Cable selection project Factory office installation maximum demand sub- mains cable • Each factory/warehouse consists of the following loads • 8- 250W mercury vapour lamps • 4-60watt incandescent lamps • 3-18watt fluorescent. External • 1-500watt sodium vapour lamp. External • 6-10A double single phase outlets • 3-20A 3 phase outlets • 1- 15A three phase storage hot water Office • • • • • Lighting 8-double 36 watt fluorescent lights Power 8- double10A single phase outlets 1- single 10A single phase outlet Step 1 • Divide the installation into circuits and distribute these circuits across the three phases • Calculate the maximum demand of the installation • The maximum demand of the sub- mains is the load on the heaviest loaded phase Arrange into circuits • Factory • • • • • • • • • • • • Circuit 1 (4-250W) lamps (R ) Circuit 2 (4-250W) lamps (W) Circuit 3 (4-60watt) + 2 EF 60W (B) Circuit 4 (3-18watt) F/lamps (W) Circuit 5 (1x500watt SV lamps) (B) Circuit 6 (2 double 10A) outlets (R) Circuit 7 (2 double 10A) outlets (W) Circuit 8 (2 double 10A) outlets (B) Circuit 9 (20A 3 phase) outlet Circuit 10 (20A 3 phase) outlet Circuit 11(20A 3 phase) outlet Circuit 12 (15A 3 phase) HWS • Office • • • • Circuit13 (8 double36 watt fluorescent) Circuit14 (3 double 10A outlets) Circuit15 (3 double 10A outlets) Circuit16 (2 double 1 single 10A outlet) (B) (R) (W) (B) MD Sub-mains using table C2 Factory Circuit no • 1 2 3 4 5 6 7 8 Load group Load calculation R A (4-250W)MV lamps 1.5A each 4 x 1.5 = 6 6 A (4-250W) MV lamps 1.5A each 4 x 1.5 = 6 A (4-18W) energy saver 0. 05A each 2x60w exhaust fans at 0.3A each (0.05 4) (0.3 2) 0.8 A (3-18W) fluorescent 0.12A each 0.12 3 .36 0.36 A 1-500w sodium vapour lamps 0.8 pf 500 2.72 230 0.8 pf 2.72 Bi 2-10A double 1Phase outlets = 4 1000 w 3 750 w 14.14 230 Bi 2-10A double 1Phase outlets =4 1000 w 3 750 w 14.14 230 Bi 2-10A double 1Phase outlets =4 1000 w 3 750 w 14.14 230 W B 6 0.8 14.14 14.14 14.14 Maximum demand Sub-mains Circuit no Load group Load calculation R W B 9 10 11 12 B (iii) 20A three phase outlet Full load 20 20 20 B (iii) 20A three phase outlet 75% Full load 15 15 15 B (iii) 20A three phase outlet 75% Full load 15 15 15 G 15A three phase HWS Full load 15 15 15 office 13 14 15 A 8-twin 36w fluorescent 8 0.78 6.24 B (i) 3-10A double outlets single phase 6 750 w 19.56 230 B (i) 3-10A double outlets single phase 6 750 w 19.56 230 16 B (i) 2-10A double 1-10A single Outlets single phase Maximum D 6.24 19.56 19.56 5 750w 16.3 230 16.3 104.7 104.7 105.6 Cable size for sub-main to factory/warehouse unit1 • The Maximum demand is 106A Mains Sub-mains X90 SDI Cables double insulated buried in separate U/G conduit Current carrying capacity T7/18 25mm² = 135A Voltage drop T41 Vc =1.62mV/Am Vd Vc L I 1.62 38 106 6.52 Volts 1000 1000 So 25mm² X90 SDI Cables in separate conduits will satisfy both current and voltage drop requirements. Unit 1 has the longest run (38 metres) so 25mm² will satisfy units 2 and 3 Installation load • • • • • • • • The installation consists of the following loads. Lighting 24 – 250W mercury vapour Lamps 24 – 2x36W Fluorescent Luminaires 0.78A each 12 – 18W fluorescent to replace 60W 8 – 18W Fluorescent 6 – 60W exhaust fans 0.3A each 3 – 500W Installation load • • • • • Power 42 – double 10A single phase outlets 3 – single 10A single phase outlets 9 – 20A three phase outlets 3 – 3 phase HWS Consumers Mains maximum demand Load Group load Calculation R W B 24 – 250W mercury vapour Lamps (8 per phase) 8 x 1.5 = 12 12 12 12 6.24 6.24 6.24 24 – 2x36W Fluorescent Luminaires (8 per phase) 8 0.78 6.24 12 – 18W fluorescent (0.05A) to replace 60W 4 x 0.05 = 0.2 0.2 0.2 0.2 6 – 60W exhaust fans (0.3A each) 2 x 0.3 = 0.6 0.6 0.6 0.6 8 – 18W Fluorescent (0.12A) 3,3,2 per phase 0.12 x 3 =.36 0.12 x 2 = .24 0.36 0.36 0.24 2.71 2.71 2.71 1000 28 750 95.65 230 95.65 95.65 95.65 9 – 20A three phase outlets 20 + 8 x 15 =140 140 140 140 3 - 15A 3phase HWS 3 x 15 = 45 45 45 45 302.8 302.8 302.7 3 – 500W 14 Double +1 single 10A single outlets per phase (29 per phase) 87 outlets total MD 500 2.71 230 0.8 Cable Size consumers mains • The consumer mains are X90 SDI cables installed in conduit U/G for a length of 40 metres • Determine the cable size to suit current and voltage drop requirements • Table 2.4 item 2 refers to Table 7/16 • 150mm² = 330A The cable can carry the MD current • Check for voltage drop. Table 41 Vc for 150mm² conductors = 0.309mV/Am (60ºC) The cable is rated at 90ºC and by choosing a Vc value at 60ºC this allows for temperature rise under Short circuit conditions Vd Vc L I 0.309 40 303 3.745 1000 1000 Progressive Voltage drop Consumers main Volt drop 3.745 volts 40 metres Turret 10 metres 20 metres MSB DB unit3 DB Unit 2 38 metres Sub-main voltage drop 6.52 volts 3.745 Volts 6.52 Volts DB Unit 1 Progressive Voltage drop distribution board unit 1 Consumers mains Sub-main Final sub-circuits 5.57 volts allowed in all single phase circuits 3 phase Value 3 phase value 9.735 Volts allowed in all 3 phase 3.745+6.52 = 10.265 volts 3 phase Therefore the circuits 3.745 volts 6.52 volts 3 phase voltage drop allowed in all 3 phase circuits supplied from the DB Unit1 is 20 – 10.265 = 9.735 V To determine the single phase voltage allowed in final sub circuits 10.265 10.265 5.93Volts 1 . 73 3 Therefore the single phase Voltage drop allowed in all single phase circuits supplied from distribution board Unit 1 is 11.5 – 5.93 = 5.57 Volts Circuit arrangements Cable Maximum Installation Parameters Designation demand AZ/NZS 3008/1/1 Table No column Consumers mains 302 A XLPE (X90) SDI enclosed UG Table 2.4 Table 7 4 16 Sub-mains 106 A X90 SDI enclosed U/G Table 2.4 Table 7 4 18 4x250W MV 6A Lamp Factory 2 circuits TPS V90 installed with 3 other circuits De rate 0.78 Table 2.1 Table 9 Table 24 4 2 8 10A outlets Factory TPS V90 installed with 3 other circuits spaced De rate 0.87 item22 Table 2.1 Table 9 Table 24 4 2 8 16A Cable Maximum designation demand Installation parameters AS/NZS 3008 Table no 3 phase outlets TPS V90 installed with 2 other circuits On cable De rate 0.82 Table 2.1 Table 12 Table 24 4 2 8 EF + Battens 0.8A In Toilets TPS unenclosed 3 other circuits on cable tray up wall from switchboard Table 2.1 Table 9 Table 24 De-rate 0.88 4 2 8 HWS 15 TPS unenclosed 3 other circuits on cable tray up wall with 3 other circuits Table 2.1 Table 12 Table 24 De-rate 0.88 4 2 8 500W SV 2.8A TPS installed enclosed U/G Table 2.4 Table 9 20A Column no 4 16 Cable Size 20A 3Ø outlets Distribution board Unit 1 Sub-main Mains U/G turret Determine the cable size for the 20A 3 phase outlets 1 per circuit, longest run 38 metres The cable is 3core TPS V 90 installed enclosed in air. No de-rating for this section. Unenclosed in air spaced on perforated tray up wall above switchboard 4 circuits 20 24.4 A 0.82 T able12/4 a 4mm2 cable 29A Unit 1 DB MSB 20A 3Ø outlet 1000 Vd Vc L I 1000 9.735 38 20 12.8m V / Am To satisfy voltage drop requirements Table 42 a 4 mm² Cable with a Vc value of 9.71 mV/Am value is required Cable Size 20A 3Ø outlets Distribution board Unit 1 Sub-main Mains U/G turret MSB Determine the cable size for the 20A 3 phase outlets 1 per circuit, Route length 25 metres Current carrying capacity is the limiting factor in this circuit 20A 3Ø outlet To satisfy Current carrying capacity, a 4mm² TPS cable is required Unit 1 DB Cable Size 20A 3Ø outlets Sub-main Mains U/G turret MSB Unit 1 DB Determine the cable size for the 20A 3 phase outlets 1 per circuit, Route length 15 metres 20A 3Ø outlet In this instance Voltage drop is not the governing factor. A 4mm² cable is required for CCC 10A single phase outlets • 6 outlets in warehouse 2 per phase, (3 circuits). • Circuit 1 (38m route length) The outlet is at the end of the run therefore use MD =10A 1000Vd 1000 5.57 Vc 14.65m V/A.m L I 38 10 convert tothreephase 14.65 0.86 12.69m V/A.m • • • • • Therefore from Table 42, 4mm² cable is required for volt drop Cable enclosed in conduit on wall with 3 0ther circuits spaced ( 4 circuits ) Table 9/6 4mm² cable = 26A De-rating Table 22 (0.9) 26 x 0.87 = 23.4A 10A single phase socket outlets • Circuit 2 (30m route length) 1000Vd 1000 5.57 Vc 18.56m V/A.m L I 3010 convert tothree phase 18.56 0.86 16.07m V/A.m • Therefore from Table 42 2.5mm² with a Vc value of 15.6mV/A.m is required • Circuit 3 route length 20m route length can also be wired in 2.5mm² • Table 9 column 6 (2.5mm² cable)=20Ax0.9 =18A So a 2.5mm² cable will satisfy both CCC and Vd Light Circuits unit 1 Circuit 1 (4x250W mercury vapour) • Route length 38m Maximum Demand 4 x 1.5A = 6A. • Circuit beaker rating 10A . Determine Cable size 1000Vd 1000 5.57 Vc 29.316m V / A.m L I 38 5 convert tothreephase Vc 0.866 29.31 0.866 25.39m V / A.m • So from Table 42 a 2.5mm² cable with a Vc value of 15.6mV/A.m three phase 15.6 x 1.155 =18mV/A.m is required Light Circuits unit 1 Circuit 2 (4x250W mercury vapour) • Route length 44m Maximum Demand 4 x 1.5A = 6A. See clause 3.5.2 50% of circuit protective device can be used • Circuit beaker rating 10A . Determine Cable size 1000Vd 1000 5.57 Vc 25.328m V / A.m L I 44 5 convert tothreephase Vc 0.866 25.318 0.866 21.925m V / A.m • So from Table 42 a 2.5mm² cable with a Vc value of 15.6mV/A.m three phase 15.6 x 1.155 =18mV/A.m is required Circuit 3 four battens and 2 EF Toilets • Route length 28m 1000Vd 1000 5.57 Vc 39.78m V / A.m L I 28 5 convert t othreephase Vc 0.866 39.78 0.866 34.45m V / A.m • So from Table 42 1.5mm² cable is required • Table 9 column 6 (1.5mm² cable = 14A) Circuit 4 (3x 18W) Fluorescent • Route length 50m 1000Vd 1000 5.57 Vc 318.28V / A.m L I 50 .36 convert tothreephase Vc 0.866 318.28 0.866 275.63m V / A.m • Voltage drop is not a factor for this circuit • Either 1mm² or 1.5mm² can be used Circuit 5 (500W) sodium Vapour • Route length 16m • TPS Cable V90 Installed enclosed U/G Distribution Board 500W Sodium vapour 1000Vd 1000 5.57 Vc 127.98m V / A.m L I 16 2.72 convert tothreephase Vc 0.866 127.98 0.866 110.8m V / A.m Voltage drop is not a factor for this circuit Either 1mm² or 1.5mm² can be used Hot Water Cylinder 3 phase 15A • • • • Route length 28m Cable 3core + E enclosed TPS V90 Table 12 column 2 (2.5mm² = 23A) Check Voltage drop 1000 Vd 1000 9.735 Vc 23.17mV/Am L I 28 15 • Table 41 (2.5mm² = 15.6mm²)Therefore 2.5mm² Cable Office • 8-2x36W(0.78A) fluorescent one circuit • Route length 40m Use 10A MCB • Rule 3.6.2 50.% circuit protective device for voltage drop 1000Vd 1000 5.57 Vc 27.85m V / A.m L I 40 5 convert tothreephase Vc 0.866 27.85 0.866 24.118m V / A.m Table 42 1.5mm² = 28.6mV/Am. Use 1.5mm² cable Office10A socket outlets • Circuit 14 (three double outlets) • Route length 22m TPS cable installed unenclosed in air Table 9 column 4 (2.5mm² = 26A)Use 20MCB • Rule 3.6.2 (50.% circuit protective device for voltage drop) 1000Vd 1000 5.57 Vc 25.318m V / A.m L I 22 10 convert tothreephase Vc 0.866 25.318 0.866 21.925m V / A.m Table 42 2.5mm² = 15.6mV/Am 2.5mm Cable for all socket outlet circuits in the office. Fault loop impedance • The earth fault-loop impedance in an MEN system comprises the following parts, starting and ending at the point of the fault. • a) The protective earthing conductor, (PE), including the main earthing terminal/connection or bar and MEN. • b) The neutral return path, consisting of the neutral conductor, (N), between the main neutral terminal or bar and the point at the transformer (the earth return path RG to RB has a relatively high resistance and may be ignored for an individual installation in an MEN system) Fault loop impedance • c) The path through the neutral point of the transformer and the transformer winding. • d) The active conductors as far as the point of the fault. • The earth fault-loop is normally regarded as consisting of the following two parts• i) conductors upstream or external to the reference point; and • ii) conductors down stream or internal to the reference point. • Refer to appendix B for detail Path taken by an earth fault current Earth fault-loop impedance Fault current IA Distributor's network A H POS MEN Neutral Bar Main Earth Faulty equipment Soil resistance high between electrodes Determine maximum route length to satisfy fault loop impedance. • The maximum length of a circuit can be determined using Table B1 • (Exceptions include circuits wired in 4mm² cable protected by a 16A or 20A Type C MCB) • The maximum length for this example will need to be calculated Calculation 16A MCB 0.8Uo Sph Spe LMax Ia ( Sph Spe) 0.8 230 4 2.5 LMax 3 16 7.5 22.5 10 (4 2.5) L Max 109metres A 4mm² Cable protected by a 16A MCB can be run 109m and not exceed the earth fault loop impedance requirements Switchboards Units 1-3 120A Main switch MCB’S L L L L L P P P P P P HW L P P P 10 10 10 10 10 16 16 16 20 20 20 16 10 16 16 16 Main Switch Board