NBS-M009 2010 LOW CARBON BUSINESS REGULATION AND ENTREPRENEURSHIP Control of Energy use in Buildings Building Regulations Recipient of James Watt Gold Medal N.K. Tovey (杜伟贤) M.A, PhD, CEng, MICE, CEnv Н.К.Тови М.А., д-р технических наук 1 Lecture 1 Lecture 2 1 11 Building Regulations • Review of Building Regulations in UK – Factors affecting energy consumption and carbon emissions – Standard Assessment Procedure • Code for Sustainable Homes • Energy Performance Certificates • Introduction in Indian Building Regulations • Introduction to Chinese Building Regulations Lecture 1 Lecture 2 Lecture 3 2 Introduction of Building Regulations • Until 1965 there were no national Building Codes. • Previously Local Bye Laws prevailed and modes of construction varied from one part of UK to another. • First Building Regulations did not include requirements for Energy Conservation – these came in 1976 • Building Regulations are divided into sections and associated Approved Documents (ADs) • Part A: Structural Maters • Part B: Fire • Part F: Ventilation • Part H: Heat producing appliances • Part L: Energy Conservation and more recently carbon emissions • Each Part has associated Ads e.g. for Part L the Approved Documents were originally ADL. • Subsequently divided into ADL1 and ADL2 covering dwellings and nondwelling separately • Then subdivided further into ADL1a and ADL1b covering new and existing buildings. 3 Changes in the Heating Standards of Houses • First introduced as Part L in 1976 • Basic Statement – largely following what was then common practice e.g. cavity walls brick cavity block with no insulation: - no insulation in floor, minimal insulation in loft. • 1994: First attempt to address overall annual energy consumption, although elemental method of compliance was still permitted • 2002: Carbon Index introduced • 2006: Target Emission Rate and Dwelling Emission Rate introduced. • 2010: Came into force Oct 1st 2010 – relatively minor updates on 2006 Regulations 4 Many Deficiencies in earlier Building Regulations • Before 1994 if double glazing was used – window area could be doubled – requirements for walls/roof/floor could be relaxed if overall loss < = standard house (type 1 trade off) • From 1995 – Could include incidental gains from appliance use/solar gains – If consumption <= standard house - regulations could be relaxed further • 1994 & 2000 regulations – If triple glazing used window area can be increased by 50% (type 2 trade off) – If higher insulations for walls used, greater window area permitted provided <= standard house. • Traditionally framed for minimum compliance rather than actively promoting energy conservation – Less an issue in 2000 Regs – 2005 Regs tightened further reducing opportunities for trade-offs On other hand some of these trade-offs potentially could encourage innovation? 5 U-Value Specification with different Regulations 1976 1985 1990 1994 2000 2005 2010 U – Values W m-2 oC-1 SAP SAP > < 60 60 External Wall 1.0 0.6 0.45 0.45 0.35 0.45 0.35 0.35 Roof 0.6 0.35 0.25 0.2 0.16 0.25 0.16 0.16 Floor 1.0 0.6 0.45 0.35 0.25 0.45 0.25 0.25 3.0 2.0* 3.3 2.0 2.0 25% 25% Windows Not specified Windows as % of external walls 17% 12% Windows as % of total floor areas - - - 15% 22.5% 25% 22.5% 6 Comparison of energy consumption for a standard detached house at various ages and improvements (Heat losses in W0C-1) 800 700 unimproved 600 25mm 500 50mm 400 100mm 300 100+CAV 200 100+DG 100 100+DG+CAV 150+DG 0 pre- post- 1960s 1976 1985 1990 1994 2000 war war DG – double glazing CAV – cavity wall insulation Numerical value indicates thickness of loft insulation 200+DG+CAV 250+DG+CAV 7 0 Bungalows centre mid-storey top centre bottom centre mid-storey end top end bottom end Houses semi-detached 600 detached terraced 500 semi-detached detached Effects of built form on energy consumption (Heat loss WoC-1) 2002 1976 Flats 400 300 200 100 8 Compliance to Building Regulations • Compliance to Building Regulations may be achieved by one of several alternative methods. – Elemental Method • Specifies maximum U-value and perhaps maximum glazed area – valid until 2002 Regs – Target U-value – weighted average U-value allowed some flexibility in design – SAP Rating (1994 Regs) – economic assessment – Carbon Index (2002 Regs) – Target Emission Rate (Current Regs) 9 1994 Regulations: A step change • Single glazing could no longer be used routinely for domestic buildings • Glazed area 22.5% of floor area – 50% greater than 1990 regs – 50% potential saving lost • Standard Assessment Procedure (SAP) rating for new buildings – – – – – 0-100 – higher the better No target SAP but requirements relaxed if >60 SAP 80-84 – Regs automatically satisfied Includes energy running costs in calculation Trade offs permitted • Does not specify ventilation rates but gives method for estimating • Make allowance for solar water heating if fitted • Include hot water requirements 10 Building Regulations 2000 • Implemented April 2002 • Energy rating method – SAP replaced by Carbon Index method for compliance – SAP ratings still to be calculated and notified to building control bodies • Requirement of heating & hot water changed to encompass overall system performance, not just controls – Boiler seasonal efficiency, inspection & commissioning included • New requirements for efficient lighting systems & provision of information for householders • Standards of fabric insulation improved – Lower (better) standards (loft insulation) – Reductions in U values (towards technical limits) – Changed methods for calculating U values • Lower U values for windows – Based on sealed double-glazed units with low emissivity panes – Area of glazing increased to 25% floor area • Target U-value method retained but provisions for trade-offs improved. 11 Compliance procedures 2000 Regulations Three methods to demonstrate compliance with Building Regulations: 1. Elemental approach 2. Target U-Value method 3. Carbon Index • 1. Elemental approach – valid if specific conditions are met. – – – – Heating must be gas, oil, heat pump, CHP DH, biogas or biomass U-values <= Building Regs 2000 standards Area window, doors, roof lights <=25% floor area Boiler: SEDBUK efficiency >=78% gas, 80% LPG, 85% oil see www.sedbuk.com [SEDBUK – Seasonal efficiency of domestic boilers in the UK. The average annual efficiency achieved in typical domestic conditions.] 12 EU Energy Performance of Buildings Directive (EPBD) 2002/91/EC • Aims at improving energy efficiency, carbon emissions from buildings could be reduced by 22%. Objectives of the Directive: • To promote the improvement of the energy performance of buildings within the EU through cost effective measures; • To promote the convergence of building standards towards those of Member States which already have ambitious levels. Measures include: • • • • Methodology for calculating the energy performance of buildings; Application of performance standards on new and existing buildings; Certification schemes for all buildings; Regular inspection and assessment of boilers/heating and cooling installations. 13 UK Response Part L Building Regulations (2005) Approved Document ADL1a • Came into force in England and Wales on 6 April 2006 (Scotland & Ireland to follow) • Office of the Deputy Prime Minister (ODPM) now Department of Local Government and Communities (DCLG) • Complies with EU legislation • Moves away from energy conservation to carbon emission reduction • UK National Calculation Methodology (NCM) for energy performance of buildings based on SAP 2005 14 2. Target U-Value method • Calculate Target U-Value – a function of areas of floor, roof, walls, windows etc • Modify target – gas & oil boilers: actual SEDBUK efficiency standard SEDBUK efficiency – electric & coal heating: divide by 1.15 – No modification for heat pumps, biomass, biogas, CHP – Purpose of modifications is to give more freedom for designs using efficient oil or gas boilers • Modify target if area south facing windows > area north facing windows • Calculate weighted average U-value of all external surfaces • Weighted average U-value must be <= Target value 15 3. Carbon Index Method • • • • • Most complex method Replaces SAP energy rating as a method of compliance Carbon index appears to be 0-10 Must be >= 8 to comply Max carbon index 10 – but actually 17.7! – Reality: 8 out of 17.7 or 4.5 out of 10! • SAP procedure is followed – up to point of introducing costs of fuels – actual annual energy consumption is used to calculate the annual carbon dioxide emission – translated into a carbon index 16 Standard Assessment Procedure (2001) • Calculate U-values • Check U-values are achieved • Calculate – – – – – – – gross heat requirements (Heat Loss Rate) hot water requirements incidental & solar gains effective gains effective internal temperature corrected degree-day parameter net space heating total energy requirement • Select heating method (pumps, appliance efficiency) • Calculate Total Energy Requirement • Estimate energy costs of total space heating, hot water & pumps • Deflate energy by Energy Cost Factor – 1994:0.96, 2001:1.05 17 Carbon emissions for same house designed to different standards Variation of Carbon Emission and Carbon Index with Building Regulations 70 pre-war 60 1955 1965 50 2 kg CO2/m /yr Theorectical Perfection in 2002 Regulations 40 1976 30 1985 1990 1994 20 2002 10 Elizabeth Fry ZICER 0 0 1 2 3 4 5 6 7 8 9 10 Carbon Index 18 Variation of Carbon Emission and Carbon Index problems with current Building Regulations 20 18 The ore cti cal Pe rfe cti on i n 2002 Re gul ati ons 16 2002 12 2 kg CO2/m /yr 14 10 8 6 El i z abe th Fry ZIC ER 4 2 0 7 8 9 10 Carbon Index 19 Building Regulation: Compliance Summary Up to and including 2000 Regulations • Elemental Method – specifying U-values of fabric elements • Target U-Value – allowed some flexibility of design. • SAP Rating – an economic measure – only permitted for compliance in 1994 Regs. 2000/2002 Regulations • Carbon Index Method- a distorted Carbon Measure 2005/6 Regulations • Dwelling Emission Rating must be better than Target Emission Rating. Latter is a derivative of the Target UValue Method. 2009/10 Regulations • Retains DER and TER but expects a 25% improvement on performance over 2005/6 standards 20 Carbon Index Calculations (2000 and onwards regulations) • Attempts to assess the true environmental performance of a building • Follow Standard Assessment Procedure to calculate Total Energy Requirement • Calculate CO2 emissions for building • Calculate Carbon Factor (CF) – CF=CO2 (TFA+45) where TFA is total floor space – Carbon Index (CI) CI=17.7-9.0 log10(CF) – Complication of scale >10 • 2000regulations indicated that compliance is 11kg CO2 per m2 – carbon index of 8 • If true scale was used Zicer & Elizabeth Fry would score 13.5 out of 10. 21 Critique of the Standard Assessment Procedure (SAP) • Energy efficiency index – but gives a rating that is monetary based not energy based • Assumes a general heating level in house – two zones (one living area one other). Does not allow for actual temperature settings. • Hot water requirements based on floor area formula not occupancy • Incidental gains based on floor area not occupancy • Problem: Is this a sensible approach? – If occupancy changes then Rating would change, but it is difficult to compare actual readings with predicted. • Alcantar (2008) found problems with methodology for incidental gains etc • 2010 Regulations partly address issue with regard to occupancy – e.g. • if TFA > 13.9: N = 1 + 1.76 × [1-exp (-0.000349 × (TFA-13.9)² )] + 0.0013 × (TFA-13.9) if TFA ≤ 13.9: N = 1 • N is the assumed number of occupants, TFA is the total floor area of dwelling. 22 2006 Regulations Dwelling Emission Rate is method of compliance - essentially the 2010 Regs are similar with only minor variations in detail • Criterion 1 • A Dwelling Emission Rating (DER) must be calculated taking due account of the U-values, the size, the types of heating etc using the Standard Assessment Procedure (SAP) • The DER must be shown to be less than the Target Emission Rating (TER) which is computed with the same size of building and U-values meeting those as specified in the Regulations. Essentially this is a derivative of the target U – value method • Details are shown in Section 2.1.11 of handout 23 2006 Regulations Dwelling Emission Rate is method of compliance - essentially the 2010 Regs are similar with only minor variations in detail Criterion 2 – limits on design flexibility • Performance of the building must not be worse than a given standard. • gives considerable latitude in design – the old trade-off problem. • However criterion attempts to limit this type of trade-off – see pages 5 and 6 of the Approved Document Criterion 3 – Limiting effects of solar overheating • Requires that the effects of overheating in summer must be addressed 24 2006 Regulations Dwelling Emission Rate is method of compliance - essentially the 2010 Regs are similar with only minor variations in detail Criterion 4 Quality of Construction • Criterion requires evidence of actual performance – e.g. changes arising from design modifications, quality of workmanship. Some of the requirements involve pressure testing the building to ensure they have achieved those used in the design specification. Criterion 5. Providing Information • Requires information on the maintenance and operation of the building to be made available. 25 Critique of the Standard Assessment Procedure (SAP) • Standing charge ignored for electricity, included for gas. Oil doesn’t have a fixed charge • Can lead to some perverse consequences – Lower efficiency oil heating can give a higher SAP rating than more efficient gas • Energy Cost Deflator is needed – Unnecessary complication that allows for inflation – But does not allow for differential prices changes between fuels • SAP 1995 – possible SAP rating of over 110 – SAP of 100 readily achievable • SAP 2001 – widened scale (over 120) for consistency with existing scale • SAP 2005 changed scale to have 100 for zero energy house – means all previous calculation have to be redone. – Now possible to get > 100 if a house is carbon negative – i.e. will be exporting more energy than it consumes. 26 CALCULATION of SAP RATING • While the Standard Assessment Procedure makes sense the final Rating known as the SAP Rating creates problems • The SAP rating is related to the total energy cost by the equations: • Energy Cost Factor (ECF) = deflator × total energy cost / (TFA + 45) (10) • The total energy running cost includes not only heating but also requirements for hot water, lighting etc as well as pumps/fans associated with heating. These are proscribed costs according to a table which are not actual costs. • The deflator is a factor which varies according to energy costs and is intended to keep SAP Ratings constant with time irrespective of changes in fuel prices - this has not been the case in the past. CALCULATION of SAP RATING 2010 • First work out the Energy Cost Factor (ECF) • where ECF = deflator × total energy cost / (TFA + 45) and TFA is the total floor area of the dwelling. [the energy cost factor initially has been set at 0.47] • if ECF >= 3.5, SAP 2009 = 117 – 121 x log10(ECF) • if ECF < 3.5, SAP 2009 = 100 – 13.95 x ECF Note (q) on page 151 of the SAP document indicates deflator will change to keep SAP Rating constant overall but that for individual fuels the Rating will vary. Impact of Changing Methodology on SAP Rating 2005 SAP 1 10 20 30 40 50 60 70 80 90 100 Mains gas 1 9 19 29 39 48 58 67 76 85 94 LPG 10 20 31 41 50 59 68 76 84 92 99 SAP Rating 2009 Oil Electricity 1 9 19 29 39 50 60 70 80 90 100 6 16 26 37 46 56 65 74 82 91 99 Solid mineral 12 21 31 41 50 59 68 77 85 93 100 Biomass 9 18 28 37 47 56 65 74 83 92 100 These changes are relatively small compared with changes in previous methodology changes – i.e. 1995 – 2001 and 2001 – 2006. However these demonstrate the problem of using Economic Cost as a Key Factor in determining the SAP Rating Climatic Issue with 2010 Calculations Calculations have to take account of Climate Variations of Solar Gain for Assessment of Cooling Requirements But NOT Heating (even though heating requirements will vary by up to +/25% from one part of country to another Benefit of Solar Panels does not account for geographic variations in solar radiation even though this information is available for coolign calculations. 30 Effective changes in SAP 1995 rating with specific changes SAP changes by: Change U-values by 10% 2–3 Change window area by 10% 1–2 Change floor area by 10% 4–5 Change heating from mains gas to LPG (little change in energy consumption) - 15 Change heating from condensing gas to inferior oil +5-10 !!!!! Sources: Monahan, J (2002) MSc Dissertation UEA; Turner, C. (2003) BSc Dissertation UEA 31 Improvements for 2010 - Environmental Impact Rating (EI) Calculating the TER • TER2010 = (Ch x FF x EFAh + Cl xEFAl) x (1–0.2)* (1 – 0.25) 25% improvement on 2005 • Where Ch is the energy requirements for space heating and hot water including any used in circulating pumps, Cl is the energy use for lighting FF is a fuel factor EFA is the relevant Emission Factor Adjustment and is a ratio of the emission factors used in the 2009 calculations divided by the equivalent ones in the 2005 calculations. Improvements for 2010 - Environmental Impact Rating (EI) • Carbon Factor (CF) = (CO2 emissions) / (TFA + 45) where TFA is the Total Floor Area • if CF >= 28.3 EI rating = 200 – 95 x log10(CF) • if CF < 28.3 EI rating = 100 – 1.34 x CF where the CO2 emissions are calculated according to the Standard Assessment Procedure • • • • • The EI rating is essentially independent of floor area It will vary slightly depending on actual plan shape A house with zero emissions will have the EI at 100 An EI > 100 if a house is a net exporter of energy. Primary energy requirements are also calculated in a similar way to CO2 emissions. Improvements for 2010 - Environmental Impact Rating (EI) • Letter Rating bands are assigned as follows It applies to both the SAP rating and the Environmental Impact rating (why the SAP Rating??). Rating Band EI Range > 92 Letter Rating A 81 to 91 69 to 80 55 to 68 39 to 54 B C D E 21 to 38 1 to 20 F G How has the performance of a typical house changed over the years? Original Construction • • • • Brick – brick cavity walls Metal windows Solid floor no insulation No loft insulation Bungalow in South West Norwich built in mid 1950s 35 Changing Energy Requirements of House Annual Energy Consumption 30000 25000 kWh 20000 15000 House constructed in mid 1950s First attempt to address overall consumption. SAP introduced. Part L first introduced ~>50% reduction 10000 5000 0 Inter post- 1960s 1976 1985 1990 1994 2002 2006 war war In all years dimensions of house remain same – just insulation standards change As houses have long replacement times, legacy of former regulations will affect ability to reduce carbon emissions in future 36 Changing Energy Requirements of House Annual Energy Consumption 30000 25000 kWh 20000 15000 House constructed in mid 1950s As Existing but with oil boiler Existing house – current standard: gas boiler 10000 5000 0 Inter post- 1960s 1976 1985 1990 1994 2002 2006 gas war war oil SAP 2005 Improvements to existing properties are limited because of in built structural issues – e.g. No floor insulation in example shown. House designed to conform the Target Emission Rate (TER) as specified in Building Regulations 2006 and SAP 2005. 37 Issue of Fuel Choice for carbon reduction Example: Heat house with condensing gas boiler ~ 90% efficient For each unit (kWh) of heat provided. – 1/0.9 = 1.11 units of gas must be supplied – Carbon associated with this ~ 0.21 kg – Direct electric heating ~ 0.52 kg •Heat Pump with Coefficient of Performance of 4 – Carbon emission associated = 0.52/4 = 0.13 – A 38% saving over gas. – Note some people claim higher savings based on incorrect DEFRA carbon factor of 0.43 – Improved performance of heat pumps is possible with under floor heating 38 Changing Carbon Dioxide Emissions CO2 emissions (kg) 9000 8000 7000 6000 5000 Annual CO2 Emissions House constructed in mid 1950s As Existing but with oil boiler Existing house – current standard: gas boiler 4000 3000 2000 1000 0 Inter post- 1960s 1976 1985 1990 1994 2002 2006 gas war war oil SAP 2005 Notice significant difference between using gas and oil boiler. House designed to conform the Target Emission Rate (TER) as specified in Building Regulations 2006 and SAP 2005. 39 Code for Sustainable Homes Responding to the Challenge Recipient of James Watt Gold Medal N.K. Tovey (杜伟贤) M.A, PhD, CEng, MICE, CEnv Н.К.Тови М.А., д-р технических наук Energy Science Director CRed Project 40 HSBC Director of Low Carbon Innovation 40 The Future: Code for Sustainable Homes • Introduced over next few years to improve standards to ultimate “zero carbon house” • But objectives of a low carbon future may be jeopardised if attention is not also paid to sustainable transport associated with new dwellings 16000 14000 Lighting 12000 Refrigeration 10000 Entertainment Miscellaneous 8000 Air/Public Travel 6000 Data for 1 household with 2 cars Washing/Drying 4000 Private Car 2000 Heating 0 1 41 The Code For Sustainable Homes The Code for Sustainable Homes is a set of sustainable design principles covering performance in nine key areas. 1. Energy and CO2 9 key areas of performance…. 2. Water 3. Materials 4. Surface water run-off 5. Waste 6. Pollution 7. Heath and well being 8. Management 9. Ecology http://www2.env.uea.ac.uk/cred/harrisongroup/Code_for_Sustainable_Homes.htm 42 Code for Sustainable Homes: Certificates Code Assessed. This house gets 5* Non Assessed Code is voluntary at present, but a NIL Certificate is needed if assessment is not done 43 Code for Sustainable Homes: Certificates 44 Relative Weighting of different Code categories Total Credits available, Weighting Factors and Points Categor ies of Environmental Impact Category 1: Energy and CO2 Emissions Category 2: Water Category 3: Materials Category 4: Surface Water Run-off Category 5: Waste Category 6: Pollution Category 7: Health and Wellbeing Category 8: Management Category 9: Ecology Total Total credits in each category Weighting factor (% points contribution) Approximate weighted value of each credit 29 36.4% 1.26 6 24 4 7 4 12 9 9 – 9.0% 7.2% 2.2% 6.4% 2.8% 14.0% 10.0% 12.0% 100.0% 1.50 0.30 0.55 0.91 0.70 1.17 1.11 1.33 – 45 Minimum Standards for Energy and Water Energy Water Code Level Standard (% better than ADL1a) Points Awarded Standard (litres / person / day) Points Awarded Other Points Required Level 1 * 10 1.2 120 1.5 33.3 Level 2 ** 18 3.5 120 1.5 43.0 Level 3 *** 25 5.8 105 4.5 46.7 Level 4 **** Level 5 ***** 44 9.4 105 4.5 54.1 100 16.4 80 7.5 60.1 Zero Carbon 17.6 80 7.5 64.9 Level 6 ****** 46 Credits gained for different improvements Dwelling Emission Rate DER (Maximum 15 credits) % Improvement of DER over TER Credits Mandatory Levels ≥10% 1 Level 1 ≥14% 2 ≥18% 3 ≥22% 4 ≥25% 5 ≥31% 6 ≥37% 7 ≥44% 8 ≥52% 9 ≥60% 10 ≥69% 11 ≥79% 12 ≥89% 13 ≥100% 14 Level 5 True Zero Carbon 15 Level 6 Level 2 Level 3 Level 4 47 Roadmap to 2016 Date 2013 2016 25% 44% Zero Carbon Water Efficiency Standard 105l/p/day 105l/p/day 80l/p/day Equivalent energy/carbon standard in the Code Code Level 3 Code Level 4 Code Level 6 Energy/carbon improvement as compared to ADL1a (Building Regulations 2006) 2010 Major progressive tightening of the minimum energy performance standards in building regulations - by • 25 % in 2010, • 44 % in 2013 – • up to the zero carbon target in 2016. 48 What Does Zero Carbon Mean? • Where the net carbon emissions from all energy used in the dwelling are zero or better. • Where the heat Loss Parameter is 0.08 W/m2K – an indicator of exemplar building fabric • Off site energy must be private wire –connected to the site • Using a “Green” Tariff cannot be used to reduce carbon • Nor can purchase of offsets 49 Implications of Code on Carbon Dioxide Emissions 8000 CO2 emissions (kg) 7000 House constructed in mid 1950s 6000 5000 4000 3000 2000 1000 -10% -18% -25% -44% 0 As current SAP Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 constructed reference Code 5: Zero Carbon House for Heating/Hot Water and Lighting Code 6: Zero Carbon House overall but in reality is this achievable? 50 Responding to the Challenge: Improvements on the SAP 2005 standards as required by the different code levels can be met by: • Improved Fabric performance • Lower U-values • Technical Solutions • • • • • • Solar Thermal Solar Photo-voltaic Heat Pumps Biomass Micro- CHP Low Energy Lighting (SAP 2005 already specifies 30%) • Energy Service Companies may offer a solution for financing • Issues of Carbon Trading 51 Responding to the Challenge: Technical Solutions What can be achieved through • Improved Fabric / standard appliance Performance • Using SAP 2005 standard reference • Explore different combinations of following improvements. Item SAP Improved Improved reference Value 1 Value 2 Windows Walls U-value = 2 U-value = 0.35 Floor Roof U-value = 0.25 U-value = 0.16 Boiler efficiency 78% U-value = 1.4 U-value = 0.25 83% default U-value = 0.1 90% SEDBUK 52 SEDBUK DataBase (Seasonal Efficiency of Domestic Boilers in UK) WEB PAGE: www.sedbuk.com/index.htm 53 The Future: Code for Sustainable Homes 3000 CO2 emissions (kg) Improvements in Insulation and boiler performance Annual CO2 Emissions 2500 Code 1 2000 Code 2 1500 1000 500 0 A B C D E Option A SAP Reference B Boiler η = 83% (default) C Boiler η = 90% (SEDBUK) D η = 90%: Walls: U = 0.25 E η = 90%: Walls: U = 0.10 F η = 90%: Windows: U = 1.4 G C+D+F H C+E+F F G H Option H nearly makes code 3 SAP 2005 standard Walls: 0.35 Wm-2oC-1 Windows: 2.0 Wm-2oC-1 Boiler η 78% CO2 Emissions (kg) Reduction 2504 0 2377 5% 2229 11% 2150 14% 2034 19% 2112 16% 2033 19% 1919 23% Credits 0 0 1 2 3 2 3 4 54 Responding to the Challenge: Technical Solutions What can be achieved through • Use of Domestic Solar Energy • Different solar thermal collector areas • Different combinations of storage tank • Use of PV • Use of combinations of solar thermal with PV 55 Responding to the Challenge: Technical Solutions Solar Thermal Energy Basic System relying solely on solar energy 56 Responding to the Challenge: Technical Solutions Solar Thermal Energy indirect solar cylinder Solar tank with combi boiler 57 Responding to the Challenge: Technical Solutions Solar Thermal Energy Solar Pump Normal hot water circuit Solar Circuit Dual circuit solar cylinder 58 Responding to the Challenge: Technical Solutions Solar Thermal Energy Solar Collectors installed 27th January 2004 Annual Solar Gain 910 kWh 59 Responding to the Challenge: Technical Solutions Solar Thermal Energy Solar Gain (kWh/day) 9 December February April June August October December 7 6 5 4 3 2 Solar Hot Water performance 6 1 5 0 kWh per day Solar Gain (kWh) 8 January March May July September November 4 2006-07 2007-08 10 20 30 9 19 29 8 18 28 10 20 30 9 19 29 9 19 29 8 18 28 8 18 28 7 17 27 6 16 26 6 16 26 5 15 25 5 15 1 11 21 31 10 3 2 Day of Month 1 0 60 The Future: Code for Sustainable Homes Annual CO2 Emissions 3000 CO2 emissions (kg) Improvements using solar thermal energy. How far can things be improved? 2500 2000 Code 1 1500 Code 2 1000 500 0 A A B C D E F G B C D E F G SAP Reference Boiler η = 90% (SEDBUK) η = 90%: Solar Thermal – 2 panels dual cylinder η = 90%: Solar Thermal – 2 panels separate cylinder η = 90%: Solar Thermal – 3 panels separate cylinder η = 90%: Solar Thermal – 4 panels separate cylinder η = 90%: Solar Thermal – 5 panels separate cylinder Note: little extra benefit after 3 panels, but does depend on size of house CO2 (kg) Reduction Credits 2504 0 0 2229 11% 1 2061 18% 3 2027 19% 3 1991 20% 3 1969 21% 3 1953 22% 4 61 S Responding to the Challenge: Technical Solutions Solar PhotoVoltaic 62 The Future: Code for Sustainable Homes 3000 CO2 emissions (kg) Improvements using solar Photovoltaic Annual CO2 Emissions 2500 Code 1 2000 Code 2 1500 Code 3 1000 Note: 2 panels of solar thermal have same benefit as 5 sqm of PV 500 0 A A B C D E F B C D E F CO2 (kg) Reduction Credits SAP Reference 2504 0 0 Boiler η = 90% (SEDBUK) 2229 11% 1 η = 90%: Solar PV 5 sqm 2052 18% 3 η = 90%: Solar PV 10 sqm 1874 25% 5 η = 90%: Solar PV 5 sqm + 2 panel solar thermal 1883 25% 5 η = 90%: Solar PV 7.4 sqm + 2 panel solar thermal 1798 28% 5 63 Responding to the Challenge: Technical Solutions What can be achieved through • Use of Heat Pumps • Biomass Boilers • Will Code 5 be achievable? 64 Responding to the Challenge: Technical Solutions The Heat Pump Any low grade source of heat may be used • Coils buried in garden 1 – 1.5 m deep • Bore holes • Lakes/Rivers are ideal • Air can be used but is not as good • Best performance is achieved if the temperature source between outside source and inside sink is as small as possible. Under floor heating should always be considered when installing heat pumps in for new build houses – operating temperature is much lower than radiators. Attention must be paid to provision of hot water - performance degrades when heating hot water to 55 – 60oC Consider boost using off peak electricity, or occasional “Hot Days” 65 The Future: Code for Sustainable Homes 3000 CO2 emissions (kg) Improvements using Heat Pumps Annual CO2 Emissions 2500 Code 3 2000 Code 1 Code 4 1500 Code 2 1000 Code 3 500 0 A A B C D E F G H B C D E F G H CO2 (kg) Reduction Credits SAP Reference 2504 0 0 Boiler η = 90% (SEDBUK) 2229 11% 1 Ground to Water Heat Pump (Radiators) 1661 34% 6 Air to Water Heat Pump (Radiators) 1962 22% 4 Ground to Air Heat Pump 1606 36% 6 Air to Air Heat Pump 1907 24% 4 Ground to Water Heat Pump (Under floor) 1553 38% 7 Air to Water Heat Pump (Under floor) 1830 27% 5 66 The Future: Code for Sustainable Homes 3000 CO2 emissions (kg) Various Combinations Annual CO2 Emissions 2500 Code 1 2000 Code 2 Code 4 1500 Code 3 1000 Code 4 500 0 A A B C D E F G H B C D E F G SAP Reference Boiler η = 90% (SEDBUK) Water to Air Heat Pump (under floor) As C with improved insulation As D with 100% Low Energy Lighting As E with Solar Thermal As E with 5 m2 Solar PV As E with 10 m2 Solar PV H CO2 (kg) 2504 2229 1553 1327 1219 1124 1042 864 Reduction 0% 11% 38% 47% 51% 55% 58% 65% Credits 0 1 7 8 8 9 9 10 67 The Future: Code for Sustainable Buildings Annual CO2 Emissions CO2 emissions (kg) 3000 Improvements using Biomass options 2500 Code 1 2000 Code 2 Code 4 1500 Code 3 1000 Code 4 500 Note: Biomass with solar thermal are incompatible options 0 A A B C D E F B C D E SAP Reference Boiler η = 90% (SEDBUK) Biomass Boiler Biomass Boiler with Solar Thermal Biomass Boiler with 5m Photovoltaic Biomass Boiler with 10m Photovoltaic Biomass Boiler + 10m PV + improved G insulation + 100% Low Energy lighting F G CO2 (kg) 2504 2229 673 670 496 318 147 Reduction Credits 0% 0 11% 1 73% 11 73% 11 80% 12 87% 12 94% 13 68 Ways to Respond to the Challenge: Technical Solutions • Micro CHP plant for homes are being trialled. • Replace the normal boiler • But there is a problem in summer as there is limited demand for heat – electrical generation will be limited. • Backup generation is still needed unless integrated with solar photovoltaic? • In community schemes explore opportunity for multiple unit provision of hot water in summer, but only single unit in winter. Micro CHP 69 Responding to the Challenge: • • • • • • • • How can low carbon homes be provided at an affordable cost? Energy Service Companies (ESCos) Home costs same initial cost as traditional home Any additional costs for providing renewable energy, better insulation/controls are financed by ESCo Client pays ESCo for energy used at rate they would have done had the house been built to basic 2005 standards ESCo pays utility company at actual energy cost (because energy consumption is less) Difference in payments services ESCo investment When extra capital cost is paid off • Client sees reduced energy bills • ESCO has made its money • Developer has not had to charge any more for property • The Environment wins 70 The Future: Code for Sustainable Buildings: Conclusions Significant Improvements can be achieved through • Better Insulation Standards • Heat Pumps • Biomass Boilers - but is fuel source sustainable? • Solar Thermal • Solar PV But avoid incompatible options • Too large a Solar thermal Array • Biomass with solar thermal • CHP with Solar Thermal Will it be realistically possible to achieve code level 5? 71 The Behavioural Dimension: Are Technical Measures Enough? • Analysis of 114 houses in Norwich using Gas Heating • Predicted consumption from SAP was within 1.9% of actual energy consumption for Space Heating/ Hot Water and Gas Cooking. • Plot shows variation from predicted for each house • Little variation with household size • Consumption varies by up to a factor of 9 for any given household size. • Education/Awareness is important. provide INFORMATION PACKS Are Technical Measures alone going to be sufficient to reduce carbon emissions? 72 The Behavioural Dimension Electricity Consumption Average kWh/month 1200 1000 800 600 400 200 0 0 1 2 4 3 No. people 5 6 7 • Household size has little impact on electricity consumption. • Consumption varies by up to a factor of 9 for any given household size. • Allowing for Income still shows a range of 6 or more. • Education/Awareness is important. 73 CO2/ year 0 - 4 tonnes Variations in Carbon Emissions in existing houses Analysis: courtesy of Karla Alcantar 4 - 6 tonnes 6 - 8 tonnes 8 - 10 tonnes > 10 tonnes 74 The Future: Code for Sustainable Buildings All non-dwellings must display a certificate such as shown • >10000m2 from 6th April 2008 • > 2500m2 from 1st July 2008 • All non-residential buildings > 1000m2 from 1st October 2008. • Separate assessments for airconditioning plant will be phased in from 1st January 2009 Elizabeth Fry Building: Penalised because it does not have thermostatically controlled radiator values . There are no radiators!!!!!! Does not get credit for triple/ quadruple glazing – analysis system cannot cope!!!!! 75 Indian Building Code • WEBSITE: http://www.hareda.gov.in/ECBC.pdf • Also available at UEA at – http://www2.env.uea.ac.uk/gmmc/energy/NBSM14x/Indian_DRAFTECBC27MARCH2006.pdf Code was formulated following Energy Conservation Act of 2001 According to Saurabh Kumar, Secretary of Ministry of Power (18th April 2007), Code was to be trialled in demonstration areas from July 2007 An initial appraisal suggests that code tends to follow the equivalent of an Elemental Approach, but with differences 76 Indian Building Code Unlike UK, elemental standards vary from region to region according to climate. UK has 18 zones each with different Degree-Days, but elemental standards are same [Technically Scotland could modify standards in Scotland] Two identical houses in UK, one in South West, the other in North East Scotland, the energy consumption for space heating in latter would be 47% higher than former Is it sensible to have different standards in different climate regimes? 77 Indian Building Code Example of U-values for walls Based on Table 4.3.2 of ECBC 2006. Note: The U-value in the UK is 0.35 W/m2 oC-1 Climate Zone Hospitals, Hotels, Call Centers (24-Hour) Maximum U-factor (W/m2 oC-1) 0.352 Other Building Types (Daytime) Maximum U-factor (W/m2 oC-1) 0.352 Hot and Dry 0.369 0.352 Warm and Humid 0.352 0.352 Moderate 0.431 0.397 Cold 0.369 0.352 Composite 78 Chinese Building Code China is adopting a similar approach to that suggested for India 79 Chinese Building Code U-Values (W m-2 oC -1) Country/District Beijing (2003) Walls Windows Roof 0.82 – 1.16 3.5 0.6 – 0.8 Beijing (current) 0.6 Shanghai (current) 1.0 Germany 0.5 1.5 0.22 Sweden 0.17 2.5 0.12 UK (2005 Regulations) 0.35 2.0 0.16 Canada 0.36 2.86 0.23 – 0.4 Hokaido, Japan 0.42 2.33 0.23 Zones in USA similar to Beijing 0.32 – 0.45 2.04 0.19 Zones in Russia similar to Beijing 0.44 – 0.77 2.75 0.33 – 0.57 80 81 A Pathway to a Low Carbon Future 未来的低碳之路 1. 不要浪费能源 Awareness: Information Packs 2. 使用效率高的设备 Technical Solutions to conserve energy Low energy lighting/better insulation etc 3. 使用可再生能源 Renewable Energy 4. 抵消碳排放 Offsetting 82