NetSure™ RDB Series
NetSure™ RDB Series
48V Plug-n-Play Rack Distribution
NetSure™ RDB Series
 Designed to feed up to 8.6kW from 200A breaker
 Zero U, rear mount
 Plug-n-play connectors for tool-less add/move/change
 Includes ground plug
 Breaker trip notification
 Universal mounting – can be mounted on the left or right in
both top and bottom cable applications
Model options by application:
• 1-2U Rack Mount Devices
• 6 or 15 outlet (L6 or L15) versions
• Larger Rack Mount Devices
• 6 outlet (M6) version
• Blade Chassis and High Power Devices
• 2 or 3 outlet (H2 or H3) versions
2
Rack Distribution Concept
DC Power
System
IT Rack
IT Rack
20A Load
20A Load
Zero U
Power Strip
20A Load
A
side
B
side
Output
Breakers
A
side
B
side
Quick
Connect
Plug
Typical 4/0 Cables
No conduit req’d
in cable tray
Rack Mount Server Example
(15) 20A inputs / side
3
Blade Server Example
(3) 70A inputs / side
Available Models
NetSure™ RDB
Model
L6
1
Outlets
6
L15
15
M6
6
H2
H3
2
3
Power Rating
Per Outlet
Per PDU
Max
Max
Max
Max
Watts
Amps1
kW
Amps1
420
630
840
420
630
840
1,050
1,260
1,470
3,360
2,100
2,520
2,940
10
15
20
10
15
20
25
30
35
80
50
60
70
2.5
3.8
5.0
6.3
8.42
8.42
6.3
7.6
8.42
6.7
6.3
7.6
8.42
60
90
120
150
2002
2002
150
180
2002
160
150
180
2002
Max Amps rated at end of battery discharge (42V)
PDU power rating limited to 200A, 8.4 kW each
All NetSure™ RDB Series PDUs are designed for up to 200A input
2
4
Part
Number
547692
547693
547499
547694
547695
547615
547696
547697
547503
547500
547698
547699
547501
NetSure™ RDB L6
Power Rating
Per Outlet
Per PDU
NetSure™ RDB
Model
L6
5
Max
Max
Max
Max
Watts Amps1
kW
Amps1
420
10
2.5
60
630
15
3.8
90
840
20
5.0
120
1 Max Amps rated at end of battery discharge (42V)
2 PDU power rating limited to 200A, 8.4 kW each
All NetSure™ RDB Series PDUs are designed for up to 200A input
Outlets
6
Part
Number
547692
547693
547499
NetSure™ RDB L15
Power Rating
Per Outlet
Per PDU
NetSure™ RDB
Model
L15
Max
Max
Max
Max
Watts Amps1
kW
Amps1
420
10
6.3
150
630
15
8.42
2002
840
20
8.42
2002
1 Max Amps rated at end of battery discharge (42V)
2 PDU power rating limited to 200A, 8.4 kW each
All NetSure™ RDB Series PDUs are designed for up to 200A input
6
Outlets
15
Part
Number
547694
547695
547615
NetSure™ RDB M6
Power Rating
Per Outlet
Per PDU
NetSure™ RDB
Model
M6
7
Max
Max
Max
Max
Watts Amps1
kW
Amps1
1,050
25
6.3
150
1,260
30
7.6
180
1,470
35
8.42
2002
1 Max Amps rated at end of battery discharge (42V)
2 PDU power rating limited to 200A, 8.4 kW each
All NetSure™ RDB Series PDUs are designed for up to 200A input
Outlets
6
Part
Number
547696
547697
547503
NetSure™ RDB H2
Power Rating
Per Outlet
Per PDU
NetSure™ RDB
Model
H2
8
Max
Max
Max
Max
Watts
Amps1
kW
Amps1
3,360
80
6.7
160
1 Max Amps rated at end of battery discharge (42V)
2 PDU power rating limited to 200A, 8.4 kW each
All NetSure™ RDB Series PDUs are designed for up to 200A input
Outlets
2
Part
Number
547500
NetSure™ RDB H3
Power Rating
Per Outlet
Per PDU
NetSure™ RDB
Model
H3
9
Max
Max
Max
Max
Watts Amps1
kW
Amps1
2,100
50
6.3
150
2,520
60
7.6
180
2,940
70
8.42
2002
1 Max Amps rated at end of battery discharge (42V)
2 PDU power rating limited to 200A, 8.4 kW each
All NetSure™ RDB Series PDUs are designed for up to 200A input
Outlets
3
Part
Number
547698
547699
547501
Output Cables
 Quick connect to PDU
 Un-terminated to IT equipment
 2 Models:
• 547613: Power Cord for H2, H3 Models - 4' Long
• 547595: Power Cord for L6, L15, M6 Models - 6' Long
10
Breaker Trip Alarm Scheme
11
•
Alarm scheme for NetSure™ RDB Series
•
-48 VDC signal provided to indicate a breaker has tripped
•
Signal can be “daisy-chained” to connect to multiple power strips
•
•
Alarm signal can be connected to NetSure™ controller, or
to other monitoring system that accepts -48 VDC signal
•
2 position removable terminal block provides a simple customer
connection point for alarm signal requiring only a stripped wire
PDU Rack Mounting Bracket
•
•
•
•
12
Mounts in rear of IT rack
Includes bracket and hardware to
mount to one side of rack
Left side or right side mounting
P/N: 547665
Mating Input Quick Connect Kits
•
•
•
•
•
13
Provides mating connector to input of NetSure™ RDB Series
Installs on cables from NetSure™ DC Power System
Includes mating SB350 housing and two contacts
4 kits to accommodate 1/0 through 4/0 wire
QTY: 1 per distribution strip depending on input wire size
KIT P/N
Wire Size
547668
1/0 AWG
547669
2/0 AWG
547670
3/0 AWG
547671
4/0 AWG