HEAT LOAD CALCULATION 2 HEAT LOAD 2 1 home back next TOPICS COVERED LOAD CALCULATIONS – – – – – – FORMS FORMULAS TABLES FACTORS AIR SIDE PSYCHROMETRY HEAT LOAD 2 2 home back next HEAT LOAD 2 3 HEAT LOAD FORM SEE TRANSPARENCY HEAT LOAD 2 4 home back next HEAT LOAD ESTIMATE PROBLEM HEAT LOAD 2 General office Ceiling 10’ Wall 4 ½” brick, plastered both side Window- ordinary ¼” single glass internal shade Door- plywood sandwich air space Occupants - 35 person Lighting - Fluorescent 5 home back next DESIGN CONDITIONS Outdoor design conditions – 92°F db / 80°F wb or 95db/83wb – Overestimating effect – Night time temp. & rh different – 76°F db/ 75°F wb / 95% rh HEAT LOAD 2 6 home back next DESIGN CONDITIONS Indoor design conditions – Base on requirement and standards – 75°F db / 55% rh – 72°F db / 55% rh – 71°F db / 50% rh Peak time at – 4.00 pm HEAT LOAD 2 7 home back next CURRENT AIR-CONDITIONING DESIGN DATA COMPARISON INDOOR TEMP.(o C) LIGHTING LOAD (w/ft2) OFFICE EQUIP. (w/ft2) OUTLET VELOCITY (ft/min.) FRESH AIR (cfm/person) JKR ASHRAE 95 CIBSE 24 23-26 22+/-2 4-6 (2) 1.85-4.65 1.4 - 0.8-2 1.4 25-50* 40-150 - 20 20 20 *-Carrier Handbook HEAT LOAD 2 8 QUESTION Fill in the table other information for the following conditions – Outdoor air 92db/80wb – Indoor 75db/55%rh HEAT LOAD 2 9 home back next SOLAR GAIN THROUGH GLASS Cooling Load = Window Area x Peak solar heat gain (Table 4) x Storage Factor (Table 5) x Shade Factor (Table 6) Refer to Table 4, Table 5 and Table 6 HEAT LOAD 2 10 home back next SOLAR AND TRANSMISSION GAIN Heat Gain Through Walls & Roofs = Area x Equivalent Temp. Difference (Table 7 for wall & Table 8 for roof) x Transmission Coefficient (U) (Table 9) HEAT LOAD 2 11 home back next TRANSMISSION GAIN (EXCEPT WALLS AND ROOFS) Heat gain through all glass = Area x Temp. Difference (OA - RA) x Transmission coefficient (U) (Table 9) Heat gain through shade wall, partition = Area x Temp. Difference (OA - RA - 5°F) x Transmission coefficient (U) (Table 9) HEAT LOAD 2 12 home back next TRANSMISSION GAIN (EXCEPT WALLS AND ROOFS) (2) Heat gain through wall, partition (adjacent to Kitchen,Boiler Room) = Area x Temp. Difference (OA - RA + 15°F to 25°F) x Transmission coefficient (U) (Table 9) HEAT LOAD 2 13 home back next INFILTRATION When ventilation exceeds infiltration (+ve pressure), then infiltration = 0 When rooms are design at -ve pressure, have to consider HEAT LOAD 2 14 home back next INTERNAL LOADS People – No. of people from no. of chairs or base on per floor area – Table 10 - Heat gain from people No. of people x Table 10 Activity, Sensible & Latent HEAT LOAD 2 15 home back next INTERNAL LOADS Power – Table 53 - Heat gain from electric motors – Electric motors contribute only sensible heat to space HEAT LOAD 2 16 home back next INTERNAL LOADS Lights - Estimate (w/ft2) Lights - Type – Incandescent rated lamp watt x 3.413 – Fluorescent lamp rated lamp watt x 1.25 x 3.413 HEAT LOAD 2 17 home back next INTERNAL LOADS Appliances – most appliances contributes both sensible and latent heat load. – They contribute latent heat by virtue of their function ex. drying, cooking – Hood to remove this is most effective – Table 50 & 51- Heat Gain from Restaurant HEAT LOAD 2 18 home back next SAFETY FACTOR Safety factor added for possible error in the survey Over estimating safety factor will cause oversized air conditioning equipment - difficult to maintain space conditions < 5% HEAT LOAD 2 19 home back next ROOM SENSIBLE HEAT (RSH) Now all the load components contributing to sensible load can be added HEAT LOAD 2 20 home back next SUPPLY AIR DUCT LOSSES In transferring air from system cooling coil to space, four losses must be considered; – – – – Supply duct heat gain supply duct leakage loss fan heat bypassed outdoor air HEAT LOAD 2 21 home back next SUPPLY DUCT HEAT GAIN Supply air in the duct at 50°F to 60°F passes through surrounding environment above 90°F - potential heat gain to supply air Insulation reduces this gain Typical figure < 2% of RSH HEAT LOAD 2 22 home back next SUPPLY DUCT LEAKGE LOSS Lost capacity in the supply air duct depends on duct shape, duct pressure and workmanship. Low pressure (0 - 2”s.p) : <5% Medium pressure (2” - 6”s.p) : 2% 3% High pressure (6” & above) : <1% HEAT LOAD 2 23 home back next FAN HEAT Draw through (draw through the cooling coil) fan add heat to air supply. Electrical losses for motor which lies in the air stream also add heat < 5% HEAT LOAD 2 24 home back next BYPASS OUTDOOR AIR Some of the air passing through the coil remain untreated. Load equivalent to infiltration load Depends on bypass factors use Load = cfm x (toa-trm) x bf x 1.09 HEAT LOAD 2 25 home back next EFFECTIVE ROOM SENSIBLE HEAT (ERSH) This load determine the cfm required across the cooling coil ERSH = RSH + (SUPPLY DUCT GAIN + SUPPLY DUCT LEAK LOSS + FAN) + BYPASS OUTDOOR AIR HEAT LOAD 2 26 home back next LATENT LOAD The latent counterpart of infiltration, internal loads, and supply duct load are also calculated to determine the Room Latent Heat and Effective Room Latent Heat Vapor Transmission - only for low or high dew point application. HEAT LOAD 2 27 home back next ROOM LATENT HEAT (RLH) HEAT LOAD 2 SUM OF ALL ROOM LATENT LOAD – – – – – – INFILTRATION PEOPLE STEAM APPLIANCES ADDITIONAL HEAT GAINS VAPOUR TRANSMISSION 28 home back next EFFECTIVE ROOM LATENT LOAD (ERLH) ROOM LATENT HEAT (RLH) + SUPPLY DUCT LEAKAGE LOSS + BYPASS OUTDOOR AIR HEAT LOAD 2 29 home back next OUTDOOR AIR / VENTILATION RATES HEAT LOAD 2 Outdoor air/ventilation rates from Table 11-Ventilation Std. Outdoor air quantity can be determined either by cfm/person or cfm/ft2 or airchange rate (ach) Air change is defined as the quantity of changed air every hour cfm = vol x ach 60 30 home back next OUTDOOR AIR HEAT Outdoor air heat comprised of both sensible and latent load Except for bypassed air, the load appears on the upstream of the coil Requirements of outdoor/fresh air base on air change rate or cfm/sq.ft or per person HEAT LOAD 2 31 home back next QUESTION Calculate the outdoor/fresh air requirement of the office space, if the recommended fresh air change is 2 ach. Answer : (ach/60) x Vol. = (2/60) x 32000 = 1067 cfm HEAT LOAD 2 32 home back next RETURN DUCT LOSSES Return duct are normally shorter than supply duct Temperature of air at about 75°F 80°F Return duct slightly negative 1% for Return duct heat gain & 1% for return duct leakage loss HEAT LOAD 2 33 home back next RETURN AIR or BLOW THRU’ FAN Fan and motor heat appear on the upstream side of the coil. …..hp x 2545 HEAT LOAD 2 34 home back next GRAND TOTAL HEAT Total heat load the coil must remove from the air passing over it. Also known as dehumidifier load HEAT LOAD 2 35 home back next REFRIGERATION LOAD Introducing two additional loads not experience by the coil – Piping sensible heat gain – Pumping heat gain HEAT LOAD 2 36 home back next APPARATUS DEW POINT (ADP) Effective Room Sensible Heat (ERSH) Effective Room Total Heat (ERTH) ADP obtained from plot ESHF line or Table 65 Indicated ADP & Selected ADP ADP must be > 48°F HEAT LOAD 2 37 home back next QUESTION ERSH = 115 000 ERLH = 15 000 Calculate the ESHF Find ADP if room is 75°F/55%rh from table HEAT LOAD 2 38 home back next DEHUMIDIFIED AIR QUANTITY Dehumidified rise = (trm-tadp)x(1-BF) Cfmda = ERSH 1.09 x (trm-tadp)x(1-BF) HEAT LOAD 2 39 home back next SUPPLY AIR QUANTITY (cfmsa) Outlet temp. diff = RSH =Fdes.dif (trm - tgrille) 1.09 x cfmda Supply cfm = Bypass cfm = cfmsa - cfmda RSH = cfmsa 1.09 x Fdes. dif HEAT LOAD 2 40 home back next RESULTING ENTERING AND LEAVING CONDITIONS AT APPARATUS tedb= trm + cfmoa x (toa - trm) cfmsa tldb = tadp + bf x (tedb - tadp) tewb & tlwb read from psych. chart HEAT LOAD 2 41 home back next SOME EX. OF COMPUTERISED HEAT LOAD CALCULATIONS See Lotus files HEAT LOAD 2 42 home back next HEAT LOAD 2 43 GO TO PSYCHRO 2 HEAT LOAD 2 44 home back next