Part V SANS 10400 – Space heating Part V of SANS 10400 serves as a guideline to the design and construction of any flue pipe, chimney, hearth or fireplace Any system of space heating in a building must be designed, constructed and installed as to operate safely and any flue,flue pipe or chimney used shall be designed to safely remove any smoke or noxious gases produced. Chimney & Flue pipes must not cause a fire hazard to,adjacent material in its installation and design A chimney or flue pipe cannot be connected to a shaft or duct which forms part of a ventilation system No other services may be connected close to a chimney or flue if it may be affected by the heat No combustible material must be built within 200mm of the inside of a chimney because of the heat. A chimney wall must be at least 190mm thick and not reduced to less than 90mm. If the wall construction is less than 190mm then the flue must be lined with a material which will withstand any action of the flue gases and will resist, without cracking or softening, the temperature to which it may be subjected. The flue lining must extend through the full height of such a chimney. Any chimney more than 4m in height must be designed in accordance with SANS 10400 Part B. The point of outlet of a chimney must be a minimum of 1m above the highest point of contact between the chimney and the roof or 1m above the highest point of a window or roof light that can be opened or a ventilation inlet situated in a roof or external wall where the horizontal distance from the nearest point of such window, roof light or opening to a vertical line through the Centre of such chimney outlet is less than 2.3m The point of outlet of a chimney must be a minimum of 1m above the eaves level in the case of a chimney that passes within 1.5m of the nearest wall of such building. On the gable end of such building the chimney shall not extend less the An 600mm above the highest point of such gable end. Every fireplace shall have a hearth made if non combustible material. A hearth must nit extend more than 500mm in front of the fog rate or fire basket and not less than 300mm beyond each side. No combustible material shall be built into a hearth.