GMV9, and GCV9 GMV9 Two-Stage Variable-Speed GCV9 Heating Capacity Model Hi-Fire Lo-Fire (thousand btu/h) (thousand btu/h) Input GMV90703B GMV90904C GMV91155D GCV90704C GCV90905D Output 70 66.9 90 88.8 115 111.1 70 65.3 90 86.5 Input Output 48 64 80 48 64 46.4 61.7 77.4 45 60.1 GMV9 Two-Stage Variable-Speed GCV9 Cooling Capacity Model GMV90703B GMV90904C GMV91155D GCV90704C GCV90905D Hi-Stage Cooling 1.5 2.0 2.5 3.0 1.5 2.0 2.5 3.0 3.5 4.0 1.5 2.0 2.5 3.0 3.5 4.0 5.0 1.5 2.0 2.5 3.0 3.5 4.0 1.5 2.0 2.5 3.0 3.5 4.0 5.0 Supports a wide range of Cooling requirements GMV9 Two-Stage Variable-Speed GCV9 VENT TERMINATION CLEARANCES GMV9 Two-Stage Variable-Speed GCV9 STANDARD CONNECTIONS GMV9 Two-Stage Variable-Speed GCV9 VERTICAL TERMINATIONS (DUAL PIPE) GMV9 Two-Stage Variable-Speed GCV9 STANDARD HORIZONTAL TERMINATIONS GMV9 Two-Stage Variable-Speed GCV9 ALTERNATE HORIZONTAL VENT TERMINATIONS GMV9 Two-Stage Variable-Speed GCV9 TERMINATIONS ABOVE ANTICAPATED SNOW LEVEL GMV9 Two-Stage Variable-Speed GCV9 HORIZONTAL CONNECTIONS (RIGHT SIDE DOWN) GMV9 Two-Stage Variable-Speed GCV9 HORIZONTAL CONNECTIONS (LEFT SIDE DOWN) GMV9 Two-Stage Variable-Speed GCV9 TUBE INSTALLATIONS / GREEN HOSES GMV9 Two-Stage Variable-Speed GCV9 Thermostat Options • • • • Single-stage heating/Single-stage cooling Two-stage heating/Single-stage cooling Two-stage heating/Two-stage cooling Fossil fuel application (Kit required) – Three-stage heat pump thermostat required GMV9 Two-Stage Variable-Speed GCV9 THEMOSTAT WIRING GMV9 Two-Stage Variable-Speed GCV9 Thermostat wiring GMV9 Two-Stage Variable-Speed GCV9 Pressure Switch Check • There are 3 Pressure Switches • Hi and Low Fire are grouped together • The Pressure Switch by itself is the Cover Switch • All Pressure Switches are open Switches GMV9 Two-Stage Variable-Speed GCV9 GAS PRESSURE ADJUSTMENTS GMV9 Two-Stage Variable-Speed GCV9 MANIFOLD GAS PRESSURE GMV9 Two-Stage Variable-Speed GCV9 Induced-Draft Blower • Jackel 2-speed blower assembly • Motor suspended on four motor mounts for vibrationfree operation • Factory-installed rubber discharge makes venting a snap • Alternate flue/vent through RIGHT side with GMV9 and LEFT side for GCV9 Air flow GMV9 Two-Stage Variable-Speed GCV9 Electronic Controls GMV9 Two-Stage Variable-Speed GCV9 Integrated Control Board 16-pin connector (ECM Motor) 3 amp Fuse Green CFM LED 12-pin connector (Diagnostics) 24V Terminal block D-hum,W2,W1,R,G,B,Y,YLO,O Yellow Dehumidification LED ICM Microprocessor Red Diagnostic LED 5-pin connector (inducer/ignitor) Hot Connections Neutral Connections (Line, XFMR, EAC, HUM) (Line, XFMR, EAC, HUM) GMV9 Two-Stage Variable-Speed GCV9 Single-stage Thermostat? Set dip switch #3 Off = 5 minutes On = 10 minutes Then Move this jumper to the left Easily converted from 2-stage to 1-stage T-stat operation GMV9 Two-Stage Variable-Speed GCV9 Accessories Supported • • • • Dehumidistat (Yellow LED indicator) 115-volt Humidifier (1 amp @ 120 volts) 115-volt EAC (1 amp @ 120 volts) 24-volt Humidifier GMV9 Two-Stage Variable-Speed GCV9 CFM LIGHT Green Light On The Bottom Right Side Of The Board 1 Blink For Every 100 CFM GMV9 Two-Stage Variable-Speed GCV9 Start-Up Procedure 1 Connect 115 power, proper grounding and polarity 2 3 Follow I&O procedure for natural or LP gas 4 Refer 5 Determine 6 7 Adjust 8 Turn Continuous flash indicates reverse polarity correct system cooling cfm Green cfm LED flashes once per 100 cfm 9 Verify 10 new cfm with green LED Select cooling speed with dips 1,2,3, & 4 to Spec Sheet for correct cfm/temp rise blower speed using ICM dip switches off power for 10 sec after each adjustment 11 Select 12 Select desired ramp profile with dip 5&6 heating speed with dip 7 & 8 GMV9 Two-Stage Variable-Speed GCV9 Adjusting the Proper CFM Setting GMNTE060-3 HEATING BLOWER SPEED TAP Low Stage A B C D COOLING / HP High Stage CFM Temp Rise CFM Temp Rise - 558 0 804 0 Norm + 620 682 0 0 893 982 - 639 0 Norm + 710 781 - Tons of AC CFM Low Stage High Stage --- 351 540 0 0 1.5 --- 390 429 600 660 920 0 --- 468 720 0 0 1022 1125 0 0 2.0 --- 520 572 800 880 720 0 1037 0 --- 585 900 Norm + 800 880 0 0 1152 1267 0 0 2.5 --- 650 715 1000 1100 - 801 0 1153 0 --- 702 1080 Norm + 890 979 0 0 1282 1410 0 0 3.0 --- 780 858 1200 1320 GMV9 Two-Stage Variable-Speed GCV9 Select Cooling Speed Cool Tap Find proper cooling tap in PDB based on ~400 cfm/ton Adjust Tap SW1 SW2 Tap SW3 SW4 Adjust Off Off A Off Off Norm On Off B On Off Pos Off On C Off On Neg On On D On On Test GMV9 Two-Stage Variable-Speed GCV9 Select Auto-Comfort Profile Profile Select Profile D for Auto-Comfort Mode SW5 SW6 Tap Off Off A On Off B Off On C On On D GMV9 Two-Stage Variable-Speed GCV9 Select Heating Speed Heat Tap Select slowest heating speed possible while maintaining temp rise for minimum energy usage SW7 SW8 Tap Off Off A On Off B Off On C On On D GMV9 Two-Stage Variable-Speed GCV9 Select Heat-Off Delay Heat-Off Delays SW1 SW2 Sec. On On 60 Off On 90 On Off 120 Off Off 150 GMV9 Two-Stage Variable-Speed GCV9 SEQUENCE OF OPERATIONS COOLING 1. RY&G Are Energized (Hi-Cooling) Call for Cooling 2. Condenser Turns On and the Blower Ramps Up to Cooling Speed, EAC Terminal are Now Energized 3. System Runs Till T-Stat is Satisfied 4. Outdoor Unit Turns Off and Blower Continues for 45 Seconds, Blower is Ramped Down and EAC Terminals are Turned Off 5. In Constant Fan Mode, Fan Continues at 56% of Cooling Speed GMV9 Two-Stage Variable-Speed GCV9 SEQUENCE OF OPERATION Heating 1. R & W1 (Low Fire) Call For Heat 2. Inducer Draft Motor Starts Pre-Purge on Hi Fire (10 seconds), Humidifer Terminals are energize 3. Inducer Draft Motor drops to Lo, Low Fire Pressure Switch Closes 4. Igniter warms up 5 Min. to 9 Seconds opens on Max. 5. Gas Valve opens on Low Fire ,…… Flame Sensor Detects Flame 6. If Call for Hi-Heat , Inducer Draft Motor and Gas Valve Jumps up to Hi-Fire 7. Blower Delay Starts Blower To Ramp Up for 30 Seconds GMV9 Two-Stage Variable-Speed GCV9 SEQUENCE OF OPERATIONS Heating 8. EAC Terminal Energized Unit is Now Heating 9. If T-Stat Call for Low Fire, Inducer Draft Motor and Gas Valve Jump to Low Fire till T-Stat is Satisfied 10. Call for Heat Has Been Satisfied, Gas Valve Shuts Off and Inducer Draft Motor Does a Pre-Purge (15 Seconds) 11. Selected Heat-Off Delay 90, 120,150, 180 Seconds and Then the Blower Ramps Down GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting Flash Pattern LED Off/Operation LED Off/No Operation LED On 1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes 9 Flashes Continuous Flash Status Indication No 115 volt or 24 volt Power No 115 volt or 24 volt Power Normal Operation Lockout due to excessive retries Pressure Switch stuck closed Pressure Switch stuck open Primary or Auxilliary high-limit Flame sense without call for heat Open rollout Low flame signal Check igniter or improper grounding Hi Stage Pressure Switch open Reversed polarity of 115 vac GMV9 Two-Stage Variable-Speed GCV9 Field Returns • Handling Boards by Edges or Use ESD Ground Strap • No Repeated Control Change-out • Moisture Control in Board Area • Return Tag Information • Boxes or Bags for Field Returns GMV9 Two-Stage Variable-Speed GCV9 Understanding ECM Motors What does ECM mean? Electrically Commutated Motor GMV9 Two-Stage Variable-Speed GCV9 How Does the ECM Work? AC POWER POWER CONDITIONING AC TO DC CONVERTER POWER INVERTER ECM MOTOR HVAC SYSTEM CONTROL INPUTS 24VAC Compressor On/Hi/Lo Fan On Rev Valve Aux/Emerg Heat Capacity Select MOTOR CONTROL Available Outputs CFM GMV9 Two-Stage Variable-Speed GCV9 How Does the ECM Sense Static Pressure? Input Power vs. RPM 550 500 Input Power (watts) 450 400 P = kN^3 350 1/2 N = 1/8 P 300 1/8 X 280W = 35W 1000 RPM 280 Watts 250 200 500 RPM 35 Watts 150 100 50 0 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 RPM GMV9 Two-Stage Variable-Speed GCV9 ECM Advantages Efficiency gain System Pressure (Pr) 0.8 PSC ECM 0.6 0.4 408W 745W 0.2 0.0 0 1 2 3 4 5 6 7 CFM/ Watt Lower static pressure yields greater efficiency gain GMV9 Two-Stage Variable-Speed GCV9 ECM Advantages Static-independent Airflow Set the airflow and go! 0.8 PRESSURE 0.7 System airflow is starved 0.6• insufficient cooling/heating • liquid refrigerant return 0.5 to condenser Over blowing the system • poor moisture removal • high power consumption • moisture in the duct work 0.4 Typical profile with a PSC motor 0.3 0.2 408W ® 745W ® 0.1 0 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 Airflow (CFM) GMV9 Two-Stage Variable-Speed GCV9 How Does the ECM Work? The End Bell defines motor characteristics. Only 3 motor sections ½, ¾, or 1 hp. The motor is really a three phase motor with a permanent magnet rotor. Motor Connector Motor Section End Bell Assembly GMV9 Two-Stage Variable-Speed GCV9 Service and Installation Basics GMV9 Two-Stage Variable-Speed GCV9 Power Connectors • Connectors are keyed • Don’t force in the wrong orientation • Pull on the plug, NOT the cable • DO NOT pull power cable out during operation – Arching could occur Low Voltage High Voltage 16 PIN CONNECTOR 5 PIN CONNECTOR GMV9 Two-Stage Variable-Speed GCV9 Power Connectors Continued 5 Pin Power Connector • 120 VAC uses a jumper (red wire) • Control operates at 240 VAC • Jumper enables voltage doubler • Do not apply 240 VAC with jumper installed as motor and control will fail. • 240 VAC input does not use a JUMPER 16 Pin Signal Connector • Pulse Width Modulation (PWM) or • 24 VAC Thermostat Mode or • Digital Serial Interface (DSI) Operating Voltages Application Note GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors What is Normal? It is normal for the blower to rock back and forth at start up. It is normal for the shaft to feel rough or bumpy when turned. Don’t judge the motor by the RPM or ramp up sequence. GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors Don’t judge the motor by the RPM or ramp up sequence. off All slew rates are controlled Profile A Profile B Profile C on Pre-run Short run Full capacity Off Delay Time: 0 - 15 min, 16 steps Level: 6 - 100% 16 steps GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors The # 1 failure of ECM motors…………… No Fault Found ! (80%) The # 2 failure of ECM Motors …………… Moisture. (16%) All other failures (4%). GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors • Always make sure the motor is oriented such that the connectors are on the bottom • Make sure the electrical connections form a drip loop to prevent any moisture from running down the harness and into the end bell assembly. • A blower wheel loose on the motor shaft can cause the blower to vibrate, excessive noise, and may cause motor malfunction. Drip Loop Electrical Connections on Bottom GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors There are some ECM motor testers on the market today. GMV9 Two-Stage Variable-Speed GCV9 GE TECMateXLTM Service Tool Analyzes the GE ECM independent of the HVAC system Can test the basic settings: Fan-only, Heating, Cooling and Dehumidification Will detect and isolate motor failures from HVAC system failures Accurate and quick diagnosis means better customer satisfaction Don’t even have to take the motor out of the blower Buy it on www.thedealertoolbox.com. Click on the TECMateXLTM Service Tool link under the Service Tools tab. GMV9 Two-Stage Variable-Speed GCV9 GE TECMateXLTM Service Tool How to Use the GE TECMateXLTM The table on the back of the TECMateXL shows expected results for various settings. 1. CAUTION: Disconnect AC power from the system being serviced and wait 5 minutes before opening motor. 2. Remove the 16-pin connector from the motor, and connect the 16-pin connector from the TECMateXL to the motor. Do not disconnect the 5-pin AC power connector from the motor (see Figure 1). 3. Connect the two alligator clips from the TECMateXL to a 24VAC source. 4. Place all switches on the TECMateXL in the off position. Figure 1 24VAC TECMate 120V or 240V AC Power ECM Motor GMV9 Two-Stage Variable-Speed GCV9 GE TECMateXLTM Service Tool Continued 5. Reconnect AC power to the system. The TECMateXL power led should illuminate when connected properly to 24VAC. 6. Place the correct switches in the ON position and observe the motor for 15 seconds. (Refer to the Table on back of the TECMateXL for switch selections of the various test mode settings). 7. If the motor starts with the TECMateXL, then the system malfunction is not caused by an ECM motor/control. Refer to the Troubleshooting Guide on page 2 for help in diagnosing the system malfunction. 8. When finished testing a mode, place all switches in the off position and wait for the motor to completely stop before testing the next switch selections. (Based on the OEM program, sometimes the motor will not shutoff immediately after a setting has been tested; this is normal.) 9. If the motor does not start with the TECMateXL, then proceed to replace the electronic control module in accordance with the instructions on page 4. Note: Before replacing the electronic control module, you must test the motor module to ensure it is not also damaged. Procedures for testing the motor module are included in “Replacing the ECM Control Module” instructions on page 4. Note: Do not operate motor without blower wheel attached. Such operation will cause the motor to oscillate up and down. GMV9 Two-Stage Variable-Speed GCV9 Ultimate Comfort Setup Guidelines GE provides a wide array of programming options in the ECM motor that make it easier to optimize homeowner comfort. Basic Steps to Ultimate Comfort 1. Perform a room-by-room load calculation using ACCA Manual J. 2. Select the proper size equipment so it delivers the expected comfort and efficiency. 3. Keep static pressure to a minimum. Design ductwork for minimum static and maximum comfort. Follow ACCA Manual D. Look for and recommend ductwork improvements where necessary. 4. Recommend high efficiency, low pressure drop filters and recommend keeping the filters clean. 5. Select the proper cooling airflow to match the system tonnage using the identified switches or jumpers on the system control board. 6. If needed make airflow adjustments to further optimize comfort using the trim selection on the system control board. 7. Finally, install a humidistat or select the airflow ramp profile that best removes humidity or improves efficiency for customized comfort. GMV9 Two-Stage Variable-Speed GCV9 Replacing the ECM Control Module Continued 7. Attaching the new control module: (a) If replacing an ECM 2.0 control with an ECM 2.3 control, insert plastic tab into perimeter of replacement control and align tab with mating hole in the end shield. Use the new shorter bolts provided to ensure a secure attachment. Orient the control to the end shield between 4 & 8 o’clock, insert bolts and tighten. (b) If replacing an ECM 2.3 with an ECM 2.3, orient the new control to the motor’s endshield with connectors facing down, insert bolts and tighten. 8. Reinstall the blower/motor assembly into the HVAC system by following the manufacturer’s guidelines. 9. Plug the 16-pin connector and the 5-pin connector back into the motor. The connectors are keyed. Observe proper orientation. 10. Be certain to form a drip-loop so that water cannot enter the motor by draining down the cables (see Figure 5). Final installation check. Ensure the system is setup as follows: 11. (a) Verify the condensate drain is not plugged or clogged. (b) Reconnect the AC power to the HVAC system and verify that the new motor control module is working properly. (c) Check and plug leaks in return ducts and equipment cabinet. (d) The system should run quietly and smoothly. Note: If this is a repeat failure, then it is important that you check the following: Any evidence of moisture requires correcting the issue. Line Transient Voltage Protection Application Note GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors How do we troubleshoot ECM motors? Rule # 1 – If the motor is running at all. The problem is not in the motor. Rule # 2 – If the motor is running at the wrong RPM/CFM, the most likely cause is the installation or controls sending signals to the ECM motor. Rule # 3 – What is the most common failure mode? Water. Look for signs of moisture damage and correct before replacing end bell. GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors Rule # 4 - ECM motors, like any motor must have a power supply. Check the incoming power supply. Inductor 5 4 3 2 1 AC Line AC Line I }V Gnd } Pin 1 & 2 must be connected together for 120Vac input applications Power Connector (viewed from plug end) Inductor is used on ¾ & 1 hp – 120 VAC applications only. GMV9 Two-Stage Variable-Speed GCV9 TSTAT Connections Pin number 9 10 111 21 31 41 51 6 Control (male) 1 2 3 4 5 6 7 8 Connector (female) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Common C1 W/W1 Common C2 Delay tap select Cool tap Select Y1 Adjust tap select Output Return valve (heat pump only) Humidistat (BK) Heat tap select 24 VAC (R) 2nd stage heat (EM/W2) 2nd stage cool (Y/Y2) Fan (G) Output + GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors Rule # 5 - ECM motors, like any motor must have a signal or switch to turn it on, or tell it to run. Controls should be checked with a true RMS meter or analog meter. Controls will activate at ½ nominal voltage and 12 milliamps. Out Adjust +/- 8 7 16 15 Out + G(fan) Y1 Cool 6 5 14 13 Y /Y2 EM Ht/W2 Delay Common 2 W /W1 4 3 2 12 11 10 24VAC (R) Common 1 1 9 Heat BK/PWM (Speed) (Rev Valve) Control Connector Cable Half (viewed from connector end) GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors Check power to control. Pins 1 to 12 and 3 to 12. You must have 24 VAC. Set thermostat to demand for cooling. Check for 24 VAC at pins 1 to 6 and 3 to 6. If you don’t record voltage as noted, repeat test at control or interface board. Out Adjust +/- 8 7 16 15 Out + G(fan) Y1 Cool 6 5 14 13 Y /Y2 EM Ht/W2 Delay Common 2 W /W1 4 3 2 12 11 10 24VAC (R) Common 1 1 9 Heat BK/PWM (Speed) (Rev Valve) Control Connector Cable Half (viewed from connector end) GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors If control is defective, remove end bell and inspect for moisture before replacing control board. Do not apply power to pins 8 or 16. Do not apply line voltage to control connections. Out Adjust +/- 8 7 16 15 Out + G(fan) Y1 Cool 6 5 14 13 Y /Y2 EM Ht/W2 Delay Common 2 W /W1 4 3 2 12 11 10 24VAC (R) Common 1 1 9 Heat BK/PWM (Speed) (Rev Valve) Control Connector Cable Half (viewed from connector end) GMV9 Two-Stage Variable-Speed GCV9 Troubleshooting ECM Motors 1. Disconnect all power to unit. 2. Disconnect 5 pin and 16 connectors from end bell. 3. Remove end bell assembly (2 Screws. 4. Disconnect 3 pin motor connector. 5. Using Ohmmeter, check for continuity in windings. 6. Using Ohmmeter, check for short to ground. Motor Connector GMV9 Two-Stage Variable-Speed GCV9 any questions? Thank you! GMV9 Two-Stage Variable-Speed GCV9