Wind Farm Protection Automation, Lattes Co-generation/Embedded Machines AR? 81U/O Frequency 27/59 Voltage 50/51N 47/46 59N Residual Voltage df/dt ROCOF dV Voltage Vector Shift O/C & E/F NPS Voltage NPS O/C Schneider Electric - Marketing - Guilhen – Oct 2010 PES system Islanded load fed unearthed 2 P341 Interconnection Protection 64 67N 46 50 51 50N 51N 59N 67 81O 81U df dt dV 27 59 47 32 R,LF,O Schneider Electric - Marketing - Guilhen – Oct 2010 3 33kV Transformer feeder extension to windfarm - <10MVA,11kV collection Schneider Electric - Marketing - Guilhen – Oct 2010 4 33kV ring network with embedded generation, 2 wind farms with collection voltage at 33 kV Schneider Electric - Marketing - Guilhen – Oct 2010 5 Comprehensive Protection Schneider Electric - Marketing - Guilhen – Oct 2010 6 Windfarm Protection Relays Models ● P341 G59 Interconnection Protection Relay ● P12x/P13x/P14x Feeder Protection (OC, EF and AR) ● P92x Voltage/Frequency protection Schneider Electric - Marketing - Guilhen – Oct 2010 7 ER G59 Protection Requirements for Connection of Distributed Generators <5MW to Systems <20kV Schneider Electric - Marketing - Guilhen – Oct 2010 8 MiCOM P341 Applications G59 Protection Equipment - MiCOM P341 Generator Protection Schneider Electric - Marketing - Guilhen – Oct 2010 9 MiCOM P341 Applications G59 Protection Equipment General Requirements Protective Equipment ● To inhibit connection of the generating equipment to the REC’s supply unless all phases of the REC’s supply are energised and operating within the agreed protection settings ● To disconnect the generator from the system when a system abnormality occurs that results in an unacceptable deviation of the voltage or frequency at the point of supply - MiCOM P341 Generator Protection Schneider Electric - Marketing - Guilhen – Oct 2010 10 MiCOM P341 Applications G59 Protection Equipment General Requirements Protective Equipment ● To disconnect the generator from the REC’s system in the event of loss of one or more phases of the REC’s supply to the installation ● To ensure that either the automatic disconnection of the generating plant, or where there is component supervision of an installation, the operation of an alarm with audible and visual indication, in the event of a failure of any supplies to the protective equipment that would inhibit its correct operation - MiCOM P341 Generator Protection - Schneider Electric - Marketing - Guilhen – Oct 2010 11 MiCOM P341 Applications G59 Protection Equipment Protection Requirements for Private Generator Operating in Parallel with Electricity Board Network Notes: (1) Protection for generators (2) Sensitive Relay (3) Optional (4) Application dependant Protection required Protection required for Electricity Board Network Permanent Parallel Operation LV Generators HV Generators Export No Export Small <150kV Medium 150-250kVA Large >250kVA Under & Over Volt & Frequency Loss of Mains (1) Overcurrent Earth Fault Reverse Power (2) (3) (3) Directional Overcurrent (3) Neutral Volt Displacement (4) Parallel Limit Timer Schneider Electric - Marketing - Guilhen – Oct 2010 12 MiCOM P341 Applications G59 Protection Equipment Protection Requirements for Private Generator Operating in Parallel with Electricity Board Network Notes: (1) Protection for generators (2) Sensitive Relay (3) Optional (4) Application dependant Protection required Protection required for Electricity Board Network Short Term ‘Test’ Parallel Operation (5 min max) LV Generators HV Generators No Export Small <150kV Medium 150-250kVA Large >250kVA Under & Over Voltage & Frequency Loss of Mains (1) Overcurrent Earth Fault Reverse Power Directional Overcurrent (3) Neutral Voltage Displacement (4) Parallel Limit Timer Schneider Electric - Marketing - Guilhen – Oct 2010 13 MiCOM P341 Applications G59 Protection Equipment Protective Equipment and Recommended Setting for LV Supply Arrangements Protection Phases Trip Setting Total* Tripping Time Under Voltage Over Voltage All -10% (Phase neutral) 0.5s All +10% (Phase neutral) 0.5s Under Frequency One -6% 0.5s Over frequency One +1% 0.5s * The total tripping time includes any intrergration or timing period of the protection relay as well as relay circuit-breaker operating time For all other arrangements the settings of the relays should be agreed with the REC Schneider Electric - Marketing - Guilhen – Oct 2010 14 MiCOM P341 Applications G59 Protection Equipment Voltage Vector Shift Protection An expression for a sinusoidal mains voltage waveform is generally given by the following: V = Vp sin (wt) or V = Vp sin (t) where (t) = wt = 2ft If the frequency is changing at constant rate Rf from a frequency fo then the variation in the angle (t) is given by: (t) = 2f dt, (F = Fo + Rf t) which gives (t) = 2{fo t + t Rf t/2} and V = V sin {2(fo + t Rf/2)t} Hence the angle change (t) after time t is given by: (t) = Rf t2 Schneider Electric - Marketing - Guilhen – Oct 2010 15 MiCOM P341 Applications G59 Protection Equipment Single phase line diagram showing generator parameters jX R IL E VT - MiCOM P341 Generator Protection - Schneider Electric - Marketing - Guilhen – Oct 2010 16 MiCOM P341 Applications G59 Protection Equipment Vector Diagram Representing Steady State Condition E IL VT IL X IL R - MiCOM P341 Generator Protection - Schneider Electric - Marketing - Guilhen – Oct 2010 17 MiCOM P341 Applications G59 Protection Equipment Transient voltage vector change due to change in load current IL E I LX VT IL VT IL I LR I LX” - MiCOM P341 Generator Protection - Schneider Electric - Marketing - Guilhen – Oct 2010 18 MiCOM P341 Applications G59 Protection Equipment df/dt The rate of change of speed, or frequency, following a power disturbance can be approximated by: P.f df/dt = where 2GH P = Change in power output between synchronised and islanded operation f = Rated frequency G = Machine rate MVA H = Inertia constant Schneider Electric - Marketing - Guilhen – Oct 2010 19 MiCOM P341 Applications G59 Protection Equipment P341 df/dt calculation df/dt = Fn - f n - 3 cycle 3 cycle Two consecutive calculations must give a result above the setting threshold before a trip decision can be initiated - MiCOM P341 Generator Protection - Schneider Electric - Marketing - Guilhen – Oct 2010 20 MiCOM P341 Applications G59 Protection Equipment df/dt+t: Time Delayed ROCOF Start t Pick up cycles Trip f Time delay df/dt Setting Schneider Electric - Marketing - Guilhen – Oct 2010 21