Ahmad Hassan AlObaidly and Abdulaziz Abdulla Alshafai Supervisor: Dr. Khaled Ellithy Department of Electrical Engineering, College of Engineering FALL 2008 Introduction Objectives In recent years, harmonics are considered as one of the most essential problems in the industrial power distribution networks. The problem of harmonics is increasing due to the use of the variable speed drives (VSDs), the uninterruptible power supplies (UPS), and the solid-state devices. Harmonics current distortion may produce negative effects on the power quality of the power networks. The negative effects include malfunctioning of sensitive devices such as protective relays, motors overheating, and transformer overheating. The current total harmonic distortion (THD) can be reduced to the IEEE standards using harmonics filters such as passive harmonic filters or active harmonic filters. To conduct a study on harmonics, harmonics sources, harmonics representation, harmonics effects, and harmonics indices. To study the recommended IEEE-519 standards for the current and voltage harmonics distortion. To conduct a study on the types of harmonics filters. To conduct a study on passive harmonics filters design. To perform the harmonics analysis and harmonics filter design for a typical gas plant power network using EDSA power system analysis software. Harmonics Indices and IEEE 510 Standards "Harmonics" term in an AC power system is defined as a sinusoidal component of a periodic waveform that has a frequency equal to an integer multiples of the fundamental frequency (50 Hz) of the power network. The Total harmonic distortion (THD) is a measure of the effective value of the harmonic components of a distorted waveform. Power Distribution Network Model for Harmonics Analysis of a Train in a Typical Gas Plant IEEE 519 standard of voltage harmonics distortions The THD of voltage is given by % THD V V h , RMS V 2 V 3 ...... V N 2 100 2 V1 Bus Voltage at PCC (KV) Individual harmonic voltage distortion (%) Total Voltage Distortion, THD (%) V < 69 3.0 5.0 69 < V < 161 1.5 2.5 V > 161 1.0 1.5 2 100 V1 IEEE 519 standard of current harmonics distortions Maximum harmonic current distortion in percentage of the fundamental V ≤ 69 kV I I 2 I 3 ...... I N 2 100 2 I1 2 100 I1 11≤h<17 17≤h≤23 23≤h≤35 <20 4.0 2.0 1.5 0.6 0.3 5.0 20-50 7.0 3.5 2.5 1.0 0.5 8.0 50-100 10.0 4.5 4.0 1.5 0.7 12.0 100-1000 12.0 5.5 5.0 2.0 1.0 15.0 >1000 15.0 7.0 6.0 2.5 1.4 20.0 % Computer Simulation Results without Harmonics Filters Single-line diagram of power distribution network Including harmonics sources Harmonics Filter Design A passive harmonic filter is designed to eliminate the 11th harmonic order for HR5343 EDSA Harmonic Analysis 544.3 Q C V LL C 2000 10 2 HR-5343 %THDi= 42.55% UPS-A %THDi= 41.38% EDSA Harmonic Analysis EDSA Harmonic Analysis 150.0 100.0 Magnitude % Magnitude % 100.0 150.0 50.0 0.0 -50.0 50.0 -50.0 -100.0 -150.0 -150.0 80 160 240 320 400 480 560 640 XC 0.0 -100.0 0 X 0 720 80 160 240 320 400 480 560 640 720 EDSA Harmonic Analysis EDSA Harmonic Analysis 100.0 83.3 83.3 Magnitude % 100.0 66.7 50.0 33.3 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 XC 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 The current total harmonic distortions (42.55% and 41.38%) exceed the IEEE-519 standards Computer Simulation Results with the Designed Harmonics Filters HR-5343 %THDi=7.37% UPS-A %THDi=2.98% EDSA Harmonic Analysis EDSA Harmonic Analysis 150.0 150.0 100.0 100.0 Magnitude % -100.0 50.0 0.0 -50.0 -100.0 -150.0 -150.0 0 80 160 240 320 400 480 560 640 720 0 80 160 240 320 400 480 Angle in Degrees Angle in Degrees EDSA Harmonic Analysis EDSA Harmonic Analysis 100.0 83.3 83.3 Magnitude % 100.0 66.7 50.0 33.3 16.7 560 640 720 45.0 50.0 66.7 50.0 33.3 16.7 0.0 0.0 0.0 5.0 10.0 15.0 20.0 25.0 Harmonic 30.0 35.0 40.0 45.0 50.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 Harmonic The current total harmonic distortions (7.37% and 2.98%) are within the IEEE-519 standards. X L 181.4 90.7 111 222 333 444 556 667 778 889 1000 778 889 1000 4 . 53562 2 * 50 * C 2 272.1 Frequency (Hz) 1 XC 362.8 0 3 3 ( 415 ) * ( 2 * 50 ) * C 2 F 50.0 33.3 453.6 0.0 C 1 . 8482 10 Harmonic -50.0 2 ) * ( 2 * 50 ) * C 548 . 811 2 Harmonic 0.0 XC 2 F Q C V LL C 100 10 66.7 50.0 50.0 2 * 50 * C h 0.0 0.0 Magnitude % L 16.7 16.7 Magnitude % 1 6 ( 33000 Passive harmonic filter to eliminate the 5th harmonic order for UPS-A Angle in Degrees Angle in Degrees Magnitude % C 5 . 8 10 3 Impedance Response (Ohms) % THD I h , RMS h<11 1 . 72225 EDSA Harmonic Analysis 1.653 Impedance Response (Ohms) The THD of current is given by TDD% 35≤h ISC / IL 1.378 1.102 0.827 0.551 0.276 0.000 0 111 222 333 444 556 667 Frequency (Hz) 0 . 06889 h5 The voltage and kVAR of the harmonics filter capacitor have been checked with limits recommended by ANSI/IEEE 18-1980 standards. Conclusions Harmonics sources, harmonics effects and harmonics representation have been presented. An industrial power distribution network of a gas plant was chosen for the study. Measurements of the current and voltage harmonics distortions at the Gas Plant were conducted using AEMC power quality analyzer. The plant power distribution network for harmonics analysis was developed using EDSA power systems analysis software. The harmonics filters were designed to eliminate the dominant harmonics orders to reduce the THD of the current and voltage to the allowable limits recommended by the IEEE 519 standards. The maximum limits of voltage and kVAR of the harmonics filter capacitor have been checked with the ANSI/IEEE 18 standards.