ME-803 Refrigeration & Air Conditioning UNIT :-I SYLLABUS:- Principles and methods of refrigeration, freezing; mixture cooling by gas reversible expansion, throttling, evaporation, Joule Thomson effect and reverse Carnot cycle; unit of refrigeration, coefficient of performance, vortex tube & thermoelectric refrigeration, adiabatic demagnetization; air refrigeration cycles- Joule’s cycle Boot-strap cycle, reduced ambient cycle and regenerative cooling cycles. Introduction Refrigeration is defined as “the process of cooling of bodies or fluids to temperatures lower than those available in the surroundings at a particular time and place”. It should be kept in mind that refrigeration is not same as “cooling”, even though both the terms imply a decrease in temperature. In general, cooling is a heat transfer process down a temperature gradient, it can be a natural, spontaneous process or an artificial process. However, refrigeration is not a spontaneous process, as it requires expenditure of energy (or availability). Thus cooling of a hot cup of coffee is a spontaneous cooling process (not a refrigeration process), while converting a glass of water from room temperature to say, a block of ice, is a refrigeration process (non-spontaneous). “All refrigeration processes involve cooling, but all cooling processes need not involve refrigeration”. Refrigeration is a much more difficult process than heating; this is in accordance with the second laws of thermodynamics. This also explains the fact that people knew ‘how to heat’, much earlier than they learned ‘how to refrigerate’. All practical refrigeration processes involve reducing the temperature of a system from its initial value to the required temperature that is lower than the surroundings, and then maintaining the system at the required low temperature. The second part is necessary due to the reason that once the temperature of a system is reduced, a potential for heat transfer is created between the system and RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I Surroundings, and in the absence of a “perfect insulation” heat transfer from the surroundings to the system takes place resulting in increase in system temperature. In addition, the system itself may generate heat (e.g. dueto human beings, appliances etc.), which needs to be extracted continuously. Thus in practice refrigeration systems have to first reduce the system temperature and then extract heat from the systemat such a rate that the temperature of the system remains low. Theoretically refrigeration can be achieved by severalmethods. All these methods involve producing temperatures low enough for heat transfer to take place from the system being refrigerated to the system that is producing refrigeration. Methods of producing low temperatures Sensible cooling by cold medium If a substance is available at a temperature lower than the required refrigeration temperature, then it can be used for sensible cooling by bringing it in thermal contact with the system to be refrigerated. For example, a building can be cooled to a temperature lower than the surroundings by introducing cold air into the building. Cold water or brine is used for cooling beverages, dairy products and in other industrial processes by absorbing heat from them. The energy absorbed by the substance providing cooling increases it temperature, and the heat transferred during this process is given by: Q= mcp(Δ T) Where, m is the mass of the substance providing cooling, cp is its specific heat and RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I ΔT is the temperature rise undergone by the substance. Since the temperature of the cold substance increases during the process, to provide continuous refrigeration, a continuous supply of the cold substance should be maintained, which may call for an external refrigeration cycle. Endothermic mixing of substances This is one of the oldest methods known tomankind. It is very well-known that low temperatures can be obtained when certain salts are dissolved in water. This is due to the fact that dissolving of these salts in water is an endothermic process, i.e., heat is absorbed from the solution leading to its cooling. For example,when salts such as sodium nitrate, sodium chloride, calcium chloride added to water, its temperature falls. By dissolving sodium chloride in water, it is possible toachieve temperatures as low as –210C, while with calcium chloride a temperature of –510C could be obtained. However, producing low temperature by endothermic mixing has several practical limitations. These are: the refrigeration effect obtained is very small (the refrigeration effect depends on the heat of solution of the dissolved substance, which is typically small for most of thecommonly used salts), and recovery of the dissolved salt is often uneconomical as this calls for evaporation of water from the solution. Methods of Refrigeration: a) Natural Method: The natural method includes the utilization ofice or snow obtained naturally in cold climate. Ice melts at 00C. So when it is placed in space or system warmer than 00C, heat is absorbed by the ice and the space iscooled. The ice then melts into water by absorbing its latent heat at the rate of 324 kJ/kg. But, now-a-days, refrigeration requirements have RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I become so high that the natural methods are inadequate and therefore obsolete b) Mechanical or Artificial Refrigeration Reversed Carnot engine A mechanical refrigeration system works on the principle of reversed Carnot cycle as shown in Work δw is delivered to the refrigerating system, causing it to remove heat δQ2 from the body or system (at lower temperature T3) and to deliver it along with work, δw, to another body at higher temperature, T1, so that, δQ1 = δw + δQ2 RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I There can be two methods bywhich the temperature T2< T3 may be attained within the refrigerating system. 1. By lowering the temperature of the working substance in the refrigerating system to the level of T2. In this case, the heat will be absorbed due to temperature difference and T3 will decrease as heat δQ2 flows out. 2. By evaporating some fluid at an appropriate pressure. In this case, a constant temperature T2 will be maintained and latent heat of fluid will be absorbed as δQ2 Depending upon the above method used, there are two types of mechanical refrigerating systems : i) ii) Air systems:Uses air as a working fluid.Air does not undergo any change of phase, but absorbs heat due to temperature difference. Chemical Agent Systems: The working fluid changing its phase while boiling from liquid to vapor state, thereby it absorbs the latent heat. Unit of Refrigeration: Capacity of refrigeration unitis generally defined in ton of refrigeration. A ton of refrigeration is defined as the quantity of heat to be removed in order to form one ton (1000 kg) of ice at 0 0C in 24 hrs, from liquid water at 00C. This is equivalent to 3.5 kJ/s (3.5 kW) or 210 kJ/min. Reverse Carnot cycle RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I Introduction The Carnot's heat engine is described almost in all courses of physics and thermodynamics Carnot engine operates on the reversible Carnot cycle. The direct Carnot's cycle includes isothermal enlargement of working substance at temperature Т 1, which equals to the temperature of hotter reservoir of heat; 2) adiabatic enlargement of working substance, in the process of which it’s temperature lowers to the temperature Т 2, which equals to the temperature of colder reservoir of heat; 3) isothermal compression of working substance at temperature Т2;4) adiabatic compression of working substance, in the process of which it’s temperature rises to the temperature Т1. In the direct cycle the Carnot's engine gets from the hotter reservoir for one cycle the amount of heat Q1, transfers the amount of heat Q2(Q2< Q1) to the colder reservoir, and the difference between Q1–Q2 converts to the work L, which can be used to lifting of weight. In the reverse cycle the Carnot's engine gets from the colder reservoir for one cycle the amount of heat Q2, transfers the amount of the heat Q1 to the hotter reservoir and converts into heat work L, obtained, for example, by of the lowering of a weight. Q1= Q2+ L. The efficiency of a heat engine (cycle efficiency) ηis defined by: 2. The proof of Carnot's theorem based on Thomson's postulate Assume there are two Carnot engine, which efficiency are η1and η2, where η1> η2. The engine 1is running on the direct Carnot cycle, the engine 2 – the reverse Carnot cycle. The engine 1for one cycle gets the amount of heat Q1from the hotter reservoir, transfers the amount of heat Q2to colder reservoir and produces work L. The engine2 gets the amount of heat Q 2' from the colder reservoir, gets from the engine 1 the amount of work L', transfer to the hotter reservoir the amount of heat Q1. Q1 = Q2 + L = Q2' + L'. If η1> η2, then Q2' > Q2 and L'< L. RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I The engine 1produces work L. Part of this work is equal to L'is giving to the engine 2, part is equal toL –L'is spending on lifting of weight GL – L'= Q2' – Q2. (see Fig.1) Fig -1 The result of the two engines is the raising of a weight and the cooling the colder reservoir (Q2' > Q2). This one contradicts to the Thomson's postulate: "It is impossible, by means of inanimate material agency, to derive mechanical effect from any portion of matter by cooling it below the temperature of the coldest of the surrounding objects". Consequently, the assumption η1> η2 is false. Suggested, η1< η2. When the engine 1 is running on reverse Carnot cycle and the engine 2 is running on the direct Carnot cycle, we get again a result that contradicts the Thomson's postulate. Efficiency of the engine 1can be neither less nor more efficient engine 2. The efficiency of the Carnot engine is independent of the working substance. 3. The proof of the Carnot's theorem based on "antipostulate" Assume there are two Carnot engine, which efficiency are η1and η2, where η1<η2. The engine 1 is running on the direct Carnot cycle, the engine 2– the reverse Carnot cycle. The engine 1for one cycle gets the amount of heat Q1from the hotter reservoir, transfers the amount of heat Q2 to colder reservoir and produces work L. The engine2gets the amount of heat Q2' from the colder reservoir, gets of the engine 1 theamount of work L, from an external source – the amount of work L' – L, transfer to the hotter reservoir the amount of heat Q1. Q1 = Q2 + L = Q2' + L'. If η1< η2, then Q2> Q2' and L < L'. The engine 2absorbs work L, which is produced by engine 1,and the work L'– L, which is obtained by lowering of weight G (see Fig. 2). L'– L= Q2 – Q2'. RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I The result of the two engines working is lowering of a weight and heating of colder reservoir (Q2> Q2'). This contradicts to the "antipostulate": "It is impossible to use the mechanical effect to the heating the coldest of surrounding objects". Consequently, the assumption η1< η2is false. Suggested that η1> η2. When the engine 1is running on reverse Carnot cycle and the engine 2 is running on the direct Carnot cycle, we get again a result that contradicts the "antipostulate". Efficiency of the engine 1can be neither less nor more efficient engine2. The efficiency of the Carnot engine is independent of the working substance. APPLICATION OF VORTEX TUBE TO REFRIGERATION CYCLES The relative inefficiency of the vortex tube as a stand-alone cooling device has thus far limited its use. The coefficient of performance (COP) of the vortex tube as a refrigerator, cooling provided per work required to compress the fluid, is very low (less than 0.1 near roomtemperature) relative to a domestic refrigeration cycle. However, its simplicity makes it an extremely compact, reliable, affordable, and flexible alternative in some special applications. A more exciting and potentially much broader use for the vortex tube exists if it can be integrated into a refrigeration system as an alternative to the conventional throttling valve in order to accomplish the required expansion process in a less irreversible manner. The vortex tube model developed in the previous section RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I will be employed to evaluate the utility of the vortex tube within vapor compression and Joule-Thomson refrigeration systems. The results of these analyses must be qualified by the statement that the vortex tube model has been developed for and verified against data taken at room temperature under single-phase operating conditions. The performance of a vortex tube may be substantially different in the two-phase and nonideal conditions encountered within a refrigeration system but the data available for these operating conditions are scarce and often conflicting. The analysis remains a valuable tool provided that the underlying physical model is accurate and it clearly points out those situations where the potential exists for significant improvements in cycle performance Vapor Compression Cycle Vapor Compression Cycle Figure 5 illustrates a conventional vapor compression refrigeration cycle with a throttling valve and Figure 6 illustrates the corresponding ideal thermodynamic cycle using a typical synthetic refrigerant, R134a. The process of expanding the twophase fluid through the valve, from state (3) to state (4), follows a line of constant enthalpy. In the situation where the valve is replaced by a vortex tube, the corresponding expansion for the fluid extracted from the cold side of the tube would be limited to an isentropic process, forreasons described earlier. The limiting exit states would therefore be (4c) and (4h), as indicated in Figure 6. Clearly, under these assumptions the vortex tube is not capable of producing a temperature separation effect under the vapor dome – the hot and cold fluids leave at the same temperature and at most we might expect a difference in quality based on centrifugal forces. This fact has been experimentally observed in those few instances where a vortex tube has been operated in the saturated region, for example by Takahama et al. (1979) using steam. Therefore, there is no benefit associated with the use of a vortex tube within a pure refrigerant, vapor compression refrigeration cycle. The isenthalpic and isentropic temperature change between two isobars are not identical when the refrigeration cycle extends into the super-critical region orutilizes non-azeotropic mixtures and in these situations it is possible that the application of a vortex tube may be beneficial. Carbon dioxide is a naturally occurring substance that has recently received renewed attention as a potential alternative to synthetic refrigerants (Lorentzen, 1994) because it is non-flammable, non-toxic, readily available, and compatible with most materials. However the theoretical COP of a carbon dioxide refrigeration system is not as high as that of most synthetic RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I refrigerants, in large part due to throttling losses (these inefficiencies explain more than 40% of the total loss according to Robinson et al., 1996). The potential for increasing the performance of a carbon dioxide cycle via modification of the expansion mechanism is therefore high. Li et al. (2000) theoretically investigated a carbon dioxide cycle with an expansion valve, a work extracting expansion device, and a vortex tube and reported that use of a vortex tube could improve the performance relative to the valve. This analysis made no attempt to model the vortex tube beyond invoking the 1stand 2ndlaw of thermodynamics. If the physical model described above is used to model the vortex tube in this situation then the predicted benefit in cycle performance disappears, again because the temperature separation effect goes rapidly to zero as the vapor dome is approached. Joule-Thomson Cycle RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I Joule-Thomson (JT) cryogenic refrigerators rely on expansion through a throttling valve yet do not necessarily operate in the vapor dome. These refrigeration devices are used in low cost applications or in situations where reliability is of paramount importance such as tactical cryocoolers for infrared detectors, refrigeration for electronics, cryotherapy probes, and cryocoolers for spaceborne detectors. Figure 7 illustrates schematically the Joule-Thomson cryogenic refrigeration cycle and Figure 8 illustrates the cycle qualitatively on a T-s diagram. Notice that the JT cycle relies on the fact that a temperature drop is produced during the isenthalpic expansion through the valve (from state 2 to state 3). This allows a small warming of the refrigerant as it accepts the refrigeration load (from state 3 tostate 4) before entering the recuperative heatexchanger. In order to be viable, the JT cycle must operate in a region where the Joule-Thomson coefficient, the partial derivative of temperature with respect to pressure at constant enthalpy, is positive. This limitation explains why typical JT systems operate with very high pressure ratio and require large, high effectiveness recuperative heat exchangers RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I The vortex tube produces a large temperature drop in the cold exit fluid regardless of the Joule-Thomson coefficient. For example, the isenthalpic temperature drop associated withexpanding room temperature air from 3 atm to 1 atm is only 0.2 °C yet Figure 3 shows that a temperature drop of 27°C can be achieved at these conditions using a vortex tube, an increase of two orders of magnitude. Figure 9 illustrates the simplest possibility for implementing a cryogenic refrigeration cycle using a vortex tuberather than the expansion valve. The fluid leaving the cold exit is used to accept the refrigeration load and the fluid leaving the hot exit bypasses the recuperative heat exchanger. Figure 10 illustrates the temperature entropy diagram for this vortex tube cycle; the state points from the original JT cycle are retained for illustration. The temperature entering the recuperative heat exchanger, state (1), remains the same but the temperature of the leaving gas, state (2), is increased as a result of unbalancing the heat exchanger. The temperature drop associated with the fluid passing through the cold side of the vortex tube is much larger than it would be had it undergone an isenthalpic expansion (the temperature of state (3) is reduced), but some part of the flow has been sacrificed to accomplish this effect. The cold fluid is heated to the same refrigeration temperature, state (4), prior to entering the recuperative heat exchanger. A model of the refrigeration cycle shown in Figure 9 has been developed using the vortex tube model already described. For a given mass flow rate (m&) and pressure RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I ratio (PR), the refrigeration load(Qload) can be predicted as a function of refrigeration temperature (Tload) given the characteristics of the heat exchanger (a total conductance UA), the vortex tube, and a cold gas mass fraction (y). Figure 11 illustrates the refrigeration load as a function of the cold gas mass fraction using air as the working fluid for one set of operating conditions (Trej= 300 K, PR = 5, m & = 10 g/s, UA = 10 W/K, and Tload= 250 K). When the cold gas mass fraction is equal to unity, the cycle is equivalent to a JT cycle – all of the gas passes through the vortex tube, undergoes an isenthalpic process, passes through the refrigeration load, and returns through the recuperative heat exchanger. Notice that under these operating conditions a JT cycle is not viable, the refrigeration load is negative because the pressure ratio is low and the heat exchanger small. As the cold gas mass fraction is reduced the refrigeration power increases and reaches a maximum value of 94 W at an optimal cold gas mass fraction near 0.5. As the cold gas mass fraction is reduced, three interrelated effects occur; there are two negative effects – unbalancing the heat exchanger and reducing the mass flow rate through the refrigeration load that are countered by a large positive effect increasing the temperature drop from state (2) to state (3). The optimal value of cold gas mass fraction balances these effects and is therefore somewhat larger than the cold gas mass fraction that maximizes the temperature drop through the vortex tube, near 0.25 as shown in Figures 3 and 4. RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I Figure 12 illustrates the refrigeration load for the vortex tube cycle using the optimal cold gas mass ratio as a function of the load temperature and at several pressure ratios for one set of operating conditions (air, T rej= 300 K, m&= 10 g/s, and UA = 10 W/K). Also shown in Figure 12 is the performance of a JT cycle at identical operating conditions. Notice that the vortex tube cycle significantly outperforms the JT cycle; this is particularly true as the pressure ratio or the heat exchanger size is reduced. This investigation clearly illustrates that the addition of a vortex tube has the potential to significantly increase the performance of a single-stage JT system and motivates further study into these devices and their use in cryogenicrefrigeration systlarge increases in the efficiency of JT systems have been made possible through the use of mixed gas refrigerants (Little, 1998) and this technology can be augmented by the use of phase separators as originally proposed by Kleemenko (1959). There is an obvious parallel between these phase separators and the natural separation mechanism that RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I occurs within the vortex tube due to centrifugal effects (Marshall, 1977). There exists then the possibility of performing augmented expansion simultaneously with some phase separation within a vortex tube in a mixed gas cycle. Complex, multi-stage cycles can be considered with the potential to significantly out-perform the currently available JT technology without adding significantly to cost or detracting from reliability. Air Cycle Refrigeration Introduction Refrigeration is a world wide multi-billion pound business, with applications ranging from food processing to air conditioning. This industry is under massive pressure to develop new ideas, technologies and methods of work that will meet the demands of an ever changing world. One major driver for the industry is the impending legislation resulting from the Kyoto and Montreal Protocols, which will outlaw the use of the most common chlorofluorocarbon (CFC) and hydrofluorocarbon (HFC) refrigerant gases RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I currently being used in the world today, in an attempt to reduce global warming and its effects. CFCs and HFCs are toxic and have large global warming and ozone depletion potentials; consequently an environmentally-friendly alternative is urgently required. A solution to this problem has been designed in the form of an air cycle refrigeration system for blast freezing applications which uses air as the refrigerant in place of CFCs and HFCs. Design Air cycle refrigeration manipulates the fact that when air expands, there is an associated drop in its temperature. Figure 1 shows a simple cycle diagram for the air cycle system. Before the air can be expanded to produce a cooling effect, it must first be compressed; this is achieved by passing the air through two stages of turbomachinerycompressors. The compression of the air RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I results inits temperature rising, so to provide very cold air at the end of the cycle, it is necessary to remove heat from the air; this is achieved by passing the air through heat exchangersimmediately after each stage of compression. The final stage of the cycle is to expand the air using a turbine, yielding an instantaneous drop in the temperature of the air to around -60oC, dependent upon necessary cooling requirements. Advantage The air cycle refrigeration system for blast freezing applications offers the following main benefits: • The system is immune to the impending phase out of CFCs and is environmentally-friendly. •It is effectively leak-free, eliminating the need for costly refills and potential fines associated with refrigerant leaks •Air cycle refrigeration systems offer better performance at off-design conditions than existing systems •The lower temperatures offered by the system lead to shorter freezing times and hence improved Process throughput, whilst also reducing moisture loss and improving food quality Air cycle refrigeration is the subject of ongoing research at Queen’s University, Belfast, by Dr. S. W. T. Spence et al. Aircraft cooling systems In an aircraft, cooling systems are required to keep the cabin temperatures at a comfortable level. Even though the outsidetemperatures are very low at high altitudes, still cooling of cabin is required due to: RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I i. ii. iii. Large internal heat generation dueto occupants, equipment etc. Heat generation due to skin friction caused by the fast moving aircraft At high altitudes, the outside pressure will be sub-atmospheric. When air at this low pressure is compressed and supplied to the cabin at pressures close to atmospheric, the temperature increases significantly. For example, when outside air at a pressure of 0.2 bar and temperature of 223 K (at 10000 m altitude) is compressed to 1 bar, its temperature increases to about 353 K. If the cabin is maintained at 0.8 bar, the temperature will be about 332 K. This effect is called as ram effect. This effect adds heat to the cabin, which needs to be taken out by the cooling system. iv. Solar radiation For low speed aircraft flying at low altitudes, cooling system may not be required, however, for high speed aircraft flying at high altitudes, a cooling system is a must. Even though the COP of air cycle refrigeration is very low compared to vapour compression refrigeration systems, it is still found to be most suitable for aircraft Refrigeration systems as: i. Air is cheap, safe, non-toxic and non-flammable. Leakage of air is not a problem ii. Cold air can directly be used for cooling thus eliminating the low temperature heat exchanger (open systems) leading to lower weight iii. The aircraft engine already consistsof a high speed turbo-compressor, hence separate compressor for cooling system is not required. This reduces the weight per kW cooling considerably. Typically, less than 50% of an equivalent vapour compression system iv. Design of the complete system is much simpler due to low pressures.Maintenance required is also less. RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I Figure 9.5 shows the schematic of a simpleaircraft refrigeration system and the operating cycle on T-s diagram. This is an open system. As shown in the T-s diagram, the outside low pressure and low temperature air (state 1) is compressed due to ram effect to ram pressure (state 2). During thisprocess its temperature increases from 1 to 2. This air is compressed in the main compressor to state 3, and is cooled to state 4 in the air cooler. Its pressure is reduced to cabin pressure in the turbine (state 5), as a result its temperature drops from 4 to 5. The cold air at state 5 is supplied to the cabin. It picks up heat as it flows through the cabin providing useful cooling effect. The power output of the turbine is used to drive the fan, which maintains the required air flow over the air cooler. This simple system is good for ground cooling (when the aircraft is not moving) as fan can continueto maintain airflow over the air cooler. By RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I applying steady flow energy equation to the ramming process, the temperature rise at the end of the ram effect can be shown to be: Bootstrap system: RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I shows the schematic of a bootstrap system, which is a modification of the simple system. As shown in the figure, this system consists of two heat exchangers (air cooler and aftercooler), in stead of one air cooler ofthe simple system. It also incorporates a secondary compressor, which is driven by the turbine of the cooling system. This system is suitable for high speedaircraft, where in the velocity of the aircraft provides the necessary airflow for the heat exchangers, as a result a separate fan is not required. As shown in the cycle diagram, ambient air state 1 is pressurized to state 2 due to the ram effect. This air is further compressed to state 3 in the main compressor. The air is then cooled to state 4 in the air cooler. The heat rejected in the air cooler is absorbed by the ram air at state 2. The air from the air cooler is further compressed from state 4 to state 5 in the secondary compressor. It is then cooled to state 6 in the after cooler, expanded to cabinpressure in the cooling turbine and is supplied to the cabin at a low temperature T 7 Since the system does not consist of a separate fan for driving the air through the heat exchangers, it is not suitable for ground cooling. However, in general ground cooling is normally done by an external air conditioning system as it is not efficient torun the aircraft engine just to provide cooling when it is grounded. Other modifications over the simple system are: regenerative system and reduced RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I ambient system. In a regenerative system, a part of the cold air from the cooling turbine is used for precooling the air entering the turbine.As a result much lower temperatures are obtained at the exit of the cooling turbine, however, this is at the expense of additional weight and design complexity. The cooling turbine drives a fan similar to the simple system. The regenerative system is good for both ground cooling as well as high speed aircrafts. The re duced ambient system is well-suited for supersonic aircrafts and rockets. RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I Dry Air Rated Temperature (DART): The concept of Dry Air Rated Temperature is used to compare different aircraft refrigeration cycles. Dry Air Rated Temperature is defined as the temperature of the air at the exit of the cooling turbine in the absence of moisture condensation. For condensation not to occur during expansion in turbine, the dew point temperature and hence moisture content of the air should be very low, i.e., the air should be very dry. The aircraft refrigeration systems are rated based on the mass flow rate of air at the design DART. The cooling capacity is then given by: where .mis the mass flow rate of air, TDARTand Ti are the dry air rated temperature and cabin temperature, respectively. A comparison between different aircraft refrigeration systems based on DART at different Mach RAC BY:- Raju Kumar Das Asst prof GIIT Gwl ME-803 Refrigeration & Air Conditioning UNIT :-I numbers shows that: i.DART increases monotonically with Mach number for all the systems except the reduced ambient system ii.The simple system is adequate at low Mach numbers iii.At high Mach numbers either bootstrap system or regenerative system should be used iv.Reduced ambient temperature system is best suited for very high Mach number, supersonic aircrafts RAC BY:- Raju Kumar Das Asst prof GIIT Gwl