Monitor service entrances and substations

PowerLogic

® ION8600

Add application photo in this area

Make the most of your energy

Make the most of your energy

SM

Overview

●Monitor network interties, service entrances and substations

●Ideal for independent power producers and co-generation applications

● Accurately measures energy bi-directionally, in both generation and standby modes

●Gives utilities the tools to manage complex energy supply contracts

● Includes commitments to power quality

●Integrate with energy management and SCADA systems

Copyright © Schneider Electric 2008. All rights reserved.

2

Revenue metering

●ION8600 meters meet stringent IEC and ANSI revenue metering standards on true RMS voltage, current, and power

● ANSI C12.20 0.2, Class 2, 10, & 20

● IEC 62053-22 Class 0.2S

●The meters perform power quality and compliance monitoring in accordance with CBEMA/ITIC, IEEE 519 – 1992, and IEEE 1159 and monitor flicker to IEC 61000-4-15, and harmonics to IEC 61000-4-7

●Multi-user, multi-level security protects the ION8600 meter, allowing you to control and customize access for up to 16 users

Copyright © Schneider Electric 2008. All rights reserved.

3

Modularity and communications

●ION8600 meters use patented ION® technology, giving meters a modular, flexible architecture that allows for extensive user programmability

●Meters address complex monitoring and control applications, and avoid obsolescence by adapting to changing needs

●The ION8600 offers complete communications: fiber, Ethernet, serial, and modem

● Gateway functionality simplifies communications architecture and reduces leased line or connection costs

● Ports communicate with a variety of protocols (ION, DNP 3.0, Modbus RTU,

Modbus TCP, MV-90)

● Meters have the capability to dial out when memory is near full, and to push data through SMTP (email)

Copyright © Schneider Electric 2008. All rights reserved.

4

Front panel characteristics

Backlit LCD Display

Master Reset Pinhole

(located under front label)

Demand Reset Switch

Test Mode Button

(located under front label)

Navigation Buttons

Alt/Enter Button

Copyright © Schneider Electric 2008. All rights reserved.

5

Features

Feature

Metering

Power, energy and demand

Power quality

Sag/swell, harmonics monitoring

Harmonics: individual, even, odd, up to

Harmonics: magnitude, phase, & interharmonics

Symmetrical components: zero, positive, negative

Transient detection, microseconds (68 µs for

60 Hz, 78 µs for 50 Hz)

Sampling rate, maximum samples per cycle

Uptime in number of nines

Logging and recording

Memory standard/optional

Min/max logging for any parameter

Timestamp resolution in seconds

Copyright © Schneider Electric 2008. All rights reserved.

ION8600

A

ION8600

B

ION8600

C

63 rd

40 th

65/78

256

10 MB

0.001

63 rd

256

4 MB

0.001

31 st

256

2 MB

0.001

6

Features

Feature

GPS time synchronization

Communications and I/O

RS-232/485; RS-485; Ethernet; Optical; IRIG-B

Internal modem

3-port DNP 3.0 via serial, modem, Ethernet, I/R ports

Modbus RTU slave/master; Modbus TCP via Ethernet

EtherGate, ModemGate, MeterM@il, WebMeter

Internal KYZ outputs/Form A inputs

Ext. digital status inputs/counter/solid state outputs

Setpoints, alarming, and control

Setpoints, number/minimum response time

Math, logic, trig, log, linearization formulas

Call-out on single- and multi-condition alarms

Revenue metering

MV-90 on serial, modem, & Ethernet ports, (if present)

Multi-year scheduling: hourly activity profiles

Transformer/line loss compensation; ITC

Copyright © Schneider Electric 2008. All rights reserved.

ION8600A ION8600B ION8600C

■ ■ ■

1

4/3

8/8

1

4/3

8/8

65/ ½ cycle 65/ ½ cycle 65/ 1 sec

■ ■ ■

■ ■ ■

1

4/3

8/8

7

Applications

Use the ION8600 to:

●Perform revenue metering

●Monitor both co-generation and IPP

●Perform energy pulsing and totalization

●Monitor compliance with international standards

●Analyze power quality

●Control demand and power factor

●Performing load curtailment

●Monitor and control your equipment

●Correct instrument transformers

Copyright © Schneider Electric 2008. All rights reserved.

8

Applications

●Revenue metering

● Revenue approved, bi-directional measurements; monitors four quadrants

● Monitor compliance with energy supply contracts

● Energy suppliers: offer customized rates, flexible billing, transformer/line loss compensation, and web-based reporting

● Energy consumers: audit power requirements and confirm bills

● Highest revenue metering accuracy

● Advanced security for 16 different users – individual passwords and rights

Copyright © Schneider Electric 2008. All rights reserved.

9

Applications

●Co-generation and IPP monitoring

● Monitors bi-directional flow for both generation and stand-by modes

●Energy pulsing and totalization

● Use digital I/O for KYZ pulsing, end-of-interval and totalization

●Compliance monitoring

● Monitor compliance with international flicker and harmonics standards, IEC

61000-4-7/ 4-15

Copyright © Schneider Electric 2008. All rights reserved.

10

Applications

●Power quality analysis

●Detects, records, and communicates information – nature and sequence of power quality events

●Identify the cause of transients, harmonics, sags and swells

●Measure percentage of system uptime in nines

●Waveform recording and compliance monitoring

● Monitor compliance with international flicker and harmonics standards

●Diagnose and benchmark power quality on the grid and at key customer locations – allows utility personnel to make informed decisions

●Analyze problems and avoid repeat interruptions

Copyright © Schneider Electric 2008. All rights reserved.

11

Applications

●Demand and power factor control

● Avoid penalties – load shedding, scheduling, peak shaving and capacitor bank control

● Standard demand calculation methods: block, rolling block, thermal, predicted

● Measure on any instantaneous value and record peak and minimum

Copyright © Schneider Electric 2008. All rights reserved.

12

Applications

●Load curtailment

● 800 user configurable channels via 50 data recorders (feature set A)

● Record energy, demand, voltage, current, power quality, etc.

● Implement load curtailment and distributed generation strategies

● Modbus Master enables detailed facility monitoring

●Identify inefficiencies; develop strategic load shedding applications

●Use like an RTU to intelligently poll downstream devices such as relays or other metering products

Copyright © Schneider Electric 2008. All rights reserved.

13

Applications

●Equipment monitoring and control

● Record details of equipment status

● Use information from several meters to correlate system-wide events and equipment operation

● Base maintenance schedules on operating history

● Meter all your utilities including gas, steam, water and more

Copyright © Schneider Electric 2008. All rights reserved.

14

Applications

●Instrument transformer correction

●Compensate for line loss, and power and instrument transformers

●Save money and improve accuracy

● Install on the low side of your transformers to compensate for less accurate equipment

Copyright © Schneider Electric 2008. All rights reserved.

15

More Information

●Visit us on the web at:

●www.powerlogic.com

Copyright © Schneider Electric 2008. All rights reserved.