Vacuum Valve Interlock Test Procedure: XTA XT01 Revised 09 July 2011 Test procedure: 1. Verify that gauge wiring and PLC programming are failsafe All gauge inputs OK a. Make up all gauge inputs to VVC: XT01:1 and reset All gauge inputs Fault interlocks. Verify gauge OK status on VVC front after removing IB32 panel. module from slot 3 b. Remove the IB32 digital input module from slot 3 of All gauge inputs OK CHAS: XT01:VA01 and verify that all gauge inputs All gauge inputs Fault are faulted and cannot be reset. after unplugging cable from slot 3 c. Insert the module and reset interlocks. d. Unplug the PLC cable from the front of slot 3 of CHAS: XT0:VA01 and verify that all gauge inputs are faulted and cannot be reset. 2. Name of tester and date of test ___________________________________ Name Document1 Page 1 of 2 __________________ Date 3. Valve logic test for VVPG:XT01:115 a. If possible, turn off all cold cathode gauges except for those interlocked to valve VVPG:XT01:115 All gauges off b. Make up all inputs to valve VVPG: XT01:115 either by turning on gauges and making up PPS inputs, or by bypassing the individual inputs. All inputs OK Intlk sum OK c. Test each input, one at a time, with all other inputs either bypassed or OK. For each input, complete the appropriate line on the following table: Valve VVPG:XT01:115 – Valve Controller VVC:XT01:11, valve #1 Input (VVC input #) Bypass Clear, Gauge/PPS fault, Intlk sum Fault and will not reset Bypass Clear, Gauge/PPS OK, Intlk sum OK after intlk reset Bypass Clear, Gauge/PPS fault, Intlk sum Fault and will not reset Bypass Set, Gauge/PPS fault, Intlk sum OK VVC VVC VVC EPICS VVC d. Verify that the valve can be opened and closed from VVC front panel and from EPICS. Set the valve control mode key switch to the appropriate position for each test. Intlk sum OK, Valve can be opened Intlk sum Fault, Valve cannot be opened VVC EPICS VVC EPICS e. Verify that valve position indicators and air pressure switch report correct status Closed switch VVC EPICS VVC EPICS VVC EPICS EPICS EPICS VGCC:XT01:112 (0) VGCC:XT01:W255 (1) VPIO:XT01:W230 (4) VPIO:XT01:112(5) VPIO:XT01:113 (6) VPIO:XT01:124 (7) Open switch Air OK indicator 4. Name of tester and date of test ___________________________________ Name Document1 Page 2 of 2 __________________ Date EPICS