Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. PowerPoint Slides to accompany Electric Machinery Sixth Edition A.E. Fitzgerald Charles Kingsley, Jr. Stephen D. Umans Chapter 2 Transformers 2-0 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Transformer with open secondary. Figure 2.4 2-1 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. No-load phasor diagram. Figure 2.5 2-2 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Ideal transformer and load. Figure 2.6 2-3 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Three circuits which are identical at terminals ab when the transformer is ideal. Figure 2.7 2-4 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Equivalent circuits for Example 2.2 (a) Impedance in series with the secondary. (b) Impedance referred to the primary. Figure 2.8 2-5 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Schematic view of mutual and leakage fluxes in a transformer. Figure 2.9 2-6 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Steps in the development of the transformer equivalent circuit. Figure 2.10 2-7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Equivalent circuits for transformer of Example 2.3 referred to (a) the high-voltage side and (b) the low-voltage side. Figure 2.11 2-8 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Approximate transformer equivalent circuits. Figure 2.12 2-9 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Cantilever equivalent circuit for Example 2.4. Figure 2.13 2-10 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. (a) Equivalent circuit and (b) phasor diagram for Example 2.5. Figure 2.14 2-11 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Equivalent circuit with short-circuited secondary. (a) Complete equivalent circuit. (b) Cantilever equivalent circuit with the exciting branch at the transformer secondary. Figure 2.15 2-12 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Equivalent circuit with open-circuited secondary. (a) Complete equivalent circuit. (b) Cantilever equivalent circuit with the exciting branch at the transformer primary. Figure 2.16 2-13 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. (a) Two-winding transformer. (b) Connection as an autotransformer. Figure 2.17 2-14 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. (a) Autotransformer connection for Example 2.7. (b) Currents under rated load. Figure 2.18 2-15 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Common three-phase transformer connections; the transformer windings are indicated by the heavy lines. Figure 2.19 2-16 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. 2.8 VOLTAGE AND CURRENT TRANSFORMERS Used in instrumentation applications 765 000 Volt, 10 000 Ampers can not be measured directly Most instruments range: Voltage (Potantial) Transformers (PT) 0-120 V rms; Current Transformers (CT) 0-5 A rms Equivalent circuit for an instrumentation transformer. Figure 2.21 Rc (core loss resistance) neglected in equivalent circuit. Zb is referred to as the BURDEN on that transformer. 2-17 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. FOR PT: Z eq Z b Vˆ2 N 2 ˆ V1 N1 ( R1 j X 1 )( Z eq Z b R2 j X 2 ) Z eq j X m ( R1 j X 1 ) R1 j ( X m X 1 ) Zb ( N1 / N2 )2 Zb FOR CT: j Xm Iˆ2 N1 Iˆ1 N 2 Z b R2 j ( X 2 X m ) 2-18 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Example 2.10: A 2400:120 V, 60 Hz potential transformer has the following parameter values (referred to the 2400 V winding side): X1 143 X 2 164 R1 128 X m 163k R2 141 a) Assuming a 2400 V input, which ideally should produce a voltage of 120 V at the low voltage winding, calculate the magnitude and relative phase-angle errors of the secondary voltage if the secondary winding is open-circuited. b) Assuming the burden impedance to be purely resistive (Zb=Rb), calculate the minimum resistance (maximum burden) that can be applied to the secondary such that the magnitude error is less than 0.5 percent. c) Repeat part (b) but find the minimum resistance such that the phase-angle error is less than 1 degree. 2-19 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. 2.9 THE PER-UNIT SYSTEM Computations relating to machines, transformers, and systems of machines are often carried out in per-unit form. Quantities are expressed as ratios to chosen BASE values. V, I, P, Q, S, R, X, Z, G (conductance), B (susceptance), Y can be translated. Quantityin per unit Single Phase: Sbase Vbase Ibase Base Change: Z pu2 2-20 Actualquantity Base value of quantity Zbase Vbase / I base 2 Vbase 1 Sbase2 Z pu1 2 Vbase2 Sbase1 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Example 2.12: The equivalent circuit for a 100 MVA, 7.97 kV:79.7 kV transformer is shown in Fig. 2.22a. Convert the equivalent circuit parameters to per-unit using the transformer rating as base. 7.97 kV:79.7 kV X L 0.04 X H 3.75 X m 114 RL 0.76 m RH 0.085 2-21 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Example 2.8: Three single-phase, 50 kV 2400:240 V transformers, each identical with an impedance of 1.42+j1.82 Ohm referred to high voltage side is connected Wye-Delta in a three-phase 150 kVA bank to step down the voltage at the load end of a feeder whose impedance is 0.15+j1 Ohm/phase. The voltage at the sending end of the feeder is 4160 V line-to-line. On their secondary sides, the transformer supply a balanced threephase load through a feeder whos impedance is 0.0005+j 0.0020 Ohm/phase. Find the line-to-line voltage at the load when the load draws rated current from the transformer at a power factor of 0.8 lagging. 2-22