Fire Dynamics II Lecture # 11 Post-flashover Fire Jim Mehaffey 82.583 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 1 Post-flashover Fire Outline • Ventilation controlled fires • Fuel-surface controlled fires • Model: Hot gas temperature (function of time) • Fire resistance test • Characterizing fire severity • Design for resistance Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 2 Post-flashover Fire • Assumptions - Well-stirred reactor - Th uniform throughout enclosure Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 3 Post-flashover Fires Wood Cribs, Pallets & Stacked Furniture • Harmathy (1972) identified two burning regimes for room fires involving wooden cribs: ventilation controlled & fuel-surface controlled • R m = mass loss rate of fuel (kg s-1) • = ventilation parameter (kg s-1) = O A g h 3.76 A h • Af = exposed surface area of fuel (m2) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 4 Post-flashover Fires Involving Wooden Cribs Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 5 Example Calculation of Equivalence Ratio Post-flashover Fires Involving Wooden Cribs • Post-flashover fire is ventilation-controlled if / Af < 0.63 kg m-2 s-1 A h A f 0.07 m 1/2 Eqn (11-1) • Fuel mass loss rate is m 0.0236 kg s 1 m 0.09 A h kg s 1 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # Eqn (11-2) 6 What do we know about ventilation-controlled post-flashover fires involving wooden cribs, pallets or stacked furniture? • Fuel mass loss rate is m 0.09 A h kg s 1 Eqn (11-2) • Rate of entry of air into room is ma 0.45 A h kg s 1 Eqn (11-3) • Rate of exit of hot gas from room is mh 0.54 A h kg s Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 1 Eqn (11-4) 7 Ventilation-controlled post-flashover fires involving wooden cribs, pallets or stacked furniture • Equivalence ratio is ~ 0.92 Eqn (11-5) • The rate of heat release of the fire is Q 1,050 A h (kW) Eqn (11-6) • The mass flow rate of soot out of the enclosure is mS 1.5 A h (g s ) -1 Eqn (11-7) (Important for assessment of visibility outside the room) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 8 Ventilation-controlled post-flashover fires involving wooden cribs, pallets or stacked furniture • The mass flow rate of CO out of the enclosure is mCO 18 A h (g s 1 ) Eqn (11-8) • Concentration of CO in hot gas leaving enclosure is VCO 3.4% 34,200 ppm Eqn (11-9) (Important for assessment of toxicity outside the room) (This is a very high and dangerous concentration) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 9 Ventilation-controlled post-flashover fires involving wooden cribs, pallets or stacked furniture • The mass flow rate of CO2 out of the enclosure is mCO2 113 A h (g s-1 ) Eqn (11-10) • Concentration of CO2 in hot gas leaving enclosure is VCO2 13.7% 137,000 ppm Eqn (11-11) This would cause significant increased CO uptake due to hyperventilation. See slide 3-32 in Fire Dynamics I. Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 10 Ventilation-controlled post-flashover fires involving wooden cribs, pallets or stacked furniture • The mass flow rate of N2 out of the enclosure is mN2 339 A h (g s ) 1 Eqn (11-12) • Concentration of N2 in hot gas leaving enclosure is VN2 64.8% Eqn (11-13) On a molar basis, air is 78% N2 and the hot gas is 65% N2. Since molecular wt of N2 is 28, molecular wt of air and the hot gas is close to 28. Therefore, the value 28.95 can be use for air and the hot gas with confidence. Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 11 Fuel-Surface Controlled: Post-flashover Fires • T.Z. Harmathy 1972 // wood cribs (cellulosic) • Post-flashover fire is fuel-surface controlled if / Af 0.63 kg m-2 s-1 A h A f 0.07 m 1/2 Eqn (11-14) • Fuel mass loss rate is 1 m 0.0062 A f kg s m 0.0062 G kg s 1 Eqn (11-15) G = Quantity of wood in room (kg) = Af / G = specific area of wood (m2 kg-1) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 12 The Rate of Burning of Fuel-Surface Controlled: Post-flashover Fires • Rate of mass loss / unit surface area of fuel is m" m Af 0.0062 kg m -2 s 1 6.2 g m -2 s 1 Eqn (11-16) • Douglas fir: – Assume = 550 kg m-3. – Assume 80% converted to volatiles and 20% to char – Rate of advance of char front: Vc = 0.85 mm min-1 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 13 Some Comparisons • For massive timbers in standard fire resistance test Vc = 0.6 mm min-1 • Rate of char advance in wood cribs is (slide 8-36) Vc = 2.2 x 10-6 D-0.6 (m s-1) • Sticks of square cross and side D (m) D (mm) 38 45 80 Vc (mm / min) 0.94 0.85 0.60 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 14 - Specific Area of Wood • For Douglas fir: = 550 kg m-3 • Dimensional lumber (4 sides exposed) – 2x2 (38 mm x 38 mm) = 0.191 m2 kg-1 – 2x4 (38 mm x 89 mm) = 0.136 m2 kg-1 – 2x12 (38 mm x 286 mm) = 0.108 m2 kg-1 • Heavy timber column (4 sides exposed) – 8x8 (191 mm x 191 mm) = 0.038 m2 kg-1 • Plywood (1 side exposed) – 1/2” = 12.7 mm thick = 0.143 m2 kg-1 – 1/4” = 6.4 mm thick = 0.286 m2 kg-1 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 15 - Specific Area of Wood • Harmathy’s correlation for fuel-surface controlled burning derived from experimental data for wood cribs • Correlation is likely okay for wood cribs, stacked wood pallets & stacked wood furniture where most surfaces are shielded from radiation from hot upper layer • For such items assume ~ 0.13 m2 kg-1 Eqn (11-17) • Harmathy’s correlation for fuel-surface controlled burning and ~ 0.13 m2 kg-1 are not appropriate for scenarios involving large exposed wooden surfaces like wall panelling Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 16 G - Quantity of Fuel (kg) • Quantity of fuel in a room is commonly expressed in terms of a calorifically equivalent quantity of wood • Many surveys have been conducted to determine mass of fuel / floor area • Definition: L = specific fire load (kg m-2) = mass of fuel / floor area G = L x (floor area) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # Eqn (11-18) 17 L - Specific Fire Load (kg m-2) • L is random variable: mean L & standard deviation L • Harmathy recommendations (old data) Occupancy Dwelling Office School Hospital Hotel L -2 (kg m ) 30.1 24.8 17.5 25.1 14.6 L -2 (kg m ) 4.4 8.6 5.1 7.8 4.2 • Assuming L follows a normal distribution 80th percentile L80 L 0.84 L 95th percentile L95 L 1.64 L Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # Eqn (11-19) 18 Duration of a Post-flashover Fire • Assume volatiles released in post-flashover phase – Little mass loss in pre-flashover phase – Dominantly glowing char in decay phase • Assume total mass loss during post-flashover phase is MT = 0.8 G (kg) Eqn (11-20) • Duration of post-flashover phase is MT Eqn (11-21) m Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 19 Duration of a Post-flashover Fire • For a fuel-surface controlled fire 0.8 G 990 s 16.5 min 0.0062 G Eqn (11-22) • For a ventilation controlled fire 0.8 G 8.89 G 16.5 min 0.09 A h A h Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # Eqn (11-23) 20 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 21 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 22 Duration of Post-flashover Fire A h Test 1 2 3 4 5 m 5/2 0.92 0.92 0.92 1.42 2.13 G Af kg 2 m 130 130 234 234 234 16.9 16.9 30.4 30.4 30.4 A h /A f m 1/2 0.054 0.054 0.030 0.047 0.070 VC or FSC VC VC VC VC VC? Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # Duration Duration test theory min min 18.5 21 28 24 17 20.9 20.9 37.7 24.4 16.5 23 Kemano F ire Exposures 1200 .0 Liv ing R oom F ire s - D uplex 1000 .0 AST M E 119 & CAN/UL C-S1 01 o Tempe ra ture ( C) 800 .0 600 .0 400 .0 200 .0 0 .0 0 .0 10 .0 20 .0 30 .0 Time (min) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 40 .0 50 .0 60 .0 S -987 24 Time-averaged Temperatures in Room Fires Experimental data from SFPE handbook Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 25 Post-flashover Fires Involving Wood, PMMA & PE Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 26 • Burning rate in post-flashover fires involving fuels with exposed surfaces is enhanced by radiation • Large burning rates inhibit inflow of air so increase equivalence ratio reduced heat release (inside) • Heat release rate still can be ventilation-controlled Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 27 Traditional Design for Fire Resistance • Basic Objective: Provide sufficient time for escape • Strategy # 1 - Compartmentation: Inhibit fire spread: enclose compartments with fire resistant separations • Strategy # 2 - Structural Fire Protection: Delay collapse of structure: make elements fire resistant • Functional Requirement: Assemblies must perform acceptably when exposed to design fire & design load • Acceptance Criterion (Not clearly stated): Fire separations & structural members must perform intended functions for duration of fire Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 28 Physical Model - Post-flashover Fire The Fire Resistance Test • Physical (as opposed to mathematical) model of a post-flashover fire • Initial development ~ 1908 Standard Fire Resistance Tests • CAN/ULC-S101, Standard methods of fire endurance tests of building construction materials • CAN/ULC-S101 = ASTM E119 (Determination of loads is different) • ISO 834 = international standard Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 29 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 30 Standard Temperature-time Curve: CAN/ULC-S101 or ASTM E119 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 31 Performance Requirements Separating Element 1. Specimen remains in place 2. No passage of hot gas / flame 3. T < 140°C (average unexposed side) T < 180°C (single point, unexposed side) 4. Hose-stream Test Load-bearing Element 1. Specimen supports design load Fire-resistance Rating • Time specimen meets performance requirements Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 32 Principle for Establishing Fire Resistance Requirements for Buildings Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 33 Principle for Establishing Fire Resistance Requirements for Buildings Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 34 NBCC Requirements Compartmentation • Fire separations often must be fire rated • Fire separations between public corridors & suites in small buildings require fire-resistance rating of 3/4 • Fire separations between public corridors & suites in large buildings require fire-resistance rating of 1 hour Structural Fire Protection • Floors and structural elements supporting floors often must be rated • In small buildings: fire-resistance rating of 3/4 or 1 h • In large buildings: fire-resistance rating of 2 h Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 35 Performance-based Design for Fire Resistance Design Fire Scenarios Buildings with High Degree of Compartmentation • Examples: Apartment & office buildings • Scenario: Post-flashover fire (no suppression) • Design Fire: A credible but severe post-flashover fire Buildings with Large Open Spaces • Examples: Warehouses & Factories • Scenario: Localized fire (diffusion flame) • Design Fire: A credible but severe localized fire Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 36 Model for Post-flashover Fire Severity Japanese Parametric Model Basic Assumptions • Ventilation: Assume unprotected openings are open Assume fire-rated closures remain intact • Heat Release: Heat released in post-flashover phase Maximum possible value from t=0 Q 1,500 A h (kW) • Fuel Load: Total fuel load is consumed Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 37 Japanese Parametric Model for Ventilation Controlled Fires • Temperature of fire gases: Th(t) (K) Th(t) - To = t1/6 where Eqn (11-24) = a constant (K s-1/6) t = time since ignition (s) 1/ 3 A h 3.0 TO AT k c Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # Eqn (11-25) 38 A = area of openings (windows) (m2) h = height of openings (windows) (m) AT = total area of boundaries (m2) k = thermal conductivity boundaries (kW m-1 K-1) = density of boundaries (kg m-3) c = specific heat of boundaries (kJ K-1 kg-1) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 39 Duration of post-flashover fire: tD (s) L AF tD 0.09 A h Eqn (11-26) L = fuel load (kg m-2) AF = area of the floor (m2) Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 40 Japanese Parametric Model Model Validation Test G = L AF (kg) Ah 5/2 (m ) AT 2 (m ) kc -2 -1/2 -1 (kJ m s K ) -1/6 (K s ) tD (s) 1 130 0.92 45.24 0.868 252 1570 2 130 0.92 45.24 0.334 346 1570 3 233 0.92 45.24 0.666 275 2814 4 233 1.42 44.96 0.666 318 1823 5 233 2.13 44.61 0.666 365 1215 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 41 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 42 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 43 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 44 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 45 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 46 Japanese Parametric Model Option 1: Response of Assembly Predicted Using Mathematical Model • Fire characterized by temperature-time curve generated by Japanese parametric model. • Load carried by structural members taken directly from structural analysis (Part 4 of the NBCC). • A fire-resistance model is used to predict thermal and structural response of each assembly. • Do fire separations and structural members meet the acceptance criteria? Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 47 Japanese Parametric Model Option 2: Response of Assembly Predicted Using Physical Model • Heat absorbed by unit surface area of fire separations or structural members in post-flashover fire: q” (kJ m-2) 3 q" ( t D) 2 • For ISO 834: • For ASTM E119: k c t 2D / 3 Eqn (11-27) = 230 K s-1/6 = 229 K s-1/6 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 48 Normalized Heat Load Concept (Harmathy & Mehaffey) • Compartment fire of duration tD is equivalent in severity to an ISO 834 fire test of duration teq in which same heat is absorbed per unit area t eq 230 3/ 2 tD Eqn (11-28) • Assembly fire resistance rating teq is acceptable • Advantage of Option 2: Existing fire resistance ratings can still be used • Drawback of Option 2: Fire-resistance ratings are determined using max load not actual design load Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 49 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 50 Design Considerations Fuel Load • Use 95th percentile in fuel load distribution: Eqn (11-19) Ventilation • Assume unprotected openings are open • Assume fire-rated closures remain intact • If several vents at approximately the same elevation A h A1 h1 A 2 h 2 A 3 h 3 ... Eqn (11-29) Compartment Boundaries • Boundaries do not include internal partitions • If there is more than one boundary material A T kc A T,1 k1 1c1 A T,2 k 2 2 c 2 A T,3 k 3 3c3 ... Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 51 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 52 Example - Design for Fire Resistance Prevent Fire Spread from an Office Suite Room Dimensions: 6.0 m x 4.0 m x 2.4 m (height) Floor Area: 6.0 m x 4.0 m = 24 m2 Window Dimensions: 4.0 m x 1.5 m (height) Fuel Load: 95th percentile Eqn (11-19) L95 = L + 1.64 L = (24.8 + 1.64 x 8.6) kg m-2 = 38.9 kg m-2 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 53 Ventilation: Window breaks & door remains intact A h 4.0 m x 1.5 m 1.5 m 7.35 m5/2 Compartment boundaries A T kc A T,1 k1 1c1 A T,2 k 2 2 c 2 = [ceiling + walls - vents][gypsum bd] + [floor][n.w. concrete] = [6x4 + 6x2.4x2 + 4x2.4x2 - 1.5x4] x 0.742 + [6 x 4] x [2.192] = 101.58 kJ s-1/2 K-1 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 54 Japanese Parametric Model • Temperature of fire gases: Th(t) (K) Th(t) - To = t1/6 Eqn (11-24) where (K s-1/6) characterises the fire 1/ 3 A h 3.0 TO AT k c Eqn (11-25) \ = 3 x 293 x [ 7.35 / 101.58 ]1/3 = 366 K s-1/6 Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 55 Japanese Parametric Model • Duration of post-flashover fire: tD (s) L AF tD 0.09 A h Eqn (11-26) \ tD = 38.9 x 24 / [ 0.09 x 7.35 ] = 1411 s = 23.5 min • Duration of equivalent fire resistance test: teq t eq 230 3/ 2 tD Eqn (11-28) \ teq = [366 / 230]3/2 x 23.5 min = 47.2 min Carleton University, 82.583, Fire Dynamics II, Winter 2003, Lecture # 56