Programming Relay Control Basics Offsets and Differentials, 2 Setpoints "COOLING" or "HIGH ALARM" Differential Output turns ON Output turns OFF Offset Cool Setpoint Offset Heat Setpoint Differential Output turns OFF Output turns ON "HEATING" or "LOW ALARM" Offsets and Differentials, 1 Setpoint "COOLING" or "HIGH ALARM" Differential Output turns ON Output turns OFF Offset Deadband Setpoint Deadband Offset Differential Output turns OFF Output turns ON "HEATING" or "LOW ALARM" Proportional ProgrammingControl Basics Direct Acting - Output 12mA @ Setpoint Direct Acting Input Setpoint + 1/ 2 P } Setpoint Setpoint - 1/ 2 P 4m A 12m A 20m A Output P 12m A 20m A 4m A Reverse Acting - Output 12mA @ Setpoint Output Reverse Acting Input Setpoint + 1/ 2 P } Setpoint Setpoint - 1/ 2 P 4m A 12m A 20m A Output P Direct Acting - Output 4 or 20mA @ Setpoint Cooling } } P PSetpoint + 1/ 2P nt Setpoint 12m 4m A 4m A 20m 12mAA Output ut Input P Setpoint + P PSetpoint + 1/ 2 P P Direct Acting Setpoint + P Setpoint Input Setpoint Setpoint - P 20m A Setpoint - P 12m 4m A 4m A 20m 12mAA Output Output Input P } Setpoint - 1/ 2P Setpoint - 1/ 2P P se Acting P Input Direct Acting Input se Acting ut Heating Setpoint P 20m A Ou Input Setpoint Setpoint - 1/ 2 P Setpoint - 1/ 2 P P P Setpoint + P } } Setpoint Setpoint } 12m 4m A 20m 12mAA Input P Setpoint + P } } 12m 4m A 20m 12mAA Output 20m A Output 12m 4m A 4m A Heating Output P Setpoint 4m A Setpoint - P Input PSetpoint + 1/ 2 P int Setpoint - P 20m A Output Cooling ut Setpoint - 1/ 2P Setpoint - 1/ 2P P Reverse Acting 4m A Direct Acti Setpoint Reverse Acting int Direct Acti Reverse Acting - POutput 4 or 20mA @ SetpointP P 2PSetpoint + 1/ 2P Setpoint 20m 12mAA Output Ou Input Setpoint } Setpoint - 1/ 2 P Setpoint - 1/ 2 P Setpoint - P 20m A Setpoint - P 4m A 12m 4m A 20m 12mAA Output P 20m A Ou Controller Programming 2100 Series Controller Programming • Menu-by-Menu Examples – Follow Along Onscreen – Some Slides Printed in Handout – Product Manuals in Reference Section • Sub-Systems in Ubiquity Manual Sect. 12 • www.tcsbasys.com • www.ubiquitysystems.net Programming Basics • Factory Defaults Preprogrammed • MUST Change Address – Default is 000 2100 Default is 10X (SL2108 => 108) • NO LCD on Device – Must Use: – Revelation Professional 2.4 – Ubiquity on Standalone QD2040 – Ubiquity on Internet – Ubiquity Mobile **available for download** Programming Options PC Based Software -- Revelation Professional • Menu Driven Programming • Use for Network Setup & Testing, Commissioning, & Load Balancing • “Read” Before Making Changes • “Write” Before Going to NEXT Menu • “Write” vs. “Write Half / Write Page” • “Load All” & “Save All” Options *** NOT SUPPORTED AS OF JAN 2009 *** PC Based Software -- Insight Similar to Revelation Professional… • Tab Driven Interface • Uses Same Datasheets as Ubiquity • Use for Network Setup & Testing, Commissioning, & Load Balancing • Shows Current Values (no “read” required) • “Write Page” Before Going to New Tab *** NEW SOLUTION AS OF JAN 2009 *** Internet Style Software – Ubiquity • • • • • • Similar to Revelation Professional Single Page for all Programming Info Shows Current Values (no “read”) Writes all Values on “Submit” “Read Controller” Option if Needed Same for Internet Based Site and Standalone QD2040 QD2040 Multi-Function Site Comm. Center • • • • • • • Stand-Alone/Dial-In, Dial-Out, or Ethernet Configuring the Controller Network Controller Addressing Setup Web Page Veris Meter (ModBus) Support XML Support Several Models Available – REG & –MAX Where to Get Help or Answers • • • • • • Instructions Sent with Product TCS Basys Controls Catalog Ubiquity Manual Training & Reference Manual www.tcsbasys.com www.ubiquitysystems.net • Call TCS Directly – 800-288-9383 2100 Series Controllers SL2105 - Five Channel Lighting Module • Independent, 365-Day Scheduling for ALL 5 Channels • Digital & Analog Light Sensor Inputs • Analog Current or kW Input • 5 Relay Outputs • 2 “Demand Limit” Outputs • Astronomical Clock SL2108 - Eight Channel Lighting Module • Independent, 365-Day Scheduling for ALL 8 Channels • Digital & Analog Light Sensor Inputs • Analog Current or kW Input • 8 Relay Outputs • 2 “Demand Limit” Outputs • Astronomical Clock SL2105 & SL2108 Applications • • • • • • Indoor or Security Lighting Outdoor or Landscape Lights Parking Lot Lights and Signs Daylight Harvesting Lighting Load Shedding Power Monitoring SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller Screenshots or Live View… Skip to Next Controller… SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SL2108 – eight channel lighting controller SZ2141 - Refrigeration Controller • Control 1 Cooler with Defrost & 2 Freezers with Defrost and Fan • 6 RTD Inputs (-40 to 160°F) • 5 Analog Inputs (4 to 20mA) • 6 Digital Inputs • 8 Relay Control Outputs • 1 Relay Alarm Output SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller Screenshots or Live View… Skip to Next Controller… SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2141 - Refrigeration Controller SZ2144 – Large Refrigeration Monitor • 3 RTD (-40 to 160°F) or Thermistor (-20 to 120°F) Inputs • • • • • 3 RTD Inputs (20 to 220°F) 2 Analog Inputs (4 to 20mA) 3 Analog Inputs (0 to 5V) 8 Digital Inputs 1 Relay Output (local alarm) SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor Screenshots or Live View… Skip to Next Controller… SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2144 – Large Refrigeration Monitor SZ2165 - Boiler Controller • • • • • • • Control 4 Boilers with Chiller Support Automatic Rotation of Boilers & Pumps 365-Day Scheduling 6 RTD & 5 Digital Inputs 1 Analog Input (4 to 20mA) 2 Analog Outputs (4 to 20mA) 9 Relay Outputs SZ2165 Application SZ2165 - Boiler Controller One or Two Boilers with Reset SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller Screenshots or Live View… Skip to Next Controller… SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2165 - Boiler Controller SZ2166 - Chiller Controller • • • • • • • Stage 4 Chillers with Boiler Support Automatic Rotation of Chillers & Pumps 365-Day Scheduling 6 RTD Inputs 5 Digital Inputs 2 Analog Outputs (4 to 20mA) 9 Relay Outputs SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller Screenshots or Live View… Skip to Next Controller… SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2166 - Chiller Controller SZ2161 - Heat Pump Water Loop Controller • • • • • • • Control 4 Boilers & a Water Tower Automatic Rotation of Boilers & Pumps 365-Day Scheduling 6 RTD Inputs 5 Digital Inputs 12 Relay Outputs 2 Analog Outputs (4 to 20mA) SZ2161 Application Cooling Tower SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller Screenshots or Live View… Skip to Next Controller… SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller SZ2161 - Heat Pump Water Loop Controller HVAC Sub-Systems – Loop Control Setup Guide 1. Click “Create Loop System” button 2. Select sub-system definition (Loop Controls) 3. Enter a descriptive name for sub-system 4. Select master & secondary master controllers from drop-downs (only appropriate, available controllers will be shown) 5. Select fallback flow switch & related control point from drop-downs 6. Select the desired master controller schedule from drop-down 7. Click the “Submit” button HVAC Sub-Systems – Loop Control HVAC Sub-Systems – Loop Control HVAC Sub-Systems – Loop Control SZ2181 - Air Handling Unit Controller • • • • • • • Enthalpy Based Economizer Option 365-Day Scheduling 6 RTD & 5 Digital Inputs 4 Analog Inputs (4 to 20mA) 3 Analog Outputs (4 to 20mA) 2 Heat & 2 Cool Stages 2 Selectable Heat and/or Cool Stages SZ2182 – Advanced AHU Controller • • • • • • • Enthalpy Based Economizer Option 365-Day Scheduling 6 RTD & 5 Digital Inputs 4 Analog Inputs (4 to 20mA) 4 Analog Outputs (4 to 20mA) 2 Heat & 2 Cool Stages 2 Selectable Heat and/or Cool Stages SZ2182 Applications • • • • Dehumidification Face & Bypass Damper Control Static Pressure Control Heat Pump with Economizer Control SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller Screenshots or Live View… SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller SZ2181 - Air Handling Unit Controller HVAC Sub-Systems – VAV System Setup Guide 1. Click “Create VAV System” button 2. Click “Add Sub-system” button 3. Click “Controllers” to expand table of options 4. Click “Controller Selection” to expand table 5. Select controllers to include in sub-system (only allowable controllers are selectable in this list) 6. 7. 8. 9. Click “Controller Detail” to expand table Select units for Discharge Air Temp. Sharing Click “System Parameters” to expand table Enter a descriptive name for sub-system HVAC Sub-Systems – VAV System Setup Guide 10. Select master/main controller from dropdown (only appropriate, available controllers will be shown) 11. Set other “System Parameter” options: 1. 2. 3. 4. 5. 6. 7. 8. Occupied Mode Operation Unoccupied Mode Operation VAV System Type (pressure independent for this example) Duct Static Pressure Controller Backup Discharge Air Sensor Warm Up Mode Operation Morning Warm Up Termination Time/Temp & Options Secondary Boiler & Chiller Master Controllers 12. Click “Submit” button HVAC Sub-Systems – VAV System HVAC Sub-Systems – VAV System HVAC Sub-Systems – CZS System Setup Guide 1. Click “Create Superzone System” button 2. Click “Add Sub-system” button 3. Click “Controllers” to expand table of options 4. Click “Controller Selection” to expand table 5. Select controllers to include in sub-system (only allowable controllers are selectable in this list) 6. Click “Controller Detail” to expand table 7. Select units for Discharge Air Temp Sharing & for Voting functions 8. Click “System Parameters” to expand table HVAC Sub-Systems – CZS System Setup Guide 9. Enter a descriptive name for sub-system 10. Select master/main controller from dropdown (only appropriate, available controllers will be shown) 11. Set other “System Parameter” options: 1. 2. 3. 4. 5. 6. 7. 8. Occupied Mode Operation Cool Priority Mode Operation Heat Priority Mode Operation Voting Mode Operation Unoccupied Mode Operation Backup Discharge Air Sensor Bypass Damper Controller Minimum Demand HVAC Sub-Systems – CZS System Setup Guide 11. Set other “System Parameter” options: (cont’d) 9. Tie Break Controller 10.Priority Zone Controller 11.Majority Maximum Run Time 12.Minority Maximum Run Time 13.Enable Hot Deck/Cold Deck 14.Secondary Boiler and Chiller Master Controllers 15.Hot Deck/Cold Deck Unoccupied Options 12. Click “Demand Proportioning” to expand table & set desired options 13. Click “Submit” button HVAC Sub-Systems – Superzone™ System HVAC Sub-Systems – Superzone™ System HVAC Sub-Systems – Superzone™ System Where to Get Help or Answers • • • • • • Instructions Sent with Product TCS Basys Controls Catalog Ubiquity Manual Training & Reference Manual www.tcsbasys.com www.ubiquitysystems.net • Call TCS Directly – 800-288-9383 Sales and Marketing