Chapter RM: Prevention and mitigation: Hydrogen releases, detection and ventilation 1 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1 Control of flammability and explosion hazards 1.1.1 Overview of modes of hazard prevention and mitigation Definition of a bow tie chart A bow tie chart is a graphical representation of the safety measures which can be implemented to control the risks associated to a hazardous event (see Figure 1). Two kinds of safety measures can be distinguished: Safety measures can act on the combination of causes of the hazardous event, so as to prevent the hazardous event from happening - they are then called prevention measures. Prevention measures are the specific measures that reduce the likelihood of the event. Safety measures can be aimed at mitigating (i.e. reducing) the consequences of the hazardous event – they are then called mitigation measures. Note: the hazardous event is the same as the “initial event” in the section on Design for safety. Mitigation Prevention Cause 1 Consequence 1 AND Cause 2 Consequence 2 Cause 3 AND Cause 4 OR hazardous event Consequence 3 AND Cause 5 Consequence 4 Condition 4 = safety measure Figure 1: Application of safety measures to control risk associated to a hazardous event (Source: Air Liquide) The bow tie chart allows for an exhaustive overview of all safety measures which can be applied to prevent feared events from happening, or to limit their consequences. 2 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Example: bow tie chart of hydrogen release Hydrogen release is the main risk induced by hydrogen use and the hazardous event most often feared in hydrogen systems. The bow tie chart of hydrogen release is a graphical representation of all the safety measures related to hydrogen release (see Figure 2). Strong blast effects Confined explosive atmosphere H2 release Unconfined explosive atmosphere Injury / casualty Flash fire Blast effects Loss of leaktightness Flame/ Jet fire Equipment failure Kinetic effects Escalation Figure 2: Overview of the causes and consequences of a hydrogen release (Source: Air Liquide) Hydrogen release can be caused either by a loss of leak-tightness of the system, or by an equipment failure1. Consequently, different hazardous phenomena may occur, generally in combination: Depending on the release properties and the presence of ignition sources, the hydrogen release may ignite immediately or after a certain delay. In the latter case, if the release takes place in a confined environment, an explosive atmosphere may build up by accumulation. In all cases, depending on the amount of flammable mixture, the mean hydrogen concentration, and presence of factors accelerating combustion (such as repeated obstacles, or pre-existing turbulence, such as that induced by the release itself), ignition of the flammable mixture will result in a flash fire as well as overpressure effects - i.e. an explosion - ranging from a simple noise to hazardous blast effects. 1 An equipment failure happens when the equipment cannot resist to excessive conditions, such as a too high internal pressure. 3 © HyFacts 2012/13 – CONFIDENTIAL – not for public use This explosion is likely to be more pronounced in a confined environment than in an unconfined one due to the aggravating effect of accumulation. Destruction of the confining structure (e.g. a building), and the associated kinetic effects2 is in itself likely to be hazardous. Once ignited, the release is very likely to produce a jet fire which persists as long as the release itself. Independently of the hazards of hydrogen, failure of an equipment containing hydrogen under pressure is likely to result in kinetics effects. All these consequences of hydrogen release can impact people - leading to injuries, or/and impacting equipments. Minor events can turn into catastrophic ones (escalation of the event) in the absence of appropriate safety measures. Active and passive prevention measures can be taken, so as to prevent hydrogen releases: Equipment validation Physical protection Periodic leak test Periodic equipment inspection. All these prevention measures will be detailed in other sections of the report. Passive Equipment validation Physical Protection Strong blast effects Active Periodic leak test Passive Equipment validation Physical protection Active Periodic inspection H2 release Confined explosive atmosphere Unconfined explosive atmosphere Injury / casualty Flash fire Blast effects Loss of leaktightness Flame/ Jet fire Equipment failure Kinetic effects Escalation Figure 3: Prevention measures related to hydrogen release (Source: Air Liquide) 2 Kinetic effects always come along with the blast effects and fire, even if it is not represented on the Figure 2 for a better ease of reading. 4 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Active and passive mitigation measures can be taken: Measures to mitigate the consequences of the hydrogen release: o Restricting hydrogen flow / using an excess flow valve (see section 1.1.2.4.1 and 1.1.2.4.2) o Detecting and isolating hydrogen (see section 1.1.4) o Detecting hydrogen and then shutting-down the power (see section 1.1.4) o Avoiding unnecessary confinement o Using natural ventilation (see section 1.1.5.4) o Using active ventilation (see section 1.1.5.5) o Designing the system with explosion vents (see section 1.1.6) o Avoiding ignition sources (see section 1.1.3) Mitigation measures to protect people and equipments: o Implementing separation distances (see section 1.1.8) o Providing emergency response. All these mitigation measures will be detailed in other sections of the report. Passive Avoid unnecessary conf inement Natural ventilation Active Active ventilation Detection and active ventilation Passive Flow restriction Active Detection and Isolation Excess f low valve H2 release Confined explosive atmosphere Passive Passive Explosion venting Separation distance Active Emergency response Strong blast effects Injury / casualty Passive Flash fire Separation distance Active Emergency response Unconfined explosive atmosphere Escalation Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Passive No ignition sources Active Detection and power shut-down Figure 4: Mitgation measures related to hydrogen release (Source: Air Liquide) A combination of measures including both prevention and mitigation need to be applied to control flammability and explosion hazards, considering the reliability of these measures with regards to the likelihood of the initiating event, in order to achieve the expected level of safety. A single measure, such as preventing ignition sources, is in general insufficient to achieve this objective. 5 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Reference: European Industrial Gases Association, 2008, “Major Hazards”, IGC Document 142/08/E 1.1.2 Prevention and mitigation of hydrogen releases Unignited releases – summary 1.1.2.1 Hydrogen is either released as a pure plume or as a jet, depending on the source flow rate and diameter. A hydrogen release is characterized by its Richardson number Ri0: Ri 0 g. a 0 R0 . 2 0 U0 Equation 1 with U0: release velocity (m/sec) R0: radius of the releasing orifice (m) a: ambient density (kg.m-3) 0: released gas density (kg.m-3) g: the gravitational acceleration (9,81 m.s-2) When the Richardson number is larger than the unity: the momentum is negligible compared to buoyancy effects; gravity effects are dominant. The flow is then a pure plume. When the Richardson number is lower than the unity: the momentum dictates the mixing and overturning is induced. The flow is a jet. 6 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.2.2 Physical extension of flammable mixture Hydrogen releases might form flammable mixtures. In order to keep people and equipment out of the physical extension of the flammable mixture, the distance from the leak source where the hydrogen concentration drops to 4% 3 by volume should be determined. In the case of momentum-controlled jets, a similarity law has been developed to calculate the axial hydrogen concentration decay: C m x d 5.4 noz x amb noz 1/ 2 Equation 2 Cm-x fuel mass fraction at location x (% by mass) dnoz real nozzle diameter (m) ρamb density of the ambient air (kg/m 3) ρH2 density of hydrogen in the nozzle (kg/m 3) x distance from the nozzle along the jet axis (m) With the aid of nomograms (see Figure 5) based on this similarity law, the axial distance to chosen hydrogen concentration can be determined once leak diameter, hydrogen pressure and hydrogen temperature in the nozzle are known. See additional explanations for the use of this nomogram in section Error! Reference source not found.. 3 The UK regulator applies the 50% LFL as the lower threshold, which corresponds to about 2% by volume - instead of 4% by volume. 7 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Figure 5: Nomogram based on the similarity law (Saffers and Molkov, 2012) 8 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Prevention measures 1.1.2.3 Prevention measures related to hydrogen releases aim at preventing any equipment failure and any loss of leak-tightness of the equipment. Passive Equipment validation Physical Protection Strong blast effects Active Periodic leak test Passive Equipment validation Physical protection Confined explosive atmosphere Injury / casualty Flash fire Active Periodic inspection H2 release Unconfined explosive atmosphere Blast effects Loss of leaktightness Flame/ Jet fire Equipment failure Kinetic effects Escalation Figure 6: Prevention measures related to hydrogen release (Source: Air Liquide) 1.1.2.3.1 Mechanical integrity Prevention measures related to the mechanical integrity of hydrogen systems consist (i) in validating equipment design through performance testing and (ii) in checking the equipment periodically once it has been put in service. Furthermore, the equipment may be removed from service at the end of a prespecified lifetime. Design tests and validation aim at proving that the equipment is suited to the application for which it is going to be used. Resistance and endurance tests are examples of tests which can be carried out on the equipment. Resistance tests are basic tests: all relevant characteristics of a system are tested (example: hydraulic pressure test). Endurance tests are more elaborate: the system is subjected to a cyclical loading, and the time until it fails characterizes its endurance. A factor is applied to establish service life (requirement to withstand 50 000 test cycles for a specified service life of 10 000 cycles) 9 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Below is a list of equipment subject to mechanical integrity validation testing: Gaseous hydrogen containers Container valves Flexible hoses Quick connection devices. 1.1.2.3.2 Types of joints and failure modes Tubing elements are connected either by welded joints or by fittings (elements joining two pipes together). Welded joints Welded joints are permanent. They have a better leak-tightness and reliability than fittings; their use limits the number of potential leaks. In order to avoid potential leaks, butt welded pipes having a diameter larger than 15 mm must be tested over their whole length using x-rays (according to the standard NF EN 13480-5). Only certified technicians are entitled to weld tubing elements. Fittings In the situations where welding is not appropriate, tubing elements can also be connected by fittings. For use in hydrogen applications, fittings are made of stainless steel of the appropriate grade. Different kinds of fittings exist. The type of fittings which should be used depends on the pressure range of the gas flowing through the piping, and of the nature of the gas itself. Typical types of connections and fittings are described hereafter. a. Valve-to-cylinder connection Tapered thread connection 10 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Table 1: Tapered thread connection (Source: Air Liquide) Examples Lots of constructors can provide this kind of sealing modes (e.g. of Swagelok® and many others). Conical metal-to-metal sealing is a providers sealing mode rather than a type of connexion: it can be manufactured on an element (e.g. valve). Range of For medium and high pressure ranges (from about 2 to 700 bar) applicatio Example of application: on hydrogen cylinders ns Picture Figure 7: Use of a metal-to-metal sealing conical fitting (in the yellow round, the sealing area) (Source: Air Liquide) Contact to Leak-tight contact takes place on the thread of the fitting, and is ensure achieved due to the conical shape of the fitting and requires tightening leak- to a certain level of torque. tightness To reduce friction upon mounting and to improve the leak-tightness of the system, a Teflon tape is applied on the thread. Proper application of the Teflon tape is required to achieve leak-tightness. Failure This kind of sealing mode requires a strong tightening torque of the modes fitting to obtain tightness. and Failure modes: associated safety Rupture of fragile cylinder neck (e.g. small cylinder, weaker materials, e.g. aluminum) due to excessive torque measures Leaks due to undertightening or to damages on the threaded 11 © HyFacts 2012/13 – CONFIDENTIAL – not for public use area Safety measures: Use additional Teflon of great quality on the threaded surface to improve tightness of this kind of connection Limit mounting-dismounting cycles. Advantage Advantage: this kind of fittings is robust and unlikely to leak after proper s/ assembly: if leaktight, will stay leaktight. drawbacks Drawback: it is not suitable for frequent dismounting/remounting. Cylindrical thread connection with O-ring sealing Leak-tight contact takes place thanks to an O-Ring located between the top surface of cylinder neck and the valve. This connection is more suitable than the tapered connection for dismounting / remounting, but it is more prone to un-tightening and leakage in service. This connection is widely used in North America. b. Tubing connections and fittings Compression fittings (also called double ring fittings) Table 2: Compression fittings (Source: Air Liquide and website of Swagelok®) Examples of Swagelok® and Rotarex® providers Range of applications Pressure ranges: Up to 420 bar with “classical” tube fittings for a 6 mm external diameter tube (fittings provided by Swagelok ® or Rotarex® for example) Up to 1034 bar with Swagelok® medium pressure tube fittings for a ½’’ external diameter tube 12 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Example of application: mainly used for tube connections in hydrogen energy based systems (for the medium and high pressure sections). Picture Nut Back ferrule Front ferrule Union Figure 8: Classical double ring tube fitting (Rotarex® or Swagelok®) (Source: website of Swagelok®) Contact to ensure leaktightness For a classical double ring tube fitting using conical ferrules: As the nut is turned, the back ferrule radially applies an effective tube grip. The tightening of the nut on the main part of the fitting also creates a force on the back ferrule which axially advances the front ferrule. This front ferrule then comes into contact with the main part of the fitting and creates a seal against the fitting body, on the tubing outside diameter. The leak-tightness takes place mainly on the conical surfaces of the fitting. The surface where the conical ring and the tube come into contact reinforces the tightness by assuring the tube grip. Failure modes Failure modes: and associated Extraction of tube – due to improper mounting plus traction safety measures Leak between Front ring and Union – due to damaged or unclean surfaces, or leaks due to undertightening 13 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Safety measures: Follow the manufacturer’s mounting recommendations Use of specific gauge in order to check the tightening Limit mounting-dismounting cycles. Advantages / Advantage: this kind of fitting is highly reliable, simple to assemble drawbacks and not affected by vibrations. Drawback: it has a severe failure mode – i.e. extraction of tube - if not properly assembled (e.g. lack of rings, wrong order, use of impropriate rings, not sufficiently tightened). This point has been improved for medium pressure fittings by a pre-assembly cartridge providing the ferrules in the right way. Threaded ring tube fittings Table 3: Threaded ring tube fittings (Source: Air Liquide) Examples of Maximator, NOVA SWISS, SITEC providers Range of Suitable for very high pressure applications (up to 1500 bar for 9/16’’ applications external diameter tubes for example) Example of application: high pressure hydrogen buffer systems for fuelling stations Picture Male nut Tube Body Threaded ring Sealing area Figure 9: Maximator® threaded ring tube fitting (Source: Air Liquide) 14 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Tube end is prepared at time of assembly after tube has been cut to the right length: threading and shaping of end of tube for leak-tight surface. Contact to The tightening of the nut on the main part of the fitting the cone- ensure leak- shaped end of the tube comes into contact with the main part of the tightness fitting. This ensures the required leak-tightness. Failure Failure modes: modes and associated Leaks – due to improper preparation of tube end, to undertightening, to an incorrect position of the screwed ring, safety to damages on the conical sealing surface by repeated measures overtightenings Safety measures: Strong tightening torque Correct position of the screwed ring: the ring must be seen through the release hole existing on the body of this kind of fitting Limit mounting-dismounting cycles. Note: for hydrogen applications (transport and/or fuel cell), silicone grease cannot be used to improve sealing. Advantages / Advantage: very robust and reliable. As the ring is screwed on the drawbacks tube, the risk of wrenching – which is the main hazard in the high pressure range – is reduced. These fittings can therefore be used for the high pressure range. Drawback: in order to ensure a good leak-tightness, the conical surface should be properly polished. This kind of fittings can be either directly bought well manufactured or it can be manufactured on-site. When it is directly bought well manufactured, a high pressure qualified welder is required. When it is manufactured on-site (threaded area for screwed ring hosting and conical sealing surface), a qualified operator is required and this operation is time-consuming. Besides, leak-tightness may be affected by vibrations. 15 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Quick connections Table 4: Quick-release fittings (Source: Air Liquide and website of Staubli®) Provider Stäubli Range of Quick-release couplings are adapted to the high pressure range applications (200-400 bar). They are appropriate fittings for frequent connections and disconnections. Picture O-ring Figure 10: Staubli® fitting (on the left) and longitudinal section of a Staubli® fitting (on the right) (Source: website of Staubli®) Contact to The contact which ensures the leak-tightness takes place on the ensure leak- gasket surface. tightness Failure modes and associated Failure modes: safety measures Large leaks from extrusion of rings – due to connection/disconnection with pressure in the connexion or when the connection is not exactly in the axis of the fitting, when the O-ring is forgotten Leaks from aging or damage to o-rings Safety measures: Use of a lyre (spiral tube) in order to provide more flexibility to position the connections correctly. 16 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Advantages / Advantage: quick-release fittings are user-friendly for applications drawbacks with frequent connections and disconnections. Drawback: vulnerability of o-rings. Leak hazards may occur when the fitting is not properly mounted (other types of fittings are preferred when there is no need for frequent connections and disconnections). References: Website of Swagelok® Website of Staubli® 17 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.2.3.3 Limitation of the extension of high pressure part Consequences of hazardous events occuring in the high pressure part of a hydrogen system are very severe. Therefore, the extension of high pressure parts inside the system should be as limited as possible, and highly secure. This can be achieved by reducing pressure as soon as practicable. Mitigation measures 1.1.2.4 Once hydrogen has been released, mitigation measures have to be taken. Limiting the amount of hydrogen released is a mitigation measure of the hydrogen release. Passive Avoid unnecessary conf inement Natural ventilation Active Active ventilation Detection and active ventilation Passive Flow restriction Active Detection and Isolation Excess flow valve H2 release Confined explosive atmosphere Passive Passive Explosion venting Separation distance Active Emergency response Strong blast effects Injury / casualty Passive Flash fire Separation distance Active Emergency response Unconfined explosive atmosphere Escalation Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Passive No ignition sources Active Detection and power shut-down Figure 11: Mitigation measures: passive flow limitation and active flow reduction / isolation devices Source: Air Liquide 18 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.2.4.1 Passive flow limitation (flow restriction) A small-diameter pipe or orifice can be used downstream of the pressure regulator which lowers the pressure of the hydrogen flow coming from the storage tank. When such calibrated pipe is used, even in the case of a hazardous hydrogen release, the flow of hydrogen is limited. This maximum flow of hydrogen through the calibrated pipe can be calculated. When the absolute source vessel pressure is at least 1.7 to 1.9 times as high as the absolute downstream ambient atmospheric pressure, the maximum4 mass flow rate of hydrogen through the calibrated orifice is then: Equation 3 Or: Equation 4 Where: Q = mass flow rate (kg/s) C = discharge coefficient, dimensionless (usually about 0.72) A = discharge hole area, i.e. section of the calibrated orifice (m²) κ = cp/cv of the gas, with cp the specific heat of the gas at constant pressure and c v the specific heat of the gas at constant volume ρ = real gas density at P and T (kg/m³) P = absolute upstream pressure (Pa) M = the gas molecular mass (kg/kmol) R = the Universal Gas Constant = 8,3145 J.mol-1.K-1 T = absolute upstream gas temperature (K) Z = the gas compressibility factor at P and T (dimensionless) Note: These formulas do not take into account the pressure drop along the piping length. 4 This flow rate is the initial instantaneous flow rate from a leak in a pressurized gas system or vessel. It is much higher than the average flow rate during the overall release period because the pressure and flow rate decrease with time as the system or vessel empties. It is therefore the maximum hydrogen flow rate. 19 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Knowing the maximum allowed hydrogen flow rate, the section of the calibrated pipe can be calculated. Note: a small-diameter pipe could also be used directly downstream of the storage tank, but it would be less convenient. Indeed, the pressure of the storage tank decreases when emptying the tank. The diameter of the pipe should then be small (to limit the hydrogen flow), but yet enough large so that the hydrogen flow rate is sufficiently high - even when the storage tank pressure is low. It is therefore more effective to use a small-diameter pipe downstream the relief valve. 1.1.2.4.2 Active flow reduction / isolation devices Two active mitigation measures aiming at interrupting the hydrogen flow exist: The excess flow valve is a valve which closed itself as soon as the hydrogen flow rate is too high. Its major drawback is that the valve might close inappropriately, as high instantaneous flows within the system may be normal in certain phases of operation. A more sophisticated active mitigation device consists in the combination of a sensor (such as a hydrogen sensor, or a pressure sensor) with a valve. As soon as an incident is detected, the valve is automatically closed. Such a measure is applied in hydrogen dispensing applications in case of hose failure. 20 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.3 Prevention of ignition sources Passive Avoid unnecessary conf inement Natural ventilation Active Active ventilation Detection and active ventilation Passive Flow restriction Active Detection and Isolation Excess f low valve H2 release Confined explosive atmosphere Passive Passive Explosion venting Separation distance Active Emergency response Strong blast effects Injury / casualty Passive Flash fire Separation distance Active Emergency response Unconfined explosive atmosphere Escalation Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Passive No ignition sources Active Detection and power shut-down Figure 12: Mitigation measure: prevention of ignition sources Prevention of ignition sources only reduces the likelihood of ignition, as hydrogen may ignite even when efforts have been made to eliminate electrical of mechanical ignition sources. 1.1.3.1 Introduction In the United Kingdom, the Health and Safety Executive (HSE) regulates COMAH 5 sites. The COMAH sites are divided into hazardous areas. The hazardous areas are broken into three classes, which are defined according to the likelihood and duration of presence of flammable gas or vapour (Health and Safety Executive, 2012a): Zone 0: An area where an explosive gas atmosphere is present continuously or for long periods Zone 1: An area where an explosive gas atmosphere is likely to occur in normal operation 5 COMAH = Control of Major Accident Hazards; sites are ranked in accordance to how much dangerous substances are stored on-site. 21 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Zone 2: An area where an explosive gas atmosphere is not likely to occur during normal operation, or if it occurs will only exist for a short period Unclassified zones are referred to as safe areas. Attempts have been made to try to quantify the duration of presence of an explosive atmosphere to aid in assigning the correct zone classification for a part of plant. However, there is no consensus on how many hours constitute long or short period of presence of an explosive atmosphere. The HSE website quotes the following commonly used durations of presence of explosive atmosphere: Zone 0: more than 1000 h, Zone 1: more than 10 h but less than 1000 hr and Zone 2: less than 10 h (Health and Safety Executive, 2012a). The Dangerous Substances and Explosive Atmospheres Regulations was introduced in 2002 (Her Majesty’s Stationary Office, 2002) and made it a legal requirement to carry out a hazardous area study and report the conclusions. Any equipment used in a zone 0 area has to be intrinsically safe. The equipment has to be certified by a notified body in order to get it marking. However, equipment might well be intrinsically safe when it was installed, but correct regular maintenance will also be required to ensure that the equipment remains intrinsically safe. 22 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.3.2 Control of ignition sources There are a number of potential ignition sources. Table 5 lists these sources, in no particular order (Health and Safety Executive, 2012a). It is not claimed that the list of ignition sources is exhaustive, but it does cover a great many of the likely sources. Table 5: Potential sources of ignition Flames Direct source of space or process heating Use of cigarettes/matches Cutting and welding flames Hot surfaces Heated process vessels, like dryers Hot process vessels Space heating equipment Mechanical machinery Electrical equipment and lights Spontaneous heating Friction heating or sparks Impact sparks Sparks from electrical equipment Stray currents from electrical equipment Electrostatic discharge sparks Lightning strikes Electromagnetic radiation of different wavelengths Vehicles, unless specially designed or modified are likely to contain a range of potential ignition sources Daycock and Rew compiled a list of ignition sources and identified their strength, frequency and density (Daycock and Rew, 2004). The authors stressed that it was a first attempt, but it complements nicely the list presented by HSE. These two lists should identify the majority of potential ignition sources and should serve as a good starting point when looking at a specific plant. 23 © HyFacts 2012/13 – CONFIDENTIAL – not for public use There are a number of measures that can be undertaken in order to eliminate or at less reduce the risk of ignition; the list below has been compiled by the Health and Safety Executive (Health and Safety Executive, 2012a): Using electrical equipment and instrumentation classified for the zone in which it is located. New mechanical equipment will need to be selected in the same way; Earthing of all plant/equipment; Elimination of surfaces above auto-ignition temperatures of flammable materials being handled/stored (see above); Provision of lightning protection; Correct selection of vehicles/internal combustion engines that have to work in the zoned areas; Correct selection of equipment to avoid high intensity electromagnetic radiation sources, e.g. limitations on the power input to fibre optic systems, avoidance of high intensity lasers or sources of infrared radiation; Prohibition of smoking/use of matches/lighters; Controls over the use of normal vehicles; Controls over activities that create intermittent hazardous areas, e.g. tanker loading/unloading; Control of maintenance activities that may cause sparks/hot surfaces/naked flames through a Permit to Work System; Precautions to control the risk from pyrophoric scale, usually associated with formation of ferrous sulphide inside process equipment; Control of static electricity might require change of material in workers’ overalls and adoption of antistatic footwear. Physical separation of ignition sources, such as welding, flames or hot working, and the explosive atmosphere is desirable (Nolan, 1999). However, the ambient wind conditions and layout of the plant greatly influences the dispersion of a flammable gas cloud and hence physical separation might not always be possible. In addition, battery powered devices, for example cameras and mobile phones, and radio transmitters have also been identified as potential ignition sources (Commonwealth of Australia, 2006). What is not covered in the list above is to do with human factors and training and supervision of personnel. The training should not just entail safe use of equipment, but also an appreciation of the safety climate. The Health and Safety at Work etc. Act of 24 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1974 places responsibility for the health and safety on both the employer and the employee/contractor (Her Majesty’s Government, 1974). The permit to work system is the main control measure during commissioning or maintenance, when the hazardous area classification might not be valid (Leroux, 2012). A Permit to Work system is not fool proof, if it not adhered to. There may also be issues at the change of shift—is all relevant information passed on the on-going shift team? An exhaustive assessment of the benefits and limitations of the permit-towork system have been considered (Daycock and Rew, 2004). Some of the issues with the permit-to-work systems were: i) lack of planning of the operation, ii) inadequate or permit-to-work system in place, and iii) permit-to-work system in places but not followed correctly (Lees, 1996; Worsell, 1996). A number of potential reasons for failure in controlling ignitions sources have been presented (Daycock and Rew, 2004). In the case of electrical equipment, the following reasons were presented: (Daycock and Rew, 2004): i) lack of or insufficient maintenance so that the protection of the equipment fails, ii) temporary use of equipment with the wrong rating for the zone where it is being used, and iii) changes to the plant without updating the hazardous area classification. Any measures put in place to control ignition have to be checked at regular intervals (if appropriate), maintained correctly and replaced if faulty. References British Standards Institution (2009). BS EN 60079-10-1:2009 Explosive Atmospheres. Classification of areas. Explosive gas atmospheres. Commonwealth of Australia (2006). Draft National Code of Practice For the Control of Workplace Hazardous Chemicals, http://www2.unitar.org/cwm/publications/cbl/ghs/Documents_2ed/D_National_Doc uments_and_Legislation/267_Australia_ASCC_Code.pdf [accessed on 20 June 2012]. Daycock, J. H., and Rew, P. J. (2004). Development of a method for the determination of on-site ignition probabilities, Health and Safety Executive Research Report No. RR226. Energy Institute (2005). IP15 Area classification code for installations handling flammable liquids: Model code for safe practice in the petroleum industry, 3 rd edition. European Parliament (1994). Directive 94/9/EC on equipment and protective systems intended for use in potentially explosive atmospheres (ATEX), 25 © HyFacts 2012/13 – CONFIDENTIAL – not for public use http://ec.europa.eu/enterprise/sectors/mechanical/documents/legislation/atex/ [accessed on 20 June 2012]. European Parliament (1999). Directive 99/92/EC on minimum requirements for improving safety and health of workers potentially at risk from explosive atmospheres, http://eurlex.europa.eu/LexUriServ/LexUriServ.do?uri=OJ:L:2000:023:0057:0064:en:PDF [accessed on 20 June 2012]. Health and Safety Executive (2012a). Hazardous Area Classification and Control of Ignition Sources, http://www.hse.gov.uk/comah/sragtech/techmeasareaclas.htm [accessed on 20 June 2012]. Health and Safety Executive (2012b). Five steps to risk assessment, http://www.hse.gov.uk/pubns/indg163.pdf [accessed on 21 June 2012]. Her Majesty’s Stationary Office (1974). Health and Safety at Work etc Act, http://www.legislation.gov.uk/ukpga/1974/37/contents [accessed on 21 June 2012]. Her Majesty’s Stationary Office (2002). Dangerous Substances and Explosive Atmospheres Regulations 2002, http://www.legislation.gov.uk/uksi/2002/2776/contents/made/ [accessed on 21 June 2012]. Institute of Gas Engineers & Managers (2010). IGEM/SR/25 Edition 2 Hazardous area classification of natural gas installations. International Electrotechnical Commission (2009). IEC 60079-10-1 Classification of areas—Explosive gas atmospheres. Lees, F. P. (1996). Loss Prevention in the Process Industries, Volume 2, 2nd edition. Butterworth-Heinemann, Oxford, Oxfordshire, United Kingdom. Leroux, P. (2012). Area Classification. Why? Where? How? Who? When?, http://www.iecex.com/dubai/speakers/Day%202_08300915_IECEx_Dubai_Area_Classif_final_Leroux_P.pdf , [accessed on 21 June 2012]. Nolan, D. P. (1999). Handbook of fire and explosion protection engineering principles for oil, gas, chemical, and related facilities, William Andrew Publishing, Norwich, New York, USA. Sherwen, S. (2012). The control of ignition sources arising from gas processing machinery, Scandic Antwerpen Conference, 22-24 February 2012, Antwerpen, Belgium. Worsell, N. (1996). Risk of Ignition of Explosive Atmospheres. Health and Safety Laboratory Report No. RAS/96/13. 26 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.4 Detection Passive Avoid unnecessary conf inement Natural ventilation Active Active ventilation Detection and active ventilation Passive Flow restriction Active Detection and Isolation Excess f low valve H2 release Confined explosive atmosphere Passive Passive Explosion venting Separation distance Active Emergency response Strong blast effects Injury / casualty Passive Flash fire Separation distance Active Emergency response Unconfined explosive atmosphere Escalation Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Passive No ignition sources Active Detection and power shut-down Figure 13: Mitigation measure: hydrogen detection An important aspect of minimizing the risk of fire and explosion is the use of detection methods to give advance warning of a potentially hazardous situation, for example arising from a leak or combustion of fuel. These detectors must be effective and reliable, because of the safety critical nature of the application, and inexpensive, to ensure their widespread use. Both fixed location (for gas and fire detectors) and personal or hand-held monitors (typically for gas detectors only) are necessary for protection of personnel and plant. Additionally, there may be a requirement to fit gas sensors on vehicles to warn of leaks (on-board sensors). Gas and fire detection methods for conventional fuels have been in use for decades and are well characterized: see for example BSI (1999) and BSI (1996) respectively. For carbon-containing alternative fuels, most of the conventional methods are appropriate; their performance in the new fuels are, however, not well known, for example sensitivity, adverse affects. Hydrogen, however, has very different characteristics to carbon-containing alternative fuels, which make it more of a challenge. Both mature and new detection technologies, which are receiving much attention, are employed. There may also be environmental pollution issues for carbon-containing fuels but for hydrogen they are non-existent as only water is produced; although CO and CO 2 are 27 © HyFacts 2012/13 – CONFIDENTIAL – not for public use generated as by-products from reforming reactions which convert carbon-containing fuels into hydrogen. However, only detectors for safety applications are considered here, not those for environmental pollution monitoring. 1.1.4.1 Detection of hydrogen leaks The applications for hydrogen sensors cover: The hydrogen generation process from carbon-containing fuel reforming or electrolysis Hydrogen storage and distribution, at production sites and filling stations; and Hydrogen fuel cell/combustion systems. These can be stationary, for example power production, or mobile, for example automotive. These systems require sensors for monitoring for the quality of hydrogen feed gas, that is to say process control (not considered further here), and the second more important system for leak detection (Jardine, 2000). The latter category may require sensors for very low level detection (trace detection in the parts per million, ppm, concentration range) and for explosion protection, where the concentration range is around the fractions of % level, around the LEL (4% v/v). Previous reviews have been reported on hydrogen sensors, for example NASA (1997) and BNFL (2003). The general characteristics of commercially available sensors for hydrogen are summarised inTable 6. The most commonly employed are catalytic and thermal conductivity sensors. These can be used for a range of gases which have different response factors. Response factors of some sensors, expressed as a percentage of the methane factor, are shown in Table 7. For the catalytic sensor, hydrogen has a similar response factor to methane but there is some variation between sensor types. Table 8 tabulates values of thermal conductivity, relative to air, which indicate the relative response of the thermal conductivity sensor to these gases in the presence of air. Hydrogen has a very high value compared to air which makes for high sensitivity and a detection limit of around 200 ppm, depending on the environment. Typical performance data from commercially available hydrogen sensors are detailed in Table 9. None of the above commercially available hydrogen sensors is completely suitable for its intended purpose. This and the potentially large market, particularly in North America, for such a sensor has led to much development of novel hydrogen sensors. A summary of the various new types of hydrogen sensor is given in Table 10. 28 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Pressure drop in the system: Leaks may be detected by sudden drops in pressure. However, the smallest fugitive leaks will go undetected, as these may not cause a large enough pressure drop to raise the alarm. A number of so-called smart tapes or smart paints have been developed. These materials reveal a leak of hydrogen by changing color. Thus it is possible to detect minute leaks at joints and flanges. These leaks fall into the category of foreseeable leaks so placement of the tap or paint is fairly straightforward. 29 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.4.2 Detection of flammable mixtures Table 6: Hydrogen sensors—general properties of commercially available monitors Type Operating principle Hydrogen oxidation at platinum sensing Electrochemical electrode, oxygen reduction at counter Advantages Quite selective Sensitive to 100 electrode generates current, ie fuel cell. Disadvantages Comments Some cross-sensitivity to ppm CO (for example 1000 Potentially very low cost, compare with domestic CO. But Very low power ppm H2 300 ppm CO) CO interference may require additional protection of personnel against CO. consumption – Narrow temp range no heating Short lifetime (2 years) Affected by total gas Poison resistant Wide detection pressure (for example range altitude) Thin-film Reversible resistance hydrogen increase of heated, sensor (Robust temp controlled Pd/Ni Rapid response Hydrogen thin film, used in Does not require SensorTM) Wheatstone bridge. oxygen Poisoned by CO, SO2, H2S Developed by Sandia Labs (Sandia, 2003). Commercialised by H2scan (formerly DCH; see ref. H2scan, 2005). Not inherently expensive technique. As more in use and with competition, price should drop. Heating introduces intrinsic safety problems which increase cost. Initial devices had Heating required to ca poor reproducibility. 150°C ChemFETs Pd/Ni thin film (forms part of deposited on the gate the Robust of a field effect Hydrogen transistor (FET), SensorTM) forming an MOS Does not require Affected by total gas Developed by Sandia Labs (Sandia, 2003). Commercialised oxygen pressure (for example by H2scan. Not inherently expensive technique. As more in Wide detection altitude) use and with competition, price should drop. Heating Poisoned by CO, SO2, introduces intrinsic safety problems which increase cost. H2S Initial devices had poor reproducibility. range Low power 30 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Type Operating principle Advantages capacitor. Hydrogen consumption Disadvantages absorption changes Comments Heating required to ca 150°C charge (capacitance) on gate which is detected sensitively. Catalytic oxidation on bead heated to 450 °C, temp increase sensed with platinum Catalytic resistance thermometry. Detector Acceptable Not selective High power consumption – Mature technology but intrinsic safety issues leading to heating higher cost. lifetime and compensator form Wide temp Requires 5-10% oxygen Although adaptation has led to a higher sensitivity and range Poisoning by Pb, Si, P, S specific sensor (RKI, 2001). High maintenance two arms of Wheatstone bridge. High thermal Quite selective conductivity of Long term Cross-sensitive to helium stability Not as sensitive as Mature technology but intrinsic safety (IS) issues leading to electrochemal/chemFETs higher cost. Still a reliable and proven technique. Thermal hydrogen changes conductivity relative heat loss of a Poison resistant pair of heated Does not require elements. Semiconductor Surface conductivity change of metal oxide Heating required Commercially Not selective Very low cost but reliability and IS issues. Not generally available with High power consumption – favoured for quantitative measurements. oxygen 31 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Type Operating principle Advantages semiconductor plus acceptable catalytic additives lifetime heated to 300°C. Disadvantages Comments heating Sensitive to humidity and temperature Wide temp range Mass spectrometry: molecules ionised and selected by their Mass mass/charge ratio by a spectrometry magnetic or quadrupole Low limit of detection expensive bulky fragile needs skilled operator Analytical tool. Not cost-effective for routine monitoring. specific Not susceptible not specific to hydrogen Ultrasonic emission to poisons, interference from from gas escaping from humidity etc only a high-pressure pipe. leak properties field. Ions detected by sensitive charge detector. Ultrasonic Non-directional? background noise only detects high pressure leaks 32 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Cannot measure whether a flammable mixture is present. Table 7: Response factors (% relative to methane*) of various catalytic and infrared flammable gas sensors to hydrogen and carbon-containing fuel fuels LEL (%) Infrared Catalytic Drager City Technology Drager City Technology RaeSystems IR Ex HC- IrceL HC Cat Ex C MICROpeL 75 LEL Hydrogen 4.0 nd nd 100 125 91 Gasoline (unleaded) 1.4 - 157 51 55 48 No.2 Diesel Fuel 1.0 - - - - - Methanol 5.5 469 357 63 105 67 Ethanol 3.1 406 257 63 80 59 - - 51 - - MTBE (up to 7% in Gasoline) n-Butane 1.4 344 257 46 70 50 Propane (LPG) 1.7 313 286 51 60 63 Compressed Natural Gas (Methane) 5.0 100 100 100 100 100 Table 8: Thermal conductivity of gases relative to air Thermal conductivity Gas/vapour = 0 °C = 100 °C Air 1.00 1.00 Methane 1.25 1.45 Propane 0.58 0.70 Butane 0.55 0.66 Hydrogen 7.0 6.8 33 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Helium 5.9 5.5 Water 0.66 0.74 Methanol 0.5 0.7 Ethanol 0.5 0.7 Table 9: Hydrogen sensors—typical performance characteristics of commercially available monitors Type Electrochemical Range Resolution 0-0.2%; 0-2% 2-10 ppm ‘Robust Hydrogen Sensor’ that is to say Chemresistor/chemFET 0.1-100% (s) (yr) 30 1-2 5 ? 10 ppm with ChemFET ChemFET 0-100% LEL 1% LEL 20 3 0-10% 0.5% range 20 10+ 50-5000 ppm 50 ppm 30 ? Thermal conductivity Semiconductor Lifetime 0.1% 10-1000 ppm with Catalytic Response time Table 10: Hydrogen sensors—general properties of monitors under development6 Type Operating principle Advantages Thick-film hydrogen Resistance change of a Pd resistor Potential low cost. sensor formed on a ceramic substrate using Simple method 6 This table will need to be updated for the second draft of this document. 34 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Disadvantages Poisoned by CO, SO2, H2S Comments Developed by Oak Ridge National Lab. Type Operating principle Advantages Disadvantages Comments thick film deposition techniques. Four (ORNL, 2005) Pd resistors are used – two coated Cost target is with a H2-impenetrable film in a < $50. Promising Wheatstone bridge. development close to commercialisation. Several types of system including: Change in optical characteristic of a mixed metal oxide (eg V2O5/WO3) on an optical fibre (Griessen et al., 2004). Mg-Ni alloy reflective mirror in air, black absorber in H2 (Butler, 1994). Optoelectronic Interferometry – Pd wire consumption interferometry. Surface Plasmon Resonance: a Immune to electromagnetic reversibly stretches in H2. Deformation is detected using Very low power interference Intrinsically safe in explosive atmospheres thin palladium layer is deposited on the bare core of a multimode fibre. Modification of the SPR is due to variation in the complex permittivity of Pd in contact with 35 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Temperature and relative humidity effects At prototype stage. Type Operating principle Advantages Disadvantages Comments gaseous hydrogen. Bragg grating: mechanical stress induced in a Pd coating when it absorbs hydrogen. The stress in the Pd coating stretches and shifts the Bragg wavelength. PdAg, PdCr or Pd/InGaP diode characteristics altered by H2 sorption. For PdAg, the diode Operating temperature structure is composed of three is layers: a Pd13%Ag catalyst metal film on a SiO2 oxide layer which MOS Schottky diodes is adherent to a n-type Si Low concentration (15 < 100 °C and < 2% H2. ppm) can be detected. PdAg system Operates in inert or Oxygen affects response developed by NASA substrate. Hydrogen dissociates oxygen-containing Lewis and Case on the surface of the metal and environments Western Reserve migrates to the interface between University. (NASA the metal and the oxide. The Lewis, 2001) resulting dipole layer changes the electronic properties of the diode. 36 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Type Operating principle Disadvantages transmittance changes of a Pd embraces a wide unproven unproven Surface acoustic wave (mass) range of technologies based on polymer nano-composite films Comments Nanotechnology Electrical resistance (DiMeo et al., 2003) and optical Nanotechnology Advantages nanomaterials. selective sorption onto a layer eg WO3, carbon nanotubes, changes the resonance frequency of the oscillator Low power microscale substrate (eg quartz, LiTaO3). 37 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Susceptible to water vapour Unlikely to compete with the above techniques. 1.1.4.3 Detection of hydrogen flames Fire detectors are the second step in the detection chain for minimising the risk of death, injury, damage and loss of production due to the flammability/explosibility of fuels. Gas detection is the first step but is not totally reliable or cannot, for example due to lack of 100 % coverage, prevent a fire from starting. It is therefore usual for the industry to install both types of detector. Fire detectors are typically installed in similar situations, but not necessarily in the same location, as fixed gas detectors. Certain types of fire detectors (optical, see below) have the advantage of being able to cover effectively large areas which would be impossible with a gas detector system, with either single or multiple detectors. The fuel industries are constantly in need of reliable and fast response fire detection systems. Additionally, the system should be able to locate the event quickly and reliably. The smaller the fire, when detected and located, the easier it is to extinguish. The fire detection system is typically configured to provide an audible/visual alarm and/or activate a fire suppression system. There are various approaches to detecting a fire (see for example Liu & Kim, 2003), based on: Heat detection Frangible bulbs (activate directly fire-water deluge valves) Fusible plugs Rate compensated heat detectors Linear heat detection (cables routed through fire risk areas); Ionisation smoke detection; Optical smoke (obscuration/line-of-sight) detection; Gaseous products of combustion detection, eg CO, volatile organic compounds; Optical flame detection (IR and UV and combined IR-UV). High speed and high sensitivity smoke detection - addressable point optical systems and aspirated optical systems (eg Very Early Smoke Detection Apparatus VESDA) CCTV based systems. Fire detectors use a variety of algorithms to process the sensor data in order to identify fires and reduce false alarms. Examples of techniques used in the analysis are: Flicker frequency between 1-10 Hz Threshold signal comparison Correlation between several signals Comparisons for example ratio, AND/OR gates Comparison with spectral library. 38 © HyFacts 2012/13 – CONFIDENTIAL – not for public use This report is concerned principally with optical instrumental methods as they are becoming the most prevalent, and are the most effective when monitoring over large areas. Background information on the principles of operation of optical detectors can be found for example in Liu and Kim (2003) and references therein, and on the websites of manufacturers such as Spectrex (2005) and Micropack (2005). Again, as with gas detectors, fire detectors can be conveniently split into those for hydrogen and those for carbon-containing fuel fires because of the very different characteristics of hydrogen flames. The general characteristics of commercially available hydrogen fire detectors are summarised in Table 11. Depending on the choice of wavelength the detectors can be used to detect not only hydrogen, but also carbon-containing fuels, while the triple IR is selective to hydrogen, ethanol and methanol but not carbon-containing fuels. Table 11: Hydrogen fire sensors—general properties of commercially available monitors Type Operating principle Advantages Disadvantages Comments False alarms, for Analysis of UV emissions in Very high solar blind speed region (< 300 High nm) at high sensitivity speed, typically Low cost around 200 nm. example lightning, Can detect arc welding, hydrogen, radiation, specific methanol and solar radiation not ethanol and absorbed by the other alternative atmosphere carbon- Blinded by thick containing fuel smoke and fuel fires. vapours UV/IR Detection based Moderate False alarms, for on a solar blind speed example Can detect UV sensor Moderate combination of hydrogen, (around 200 nm) sensitivity UV and IR methanol and and an IR Low false sources. ethanol and sensor (over alarm rate, not Blinded by thick other alternative region 1-3 µm). blinded by smoke and carbon- The IR sensor CO2 fire vapours containing fuel reduces false protection Moderate cost fires. alarms from use discharges 39 © HyFacts 2012/13 – CONFIDENTIAL – not for public use of UV only. Automatic self test Spectral and flame pattern Triple IR Detects analysis from IR Very high bands in the sensitivity H2O emission Very high region (1-4 µm) speed hydrogen, Moderate cost ethanol and methanol but not hydrocarbon fuel and reference flames. regions. Superimposes IR/vis imaging flame image Images the from 2 CCDs in flame the near-IR and Systems in visible onto a use at NASA colour video Stennis image. Developed by NASA and Moderate cost Duncan Technologies Inc. (NASA, 2000). Careful choice of fire detector is required because of the wide variety of types available. The choice is determined by the type of fire, for example hydrogen, alcohol, or hydrocarbon fuel, and the application and environment, as these affect the type of detector (for example point, optical) and potential interferences, especially for optical detectors. Guidance on fire detectors can be found in the BS EN 54 series (BSI, 1996). Various rules of thumb are used to determine the location and coverage of the different types of fire detector. For example in offshore modules, point heat detectors in open, naturally ventilated areas are sited at approximately a density of 1 per 25 m 2 and at spacing of 7 m with a maximum distance from bulkheads of 3.5 m. In enclosed, mechanically ventilated modules, they are sited at approximately 1 per 37 m 2 and 9 m apart with a maximum distance from bulkheads of 4.5 m. They are not applied in areas with high ceilings above 8 m (point heat detectors have poor sensitivity with height). However they do still need to be located at high level as heat rises. Heat shields can be used when they are not under a solid ceiling to improve heat build up. Optical flame detectors are sited such that their vision cone covers areas where fire may occur. For IR flame detectors around 15 m is considered a reasonable range because of obscuration by smoke and lack of sensitivity at the periphery of their field of view. They are generally sited at the corners of an area. CAD tools are used to optimise their coverage at the design stage and assess the effectiveness of current installations (Shell Global Solutions, 2005). 40 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Point smoke detectors rely on transport of products of combustion (particulates and gases) to the detector by convection. The numbers of detectors can be reduced with increased ceiling height because of more uniform distribution, although the concentration will be less and the sensitivity of the detectors must be adequate. In offshore applications, current smoke detectors are located not more that around 7.5 m apart and not appropriate for high ceilings (>10.5 m). They are also located just below the ceiling. Open path smoke detectors need to be at high level to avoid obstruction, eg above 3 m. Smoke detectors in ventilation ducts should be located to avoid the effects of turbulence, ie in a straight length away from bends. References: Bechtold, R. L. (1997) Alternative fuels guidebook. SAE, Pa, USA. BNFL, (2003) Design Guide for: Hydrogen sampling and measurement. The sampling & measurement of gaseous hydrogen in active and non-active applications, BNF.EG.0053_5_A. BNFL Commercial. Brett, L. (2003) Hydrogen safety sensors and their applications in hydrogen storage, distribution and use. http://www.jrc.cec.eu.int BSI (1999) BS EN 50073 : 1999 BSI London. BSI (2000) BS EN 61779 series. BSI London. BSI (2002) BS EN 61508 BSI London. BSI (1996) BS EN 54-1: 1996 Fire detection and fire alarm systems. Introduction. BSI London. Butler, M. A. (1994) Micromirror optical-fibre hydrogen sensor. Sensors and Actuators, B22, 155-163 Concawe (1995) Alternative fuels in the automotive market. Report no. 2/95. CONCAWE, Brussels. DiMeo, F. et al (2003) Micro-machined thin film H2 gas sensors. http://www.eere.energy.gov/hydrogenandfuelcells/pdfs/viib5_dimeo.pdf Ferree, S. (2003) Gas detection for alternate-fuel vehicle facilities. Occupational Health & Safety. May 2003, 68-75. Griessen, R. et al. (2004) Optical fibre hydrogen sensors. http://www.nwo.nl/nwohome.nsf/pages/SPES_5RUFNL H2scan (2005) Details on Robust hydrogen sensor. http://www.h2scan.com HSE (2004) HSG243 (2004) Fuel cells Understand the hazards; control the risks, HSE Books. Jardine, A.P. (2000). Hydrogen sensors for hydrogen fuel cell applications. http://www.powerpulse.net/powerpulse/archive/pdf/aa_111300a.pdf 41 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Knight, B. A. et al (2003) Development of sensors for automotive fuel cell systems. http://www.eere.energy.gov/hydrogenandfuelcells/pdfs/viib4_knight.pdf Liu, Z., and Kim, A. (2003) Review of recent developments in fire detection technologies. J. Fire Protect. Engin. 13, 129-151. Micropack (2005) http://www.micropack.co.uk/ NASA (1997) Safety standard for hydrogen and hydrogen systems. Guidelines for hydrogen system design, materials selection, operations, storage, and transportation. Ch 6. Hydrogen and hydrogen fire detection. Office of Safety and Mission Assurance, Washington DC. NASA (2000) http://technology.ssc.nasa.gov/suc_sbir_hyd_flame_imaging.html NASA Lewis (2001) PdAg Schottky diode. http://www.sensorsmag.com/articles/0401/14/main.shtml ORNL (2005) Low-cost, thick film hydrogen sensors. http://www.ornl.gov RKI (2001) Hydrogen gas detector for fuel cells. http://www.fuelcellsensor.com Sandia (2003) New hydrogen sensor is small, rugged, and inexpensive. http://www.sandia.gov/mstc/technologies/microsensors/hydrogensensor.html Shell Global Solutions (2005) http://www.shellglobalsolutions.com/products_services/flame.htm Spectrex (2005) http://www.flame-detection.com and http://www.spectrexinc.com Van Well, Murray, S., Hodgkinson, J. et al. (2005) An open-path hand-held laser system for the detection of methane gas. J. Opt. A. 7, S420-424. Vesda (2005) http://www.vesda.com/ Zalvidea, D. et al. (2004). Wavelength multiplexed hydrogen sensor based on palladium-coated fibre-taper and Bragg grating, Electronics Letters 40, 301302. 42 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.5 Prevention of flammable/hazardous mixtures by means of ventilation Passive Avoid unnecessary confinement Natural ventilation Active Active ventilation Detection and active ventilation Confined explosive atmosphere Passive Flow restriction Active Passive Explosion venting Active Emergency response Strong blast effects Injury / casualty Passive Flash fire Detection and Isolation Excess f low valve H2 release Passive Separation distance Separation distance Active Emergency response Unconfined explosive atmosphere Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Escalation Passive No ignition sources Active Detection and power shut-down Figure 14: Mitigation measure: ventilation 1.1.5.1 Dispersion of hydrogen in enclosures – summary In the case of a hydrogen release in an enclosed area 7, a flammable mixture might form. The formation of this hazardous mixture is determined by the hydrogen dispersion (see details in the section Error! Reference source not found.). 7 A roofed area with less than 1/3 of the structure perimeter open to the outdoors shall be considered as an enclosed area. 43 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Dispersion regimes in a closed unventilated room Different dispersion regimes occur when hydrogen is released in a closed unventilated room. Gaseous hydrogen releases are characterized by the Richardson number Ri0: Ri 0 g. a 0 R0 . 2 0 U0 Equation 5 With: U0: release velocity (m.s-1) R0: radius of the releasing orifice (m) ρa: ambient density (kg.m-3) ρ0: released gas density (kg.m-3) g: the gravitational constant (9,81 m.s-2). If the Richardson number is larger than the unity, gravity effects are dominant, the hydrogen flow is a pure plume and its dispersion is said to be buoyancydominant. The plume develops vertically up to the roof where it is deflected horizontally up to the walls. A horizontal interface is formed on the section of the enclosure. In the upper part of the enclosure, the injected gas build-ups and the density increases gradually from the interface to the roof. If the Richardson number is lower than the unity, the momentum dictates the mixing, overturning is induced and the hydrogen flow is a jet. Several dispersion regimes can be distinguished, according to the volumetric Richardson number Riv of the hydrogen jet (see details in section Error! Reference source not found.). If Riv is very small compared to 1, there is a homogeneous concentration in the enclosure. If Riv has a very large value compared to 1, a continuous concentration distribution is obtained in the enclosure. If Riv has an intermediate value: a stratified profile with a homogeneous upper layer is observed. 44 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Dispersion regimes in an enclosure ventilated with a single or two openings The presence of ventilation in an enclosure has an influence on the dispersion regimes of hydrogen: In the case of a buoyant-dominated or momentum-dominated release in an enclosure with one opening, a well-mixed regime is observed. When two openings are present in an enclosure (on the lower and upper parts) in which a buoyant-dominated release is occurring, a ventilation mode called displacement ventilation takes place in the volume. This displacement ventilation comes along with a homogenous layer in the upper part of the enclosure and stratification in the lower part. For larger momentum release, the concentration becomes well mixed in the enclosure. Note 1: see the figurative schemes in section Error! Reference source not found. for the conditions under which the models are valid. Note 2: external wind conditions, that is to say the direction and speed of the ambient wind can play a very important role in the venting and dispersion regimes. See details in section Error! Reference source not found.. 1.1.5.2 Safety objectives and criteria Safety targets are defined, allowing designing the means of protection against hazards specifically resulting from use of hydrogen in enclosures: 45 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Leak scenario Leak scenario Leak scenario • Hypothesis • Model • Consequences Safety Targets Safety Targets Safety Targets Safety strategy of the application Means of protection Figure 15: Definition of safety targets Source: HyIndoor project, WP1: Scenario, objectives, and project expected outcomes, May 2012 Safety objectives (frequency limit for feared event) are translated into practical design objectives (see section Error! Reference source not found.): For expectable leaks, there should be no damage. For foreseeable leaks, there should be no possible material damage. For conceivable leaks, mitigation actions should be taken to avoid destruction of the system. The formation of a flammable atmosphere can be allowed as long as the destruction of the system or hazardous effects outside of the system are avoided. In this objective, the hydrogen concentration should be limited to a determined value. No design objectives are set for unlikely feared leaks. There is no specific measure other than prevention (material choice...) and for emergency responses. 1.1.5.3 Review of ventilation configurations To prevent the formation of flammable mixtures and hence meet the safety objectives, effective ventilation of enclosed spaces should be provided. Several ventilation configurations exist: one opening, two openings. Enclosures with two openings allow for better ventilation than enclosures with one opening. 46 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Design and sizing of natural ventilation (for a given leak size) 1.1.5.4 An enclosed area where hydrogen may be released should be ventilated by openings, in order to prevent the formation of an explosive atmosphere. If possible, two openings at least should be provided: one in the upper part of the enclosure, the other in the lower part - the latter conditions are essential for effective natural ventilation. Example of design and sizing of natural ventilation, when two openings can be provided: 1. The flow rates of the foreseeable hydrogen leaks are assessed. 2. Models described in sections Error! Reference source not found. and Error! Reference source not found. are used in order to size the openings. Note: external wind conditions, that is to say the direction and speed of the ambient wind can play a very important role in the venting and dispersion regimes. See details in section Error! Reference source not found.. 1.1.5.5 Forced ventilation A forced ventilation system can be included in a hydrogen system, if the natural ventilation is not sufficient or not reliable. The design of the forced ventilation system can be based on the model described below. Two openings are present on the enclosure pictured on the Figure 16. In the upper part of the enclosure, a ventilation system extracts air at the ventilation flow rate Qv. This induces a depressurization in the enclosure, which makes air come into the system through the opening on the lower part of the system. In this model, the volume below the leak point does not contain any hydrogen. 47 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Ventilation Qv xV z V H2 release QS Air inlet Qv - QS Figure 16: Forced ventilation (Source: Air Liquide) The forced ventilation is designed for the steady state. At steady state 8, the hydrogen concentration is: xH 2 QS QV Equation 6 Note 1: when designing a system, it might be difficult to assess the volume V as the location of the future potential leak is unknown. The design of the system should then be based on a model where the volume V is the smallest (i.e. with the highest leak point). Indeed, the highest hydrogen concentration is reached in the smallest volume. Note 2: when designing forced ventilation, special attention has to be spent on the location of extraction (dead zones formation) and to the location of the compensating air vents. 1.1.6 Prevention and mitigation of explosions Explosion venting is a protective measure preventing unacceptable explosion pressure build-up inside confined spaces leading to enclosure destruction and formation of flying fragments. The vent can either be used: 48 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Both as a protective measure preventing unacceptable explosion pressure build-up inside confined spaces AND as a ventilation opening. In this case, the vent always stays open. Only as a protective measure preventing unacceptable explosion pressure build-up. In this case, the vent opens when the opening pressure of the vent is reached, because of the combustion of the flammable mixture. Such vent is considered in the system described in the section 1.1.6.2. Passive Passive Avoid unnecessary Explosion conf inement Natural ventilation Active Active ventilation Detection and active ventilation venting Passive Flow restriction Active Detection and Isolation Excess f low valve H2 release Confined explosive atmosphere Passive Separation distance Active Emergency response Strong blast effects Injury / casualty Passive Flash fire Separation distance Active Emergency response Unconfined explosive atmosphere Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Escalation Passive No ignition sources Active Detection and power shut-down Figure 17: Mitigation measure: explosion venting (Source: Air Liquide) 1.1.6.1 Deflagration of unconfined hydrogen air mixtures – summary and extension of hazardous effects Deflagration of unconfined hydrogen air mixtures: summary Hydrogen air mixtures are flammable when the proportion of hydrogen in this mixture ranges from 4 to 78% by volume (these values are for a hydrogen air mixture at 20°C and 1 bar). The combustion is characterized by the speed at which the thermal flame front propagates. The speed of the flame front increases with increasing hydrogen concentrations up to 40 % in the flammable zone. Different factors may speed up the flame, such as the turbulence created by obstacles or fans. 49 © HyFacts 2012/13 – CONFIDENTIAL – not for public use When a hydrogen air mixture is ignited, its temperature rises and an overpressure wave develops within the flammable zone. As showed in Figure 18, the maximum overpressure value strongly depends on the hydrogen concentration of in the mixture. This figure shows the maximal overpressure value which has been experimentally measured in an enclosure of a few cubic meters after the ignition of a hydrogen-air mixture. Figure 18: Influence of the hydrogen concentration in the mixture of the maximal overpressure value Source: Air Liquide Note: the damage threshold for structures is of 150 mbar; but it could be also lower, possibly 50-100 mbar. The integrity of the structure is highly dependent on the method of construction, its age and its state of repair. The pressure wave created by the ignition of the hydrogen air mixture propagates outside of the flammable zone, while its amplitude decreases. In the case of the unconfined explosion of a sphere from a mixture characterized by its constant flame speed, the maximum overpressure decreases as the ratio R/R 0 (with R the distance from the ignition source and with R0 the initial radius of the sphere). 50 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Maximal overpressure (hPa) Figure 19: Wave propagation during the unconfined explosion of a sphere from a mixture characterised by its constant flame speed Sf (Source: A. Lannoy L'evaluation des risques d'explosions en phase gazeuse dans l'industrie de production d'électricité Journal de Physique III 1, 8 (1991) 1359-1376) Caption: R is the distance from the ignition source and R 0 is the initial radius of the sphere Note 1: the higher flame speed, the higher overpressure. Note 2: 1 hPa = 100 Pa Ignition of a flammable gas cloud (delayed ignition so that the cloud can form) can lead to either a deflagration (a.k.a. explosion) or detonation. Deflagration is a term describing subsonic combustion; the speed of the flame front is smaller than the speed of sound in the burnt gases. In the case of detonation, the speed of the flame is supersonic and therefore generates a shock wave. Greater pressures are then generated by detonations, which are thus more destructive than deflagrations. A deflagration may become a detonation as the flame front is accelerated by turbulence (Deflagration to Detonation Transition). A detonation may also be initiated from the onset if ignition is performed with a high energy source (e.g. explosive). The explosions occurring in unconfined environments deflagrations since the ignition energies are most often small. 51 © HyFacts 2012/13 – CONFIDENTIAL – not for public use are generally Extension of hazardous effects Deflagrations of unconfined hydrogen air mixtures have overpressure and thermal effects. In the case of “small” deflagrations (i.e. when the hydrogen concentration and the ignition energy are low), thermal effects are generally more severe than overpressure effects. On the contrary, in the case of large powerful deflagrations, the extension of hazardous effects depends mostly on the value of the overpressure generated by the combustion of the flammable hydrogen air mixture. Different thresholds have been defined, depending on the severity of the overpressure effects. Extension of overpressure effects In order to determine the severity of the overpressure effects, the overpressure value shall be calculated. One shall consider that hydrogen-air mixtures containing less than 10 % of hydrogen approximately contribute to the combustion only in a small extent. Hydrogen-air mixtures containing more than 10 % of hydrogen approximately have a more significant contribution to the combustion. The overpressure value decreases with increasing distance to the ignition point. See section Error! Reference source not found. for details on the deflagration pressure decay in the far field. Extension of fire effects The area where the combustion occurs is larger than the zone where the flammable mixture was. Note: the impulse is also very important. A longer duration of low overpressure can cause more destruction than a higher overpressure but of short duration. (Source: Center for Chemical Process Safety (1994). Guidelines for Evaluating the Characteristics of Vapor Cloud Explosions, Flash Fires, and BLEVEe. American Institute of Chemical Engineers, New York, USA) 1.1.6.2 Vented deflagration phenomena – summary A system with an explosion venting is characterized by its vent area A v and the pressure Pdesign above which the building structure fails. This pressure is defined by the design of the structure. In the following section, it is assumed that there is a homogeneous distribution of hydrogen in the enclosure before ignition of the flammable mixture. Once the flammable hydrogen-air mixture has been ignited, the flame front expands 52 © HyFacts 2012/13 – CONFIDENTIAL – not for public use spherically, and then expands to an ellipsoid when it reaches the walls of the enclosure. In the case of a confined area, the gas cannot expand9: the unburned gas is compressed and the pressure starts to increase exponentially (phase (a) on the Figure 20). The pressure continues to increase due to combustion processes until it reaches the opening pressure P1 of the vent (see on the Figure 20). Figure 20: Time dependence of a vented explosion in a near-cubic vessel with an explosion relief opening at low pressure (Lautkaski, R., 1997, “Understanding vented gas explosions”, Technical Research Center of Finland) Caption: P1: opening pressure of the vent P2: pressure of the external explosion P3: pressure associated with the maximum rate of combustion within the room P4: oscillatory pressure peak At this time the unburned gas flammable mixture starts to flow out of the enclosure. The unburned gas then forms a turbulent cloud outside the vessel. If the volume production rate of burnt gases exceeds the volume rate of loss of unburnt and burnt gas through the vent, the pressure rises until the flame reaches the vent (phase (c) on Figure 20). The flame joins the turbulent cloud which burns, generating 9 When an explosion occurs in open space, the volume of gas expanses. 53 © HyFacts 2012/13 – CONFIDENTIAL – not for public use an external explosion with a high pressure P2. Highly destructive effects of the vented deflagration phenomenon may be caused by the combustion and by the propagation of the overpressure wave outside of the enclosure. Figure 21: Development of external explosion (Lautkaski, R., 1997, “Understanding vented gas explosions”, Technical Research Center of Finland) The combustion goes on within the enclosure, which still contains unburned flammable gas mixture. The pressure P3 is associated with the maximum rate of combustion within the room. It typically occurs when the flame front reaches the walls. The external explosion due to the venting of unburnt gas can generate a pressure wave propagating back into the enclosure, contributing to an additional increase of the internal pressure. The flame front interacts with the enclosure; the excitation of acoustic resonances in the gaseous combustion products within the room results in an oscillatory pressure peak P4. Note 1: influence of the ignition location The overpressure effects of the vented deflagration phenomenon depend on the location of the ignition. When the flammable mixture ignites at the back of the enclosure (on the side opposite to the vent), the pressure of the external explosion P ext is higher than when the mixture ignites in the middle of the enclosure. On the other hand, the acoustic pressure Pac is smaller. Indeed, when the flammable mixture ignites at the back of the enclosure, a smaller amount of unburned gas is left in the enclosure after that the external explosion has happened. When the flammable mixture ignites in a location close to the vent, there is almost no external explosion as the front flame propagates in the system and the unburnt gases 54 © HyFacts 2012/13 – CONFIDENTIAL – not for public use are pushed out of the vessel. The only overpressure effect comes from the acoustic peak. Note 2: size of the enclosure Depending on the size of the enclosure, the most destructive pressure can be either the external pressure or the oscillatory pressure peak. For small enclosures, the most destructive pressure occurs during the external explosion as the quantity of unburned gas still in the enclosure is smaller than in large enclosures. References: Lautkaski, R., 1997, “Understanding vented gas explosions”, Technical Research Center of Finland (VTT Tiedotteita) C. R. Bauwens, J. Chaffee and S. Dorofeev, FM Global, “Experimental and numerical study of hydrogen air deflagrations in a vented enclosure”, ISHPMIE 2008 A. Lannoy, L'évaluation des risques d'explosions en phase gazeuse dans l'industrie de production d'électricité Journal de Physique III 1, 8 (1991) 13591376 1.1.6.3 Review of vented deflagration configurations Different vented deflagration configurations exist; the location of vents and their size impact their effectiveness. The larger the vents, the better. Vents shall be located where the maximal overpressure is expected. This is most often in the upper part of the room, because of the buoyancy of hydrogen. The vent shall be located so that nobody or no equipment would be reached by the hydrogen cloud. Vents always staying open shall be preferred over closed vents whose opening is triggered when the opening pressure is reached. Indeed, in the case of initially closed vents, overpressures higher than the opening pressure are reached in the enclosure. A competition between the combustion and the opening dynamics occur. Besides, the vent effectiveness is not maximal during its opening, as the free surface of the vent gradually increases. 55 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Safety objectives and criteria 1.1.6.4 The safety objective is that the building structure does not fail if an explosion occurs in the structure. So as to assess whether this safety objective is met, the maximum pressure reached during an explosion should be calculated (this pressure being calculated with the assumption that the structure does not fail and is not even bended). If this pressure is smaller than the pressure Pdesign above which the building structure fail, the safety objective is met. If not, safety measures should be taken, so that the maximum pressure reached during an explosion gets smaller than the design pressure. Examples of safety measures (detailed in the following sections) are: 1.1.6.4.1 o Avoiding elevated hydrogen concentration o Avoiding flame accelerating factors o Properly designing the venting system. Avoidance of elevated concentrations – criteria Elevated concentrations should be avoided thanks to appropriate ventilation, to the detection and isolation of hydrogen. Note: the maximum allowed hydrogen concentration is defined by the designer of the system. The higher this hydrogen concentration is, the more difficult it is to limit the overpressure effects (see section 1.1.6.4.3). 1.1.6.4.2 Avoidance of flame accelerating factors – criteria The presence of obstacle in the enclosure will generate more turbulence and then the overpressure will be higher than in an empty room. Therefore, there should be in the enclosure as few obstacles as possible. 1.1.6.4.3 Properly designing the venting system – criteria Vents can be used to avoid any overpressure build-up. In order to be effective, the vent must be correctly designed to limit the explosion pressure below the failure pressure of the building structure. See section 1.1.6.5.2 for the calculation procedure used to design the vent (assessment of its size). 56 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 57 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Mitigation of deflagrations by venting 1.1.6.5 1.1.6.5.1 Principle Explosion venting is the most wide spread deflagration mitigation technique for enclosure. It reduces explosion-incurred pressure to an acceptable level by venting gases out of an enclosure through a vent or number of vents of sufficient area during the deflagration. 1.1.6.5.2 Design criteria The size of the vent can be calculated using the Vent Sizing Technology (VST) (Molkov, 2001; Molkov et al, 1999). The latest procedure of the VST for empty enclosures or enclosures with insignificant influence of obstacles is as follows (Molkov et al, 2009): 1. Calculate the value of the dimensionless reduced explosion overpressure red pred / pi 2. Determine the Equation 7; value of dimensionless activation pressure 3. Then calculate the value of the dimensionless pressure complex red / v2.5 v ( pstat pi ) / pi static Equation 8; Equation 9; 4. Based on the value of red / v2.5 , calculate the value of Br by using the t relevant equation: If red 1 : red 5.65 Brt 2.5 2.5 2 .5 v v If red 1 : red 7.9 5.8 Brt0.25 2.5 v v2.5 Equation 10, Equation 11; 5. Determine the appropriate values of Sui and Ei for the mixture in the enclosure using Figure 22. The correlations were calibrated against experimental data using the dependence of burning velocity on hydrogen concentrations in air from Lamoureux et al (2003). For instance, for stoichiometric hydrogen-air mixtures at an initial pressure of 1 bar and temperature 298 K the burning velocity Sui=1.96 m/s (Lamoureux et al, 2003; Tse et al, 2000) should be applied for 58 © HyFacts 2012/13 – CONFIDENTIAL – not for public use vent sizing. The corresponding value of expansion coefficient of the combustion products is Ei=6.90. The influence of the initial temperature on the laminar burning velocity can be estimated by the formula m Su i S u 0 Ti / 298 0 , where Su0 is the laminar burning velocity at 298 K, Ti 4.0 3.8 3.6 3.4 3.2 3.0 2.8 2.6 2.4 2.2 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 8.0 7.6 7.2 6.8 6.4 6.0 5.6 5.2 4.8 4.4 4.0 3.6 3.2 2.8 2.4 2.0 1.6 1.2 0.8 0.4 0.0 Laminar burning velocity Expansion ratio 0.1 0.2 0.3 0.4 0.5 Hydrogen volume fraction Figure 22 : Dependence of laminar burning velocity (Lamoureux et al, 2003) and expansion coefficient of the combustion products on hydrogen concentration in air at an initial pressure of 1 bar and temperature 298 K (Molkov et al, 2009). 59 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 0.6 Expansion ratio Laminar burning velocity (m/s) is the initial temperature; and m0 =1.7 is temperature index (Babkin, 2003). 6. Determine the vent area by solving numerically the following transcendental equation (by changing area F until the right hand side of the equation is equal to the left hand side): 0.8 F cui F 1 v 1 0.5 2 / 3 S ( E 1 ) V ui i 0.94 0.4 (1 2 V ) S u i ( E i 1) 0.4 0.4 Brt 3 36 0 V 2 / 3 cui Ei / u Equation 12 Where empirical coefficients e=2 and g=0.94, and other parameters are: Brt Turbulent Bradley number cui Speed of sound, m/s, cui = (γuRTui/Mui)0.5 Ei Expansion coefficient, Ei = MuiTbi/MbiTui F Vent area, m2 M Molecular mass, kg/mol pi Initial pressure, bar abs. pred Reduced pressure, bar gauge pstat Static activation pressure, bar gauge R Universal gas constant, 8.31 J/K/mol Sui Initial burning velocity, m/s V Volume of enclosure, m3 γu specific heats ratio Pi number, 3.14 red Dimensionless reduced pressure, Pred/Pi; v Dimensionless static activation pressure, v = (pstat + pi)/pi The correlations have been calibrated against experimental data for hydrogen-air deflagrations for the following range of conditions: L/D ≤ 5.43; V ≤ 37.4 m3; 0.005 < F/V2/3 < 0.34; 0 kPa ≤ pstat ≤ 13.5 kPa; pi =1 bar abs. 0.3 ≤ red ≤ 5. The maximum experimentally observed overpressures for initially quiescent 4-8% hydrogen-air mixture deflagrations without turbulisers are below 10 kPa (Saffers et al, 2010). Explosion pressure increases drastically for hydrogen concentrations above 60 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 8% by vol. and could reach an adiabatic explosion maximum in a closed vessel already at 9% by vol. Theoretical deflagration overpressure at 9% is about 4 bar, i.e. sufficient to destroy any building or residential structure, as they can withstand overpressure not greater than 10 kPa. Thus, deflagrations of hydrogen-air mixtures with concentration above 8% should be mitigated (Molkov et al, 2008). Let us calculate vent size for the enclosure depending on the concentration of hydrogen in air in the range 8-10.5% in assumption that the enclosure is a “standard house construction” that could withstand overpressure 10 kPa (Lees, 1996). The vent area F was calculated using (HYPER Report, 2009) with an assumption that the static activation pressure is v= (pstat + pi)/pi =1, i.e. it opens with negligible overpressure. The expansion coefficient for combustion products Ei was calculated by Cantera software [http://www.cantera.org/] using the GRI mechanism. Laminar burning velocity Sui of hydrogen-air mixtures in the range 8-10.5% were taken from (Tse et al, 2000): 10.8 cm/s for 9% of hydrogen by vol., 13.1 cm/s for 10% by vol. and 14.7 cm/s for 10.5% by vol. Minimum vent area to mitigate hydrogen-air deflagration in F, m2 the garage to the level 10 kPa in the range 8-10.5% is shown in figure below. 2.8 2.7 2.6 2.5 2.4 2.3 2.2 2.1 2 1.9 1.8 1.7 1.6 1.5 8 8.5 9 9.5 10 10.5 Hydrogen concentration, % by vol. Figure 23: Vent area for the enclosure as a function of hydrogen concentration. To mitigate a deflagration of a 10.5% by vol. hydrogen-air mixture, the minimum vent size is 2.8 m2 in the enclosure of 33 m 3 volume. Hence, the venting of deflagration system designed as described would mitigate explosion of a leaked hydrogen without construction failure. Indeed, a venting device with such area can be mounted, 61 © HyFacts 2012/13 – CONFIDENTIAL – not for public use depending on the particular location and design of the enclosure, on any on the four walls or at the ceiling. 1.1.6.5.3 Extension of hazardous effects of vented deflagrations In the case of a vented deflagration, the deflagration pressure decay in the far field can be calculated thanks to the model described in section Error! Reference source not found.. 1.1.6.6 1.1.6.6.1 Mitigation of overpressure effects by separation Extension of overpressure effects As explained in section 1.1.6.2, the most destructive effects of the vented deflagration phenomenon may be caused by the external explosion occurring when the flame front reaches the vent of the enclosure. Significant overpressure effects might occur outside of the enclosure, in front of the vent. Hazards perimeters are defined by different pressure thresholds. These pressure thresholds slightly differ, according to the considered country. In France, 50 mbar is the lowest pressure threshold; it corresponds to the first high wounded level as well as to significant material impacts. A similarity law has been developed to calculate the overpressure decay (see section Error! Reference source not found.). Thanks to this law, the distance where the overpressure drops to 50 mbar can be calculated, in order to determine the appropriate safety distance in front of an enclosure vent. 1.1.6.6.2 Walls Although this is usually not the most effective approach to ensure safety, protective barriers can be used to protect environment from blast effects, as a reduced pressure region is formed behind the wall. 62 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Figure 24: Schematic of the protective mechanism (Source: Air Liquide) Experiments conducted by the Health and Safety Laboratory and by the Sandia National Laboratory showed that a lower overpressure is induced behind the barrier as it diffracts the shock wave generated by the explosion. This reduced pressure region is mainly proportional to the wall height but is also dependant to other parameters (wall width, flame speed...). After this zone, the shock waves reforms. In an appropriate design of the wall, when the shock waves reforms, the corresponding overpressure should not be dangerous anymore for people or structures. On the other hand, the presence of a barrier also induces a higher overpressure front side the barrier (due to shock wave reflexion). The barrier design is therefore a tradeoff between increase of the pressure front side of the barrier and decrease of the overpressure behind it. 1.1.7 Mitigation of thermal effects from jet fires 1.1.7.1 Thermal effects from jet fires – summary Direct or indirect impact of jet fires on structures are listed below: The increase in temperature and pressure in liquid and gas storage can lead to a rupture of confinement, 63 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Structural elements are weakened and structures or building can fail. The intensity and duration of exposure depends on the materials under consideration; Jet fires can remotely ignite certain type of materials like wood. There are three basic ways in which exposure of people to hydrogen jet fires, may lead to incapacitation and death: hyperthermia, respiratory tract burns and body surface burns (NFPA, 2002). Hyperthermia or heat stroke involves prolonged exposure (approximately 15 minutes or more) to heated environments at temperatures too low to cause burns; Heat damage to the respiratory tract is more severe when the heated air contains steam and can cause damage down to the deep lung; The time from the application of heat to the occurrence of burns of various degrees of severity, depends the heat flux to which the skin is exposed. 1.1.7.2 Extension of hazardous thermal effects Experimental work conducted by (Schefer et al, 2006; Molina et al, 2007) aimed at defining spatial and radiative properties of an open-flame hydrogen plume and predict the heat fluxes at any radial (r) and axial (x) position from underexpanded jet fires (see Figure 25). The validity of the method presented below has been compared against experiments and demonstrated good agreement in the range ±10% of the nominal value (Schefer et al, 2006; Molina et al, 2007). 64 © HyFacts 2012/13 – CONFIDENTIAL – not for public use x r Figure 25: Coordinate system for jet flame (Source: University of Ulster) To determine radiant heat flux, the following steps have to be followed. It is first necessary to calculate the flame residence time using the following equation: 125.13 W f L f f s 2 f Equation 13 3 noz d noz U noz 2 Where: f flame residence time (s) Wf flame width assuming Wf =0.17·Lf (m) Lf flame length (m) fs mass fraction of fuel at stoichiometric conditions (0.0283) noz density of the flow at the nozzle (kg/m 3) dnoz initial jet discharge diameter (m) Unoz velocity of the flow at the nozzle (m/s) When knowing the flame residence time, the total emitted radiative power Srad shoud be calculated using the Equation 14. 65 © HyFacts 2012/13 – CONFIDENTIAL – not for public use noz H c S rad 0.0304 ln( f ) 0.0595 m Equation 14 Where: Srad total emitted radiative power (W) m noz hydrogen mass flow rate at the nozzle (kg/s) Hc heat of combustion of hydrogen (141×106 J/kg) f flame residence time (s) At this point the there are two possibilities: Determine the heat flux at a chosen location: The coordinates (r, x) correspond to potential targets of a jet fire: occupants, building, escape routes, other source of potential hazards like storage of flammable or toxic substance, etc. In that case, x Equation 17. The must be inserted in Equation 15 or Equation 16, and r in Equation 17. radiative heat flux at the location (x,r) is given by Determine the coordinates for a chosen heat flux: The coordinates are extracted for a chosen radiative heat flux and draw a contour around the jet fire. The radiant power C*, is calculated using one of these two equations. For Values of x/Lf≤0.65: x C 1.95 L f * 3 1.345 x L f 2 0.777 x L f 0.254 Equation 15 For values of x/Lf >0.65: x C 0.212 L f * 5 2.004 x L f 4 7.149 x L f 3 11.64 x L f 2 7.851 x L f 1.016 Equation 16 Then the radiant fraction Srad and the non-dimensional radiant power C* have to be implemented in the Equation 17 to calculate qrad(x,r) the radiative heat flux at the location (x,r): C * Srad qrad ( x, r ) 4 r2 Equation 17 An example of the application of these equations is shown in Figure 26. 66 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Radial distance, r (m.) 16 1577 W/m2 4732 W/m2 25237 W/m2 Jet fire 1.577 kW/m2 12 8 4.732 kW/m2 4 25.237 kW/m2 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Axial distance, x (m) Figure 26: Radiative heat flux regions around jet fire along jet axis, from a 400 bar storage pressure through 5 mm nozzle (half domain) (Source: University of Ulster) The hot currents downstream of hydrogen jet fire can extend over very large distance, heating the air to dangerous levels. The limit of 300OC is of interest for separation distance as it corresponds to the temperature causing third degree burns for a 20 seconds exposure, burns to larynx after a few minutes and would make escape improbable. This limit extends up to twice the flame length. Another important limit is 115 oC and it corresponds to a level of air temperature at which occupants can evacuate and withstand more than 5 minutes and is reached at about 3 times the jet flame length. 2200 2000 1800 Tair-x , K. 1600 1400 1200 1000 800 600 400 200 0 0.5 1 1.5 2 x/Lf 2.5 3 3.5 Imamura et al. Imamura et al. Imamura et al. Imamura et al. Imamura et al. Imamura et al. Imamura et al. Imamura et al. Barlow Sandia 5 s Sandia 20 s Sandia 50 s Sandia 60 s Sandia 70 s 300 oC limit 115 oC limit 2008, 2008, 2008, 2008, 2008, 2008, 2008, 2008, Figure 27: Normalized plume temperature from hydrogen jets (Saffers, 2011) 67 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1 mm, 1 mm, 1 mm, 2 mm, 2 mm, 3 mm, 3 mm, 3 mm, 12 bar 20 bar 35 bar 3 bar 5 bar 4 bar 7 bar 10 bar 1.1.7.3 Control of direction of flow The flow shall be directed so that it will not reach equipment or people. For instance, flanges (which are components where hydrogen leaks might occur) should be placed and directed in such a way that a possible leak would not cause any domino effect. 1.1.7.4 Shielding The basic intent of the various methods of protection is to reduce the rate of heat transfer to the potential targets in the vicinity of a hydrogen jet fire (NFPA, 2002). Flame shields are specifically intended to reduce the incident radiant heat flux by preventing direct flame impingement on equipment. Flame shields shall be properly designed (choice of the material, thickness...). 68 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.7.5 Thermal insulation The basic intent of thermal insulation is to reduce the rate of heat transfer to the potential targets (i.e. hydrogen tanks) in the vicinity of a hydrogen jet fire (NFPA, 2002). Thermal insulation is achieved by surrounding equipment with materials that preferably have the main following characteristics: Relatively non-conductive materials; Non-combustibility and the added attribute of not producing smoke or toxic gases when subjected to elevated temperatures; Product reliability giving positive assurance of consistent uniform protection characteristics; Availability in a form that permits efficient and uniform application; Sufficient bond strength and durability; Resistance to weathering or erosion resulting from atmospheric conditions. Fire protection coatings providing thermal insulation can be part of the fire protection strategy of compressed gaseous hydrogen vessels (see in section Error! Reference source not found.). Such coatings are currently under research. References for section 3.2.8.: Babkin V.S., Private communication. Institute of Chemical Kinetics and Combustion, Siberian Branch, Russian Academy of Science, Novosibirsk, Russia, 2003. Lamoureux N., Djebaili-Chaumeix N., Paillard C.-E., Flame velocity determination for H2-air-He-CO2 mixtures using the spherical bomb, Experimental Thermal and Fluid Science, Volume 27, Issue 4, pp 385-393, 2003. Molkov V., Journal of Loss Prevention in the Process industries 14, 567-574, Draft European standard pr14994, “gas explosion venting protective systems, 2001. Molkov V., Dobashi, R., Suzuki, M., Hirano, T., Modelling of vented hydrogenair deflagrations and correlations for vent sizing, Journal of Loss Prevention in the Process Industries, volume 12, issue 2, pp 147-156, 1999. Molkov V., Verbecke F., Saffers J.B., Venting of uniform hydrogen-air deflagrations in enclosures and tunnels: vent sizing and prediction of 69 © HyFacts 2012/13 – CONFIDENTIAL – not for public use overpressure, Submitted for presentation at the 7th ISHPMIE, St. Petersburg, Russia, July 7–11, 2008. NFPA, Society of Fire Protection Engineers Handbook, Third edition, 2002. Saffers, J.B, Principles of Hydrogen Safety Engineering, PhD thesis, University of Ulster, 2011. Tse S.D., Zhu D.L., Law C.K., Morphology and burning rates of expanding spherical flames in H2/O2/inert mixtures up to 60 atmospheres, proceedings of the 28th Symposium (International) on Combustion, pp. 1793–1800, Pittsburgh, PA: the Combustion Institute, 2000. 1.1.8 Separation distances Passive Avoid unnecessary conf inement Natural ventilation Active Active ventilation Detection and active ventilation Passive Flow restriction Active Detection and Isolation Excess f low valve H2 release Confined explosive atmosphere Passive Passive Explosion venting Separation distance Active Emergency response Strong blast effects Injury / casualty Passive Separation distance Flash fire Active Emergency response Unconfined explosive atmosphere Escalation Blast effects Loss of leak tightness Flame/ Jet fire Equipment failure Kinetic effects Passive No ignition sources Active Detection and power shut-down Figure 28: Mitigation measure: separation distances (Source: Air Liquide) 1.1.8.1 Purpose and objective Safety distances are a generic means for mitigating the effect of a foreseeable incident and preventing a minor incident escalating into a larger incident. It can be in principle applied to any facility using gaseous hydrogen. All readily applicable prevention and mitigation measures should be applied before considering mitigation by means of safety distances. These are to be considered as 70 © HyFacts 2012/13 – CONFIDENTIAL – not for public use one element of a comprehensive safety approach and are appropriate when used along with other means. Separation is not always the most appropriate means. Separation distance requirements are typically specified by means of a table indicating the separation to be applied between the equipment considered and elements potentially present in its environment. Different tables are used for different applications (e.g. fuelling stations, bulk hydrogen storage systems, and hydrogen installations in non industrial environments). Distance in meters Passive hydrogen systems Category 1 (SP <= 55 MPa) Safety distances (m) Cat. 3 (Q > 100 kg) VS S C VS S C S C 1,5 4,0 6,0 2,0 5,0 8,0 7,0 10,0 Occupied buildings - bay-windows* - 5,0 8,0 - 7,0 12,0 9,0 15,0 Unoccupied buildings - openable openings and air intakes - 2,0 3,0 - 3,0 5,0 4,0 5,0 Buildings of combustible material 1,5 3,0 5,0 2,0 4,0 7,0 8,0 8,0 Flammable liquids above ground <= 4000 L 1,0 2,0 3,0 - 2,5 4,0 8,0 8,0 Flammable liquids above ground > 4000 L 1,5 3,0 5,0 2,0 4,0 7,0 8,0 8,0 5,0 5,0 Occupied buildings - openable openings and air intakes Exposures or Sources of hazard Category 2 (55 < SP <= 110 MPa) Underground flammable liquid storage - vents and fill openings 3,0 - 3,0 - Stocks of combustible material 1,0 2,0 3,0 - 2,5 4,0 8,0 8,0 Flammable gas storage above ground > 500 Nm3 1,0 2,0 3,0 - 2,5 4,0 8,0 8,0 Facility lot line - 2,0 3,0 - 3,0 5,0 4,0 5,0 Areas not subjected to restrictions of activity - 2,0 3,0 - 3,0 5,0 4,0 5,0 Pedestrian and vehicle low-speed passage ways - 2,0 3,0 - 3,0 5,0 4,0 High voltage lines and trolley or train power line - 5,0 - 5,0 10,0 Other overhead power lines - 5,0 - 5,0 5,0 Roadways - 5,0 - 5,0 5,0 5,0 * non-re-enforced to withstand overpressure effects Figure 29: Example of separation distances table, for a given application (Source: Air Liquide) Note: in the table lines are listed exposures or sources of hazard while system categories are listed in columns. Note: safety distances are not intended to provide protection against catastrophic events or major releases. This is to be achieved by other means such as prevention, specific means of mitigation, or emergency response, which standards also need to address. 71 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.1.8.2 Risk informed separation distances A specific risk informed rationale has been developed to define and substantiate separation distance requirements for refuelling stations in ISO/DIS 20100 Gaseous hydrogen – refuelling stations. This approach, which is applicable to all types of hydrogen installations, is based on the premise that the safety distances can be defined taking into account a criterion on risk to exposures. The basic steps of the construction of a safety distance are listed hereafter: Key system characteristics or parameters that determine actual risk impact are selected. For fuelling stations the following principles were adopted: o Separation distances should not be determined only by pressure and internal diameter. o They need to integrate fundamental factors such as storage system size, operating pressure (for small systems only), system complexity (reflected by the number of components of the system), and exposure criticality (high in locations where there is a risk of affecting many people at once). Through the application of this categorization scheme, system categories associated to a graduation of risk impact are defined. Systems belonging to the same category can be considered to have a roughly similar risk impact, and, therefore, a single set of separation distance requirements can apply to these. Boundaries can be defined according to equipment types in use (see Table 12). Table 12 : Classification of storage systems (Reference: Air Liquide) 72 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Storage classification for determination of clearance distances 100 2 55 St 3 y tit an qu kg ed 0 or > 10 Service pressure (MPa) P > 55 Mpa P <= 55 MPa 1 1k g 10 100 1000 10000 3000 100000 Water volume (L) Figure 30: Storage classification for determination of separation distances (Source: Air Liquide) For smaller hydrogen installations the classification below based on the quantity of stored hydrogen in the system, its power and its maximal operating pressure, was adopted in the French standard NF M58-003. Max. operating pressure Power and mass of stored hydrogen < 5 bar < 50 bar >50 bar >500 bar P < 30 kW and M < 8kg AA A B C P < 70 kW and M < 35kg A B C D P > 70 kW and M > 35 kg C C D D Class of the system Table 13: Assessment of the class of a hydrogen system (Source: French standard NF M58-003) 73 © HyFacts 2012/13 – CONFIDENTIAL – not for public use For each class of the system, leak flow rates are given (by default): Leak flow rate (g/s) AA A B C D Expectable 0,075 0,24 0,53 0,95 1,48 Foreseeable 0,75 2,23 5,02 8,93 13,95 Table 14: Leak flow rates (by default) (Source: French standard NF M58-003) Safety distances are defined, depending on the class of the system (AA, A, B, C or D) and on the potential targets (opening of the ventilation of a building, etc). Class of the system AA A B C D - - - 0.6 0.6 1 1.5 2.5 3.5 4 1 2 3 4 5 Openings of non-occupied premises - 1 2 2.5 3 Depot of combustible materials 1 1.5 2.5 3.5 4 Vehicle parking spots 0 1 2 2.5 3 Public traffic lanes - 1 2 2.5 3 - 1 2 2.5 3 Buildings where the closest wall has a fire-resistance rating above one hour Buildings where the closest wall has a fire-resistance rating below one hour Openings and bay windows of occupied premises Extension of perimeter where activities are limited Table 15: Example of safety distances (Source: NF M58-003) 74 © HyFacts 2012/13 – CONFIDENTIAL – not for public use (in meters) For each system category, a risk model is used to determine the separation distances, by application of a criterion on estimated residual risk. Hereafter are listed the main elements integrated in this model: o The function providing the cumulated frequency of having a leak greater than a given size. See in the next section how the whole system leak frequency distribution can be determined, in function of components leak frequency distribution. o The model also includes an evaluation of the conditional probability that the leak will produce the feared consequences on exposed objects, assuming they are close enough to be impacted. This probability depends on the probability that the leak will generate dangerous phenomena (probability of ignition), the probability that the phenomena will impact the exposure (geometric factor) as well as the probability that the phenomena (flash fire, fire, overpressure) will have the feared effect on the exposure. o The consequence model enables the estimation of the distance at which a leak of a given size can produce the feared effects if all the conditions for these effects to materialize are present (e.g. ignition, jet in the right direction…). The model is based on the interpolation of flame length and flammable cloud length formulas developed by SNL (Bill Houf). 75 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Table 16: Consequence model (Source: Air Liquide) With: SD: separation distance (m); LD: leak diameter (mm) SP: service pressure (MPa); LQ: leak flow (g/s) LA: leak area (mm²) o A residual risk criteria is defined for the exposure considered, translated into a frequency limit. Target value for the feared event frequency is set at 10-5 /yr for non-critical exposure, and 4 10-6/yr for critical exposure. occ./yr Separation distance To be applied Frequency 10-1 1 10 3 30 Separation distance (m) Leaks Cumulated frequency of feared effects from leaks greater than X g/s 10-2 10-3 10-4 Feared Effect Target 10-5 10-6 0,01 0,1 1 10 100 Reference leak size Figure 31: Risk model applied (Source: Air Liquide) 76 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Leak rate (g/s) Then the separation distance table is populated and the result is evaluated. If the result is not consistent with the separation distances which are used and accepted for existing applications, it means that the hypothesis of the model were inadequate and should be changed before re-computing the separation distances. Indeed, the risk model does not provide an accurate evaluation of risk, but allows taking into consideration the main risk factors consistently. Note: the separation requirements are said to be risk informed because it takes into account the risk impact of the particular system and involves the application of a risk criteria. 1.1.8.3 System parameters determining separation requirements The whole system leak frequency distribution can be determined in function of components leak frequency distribution. The main components which contribute to leaks are fittings, joints, hoses, etc. The main pieces of equipment that are exposed to leaks are compressors, because they are exposed to vibration, etc. By summation of contributing component leak frequency data, the cumulated leak frequency in function of leak size can be estimated for the whole system. 1.1.8.4 Reference hydrogen leak frequencies Component leak frequencies data input to the risk model is derived from the work of J. Lachance of Sandia National Laboratories (SNL), which consisted in reviewing various sources of statistical data on component leak frequencies in order to generate reference data for components in hydrogen service. For each type of component, the cumulated leak frequency in function leak size (% of flow section) can be estimated (see Figure 32). 77 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Figure 32: Component leak frequency in function of leak size in % of flow section (Source: Frederic Barth, Air Liquide Hydrogen Energy, 2011, “Risk informed separation distances for hydrogen refuelling stations”) Reference: Frederic Barth, Air Liquide Hydrogen Energy, 2011, “ Risk informed separation distances for hydrogen refuelling stations”, International Conference on Hydrogen Safety, San Francisco 1.1.8.5 Use of walls A possible mitigation strategy to reduce exposure to hydrogen hazards is to build protective barriers (walls). These protective barriers can be used to reduce the extent of unacceptable consequences in hydrogen energy applications. Walls protect from thermal effects in some configurations: with a flame impinging at the half of the wall height, there is no flame and thermal radiation hazards on the other side of the wall. While in other configurations, walls create additional hazards. For instance, in some cases, a jet flame can turn back toward the jet source, resulting in an additional hazard. Besides, the presence of a barrier induces a higher heat flux front side the barrier and a lower heat flux behind the barrier. As explained in the section 1.1.6.6.2, walls protect people and structures from overpressure effects in a reduced pressure region behind the wall. On the other hand, it also induces a higher overpressure front side the barrier. 78 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Besides, walls contribute to the formation of a confined atmosphere, and prevent the system from being easily accessible. Thus, walls are a protective mitigation strategy which should not be used systematically as they can simultaneously protect people and structure right behind the wall, but can also create additional hazards 1.1.9 1.1.9.1 Coverage by regulations and standards Regulations See section Error! Reference source not found. for a focus on European directives and regulation. Example of EC directive: the ATEX directive In 1994, the European Parliament issued a directive, Directive 94/9/EC on the use of equipment and protective systems in explosive atmospheres, the so-called ATEX directive (European Parliament, 1994). However, the ATEX regulations did not come into force until 2003. Equipment in first use prior to June 2003 was allowed to be used provided that a risk assessment was carried out (Sherwen, 2012). In the Directive, it is set out that the equipment has to be certified by a notified body. The text also stresses that national regulations must not be a barrier to free trade within the European Community, that is to say there must be freedom of movement for the equipment to which the Directive applies. Directive 99/9/EC is focused on the human being and complements the ATEX Equipment Directive (European Parliament, 1999). 1.1.9.2 Standards Below are described the ISO and IEC standards which are the most commonly used for the control of flammability and explosions hazards. ISO/TR 15916:2004 provides guidelines for the use of hydrogen in its gaseous and liquid forms. It identifies the basic safety concerns and risks, and describes the properties of hydrogen that are relevant to safety. ISO 26142:2010 defines the performance requirements and test methods of hydrogen detection apparatus that is designed to measure and monitor hydrogen concentrations in stationary applications. ISO 26142:2010 sets out only the requirements applicable to a product standard for hydrogen detection 79 © HyFacts 2012/13 – CONFIDENTIAL – not for public use apparatus, such as precision, response time, stability, measuring range, selectivity and poisoning. ISO 26142:2010 is intended to be used for certification purposes. IEC 60079-29-2 gives guidance on the selection, installation, safe use and maintenance of electrically operated group II apparatus intended for use in industrial and commercial safety applications, for the detection and measurement of flammable gases complying with the requirements of IEC 60079-29-1. 20100:2008 specifies the characteristics of outdoor public and non-public fuelling stations that dispense gaseous hydrogen used as fuel onboard land vehicles of all types. IEC 600796-10 specifies the requirements for the construction and testing of oil-immersed electrical equipment, oil-immersed parts of electrical equipment and Ex components in the type of protection oil immersion "o", intended for use in explosive gas atmospheres. IEC 60204-1 applies to the application of electrical, electronic and programmable electronic equipment and systems to machines not portable by hand while working, including a group of machines working together in a coordinated manner. IEC 62282-3-300:2012 provides minimum safety requirements for the installation of indoor and outdoor stationary fuel cell power systems in compliance with IEC 62282-3-100. IEC 62282-3-100:2012(E) is applicable to stationary fuel cell power systems intended for indoor and outdoor commercial, industrial and residential use in non-hazardous (unclassified) areas. ISO 22734-1:2008 and ISO 22734-2:2011 defines the construction, safety and performance requirements hydrogen generators, using electrochemical reactions to electrolyse water to produce hydrogen and oxygen gas. defines See the fields of application of these standards in Table 17. 80 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Fields of application of the standards Prevention of Standard name Prevention & mitigation of hydrogen releases flammable / Prevention of ignition Detection of leaks sources hazardous mixtures by means of Prevention and Mitigation of mitigation of thermal effects explosions from jet fires Separation distances ventilation ISO/TR 15916:2004 Basic considerations for the safety of hydrogen systems Limited cover in clauses 4.2.3 Fluid delivery lines, piping, joints and seals and Discussion of 7.2.5 Considerations for ignition sources piping, joints and connections ISO 26142:2010 Hydrogen detection apparatus -Stationary applications Detection limits and ISO/TS 20100:2008 Gaseous hydrogen -Fuelling stations activation thresholds Presence of isolation valve (in clause 21.3. Sections 21 Detection limits and activation thresholds Safety systems and 15.5. Prevention of accumulation of Safety and emergency ignitable mixtures in shut-off systems) enclosures 81 © HyFacts 2012/13 – CONFIDENTIAL – not for public use Clause 15.3.1. Lay-out Construction of requirements enclosure and location of containing points of hydrogen potential leaks systems Stationary ISO 22734-1 and -2:2008 Hydrogen generators using water electrolysis process fuel cell power systems Installation clause IEC 60079-29-2 Explosive atmospheres - Gas detectors IEC 62282-3-3 Fuel cell technologies - Stationary fuel cell power systems Installation Selection, installation Selection, and use installation and use Use of detection in Clauses 8.3. Fuel shut fuel cell installations off and piping and 8.4. indoors: clause 7.1.2. Connections to auxiliary Combustible gas media supply and media detection (indoor disposal installations only) Classification IEC 60079-6-10 Explosive of areas for atmospheres - Equipment proper selection protection by oil of equipment in immersion "o" order to prevent ignition sources IEC 60204-1 Safety of machinery - Electrical equipment of machines Grounding and bonding Table 17: Standards 82 © HyFacts 2012/13 – CONFIDENTIAL – not for public use 1.2 Venting systems 1.2.1 Description Venting systems are used to pipe outdoors hydrogen flows from vents and safety relief equipment. Hydrogen should be piped to a safe location, where it will not generate any hazard for persons or neighboring structures. 1.2.2 Safety measures and coverage by standards The design of hydrogen vent stacks should take into account these three main risks: The risk of explosion due to the delayed ignition of the explosive hydrogen/air mixture out of the vent stack. The risk of thermal radiation generated by the jet fire (the flame out of the vent stack). The risk of Deflagration to Detonation Transmission (DDT) inside the stack at the beginning of the venting (see explanations on the DDT in section Error! Reference source not found..). Below are listed some examples of design rules for hydrogen venting systems: Conditions on the vent outlet location: Explosion venting shall be provided in exterior walls or roof only. The vent outlet location should be such that the vent may be used without any limitations and without creating hazardous conditions for operation, maintenance and emergency responses. The vent outlet should be away from personnel areas, from electrical lines and from other ignition sources, air intakes, building openings and overhangs. The vent outlet location (height, and distance to exposures) should be such that given limits on maximum hydrogen concentration, on maximum thermal radiation and on maximum overpressure effects are not exceeded under any foreseeable venting situation10. 10 The limits applicable to the outlet of a venting system used for the emergency discharge of gaseous hydrogen storage systems slightly differ from those specified in this section. 83 © HyFacts 2012/13 – CONFIDENTIAL – not for public use The maximum pressure drop resulting from the sum of design flows of all the vent devices discharging into the common vent system should not exceed 10% of the lowest set pressure of all the relief valves collected. The vent piping diameter should not be smaller than the diameter of any pressurerelief valve outlet, and large enough to avoid exceeding the maximum allowable pressure drop previously specified. Design pressure should be such that the stack should withstand the overpressure generated by an eventual detonation (in the cases where a Deflagration to Detonation Transmission would occur). Cryogenic and non-cryogenic hydrogen should be vented through distinct venting systems. Coverage by standards: ISO/DIS 20100 84 © HyFacts 2012/13 – CONFIDENTIAL – not for public use