PS100 - Schneider Electric

advertisement
Easergy PS100
Backup Power supply for Electrical substations
Overview
01/2012
Content
> Why PS 100 ?
> Examples of architectures
> PS 100 Main features and benefits
> HMI & lay out
> Communication and Monitoring
> References & Logistic
> Documentation
> Conclusions
Schneider Electric - Easergy –PS100 presentation – Feb 2012 v4
2
Why PS 100 ?
● The “PS 100” unit supplies back-up operating power for :
• MV switchgear electrical mechanism ( motors and coils )
• Transmission equipment ( e.g radio )
• Protection relays , Fault passage indicators or others IEDs
• And all others devices in MV/LV substations (LV breakers, PLC concentrator..)
● The “PS 100” has been designed for supplying power in distributed
architectures ( SC110A, Flair 23VD, VIP410, Sepam…) to fit in LV cubicles of SM6,
Premset * …
* New MV switchgear range (ex- Matrix project)
● The “PS 100” will offer a new elegant solution in application in current MV/LV
substations without RTU ( Remote Terminal Unit)
- is integrated in Advan6 wave 3
- in repetitive MV/LV substation with SM6, MH 24+, FBX & RM6 (3 or 4
functions)
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
3
e.g : RM6 or M24,SM6 in MV/LV SS
protection transformer power
PS100
VIP410 or
Sepam 10
Functions :
Transformer Protection,
DGPT2, DMCR or thermal
protection activating coil tripping of
Fuse switch combination or Circuit
breaker
or
IM Switch units
wo electrical
mechanism
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
Circuit breaker
unit with
autonomous
protection or
Sepam
Fuse switch
Combination
unit
4
e.g : SM6 in CIB SS
( in commercial and industrial building)
protection transformer power
PS100
VIP410 or
Sepam 10
Functions :
Transformer Protection,
DGPT2, DMCR or thermal
protection activating coil tripping of
Fuse switch combination or Circuit
breaker
or
IM Switch units
wo electrical
mechanism
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
Circuit breaker
unit with
autonomous
protection or
Sepam
Fuse switch
Combination
unit
5
e.g : RM6 or M24+ or SM6 in MV/LV SS
Monitoring & protection transformer
L500
Third Party
R200
220Vac
IEC 101
IEC 104
DNP3
over radio, GSM,
GPRS,…
Functions :
Coil / Transformer Protection by
Fuse switch combination or Circuit
breaker
Feeder automation
- FPI
LV monitoring
Load management
Alarms management
PS100
RS 485
48Vcc
12V
IM Switch units
(wo Electrical
mechanism)
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
Fuse switch
Combination or
circuit breaker
unit
6
e.g : Premset or FBX+ RMU in Utilities
Full feeder automation in distributed architecture
DMS
MDM
Functions :
Transformer Protection
Feeder automation
- FPI
- Switchgear control by Switch
controller SC110A or SC105
- Sectionalizer
- LV monitoring
Load management
Alarms management
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
R200
PS100
F23D
SC110A
PM800 VIP
IEC 101
IEC 104
DNP3
over radio,
GSM,
GPRS,…
PLC
connection
Smart meters
7
PS 100 Main features
High-availability back-up power supply for medium voltage substations
Uninterrupted power supply
24 or 48 V dc
LV main power supply
100-250 V ac or
110 V dc
90W + 300W 1mn
Uninterrupted power supply
12 Vdc
25 W
PS100
Charging or
supplying
Communication devices
• RTU
• Modem
• Radio
Power supply
Information
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
12 Vdc battery
8
PS 100 Main features
IP 20 / IK 7
Dimensions : 125 x 165 x 160 mm & 2,6 kg
Installation on Din rail mounting
Battery size : 38 AH
170 x 165 x 197 mm
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
9
PS 100 : HMI & lay out
250 Vac main power
supply terminals
Battery & Sector state outputs
2 rotary switches for Modbus
address configuration
Display
AC power
supply OFF
Battery fault
Reset button
Status of the
unit
24 or 48V ON
12V ON
2 RJ45 connectors for
Data transmission
Communication
life indicator
12 -24 or 48 V
Vcc outputs
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
10
Autonomy
● Autonomy up to 24 hours
● Depend on
● Mainly the permanent Load (PL)
● the “Energy backup” (Pb)
● The type of battery (38Ah, 24Ah)
● Temperature
● Battery age
● The non permanent load is estimated
to 16 Open&Close cycles of
Switchgear. (Ps)
I.e : 4 operating Sepam10 (4x8=32 W)
allows 12 hours of autonomy
● PS100 Autonomy
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
11
PS100 supply capacity
● 3 examples of maximum number of
devices for 1 PS100:
CB with
protection
relay and
motorization
Switch with
Fault
detector and
motorization
● 1 PS100 supplies up to 2 protection
relays or 16 switches
ATS with 2 SW
or 2CB
2
4
0
1
15
0
0
8
1
● With 3 or 4 protection relays, it is
recommended to use 2 PS100 with
redundancy
● With an Automatic Transfer Switch
device, it is recommended to use a
second PS100 for protection relays.
● For more than 4 Protection relays ,
PS100 isn’t usable
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
12
Benefits
Optimized battery backup
● Only one battery to simplify the replacement
● The PS100 needs only one battery, simplifying replacement vs traditional
backup power supplies require a set of 2 or 4 batteries to produce 12V or
48V, with complicated replacement and adjustment of the battery pack.
● Battery can be purchased easily, anywhere in the world : sealed lead 12V
battery ,10 years life
● To prevent power network cuts
● Enables output voltage backup in case of cuts up to 24 hours
● PS100 protects and optimizes the battery duration
● Ensures its charge with a regulated and temperature-compensated charger
● Checks the battery and prevents the battery deep discharge level
● Measures battery ageing and alarms before battery end of life
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
13
Benefits
High availability
● PS100 is robust to the harsh environment of electrical substation
● Reliability is a key point for Electrical substations :
Insulation: 10 kV,
- 40°C to +70°C operating temperature...
● Electronic protection against over voltage, overloads and short circuit
● Automatic restart after fault
● Additional “Energy back up” to restart the installation after a prolonged network
cut
● an optional Energy back up can be enabled with a local push button to provide
energy for restarting the protection relays and electrical control of MV
switchgears at installation restarting.
● Forecast backup reservation : 300 W - 1mm
●
Modbus communication port forwards monitoring data to allow optimized
maintenance operations.
● A limitation, dedicated for radio units, is set up to avoid the battery deep discharge
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
14
Benefits
Redundancy to increase availability and power
Power supply paralleling
- more availability
- or additional power
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
15
Communication and monitoring
Protocol
Modbus
RS 485- configuration of Modbus address by means of 2
rotary switches
Connector
RJ45
2
Data
transmission
Measuring &
status Data with
date and time
 AC supply presence
 Battery state ( disconnected, failure, available capacity,
optional back-up reservation)
 PS100 Global Status (Ready /internal Fault)
 12V & 48V or 24V output failure
 Threshold Serious discharge, threshold Energy back-up
 Charge indicator, diagnosis information
 Reset
Settings
 AC voltage loss threshold , DC serious battery discharge
threshold
 Battery Test frequency
 Energy Back-up enable / disable
Command
 Restart 12/48 V ( Energy Back-up)
 Run led test
 Run battery test
Time stamped
events
 100 events ( clock resolution 1ms )
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
16
References
DESIGNATION
REFERENCE
FEATURE
PS100-24V
EMS58580
Back-up Power supply - 12V, 24V output
PS100-48V
EMS58581
Back-up Power supply - 12V, 48V output
Bat 24AH
EMS58582
Long life battery - 12V - 24A.h
Bat38AH
EMS58583
Long life battery - 12V - 38A.h
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
17
e.g : integration PS 100 in IP 31 cabinet
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
18
Documentation
User guide – Manuel d’utilisation
Leaflet – Notice technique
Sales support - Memo vente
Schneider Electric - Easergy – 01/2013 /PS100 Introduction
19
Download