On-line PD testing & Diagnosis of MV & HV Cables Contents Introduction to PD damage to cables On-line PD Measurement • Motivations • Sensors and Measurement • Location and Field Applications • Monitoring Case Studies Conclusions Cables • • • • • Paper (PILC, MIND etc.) XLPE EPR PVC 3 Core and Single Core • Cables • Mixed cables with transition joints 33kV XLPE 3-core cable Right: 33kV PILC 3-core cable Left: 11kV PILC ‘Belted; cable 33kV XLPE single-core armoured cable PD Detection – Energies for Different Points in Cable System Corona at metal contacts Electrical charge RF Electromagnetic radiation Acoustic Ultraviolet Ozone Discharges on insulator surface Electrical charge RF Electromagnetic radiation Acoustic Ultraviolet Ozone Partial discharge in termination insulation system Electrical charge RF Electromagnetic radiation (local) Acoustic (local) Partial discharge in cable insulation or joint Electrical charge RF Electromagnetic radiation (local) Acoustic (local) PD Damage – Incorrect Fitting of Stress Cone Tracking on 115kV Termination (before failure) Failed 115kV Termination (same type) PD Damage to Cables – Water Tree Conversion to Electrical Tree in XLPE Cable • Water trees turn into electrical trees immediately before failure • PD testing will not detect early stages of water tree growth Electrical trees Bow-tie water trees On-line PD Spot-Testing • Quick to perform • Overview of PD activity • MV and HV Cables, all insulation types • Advanced diagnostic techniques for noisereduction Continuous Monitoring • Detect load varying and intermittent PD (mostly on PILC) • Detect incipient faults through changes in pattern • Temporary and permanent applications PD Detection Theory • HV Capacitor – Placed in parallel with cable at termination – C = 500pF – 1nF (typically) – C is high impedance to low freq (i.e. 0.1 – 400 Hz) high voltage applied to cable – C is short circuit to high frequency PD signals (i.e. kHz/MHz range) – Off-line only Cable under test Coupling Capacitor Measurement Impedance Sensors Sensor HFCT Attachment Point Power cable earth strap/drain wire or power cable with earth strap/drain wire brought back through sensor. Current impulses from PD in cables, cable terminations and plant/switchgear cables are terminated into. Metal-clad plant housing close to vents/seams/gaskets. Electromagnetic radiation from PD sites in plant that is induced onto the plant metal housing. Over vents in plant housing with line of site to PD source. Airborne acoustic (ultrasonic) radiation from corona and surface discharges in the plant. TEV Airborne Acoustic PD Detection Method HFCT Sensor Attachment Temporary Outside Cable Box 2 1 HFCT Attachment at Cross-bond Points Circuit Name Cable Type Voltage (kV) Length (m) Return Time (μs) Hotel Maluri Inn Taman Maluri Y Phase 3c XLPE 11 232 2.9 Test Date 27/07/08 Test method OWTS HV Capacitor OWTS, PD at 1.3U0 Cable under test PD Map of Circuit Hotel Maluri Inn - Taman Maluri - Y Phase All 500 HFCT 450 HFCT 400 All Phases PD OWTS Supply with inbuilt HV Capacitor Return Propagation Speed (m/μs) 80 350 300 250 200 150 100 50 0 0 20 40 60 80 100 120 140 Location (meters) 160 180 200 220 240 On-line PD Detection Equipment PD Detection Equipment and Methodology Detect cable and local PD Cable PD • PD signals from power cable components • HFCT detection Local PD • PD signals from nearby sources: cable terminations, switchgear, transformer etc • HFCT/TEV/Acoustic detection Wideband Capture of PD signals, BW, 50-400MHz • Capture all of the PD energy detected by sensor • Capture simultaneously with power cycle and extract impulsive signals • Separation of PD and noise signals based on wave shape • Continuous (RF, etc) noises removed with hardware notch/high pass filters Hardware Filtering/ Amplification PD Sensors Digitiser/DSO Trigger signal PD Data Analysis Software HVPD On-line PD Technology PD Detection • HVPD-Longshot™ with PDGold© Software • Wideband PD test system PD Location • HVPD Longshot™ with PDMap© Software • Transponder Installed at far cable end PD Monitoring • HVPD Longshot™ (up to 48 hours) • HVPD Mini™ On-line PD Signal Measurement 20 ms Available Waveform Display 0.015 0.01 Chan 1 One power cycle of raw data from HFCT sensor 0.005 0 -0.005 -0.01 -0.015 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Time (mSec) Chan 1 15 us Segment Waveform Curs 1 Curs 2 Segment Waveform Segment Waveform Ch 1 15 15 10 4 Volts (mV) 0 -5 Volts (mV) 10 5 5 0 -5 -10 -10 -15 -15 Ch 1 Ch 1 2 0 -2 -4 0 2 4 6 8 Time uSec 10 12 14 Cable PD Pulse: 16mV, 1160pC 0 2 4 6 8 Time uSec 10 12 14 Local PD Pulse: 15mV, 24dB 0 2 4 6 8 Time uSec 10 12 Noise Pulse: 6mV 14 Normal Distribution of All Events in a Single Power Cycle 1 Power Cycle 0.015 Noise Peak Cable PD Peak Chan 1 (V) 0.01 0.005 0 -0.005 -0.01 100 -0.015 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Time (ms) Segment Waveform 10 Volts (mV) 10 5 0 -5 -10 -15 0 2 4 6 Time uSec 8 10 Segment Waveform 15 1 10 4 6 8 10 12 Peak (mV) 14 16 18 20 Volts (mV) Counts 15 5 0 -5 -10 -15 0 5 10 15 20 Time uSec 25 30 Noise and Interferences in On-line PD Measurements Noise can be problem on-line • Cables/plant not isolated from network • Sensors often attached to ground Noise sources • Continuous: Radio/TV stations, communications • Impulsive - Periodic • Power electronics, e.g. inverter power supplies, UPS • Rotating machine excitation • Impulsive – Random • Switching Events • Corona • PD on other cables/plant Noise Source Summary RF broadcast signals overhead lines corona/ surface discharge outdoor termination switchgear bus power electronic devices corona/surface discharge/RF signals/PD in outdoor equipment PD in switchgear switching noise/ interference switchgear earth excitation signals/ PD from generator PD from adjacent feeders noise from far end of cable PD from transformers substation earth excitation signals/ PD from motor G Noise Discrimination – Hardware Filters • Preferred over software filtering • Remove interferences in HFCT pass-band • Use in difficult measurement situations Noise Discrimination – Hardware Filters • Single Frequency RF Noise Reduction Power Cycle PD and noise detail Noisy Data Denoised Data 0.08 0.06 0.04 CH3 (V) 0.02 0.00 -0.02 -0.04 -0.06 -0.08 13.0m 13.0m Time (s) 13.0m 13.1m Noise Discrimination – Event Recognition • Power Electronic Switching 0.015 Voltage (V) 0.01 Continuous amplitude across power cycle 0.005 0 No phase pattern -0.005 -0.01 -0.015 Segment Waveforms 2 4 6 8 10 12 Time (ms) 14 16 18 20 Main segment 0 Pulses appear as chain 16kHz repetition frequency 0.15 0.1 0.05 0 -0.05 -0.1 -0.15 0 20 40 60 80 Time (uSec) 100 120 140 PD Test and Location Applications PD location at RMU • Signals propagate between cables with little attenuation on two feeder RMUs • Reduced detection points on network – no need to test every RMU • Synchronous capture necessary to determine source feeder Measured PD pulse Segment Waveform Zoom of pulse start Ch 3 Ch 4 100 50 Segment Waveform 0 -50 -100 150 C C 100 -150 -200 0 1 2 3 4 5 6 Time uSec 7 8 9 10 Volts (mV) Volts (mV) 200 150 50 0 -50 -100 -150 1 2 3 Time uSec Example Test Configuration for PD Location on Circuit with RMUs Section of Cable Undergoing Mapping Test 11kV RMU (Normally open) HVPD-Longshot RMU RMU (Normally closed) (Normally closed) Transponder Cable Return Time, L for On-line Measurements • Use from Off-line Tests • Estimate from cable length and average propagation speed for cable type • Measure with on-line TDR (requires impedance change at far end of cable) PD Site Location, T PD% 1 100 L Cables with Cross-Bonding PD Propagation in Cross-bonded Cable Systems • Cross-bond point is seen as change in impedance in cable system • Some of pulse propagates into cross-bond point and onto all cables • Some of pulse is reflected back down source cable • Long-cross bond leads/coaxial cross-bond cables are high impedance to HF PD signals ZA ZD ZB ZE ZC ZF Cross-bond Propagation Example Current Transformers Pulse on outgoing side of CB, L1 L1 Input signal, L1 50Ω L2 50Ω 50Ω 50Ω Cross Bond Point Chan 2 L3 Available Waveform Display 0.035 0.03 0.025 0.02 0.015 0.01 0.005 0 -0.005 -0.01 -0.015 -0.02 -0.025 -0.03 -0.035 Chan 1 50Ω Outgoing Side Injection Side Pulse Injection Test Set-up 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 Outgoing scale 50% of Injection scale Reflection from CB 0 1 Time (uSec) Chan 1 Chan 2 Curs 1 2 Curs 2 Procedure for Testing Cross-bonded Cable System Detection • Sequentially test at terminations and all CB-points N = 2 + number of joints Test 1 Test 2 Test 3 Test N Continuous PD Monitoring Continuous PD Monitoring Aspects Detect cyclic changes in activity • Load varying activity on PILC cables • Humidity related activity from surface discharges Detect changes that relate to incipient faults • Gradual rise • Sudden rise • Sudden drop Carried out on: key circuits, circuits with suspected cyclic PD changes, circuits with high spot-test results PD and Load Relations CT PD Activity (Pc/Cycle) • Although PD incepted by voltage, load can have effect • Mostly on PILC cables • Load variations – Movement of oil/impregnant – Expansion of conductors Cumlative PD Activity (CT) 10,000 Time T F F 06/01/2011 00:00 W T 05/01/2011 00:00 T W 04/01/2011 00:00 M T 03/01/2011 00:00 S M 02/01/2011 00:00 30/12/2010 00:00 S S 31/12/2010 00:00 S 0 01/01/2011 00:00 5,000 Time Lower Richmond 23/03/2010 00:00 21/03/2010 00:00 19/03/2010 00:00 Time 17/03/2010 00:00 15/03/2010 00:00 13/03/2010 00:00 11/03/2010 00:00 09/03/2010 00:00 06/03/2010 00:00 07/03/2010 00:00 CT PD Activity (Pc/Cycle) 23/03/2010 00:00 21/03/2010 00:00 19/03/2010 00:00 17/03/2010 00:00 15/03/2010 00:00 13/03/2010 00:00 11/03/2010 00:00 09/03/2010 00:00 06/03/2010 00:00 07/03/2010 00:00 CT PD Activity (Pc/Cycle) Examples of Monitoring • Simultaneous change in PD with monitors on 11kV network Cumlative PD Activity (CT) 10,000 5,000 0 Bemish Road Cumlative PD Activity (CT) 10,000 5,000 0 On-line PD Severity Evaluation PD Level Guidelines • To determine the true severity the PD is posing to the cable, the following should be taken into account – Cable accessories (joints and terminations) have a higher tolerance to PD than the cable insulation – Mixed circuits: Paper/PILC has a much higher tolerance to PD than XLPE PD Level Guidelines Example of Normalised Distribution of Off-line PD Levels Measured in 33kV Paper and XLPE Cables Mackinlay, R. & Walton, C. Some advances in PD monitoring for high voltage cables MV Paper Cables: Asset or Liability?(Digest No. 1998/290), IEE Colloquium on, 1998 Case Study: On-line PDMapping TNB-D PPU – Central Spectrum May 2006 PDGold Test: Central Spectrum PD Magnitude (pC) Cable PD 2,000 1,000 0 -1,000 -2,000 0 90 180 270 360 Phase of Pow er Cycle (deg) Cable PD Segment Waveform Volts (mV) 40 20 0 -20 -40 0 2 4 6 8 10 Time us 12 14 PDGold Test: Central Spectrum PD Magnitude (pC) Cable PD 2,000 1,000 0 -1,000 -2,000 0 90 180 270 360 Phase of Pow er Cycle (deg) Cable PD Segment Waveform Install transponder at Substation B due to lower noise level 20 Volts (mV) • 10 0 -10 -20 0 2 4 6 8 10 Time us 12 14 Transponder at Central Spectrum Detection HFCT Trigger Unit Pulse Generator Injection HFCT Voltage (mV) Transponder Waveform Measured at PPU Waveform data in Time 15 Chan 1 (mV Cur 1 Cur 2 Cur 3 Cur 5 Transponder Injected Pulse 10 Reflected Pulse 5 0 -5 Direct Pulse Transponder time delay -10 -15 -20 0 10 20 30 40 50 60 Time (uSec) 70 80 90 PDMap Waveform PD Map of Circuit main substation to central spectrum All 2,000 1,800 All Phases PD 1,600 1,400 1,200 1,000 800 600 400 200 0 0 • 500 1,000 1,500 2,000 2,500 Location (meters) Result: 3x PD Sites found on Cable 3,000 3,500 4,000 Conclusions Conclusions • HFCT sensors allow sensitive measurements to be made at multiple points in the cable system • On-line PD location can relatively quickly identify weak points for timely remedial action • Solutions available for complex circuits such as with cross-bonding