CHEMISTRY BUILDING RCX Presenters: Bob Kilgore Matthew McReynolds Brenna Goode Project History The Challenge? PH 1 Starts PH 2 Ends FLOOD Utility & Energy Use 7,945,346 kWh 26% Increase 5,827,190 kWh Utility & Energy Use 40,956 MMbtu 36,467 MMbtu 11% Decrease Utility & Energy Use 46,900 MMbtu 196% Increase 15,828 MMbtu Utility & Energy Use 46,900 MMbtu 26% Difference Due to Excess Flow 37,268 MMbtu Utility & Energy Use How Did Chemistry Compare? PH 1 Starts Labs21 Benchmark Data PH 2 Ends FLOOD Processes Fume Hood Testing Over 250 Hoods Currently Operational • Verify sash velocities at multiple positions • Compared to most recent EHS testing reports • Verify current hood use Processes AHU Testing • Verify actuator extents and mid-point stroke positions It’s All about building trust • Verify sensor installation and accuracy When we can trust the BAS to give us good data, we utilize the trends to analyze the systems for deficiencies and opportunities This is also the basis for a Continuous Commissioning program Findings Improve Averaging Sensor Coverage T T T T Existing Recommended Improvement • Improves sensing and therefore control (adding temp sensors) • Reduces risk of freezing coils (adding freeze stats) It’s pretty cheap insurance! Findings AHU Heat Recovery Control Single point of control for heat recovery creates one satisfied AHU and three unsatisfied AHUs Findings Chilled Water System Investigation • AHU Control Sequences • AHU Coil Capacities • Pumping Capacity • Historical Weather Data Findings Chilled Water System • AHU Control Sequences Reduce Discharge Air Temperature Based on Return/Exhaust Humidity Level. 52°F 47°F +3°F 55°F 50°F Findings • AHU Coil Capacities Chilled Water System Modeling showed Air Handling Units are driven beyond coil capacity. Coils sized for 51.6°F (LAT) @ 89°F / 78°F Program Demands 47°F (LAT) @ 89°F / 78°F Coil Physically can’t meet DAT requirements Findings Chilled Water System • Pumping Capacity Building Chilled Water Users AHU Tag Quantity SAHU-1 1 SAHU-2 1 SAHU-3 1 SAHU-4 1 SAHU-5 1 EXISTING AHU (NW) 1 PROCESS HEAT EXCHANGER 1 AHU-1 (Auditorium) 1 FC-1 2 FC-2 5 FC-4 1 FC-5 1 TOTAL FLOW = PUMP CAPACITY = CAPACITY SHORTFALL= Design Flow gpm 785 530 785 395 535 2050 341 25 1.5 3 4 4.5 5459 GPM 3600 GPM 1859 GPM Control Valve Size 8 6 8 6 6 10 6 ?? 1/2 1/2 1/2 3/4 Model Number 8"-IDP-415-05-L 6"-EDP-340-05-L 8"-IDP-415-05-L 6"-EDP-280-05-L 6"-EDP-340-05-L 10"-JDP 6-EDP-280-05-L ?? 1/2"-FDP-4-05-H 1/2"-FDP-4-05-H 1/2"-FDP-4-05-H 3/4"-HDP-6-05-H Max GPM 5-70 psig 900 590 900 420 590 2200 420 ?? 2 3 4 6 Actuator With a 150 Weight PSI Close Off (lbs) NEPTRONIC UB9040 575 NEPTRONIC UB8040 240 NEPTRONIC UB9040 575 NEPTRONIC UB8040 240 NEPTRONIC UB8040 240 NEPTRONIC UB9040 1200 NEPTRONIC UB8040 240 ?? ?? BELIMO LF24-SR 5 BELIMO LF24-SR 5 BELIMO LF24-SR 5 BELIMO LF24-SR 10 Control Signal 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V 0-10V ?? 0-10V 0-10V 0-10V 0-10V Fail Safe Action NC NC NC NC NO NC NC ?? NC NC NC NC NC NC NC NC NO NC NC ?? NC NC NC NC Findings • Historical Weather data Chilled Water System Data From University of Iowa Chilled water Plant PI System Airflow CFM 57,067 56,907 56,906 56,874 56,814 56,714 56,598 56,547 56,530 GPM 745 425 745 470 745 460 745 405 745 375 745 335 745 295 745 227 530 127 Flow Gallons 44,700 25,500 558,750 352,500 2,592,600 1,600,800 6,302,700 3,426,300 12,583,050 6,333,750 16,024,950 7,205,850 20,360,850 8,062,350 20,562,000 6,265,200 14,946,000 3,581,400 CoilModel ModelInputs Inputs(ECM-10) SAHU-1 Coil EAT Coil Target DB WB EWT LWT Delta T LAT 56.3 11.4 46.5 90.4 73.2 44.9 62.7 17.8 51.5 56.9 11.8 46.5 87.4 74.1 45.1 62.2 17.1 51.5 56.5 11.3 46.5 84.3 73.2 45.2 61.8 16.6 51.5 55.1 10.1 46.5 78.1 70.4 45.0 61.1 16.1 51.5 54.5 9.5 46.5 79.9 69.2 45.0 61.0 16.0 51.5 53.5 8.5 46.5 76.1 67.0 45.0 60.4 15.4 51.5 52.5 7.6 46.5 72.0 64.9 44.9 59.7 14.8 51.5 50.9 6.0 46.5 67.0 61.2 44.9 58.5 13.6 51.5 62.0 56.9 44.8 50.5 5.7 46.5 57.8 13.0 51.5 Coil LAT 48.1 51.4 48.5 51.4 48.5 51.4 47.8 51.5 47.6 51.5 47.3 51.5 46.9 51.5 46.5 51.5 46.5 51.5 Target Tons 400.51 341.79 416.87 358.29 400.47 341.89 345.74 287.19 322.61 264.11 284.43 226.02 248.71 190.41 190.73 132.47 129.07 70.83 Coil Tons 353.13 314.78 365.09 334.12 351.44 318.58 314.75 272.36 295.68 250.39 264.26 215.14 234.59 181.39 185.71 128.47 125.40 68.68 Calc Mmbtu 5.2 3.0 65.2 41.2 302.7 186.9 735.9 400.1 1,469.2 739.5 1,871.1 841.4 2,377.3 941.4 2,400.8 731.5 1,745.1 418.2 Findings • Historical Weather data Findings AHU-NW Discharge Air Temperature Sensor • Discharge air sensor was found to be reporting 5°F high. • Resulting in Cooling Coil being overdriven and Heating Coil Under driven. Findings • Sensor Calibration Northwest AHU chilled water valve was consistently at 100% while the discharge air temperature struggled to maintain set point. Unit is running at approximately 60% Unit is running at approximately 60% full design capacity. full design capacity. Recommendations ECM-11 Fix AHU-NW Discharge Air Temperature Sensor • Recalibrate DAT sensor to read true value of conditioned air. • This measure was implemented during study. Results ECM-11 Results ECM-11 Recommendations ECM Number Energy Conservation Measure (ECM) Estimated Implementation 1 Advanced AHU Heat Recovery Control 2 Singe Loop AHU Discharge Air Temperature Control 3 Dynamic Duct Static Pressure Reset 4 Discharge Air Temperature Set Point Reset 5 Dynamic Pump Differential Pressure Reset 6 Teaching Lab Occupancy Air Flow Reset 7 Reduce Minimum Laboratory Ventilation Rate During Occupied Hours 8 Decommission Unused Fume Hoods 9 Re-Balance Over-Exhausted Fume Hoods 10 Decommission Existing AHU Dehumidification Sequences 11 Fix AHU-NW Discharge Air Temp Sensors 12 Reduce Classroom Lab Fume Exhaust Levels During Unoccupied Hours 13 Reduce Minimum Humidification Setpoint TOTAL 1 Cost $164,000 $11,000 $57,000 $42,000 $13,000 $96,000 $108,000 $18,000 $24,000 $5,000 $1,000 $131,000 $7,000 $677,000 Estimated Estimated Annual Utility Savings Electric Steam Chilled Annual Cost (kWh) (MMBtu) Water Avoidance 720 402 $21,500 834 601 $28,300 101,535 776 1,115 $48,800 (68,205) 4,169 3,821 $156,100 13,784 $1,200 33,257 487 13 $10,900 83,226 1,880 1,414 $72,300 18,876 609 216 $16,700 45,783 1,381 2,508 $88,600 41,647 2,326 3,346 $124,100 3,711 1,069 $85,800 30,465 435 7 $9,700 853 $13,600 $677,600 Notes: Estimated Blended Marginal Rates (Fiscal Year 2013) 1. Cost estimates are based on RS Means data and past project experience, and does not include project soft costs. 2. Savings calculated assume that ECM-10 and ECM-11 have already been completed 3. This measure is intended to identify approximate itemized savings of removing one (1) hood from operation. 4. This measure was implemented during the summer of 2012. Simple Payback Notes Years 7.6 2 0.4 2 1.2 2 0.3 2 10.8 2 8.8 2 1.5 2 1.1 2,3 0.3 2 0.0 0.0 4 13.5 2 0.5 2 1.0 $ $ $ 0.084 /kWh Elec 15.91 /MMBtu Steam 24.98 /MMBtu Chilled Water User Concerns • Uncertainty of purpose • Unrealistic solutions • Overly burdensome implementation • Impact on research and instrumentation • Impact on the instructional mission Recommendations 7 of 13 ECMs required coordination with building users and lab equipment: ECM Number Energy Conservation Measure (ECM) Estimated Implementation Cost1 Estimated Annual Utility Savings Estimated Chilled Electric Steam Annual Cost Water (kWh) (MMBtu) Avoidance (MMBtu) (68,205) 4,169 3,821 $156,100 Simple Payback Years Notes 4 Discharge Air Temperature Set Point Reset $42,000 0.3 2 6 Teaching Lab Occupancy Air Flow Reset $96,000 33,257 487 13 $10,900 8.8 2 7 Reduce Minimum Laboratory Ventilation Rate During Occupied Hours $108,000 83,226 1,880 1,414 $72,300 1.5 2 8 10 Decommission Unused Fume Hoods Decommission Existing AHU Dehumidification Sequences $24,000 $5,000 18,876 41,647 609 2,326 216 3,346 $16,700 $124,100 1.4 0.0 2,3 12 Reduce Classroom Lab Fume Exhaust Levels During Unoccupied Hours $131,000 30,465 435 $9,700 13.5 2 $7,000 $413,000 - 853 $13,600 $403,400 0.5 1.0 2,4 13 Reduce Minimum Humidification Setpoint TOTAL Notes: 1. Cost estimates are based on RS Means data and past project experience, and does not include project soft costs. 2. Savings calculated assume that ECM-10 and ECM-11 have already been completed 3. Costs associated with this measure include both the decommissioning and recommissioning effort of hood identified. 4. This measure is listed on this table because it was identified as part of this study. However it is no longer recommended to be implemented. 7 - Estimated Blended Marginal Rates (Fiscal Year 2013) $ $ $ 0.084 /kWh Elec 15.91 /MMBtu Steam 24.98 /MMBtu Chilled Water ECM-4 Discharge Air Temperature set Point Reset • reduce the reheat load: reset the AHU Discharge air set points upward when dehumidification is not necessary Room Number W254 W76 W182 W174 E127A-1 W290A E236 W338 W344 W444 E303 E309 W436 Space Use Description Teaching Laboratory Lab Equipment Room Lab Analytical Room Research Lab Research Lab Core Collegiate Lab Classroom Projection Room Electrical Closet Lab Computer Server Room Class Lab Preparation RoomW428 Classroom Laboratory Research Lab (Dry) Research Lab (Dry) Collegiate - Special Procedures • Individual spaces identified • Majority of concerned spaces currently have supplemental cooling systems User Discussion ECM-6/ECM-12 Teaching Lab Occupancy Air Flow Reset • Modify Control Sequence to Reduce Ventilation and hood exhaust Rate Setpoints during Unoccupied Hours • Reduce Minimum Room Airflow to 4 ACH and hood air flow to NFPA minimum User Discussion ECM-6/ECM-12 Teaching Lab Occupancy Air Flow Reset • Minimum Turndown Capabilities of VAV’s • Temperature Confirmed Control through Infrastructure sample of Shop Drawings Add Controllers •• Reviewed Viable(Nae) Timeframes Winter And Spring Break • Each Room Program Individually Modified User Discussion ECM-7 Reduce Minimum Laboratory Ventilation Rate During Occupied Hours • Modify Control Sequence to Reduce Ventilation Rate Setpoints during Occupied Hours in Classroom Laboratories. • Reduce Minimum Room Airflow to 6 ACH User Discussion ECM-7 Reduce Minimum Laboratory Ventilation Rate During Occupied Hours • Minimum Turndown Capabilities of VAV’s • Temperature Control Infrastructure User Discussion ECM-8 Decommission Unused Fume Hoods • This measure identifies the savings potential of decommissioning Individual Fume Hoods Scope Would Include1. Shut off the exhaust VAV Terminal at Each hood 2. Fully close hood and Secure sash 3. Visually Identify Hood as being Decommissioned and cannot be used 4. Rebalance Room Airflows to maintain pressure requirements User Discussion ECM-8 Decommission Unused Fume Hoods Five Rooms Identified E124 W100 W105 W109 W147 User Discussion ECM-10 Decommission AHU Dehumidification Sequence • Remove program to reset DAT down based on return air humidity. Impact To Building Occupants: • Building humidity levels may increase from values currently seen when mechanical cooling is active (chilled water available). Spaces will remain within standards for thermal comfort. User Discussion Decommission Existing AHU Dehumidification Sequence Impact To Building Occupants: • Building humidity levels may increase from values currently seen. Spaces will remain within standards for thermal comfort. Risks Associated with Implementation: • Areas requiring specific environmental humidity levels may need supplemental dedicated dehumidification equipment. User Discussion User Discussion ECM-13 Reduce Humidification Set Point • Lower humidification set point from 30% to 20% RH • Based on equipment environmental tolerances, this measure was not implemented. Actual Implementation • Engaged building participants; early and often • Free-flow of information • Responded quickly to concerns • Took time to learn Questions? Thank You