STAMI

advertisement
STAMI (ST Advanced Metering Interface)
Web Tool for the advanced management
of LV Network
Trends in Power Industry in the European Context VIII
Antonello Buondonno
Head of Europe and Americas Business Development
Enel Infrastructures and Network Division
Spindleruv Mlin, April 18th 2013
Uso:
STAMI: ST Advanced Metering Interface
Agenda
• ST Web Applications
• STAMI
• System Architecture
• Main features and tools for the LV Operation Management
Aziendale
Uso:
Aziendale
ST Web Applications
Remote Control and automation system – ST Web Applications
Network
Other Company
applications
Metering System
HV
MV
LV
ST Web
Applications
STUX/STM
ST Remote Control
and Automation
System
Uso:
Aziendale
ST Web Applications
Remote Control and automation system – ST Web Applications
Events
STAMI – ST Advanced
Metering Interface
GIS & Network Schemes
Measurements
Maintenance
Systems Statistics
and Performances
Management
Of the Active Grid
Uso:
Aziendale
STAMI: ST Advanced Metering Interface
Web Tool for the advanced Network Management
STAMI: dedicated Web Interface to collect (on demand and real time) specific
high quality data stored in smart meters for network management purposes.
STAMI main applications:
 Customer Service
STAMI
interface
 Network Operations
On field
installed Smart
Meters
 Electricity Regulation Compliance
 Energy Balance and fraud detection
Web Client
Network Control
Center
Workstations
The European Utility Award for 2010 has been awarded to Enel for STAMI
Uso:
Aziendale
STAMI: ST Advanced Metering Interface
Web Tool for the advanced Network Management
STAMI: dedicated Web Interface to collect (on demand and real time) specific
high quality data stored in smart meters for network management purposes.
STAMI allows to access to the following
data stored in Smart Meters:
 Voltage Quality
 Voltage Outages
STAMI
interface
 Monthly consumption
On field
installed Smart
Meters
 Load Profile
 Power threshold
 Daily consumption
Web Client
Network Control
Center
Workstations
The European Utility Award for 2010 has been awarded to Enel for STAMI
Uso:
Aziendale
STAMI: Advanced Metering Interface
Architecture
1
GSM/GPRS
or
PSTN
Users send requests through STAMI interface
Interface available on Enel Intranet and on the workstations
installed in Network Control Centers
LVC
STAMI
Interface
LV network
Remote Control LAN
Company IP Network
2
3
Server Zeus processes requests
directly connecting with Smart
meters through concentrators in
secondary substation.
Requests are
forwarded to
STAMI WS
which interacts
with Server
ZEUS
Security to read meters is managed by
Zeus Itself
DMZ
Web Server
AMM
Zeus
Web interface for
Telegestore
Uso:
Aziendale
Main features and tools for the Operation Management
Main Features and related benefits
Customer Service: Improvement of Customer Service and LV operation activity
related to customer request
Network Operations: Optimization of Work Force Activities
Electricity Regulator Compliance: Provide reliable and immediate data related
to LV continuity and quality of supply
Energy Balance: Effectively localize energy fraud & theft
Uso:
Aziendale
Main features and tools for the Operation Management
Customer Service
Support the Control Center Operator in case of customer request:
Customer satisfaction improvement
STAMI operator can give immediate feedback in case of
customer service anomalies
1
4
3
Real time response from field installed equipment
Throw STAMI it is possible to check voltage presence and
voltage quality at the supply terminal without involving a
crew for verification on field
Immediately check defaulting customer
STAMI allows to check the power threshold available to the
customer to immediately localize a bad payer
VOLTAGE INTERRUPTIONS
VOLTAGE QUALITY
POWER THRESHOLD (%)
10
2
Uso:
Aziendale
Main features and tools for the Operation Management
Operations
STAMI support daily Low Voltage Network Operations Activity:
Low Voltage Network supervising
LV line fault
In case of LV customer warning call, STAMI operator is able
to real time check the condition of the LV network supplying
the electronic meter.
Optimization of Work Force activities
In case of LV network fault, STAMI operator may
immediately verify the origin of the anomaly and program
the activity on field.
VOLTAGE INTERRUPTIONS
VOLTAGE QUALITY
Electronic Meter
fault
Uso:
Aziendale
Main features and tools for the Operation Management
Electricity Regulator Compliance
Reliable and immediate data related to LV supply
Throw STAMI It is possible to directly see voltage outages
without waiting for documentation
VOLTAGE INTERRUPTIONS
STAMI
operator
Voltage Interruptions recording
Thanks to STAMI it is possible to identify LV outages with the
exact indication of the beginning and the end
Low voltage faults
and interruptions
form
Quality of service monitoring
Quality of service data related to MV/LV TR and LV lines
available throw STAMI may be used for reporting
Date/Hour/Time
....
Interruption
....
Fault
....
Username
....
On field technician
Uso:
Aziendale
Main features and tools for the Operation Management
Energy Balance
STAMI operators are able to perform
detailed analysis on the LV network,
providing support to the crews in the
identification of frauds
Effectively localize energy fraud & theft
Acquisition of load profile and daily consumptions to
support fraud detection
Central access
Energy
Balance
meter
MV/LV
By accurate analysis, it allows to
identify precisely the customers to
be checked on field
For more accurate analysis, STAMI
allows to upload and analyze data
coming from portable energy balance
meters (ALVIN)
DAILY CONSUMPTIONS
Intranet
Enel
On field access
Energy
Balance
Load profile
Uso:
Thank you
Antonello Buondonno
Head of Europe and Americas
Business Development
Enel Infrastructure and Network Division
antonello.buondonno@enel.com
Aziendale
Uso:
Backup
Aziendale
Uso:
Aziendale
STAMI: Advanced Metering Interface
Web Interface: main operations
Data request
Used to send data requests: it is possible to
directly ask about a Meter, a Concentrator, a
customized group of meters
Status of transactions
Used to display all the data requests and to
check their status.
Information Viewing
It makes possible to quickly access and
download the results coming from user
requests
ALVIN Management
Used to upload and analyze data coming from
portable energy balance meters (ALVIN)
Uso:
STAMI: Advanced Metering Interface
Data availability from Electronic Meters
 Voltage Quality
Period, Instantaneous Voltage value, VMIN and VMAX for each phase, number of samples in the allowed
range (230V+-10%), number of samples out of allowed range.
Electronics meters record a value every ten minutes: 1008 samples a week available.
 Voltage Outages
Period, onset time, duration of the interruption, affected phase, electric line involved
 Monthly consumption
Date, energy consumption value in a billing period on T1, T2 and T3
Aziendale
Uso:
STAMI: Advanced Metering Interface
Data availability from Electronic Meters
 Load Profile
Graph and list of active and reactive power consumption and active power
feeding the grid (in case of active customers).
Electronic Meter stores Power average value every 15 minutes
 Power threshold
Percentage of contractual power available to the customer
 Daily consumption
Date and daily value of energy consumption
Aziendale
Uso:
Aziendale
STAMI: Advanced Metering Interface
Viewing information menu: Power Threshold
Defaulting Customer
In case of a customer's phone call,
Enel doesn’t need to send a
technician on site to check if he is
a bad payer.
Uso:
Aziendale
STAMI: Advanced Metering Interface
Viewing information menù: Voltage Outages
The fault can
affect one or more
phases
Uso:
Aziendale
STAMI: Advanced Metering Interface
Load Profile
Active Customer Load Profile: set of
graphs available for each meter.
 A Load Profile Request returns to the operator a set
of graphs with the average active and reactive
power consumption profile and, in case of active
customers, the active power feeding the grid.
 Instead of a graphic representation it is also possible
to display the list of the average power
consumption values stored in the smart meter
every 15 minutes.
 It is possible to send a Load Profile request for a
single Smart Meter or a whole MT/bt
Transformer. In this case STAMI returns the load
profile of each Smart Meter, the Load profile, in a
unique curve, of the sum of al the smart meters
connected to the TR and the load profile of the
energy balance meter installed in the secondary
substation.
 It is possible draw the Load profile of each LV line
feed by the Transformer, to create any customized
group of meters of which the operator wants to
draw the Load Curve, to upload and display the Load
curve recorded by ALVIN, the portable energy
balance meter.
Uso:
Aziendale
STAMI: Advanced Metering Interface
Load Profile
Transformer Load
Profile
Measured Energy Balance
Meter
Aggregation of
customers’ Load
Profiles
Sum of Energy measured by
each Smart Meter
Probable energy fraud
Between 9.00 am to 6.00 pm the difference between the 2 curves is greater
than the expected technical losses: a verification on field is needed
Uso:
Aziendale
Metering activities
Rules and Obligations: Italian Timebased Tariff Regulation
Following the introduction of the Telegestore, the Italian Regulator established specific
metering rules depending on the characteristic of the customer:
 For HV, MV and LV customers with power installed >55 kW it is mandatory a meter
reading each hour.
 For LV customers with power installed <55 kW the reading is done per consumption
timeslots, F1, F2, F3, compliant with the timebased tariff regulation.
Mon-Fri
F3
00:00
Sat
00:00
F2
07:00
F2
F1
08:00
19:00
F3
F2
F3
23:00
F3
07:00
23:00
Sun
24:00
24:00
F3
00:00
24:00
Peak
Mid peak
Off peak
Download