene and similar synthetic compounds, not subject to deterioration due to the climatic conditions, shall be used for gaskets, sealing rings, diaphragms, etc. 1.5 WORKING STRESS AND EQUIPMENT /APPARATUS DESIGN 1.5.1 General (a) The design, dimensions and materials of all parts shall be such that they will not suffer damage under the most adverse conditions nor result in deflections and vibrations, which might adversely affect the operation of the equipment. Mechanisms shall be constructed to avoid sticking due to rust or corrosion. (b) The equipment and apparatus shall be designed and manufactured in the best and most substantial and workmanlike manner with materials best suited to their respective purpose and generally in accordance with up-to-date recongnized standards of good practice. (c) The equipment shall be designed to cope with 0.2g horizontal acceleration of seismology on the centers of gravity. (d) Whenever possible, all similar parts, including spare parts, shall be made interchangeable. Such parts shall be of the same materials and workmanship and shall be constructed to such tolerances as to enable substitution or replacement by spare parts easily and quickly. (e) All equipment shall be designed to minimize the risk of fire and consequential damage, to prevent ingress of vermin and dust and accidental contact with electrically energized or moving parts. The switchgear panels shall be capable of continuous operation with minimum attention and maintenance in the exceptionally serve conditions likely to be obtained in a tropical climate and where the switchgear is called upon to frequently interrupt fault currents on the system and also where the duty of operation is high. 1.5.2 Strength and Quality (a) All steel casting and welding shall be stress-relieved by heat treatment before machining and castings shall be stress-relieved again after repair by welding. (b) Liberal factors of safety shall be used throughout, especially in the design of all parts subject to alternating stresses or shocks. 1.5.3 Design data low voltage equipment Low voltage equipment and installation shall be designed in accordance with EMC directives. The rating and design criteria for low voltage equipment shall be as follows: (a) AC Supply Rating system Rated voltage between phases Connection type Rated voltage between phase to earth Grounding system Frequency Voltage variation Frequency variation 415 V AC 3ph 4 wire 240 V AC PME 50 HZ +/-10% +/-2% KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 144 of 270 145 SECTION V: TECHNICAL SPECIFICATIONS Power frequency 1 min, Test Voltage Thermal rating of conductors Max short-circuit current 3 kV 120% of load 31.5 kA The AC supply shall be used for power circuit and for lighting, indication,motor controls and similar small power circuits. Unless otherwise specified, the equipment provided under this tender is to be capable of reliable operation at voltages as low as 85% of the rated voltage, and to withstand continuously up to 110% supply voltage above the rated value of 240V or 415 V AC. (b) DC Auxiliary Supply Rating Equipment/ Device Rated voltage Connection type Voltage variation (I) 110 V DC 2 wire 85-137 V DC The auxiliary dc supply shall be used for controls, indication, alarm, protection relays, and circuit breaker tripping and closing circuits, e.t.c. All equipment and apparatus including the circuit breakers, protective relays, control, devices and accessories, measuring and indicating instruments and electronic equipment shall be capable of satisfactory operation at 80% t0 125% of the rated dc supply voltage. (II) 1.5.4 Design data for Medium voltage plant and equipment The rating and design criteria for the MV plant and equipment shall be as follows:ITEM 1 2 3 4 5 6 7 8 9 10 11 12 12a 12b 13 12a 12b 13 Parameters System description Neutral point earthing Nominal system voltage Highest system (Service) voltage as defined by IEC 0 69938 Highest Equipment Rated Voltage as defined by IEC 60071 Symmetrical Short – Circuit Rating Short-circuit current withstand , not less then 3 second Dynamic peak current (min making current) not less than Rated current of busbars Rated current for transformer incomers and bus coupler Minimum rated continuous current of circuit breakers Insulation level according to IEC 60071: Lightning impulse withstand voltage (1.2/50 µ kV Peak Test voltage at power frequency 1 min dry and wet. To earth and between phases For the design and erection of the busbars the following minimum clearance shall be observed Phase to earth [mm] Phase to phase[mm] Minimum nominal creepage distance as defined in IEC 60815, Table II SYSTEM PARAMETER 50Hz, 3 phase, 3 wire Solid earthed 11 kV 12 kV 17.5 kV 31.5 kA 31.5 kA 78 kA 2000 A 1500 A 630 A 95 kV 38 kV 300 250 25mm /kV KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 145 of 270 146 SECTION V: TECHNICAL SPECIFICATIONS 1.6 BASIC REQUIREMENTS FOR ELECTRICAL EQUIPMENT All materials supplied under this Contract shall be new and of the best quality and of the class most suitable for working under the conditions specified. They shall withstand the variations of temperature and atmospheric conditions arising under working conditions without distortion, deterioration or undue stresses in any parts and also without affecting the suitability of the various parts of the works for which they were designed. 1.6.1 Electrical controls, auxiliaries and power supplies (a) Responsibility for electrical control and auxiliaries. The manufacturer shall provide all control, indication, alarm and protection devices and all auxiliary equipment with wiring and interconnecting cable which are integral parts of or are directly associated with or mounted on the switchgear panels to be supplied under this tender. The design of protection and control schemes for the switchgear panels shall be subject to approval by the employer. (b) Operation and control Interlocking devices shall be incorporated in the control circuit to ensure safety, and proper sequence and correct operation of the equipment. 1.6.2 Corona and radio interference (a) (b) (c) Switchgear shall electrically be designed to avoid local corona formation and discharge likely to cause radio interference. The design of jointing of adjacent metal parts and surfaces shall be such as to prevent corrosion of the contact surfaces and to maintain good electrical contact under service conditions. Particular care shall be taken during manufacture of busbars and fittings and during subsequent handling to ensure smooth surface free from abrasion . All joints on the busbars and the circuit within the switchgear board shall be silver or tin-plated to ensue good electrical connection. 1.6.3 Switchgear Panels (a) (b) (c) (d) (e) The switchgear panels shall be dead-front, floor-standing, rigid welded steel frames, completely enclosed by metal sheets and suitable for indoor installation. The floor-standing switchgear panel shall have provision for bolting to the floor. Suitable terminal blocks shall be provided for all outgoing power and control cables. All cable terminals shall generally be located for bottom entry and connections. The switchgear panels shall be painted to RAL 7032 colour. Enclosures for the switchgear panel and for other electrical equipment shall have the following degree of protection (ref IEC 60034, IEC 60529 and IEC 60947) Equipment Degree of protection Medium voltage enclosed switchgear IP 41 Indoor control and relaying equipment IP 51 (f) Interior illumination lamps operated by door switches shall be provided for each switchgear control compartment. The Lamps should be easily available in the local market for future replacements. One 240V socket outlet of 3-points square terminals shall be provided for each switchgear panels in the control compartment. (g) Space heaters for 240V AC shall be provided inside the switchgear panel, circuit breaker and control compartments to prevent moisture condensation. A hygrostat control unit with variable temperature and humidity control setting shall be installed to control the heater. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 146 of 270 147 SECTION V: TECHNICAL SPECIFICATIONS 1.6.4 Measuring Instruments (a) All measuring instruments, including energy meters, shall be of flush-mounted, backconnected, dust-proof and heavy-duty switchboard type. Each measuring instruments shall have a removable cover, either transparent or with a transparent window. Each instrument shall be suitable for operation with the instrument transformers detailed in these specifications, under both normal; and short-circuit conditions. (b) For analog type instruments, scale plates shall be of a permanent white circular or rectangular finish with black pointer and markings. The scale range shall be determined from the current transformer and voltage transformer ratios and is given in the detailed specification for each instrument. (c) All measuring instruments of analog type shall be approximately 110mm2 enclosures and shall be provided with clearly readable long scale, approximately 240 degree. The maximum error shall be not more than one and a half (1.5) percent of full-scale range. 1.6.5 Indicating lamps (a) Indicating lamps assemblies shall be of the switchboard type, insulated for 110 V DC services, with appropriately coloured lens. The lens shall be made of a material, which will not be softened by the heat from the lamps. (b) For the circuit breaker, red indicating lamps shall be used for “ON” position, green lamps for “OFF” position indication and amber for circuit breaker auto trip. 1.6.6 Nameplate and Escutcheon Plates (a) Nameplate and Escutcheon Plates Each cubicle, panel, meter, switch and device shall be provided with a nameplate of escutcheon plate for identification with English description and also where appropriate the IEC number on the front of the panel directly below each device as appropriate. On the inside of the control compartment of the switchgear panel, a white label, engraved in Black Letter and Numbers shall be fixed on or below each device. The device name/number fixed in the drawings. Each equipment shall be provided with a rating plate containing the required information as specified in the relevant IEC standards. (b) The plates shall be made of stainless steel and shall not be deformed under the services conditions at the site. The entries on the plates shall be indelibly marked by engraving with black letter on a white background or vice versa as specified. 1.6.7 Wiring (a) General (i) All wiring inside the switchgear panel shall be done with PVC insulated wire not less than 2.5 sq.mm. flexible cable. A suitable wiring duct system firmly fixed on the panel and having covers shall be installed for all inter-panel and front-to-rear panel wiring as well as for wiring within the panels, which will provide easy access for inspection and replacement of the wires. (ii) Wiring between terminals of the various devices shall be point to point. Splices or tee connection will not be acceptable. Wire runs from the duct to the device shall be neatly trucked or clamped. (iii) Exposed wiring shall be kept to a minimum, but where used, shall be formed into compact groups suitably bound together and properly supported. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 147 of 270 148 SECTION V: TECHNICAL SPECIFICATIONS (iv) Instruments transformer secondary circuits shall be grounded only on the terminal block in the control compartment. Facilities for short circuiting the current transformers secondary windings while the switchgear panel is in service shall be provided. (v) Cable supports and clamp type terminal lugs shall be provided for all incoming and outgoing power wiring terminated at each panel. All wiring conductors (wires) shall be marked at each point of termination onto the terminal block or device. These wire markers shall be of an approved type and permanently attached to the conductor insulation. The method of ferruling shall be subject to approval by the employer; it is however preferred that the wire marker (ferrule) correspond to the device number or terminal block number and the number of the terminal where it is connected. All the devices and the terminal block must therefore have unique number. (b) Phase arrangement The standard phase arrangement when facing the front of the panel shall be R-S-T-N, and P-N from the left to right, from top to bottom, and front to back for A.C. threephase and single-phase circuits. For DC circuit it shall be N-P from top to bottom and front to back. All relays, instruments, other devices, buses and equipment involving three-phase circuit shall be arranged and connected in accordance with the standard phase arrangement wherever possible. (c) Wiring colour code All wires shall have ferrules at all terminations to distinguish each wire and terminal. In addition, the wire shall have the following colours: Circuit Colour Voltage transformers / Current transformers R, Y, B, BLK Auxiliary A.C. supply connection cables / bus-wires D.C. control wiring within the panel Grounding / earthing cable/wire Brown and Black Grey or Black Green with yellow stripe (d) Phase and polarity colour code The following coloured ferrules shall be provided on each wire in order to identify phase and polarity. Phase and Polarity A.C., three-phase, for First phase Red CT and VT secondary Second phase Yellow wiring Third phase Blue Neutral Black A.C., Single-phase First phase Red Neutral Black Ground Green with yellow stripe DC auxiliary Supply Positive Brown connection Negative Black Cables markers and wire numbers system must be submitted to the employer for approval before commencing the detailed design work for protection and control. 1.6.8 Terminal blocks (a) Terminal block for control wiring shall be rated not less then 600V AC (b) White or other light-coloured marking strips, fitted to each block, shall be provided for circuit designation. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 148 of 270 149 SECTION V: TECHNICAL SPECIFICATIONS 1.7 (c) The terminal arrangement, including the terminal blocks for VT and CT circuits connections, shall be subject to the employer’s approval. A total of not less than 20 spare terminals shall be provided for future use. (d) Shorting Links shall be provided on the current transformer (CT) circuits on the terminal block. It shall be possible to short the CT’s under live system conditions without open-circuiting the CTs. (e) Isolation links (sliding Links) shall be provided on the trip circuits, alarm and on the VT circuits to allow easy isolation of these circuits without disconnecting the wires from the terminal block. (f) Each individual terminal block shall be market with a distinctive number, which shall be the same number used in the drawings, for identification purposes. The TB number shall be engraved in black numbers in white background and shall be durable so as to last the life time of the switchgear board. (g) Each set of terminal block shall be identified by a label to distinguish it from another set of terminal block. The numbers used to mark the terminals on the terminal block shall be unique. The labels used will match those used in the drawings. EQUIPMENT AND SWITCHGEAR EARTHING 1.7.1 General All the compartment including the hinged doors of the switchgear panels and all the earthing points of the equipment installed/mounted in the switchgear panels shall be connected to the grounding conductor at the bottom of the panel for external connection to the substation earthing system. Earthing conductors shall be of annealed high conductivity copper stranded in accordance with Table 4 in BS.6346 and protected with extruded PVC sheath of 1000 volts grade. The earthing conductor on the primary equipment such as the Earth Switch and also for interpanel earth-bonding as well as for external connection to the substation Earthing- grid shall be adequate to carry the rated switchgears short-circuit current of 31.5 kA for 3 seconds. 1.8 MATERIALS AND WORKMANSHIP 1.8.1 General (a) Materials shall be new; the best quality of their respective kinds and such as are usual and suitable for work of like character. All materials shall comply with the least issue of the specified standard unless otherwise specified or permitted by the employer. (b) Workmanship shall be of the highest class throughout to ensure reliable and vibrations free operations. The design, dimensions and materials of all parts shall be such that the stresses to which they may be subjected shall not cause distortion, undue wear, or damage under the most severe conditions encountered in service. (c) All parts shall conform to the dimensions shown and shall be built in accordance with approved drawings. All joints, datum surfaces and meeting component shall be machined and all castings shall be spot faced for nuts. All machined finished shall be shown on the drawings. All screw, bolts, studs and nuts and threads for pipe shall conform to the latest standards of the International Organization for Standardization covering these components and shall all conform to the standards for metric sizes. (d) All materials and works that have cracks, flaws or other defects or inferior workmanship will be rejected by the employer. 1.8.2 Assembly Necessary items of equipment shall be assembled in the factory prior to shipment and routine tests shall be performed by the manufacture as per the requirements of the latest issue of IEC as specified under each equipment in these specifications to demonstrate to the satisfaction of the employers that the switchgear panels comply with the requirement of the relevant IEC standards. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 149 of 270 150 SECTION V: TECHNICAL SPECIFICATIONS 1.8.3 Casting Casting shall be true to pattern, of workmanlike finish and of uniform quality and condition, free from blowholes, porosity, hard spots, shrinkage defects, cracks or other injurious defects, shall be satisfactorily cleaned for their intended purpose. 1.8.4 Welding Wherever welding is specified or permitted, a welding process, including stress relieve treatment as required if necessary, conforming to an appropriate and widely recognized professional standard shall be used. All welders and welding operators shall be fully qualified by such a standard. 1.8.5 Colour standard The final colour of each item shall be as described under each item. 1.8.6 Operation Details Instructions shall be engraved on the switchgear panel, on the circuit breaker compartment describing in simple steps how to carry our correct and safe isolation, racking-in and racking-out switching operations on the circuit breaker. Similar details should be provided for the operation of the earth switch. 1.9 PROTECTION, CLEANING AND PAINTING 1.9.1 Embedded Steelwork All parts to ultimately be buried in concrete shall be cleaned and protected before leaving the manufacturer’s plant by cement wash or other approved method. Before being installed they shall be thoroughly desiccated and cleared of all rust and adherent matter, or be treated according to a method approved by the Employer. Such cleaning or treatment shall not detrimentally affect the strength or final operation and function of the equipment. 1.9.2 Steel exposed to atmosphere (a) All machined parts or bearing surfaces shall be cleaned and protected from corrosion before leaving the manufacturers plant by the application of an approved rust preventive coating, or a peelable plastic film. Where the latter is impracticable, such parts shall be heavily covered with high melting points grease. After erection such parts shall be cleaned with solvent and lapped or polished bright. (b) All parts, other than machined parts, which will be exposed after erection shall be thoroughly cleaned and galvanized or given with two coats of best quality approved primer and one coat of best quality approved finish paint before leaving the manufacturer’s plant and a further one coat of paint of an approved quality and colour after erection and touching up on the site, expect such apparatus as panels and instruments which shall be finished painted under approved procedures. (c) All outside panel surfaces shall be primed, filed where necessary, and given not less than two coats of synthetic undercoat. The finishing coat for the outdoor and indoor installation shall be a gloss paint. (d) Primer shall be applied to surfaces prepared in accordance with the plant manufacturer’s instructions. The surface shall be wiped clean immediately prior to applying the paint. The primer and finish coats of paint shall be applied using the methods and equipment recommended by the manufacturer. (e) The Internal surface of all pipelines shall be cleaned out by the approved methods before installation and again prior to commissioning, to ensure freedom from dirt, rust , scale, welding slag, etc. all exposed pipes shall be painted with identifying colour after erection is completed. The colour code system shall be approved by the employer. (f) All steel surfaces, which are in permanent contact with oil, shall be given three coats of approved oil resistant. (g) No painting or protection is required for finished or unfinished stainless steel parts. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 150 of 270 151 SECTION V: TECHNICAL SPECIFICATIONS (h) The final colour of all equipment, frames for meters and relays, and switch handle shall be as described under each particular item. (i) The humid and tropical conditions shall be taken into account on selection of the paints and painting procedure. 1.10 DRAWING (a) Before starting manufacture of the switchgear panels, dimensioned drawings and data showing all significant details of the equipment and materials to be used shall be submitted to the employer for approval. Four 4 weeks shall be allowed for Review of the drawings by the employer. The employer shall indicate on the drawings whether the drawings are Approved with comments or Not Approved. Where the drawings are Not Approved, the manufacturer shall modify the drawings as per the Employers comments and in line with the specifications and re-submit to the Employer for review. Manufacturing of the switchgears panels shall not commence under any circumstances without receipt of Approved drawings by the manufacturer from the employer. Any delays in approval of the drawings caused by submission of incorrect drawings by the manufacturer shall be the responsibility of the manufacturer, who shall fully offset any associated cost. (b) The manufacture of the switchgear shall then proceed strictly in accordance with the approved drawings and also in accordance with the detailed specifications as contained herein. Where conflict may arise between the specifications and the approved drawings, the specifications will take precedence, unless it’s specifically indicated in writings on the approved drawings that the conflicting clauses in the specifications is superseded, or where followings discussions between the manufacturer and the employer, the employer gives approval in writing to supersede the conflicting clauses in the specification. (c) It is to be understood, however, that approval of the drawings will not relieve the manufacturer of any responsibility in connection with the works that the switchgear will fully comply with the relevant IEC/ANSI standard and with these specifications. (d) All drawings submitted for approval or sent to the Employer for any other reason shall be in hard copy form and shall be sent by courier. Drawings for Approval shall not by any means be forward via-e-mail or any other media except in hard copy form. (e) On successful completion of the initial FATs and following completion of the manufacture of the complete switchgear panels, the manufacturer shall carry out all the tests listed under section 2.5 for the completed switch board and for current transformers, voltage transformers, circuit breakers and for protection relays. The above test shall be carried out on each and every switchgear panel. Any problem noted will be rectified and the Employer will only be invited to the factory when all the test are successful. This will ensure that the employer does not spend time in the factory waiting for the manufacture to fix problems that arise during the FATs. While such anomaly would have been detected and rectified by the manufacturer before hand after conducting the above routine tests. (f) Upon testing of the panels as in (f) above the drawings will be edited to capture any minor wiring errors detected in order to produce the final As Built Drawings. A copy of the final As Built Drawings and Routine test results for each panel, signed by the Manufacturer shall be sent by courier to the employer before attendance of FATs. (g) Each individual switchgear panel shall have its own separate drawings, with the name of the panel included on the drawings for identification (h) Before Approval of shipment of the switchgear panel, Five (5) copies of bound As Built drawings (A4 size) in Hand Copy shall be forward to the employer in Durable Hard Cover Box File. The files shall have a tag with the following inscription. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 151 of 270 152 SECTION V: TECHNICAL SPECIFICATIONS “Kenya Ports Authority 11kV Switchgear Board AS Built Drawings” Also three (3) software copies (in CD ROM) of the As Built drawings in AutoCAD Electrical 2010 SLM or later version shall be sent to the employer via courier. The CD ROM will have the same label as above. The drawings provided on soft copy shall be freely editable to allow the employer to incorporate any changes made in future. All protection and control drawings shall be done on A4 – size paper. The function of each drawing shall be clearly indicated. Related drawings shall be arranged sequentially, and have the same drawing numbers/name but different sheet numbers. The drawing shall include the following: Substation drawings AC single line drawing AC Schematics DC Schematics Functional Drawings Panel wiring, including inter-panel bus-wiring list Panel device layout drawing General layout drawings for the switchgear panels Relays and device list (bill of quantities) for each type of panel 1.11 MANUFACTURE OF SAMPLE PANELS The manufacturer shall initially manufacture 3 panels as follows - One incomer panel One Bus-coupler panel One feeder panel Upon manufacture of the three (3) panels, the manufacturer shall invite the Employer to inspect and conduct factory acceptance tests (FATs) on the panels. The manufacturer shall rectify any minor defects noted during FATs. Upon successful FATs, the Employer shall authorize the manufacturer to proceed with manufacture of all the other switchgear board. Where the manufactured sample panels are unsatisfactory and the manufacturer fails to rectify the switchgear panels to satisfactory status within four weeks after attendance of FATs, the Employer shall have the option to cancel the tender. 1.12 OPERATING AND MAINTENANCE INSTRUCTIONS (a) The manufacturer shall supply detailed instruction manuals concerning the correct manner of assembling / installing, configuring, setting, testing and commissioning, operating and maintaining the equipment and devices constituting the switchgear board, including the board itself. The maintenance details of each component shall also be described, including the frequency of inspections and lubrication. The instruction manual shall include a separate and compete section describing the normal and emergency operating procedures for the switchgear, and shall include explanatory diagrammatic drawings to facilitate understanding of the instructions. (b) The manufacturer shall, in preparing the instruction manuals, take into account the lack of experience and familiarity of the operators with this type of equipment. (c) The manual shall give specific information as to oil, grease, or any other materials needed for maintenance operations. This information shall include brand names and KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 152 of 270 153 SECTION V: TECHNICAL SPECIFICATIONS manufacturer’s number or designations for at least two brands available in Kenya, preferably manufactures in Kenya. (d) One complete set of the operating and maintenance manuals for all the plant, equipment and accessories to be installed/ mounted in the switchgear panels shall be sent to the employer together with the drawings for approval. The operating and maintenance manuals shall be original copies printed and bound by the manufacturer. Any illegible copies of the operating and maintenance manuals submitted shall be rejected by the employer. (e) Before approval of shipment of the switchgear panels, Five (5) Copies of the operating and maintenance instructions/manuals shall be sent to the employers by courier. The operating and maintenance manuals shall be original copies printed by the manufacturer. Any illegible copies of the operating and maintenance manuals submitted shall be rejected by the employer. In addition, three (3) soft copies of the manuals in CD Rom shall be delivered to the employer. 1.13 TESTING AT PLACE OF MANUFACTURE (a) The manufacturer shall be responsible for performing or for having performed all the required tests listed under the specification for the switchgear and all the current transformers, voltage transformers, protection relays, energy meter, measuring and indicating instruments. (b) The tenders shall confirm the manufacturer’s capabilities in this regards when submitting tenders. Any limitations shall be clearly specified. (c) Tender documents shall be accompanied by copies of Type test and Routine test report and Certificates for similar rated equipment for the purpose of tender evaluation. Type test reports and certificates shall be certified by the National Standards and Testing Authority (NSTA) of the country of origin or by a third party Reputable Testing Authority. Where a body other than NSTA is used to certify the type-test reports, a copy of the certificate of accreditation shall be attached. Current contract information of the testing and certification authority shall be provided. (d) Upon completion of the manufacturing process, routine tests shall be carried out as per the respective IEC standards of each equipment as follows:i. Circuit Breaker IEC 62271-100 & IEC 60298. ii. Switchgear panels, IEC 60294 iii. Current Transformers, IEC 60044-1 iv. Voltage Transformer, IEC 60044-2 v. Protection Relays and Measuring and Indicating Instruments, IEC 60255 (e) The manufacturer shall arrange for two (2) engineers from the employer attend Factory Acceptance Tests (FATs) on the switchgear panels, where routing tests as per the IEC standard listed above another special tests listed in this specifications shall be carried out in their presence. The duration of the FATs shall be adequate to test all the offered switchgear boards, Testing shall strictly be carried out during working hours from 8.00 am to 5.00 pm. In case the equipment fails the test and has to be rectified or the manufacturer is not able to complete the tests within the set duration, then the manufacturer shall meet the cost of accommodation and meals for the Employers Engineers for the additional days required for completion of the tests. The employer’s engineers will only sign the Test Reports/Certificates only when the test are conducted in their presence in accordance with the relevant IEC standard or the procedure agreed beforehand between the employer and the manufacturer. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 153 of 270 154 SECTION V: TECHNICAL SPECIFICATIONS 1.14 (f) Only upon receipts of authentic certified copies of the FATs Routine Test Reports/certificates and special tests and satisfactory report from the engineers, shall the employer give clearance for shipment of the switchgear boards one all other listed requirements on drawings, operation and maintenance manuals and software have been meet. SOFTWARE REQUIREMENT (a) Seven (7) copies of each different type of software in a CD Rom, for the protection relays, energy meters, transducers and other measuring devices whose configuration and settings is software based shall be supplied with the board. Eight (8) connection cables for each type of device shall also be supplied with the switchgear board. Before approval for shipment of the switchgear board is granted by the employer, all the software indicated in the completed technical schedules shall be supplied. The software shall be for configuration, parameter setting and for data download and analysis. It shall be possible to load the software into at least ten (10) different laptop computers without requirement for additional licenses. Where additional licenses are required, the cost shall be considered to have been included in the bid. Four (4) sets of hard covers manuals for each type of software supplied providing detailed instructions for programming setting and configuration of the relays and other devices and downloading of data, shall be supplied with the switchgear. 1.15 SPARE PARTS 1.15a SPARES PARTS The manufacturer (bidder) shall furnish spare parts as listed below and indicate in the price schedules:i Two (2) Feeder circuit breakers, rated at 630A, 31.5 kA, 3 second mounted on withdraw/isolation trolley ii One (1) Incomer circuit breaker, rated at 1500A,31.5 kA, 3 second mounted on withdraw/isolation trolley. iii Two (2) circuit breaker spring charging motors iv Three (3) circuit breakers closing coils v Three (3) circuit breaker tripping coils vi Two (2) circuit breakers interlocking coils vii Two (2) earth switch interlocking coils viii Ten (10) indication lamps of each type ix Two (2) auxiliary relays of each type x Two (2) protection relays of each type xi Four (4) MCBs of each type xii Two (2) power measurement units xiii Two (2) energy meter xiv VT Fuses: Three (3) for primary side and three (3) for secondary side for each switchgear board. (a) The spare parts supplied shall be packed or treated in such a manner as to be suitable for storage under the climate condition at the site for a period of not KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 154 of 270 155 SECTION V: TECHNICAL SPECIFICATIONS less than two years, and each part shall be clearly marked with the description and purpose on the outside of the package. The manner of storage shall be recommended by the manufacturer. (b) Spare parts so provided shall be delivered with the switchgear to the employers stores. Delivery of spare parts will not be deemed to be complete until the package have been opened and their content checked and verified by a representative of the employer. 1.15b ACCESSORIES FOR THE SWITCHGEAR BOARDS The following accessories shall be supplied with each separate i. ii. iii. iv. 1.16 Two Two Two Two (2) (2) (2) (2) switchgear board:- circuit breaker rack in/rack out handle/tool circuit breaker manual spring charging handle/tool earth switch operating handle/tool circuit breaker withdrawal trolley PACKING (a) The switchgear panels and spares shall be packed properly and protected for shipment from the place of manufacture to the employer’s stores. (b) Each crate of package shall contain a packing list in a waterproof envelope and a copy in triplicate shall be forward to the employer prior to dispatch. All items of materials shall be clearly marked for easy of identification against the parking list. (c) All cases, packages, etc, shall be clearly marked on the outside to indicate the total weight, to show where the weight is bearing and the correct position of the slings and shall bear an identification mark relating them to the appropriate shipping documents. (d) Bolts, nuts, washers and fillers shall be bagged in sealed vinyl and packed in steel cans. The cans shall bear the contents and be created together. (e) The Employer shall reserve the right to inspect and approve the equipment and the packing before the items are dispatched. However the manufacturers shall be entirely responsible for ensuring that the packing is suitable for transit and such inspection will not relieve the manufacturer from responsibility for any loss or damage due to faulty packing. (a) Consignee: KENYA PORTS AUTHORITY (b) Name of Project: Distribution 11 kV switchgear boards (c) Contract No: ………………………………………… (d) Port of destination …………………………………. (e) Item Number, if applicable, Package number in sequences, And quality per package …………………………… (f) Description of contents: …………………………….. Net and gross weigh, cubic measure……………………. The shipping mark is finally subject to the Employer’s approval. 1.17 DELIVERY (a) The manufacturer shall deliver the switchgear and spares to the designated employers store. (b) The notification for shipment/delivery shall include a complete shipping list if the contents of each package to be delivered and shall indicate the anticipated date of delivery and the serial number of each component to be used for identification and evidence of the insurance cost arranged for it. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 155 of 270 156 SECTION V: TECHNICAL SPECIFICATIONS 2. DETAILED TECHNICAL SPECIFICATIONS FOR 11kV METAL CLAD SWITCHGEAR PANELS. 2.1 INDOOR SCOPE This specification is for 11kV Indoor, three pole, metal clad switchgear with vertical or horizontal isolation, horizontal draw out with circuit breaker employing vacuum interrupter. 2.2 REFERENCES The following documents were referred to during the preparation of this specification, and may be referred to; however in case of conflict, the provision of this specification shall take precedence. Unless otherwise specified, the latest revision, edition and amendments of the standard shall apply. IEC 60298 AC metal – enclosed switchgear and control gear for rated voltages above 11 kV and upto 72.5 kV IEC 60051 Direct acting indicating analogue electrical measuring instruments and their accessories. IEC 62271- 100 High-Voltage alternating circuit breakers IEC 60044-1: Current transformers IEC 60044-2: Voltage transformers IEC 60255: Electrical Relays ANSI 37: Medium Voltage AC metal – enclosed switchgear and control gear 2.3 CONSTRUCTION OF EACH PANEL a) The whole switchgear equipment and components shall be designed and constructed in accordance with IEC 60298. The board shall be complete with all the relevant components including, busbars, circuit breaker, cable compartment, instrument transformers, protection relays, instruments and controls. b) The switchgear board shall be constructed to 1P41 degree of protection in accordance with IEC 60529. A type test report for the degree of protection of the switchgear panels from a third party reputable testing laboratory or certified by the national standards and testing authority (NSTA) or a laboratory accredited to the NSTA shall be submitted with the tender for evaluation purposes. c) The panels shall have restricted dimensions suitable for installation in limited spaces. In particular and without compromising the insulation level, bus - bar current rating and short circuit current performances, the width of the panels shall not exceed 800mm. The LV compartment shall not be less than 650 mm in height, to ensure adequate space for mounting the relays and other devices and accessories and adequate space for the cable trucks, terminal blocks and wiring. The depth of the switchgear, i.e., from the front to the back shall be kept o the minimum and in any case not exceeding 1800mm. d) The switchgear panel or cubicle shall be built up of separate metal cladcompartmented cubicles with earthed metal partitions. The compartments shall be for busbar, cable connection, circuit breaker, current transformer and control (LV) compartments. A drawing showing the layout and dimensions of each of the compartments of the switchgear panel and the devices/components installed in the compartment shall be submitted with the bid for tender evaluation. Also a drawing showing the arrangement and dimensions of a complete switchgear board, comprising two incomers, one bus-coupler and five feeder panels assembled together shall be included with the bid for tender evaluation. The drawing shall also include the arc venting chamber to be supplied with the switchgear board. Different drawings shall be provided for the switchgear board rated and 31.5 kA. e) The circuit breakers shall be mounted on an inbuilt carriage to facilitate isolation withdrawal of the circuit breaker. Where the carriage is fixed in the compartment KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 156 of 270 157 SECTION V: TECHNICAL SPECIFICATIONS and do allow complete withdraw of the circuit breaker outside it's compartment, then a purposely trolley shall be provided equipped with a lowering/raising gear to lower the circuit breaker to the floor, and to raise the circuit breaker to it’s compartment by one person. This requirement shall be demonstrated during FATS. f) The complete switchgear shall be such that the complete switchgear is of flush-front design. g) Each of the switchgear panels shall have four separate compartments as follows:i. LV Compartment ii. Circuit Breaker Compartment iii. Busbars Compartment iv. Cable, CTs, VTs and Earth Switch compartment The circuit breaker, busbars and cables compartments shall be provided with arc venting outlets to the top of the switchgear board. The top of the complete switchgear board shall be equipped with arc by-products venting chambers to direct the arc by products outside the switchgear room. The design of the arc chamber shall be adequate to handle arc by products at the rated withstand level of the switchgear board of 31.5 kA, 3 seconds. The design of the arc chamber shall be complete in every way with provision of connection to the switchgear wall at least at two points and the terminal expansion flaps to be fitted on the switch gear wall. During the FATs the complete venting chamber for one of each type of switchgear boards, i.e.31.5 kA shall be fully assembled for demonstration to the Employer’s Engineers. h) The low voltage section shall be completely separate from the high voltage section. All the protection relays, auxiliary relays, energy meters indication lamps, instruments, control and selection switches and any other associated accessories will be mounted arc by-products venting requirements to be provided (built into) in the switchgear room. i) The switchgear shall be designed for erection with the rear side close to wall as well as for free standing erection. The manufacturer shall provide single line layout drawings giving the required minimum dimensions of the switchgear room, including arc by-products venting requirements to be provided (built into) in the switchgear room. j) The switchgear shall be of arc resistant design as per IEEE/ANSI C37.20 and hence ensure complete safety for switching personnel standing in-front or at the rear of the switchgear board. A copy of the type test report shall be submitted with the bid for tender evaluation purposes. k) Where the venting is intended to penetrate an external wall, the vent shall be covered such that it meets all environmental conditions (e.g. rain-proof, dust-proof, verminproof). l) The cable compartment should have an anti vermin guard plate giving protection against rats, rodents etc. m) The circuit breaker compartment door shall be provided with provisions for padlocking. n) The doors shall be capable of withstanding the effects of maximum internal arcing fault without being blown off and causing danger to personnel and other equipment. This should be proven by successful testing, as per ANSI C37.20.7 or equivalent IEC standards. Type test report shall accompany the bid. o) The busbar shall be single, three phase, air insulated. The primary busbars and connections shall be of high conductivity and electrolytic material, high grade copper, and shall be in unit lengths. The busbars shall preferably have a PVC cover to prevent accidental short-circuits p) Busbars, connections and their support shall be rated 2000A as required continuously KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 157 of 270 158 SECTION V: TECHNICAL SPECIFICATIONS under ambient conditions and capable of carrying the short-time current associated with the short circuit ratings of the circuit breakers, for 3 Seconds. q) Busbars shall be extensible at both ends, such extension shall entail the minimum possible disturbance to the existing busbar. r) Provision shall be made for locking busbar and circuit shatters separately in the circuit breaker compartment. These shutters shall open and close automatically during the racking in and racking out of the circuit breaker. s) Provision shall be made for integral circuit earthing and for busbar earthing. Means of earthing shall be by circuit breaker or purposely built earth switch. Mechanical interlocks to ensure correct switching operation shall then be provided. It shall not be possible to close the earth switch on the incomer panel, when the incoming 11kV cable is live. t) The earth switch shall be easy to operate by one operator and be spring loaded to ensure effective make operation independent of the operator action. The earth switch shall be rated to make and carry for 3 seconds, the rated short-circuit current of the respective switchgear panel of 31.5 kA. The Status of the earth Switch shall be visible from the front of the Panel. It shall not be possible to rack-in the circuit breaker into the service position with the earth switch in closed position. The mechanical interlock between the circuit breaker and the earth switch shall be strong enough to guarantee safety of the switching personnel and the switchgear. The earth switch shall be equipped with auxiliary contacts for local and supervisory indication of the status of the earth switch. The earth switch operating lever shall be covered by a shutter and shall only be accessible when it is permitted to operate the earth switch. u) The operation of the Earth Switch shall be set in such a way that during both the close and open operations, a clearance of at least 22.5mm shall be maintained between the operating handle and the bottom of the switchgear panel. v) It shall not be possible to insert the earth switch operating handle into position except when the circuit breaker is in the test or isolated position. The earth switch shall be equipped with pad-locking facilities when in the closed position w) All earthing facilities shall be rated for fault making at the rated switchgear short-circuit current. x) Earthing switches shall be provided for earthing each of the Busbar Sections separately. All the interlocks required toensure safe operation of the busbar earth switch shall be built into the switchgear board. In particular it shall not be possible to close the earth switch when any of the circuit breakers on that part of the busbar is in service position, i.e., all the circuit breakers shall be withdrawn for the Busbar earth to be closed. Once the Busbar earth has been closed, it shall not be possible to rack-in any circuit breaker. Indications for busbars earth On and OFF shall be provided and visible from the front of the board. The Panel wiring for protection, instruments, indication and metering circuits and other control accessories shall be completely done. All circuits for connection to external cables such DC & AC auxiliary supplies, external tripping, supervisory control and indications shall be wired upto the terminal Block at the Back of the panel where external cables shall be connected. At least 12 spare terminals shall be provided on the terminal board for any future requirements y) It is emphasized that Each Switchgear panel will have a terminal block at the back of the panel where all external cables such as for 110V DC supply, 240V AC supply, connection of SCADA, measurands/commands and alarms shall be made. z) 110V DC, 110V AC and 240V AC supplies for circuit breaker control, alarm circuits, protection relays, metering and motor supply for each panel, shall be controlled by suitably rated miniature circuit breakers. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 158 of 270 159 SECTION V: TECHNICAL SPECIFICATIONS aa) The switchgear panels shall be tropical vermin proof. The plates shall be of high quality mild steel of at least 2mm thickness thoroughly cleaned by shot blasting or other approved methods They shall then be given a primary coat and two coats of contrasting colour of durable and weather resisting paint. The final coat shall be gloss and of RAL 7032. The final thickness of the paint shall not be less that 80 Microns at any point within the switchgear panel. The paint thickness shall be measured during the Factory Acceptance Tests. bb) Anti-condensation heaters shall be provided inside each switchgear panel. They shall be located so as not to cause injury to personnel or damage to equipment. The heaters shall be controlled by a hygrostat with a variable humidity and temperature setting. The heaters shall be dimensioned to ensure that condensation cannot occur within the switchgear panel. Heaters of adequate rating shall be provided for the circuit breaker, cable and LV compartments. The 240V AC supply, for the heaters shall be controlled by a suitably rated single pole miniature circuit Breaker. cc) The circuit breaker cubicle shall have a limit switch which shall be wired to provide SCADA indications on whether the breaker is fully racked in or fully racked out(withdrawn). dd) All the switchgear panels shall be rodent and vermin proof. ee) Suitable means shall be provided to monitor the status of the HV cable, i.e., whether it is live or dead. The monitoring device shall be a three phase device with illumination in red colour for live status visible from the front of the panel without opening any compartment doors. The indications shall be labeled R, Y & B or Ll, L2 & L3. The device shall meet the requirements of IEC 61243-5. ff) Each switchgear panel shall be provided with Tinned Copper earth bar of adequate cross section area to be able to withstand the rated short-circuit current of 25 kA or 31.5 kA for 3 seconds, and arranged so that the bars of adjacent panels are joined together to form a common earth busbar. Provision shall be made at either end the assembled switchgear board for connection of the earthing bar to the substation earthing grid. gg) Manual close & open push buttons shall be provided on the circuit breaker compartment door for manual close and open of the circuit breaker both in the service and in the test(withdrawn) position. The manual close and open push buttons shall be clearly labeled with CLOSE and OPEN Labels and with I(red) and O(Green) Symbols and colour codes as per the IEC standard. hh) The complete switchgear board shall be equipped with ARC protection, consisting of ARC protection relays and arc sensing devices located in the Cable, Circuit Breaker and Busbar Compartment of each panel. Optical sensors shall be used. The sensors shall operate upon occurrence of a flash (light) from the ARC. The sensors shall be connected to the ARC protection Relays via fiber cables or any other suitable means that is already in use. The ARC protection relay shall monitor both the operation of the Optical sensors and over current relay and shall only operate upon operation of both the sensing device and the pick up of the over current element. It shall also be possible to select the operation of the scheme due to operation of the optical sensor alone but with longer time delay. Upon operation of the ARC Protection, all circuits within the fault Zone shall be tripped by the ARC protection relay. The ARC protection scheme shall have means for indicating the panel and the compartment where the ARC occurred. The scheme shall be secure and immune to mal-operation. The fundamental operating time of the ARC protection scheme shall preferably be 50 ms and in any case not more than 100 ms. However adjustable time delay and over current pick-up shall be provided. The design of the complete scheme shall be to the approval of the employer. A single line drawing shall be enclosed with the bid to show how the scheme is implemented. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 159 of 270 160 SECTION V: TECHNICAL SPECIFICATIONS 2.3.1 CIRCUIT BREAKERS a) The circuit breaker shall be three pole operated, indoor type, employing Vacuum Interrupter with air or solid Insulation and shall comply with the requirement of IEC62271-100 in respect of design, type tests, service operation and the making and breaking of faulty currents. b) The moving portion of each circuit breaker shall consist of a three-pole circuit breaker, operating mechanism, primary and secondary disconnecting devices, auxiliary switches, position indicators and necessary control wiring. The Auxiliary switches shall be of the plug-in type, with the male contacts mounted on the breaker carriage and the female contacts on the plug-in cable connected to the panel wiring. Other options may be considered where there is adequate proof that the auxiliary contacts will always be making firmly without mis-alignment. Finger contacts will however not be acceptable. c) The circuit breakers of the same current and voltage ratings shall be fully interchangeable, both electrically and mechanically. d) Name plate for the circuit breaker shall be provided with all the required details as per IEC standards, including:i) ii) iii) iv) v) vi) vii) viii) ix) x) xi) xii) xiii) xiv) Circuit Breaker type Applicable IEC standard Total Weight Rated Voltage Lightning impulse withstand voltage 1 minute Power frequency withstand voltage Rated frequency Rated Current Breaking Capacity Short time current Making capacity Operating sequence Rated voltage of closing and opening coil Rated voltage of spring charging motor e) The circuit breaker operating mechanism shall be motor wound spring operated, power closing with electrical release and with provision for hand spring charge. f) Mechanical indication shall be provided to indicate the state of the spring. This shall be visible without opening the circuit breaker compartment door. Also two pairs of Auxiliary contacts, which are open, when the springs are charged shall be provided for local and supervisory indication. g) A spare set of 4 normally open and 4 normally closed auxiliary contacts of the circuit breaker shall be provided and shall be wired to a terminal block (box), for connection to SCADA equipment, etc. h) The control circuits for the inserting the breakers into auxiliary contacts shall be breaker without connecting i) The operating mechanism shall be completely trip free both electrically. j) The circuit breaker shall have a mechanical operations counter k) One mechanical ON/OFF indicator, with inscription "ON" white letters on red background and inscription "OFF" white letters on green background shall be provided for the circuit breaker. Alternatively approved IEC indications for circuit breaker ON and OFF shall be used. l) The breaker controls shall have anti-pumping facilities circuit breaker shall automatically be connected when the cubicle. Alternatively a single plug-in cable for all provided. It will not be possible to rack-in the circuit the plug in cable first. mechanically KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV and Page 160 of 270 161 SECTION V: TECHNICAL SPECIFICATIONS m) Where the Circuit Breaker is used for circuit or busbar integral earthing, the control wiring of the breaker housing should be such that when the breaker is in circuit earth or busbar earth positions it shall only be operated mechanically and not electrically. n) Circuit breaker poles between the interrupters and the primary plug-in contacts shall be fully insulated with durable material. o) The circuit breaker maintenance and operations manual shall contain clear instructions on the maintenance requirements of the circuit breaker (if any), to prevent switchgear failure in service, due to excessive fault current clearance or any other cause . 2.3.2 CURRENT TRANSFORMERS a) Current transformers shall be Cast Resin Type and shall be accommodated inside the cubicle, in a separate compartment or in the same compartment as the cable. b) The current transformers shall be in accordance with the requirements of IEC 60044-1 and IEC 60044-6 and shall have the specified accuracy under load and short-circuit conditions and shall be able to withstand the effect of short-circuit fault current rating of the switchgear, of 31.5 kA for 3 seconds. c) Current transformers shall have a rated burden as specified, sufficient for the connected Numerical Protection relays and Energy meters and instruments. The CT rated burden shall however not be less than 15 VA. d) The Manufacturer of the CTs shall be identified at the time of tender. Copies of Type Test certificates and routine Test Reports/Certificates as per IEC 60044-1 of CTs of similar rating and class verifying the class and accuracy as well as the limits of error for the declared class similar to those of the specified CTs shall be submitted with the bid for tender evaluation purposes. The specified CTs must be within the product range of the manufacturer. A catalogue of the CT manufacturer shall be supplied with the bid. e) The current transformer shall have markings on the secondary and primary terminals as per requirements of the IEC 60044-1 standard. The markings shall be indelibly made. The secondary terminals shall have screw terminals. f) Name plate for the current transformer shall be provided with all the required details as per IEC 60044-1 Standards, including:i) ii) iii) iv) v) vi) vii) viii) ix) x) The manufacturer's name Serial number and a type designation Rated primary and secondary current Rated frequency Rated output and corresponding accuracy class for each secondary winding, including the rated accuracy limit factor and Instrument security factor for protection and metering secondary windings respectively. The highest voltage of the equipment The rated Insulation level The rated short-time thermal current (I th) and the rated dynamic current Class of Insulation Rated continuous thermal current 2.3.3 VOLTAGE TRANSFORMERS a) The VT shall be of Cast resin, indoor, type mounted within the 11kV incomer panel. The VT shall be a three phase unit or Three (3) Single phase units. b) Voltage transformers shall be suitable for operation of the protection relays, metering and transformer voltage regulating relay and shall be in accordance with the requirement of IEC60044-2. c) Each voltage transformer shall be three phase, five limb, star/star connected and KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 161 of 270 162 SECTION V: TECHNICAL SPECIFICATIONS complete with HV and LV fuses and links, alternatively three single phase units shall be installed and connected. d) It shall have an open delta winding to be used for directional earth fault Relay. e) The Manufacturer of the VTs shall be identified at the time of tender. Copies of Type Test certificates and routine Test Reports/Certificates as per IEC 60044-2, of VTs of similar rating and class as the specified VTs shall be submitted with the tender for evaluation purposes. The Specified VTs must be within the product range of the manufacturer. f) Name plate for the voltage transformer shall be provided with all the required details as per IEC 60044-2 Standards, including:i) The manufacturer's name ii) Serial number and a type designation iii) Rated primary and secondary voltage iv) Rated frequency v) Rated output and corresponding accuracy class for each secondary winding, vi) The highest voltage of the equipment vii) The rated Insulation level ix) Class of Insulation for the equipment x) Rated voltage factor and corresponding rated time. xi) The use each secondary winding and it's corresponding terminals 2.3.4 PROTECTION RELAYS a) The LV compartment terminal block shall include a test switch (block), which enables the CTs circuits to be isolated from the relay and shorted without opening circuiting the CT, to facilitate relay testing in situ and to allow for isolation of VT circuits, alarm and trip circuits without disconnecting wires at the terminal block. b) The measurement relays shall be flush mounted and of Numeric Design, with event recording. Fault recording, power measurements, and shall be in accordance to IEC 60255. c) Besides the communication port, the relays shall have a human — machine interface facility (MMI) with and LCD Screen where one can easily access relay information. d) Relays contacts shall be suitable for making and breaking the maximum currents, which they are required to control in normal service. Where contacts of the protective relays are not sufficient for circuit breaker tripping, auxiliary trip relays shall be provided, in order to prevent damage to output contacts of measuring relay. e) Operating time for auxiliary tripping relays shall not significantly affect the overall fault clearance time, i.e., the auxiliary trip relays must have short pick up time of less than 30 ms. f) Relay contacts shall make firmly without bounce and the relay mechanism shall not be affected by Panel vibration or external magnetic fields. g) Relays shall be provided with clearly inscribed labels describing their functions and IEC Device Function numbers. The labels shall be to the approval of the Employer. h) Relays shall be suitable for operation on the station D.C. supply without use of dropping resistors or diodes. i) To reduce the effect of electrolysis, relay coils operating on DC shall be so connected such that they are not continuously connected from the positive pole of the station battery. j) The relay Thermal rating shall be such that the fault clearance times on any combination of current and time multiplier settings shall not exceed the thermal withstand capability of the relay. (Max. fault current = 31.5 kA). k) The relays shall be EMC 89/336/EEC compliant. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 162 of 270 163 SECTION V: TECHNICAL SPECIFICATIONS 2.3.5 INDICATIONS AND INSTRUMENTS All instruments shall be flush mounted and shall be in accordance with the requirement of IEC 51. Each cubicle shall have the following indications. One indicator lamp to show the breaker in closed position - RED colour One indicator lamp to show the breaker in open position - GREEN colour One indicator lamp to show breaker Auto-trip - Amber colour The instruments shall be supplied as described under each panel in the subsequent sections. 2.3.6 POWER CABLE TERMINATION Cable compartment design shall be suitable for heat shrinkable (or equivalent) jointing application termination. The following provisions shall be made:i) Single core, twelve gland fabricated sheet steel cable box, complete with gland and armour clamp, suitable for receiving four(4) single core 1 kV cable of size upto 600mm2 per phase, for Incomer type panels. ii) Three core single gland fabricated sheet steel cable boxes complete with gland and armour clamp suitable for receiving one (1) single core 11kV cable upto 400mm 2 11kV XLPE cable per phase, for feeder type panels. iii) The cable connection terminals shall be located at least 250mm from the CT Primary terminal. 2.3.7 SCOPE OF SUPPLY FOR DISTRIBUTION SUBSTATIONS 11kV SWITCHGEAR BOARD. The scope of supply for the Distribution Substation Switchgear boards is listed else where in this tender document. LABELLING OF THE SWITCHGEAR PANELS. NB1. For each Switchgear Board the panels shall be assigned a distinct numerical numbers for identification starting with number one (1) on the left hand side. The number will be embedded on a stainless steel plate of width not less then 5 cm. The size of the number shall be at least 3 cm high. The stainless steel plate shall be fixed to the panel using stainless steel bolts. NB2: For each switchgear board the panels shall be assigned a distinct AlphaNumeric name corresponding to the transformer or feeder to which it shall be connected. The Alpha-Numeric name shall be embedded on a stainless steel plate, of width not less than 5 cm. The size of the letters/number shall be at least 2 cm high. The letters/numbers shall be of black colour on white background. The stainless steel plate shall be fixed to the panel using stainless steel bolts. The arrangement and names of the switchgear panels for various switchgear boards shall be given after tender award. 2.4 RATINGS OF SWITCHGEAR EQUIPMENTS a) 11kV Incomer, Bus-coupler and Feeder Circuit BreakerInterrupting Medium Vacuum Number of poles 3 Highest equipment Voltage 17.5kV One minute power frequency withstand voltage 38 kV Impulse withstand voltage (BIL) 95 kV Frequency 50Hz Rated short time current 31.5 kA KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 163 of 270 164 SECTION V: TECHNICAL SPECIFICATIONS Rated short time marking current (peak) 79 kA Rated short circuit current withstand First pole to clear factor Operating sequence Auxiliary D.C. voltage for closing and tripping coil Auxiliary a.c voltage Tripping/closing coil auxiliary voltage Spring charging motor supply Rated normal Current – Incomers Rated normal Current – Bus-coupler Rated normal Current – Feeder 31.5 kA, 3seconds 1.5 0-0.3 sec-co-15 sec-co 110V 240V AC, 50Hz 110 V DC 240 V AC 1500 A 1500 A 630 A b) Current Transformer for Incomer, Bus-coupler and Feeder Panels Ratings: Rated Short time current (STC) withstand : 31.5 kA for 3 seconds Rated Voltage of the CT :17.5kV One minute power frequency withstand voltage :38 kV Impulse withstand voltage : 95 kV Rated maximum continuous current: Incomer : 1500 A Bus-coupler : 1500 A Feeder :630A Ratio and Class: i) 11 kV feeder panel ii) Core 1 : C.T. Ratio Class Core 2 : C.T Ratio Class Burden 11 kV Bus-coupler: Core 1 : C.T. Ratio Class Core 2 : C.T Ratio Class Burden iii) : : : : 600/300/1 A 5P15 600/300/1 A 0.5 : 15 VA : : : : 1500/1 A 5P15 1500/1 A 0.5 : 15 VA 11 kV Incomer panel: Core 1 : C.T. Ratio Class Imag Vk : : : : 1500/1 A (Turns Ratio) X 0.02 A 250 V Core 2: C.T. Ratio Class Imag Vk Core 3: C.T Ratio Class VA : : : : : : : 1500/1 A (Turns Ratio) X 0.02 A 250 V 1500/1 A 5P15 15 VA Core 4: C.T Ratio Class VA : 1500/1 A : 5P15 : 15 VA KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 164 of 270 165 SECTION V: TECHNICAL SPECIFICATIONS c) Voltage Transformers: Rated Voltage of the CT : 17.5kV One minute power frequency withstand voltage : 38 kV Impulse withstand voltage : 95 kV Ratio: Core 1, Core 2 : 11000/√3 : 110/√3V : 11/√3V VA : 150 VA Class : 0.5 & 3P NB: The rated VA of 150 VA is for three Phase unit. Incase three (3) single phase units are supplied, the minimum acceptable burden for each is unit 50VA. 2.5 FACTORY ACCEPTENACE TESTS (FATs) (see clause 1.10(e)) All the switchgear panels shall be tested in accordance with the requirements of IEC 60298 Tests shall be carried out on the circuit breaker as per the requirement of IEC 62271100. Current transformers and Voltage transformers shall be tested in accordance with the requirement of IEC 60044-1 and 6044-2 respectively. The following tests shall be carried out during the FATs, by the manufacturer in presence of the employer’s engineers. 1. Complete Switchgear Board a) Dimensional Checks b) Operational Tests c) Primary Injection Tests d) Calibration Tests on Relays and Instruments Power frequency Withstand Test e) Megger Test f) Contact resistance test for Primary joints g) Lighting Impulse withstand test h) Power frequency Withstand Test on Secondary Wiring 2. 17.5kV Circuit Breaker Routine tests a) Operation test b) High Voltage tests, dry. c) Voltage tests on controls and auxiliary circuits d) Measurement of resistance of the main circuit Type Tests: Submit copies of Type test Reports and Certificate e) f) g) h) Mechanical endurance test Temperature rise test Impulse voltage test Interrupting Capacity NB: Copies of Type Test Certificate for similar rated Circuit Breakers and Certified by National Standards and Testing Authority body or Reputable Third Party Test Laboratory shall be submitted with the Tender for Evaluation Purposes. 3) Current Transformer Routine tests shall be carried out at the manufacturer's plant as per the requirement of IEC 60044-1, as listed below, in the presence of KPA Engineers. i. ii. Polarity test and verification of terminal markings test Ratio and phase angle error tests (accuracy class composite error test) KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 165 of 270 166 SECTION V: TECHNICAL SPECIFICATIONS iii. iv. v. vi. Power frequency tests on primary and secondary windings Power frequency withstand tests between sections (windings) Inter-turn over voltage tests Partial discharge measurement Certificate and type test report for the following type test shall be provided during the FATs: i. Lightning, Impulse voltage withstand test ii. Temperature rise test iii. Short tine current test iv. Determination of Errors test v. Radio Interference voltage measurements (RIV) 4) Voltage Transformer Routine tests shall be carried tout at the manufacturer’s plant during FATs as per the requirements of IEC 60044-2, as listed below:(a) (b) (c) (d) (e) (f) Polarity tests and verification of terminals Power frequency withstand tests on Primary windings Power frequency withstand tests on secondary windings Power frequency withstand tests between sections Determination of errors Partial discharges measurement Certificates and type test report for the following type tests shall be provided during the FATs:(a) (b) (c) (d) (e) Temperature rise test Lightning Impulse Test Determination of errors Short-circuit withstand test capability Measurement of the radio interference voltage (RIV) 5) Protection Relay Tests a. Relay Pick-up test for all functions and phases b Relay timing test for all functions and phases c Directional characteristic test d. In-zone and out of Zone tests for unit schemes 2.6 TRAINING AT THE MANUFACTURER’S PLACE During the FATs the manufacturer shall conduct complete training for the following equipments for at least four (4) KPA Engineers: (a) Feeder Protection and Control relay The Training shall include:(i) Theory on application of all the functions included in the relay (ii)Complete configuration of the relay using software including creation and editing of the switchgear Mimic (iii) Relay parameter setting (iv) Downloading and analysis of all the data including disturbance recording (vi) Installation and testing (vii) (vi) Trouble-shooting and repair (viii) Complete testing of all the relay functions The manufacturer shall plan adequate time for the training separate from the FATs. The duration of the training shall however not be less than three (3) eight hour working days. The employer may send a separate team from the team witnessing the FATs to attend the training. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 166 of 270 167 SECTION V: TECHNICAL SPECIFICATIONS The Training shall be considered to have been successful once the engineers are able to carry out all the above activities on their own. The manufacturer shall conduct evaluation tests and give a feedback report on the training to the employer for each of the engineers. (b) 17.5 kV Circuit Breaker. The Training shall include:(a) Functions of the Circuit breaker (b) Installation checks and operational tests (c) Inspections, repair and maintenance The manufacturer shall plan adequate time for the training separate from the FATs. The duration of the training shall be at least one (l) day. The engineers attending the FATs will attend this training. The training shall be conducted for Five (5) Engineers/Technicians. The duration of the Training shall be at least two (2) days. The manufacturer shall arrange for the complete training and pay for the venue and for meals and refreshments and any other associated costs. The training shall be considered to have been successful once the engineer / technicians are able to carry out all the above activities on their own. The manufacturer shall conduct evaluation tests and give a feedback report on the training to the employer for each of the engineers/technicians. 2.8 PROTECTION RELAYS, CONTROLS AND MEASURING DEVICES REQUIREMENTS FOR SWITCHGEAR PANELS: 2.8.1 GENERAL REQUIREMENTS 2.8.2 (a) The equipment for the control system shall be highly reliable, long-lived and suitable for continuous operation. (b) All instruments scales, coils, relay contacts and other features shall be suitable for the apparatus controlled or the purpose intended. (c) It shall be the manufacturer’s responsibility to properly design the electrical control, protective relaying, alarm and indication schemes related to the 11 kV switchgear panels. (d) The manufacturer shall prepare arrangement and detailed drawings, equipment lists and wiring diagrams based on the requirement of meters, relays, control switches, indicating lamps and other devices including those to be supplied under other subsections. (e) Protection against electrical faults and abnormal conditions on 11 kV switchboard and the outgoing 11 KV feeder shall be conducted by the protective relays and associated switchgear. ;BILL OF QUANTITIES The items listed under the bill of materials shall be installed and connected to form a complete and safe working system. Any components and accessories required to form a complete safe and correct working system, though not listed below shall be installed wired and connected by the manufacturer and shall be deemed to have been included in the bid and contract price. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 167 of 270 168 SECTION V: TECHNICAL SPECIFICATIONS 2.8.2.1 FEEDER PANELS REQUIREMENTS The feeder panel shall be equipped with the following protection relays, measuring and indicating devices, control and other accessories. i) Feeder protection and control relay. The relay must fully meet the requirements of the detailed specifications included in these specifications. ii) Trip circuit supervision relay visible from front of panel without having to open any panel compartment door. The TCS Relay shall be offered as a separate relay and NOT as a function of the feeder protection relay. Alternatively, the trip circuit supervisory function may be included in the feeder protection and control relay provided that it meets all the Requirements of the specifications iii) A single power measurement unit shall be provided for each feeder panel to capture instantaneous and maximum demand values for the following parameters; I, kV, MW, MVAR and p.f iv) Tariff Energy Meter v) Current Transducer; output 0-20mA, for input current of 0 — 1 Amp vi) Circuit breaker control switch (Close, Open &Neutral), with a mechanical Lock vii) Sensitive Earth Fault (SEF) mechanical ON/OFF switch, mounted on the panel and indelibly marked. viii) Circuit Breaker ON (red), OFF (green) and auto-trip (amber)indication lamps ix) Anti-condensation heaters for the Circuit Breaker and the LV compartment x) Hygrostat with separate humidity and temperature control setting to control the heater. xi) DC supply under voltage relay on the feeder panels at the two ends of the switchgear board when assembled xii) AC supply under voltage relay on the feeder panels at the two ends of the switchgear board when assembled xiii) Door switch operated lighting point and bulb xiv) 3 Pin - square power socket outlet with red neon indicator xv) Suitably rated MCBs for auxiliary 110V DC for control, 110V DC for Trip, 240 V AC for motor, 240 V AC for heaters and illumination and VT 110 V AC supplies shall be fitted 2.8.2.2 BUS-COUPLER PANEL REQUIREMENTS The Bus Coupler Panel shall be equipped with the following Protection Measuring and indicating devices, Controls and other Accessories. (i) (ii) (iii) Relays, Feeder protection and control relay. The relay must fully meet the requirements of the detailed specifications included in these specifications. Trip circuit supervision (TCS) relay visible from front of panel without having to open any panel compartment door with Push Button and indicating lamp. . The TCS shall be offered as a separate relay and NOT as a function of the feeder protection relay. Alternatively, the trip circuit supervisory function may be included in the feeder protection relay if can clearly be annunciated and meets all the requirements and of the specifications. Annunciator relay with at least 16 alarm windows for annunciations of all protection trips and equipment defects and power supply failures for the whole switchgear board and other equipments that will be connected to the switchgear board at site. The following alarms shall be connected to annuciator relay:(a) 110V DC supply fail – urgent (b) 240V AC supply fail – urgent (c) Incomer 1 Fault Trip – urgent KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 168 of 270 169 SECTION V: TECHNICAL SPECIFICATIONS (d) Incomer 2 Fault Trip – urgent (e) Bus-coupler Fault Trip – urgent (f) Feeder Fault Trip – urgent (g) Relay Fail – urgent (h) Trip Circuit Fail – urgent (i) Busbar Earth Switch 1 applied – non-urgent (j) Busbar Earth Switch 2 applied – non-urgent (k) VT change-over operated – non-urgent (l) Urgent Alarm (m) Non-urgent alarm The following alarms shall be engraved on the alarm windows and wired to the terminal block for connection at site. a) Battery Changer Failure - urgent b) Local Supply change-over operated — non-urgent c) Fire Alarm – urgent All the alarms marked urgent will be connected to an urgent alarm out put relay. All the alarms marked non-urgent will be connected to an non-urgent alarm out put relay. One output contact from each relay will be connected to the Hooter, one contact each will be connected to the annunciator window and one contact each will be connected to the terminal block for external connection to SCADA. iv) Hooter v) Circuit breaker control switch (close, open & Neutral), with a mechanical lock vi) Single power measurement unit shall be provided for each feeder panel to capture instantaneous and maximum demand values for the following parameters: I, kV, MW, MVAR and p.f. vii) Current Transformer: output 0-20Ma, for input current of 0-1 Amp viii) Circuit breaker ON (red) and OFF (green) indication lamps ix) Heater ONOFF switch for anti-condensation heater x) 11 kV board 110 V AC supply changeover circuit for energy metering. NB: A scheme consisting of contactors shall be designed to ensure that energy recording by energy meters is achieved at all times even when one of the 11kV incomer circuits is isolated and hence the bus-coupler closed. The scheme shall be designed so that under normal conditions, the feeder on each side of the section shall be supplied by the VT from the corresponding 11kV incomer, with the bus-coupler open. In case one 11kV incomer is switched off and the bus-coupler closed the 11kV Feeder shall receive 110V AC for energy metering from the remaining incomer. The scheme shall however not permit parallel connection of the VTs on the secondary side. The scheme shall be subject to approval by the employer. xi) xii) xiii) xiv) xv) xvi) Anti-condensation heater Hygrostat with separate Humidity and Temperature control Setting. DC supply under voltage relay Door switch operated lighting point and bulb 3-Pin – square power socket outlet with neon indicator Suitably rated MCBs for auxiliary 110V DC for control, 110V DC for Trip, 240 V AC for motor, 240 V AC for heaters and illumination and VT 110 V AC supplies shall be fitted. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 169 of 270 170 SECTION V: TECHNICAL SPECIFICATIONS 2.8.2.3 INCOMER PANELS REQUIREMENTS The Incomer Panel shall be equipped with the following Protection Measuring and indicating devices, controls and other Accessories Relay, (a) Feeder protection and control relay. They must fully meet the requirements of the detailed specifications included in this specifications. Three phase over current and each fault relay. (b) Three phase directional over current and earth fault relay (c) Trip relay with a push button for electrical reset (d) Trip circuit supervision relay visible from front of panel without opening relay compartment door. TCS shall be offered as a separate Relay and NOT as a function of the feeder protection relay. Alternatively, the trip circuit supervisory function may be included in the feeder protection relay if can cleared be annunciated and meets the requirements of specifications. (e) A single power measurement unit shall be provided for each feeder panel to capture instantaneous and maximum demand values for the following parameters: I, kV, MV, MVAR and p.f (f) Tariff Energy Meter (g) MW Transducer, ±20 mA (h) MVAr Transducer, ±20 mA (i) Current Transducer, 0-20 mA, for current input of 0-1Amp (j) Voltage Transducer, 0-20 mA, for voltage input of 0-110V AC (k) Circuit breaker control switch, (Close, Open & Neutral) with mechanical locking to prevent in-intended operation. (l) Circuit breaker status ON (red) and OFF (green) indication lamps (m) Heater ON/OFF switch, for anti condensation heater (n) Anti-condensation Heater (o) Hygrostat with separate Humidity and Temperature control setting. (p) DC Supply Under-voltage Relay (q) AC Voltage Under-voltage Relay (r) Door switch operated lighting point and bulb (s) 3-Pin-square power pocket outlet with neon indicator (t) Suitably rated MCBs for Auxiliary 110 V DC for control, 110V DC FOR Trip, 240 V AC for motor, 240 V AC for heaters and illumination and VT 110 V AC supplies shall be fitted. 2.8.3 PROTECTION RELAYS 2.8.3.1 REFERENCES IEC 60255: 2.8.3.2 Electrical Relays GENERAL REQUIREMENTS (a) The electrical protective relay shall be of Numeric design (b) Auxiliary relays, of Static or electromechanical design, with mechanical flag indicators are acceptable. (c) The protective relays and auxiliary relay shall operate successfully for any value of the DC supply voltage between 85% and 125% of the rated voltage of 110 V DC without exceeding the temperature rise limits for the operating coils. (d) Each Measuring protection relay shall be of the panel flush mounted, back connected type with rectangular case. Each relay shall have a removable transparent cover or cover with a transparent window making the front of the KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 170 of 270 171 SECTION V: TECHNICAL SPECIFICATIONS relay visible. It is preferred that each measuring relay shall be of a withdrawable type from the front of the panel with sliding contacts, without opening the current transformer secondary circuits, disturbing external circuits or requiring disconnection of leads on the rear of the panels. (e) Each protection relay shall be equipped with adequate electrically independent contacts, of adequate rating for Trip and alarm functions. The relay shall also have adequate number of LEDs to assign each of the available protection functions. The number of LEDs shall not be less than eight (8). (f) Test facilities for each AC current secondary circuit so as to provide access for testing of the protective relay and its associated circuits. This shall be provided on the terminal block and will consist of isolation links on the current transformer and voltage transformer circuits and suitable terminals for insertion of test leads banana terminals for injection of secondary current and voltage. (g) Each current transformer circuit shall be earthed through a removable link at one point only in the control compartment's terminal block. The protection trip and alarm circuit for each panel shall be provided with an isolation link to facilitate isolation of the trip or alarm circuit for testing and trouble-shooting of the circuits. (h) Relays contacts shall be suitable for making and breaking the maximum currents, which they may be required to control in normal service. Where contacts of the protective relays are unable to deal directly with the tripping currents, Auxiliary Trip relays shall be provided. This will ensure safety for the protection relays output contacts. (i) Relays contacts shall make firmly without bounce and the whole of the relay mechanism shall be as far as possible unaffected by vibration or external magnetic fields. (j) Relays shall be provided with clearly inscribed labels on the surface of the panel describing their application in words e.g., "Three over-current & earth Fault relay" in addition to the IEC numbering. (k) To minimise the effects of electrolysis, relay coils operating on DC shall be so connected that the coils are not continuously connected from the positive pole of the battery. (l) The relay thermal rating should be such that the fault current clearance times on any combination of current and time multiplier setting shall not exceed the thermal withstand capability of the relay (Maximum Fault current= 31.5 kA). (m) The numerical relays will be equipped with an RS232 communication port to facilitate connection to a Laptop computer for configuration and parameter setting. Also a communication port shall be provided on each numerical relay for interface into a substation control and monitoring system and for remote interrogation and programming of the protection relays. (n) The relays will also have a MMI with LCD screen and keypad to facilitate manual relay programming and data access. (o) Relay operation due to system fault, shall be indicated by a Red L.E.D, and the fault details (flags) shall be displayed on the MMI. Both the relay fault flags and red L.E.D shall be reset via reset push buttons without opening the relay cover. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 171 of 270 172 SECTION V: TECHNICAL SPECIFICATIONS 2.9 DETAILED SPECIFICATIONS FOR RELAYS, MEASURING AND INDICATING INSTRUMENTS, CONTROL SWITCHES AND OTHER ACCESSORIES These specifications indicate the required performance characteristics for each of the Protection Relays and are in accordance with IEC 60255. a) The Feeder Protection and Control Relay 1: This relay shall be installed on the feeder and bus-coupler switchgear panels and shall as a minimum meet the following requirements. The Feeder protection and control relay shall be of numeric design The Relay will have a large LCD screen measuring at least 7 cm x 7 cm where a mimic of the switchgear arrangement and status of the switchgear for the bay shall be displayed. The position of the circuit breaker, i.e., racked-in or withdrawn shall be indicated. Circuit breaker close and open key buttons with symbols and colour codes as per the IEC standards shall be provided on the relay as well as switchgear selection key. A local/remote key selector switch shall be provided on the relay and the selected status of the selector switch indicated by means of an LED. The relay shall be equipped with a keypad for manual configuration and parameter settings and for access of settings, fault and event records. The relay offered shall have at least the following protection functions; three phase overcurrent and earth fault, sensitive earth fault, having separate current transformer inputs to be connected to a core -balance CT to be installed in the switchgear panels. Other protection functions include; broken conductor protection, breaker failure protection, under and over frequency as well as over and under voltage functions. All the protection functions shall meet the requirements of each function as included in these specifications. The relay shall monitor, measure and display on the screen the following parameters; I, V, P, Q and p.f. Also the circuit breaker wear shall be monitored and stored. The relay shall store at least 20 fault records, 20 events and 6 oscillographic fault records. It shall be possible to display instantaneous measurands on the screen alongside the Bay Mimic. The unit shall have a green L.E.D to indicate healthy status and a red L.E.D to indicate operation (Trip) of the protection functions. It shall be equipped with a red L.E.D indicator to indicate relay failure as well as output contacts to signal relay failure. The relay shall have at least eight (8) programmable LEDs for displaying protection and other alarms. The Relay terminals shall be screw type terminals large enough to accommodate at least 4mm2 cable and shall be located at the back of the Relay. shall be Equipped with an RS232 serial port for connection to a laptop computer for configuration and setting of relay and control functions and also for access of the relay data. Also a communication port for connection to local area network shall be provided. Seven (7) laptop to relay connection cables shall be provided Seven (7) sets of Installation, commissioning, operation and maintenance manuals shall be provided. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 172 of 270 173 SECTION V: TECHNICAL SPECIFICATIONS b) Software for relay configuration, parameter settings and data download shall be supplied in CD ROM with the switchgear boards. Seven (7) copies (CD ROMs) of Software shall be supplied. The Feeder Protection and Control Relay 2: This relay shall be installed on the incomer switchgear panels and shall as a minimum meet the following requirements. •The feeder protection and control relay shall be of numeric design The relay will have a large LCD screen measuring at least 7cm x 7cm where a mimic of the switchgear arrangement and status of the switchgear for the bay shall be displayed. The position of the circuit breaker, i.e., racked-in or withdrawn shall be indicated. Circuit Breaker close and open key buttons with symbols and colour codes as per the IEC standards shall be provided on the relay as well as switchgear selection key. A local/remote key selector switch shall be provided on the relay and the selected status of the selector switch indicated by means of an LED. The relay offered shall have at least the following protection functions;three phase overcurrent and earth fault, directional three phase overcurrent and earth fault relay, sensitive earth fault. Other protection functions include; broken conductor protection, , breaker failure protection, under and over frequency as well as over and under voltage functions. All the protection functions shall meet the requirements of each function as included in this specifications. The Relay shall monitor, measure and display on the screen the following parameters; I, V,P, Q and p.f.. Also the circuit breaker ware shall be monitored and store. The relay shall store at least 20 fault records, 20 events and 6 oscillographic fault records. It shall be possible to display instantaneous measurands on the screen alongside the bay mimic. The unit shall have a green L.E.D to indicate healthy status and a red L.E.D to indicate operation (trip) of the protection functions. It shall be equipped with a red L.E.D Indicator to indicate relay failure as s well as output contacts to signal relay failure. The relay shall have at least eight (8) programmable LEDs for displaying protection and other alarms. The relay terminals shall be screw type terminals large enough to accommodate at least 4mm2cable and shall be located at the back of the relay. It shall be equipped with an RS232 serial port for connection to a laptop computer for configuration and setting or relay and control functions and also for access or the relay data. The relay shall be equipped with a keypad for manual configuration and parameter settings and for access of settings, fault and event records and other data. Software for relay configuration, parameter settings and data download shall be supplied in CD ROM with the switchgear boards. Seven (7) copies (CD ROMs) of Software shall be supplied. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 173 of 270 174 SECTION V: TECHNICAL SPECIFICATIONS NB: The Protection Functions Offered in the feeder protection and control relay shall satisfy the detailed specifications for each of the functions, detailed below:i. Three phase overcurrent and earth fault relay Should incorporate the following features; Relay must be of Numerical Design Shall be suitable for mounting on the panel front. Current setting range for overcurrent relay 0.51n-2.41n Current setting range for earth fault relay 0.051n-0.81n I.D.M.T characteristics according to BS142 or IEC255 i.e. SI,VI,EI,LTI, including definite time for the high-set Elements. Time setting multiplier 0.05 - 1.0 Broken conductor protection feature Highset Element for both overcurrent and earth fault with. Protection, with a setting range of 1-301n and a definite time delay setting of Seconds. Circuit breaker maintenance Fault records and event records Trip and start contacts shall be freely configurable to the output relays. Drop off /pickup ratio >90% Low transient overreach < 10% ii. Sensitive Earth Fault Relay Should incorporate the following features Relay must be of Numerical Type Current setting range for earth fault relay 0.010In – 0.8In Definite time delay characteristic: setting range, 0-30 Seconds Circuit breaker maintenance Fault records, event records and disturbance records Drop off/pickup ratio >90% Low transient overreach < 10% iii. Three Phase Directional Overcurrent and Earth Fault Relay Should incorporate the following features Relay must be of Numerical Type Current setting range for overcurrent relay 0.5In – 2.4In Current setting range for earth fault relay 0.05In – 0.8In Quadrature connection for polarizing voltage Applicable on the LV side of a Dyn1 transformer High set Element, with a setting range of 1-32In All stages of the phase and earth elements shall be freely assigned the directional feature. Shall have the ability to program the directional feature forward or reverse for each setting stage. I.D.M.T characteristics according to BS 142 or IEC 255 and define time characteristic The normal operating boundary shall be +/-90 degrees from relay characteristic angle. Relay sensitivity should be 1% of rated value of current and polarizing voltage at an angle equal to the relay characteristic angle. Time setting multiplier 0.05 – 1.0 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 174 of 270 175 SECTION V: TECHNICAL SPECIFICATIONS High set element for both overcurrent and earth faults protection, with a setting range of 1-20In. Circuit breaker maintenance Incorporate faults records, event records Configurable output relays with ability to output starting elements to control tripping of other upstream protection relays. iv. Trip Relay High burden tripping relay, immune to capacitance discharge current and leakage current. At least 7 pairs of output contacts two of which should be NC contacts Instantaneous operation, t >15ms Flag or target shall be a red L.E.D, durable bulb or red mechanical flag The relay shall be suitable for flush mounting The relay shall be electrically reset, the rest button shall be inbuilt on the relay and accessible without opening the relay cover OR shall be supplied separately for panel surface mounting. Relay Terminals- shall be screw type terminals large enough to accommodate at least 4mm2 cable and shall be located at the back of relay. Relay terminals shall be clearly marked Relay contacts configuration shall preferably be drawn on the relay casing v. Trip Circuit Supervision Relay The relay shall have the following features Continuous supervision of trip circuit for circuit breaker in both OPEN & CLOSED position Trip circuit fail – Red L.E.D or Flag\ Suitable for panel surface mounting: However if mounted inside the control compartment, then the relay must be visible from the front. Two (2) normally closed (NC) and two (2) normally open (NO) or 2 NO/NC output contacts Relay Terminals shall be screw type terminals large enough to accommodate at least 4mm2 cable and shall be located at the back of the relay. Relay terminals shall be clearly marked Relay contacts configuration shall preferably be drawn on the relay casing. vi. Annunciator Relay Unit Shall have Silence, Accept and Reset, push buttons, to control the Alarms Shall be equipped with at Least 16 separate alarm elements Each of the elements shall be freely assigned to one of two common output alarms; urgent and non-urgent alarm. Each alarm element shall have a red L.E.D. to indicate ON status. It shall also have provision for fixing of identification label changeable on site. A flashing alarm element shall be clearly visible. The urgent and non-urgent common alarms shall be freely configurable to the output relays. High immunity against electrical interference KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 175 of 270 176 SECTION V: TECHNICAL SPECIFICATIONS vii. Relay output for audible alarm and for self supervision shall be provided Integrated events register to provide analysis of the latest sixteen (16) events Each of the elements shall be freely assigned to one or two common output Alarms; Urgent and Non-urgent Alarms Relay Terminals-shall be screw type terminals large enough to accommodate a 2.5 mm2 cable and shall be located at the back of the relay. Relay terminals shall be clearly marked Relay contacts configuration shall preferably be drawn on the relay casing. At least two output relays one for urgent and the other for non-urgent alarm. At least two (2) pairs of NO pair of output contacts for each output relay. Circuit breaker Close/Open control Switch The switch shall have a mechanical interlock to prevent accidental operation of the switch. It shall have a close, neutral and open positions engraved on the switch, black letters on white background. After an operation, the switch shall return to the neutral position by spring action. The terminals of the switch shall be screw type and shall be indelibly marked. viii. Transducers: (a) MW Transducer Connection shall be 3-Phase, 4-Wire Inputs 110V AC and l Amp Programmable output characteristic Out put shall be 0 - ±20 mA Auxiliary power supply shall be 110 V AC/DC. The transducer terminals shall be of screw type, large enough to accommodate 4 mm2 cable and shall be indelibly marked. (b) MVAr Transducer Connection shall be 3-Phase 4-Wire Inputs 110V AC and l Amp Programmable output characteristic Out put shall be 0 - ±20 mA Auxiliary power supply shall be 110 V AC/DC The transducer terminals shall be of screw type. Large enough to accommodate 4mm 2 cable and shall be indelibly marked. (c) Current Transducer Input 0-1 Amp Output 0 -20 mA Auxiliary power supply shall be 110 V AC/DC Transducer terminals shall be screw type, large enough to accommodate 4mm2 cable and indelibly marked. (d) Voltage Transducer Input 0-110 V AC Output 0 -20 mA KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 176 of 270 177 SECTION V: TECHNICAL SPECIFICATIONS Programmable output characteristic Auxiliary power supply shall be 110 V AC/DC Transducer terminals shall be screw type, large enough to accommodate 4mm2 cable and indelibly marked. NB: A single transducer units with all of the above listed functionality in one casing is acceptable. ix. Moulded Case Circuit Breaker: Three phase unit with Auxiliary contact Rated operating voltage, 400 V AC Rated Insulation voltage 600V AC Rated frequency 5O HZ Setting value of Thermally delayed Overhead release, 3A Auxiliary switch should have 1 NC & I NO contact. Suitable for fixing on a DIN rail Terminals suitable for connection of at least 4mm2 cable x. Signalling Hooter: The actuator system shall consist of a strong, non polarized electromagnet with an impact resistance sturdy casing. Rated frequency 50 HZ. Rated voltage shall be 240V AC; +6/-10 % Protection degree shall be IP 55 Operating mode continuous Volume approximately 108 dB(A) 1 1/4 m Hooter terminals shall be large enough to accommodate 4 mm 2 cable and indelibly marked. xi. Anti-condensation Heater: The heater should be suitable for mounting inside the circuit breaker, the cable and LV compartment. The Heater for each compartment shall be adequately rated to preventing condensation within the respective compartment. xii. DC Supply under voltage Relay Shall have a settable range for under-voltage pick ups, of 30-80% of the rated DC voltage Shall be of electromechanical or electronic design Shall have an accuracy of < ± 4% Shall be self reset when the voltage returns to normal level Shall have a built in indication LED (green) and a built in operation LED (red) Shall have at least 2 NC auxiliary contacts (Contacts close for under voltage conditions) The relay shall be rated for continuous operation at the rated DC voltage. Shall be suitable for mounting on DIN rail Relay terminals shall be screw type, large enough to accommodate 4mm2 cable and indelibly marked. xiii. Indicating Lamps: Shall be suitable for mounting on the front of the panel KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 177 of 270 178 SECTION V: TECHNICAL SPECIFICATIONS The Lamp Indicators should be rated for 130V DC and equal or less than 2.5W rating. The lamp indicators should be designed for continuous operation and give a long life of at least 10 years. The bulb shall be easily replaceable without using a special tool. The Lamp Indicators shall be of LED design NB: LED Indicators are preferred xiv. Power Measurement Unit: This is a power monitoring meter for panel mounting The unit shall be of numerical design The unit shall have a large LCD display for displaying the measurements The unit shall measure instantaneous values of; rms voltage, both phase – phase and phase to ground, currents, active reactive and apparent power, energy, frequency, power factor and phase angle per phase. The unit shall the following input rating, 1A and 110V AC phase to phase The unit shall be for flush mounting on the front of the panel The unit shall be for 3 phase, 4 –wire connection on the secondary or current and voltage transformers The unit shall be equipped with an RS232 port for programming the unit to ensure correct measurement and display of the parameters. The CT and VT ratio shall be programmable. The accuracy of measurement shall be at least class 1.0 It shall be possible to display all the measured parameters on the screen through the pre-programmed display screen. The screen to be displayed shall be selectable using the keys on the front of the unit. The software and the PC to measurement unit connection cable shall be supplied with the unit \The LCD screen shall be large enough to accommodate at least three measurands simultaneously All the terminals shall be clearly marked The measurement range for power shall at least be up to 30 MVA The measurement unit terminals shall be screw type, large enough to accommodate 4mm2 cable and indelibly marked. 2.10 DETAILED SPECIFICATIONS FOR ENERGY METERS: SPECIFICATIONS FOR HIGH TENSION (HT) VOLTAGE AND TRANSFORMERS (CT) CONNECTED STATIC METERS FOR METERING ON THE INCOMERS AND FEEDERS. CURRENT ENERGY 1 Scope This specification is for newly manufactured High Voltage current transformer connected static meters for measurement of alternating current active energy in 50 HZ networks. 2 Requirements 2.1 Meters shall meet requirement of IEC 62052-11: 2003 and IEC 6205321:2003 2.2 Meters shall be suitable for operation in tropical climate where temperature may vary from -1 to +45 degrees Celsius and Average Annual Relative humidity reaching 90% and altitude of 0-1000m. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 178 of 270 179 SECTION V: TECHNICAL SPECIFICATIONS 2.3 The meters shall be constructed as 3 phase 4-wire meters but may be wired as 3 phase 4-wire or 3 phase 4-wire meters. 2.4 The meters shall have terminals with bottom entry for cables and the arrangement shall be L1, V1, L1:L2V2L2:L3V3L3: N for 3 phase 4-wire meters. 2.5 The meters shall conform to the degree of protection IP 51 as given in IEC 60529: 1989 Degrees of protection provided by enclosures (IP Code) Amendment 1:1999. 2.6 The meters terminal hole and screws shall be made of brass or nickelplated brass for high strength and high conductivity. Terminal hole shall be of sufficient size to accommodate the cables of at least 6mm diameter. 2.7 The meters shall have LED indicators for testing and indication of KWh and kVArh – meter operation. 2.8 The meter shall be equipped with auxiliary terminals for inputs and outputs. 2.9 The meters shall have a real-time clock controlled by a quartz crystal oscillator and a back up power supply to run the calendar clock for a minimum of 1 year without mains voltage. 2.10 The meters shall have a non-volatile memory capable of data storage. 2.11 The meters shall be capable of storing load profile for at least 180 days on four channels with 20 minutes integration for the following parameters namely Import watts, Export watts, Export VA. Import VA, 4-quadrant Reactive energy Q1,Q2,Q3 and Q4, Phase voltage. Phase currents and Power factor. 2.12 The meters shall be capable of measuring the following parameters: Active, reactive and apparent energy and demand in export and import modes; Maximum demand in kVA and kW: Four quadrant power measurement: Multi-tariff metering: Accurate measurement for incorrect phase sequence; and Instrumentation data (V, I, Pf, Phase angles, Power etc) 2.13 Additional operational and security features of meter: Meter sealing provisions; meter software with enhanced access level; Logging of loss of voltage, over-current, over-voltage, date of last programming; at least 6 and 6 registers for energy and demand respectively; Programmable billing dates; Non resettable billing registers and a minimum of 12 months; LCD with 5 digit ID codes that are EDIS compliant; No mains supply reading facility: RS 485 and optical ports for communication; Primary metering for Demand and Energy. 2.14 Meters rating: 3 x 63.5/110 V, 3 x 1 A and at 50 Hz 2.15 Meter type and other test: Meters to pass tests on Power consumption, Influence of short-time over-current, Influence of selfheating, AC voltage test, Limits of errors due to variation of the current, Limits of error due to influence quantities, Test of starting and no-load condition and EMC tests. 2.16 Name plate marking requirements: Each meter market legibly and indelibly in English with the following information: Name or trade mark of the Manufacturer, Country of origin, Type/model, meter number up to ten digits, in inscription “Property of Kenya Port Authority (KPA), Standard(s) to which the meter complies and Year of manufacture. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 179 of 270 180 SECTION V: TECHNICAL SPECIFICATIONS 2.17 Warranty requirements: 18 months from date of supply of meters 2.18 Schedule of Technical data Standard and type tests General requirements, tests and test Particular requirements for static meters for active energy Power consumption and voltage Shock test Plastic-determination of temperature Degree of protection Measurement Base Network type Connection type Accuracy Humidity: Altitude Temperature range (operating) Voltage measurement (Uri) Voltage range Voltage circuit burden Burst test Impulse voltage Current measurement Short circuit current Starting current Current circuit burden LCD Load profile Dielectric strength IEC 62052-11:2003 IEC 62053-21:2003 IEC 62053-21:2003 IEC 62052-11:2003 IEC 62052-11:2003 IP51 Active / Reactive energy, 3 element, 4 quadrant 3phase 3 or 3 phase 4wire VT and CT connected kWh class 1.0 kVArh class 2 Reaching 90% Up to 2,200m -1 to+45 ° C 3x 63.5/110 V 50Hz, 3 or 4 wire 0.8 U, to 1.15 U, 5 2 W and 10 VA 4 kV 6 KV, 1.2/50 us I„ =1 A; I,,,, > 6 A 20 Imax for 0.5 s 0.001 L < 1 VA 7 Measurement and 5 ID (EDIS) digits _❑ 180 day-4-channel capacity at 20 minute 4 kV, 50 Hz., 1 min. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 180 of 270 181 SECTION V: TECHNICAL SPECIFICATIONS A. TECHNICAL SCHEDULES FOR 11kV SWITCHGEAR, CONTROL, PROTECTION AND COMMUNICATIONS EQUIPMENT Technical Schedules for 11kV switchgear control, protection and communications equipment The Tenderer shall after reading through the Technical Specifications and the Tender Documents in general complete the technical schedules below, which also constitute the guaranteed technical particulars. The completed schedules shall accompany the bid. Attach manufacturer's profile, catalogues and manuals to verify details entered in the schedule. Schedule A DESCRIPTION SWITCHGEAR BOARD KENYA PORT AUTHORITY REQUIREMENT Manufacturer's name Indicate Manufacturer's letter of Authorization. Copy of ISO 9001/2 certificate. Provide copy Provide copy Type or designation number of Switchgear offered and applicable standard. Manufacturer's experience in Manufacturing same type of Switchgear panels. Manufacturer's experience in Manufacturing similar type of Switchgear panels No. of units sold in the last 5 years. No. of units sold in the export market [attach list] in the last 5 years [attach export list] Enclosure [IP] class of protection [attach type test certificate]for the offered panel type Arc proof design [attach type test certificate] for offered panel type Rated voltage Rated power frequency withstand [attach routine test report] offered panel type Rated lighting impulse withstand [attach type test report] for the offered panel type Metal clad compartments [CB], Busbar, LV, CT, Cable] attach layout -drawing for the offered panel type Busbar material SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} At least 7 Years 15 years > 400 > 200 IP41 Yes 17.5KV 38KV 95 KVp 5 copper KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 181 of 270 182 SECTION V: TECHNICAL SPECIFICATIONS Dimensions [WxHxD [attach layout drawing] Short circuit withstands. provide Arc Proof design for entire switchgear board ARC venting Lockable door with viewing glass in CB compartments. Lockable door for LV compartment Earth switch rating on making and withstand Earth switch position visible from front Shutters for Busbars [red] and circuit [yellow] provided. Provision to safely open the shutters for phasing out provided Anti condensation heater Hygrostat with variable Humidity and temperature control setting Busbar rating Yes Circuit rating - Incomer 1500A Circuit rating - Feeder Integral Feeder earth switch Horizontal or vertical Isolation and withdraw of circuit Breaker Live cable indicator Interlock between Incomer live cable and Earth switch Integral Busbar earth switch Separate locking of Busbar and circuit shutters Earth switch operating handle cannot be inserted in to operate position when CB is in circuit position Switchgear panel width Switchgear panel depth Length(Height) of LV Compartment Detailed catalogue and manual for the switchgear panels with detailed design drawings Dimensioned Layout drawing for the complete switchgear board, including the Arc venting channel Single line drawing(SLD)for the complete switchgear board Routing test report for similar panel as per IEC 298? 31.5KA, 3sec Yes Yes 31.5KA, 3 sec Provide Provide Provide Provide Provide 2000A 630A Provide State Provide Provide Provide Provide Yes ≤800 mm ≤800 mm ≤650 mm Provide Provide Provide Provide KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 182 of 270 183 SECTION V: TECHNICAL SPECIFICATIONS Schedule B DESCRIPTION Manufacturer's name Manufacturer's letter of Authorization. Copy of ISO 9001/2 certificate. Type or designation number of circuit breaker offered Applicable standard for manufactures and testing Manufacturer's experience in Manufacturing same type of Circuit breaker. Manufacturer's experience in Manufacturing similar type circuit breaker [MV indoor circuit breaker] No. of units sold in the last 5 years. Units sold in to export market in the last 5 years 12kV CIRCUIT BREAKER KENYA PORT AUTHORITY REQUIREMENT Indicate Provide copy Provide copy state At least 7 Years A least 15 years ≥1000 ≥ 500 Type of interrupter employed Name of manufacturer of vacuum interrupter Vacuum Provide Manufactures experience in manufacturing vacuum interrupters Rated circuit breaker voltage 1 minute power frequency withstand [attach test report] Impulse withstand voltage [attach test report] Rated short circuit current and withstand [attach type test report] Rated short time making current peak [attach type test report] Circuit breaker operating sequence [attach type test report] Motor wound spring operated mechanism Auxiliary DC voltage for closing and tripping coils Trip-free mechanism Anti-pumping feature Auxiliary AC supply CB mechanism ≥15 years Visible spring charges/discharged mechanical indication on CB as per specifications. SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} 17.5 kV 38 kV 95 kV 31.5 kA, 3 sec 63 kA or 79 kA 0-0.3 sec-co-3 minco 110 V DC State Provide 240 VAC Motor wound spring Provide KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 183 of 270 184 SECTION V: TECHNICAL SPECIFICATIONS Visible CB ON/OFF indications as per specifications Connection of CB to auxiliary panel circuits via a plug-in cable Operation counter CB close and open mechanical push Button on CB CB isolation CB withdrawal CB lowering trolley provided [for horizontal withdrawal] suitable for use by one switching operator CB withdrawal not possible when CB is closed CB cannot be drawn-in until the earth switch is open and auxiliary circuit connected [powered] Earth switch cannot be closed when the CB is in circuit position or in transit CB cannot close when in transit Circuit breaker is equipped with anti pumping device CB routine test report as per IEC 62271-100 CB rating for incomer and bussection CB rating for feeder Circuit breaker poles between the interrupters and the primary plug in contacts-insulated. Provide Yes Provide Provide Vertical / Horizontal Horizontal provide Yes Yes Yes Provide 1500A 630A Yes KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 184 of 270 185 SECTION V: TECHNICAL SPECIFICATIONS Schedule C DESCRIPTION Manufacturer's name Manufacturer's letter of Authorization. Copy of ISO 9001/2 certificate. Type or designation number of CT Applicable standard Manufacturer's experiencein Manufacturing same type of CTs Manufacturer's experiencein Manufacturing similar type CTs [MV indoor type] No. of units sold in the last 5 years. Units sold in to export market in the last 5 years Rated circuit breaker voltage 1 minute power frequency withstand [attach test report] Impulse withstand voltage [attach a copy test report] Short -circuit withstand current duration [attach copy of type test report] Feeder CT details Raito – 600/300/1A Core 1 – 15VA,5P15 Core 2 – 15VA,cl 0.5 Incomer CT details Ratio – 1500/1A Core 1 : clx; VR≤250V;Ie≤0.02A Core 2 : clx; VR≤250v;Ie≤0.02A Core 3 : 15VA,5P15 Core 4 : 15VA cl 0.5 Bus coupler CT details Ratio : 1500/1A Core 1 : 15VA, 5P15 Core 2 : 15VA, cl 0.5 Routine test certificates of similar CTs as those listed in 14, 15 and 16 above. NB: the classes must be the same as per IEC 60044-1 Provide manufacturer’s CT catalogue CURRENT TRANSFORMERS KENYA PORT AUTHORITY REQUIREMENT SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} Indicate Provide copy Provide copy state At least 7 Years ≥15 years ≥600 ≥ 300 17.5 kV 38 kV 95 kVp 31.5 kA, 3 sec Yes Yes Yes Provide Provide Provide Provide Provide Provide Provide Provide KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 185 of 270 186 SECTION V: TECHNICAL SPECIFICATIONS Schedule D DESCRIPTION Manufacturer's name Manufacturer's letter Authorization. Copy of ISO 9001/2 certificate. Type or designation number Applicable standard Manufacturer's experience Manufacturing same type of VTs Manufacturer's experience Manufacturing MV, indoor VTs No. of units sold in the last 5 years. Units sold in to export market in the last 5 years Rated voltage of offered VT 1 minute power frequency withstand voltage [attach routine test report] Impulse voltage withstand voltage [attach a copy test report] Feeder VT details Raito : 11KV/√3; 110/√3; 110/√3 VAC Core 1 : 100VA, cl 0.5 Core 2 : 50VA, cl 3p Primary fuses Secondary fuses Copies of routine test reports for VT of similar voltage rating as per IEC 60044-2 Manufacturer’s catalogue VOLTAGE TRANSFORMERS KENYA PORT AUTHORITY REQUIREMENT SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} Indicate ofProvide copy Provide copy of VT state in At least 7 Years in ≥ 15 years ≥ 500 ≥200 17.5 kV 38 kV 95 kV Provide Provide Provide Provide Provide Provide Provide KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 186 of 270 187 SECTION V: TECHNICAL SPECIFICATIONS Schedule E RELAYS DESCRIPTION PROTECTION RELAYS AND AUXILIARY KENYA PORT AUTHORITY REQUIREMENT Manufacturer's name Indicate Manufacturer's letter Authorization. Copy of ISO 9001/2 certificate of manufacturer. Applicable standard Provide of copy SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} Provide copy state Manufacturer's experience ≥ 15 in Years Manufacturing protection and auxiliary relays Total No. of measuring ≥ 5000 relays sold in the last 5 years Experience in manufacture ≥ 10 years of numerical protection relays. Number of numerical ≥ 5000 protection relays sold in the last 5 years Number of numerical relays ≥ 2000 sold to the Export Market in the last 5 years. NB: Attach manufacturers export sales list. FEEDER PROTECTON AND CONTROL RELAY Relay shall be of Numeric Design Relay designed for Bay Protection & Control Size of Relay LCD screen state State State For flush mounting on panel surface Relay is equipped with Circuit Breaker close and open key/push buttons Relay has the following protection functions: Three phase over current Provide Earth fault function Provide Sensitive earth fault function Broken Conductor function Provide Provide Provide KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 187 of 270 188 SECTION V: TECHNICAL SPECIFICATIONS Auto-reclose function Provide Circuit breaker maintenance function Measurement and display of instantaneous values of I, V, P, Q and p.f on the LCD Trip Indication Via Red LED Provide Healthy Indication via Green LED Relay has eight LEDs for Annunciation Start and Trip output contracts are freely configurable Relay terminals are screw type and adequate to accommodate 4mm2 cable Fault Records storage capacity Events storage capacity State State State Disturbance Record storage capacity MMI with keypad and LCD State Serial RSS232 port Provide Communication Port for connection to Local Network Software to be provided: Seven Copies of software in CD ROM required Relay is equipped with IEC 61850 communication Seven (7) connection cables from relay to laptop Seven (7) Detailed publication / operation and instruction manual attached to verify all the specifications Provide State name of software State Provide Provide KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 188 of 270 189 SECTION V: TECHNICAL SPECIFICATIONS Schedule F FAULT RELAY THREE PHASE OVER CURRENT AND EARTH DESCRIPTION One tine delay element and two high set elements Setting range and step for IDMT element for both current and Time Multiplier Setting Selectable Current/Time curves for IDMT element. Broken conductor protection KENYA PORT AUTHORITY REQUIREMENT state state State Provide Schedule F.1 EARTH FAULT RELAY DESCRIPTION KENYA PORT AUTHORITY REQUIREMENT One time delay element and two high set elements Setting range and step for IDMT element for both current and Time Multiplier Setting Selectable Current/Time curves for IDMT element. Setting range and step for high set elements for both current and time delay Schedule F.2 DESCRIPTION SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} state state Numeric State SENSITIVE EARTH FAULT FUNCTION KENYA PORT AUTHORITY REQUIREMENT Current setting range State Time delay. state SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 189 of 270 190 SECTION V: TECHNICAL SPECIFICATIONS Schedule F.3 OVERCURRENT THREE-PHASE DIRECTIONAL AND EARTH FAULT RELAY DESCRIPTION Current setting range for over current element Current setting range for earth fault element. Quadrature connection of polarizing voltage Directional feature freely assigned to Over current and Earth faults elements Directional element voltage sensitivity Circuit breaker maintenance One time delayed element and two high set elements. KENYA PORT AUTHORITY REQUIREMENT state state State State State Provide Provide Schedule G DESCRIPTION SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} TRIP RELAY KENYA PORT AUTHORITY REQUIREMENT Manufacturers name state Type or designation name state Electrical reset Provide High burden relay State Operating time State Contracts configuration State SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 190 of 270 191 SECTION V: TECHNICAL SPECIFICATIONS Schedule H TRIP CIRCUIT SUPERVISORY RELAY DESCRIPTION KENYA PORT AUTHORITY REQUIREMENT Manufacturers name state Type or designation name state Supervision for CB open and closed status Contracts configuration State State Schedule I ANNUNCIATOR DESCRIPTION KENYA PORT AUTHORITY REQUIREMENT Manufacturers name Type or designation name Number of alarm elements Each alarm has RED LED for visual indication Has silence, accept and rest push buttons Alarms freely assigned to urgent or non-urgent buswires Schedule J DESCRIPTION SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} RELAY UNIT SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} state state state Provide State State CIRCUIT BREAKER CLOSE/OPEN SWITCH KENYA PORT AUTHORITY REQUIREMENT Manufacturers name state Type or designation name state Mechanical interlock Provide Close and open position marked on the switch State SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 191 of 270 192 SECTION V: TECHNICAL SPECIFICATIONS Schedule K DESCRIPTION Manufacturers name Type or designation name Connection 3 phase – 4 wire Input and output range Programmable output characteristic MVAR TRANSDUCERS Manufacturers name Type or designation name Connection 3 phase – 4 wire Input and output range Programmable output characteristic TRANSDUCERS KENYA PORT AUTHORITY REQUIREMENT state state Provide State State state state Provide State State CURRENT TRANSDUCER Manufacturers name Type or designation name Input and output range state state State VOLTAGE TRANSDUCER Manufacturers name Type or designation name Input and output range state state State DESCRIPTION SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} KENYA PORT AUTHORITY REQUIREMENT Schedule L LAMPS SUPPLIER’S DETAILS/ RESPONSE {Enter value or Yes or No as appropriate} HOOTER, HEATER & INDICATING HOOTER Manufacturers name Type or designation name Auxiliary Supply 240 V AC supply state state state ANTI CONDENSATION HEATER Manufacturers name Type or designation name Duty – continuous operation state state state KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 192 of 270 193 SECTION V: TECHNICAL SPECIFICATIONS INDICATING LAMPS AND HOLDERS Manufacturers name Type or designation name Rating Duty Duration of service state state ≤ 2.5W Continuous ≥ 10 years Schedule M Manufacturers name Type or designation name of the unit Unit suitable for flush mounting Complete order number of offered unit Parameters measured Class of accuracy of measurement Configuration of the unit (3 phase + 4 wire) POWER MEASUREMENT UNIT state state State State State State NOTE: The Bidders should note that the above Technical schedules must be fully completed and submitted with the bid. Failure to complete the schedules shall lead to rejection of the bid. Each entry in the schedule in compliance with the specifications shall constitute marks as shown in the bidders evaluation sheet. The maximum possible score shall be 28% and the lowest possible score shall be 0%. Note: This schedule does not in any way substitute for details information required elsewhere in the specification. NB: The Bidder should read through the document thoroughly and submit with the bid all the required test certificates, manuals and drawings, etc. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 193 of 270 194 SECTION V: TECHNICAL SPECIFICATIONS B. TECHNICAL SCHEDULES FOR 132KV SWITCHGEAR, CONTROL, PROTECTION AND COMMUNICATIONS EQUIPMENT The Tenderer shall after reading through the Technical Specifications and the Tender Documents in general complete the technical schedules below, which also constitute the guaranteed technical particulars. The completed schedules shall accompany the bid. Attach manufacturer's profile, catalogues and manuals to verify details entered in the schedule. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 194 of 270 195 SECTION V: TECHNICAL SPECIFICATIONS Technical Schedules for 132 kV switchgear, control, protection and communications equipment. SCHEDULE -1a TECHNICAL GUARANTEES, OUTDOOR SWITCHGEAR OUTDOOR SWITCHGEAR ITEM PARTICULAR A1 Circuit Breaker (Type__________) Breaking Medium Manufacture Rated voltage 132 kV UNIT TOLERAN CE SF6/Vacu um kV - Maximum service voltage kV - Rated frequency Hz - Rated Continuous current A - One minute power frequency withstand voltage, dry and wet (a) To earth GUARANTEED FIGURE kV rms (b) Across open breaker pole kV rms Impulse withstand voltage 1.2/50 ms (a) To earth kV peak (b) Across open breaker Breaking capacity at rated voltage (a) symmetrical kA rms (b) asymmetrical kA rms - - Making capacity kA peak - A - Breaking capacity of capacitive current Overvoltage factor for disconnection of unloaded transformers (without voltage limitation by lighting arresters) - Rated inductive current switching capacity A - Permissible 1 second short-tine current kA rms KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 195 of 270 196 SECTION V: TECHNICAL SPECIFICATIONS OUTDOOR SWITCHGEAR ITEM DESCRIPTION Circuit breaker continued Dynamic short-time current - - UNIT GUARANTEED FIGURE TOLERAN CE kA peak m.sec (a) At 100% breaking capacity m.sec (b) Under phase opposition m.sec - A2 Opening time, interval of time between the instant of application of tripping impulse to the instant when the main contacts have separated in all poles Total break time, interval of between the instant of application of tripping impulse to the instant of final arc extinction in all poles. 132 kV Rate of rise of recovery voltage (RRRV) at 100% short circuit current. (a) 3-phase kV/msec (b) 1-phase kV/msec - RRRV out of phase duty kV/msec - Minimum temperature rise at rated current of main contract 0C Current Transformers Manufacturer - Rated voltage kV - Maximum service voltage kV - Rate frequency Hz One-minute power frequency test voltage of (a) Primary winding kV rms (b) Secondary winding kV rms - - Lighting impulse withstand voltage kV peak - KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 196 of 270 197 SECTION V: TECHNICAL SPECIFICATIONS OUTDOOR SWITCHGEAR ITEM DESCRIPTION 132 kV UNIT - Rated primary currents A - Rated secondary current A Short-time thermal rating (a) 1 second - Short –time dynamic rating GUARANTEED FIGURE TOLERANCE kA rms kA peak Burden and accuracy class of Measuring core Protection core Instrument security factor of the measuring core Accuracy limit factor of the (a) Protection core (a) (b) - A3 Voltage Transformers, (Type _____________) Manufacturer Rated voltage kV - Maximum service voltage kV rms - Rate frequency Hz One-minute power frequency test voltage of (a) Primary winding kV rms (b) Secondary winding kV rms - - Lighting impulse withstand voltage kV peak - - Burden and accuracy class of (a) Measuring winding protection winding Ratio kV - Country of manufacture Cubicles - Circuit breaker - Voltage transformers A4 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 197 of 270 198 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 1a: TECHNICAL GURANTEES, OUTDOOR SWITCHGEAR OUTDOOR SWITCHGEAR ITEM PARTICULAR A5 UNIT 132 KV GUARANTEED. FIGURE TOLERANCE Disconnector (Type ________) - - - - - - Manufacturer Applicable Standards Breaking Medium Rated voltage Maximum service voltage Rated Frequency Rated Continuous current Contact Resistance Max temperature rise under rated voltage and current Rated power frequency withstand voltage (a) To earth (b) Across open contacts Impulse withstand voltage 1.2/50 ms (a) To earth Breaking capacity at rated voltage (a) symmetrical Current density Moving Blade Terminal Pad Contacts Terminal connector Breaking capacity of capacitive current Rated inductive current switching capacity Rated inductive current switching capacity Permissible 1 second short-time current Dynamic short-time current Auxiliary Supplies DC AC No of spare auxiliary contacts Disconnector Earthing switched (state) (state) Air kV kV Hz Amps (state) (state) kV kV kV peak kA rms kA rms A/sq.mm A/sq.mm A/sq.mm A/sq.mm (state) (state) (state) kA rms kA peak V V KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 198 of 270 199 SECTION V: TECHNICAL SPECIFICATIONS SHEDULE 1a: TECHNICIAL GUARANTEES, OUTDOOR SWITCHGEAR OUTDOOR SWITCHGEAR ITEM PARTICULAR Disconnector (Type___________) continued Auxiliary contacts’ current rating Motor rating Level of galvanization Padlocking facility in both open and closed position Tolerance (DC) Degree of Protection for Control Box Thickness of sliver coating Creepage distance Operation Local (manual) Local ( motorized) Remote (motorized) Interlocking with breaker (electrical / mechanical) Interlocking with earth switch (Mechanical) Position indication on control box Clearances Between phase Between phase and ground Type of break Any special assembly tool UNIT 132 kV GUARANTEED FIGURE Amps Amps (state) µ mm (state) (state) (state) mm Mm (state) (state) KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 199 of 270 200 SECTION V: TECHNICAL SPECIFICATIONS SHEDULE -1b INFORMATVE DATA OUTDOOR SWITCHGEAR ITEM PARTICULAR UNIT Circuit Breaker B1 Reference standard Type of breaker and designation mV Voltage drop across main contacts at rated current mm Type of main contact m/s Type of arc control device Method of closing Method of tripping Max. percentage of recovery voltage % across any break Mm Minimum clearance between live parts and earth, in SF6 or vacuum Min distance between phases Number of opening operations Permissible before inspection and maintenance of contacts, gas treatment etc. At rated current At maximum short circuit current For SF6 breakers Normal gas density for SF6 circuit breaker (represented by gas pressure) At 200C Bar At 400C Bar Minimum gas density for safe operation At 200C Bar AT 400C Bar Quantity of gas required per 3-pole Kg breaker Bar Operating pressure of relief device Method of monitoring pressure and temperature compensation 0C Max. permissible dew point temperature Max. permissible acidity level %/year Max. permissible leak rate For vacuum breakers torr Vacuum in break chamber % Max. permissible leak rate DATA KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV TOLERANCE Page 200 of 270 201 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 1b : INFORMATIVE DATA OUTDOOR SWITCHGEAR ITEM PARTICULAR UNIT Circuit Breaker (Continued) For all breakers V DC Control voltage Type of operating device Motor voltage AC of DC Max. permissible service V voltage (a) Min. service voltage V Starting current of motor Power consumption of motor When starting W When running W Power consumption of B2 Closing coil Trip coil Heater Auxiliary switch Rupturing current at 110 V DC Number of free NO contact Number of free NO contact Test voltage 50Hz, 1 min. Manufacturer’s of Support insulators Breakers insulators Operating mechanism NOTE Indication to the characteristics listed above, the following information shall be given for all switchgear: Layout and overall dimensions drawings descriptions Earthing Switches Reference standard Type of isolating switch Min creepage distance (live part to earth) Min. isolating distance (clearance between open contacts) Materials of contract surface Total contact pressure Type of operating device Weight of earthing switch DATA TOLERANCE W W W A V mm mm KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 201 of 270 202 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE -1b INFORMATIVE DATA, OUTDOOR SWITCHGEAR ITEM PRARTICULAR UNIT B3 Current Transformers Reference standard Type designation Overall dimensions kg Total weight of one current transformer Type of insulation B4 Voltage Transformers Reference standard Type designation Overall dimensions Total weight of one current transformer Type of insulation DATA TOLERANCE kg KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 202 of 270 203 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE -2a TECHNICAL GUARANTEES, CONTROL SYSTEM SUB-STATION CONTROL SYSTEM (SCS) ITEM PARTICULAR UNIT a.1 GUARANTED FIGURE Control system response and update time under ‘moderate load’ conditions The control system shall be designed to yield the following response and update time under ‘moderate load’ conditions:Time taken to complete refresh data held with the SCS: (a) Maximum (b) Average s s Time taken to carry out a complete status check of all indications and alarms (a) Maximum (b) Average The time between selection and display of a VDU diagram fully updated from the existing main computer data base shall not exceed The time between selection of a control function and check back shall not exceed The time between execution of a control function and successful completion being displayed at the Operation Workshop shall not exceed for (a) Circuit breaker (operating time = 250 ms) (b) Isolator (operating time=10s) The time between the occurrence of the first change of state/alarm and display at the Operators Workstation shall not exceed The time between selecting display of analogue measurements and the corresponding value in the database being displayed shall not exceed The time between successive updates of the data base with analogue measurements shall not exceed (a) Network MW measurements (b) Other analogue measurements Equipment Reliability Mean time between failure shall be not less that: Each computer VDC Logging printer System console Communication system - a.2 s s s s s s s s s s s h h h h h KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 203 of 270 204 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 2b INFORMATION DATA, CONTROL SYSTEM ITEM b.1 b.2 DESPRIPTION General System Considerations Soft ware Package Which RTU communication protocols are supported Real-time database Package Is an SOL interface supported Database Management Tool Package State type of man-machine interface software Operator Workstation Reference standards Type designation Weight Mounting arrangement VDU Reference standard Type designation Diagonal screen size Usable display area Weight Mounting arrangement Alphanumeric Keyboard Reference standard Type designation Mounting arrangement UNIT DATA kg mm Max.mm kg KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 204 of 270 205 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 3a TECHNICAL GUARANTEES, PROTECTION ETC CONTROL, PROTECTION, METERING, SIGNALLING ITEM PARTICULARS UNIT GUARANTED FIGURE Indicating Instruments a.1 - a.2 a.3 a.4(a) Meters To be filled in for each AC and DC Ampere meter and Voltmeter and for each Wattmeter, VAr-meter, Frequency-meter and other indicating instruments :Instrument for: (A,V (AV), V (DC), W, etc Error Max. admissible current Max. admissible voltage % %.1N %1N To be filled in for each meter Meter for (MWh, MVArch: Error with 5% load Error with 10% load Error with 20% load Error with 100% load % % % % Max. admissible current Metering Converters (Transducers) Converter for (MW, MVAr, A, etc: Error Linearity Max. admissible current continuously Max. admissible voltage for 0.5 seconds Max. admissible current continuously Protection Relays To be copied and filled in for each type of relay as applicable. Relay for ___________________________ Accuracy of the adjustable tripping time Min. possible tripping time Drop out ratio Directional sensitivity (dist, relay only) Max. admissible current during 0.5 sec Max admissible current continuously Relation between tripping coil current and holding coil current (diff. relay only) Limit value of the adjustable tripping current (O.C.R.) Limit value of the instantaneous tripping current (O.C.R.) TOLERANCE %1N % % %1N %1N %1N sec ms % %.UN %1N %1N % %1N %1N KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 205 of 270 206 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 3a TECHNICAL GUARANTEES, PROTECTION ETC CONTROL, PROTECTION, METERING, SIGNALLING ITEM PARTICULARS UNIT GUARANTEED FIGURE Limit value of the adjustable tripping %1N voltage (O.C.R.) Limit value of the instantaneous tripping voltage (O.C.R) Protection Relays To be copied and filled in for each type of relay as applicable. Relay for Accuracy of the adjustable tripping time Min. possible tripping time Drop out ratio Directional sensitivity (dist, relay only) Max. admissible current during 0.5 sec Max admissible current continuously Relation between tripping coil current and holding coil current (diff. relay only) Limit value of the adjustable tripping current (O.C.R.) Limit value of the instantaneous tripping current (O.C.R.) Limit value of the adjustable tripping voltage (O.C.R.) Limit value of the instantaneous tripping voltage (O.C.R) Auxiliary Circuit Breaker To be filled in for each type of AC and DC breaker: Min. operating voltage Max. operating voltage Drop out voltage Service life (min, number of contact operation) Manufacturer’s Name Control room boards Local relay boards Protection relays Auxiliary contactors Country of Manufacture Control room boards Local relay boards Protection relays Auxiliary contactors - a.4(b) a.5 a.6 a.7 TOLERANCE %1N sec ms % %.UN %1N %1N % %1N %1N %1N %1N %UN %UN V KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 206 of 270 207 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 3b INFORMATION DATA, PROTECTION ETC CONTROL, PROTECTION, METERING, SIGNALLING ITEM PARTICULARS UNIT b.1 Indicating Instruments To be filled in for each type of instrument: Reference standard Type (moving coil, iron type, etc.) b.2 b.3 b.4 b.5 Consumption of internal resistance Size Meters To be filled in for each type of meter Reference standard Type Consumption of internal resistance Size Metering Converters (Transducers) To be filled in for each type for converter Reference standard Type Consumption current Consumption, voltage Time constant Size Alarm Annunciators Reference standard Type Number of annunicators Size of each annunicator (areas of the cap) Total size of panel Control Room Board Height Width Length Relay board Height width Length DATA TOLETRANCE VA/ohm mm VA/ohm mm VA VA Ms mm mm mm mm mm mm KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 207 of 270 208 SECTION V: TECHNICAL SPECIFICATIONS SHEDULE 3b INFORMATIVE DATA, PROTECTION ETC CONTROL, PROTECTION, METERING, SIGNALLING ITEM PARTICULARS UNIT b.6a Protection Relays To be copied and filled in for each relay with the applicable items of the data below: Relay for ________________________ Reference standard VA Consumption Sec Limit values of the adjustable tripping time % Limit values of adjustable sensitivity % Limit values of adjustable operating quantity (current, voltage, frequency, etc.) in % normal % Limit values of the instantaneous operating quintet in % of nominal value mm Size For distance relay only:ohm/ph Starting impendence adjustable between x.1N Earth fault tripping current adjustable between b.6b Protection Relays To be copied and filled in for each relay with the applicable items of the data below: Relay for ________________________ Reference standard VA Consumption Sec Limit values of the adjustable tripping time % Limit values of adjustable sensitivity % Limit values of adjustable operating quantity (current, voltage, frequency, etc.) in % normal % Limit values of the instantaneous operating quintet in % of nominal value mm Size For distance relay only:ohm/ph Starting impendence adjustable between x.1N Earth fault tripping current adjustable between DATA TOLETRANCE KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 208 of 270 209 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 4a INFORMATION DATA, CABLES POWER CABLES, CONTROL CABLES, CABLE RACKS ITEM PARTICULAR UNIT a.1 a.2 a.3 Low Voltage Cables Conductor material Insulation material Armouring/screen Protective coating Overall diameter of cable of biggest cable Weight of heaviest reek, including cable Size of biggest reel, diameter/width Control and Measuring Cables Conductor material Insulation material Armouring/screen Protective coating Overall diameter of cable of biggest cable Weight of heaviest reel, including cable Size of biggest reel, diameter/width Special Cables To be used for: Relevant informative data DATA TOLERANCE mm kg mm/mm mm kg mm/mm KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 209 of 270 210 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 4a INFORMATION DATA, CABLES POWER CABLES, CONTROL CABLES, CABLE RACKS ITEM PARTICULAR UNIT 11 KV Voltage Cables a.1 Conductor material Insulation material Armouring/screen Protective coating Overall diameter of cable of biggest mm cable kg Weight of heaviest reel, including cable mm/mm Size of biggest reel, diameter/width 132 KV Voltage Cables a.2 Conductor material Insulation material Armouring/screen Protective coating Overall diameter of cable of biggest mm cable kg Weight of heaviest reel, including cable mm/mm Size of biggest reel, diameter/width Special cables, optical fibre a.3 Relevant informative data DATA KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV TOLERANCE Page 210 of 270 211 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 5a TECHNICAL GUARANTEES, EARTHING EARTHING SYSTEM ITEM PARTICULARS UNIT a.1 GUARANTEED FIGURE TOLERANCE Resistance to Earth of Earthing Electrode system - Under the control building max. ohms Nil - Under the switchyard max. ohms Nil - Complete earthing system ohms Nil KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 211 of 270 212 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 5b TECHNICAL GUARANTEES, EARTHING EARTHING SYSTEM ITEM PARTI CULARS UNIT b1 - Reference standard - Material of earth conductor - Max temp of any earth conductor during 1 sec. rated phase – ground fault - Method of interconnecting earth grid conductors GUARANTEED FIGURE KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV TOLERANCE Page 212 of 270 213 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 1. 2. 3. 4. Continuous maximum rating on any tapping when operation under the ambient conditions specified in() With ONAN cooling: HV winding LV winding TV winding MVA MVA MVA With ONAF cooling: HV winding LV winding TV winding Rated frequency MVA MVA MVA Hz Rated no-load voltage at rated frequency on: HV, principal tapping HV, extreme plus tapping HV, extreme plus tapping LV, TV kV kV kV kV kV Tapping ranges from principal tapping: HV, no. of plus tappings HV, no of minus tappings HV, steps in % of rated voltage % 5. No-load losses at rated voltage and frequency 6. No-load current at rated voltage and frequency kW KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 213 of 270 214 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 7. Load losses at 750C at rated current, the third winding being open: HV – LV , ONAN HV – TV, ONAN LV – TV, ONAN HV - TV , ONAF HV – TV, ONAF LV – TV ONAF kW kW kW kW kW kW 8. Cooling plants power consumption kW 9 Total losses at 750C on principal tapping and unity power factor and rated currents: ONAN ONAF including input to cooling plant 10. - kW kW Impedance voltage at 750 refereed to mutual capacities at rated frequency and 100% rating. Principal tapping: HV – LV , ONAN HV – TV, ONAN LV – TV, ONAN HV - TV , ONAF HV – TV, ONAF LV – TV ONAF % % % % % % - KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 214 of 270 215 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA Extreme plus tapping HV – LV , ONAN HV – TV, ONAN LV – TV, ONAN HV - TV , ONAF HV – TV, ONAF LV – TV ONAF % % % % % % - % % % % % % - Extreme minus tapping: HV – LV , ONAN HV – TV, ONAN LV – TV, ONAN HV - TV , ONAF HV – TV, ONAF LV – TV ONAF 11. Temperature rise after continuous operation with rated MVA, under the ambient conditions specified and the rated conditions giving the highest losses: Top oil (by thermometer) Winding (by resistance) 12 0C 0C Efficiency on principal tapping max. temperature of winding and unity power factor and TV winding open. -120% load, ONAN -100% load, ONAN -50% load, ONAN -120% load, ONAF -100% load, ONAF -50% load, ONAF % % % % % % KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 215 of 270 216 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 13. Inherent voltage regulation on principal tapping, 750C and unity power factor: - 14. TV winding open 80% of full load on LV winding and 20% on TV winding % % Inherent voltage regulation on principal tapping, 750C and 0.8 factor lagging: - TV winding open 80% of full load on LV winding and 20% on TV winding % % 15. Vector group - 16. No. of phases per transformer - 17 Type of cooling - 18. Whether star connected windings shall be fully insulated or graded - 19. - Insulation levels of star points - 20. HV winding LV winding HV winding LV winding kV kV Method of system earthing: - HV system LV system KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 216 of 270 217 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 21. Method of transformer earthing: - 22. HV windings – star point LV windings – star point TV winding – one corner or closed delta - Whether TV windings are to be brought out to separate bushing insulators - 23. Indoor or outdoor installation - 24. System highest voltage according to IEC: -HV -LV -TV 25. Maximum flux density at rated voltage on principal tapping and rated frequency: - 26 Transformer legs Transformer yokes T T Maximum flux density at most onerous voltage and frequency conditions: - 27. kV kV kV Transformer legs Transformer yokes Specific core loss T T W/kg KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 217 of 270 218 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 28. Maximum current density in winding at rated output: HV, higher voltage, ONAN HV, lower voltage, ONAF LV, ONAN LV, ONAF TV, ONAN TV, ONAF A/mm2 A/mm2 A/mm2 A/mm2 A/mm2 A/mm2 29. Magnetising current at rated nominal voltage on principal tapping A 30. Maximum hot spot temperature of winding 0C 31. Equivalent resistance referred to HV side ohms 32. Equivalent reactance referred to HV side ohms 33. Maximum current carrying capacity of bushings: HV LV TV 34 A A A Rated service voltage of bushing: HV LV TV HV, neutral LV, neutral kV kV kV kV kV KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 218 of 270 219 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6a – TECHNICAL GUARANTEES, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 35. I minute, 50Hz dry withstand voltage: HV bushing LV bushing TV bushing HV, LV neutral bushings 36 I minute, 50Hz wet withstand voltage: HV bushing LV bushing TV bushing HV, LV neutral bushings 37. kV kV kV kV Impulse withstand voltage: HV bushing LV bushing 38. kV kV kV kV kV kV Maximum noise level - Transformer and tap changing equipment energized and at no-load with ONAN dB - Transformer and tap changing equipment energized and at no-load with ONAF (fan running) dB KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 219 of 270 220 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 1. Type of transformer (core or shell type) - 2. Number of core leg - 3. Type of windings: HV LV TV 4. 5. Type of insulation: HV, winding LV, winding TV, winding - Tappings Tappings connection Core bolts (if any) Core bolt washers (if any) Core lamination designation Specific core loss w/cm3 Type of axial coil supports: HV, winding LV, winding TV, winding 6. - - Winding conductor material HV LV 7. Type of joints in the magnetic core (butt type, interleaved etc.) 8. Calculated thermal time constant: ONAN ONAF - Hours hours KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 220 of 270 221 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 9. Type of bushing: HV LV TV HV, LV neutral 10. Principal bushing insulator material: HV LV TV HV, LV neutral 11. mm mm Protected leakage distance over porcelain externally (900 shadow). HV bushing LV bushing 13. - Total creepage distance over porcelain externally: HV bushing LV bushing 12. - mm mm Thickness of transformer tank: Sides Bottom Top mm mm mm 14. Thickness of radiator plates mm 15. Number of radiators per transformer - KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 221 of 270 222 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 16. On-load lap changer: Type (resistor type, reactor type, etc.) Total number of tappings including principal rated current of: - Selector switch Diverter switch Resistors A A A Maximum overcurrent of: Selector switch Diverter switch Resistors Driving motor input A A A kW Type of driving motor (3-phase etc) - Motoring contact: Closing time in advance of parting of diverter switch. Opening time after diverter switch contact have fully opened Diverter switch opening time sec Time from ‘point of no return’ to parting of diverter switch contact. sec Whether outdoor cabinets/kiosks are provided with heaters. - - 17. Sec Sec KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 222 of 270 223 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 18. Forced air cooling system: State if fans are blowing directly on radiators - Total number of fan units per transformer - Cooling capacity of each complete cooling system kW 19 Total oil quantity in completely filled transformer kp 20 Total weight of oil in completely filled transformer 1 21 Total oil quantity in conservator 1 22 Total quantity of oil conservator between highest and lowest level 1 23 Volume of conservator tank 1 24 Weight of copper in winding kg 25 Weight of core/winding assembly kg 26 Weight of each radiator: Filled with oil Empty 27 kg kg Total weight of bushings HV LV kg/each kg/each KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 223 of 270 224 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 28. Total weight of complete transformer erected at site Tons 29 Weight of transformer as arranged for transport tons 30. Filling medium during transport - 31 Overall dimensions of transformer completely erected at site, including bushings, radiators Length Width Height 32 mm mm mm Overall dimensions of transformer arranged for transport: Length Width Height mm mm mm 33 Minimum lift of core/winding assembly incl. Lifting beam, slings. Etc. for untanking mm 34 Rated output per fan unit m3/min 35 Speed of fan motors rpm 36 Continuous rating of fan motors Hp 37 Starting current of fan motors A 38 Efficiency of fan motors % 39 Power factor for fan motors at rated output % KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 224 of 270 225 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 40 Materials in rating and diagram plates - 41 Are on-load tap changing equipment prepared for fully automatic operation - 42 Are on-load tap changing equipment prepared for local, remote control (control room) and supervisory (NCC) operation and indication - 43 Are on-load tap changing equipment prepared for fully automatic parallel operation with similar transformers - 44 Whether first filling of oil is included - 45 Whether tap changer cubicle and wiring cabinet are provided - 46 Whether winding, and top oil indicators are provided - 47 Whether cooling fans are automatically operated from the winding temperature indicators - 48 Whether pressure relief device is to be fitted - 49 Whether Buchholz relay is fitted - 50 Whether all internal cabling/wiring on transformer is supplied to form a complete self contained unit - KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 225 of 270 226 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 51 Are the following alarms/trip signals provided: Tap changer not operating, alarm Tap changer out of step, alarm Voltage transformer failure Fan failure, alarm Oil/gas flow transformers, alarm Oil/gas flow transformers, trip On load tap changer protective relay operated, trip Oil gauge low level, alarm Tap changer oil gauge level low , alarm Tap changer oil gauge level critical, trip Top oil temp. high, alarm Top oil temp. critical, trip Winding temp. high, alarm Winding temp, critical, trip 52 - Are the following temperature indicators provided: HV winding LV or common winding TV winding 53 - - Are the following oil level gauges provided: Main conservator tank On-load tap changer conservator tank - 54 Tap change indicator provided - 55 Tap change in progress indicator - - KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 226 of 270 227 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA , POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 56 Tap changer out of step indicator - 57 Potentiometer switch for remote/supervisory on-load tap changer position indicator - 58 Will all the tests specified in the technical specifications be adhered to? If deviations, please state underneath 59 State all Standards applied underneath: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 227 of 270 228 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 6b – INFORMATIVE DATA, POWER TRANSFORMERS HV POWER TRANSFORMER GUARANTEED DATA ITEM PARTICULAR UNIT 15 MVA 60 State identity of transformer manufacturer and all submanufactures including the parts manufactured below:Transformer Cooling equipment On-load tap changer Current transformer Bushings Core steel Oil Buchholz relay Breather Thermometer Other equipment to be listed by the Bidder: - KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 228 of 270 229 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 7a – TECHNICAL GUARANTEES, STATION TRANSFORMER STATION TRANSFORMER GUARANTEED DATA ITEM PARTICULARS UNIT 1 Continuous Maximum Rating C.M.R kVA 2 Normal voltage between phases at no load (a) H.V. (b) L.V. 3 Volts volts Tappings (a) Plus (b) Minus 4 11/0.4kV % % Performance Data at Sea Level, corrected at 75% (a) No load loss at normal primary voltage (b) No load loss at 10% primary over voltage (c) Load loss at C.M.R (d) Impedance volts at C.M.R. and normal ratio (e) Regulation at C.M.R. and unity power factor (f) Regulation at C.M.R. and 0.8 power factor (g) Max temperature rise at C.M.R: i) Top oil by thermometer ii) Average winding by resistance iii) ‘Hot Spot’ corresponding to (ii) watts watts watts % % % 0C KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 229 of 270 230 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE 7a – TECHNICAL GUARANTEES, STATION TRANSFORMER STATION TRANSFORMER GUARANTEED DATA ITEM PARTICULARS 5 Type of insulation used on winding UNIT 11/0.4kV (a) H.V. (b) L.V. 6 Lighting impulse Insulation level of: (a) H.V. winding (b) L.V winding (a) Tap change equipment and connections i) To earth ii) Between contacts 7 Are test certificate supplied supporting the level sated in Clause 6 8 Silica gel Breather kVpk kVpk kVpk kVpk Yes/No (a) Make of unit fitted (b) Size of Unit KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 230 of 270 231 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE -7b – INFORMATIVE DATA, STATION TRANSFORMER STATION TRANSFORMER GUARANTEED DATA ITEM 1 2 PARTICULARS UNIT 11/0.4kV Transformer type (sealed or breathing) Type of windings HV LV 3 Type of insulation HV winding LV winding 4 Type of tap changer 5 Tap changer designation 6 Type of axial coil supports HV winding LV winding 7 Winding conductor material HV winding LV winding 8 Core laminations designation - 9 Specific core loss w/cm3 10 Type of bushings HV LV KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 231 of 270 232 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE -7b – INFORMATIVE DATA, STATION TRANSFORMER STATION TRANSFORMER GUARANTEED DATA ITEM 11 PARTICULARS UNIT 11/0.4kV Bushing insulator material HV LV 12 Creepage distance across bushing HV LV 13 Type of cooling system 14 Total oil quantity 15 Total weight 16 Volume of conservator tank 17 Overall dimension Mm mm K 1 Length Width Height 18 State all standards applied underneath: 19 State identity of manufacturer underneath KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 232 of 270 233 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE -8a – GUARANTEED DATA TELECOMMUNICATION SYSTEM UHF LINK RADIOS TYPE _____________________________________________________ ITEM PARTICULAR UNIT 1 Output power W EMPLOYER’S REQUIREMENT 1-25 2 Sensitivity (12dB SINAD) µV 0.35 3 Frequency Range MHz 403 -420 4 Frequency stability ppm ±2 5 Channel spacing Hz 12.5/20/25 6 Channel capacity 7 Signalling standards CCIR. ZVEI and EEA 8 Mode of operation Simplex/semiduplex/duplex 9 Antenna connectors 10 Antenna impedance 11 Temperature range 0C -30 to + 60 12 Voltage (nominal) V DC 13-2 13 Designed for continuous-duty cycle operation Y/N 14 Power consumption @full power W 15 Power consumption, standby mode W 16 Mounting Ώ TENDER VALUE 50 N-female Rack or wallmounting bracket KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 233 of 270 234 SECTION V: TECHNICAL SPECIFICATIONS SCHEDULE -8b – GUARANTEED DATA TELECOMMUNICATION SYSTEM UHF LINK ANTENNA TYPE _____________________________________________________ ITEM PARTICULAR UNIT EMPLOYER’S REQUIREMENT 1 Antenna type 2 Frequency band (minimum) MHz 400-420 3 Impedance Ώ 50 4 Polarisation 5 Gain dBi Vertical or horizontal >10 6 Front to back ratio db >20 7 Half-power Beam Width, vertical Deg <40 8 Half-power Beam Width, Horizontal Deg <50 9 Bandwidth MHz >10 10 SWR 11 Max. power 12 Connection N-female 13 Mounting On 30-58mm tube 14 Wind survival rating m/s 15 Wind surface m2 16 Wind load @40 m/s N 17 Weight kg 18 Dimensions mm TENDER VALUE <1.5:1 W 150 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 234 of 270 235 SECTION VII: DRAWINGS SECTION VII: DRAWINGS SEE ATTACHED DRAWINGS All other Architectural, structural, mechanical and electrical drawings complete with their details shall be obtained from the Project Manager through the office of Principal Electrical Engineer Kenya Ports Authority. Any clarifications as regards the drawings and detailing should be channelled through the same office. No claims shall be entertained out of ignorance or misinterpretation of the drawings by the contractor. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 235 of 270 236 SECTION VII: DRAWINGS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 236 of 270 237 SECTION VII: DRAWINGS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 237 of 270 238 SECTION VII: DRAWINGS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 238 of 270 239 SECTION VII: DRAWINGS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 239 of 270 240 SECTION VII: DRAWINGS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 240 of 270 241 SECTION VIII: BILLS OF QUANTITIES SECTION VIII: BILLS OF QUANTITIES KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 241 of 270 242 SECTION VIII: BILLS OF QUANTITIES PRICE SCHEDULES ITEM 1 a b c d e f g h i j 2 a b c d e 3 a b c d e f g MATERIALS 132 kV Takeoff, Kipevu 132 KV cable sealing ends 132 KV circuit breakers 132 KV line isolators 132 KV surge arresters 132 KV voltage transformers 132 KV current transformers Substation structures Foundation and trench works Allow Pc Sum to be used in clearing KPLC switchyard of existing equipment Any other item to complete the installation (describe) Total, 132 kV Takeoff, Kipevu Cable, Kipevu to KPA (1.5km) 3 ×400mm² s/c XLPE copper cables(or appropriate cable as calculated by the contractor) 48 strand fibre optic cable Cable terminations Cable trench including back-filling and Hatari tiles Any other items(describe) Total, Cable, Kipevu to KPA KPLC metering at KPA 132 kV Isolator with Integral earth switch 132 kV isolator without earth switch 132 kV sure arresters 132 kV line traps 132 kV current transformers 132 kV Voltage transformers 132 kV circuit breaker QTY UNIT COST (currency ) UNIT COST (KSH) TOTAL (KSH) Country of origin 9 1 2 3 3 3 lot lot sum 2,200,000 1500M 1500M lot lot 1 1 3 2 3 3 1 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 242 of 270 243 SECTION VIII: BILLS OF QUANTITIES h i j K Switchgear connection cables including terminations and accessories Allow PC sum for design detailing and technical coordination with KPLC Training for 3 KPA engineers and technicians Any other items (describe) lot 2,500,000 l Total, KPLC Metering at KPA ITEM 4 a b c d e f g h i j 5 a b c d e f g h KPA 132 KV yard 132 kV isolator with earth switch 132 kV isolator without earth switch 132 kV circuit breakers 132 kV current transformers 132 kV voltage transformers 132 kV busbars 132 kV surge arresters(tx protection) 15MVA 132/11 kV power transformers Switchgear connection cables including terminations and accessories Any other items (describe) Total, 132kV at Switchyard 11 KV unit (KPA) 2000A 11kV busbars 1500A 11kV circuit breakers(busbar incomers) 11kV bus coupler 630A 11kV circuit breakers(Feeders) 1500A 11kV circuit breaker(substation M feeder) 11kV voltage transformer(metering) 200kVA 11kV/433 V station transformer 2 × 300mm² 4c XLPE copper cables(or QTY UNIT COST (currency) UNIT COST (KSH) TOTAL (KSH) Country of origin 2 2 3 6 3 set 6 2 lot set 2 1 5 1 2 1 100M KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 243 of 270 244 SECTION VIII: BILLS OF QUANTITIES i j k l appropriate cable as calculated by the contractor) to link to existing substation M. 100 m of 240 sq mm 4- core cable at 415 volts complete with changeover panel and connection for emergency power from generator at Substation M to new subststion Allow PC sum for works in substation M to accommodate the incoming feed Training for 3 KPA Technicians and Engineers Any other items (describe) Lot Sum 5,000,000. Total 11kV Switchgear 6 a b c Control Panels Control panel for 132 kV switchgear as described in the technical specifications Control panels for 11kV switchgear as described in the technical specifications Any other items Total, Control Panels lot lot KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 244 of 270 245 SECTION VIII: BILLS OF QUANTITIES ITEM 7 a b c d 8 a b c 9 Protection relays Protection relays for 132kV switchgear as described in the technical specifications Protection relays for the 11kV switchgear as described in the technical specifications Training for 3 KPA engineers and technicians Any other items Total, Protective Relays Communication Communication equipment including SCADA system equipment as described in the technical specifications Allow PC sum for interconnection to existing SCADA, including necessary interface and rehabilitation Training for 2 KPA engineers Total Communication All the necessary substation steel structures, including lightning protection and communication towers QTY UNIT COST (currency ) UNIT COST (KSH) TOTAL (KSH) Country of origin lot lot lot 25,000,000.00 lot KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 245 of 270 246 SECTION VIII: BILLS OF QUANTITIES 10 a b c 11 CIVIL WORKS AND PERMITS All civil works, including substation building, Structural foundations, cable channels, roads, fencing, lighting Allow PC sum for permits and licensing from Municipal and other statutory authorities including NEMA Allow PC sum for clerk of works, and transport for resident engineer Total civil works All the necessary cables including control and communication cables Total Cables lot 3,000,000.00 2,800,000 lot KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 246 of 270 247 SECTION VIII: BILLS OF QUANTITIES ITEM 12 i ii iii iv v vi vii viii ix x xi xii xiii xiv 13 i ii iii iv v vi Spares Spares for 11 KV switchgear 630A feeder circuit breakers 1500A incoming circuit breaker Circuit breaker charging motors Circuit breaker closing coils Circuit breaker tripping coils Circuit breaker interlocking coils Earth switch interlocking coils Indicating lamps(each type) Auxiliary relays (each type) Protection relays (each type) MCBs of each type Power measurement units Energy meter VT fuses (3 for primary & 3 for secondary side) Spares for 132KV switchgear 132 KV circuit breaker(complete unit) 132 KV voltage transformer (single phase unit) 132 KV current transformer (single phase units) 132 KV line isolator with earth switch 132 KV line isolator without earth switch OTHER SPARES NECESSARY QTY UNIT COST (currency ) UNIT COST (KSH) TOTAL (KSH) Country of origin 2 1 2 3 3 2 2 10 2 2 4 2 2 6 1 3 3 1 1 vii viii ix x KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 247 of 270 248 SECTION VIII: BILLS OF QUANTITIES SUMMARY ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TOTAL (currency ) TOTAL (KSH) Country of origin 132 kV Takeoff, Kipevu Cable, Kipevu to KPA (1.5km) KPLC metering at KPA KPA 132 kV yard 11 kV unit (KPA) Total, Control Panels Total, Protective Relays Total Communication Substation steel structures Total civil works Total Cables Spares for 11 kV switchgear Spares for 132kV switchgear Allow 10% contingency to be used at the discretion of the Engineer Total carried forward to Form of Tender Authorized Official: ____________________________ Name ______________________ Signature Date____________________ KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 248 of 270 SECTION IX: 249 TENDER FORMS SECTION IX: TENDER FORMS KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 249 of 270 SECTION IX: 250 TENDER FORMS A. Form of Tender [date] To: To: [name and address of Procuring Entity] Sir/Madam: Having examined the Tender documents including Addenda Nos. [insert addenda numbers], the receipt of which is hereby duly acknowledged, we, the undersigned, offer to supply, “UPGRADING OF INCOMING POWER FROM 11KV TO 132KV SUPPLY, INSTALLATION AND COMMISSIONING OF 132KV/11KV SUBSTATION AND ASSOCIATED EQUIPMENT” in conformity with the said Tender documents for the sum of ______________________________________________[total Tender amount in words and figures] or such other sums as may be ascertained in accordance with the Schedule of Prices attached herewith and made part of this Tender. We undertake, if our Tender is accepted, to Execute the works in accordance with the delivery schedule specified in the Schedule of Requirements. If our Tender is accepted, we undertake to provide a performance security in the form, in the amounts, and within the times specified in the Tender documents. We agree to abide by this Tender for the Tender validity period specified in Clause 18.1 of the Tender Data Sheet, and it shall remain binding upon us and may be accepted at any time before the expiration of that period. We are not participating, as Tenderers, in more than one Tender in this Tendering process. Our firm, its affiliates or subsidiaries – including any subcontractors or suppliers for any part of the contract – has not been declared ineligible by the Government of Kenya under Kenyan laws. Until a formal Contract is prepared and executed, this Tender, together with your written acceptance thereof and your notification of award, shall constitute a binding Contract between us. We understand that you are not bound to accept the lowest or any Tender you may receive. We certify/confirm that we comply with the eligibility requirements as per ITT Clause 3 of the Tender documents Dated this ________________ day of ________________ 20______. (Name) _________________ [Signature] __________________________ [In the capacity of Duly authorized to sign Tender for and on behalf of ______________________________ Authorized Signature: Name and Title of Signatory: Name of Tenderer: Address: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 250 of 270 SECTION IX: 251 TENDER FORMS Appendix to Tender Schedule of Adjustment Data [In Tables A, B, and C, below, the Tenderer shall (a) indicate its amount of local currency payment, (b) indicate its proposed source and base values of indices for the different foreign currency elements of cost, (c) derive its proposed weightings for local and foreign currency payment, and (d) list the exchange rates used in the currency conversion. Table A. Local Currency Index code Index Source descriptio of index n Nonadjustable — Base value and date — Tenderer Range of Tenderer’s ’s related weighting proposed currency Proposed by the weighting amount Procuring Entity — a: * a: * b: ------ to -------- b: * c: c: ------- to ------* d: d: ------- to ------- e: * e: ------- to ------* etc. etc. Total KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV 1.00 Page 251 of 270 SECTION IX: 252 TENDER FORMS Table B. Foreign Currency State type: ....................... [If the Tenderer wishes to quote in more than one foreign currency, this table should be repeated for each foreign currency.] Index code Index description Source of index Base value and date Non adjustable — — Tenderer’s Equivale Range of Tenderer’s related nt in weighting proposed source Foreign Proposed by weighting currency Currency the in type/ 1 Procuring amount Entity — a: * a: b: ------ to -- * ------* b: c: ------- to ------* c: d: ------- to - d: ------* e: e: ------- to ------* etc. etc. Total 1.00 Table C. Summary of Payment Currencies For ………………………..[insert name of Section of the Works] [Separate tables may be required if the various sections of the Works (or of the Bill of Quantities) will have substantially different foreign and local currency requirements. The Procuring Entity should insert the names of each Section of the Works.] Name of payment currency Local currency A B C Amount Rate of Local currency of exchange equivalent currency (local currency C=AxB per unit of foreign) D Percentage of Net Tender Price (NBP) 100xC NBP 1.00 Foreign currency #1 Foreign currency #2 KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 252 of 270 SECTION IX: 253 TENDER FORMS Foreign currency # Net Tender Price Provisional sums expressed in local currency 100.00 * * * TENDER PRICE Authorized Signature: Name and Title of Signatory: Name of Tenderer: Address: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 253 of 270 SECTION IX: 254 TENDER FORMS B. Tender-Securing Declaration (Mandatory) Date: [insert date (as day, month and year)] Tender No.: [insert number of Tendering process] To: [insert complete name of Procuring Entity] We, the undersigned, declare that: We understand that, according to your conditions, Tenders must be supported by a TenderSecuring Declaration. We accept that we will automatically be suspended from being eligible for Tendering in any contract with the Procuring Entity for the period of time of [insert number of months or years] starting on [insert date], if we are in breach of our obligation(s) under the Tender conditions, because we; a) Have withdrawn our Tender during the period of Tender validity specified in the Form of Tender; or b) Having been notified of the acceptance of our Tender by the Procuring Entity during the period of Tender validity, (i). (ii). Fail or refuse to execute the Contract, if required, or Fail or refuse to furnish the Performance Security, in accordance with the ITT. We understand this Tender Securing Declaration shall expire if we are not the successful Tenderer, upon the earlier of; 1) Our receipt of your notification to us of the name of the successful Tenderer; or 2) Thirty days after the expiration of our Tender. Signed: [insert signature of person whose name and capacity are shown] In the capacity of [insert legal capacity of person signing the Tender Securing Declaration] Name: [insert complete name of person signing the Tender Securing Declaration] Duly authorized to sign the Tender for and on behalf of: [insert complete name of Tenderer] Dated on ____________ day of __________________, _______ [insert date of signing] Corporate Seal (where appropriate) KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 254 of 270 SECTION IX: 255 TENDER FORMS C. Confidential Business Questionnaire 1 Individual Tenderer or Individual Members of joint Ventures 1.1 Constitution or legal status of Tenderer: [attach copy] Place of registration: [insert] Principal place of business: [insert] Power of attorney of signatory of Tender: [attach] Registration certificate [attach] current Business License [attach] Similar works Project name and country 1.2 Total annual volume of construction work performed in two years, in Kenyan shillings /USD as specified in the Tender Data Sheet; [insert] 1.3 Work performed as prime Contractor on works of a similar nature and volume over the last two years or as specified in the Tender Data Sheet in Kenyan Shillings. Also list details of work under way or committed, including expected completion dates. Name of client and contact person Contractors Participation Type of work performed and year of completion Value of contract (a) (b) 1.4 Item of equipment Major items of Contractor’s Equipment proposed for carrying out the works. List all information requested below. Refer also to sub-Clause 12.3 of the Instructions to Tenderers. Description, make, and age (years) Condition (new, good, Poor) and number available Owned, leased (from whom?) or to be purchased (from whom?) (a) (b) (c) (d) Qualification and experience of key personnel 1.5 Qualifications and experience of key personnel proposed for administration and execution of the Contract. Attach biographical data. Refer also to sub-Clause 12.3 of the Instructions to Tenderers and Sub- Clause 10.1 of the General Conditions of Contract. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 255 of 270 SECTION IX: Position 256 TENDER FORMS Name Years of Experience (general) Years of experience in proposed position (a) (b) Use format of CV attached 1.6 Sections of the Works Proposed sub-contractor and firms involved. Clause 7 of General Conditions of Contract. Value of subcontract Subcontractor (name and address) Refer to Experience in similar work (a) (b) Litigation History 1.7 Financial reports for the number of years specified in the Tender Data Sheet. 1.8 Evidence of access to financial resources to meet the qualification requirements: cash in hand, lines of credit, etc. List below and attach copies of support documents. 1.9 Name, address, and telephone, e-mail address, and facsimile numbers of banks that may provide references if contracted by the Procuring Entity. 1.10 Information on current litigation in which the Tenderer is involved. Other party(ies) (a) Cause of dispute Amount involved (b) 1.11 Statement of compliance with the requirements of sub-Clause 3.2 of the Instructions to Tenderers. 1.12 Proposed Program (work method and schedule). Descriptions, drawings, and charts, as necessary, to comply with the requirements of the Tendering documents. 2. Joint Ventures 2.1 The information listed in 1.1 – 1.11 above shall be provided for each partner of the joint venture. 2.2 The information in 1.12 above shall be provided for the joint venture. 2.3 Attach the power of attorney of the signatory (ies) of KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 256 of 270 SECTION IX: 257 TENDER FORMS the Tender authorizing signature of the Tender on behalf of the joint venture. 2.4 3. Additional Requirements 3.1 Attach the Agreement among all partners of the joint venture (and which is legally binding on all partners), which shows that: (a) all partners shall be jointly and severally liable for the execution of the Contract in accordance with the Contract terms; (b) one of the partners will be nominated as being in charge, authorized to incur liabilities, and receive instructions for and on behalf of any and all partners of the joint venture; and (c) the execution of the entire Contract, including payment, shall be done exclusively with the partner in charge. Tenderers should provide any additional information required in the Tender Data Sheet or to fulfil the requirements of sub-Clauses 12.1 of the Instructions to Tenderers, if applicable. We, the undersigned declare that (a) The information contained in and attached to this form is true and accurate as of the date of Tender submission Authorized Signature: Name and Title of Signatory: Name of Tenderer: Address: Company Stamp / seal ____________________________ KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 257 of 270 SECTION IX: 258 TENDER FORMS Integrity Declaration UNDERTAKING BY TENDERER ON ANTI – BRIBERY POLICY / CODE OF CONDUCT AND COMPLIANCE PROGRAMME 1. Each Tenderer must submit a statement, as part of the Tender documents, in either of the two given formats which must be signed personally by the Chief Executive Officer or other appropriate senior corporate officer of the Tendering company and, where relevant, of its subsidiary in the Kenya. If a Tender is submitted by a subsidiary, a statement to this effect will also be required of the parent company, signed by its Chief Executive Officer or other appropriate senior corporate officer. 2. Tenderers will also be required to submit similar No-bribery commitments from their subcontractors and consortium partners; the Tenderer may cover the subcontractors and consortium partners in its own statement, provided the Tenderer assumes full responsibility. 3. a) Payment to agents and other third parties shall be limited to appropriate compensation for legitimate services. b) Each Tenderer will make full disclosure in the Tender documentation of the beneficiaries and amounts of all payments made, or intended to be made, to agents or other third parties (including political parties or electoral candidates) relating to the Tender and, if successful, the implementation of the contract. c) The successful Tenderer will also make full disclosure [quarterly or semiannually] of all payments to agents and other third parties during the execution of the contract. d) Within six months of the completion of the performance of the contract, the successful Tenderer will formally certify that no bribes or other illicit commissions have been paid. The final accounting shall include brief details of the goods and services provided that they are sufficient to establish the legitimacy of the payments made. e) Statements required according to subparagraphs (b) and (d) of this paragraph will have to be certified by the company's Chief Executive Officer, or other appropriate senior corporate officer. 4. Tenders which do not conform to these requirements shall not be considered. 5. If the successful Tenderer fails to comply with its No-bribery commitment, significant sanctions will apply. The sanctions may include all or any of the following: a) Cancellation of the contract; b) Liability for damages to the public authority and/or the unsuccessful competitors in the Tendering possibly in the form of a lump sum representing a pre-set percentage of the contract value (liquidated). 6. Tenderers shall make available, as part of their Tender, copies of their anti-Bribery Policy/Code of Conduct, if any, and of their-general or project - specific - Compliance Program. 7. The Government of Kenya has made special arrangements for adequate oversight of the procurement process and the execution of the contract, and has invited civil society and other competent Government Departments to participate in the oversight. Those charged with the oversight responsibility will have full access to all documentation submitted by Tenderers for this contract, and to which in turn all Tenderers and other parties involved or affected by the project shall have full access (provided, however, that no proprietary information concerning a Tenderer may be disclosed to another Tenderer or to the public). KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 258 of 270 SECTION IX: 259 TENDER FORMS ANTI-CORRUPTION DECLARATION COMITTMENT/ PLEDGE (Sections39, 40,41,42,43 & of the PPD Act, 2005) I/We/Messrs……………………………………………………………………………. of Street, Building, P O Box…………………………………………………………… ………………………………………………………………………………………….. Contact/Phone/E mail………………………………………………………………….. declare that Public Procurement is based on a free and fair competitive Tendering process which should not be open to abuse. I/We ..………………………………………………………………………………….. declare that I/We will not offer or facilitate, directly or indirectly, any inducement or reward to any public officer, their relations or business associates, in connection with Tender/Tender No ………………………..………………………………………………. for or in the subsequent performance of the contract if I/We am/are successful. Authorized Signature................................................................................................ Name and Title of Signatory…………………………………………………………… KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 259 of 270 SECTION IX: 260 TENDER FORMS D. Letter of Acceptance [Letter head paper of the Procuring Entity] [date] To: [name and address of the Contractor] This is to notify you that your Tender dated [date] for execution of the [name of the Contract and identification number, as given in the Contract Data Sheet] for the Contract Price of the equivalent of [amount in numbers and works] [name of currency], as corrected and modified in accordance with the Instructions to Tenderers is hereby accepted by us. We confirm that [insert name proposed by the procuring entity] to be the Adjudicator. We accept that [name proposed by Tenderer] be appointed as Adjudicator. Or We do not accept that [name proposed by Tenderer] be appointed as adjudicator, and by sending a copy of this letter of acceptance to [insert the name of the Appointing Authority], we are hereby requesting [name], the Appointing Authority, to appoint the adjudicator in accordance with Clause 44.1 of the Instructions to Tenderers. You are hereby instructed to proceed with the execution of the said works in accordance with the Contract documents. Please return the contract dully signed. Authorized Signature: Name and Title of Signatory: Name of Agency: Attachment: Form of Contract KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 260 of 270 SECTION IX: 261 TENDER FORMS E. Contract Data Sheet This Agreement, made the [day] day of [month], 2011] between [The Kenya Ports Authority] (hereinafter called “the Procuring Entity”) and [name and address of Contractor] (hereinafter called “the Contractor”) of the other part. Whereas the Procuring Entity is desirous that the Contractor execute [Upgrade of Incoming Power from 11kV to 132kV] (hereinafter called “the Works”) with the objectives of [insert functional objectives of the works] and the Procuring Entity has accepted the Tender by the Contractor for the execution and completion of such works and the remedying of any defects therein in the sum of [contract price in words and figures] (hereinafter called “Contract Price”). NOW THIS AGREEMENT WITNESSES AS FOLLOWS: 1. In this Agreement, words and expressions shall have the same meanings as are respectively assigned to them in the Conditions of Contract hereinafter referred to, and they shall be deemed to form and be read and construed as pert of this Agreement; 2. In consideration of the payments to be made by the Procuring Entity to the Contractor as hereinafter mentioned, the Contractor hereby covenants with the Procuring Entity to execute and complete the Works and remedy any defects therein in conformity in all respects with the provisions of the Contract; 3. The Procuring Entity hereby covenants to pay the Contractor in consideration of the execution and completion of the Works and the remedying of defects wherein the Contract Price or such other sum as may become payable under the provisions of the Contract at the times and in the manner prescribed by the Contract. In Witness whereof the parties thereto have caused this Agreement to be executed the day and year first before written. The Common Seal of Was hereunto affixed in the presence of: Signed, Sealed, and Delivered by the said In the presence of: Tendering Signature of Procuring Entity Binding Signature of Contractor KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 261 of 270 SECTION IX: 262 TENDER FORMS MANUFACTURER’S AUTHORIZATION FORM To Kenya Ports Authority [Name of the Procuring entity] …………………. WHEREAS …………………………………………………………[ name of the manufacturer] who are established and reputable manufacturers of ………………….. [Name and/or description of the goods] having factories at ………………………………… [Address of factory] do hereby authorize ………………………… [name and address of Agent] to submit a tender, and subsequently negotiate and sign the Contract with you against tender No. ………………………. [Reference of the Tender] for the above goods manufactured by us. We hereby extend our full guarantee and warranty as per the General Conditions of Contract for the goods offered for supply by the above firm against this Invitation for Tenders. ___________________________________________ [Signature for and on behalf of manufacturer] Date:_______________________ Note: This letter of authority should be on the letterhead of the Manufacturer and should be signed by an authorized person. KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 262 of 270 263 FORMAT OF CURRICULUM VITAE (CV) FOR PROPOSED PROFESSIONAL STAFF FORMAT OF CURRICULUM VITAE (CV) FOR PROPOSED PROFESSIONAL STAFF 1. Proposed Position [only one candidate shall be nominated for each position]: 2. Name of Staff member [insert full name]: 3. Date of Birth: Nationality: 4. Education [indicate college/university and other specialized education of expert, giving names of institutions, degrees obtained, and dates of obtainment]: 5. Membership in Professional Associations: 6. Other Trainings [indicate significant training since degrees under 5 - Education were obtained]: 7. Countries of Work Experience: [list countries where expert has worked in the last ten years]: 8. Languages [For each language indicate proficiency: good, fair, or poor in speaking, reading, and writing]: 9. Employment Record [Starting with present position, list in reverse order every employment held by expert since graduation, giving for each employment (see format here below): dates of employment, name of employing organization, positions held.]: From [Year]: To [Year]: Employer: Positions held: KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 263 of 270 264 FORMAT OF CURRICULUM VITAE (CV) FOR PROPOSED PROFESSIONAL STAFF 10.Detailed Tasks Assigned 11.Work Undertaken that Best Illustrates Capability to Handle the Tasks Assigned [Among the assignments in which the expert has been involved, indicate the following information for those assignments that best illustrate the expert’s capability to handle the tasks listed in line 11.] [List all tasks to be performed under this assignment] Name of assignment or project: Year: Location: Client: Main project features: Positions held: Activities performed: 12. Certification: I, the undersigned, certify to the best of my knowledge and belief that (i) this CV correctly describes my qualifications and my experience; (ii) In the absence of medical incapacity, I will undertake this assignment for the duration and in terms of the inputs specified for me in the Personnel Schedule in Form provided team mobilization takes place within the validity of this proposal or any agreed extension thereof; (iii) I am committed to undertake the assignment within the validity of Proposal; (iv) I am not part of the team who wrote the terms of reference for this consulting services assignment; I understand that any willful misstatement described herein may lead to my disqualification or dismissal, if engaged. Date: [Signature of expert or authorized representative of the firm]1 Day/Month/Year Full name of authorized representative: 1 This CV can be signed by an authorized representative of the Consultant provided that if the Consultant’s proposal is ranked first, a copy of the CV signed by the expert and/or specialist must be submitted to the Client prior to the commencement of contract negotiations IMPORTANT NOTE: Attach certified copies of academic certificate and Professional membership certificates KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 264 of 270 265 SECTION X: FORMS OF SECURITY SECTION X: FORMS OF SECURITY KPA/169/2010-11EE PROPOSED UPGRADING OF INCOMING POWER FROM 11KV TO 132 KV Page 265 of 270 266 SECTION X: FORMS OF SECURITY A. Tender Security Guarantee (MANDATORY) [the Bank shall fill in this Guarantee form in accordance with the instructions indicated in brackets.] [insert bank’s or insurance company’s name, and address of issuing branch or office] Beneficiary: [insert name and address of Procuring Entity] Date: [insert date] TENDER GUARANTEE No.: [insert number] We have been informed that [insert name of the Tenderer; if a joint venture, list complete legal names of partners] (hereinafter called "the Tenderer") has submitted to you its Tender dated [insert date] (hereinafter called "the Tender") for the execution of [insert name of Contract] under Invitation for Tenders No. [insert IFT number] (“the IFT”). Furthermore, we understand that, according to your conditions, Tenders must be supported by a Tender Guarantee. At the request of the Tenderer, we [insert name of bank or insurance company] hereby irrevocably undertake to pay you any sum or sums not exceeding in total an amount of [insert amount in figures expressed in the currency of the Purchaser’s Country or the equivalent amount in an international freely convertible currency] ([insert amount in words]) upon receipt by us of your first demand in writing accompanied by a written statement stating that the Tenderer is in breach of its obligation(s) under the Tender conditions, because the Tenderer; a) Has withdrawn its Tender during the period of Tender validity specified by the Tenderer in the Form of Tender; or b) Does not accept the correction of errors in accordance with the Instructions to Tenderers (hereinafter “the ITT”) of the IFT; or c) Having been notified of the acceptance of its Tender by the Procuring Entity during the period of Tender validity; (i). Fails or refuses to execute the Contract Form, if required, or (ii). Fails or refuses to furnish the Performance Security, in accordance with the ITT. This Guarantee shall expire; a) If the Tenderer is the successful Tenderer, upon our receipt of copies of the Contract signed by the Tenderer and of the Performance Security issued to you by the Tenderer; or b) If the Tenderer is not the successful Tenderer, upon the earlier of; (i) Our receipt of a copy of your notification to the Tenderer that the Tenderer was unsuccessful, or (ii) Thirty days after the expiration of the Tenderer’s Tender. Consequently, any demand for payment under this Guarantee must be received by us at the office on or before that date. _____________________________ [signature(s) of authorized representative(s) ] Page 266 267 SECTION X: FORMS OF SECURITY B. Performance Bank Guarantee [Unconditional] [The Bank or Insurance providing the Guarantee shall fill in this form in accordance with the instructions indicated in brackets, if the Procuring Entity requires this type of security.] [insert bank’s or insurance company’s name, and address of issuing branch or office] Beneficiary: [insert name and address of Procuring Entity] Date: [insert date] PERFORMANCE GUARANTEE No.: [insert Performance Guarantee number] We have been informed that [insert name of Contractor] (hereinafter called "the Contractor") has entered into Contract No. [insert reference number of the Contract] dated with you, for the execution of [insert name of Contract and brief description of Works] (hereinafter called "the Contract"). Furthermore, we understand that, according to the conditions of the Contract, a Performance Guarantee is required. At the request of the Contractor, we [insert name of Bank or Insurance Company] hereby irrevocably undertake to pay you any sum or sums not exceeding in total an amount of [insert amount in figures] ([insert amount in words]), such sum being payable in the types and proportions of currencies in which the Contract Price is payable, upon receipt by us of your first demand in writing accompanied by a written statement stating that the Contractor is in breach of its obligation(s) under the Contract, without your needing to prove or to show grounds for your demand or the sum specified therein. We hereby waive the necessity of your demanding the said debt from the Contractor before presenting us with the demand. We further agree that no change, addition or other modification of the terms of the Contract or of the Works to be performed there under or of any of the Contract documents which may be made between you and the Contractor shall in any way release us from any liability under this Guarantee, and we hereby waive notice of any change, addition, or modification. This guarantee shall expire not later than thirty days from the date of issuance of the Taking-Over Certificate. [signature(s) of an authorized representative(s) of the Bank or Insurance Company] Page 267 268 SECTION X: FORMS OF SECURITY C. Bank Guarantee for Advance Payment [Bank’s Name and Address of Issuing Branch or Office] Beneficiary: Date: ___________________ [Name and Address of Procuring Entity] ________________ ADVANCE PAYMENT GUARANTEE No.: _________________ We have been informed that [name of Contractor] (hereinafter called "the Contractor") has entered into Contract No. [reference number of the contract] dated ______ with you, for the execution of [name of contract and brief description of Works] (hereinafter called "the Contract"). Furthermore, we understand that, according to the conditions of the Contract, an advance payment in the sum [amount in figures] ( ) [amount in words] is to be made against an advance payment guarantee. At the request of the Contractor, we [name of Bank or Insurance Company] hereby irrevocably undertake to pay you any sum or sums not exceeding in total an amount of [amount in figures] ( ) [amount in words] upon receipt by us of your first demand in writing accompanied by a written statement stating that the Contractor is in breach of its obligation under the Contract because the Contractor used the advance payment for purposes other than the costs of mobilization in respect of the Works. We further agree that no change or addition to or other modification of the terms of the Contract or of the Works to be performed thereunder or of any of the Contract documents which may be made between ________________________[name of Procuring Entity] and the Contractor, shall in any way release us from any liability under this guarantee, and we hereby waive notice of any such change, addition or modification. No drawing may be made by you under this guarantee until we have received notice in writing from you that an advance payment of the amount listed above has been paid to the Contractor pursuant to the Contract. The maximum amount of this guarantee shall be progressively reduced by the amount of the advance payment repaid by the Contractor as indicated in copies of interim statements or payment certificates which shall be presented to us. This guarantee shall expire, at the latest, upon our receipt of a copy of the interim payment certificate indicating that eighty (80) percent of the Contract Price has been certified for payment, or on the ___ day of _____, 2___, whichever is earlier. Consequently, any demand for payment under this guarantee must be received by us at this office on or before that date. Yours truly, Signature and seal: Name of Bank or Insurance Company: Address: Date: Page 268 269 SECTION XI: APPLICATION TO PUBLIC PROCUREMENT ADMINISTRATIVE REVIEW BOARD SECTION XI: APPLICATION TO PUBLIC PROCUREMENT ADMINISTRATIVE REVIEW BOARD Page 269 270 SECTION XI: APPLICATION TO PUBLIC PROCUREMENT ADMINISTRATIVE REVIEW BOARD FORM RB 1 REPUBLIC OF KENYA PUBLIC PROCUREMENT ADMINISTRATIVE REVIEW BOARD APPLICATION NO…………….OF……….….20……... BETWEEN ……………………………………………………….APPLICANT AND …………………………………RESPONDENT (Procuring Entity) quest for review of the decision of the…………… (Name of the Procuring Entity) of ……………dated the…day of ………….20……….in the matter of Tender No………..…of …………..20… REQUEST FOR REVIEW I/We……………………………,the above named Applicant(s), of address: Physical address…………….Fax No……Tel. No……..Email ……………, hereby request the Public Procurement Administrative Review Board to review the whole/part of the above mentioned decision on the following grounds , namely:1. 2. etc. By this memorandum, the Applicant requests the Board for an order/orders that: 1. 2. etc SIGNED ………………. (Applicant) Dated on…………….day of ……………/…20… FOR OFFICIAL USE ONLY Lodged with the Secretary Public Procurement Administrative Review Board on ………… day of ………....20….……… SIGNED Board Secretary Page 270