Title: G3-FIELD-TEST-REPORTTEMPLATE File : Author: Date: Page: 50100-1A-G3-FIELD-TEST-REPORT-TEMPLATE K. WEISS Rev. 2015-03-12 1 of 5 PN: 1A ECO# 0162 50100 G3 Test Report Operator: Kevin Weiss Job Number: 100.56 NVO Location: North Vancouver Office Date: 12/Mar/2015 Notes: This is to be used as an example of how to fill out a report. Any notes concerning the overall system can go here. Powell Canada Inc. Suite 201, 55 Gostick Place North Vancouver, BC, V7M 3N2 Powered by safety ® Tel.:604.288.4212 www.powellbrite.com Title: File : G3-FIELD-TEST-REPORTTEMPLATE 1 K. WEISS Rev. 2015-03-12 2 of 5 PN: 1A ECO# 0162 50100 CHANNEL LOCATIONS Location Channel 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Author: Date: Page: 50100-1A-G3-FIELD-TEST-REPORT-TEMPLATE Stimulus Check Y Y Y Y Y Y N N N LBS (LOWER)-AØ U#1A LBS (LOWER)-BØ U#1A LBS (LOWER)-CØ U#1A LBS (UPPER)-AØ U#1A LBS (UPPER)-BØ U#1A LBS (UPPER)-CØ U#1A CABLE CONNECTION-AØ U#1A CABLE CONNECTION-BØ U#1A CABLE CONNECTION-CØ U#1A N/A N/A N/A N/A N/A N/A N/A N/A N/A Notes: Here is where notes about the locations would be. Such as; stimulus check on cable landings not done due to enclosed area or found mislabeled ch3 and 4, swapped to correct channels. Powell Canada Inc. Suite 201, 55 Gostick Place North Vancouver, BC, V7M 3N2 Powered by safety ® Tel.:604.288.4212 www.powellbrite.com Title: G3-FIELD-TEST-REPORTTEMPLATE 2 File : Author: Date: Page: 50100-1A-G3-FIELD-TEST-REPORT-TEMPLATE K. WEISS Rev. 2015-03-12 3 of 5 PN: 1A ECO# 0162 50100 DEVICE OVERVIEW Hardware Part Number: 10121 Firmware: 60036-1.00.01 Device Type: BSG3.9S Device S/N: 300020 Brite Spot 1 S/N: 4294967295 Brite Spot 2 S/N: 4294967295 Brite Spot 3 S/N: 4294967295 Brite Spot 4 S/N: N/A Brite Spot 5 S/N: N/A Brite Spot 6 S/N: N/A Slave ID: 1 Modbus Port: 502 Modbus Serial Baud: 19200 IP Address: 192.168.1.50 Subnet Mask: 255.255.255.0 Gateway: 192.168.1.2 MAC: A4:3B:FA:24:93:F4 Log Spacing: 1 hour Memory Capacity: 5% Degree Type: °F Warning Threshold: 194 Alarm Threshold: 221 Warning Flags: 000000000 Alarm Flags: 000000000 Device Tick: 32087 Stack Version: v5.42 Build Date: Apr 21 2014 Device Time: 28/12/2011 23:56:04 Notes: Should be able to copy and paste from the Overview tab on the webpage. Notes like memory getting full or if any changes were made to the device from defaults should go here (eg. Changed slave ID from 1 to 6). Powell Canada Inc. Suite 201, 55 Gostick Place North Vancouver, BC, V7M 3N2 Powered by safety ® Tel.:604.288.4212 www.powellbrite.com Title: G3-FIELD-TEST-REPORTTEMPLATE 3 File : Author: Date: Page: 50100-1A-G3-FIELD-TEST-REPORT-TEMPLATE K. WEISS Rev. 2015-03-12 4 of 5 PN: 1A ECO# 0162 50100 BRITESPOT CHANNEL PERFORMANCE Status Temp °F Fiber Power Ch 1 Good 80 10 Ch 2 Good 77 10 Ch 3 Good 79 10 Ch 4 Good 77 10 Ch 5 Good 85 10 Ch 6 Good 81 10 Ch 7 Good 79 10 Ch 8 Good 63 10 Ch 9 Good 78 10 Ch 10 N/A N/A N/A Ch 11 N/A N/A N/A Ch 12 N/A N/A N/A Ch 13 N/A N/A N/A Ch 14 N/A N/A N/A Ch 15 N/A N/A N/A Ch 16 N/A N/A N/A Ch 17 N/A N/A N/A Ch 18 N/A N/A N/A Notes: If any channels need to be corrected (maybe a bend or the fiber isn’t plugged in all the way) make notes here. Also if you have a lower fiber power it would be good to give a reason (fiber power 8 because it is 15meter probe with lots of bends). As well as mention the desired temperature (test done at room temperature with no current). Powell Canada Inc. Suite 201, 55 Gostick Place North Vancouver, BC, V7M 3N2 Powered by safety ® Tel.:604.288.4212 www.powellbrite.com Title: G3-FIELD-TEST-REPORTTEMPLATE 4 File : Author: Date: Page: 50100-1A-G3-FIELD-TEST-REPORT-TEMPLATE K. WEISS Rev. 2015-03-12 5 of 5 PN: 1A ECO# 0162 50100 PICTURES 4.1 INSTALLED G3 LOCATION Powell Canada Inc. Suite 201, 55 Gostick Place North Vancouver, BC, V7M 3N2 Powered by safety ® Tel.:604.288.4212 www.powellbrite.com