Scope of Work 1. Remove Existing Generator Price includes cost of removal and disposal of existing generator, complete including oil disposal or recycling, disconnection of wiring and gas line and patching of concrete pad, if necessary. 2. Remove Vent and Patch Roof Price includes cost of removal and disposal of existing exhaust vent through roof and the patching of the roof in accordance with the manufacturer of roof’s specifications. This work must be performed by Likar Roofing of North Versailles, PA (412-823-1561) in order to preserve the warranty on the roof. 3. New Generator Price includes cost of purchase, delivery and installation of new Kohler natural gas generator as Model 45REZG, or pre-approved equal. In order to use an “or equal” product, submittals must be submitted 7 days prior to the bid opening for review. Also includes cost of crane to load equipment onto the concrete pad. Voltage requirements are 120/208 volts. 4. Transfer Switch Price includes cost of supply and installation of new 150 amp transfer switch to be compatible with proposed generator, complete including all necessary mounting hardware and connection of wiring. 5. Area Protection Monitor Price includes cost of supply and installation of new area protection monitor to be compatible with proposed generator, complete including all necessary mounting hardware and connection of wiring. The Bidder is required to field visit and inspect the existing Area Protection Monitor to familiarize which areas of the building are supplied by the generator. Contractor will be responsible to reconnect these areas to the new Area Protection Monitor. 6. Electrical Panel Box Price includes cost of supply and installation of new 30 circuit, 150 amp electrical panel board complete including connection of wiring and labeling of all circuits. Also includes 12” x 12” trough under panel board. 7. Concrete Pad for Generator Price includes cost of excavation, stone base and supply and installation of 12” thick reinforced concrete pad, as specified and shown on the plans, complete including reinforcing and forming. 8. Extend Gas Line, Interior Price includes cost of supply and installation of new gas line inside the building to extend gas service to the exterior wall as shown on the plans. All pipe to be in accordance with the international building code and anchored to the wall. 9. Extend Gas Line, Exterior Price includes cost of supply and installation of new gas line outside the building to extend gas service to the new generator as shown on the plans. All pipe to be in accordance with the international building code. On the exterior wall, pipe to be anchored to the wall. Price includes patching of wall. In the area where the line is to be buried, price also includes excavation and backfill. 10. Extend Electrical Wiring & Conduit, Interior Price includes cost of supply and installation of new electrical wiring & conduit inside the building to the exterior wall as shown on the plans. All wire and conduit to be copper and in accordance with the international electrical code and anchored to the wall. 11. Extend Electrical Wiring & Conduit, Exterior Price includes cost of supply and installation of new electrical wiring & conduit outside the building to extend connect to the new generator as shown on the plans. All wire and conduit to be copper and in accordance with the international electrical code. On the exterior wall, conduit to be anchored to the wall. Price includes patching of wall. In the area where the line is to be buried, price also includes excavation and backfill. 12. Landscaping Restoration Price includes cost of restoring landscaping in disturbed area to match existing conditions including mulch. ALTERNATE BID is for exact same items except that the borough would purchase the generator directly and have it delivered to a location near the installation site. General Notes 1. All work to be in compliance with the International Electrical Code, latest edition. 2. All pricing to include cost of inspection by a Pennsylvania Certified Electrical inspector. 3. Any questions or concerns regarding this project must be submitted to the engineer’s office prior to submission of bid. 4. The work site is at 125 Monroeville Avenue in Turtle Creek, PA and may viewed by contacting Nick Lorito at 412-576-9643 between the hours of 7am to 3pm.