Form for a Large Facility Interconnection Request - DOC

advertisement
Instructions for Submittal of a Large Facility Interconnection Request to the NYISO
Introduction
The NYISO Standard Large Facility Interconnection Procedures (LFIP), contained in Attachment X of
the NYISO Open Access Transmission Tariff (OATT), apply to Generating Facilities that exceed 20 MW
and to Merchant Transmission Facilities. The following instructions are for Developers that wish to
submit an Interconnection Request to the NYISO under the LFIP.1
Submittal of an Interconnection Request to the NYISO
To initiate an Interconnection Request, a Developer must submit all of the following: (i) a $10,000 nonrefundable application fee; (ii) a study deposit of $30,000; (iii) a completed application in the form of
Appendix 1 of the LFIP (see attached); and (iv) demonstration of Site Control or a posting of an
additional deposit of $10,000. To facilitate processing, NYISO prefers these items to be submitted
electronically (fee and deposit(s) via wire transfer, application form and documentation of Site Control by
e-mail). The scanned copy of the completed application and documentation should be submitted via email to: NewProject@nyiso.com
Wire transfers are preferred for making deposits. Please request wiring instructions via e-mail from:
Chelsea Bonesteel
Accounting Associate, Finance
Phone No. (518) 356-8805
E-mail: cbonesteel@nyiso.com
If paying by check, make deposit check(s) payable to: New York Independent System Operator, Inc.
A separate Interconnection Request must be submitted for each site and multiple Interconnection
Requests may be submitted for a single site. A deposit must be submitted for each Interconnection
Request even when more than one request is submitted for a single site. An Interconnection Request to
evaluate one site at two different voltage levels shall be treated as two Interconnection Requests.
Upon Receipt of an Interconnection Request
Within five (5) business days of receipt of an Interconnection Request, the NYISO will:
 Acknowledge Receipt of the Interconnection Request,
 Forward a copy of the Interconnection Request to the connecting Transmission Owner(s),
 Review the Interconnection Request and notify the Developer and connecting Transmission
Owner(s) if the request is determined to be invalid and the reasons for such determination,
 If the Interconnection Request is determined to be valid, provide a form Interconnection Feasibility
Study Agreement to the Developer and connecting Transmission Owner(s).
Within ten (10) business days after receipt of a valid Interconnection Request, the NYISO will establish a
date agreeable to the Developer and connecting Transmission Owner(s) for a Scoping Meeting.
S. Corey
Revised 2/14/2014
1
Note that if there is anything in these instructions that is inconsistent with the LFIP, it is the effective
LFIP that will govern.
INTERCONNECTION REQUEST
1.
The undersigned Developer submits this request to interconnect its Large Generating
Facility or Merchant Transmission Facility with the New York State Transmission
System or Distribution System pursuant to the Large Facility Interconnection Procedures
in the NYISO OATT.
2.
This Interconnection Request is for (check one):
____ A proposed new Large Generating Facility, named ___________________.
____ A proposed new Merchant Transmission Facility, named ______________.
____ An increase in the capacity of an existing Large Generating Facility or existing
Merchant Transmission Facility.
3.
The type of interconnection service evaluation requested for Class Year Interconnection
Facilities Study:
____ Energy Resource Interconnection Service
____ Capacity Resource Interconnection Service
____ Partial Capacity Resource Interconnection Service
4.
The Developer provides the following information:
a.
Address or location or the proposed new Large Facility site (to the extent known)
or, in the case of an existing Generating Facility or Merchant Transmission
Facility, the name and specific location of that existing facility;
b.
Maximum summer at _______ degrees C and winter at ______ degrees C
megawatt electrical output of the proposed new Large Facility or the amount of
megawatt increase in the capacity of an existing facility;
c.
Megawatt allocation for partial CRIS evaluation;
d.
General description of the equipment configuration;
e.
In-Service Date, and Commercial Operation Date (Day, Month, and Year);
f.
Name, title, company address, telephone number, FAX number and e-mail
address of the Developer’s contact person;
g.
Approximate location of the proposed Point of Interconnection (optional); and
h.
Interconnection Customer Data (set forth in Attachment A).
1
5.
Applicable deposit amount as specified in the LFIP.
6.
Evidence of Site Control as specified in the LFIP (check one)
____ Is attached to this Interconnection Request
____ Will be provided at a later date in accordance with the Large Facility
Interconnection Procedures
7.
This Interconnection Request shall be submitted to the representative indicated below:
Name:
Title:
Address:
Phone No.:
Fax No.:
E-mail Add.:
8.
Steven L. Corey
Manager, Interconnection Projects
10 Krey Blvd.
Rensselaer, NY 12144
(518) 356-6134
(518) 356-7524
scorey@nyiso.com
Representative of the Developer to contact:
[To be completed by Developer]
9.
This Interconnection Request is submitted by:
Name of Developer:
By (signature):
Name (type or print):
Title:
Date:
2
ATTACHMENT A
LARGE GENERATING FACILITY DATA UNIT RATINGS
kVA _________
°F ___________
Voltage __________
Power Factor __________
Speed (RPM) __________
Connection (e.g. Wye) __________
Short Circuit Ratio __________
Frequency, Hertz __________
Stator Amperes at Rated kVA __________
Field Volts __________
Max Turbine MW __________
°F __________
COMBINED TURBINE-GENERATOR-EXCITER INERTIA DATA
Inertia Constant, H =
____________________ kW sec/kVA
Moment-of-Inertia, WR2 = ____________________ lb. ft.2
REACTANCE DATA (PER UNIT-RATED KVA)
DIRECT AXIS
QUADRATURE AXIS
Synchronous - saturated
Xdv __________
Xqv __________
Synchronous - unsaturated
Xdi __________
Xqi __________
Transient - saturated
X’dv __________
X’qv __________
Transient - unsaturated
X’di __________
X’qi __________
Subtransient - saturated
X”dv __________
X”qv __________
Subtransient - unsaturated
X”di __________
X”qi __________
Negative Sequence - saturated
X2v __________
Negative Sequence - unsaturated
X2i __________
Zero Sequence - saturated
X0v __________
Zero Sequence - unsaturated
X0i __________
Leakage Reactance
Xlm __________
A-1
FIELD TIME CONSTANT DATA (SEC)
Open Circuit
T’do __________
T’qo __________
Three-Phase Short Circuit Transient
T’d3 __________
T’q __________
Line to Line Short Circuit Transient
T’d2 __________
Line to Neutral Short Circuit Transient T’d1 __________
Short Circuit Subtransient
T”d __________
T”q __________
Open Circuit Subtransient
T”do __________
T”qo __________
ARMATURE TIME CONSTANT DATA (SEC)
Three Phase Short Circuit
Ta3 __________
Line to Line Short Circuit
Ta2 __________
Line to Neutral Short Circuit
Ta1 __________
NOTE: If requested information is not applicable, indicate by marking “N / A.”
MW CAPABILITY AND PLANT CONFIGURATION
LARGE GENERATING FACILITY DATA
ARMATURE WINDING RESISTANCE DATA (PER UNIT)
Positive
R1 __________
Negative
R2 __________
Zero
R0 __________
Rotor Short Time Thermal Capacity I22t
= __________
Field Current at Rated kVA, Armature Voltage and PF
= __________ amps
Field Current at Rated kVA and Armature Voltage, 0 PF = __________ amps
Three Phase Armature Winding Capacitance
= __________ microfarad
Field Winding Resistance
= ______ ohms _____°C
Armature Winding Resistance (Per Phase)
= ______ ohms _____°C
A-2
CURVES
Provide Saturation, Vee, Reactive Capability, Capacity Temperature Correction curves.
Designate normal and emergency Hydrogen Pressure operating range for multiple curves.
GENERATOR STEP-UP TRANSFORMER DATA
RATINGS
Capacity
Self-cooled/Maximum Nameplate
___________/__________________kVA
Voltage Ratio (Generator Side/System Side/Tertiary)
___________/__________/__________kV
Winding Connections (Low V/High V/Tertiary V (Delta or Wye))
___________/_________/_________
Fixed Taps Available
Present Tap Setting
IMPEDANCE
Positive
Z1 (on self-cooled kVA rating) ___________ % _________ X/R
Zero
Z0 (on self-cooled kVA rating) ___________ % _________ X/R
EXCITATION SYSTEM DATA
Identify appropriate IEEE model block diagram of excitation system and power system stabilizer
(PSS) for computer representation in power system stability simulations and the corresponding
excitation system and PSS constants for use in the model.
GOVERNOR SYSTEM DATA
Identify appropriate IEEE model block diagram of governor system for computer representation
in power system stability simulations and the corresponding governor system constants for use in
the model.
A-3
WIND GENERATORS
Number of generators to be interconnected pursuant to this Interconnection Request: ______
Elevation: __________
________ Single Phase
_______ Three Phase
Inverter manufacturer, model name, number, and version:
List of adjustable setpoints for the protective equipment or software:
Note: A completed General Electric Company Power Systems Load Flow (PSLF) data
sheet or other compatible formats, such as IEEE and PTI power flow models, must be
supplied with the Interconnection Request. If other data sheets are more appropriate to
the proposed device, then they shall be provided and discussed at Scoping Meeting.
INDUCTION GENERATORS:
(*) Field Volts: ________________
(*) Field Amperes:
________________
(*) Motoring Power (kW):
________________
(*) Neutral Grounding Resistor (If Applicable): ________________
(*) I22t or K (Heating Time Constant): ________________
(*) Rotor Resistance: ________________
(*) Stator Resistance: ________________
(*) Stator Reactance: ________________
(*) Rotor Reactance: ________________
(*) Magnetizing Reactance: ________________
(*) Short Circuit Reactance: ________________
(*) Exciting Current: ________________
(*) Temperature Rise ________________
(*) Frame Size: ________________
A-4
(*) Design Letter: ________________
(*) Reactive Power Required In Vars (No Load): ________________
(*) Reactive Power Required In Vars (Full Load): ________________
(*) Total Rotating Inertia, H: ___________ Per Unit on KVA Base
Note: Please consult the NYISO prior to submitting the Interconnection Request to determine if
the information designated by (*) is required.
MERCHANT TRANSMISSION FACILITIES:
Note: Please consult with the NYISO prior to submitting the Interconnection Request for
guidance on the information required for Merchant Transmission Facilities.
A-5