Daikin Altherma™ Troubling Shooting Outlet thermistor failure • • • • • Code: 81 Part: Outlet water thermistor Location: Activation failure: Possible action to resolve the problem: – Check connector – Check resitance value – Replace thermistor R3T 2 Freeze up problem • • • • • Code: 89 Part: Heat exchanger freez-up Activation failure: Outlet water temp. too low Location: Possible action to resolve the problem: – Check water flow in the system. Minimum water flow system 9liter / min. R3T 3 Flow failure • • • • • Code: 7H Part: Flow failure Location: Activation failure: Flow switch open during operation (no signal) Possible action to resolve the problem: – Check water flow in the system. (Minimum water flow system 20liter / min.) – Check water pressure in the installation. (Minimum 0.3 bar) – Check shutt OFF valves – Is water system purged – Check pressure drop and speed of the waterpump – Check pump operation R3T 5 Outlet water temperture too high • • • • • Code: 8H Part: Outlet water thermistor Location: Outlet back up heater Activation failure: If outlet water > 65°C Possible action to resolve the problem: – Check if contactor(s) back up heater is not welded – Check if thermistor is not damaged – Check if correct resistor value of thermistor • Procedure :Refer to service manual R3T 6 Indoor PCB failure • • • • • Code: A1 Part: Indoor PCB Location: Switchbox Activation failure: Possible action to resolve the problem: – Replace PCB 7 Insufficient cooling or heating • • • • Code: A5 Part: Liquid sensor hydrobox Location: Possible action to resolve the problem: – – – – – – – Check water flow in the system. (Minimum water flow system 9liter / min.) Check water pressure in the installation. (Minimum 0.3 bar) Check shutt OFF valves Is water system purged Check pressure drop and speed of the waterpump Check refrigerant charge Check thermistor • Procedure: refer to service manual R3T 8 Booster heater thermal protector • Code: AA • Part: Thermal protector booster heater or back up heater * • Location: • Possible action to resolve the problem: – Check if thermal protection is not damaged. – Check contactor of the electric BUH / BSH 9 Stucked flow switch • • • • • Code: CO Part: Flow switch failure Activation failure: Flow swith remains closed when pump is not operating Location: Possible action to resolve the problem: – Check for dirt in flow switch – Replace part is required R3T 10 Heat exchanger thermistor failure • • • • • Code: C4 Part: Liquid sensor Activation failure: Sensor broken or out of range Location: Possible action to resolve the problem: – Check connector – Check resistance of the sensor – Procedure: refer to servicemanual for procedure – If damaged replace part R3T 11 Outdoor PCB failure • • • • • Code: E1 Part: Outdoor PCB failure Activation failure: Location: Possible action to resolve the problem: – Out of control of CPU • Voltage drop • Power loss • Noise on power supply – Defect outdoor PCB 12 Overload activation of compressor • • • • • Code: E5 Part: Overload protector compressor Activation failure: Failure If overload protector ( >130°C) is activated twice in one hour Location: Outdoor unit Possible action to resolve the problem: – – – – Refrigerant shortage. Malfunction four way valve. Outdoor PCB failure. Electronic expansion valve defective. 13 Compressor start up failure • • • • • Code: E6 Part: Compressor locked Activation failure: : Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes Location: Outdoor unit Possible action to resolve the problem: – Replace outdoor PCB – Replace compressor 14 Fan motor failure • • • • • Code: E7 Part: Outdoor fan motor Activation failure: Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes Location: Outdoor unit Possible action to resolve the problem: – Fan motor breakdown – Bad contact between PCB and fan motor – Blockage of the fan blades 15 Sanitary water too high • Code: EC • Part: Sanitary tank temperature • Activation failure: If temperature sanitary water > 89°C • Location: Sensor inside sanitary tank • Possible action to resolve the problem: – Check position of sensor in socket – Check if contactor(s) booster heater is not welded – Check if thermistor is not damaged – Check if correct resistor value of thermistor 18 Discharge temperature too high • • • • • Code: F3 Part: Discharge sensor Activation failure: Failure if discharge temperature > 120°C for 6 times Location: Sensor located on the discharge pipe of compressor Possible action to resolve the problem: – – – – Refrigerant shortage. Malfunction four way valve. Defective discharge sensor. Defective EEV driver. 19 Voltage and current sensor failure • • • • Code: H0 Part: Voltage / Current sensor Activation failure: No measurement of current during compressor operation. Possible action to resolve the problem: – – – – Reactor disconnected Compressor disconnection Outdoor PCB failure Compressor defective 22 Outdoor ambient thermistor • • • • • Code: H9 Part: Thermistor Location Activation failure: Resistance value out of range Possible action to resolve the problem: – – – – Check connector Check resistance value Replace thermistor. Outdoor PCB 25 Discharge pipe thermistor • • • • • Code: J3 Part: Discharge pipe thermistor Location Activation failure: Resistance value out of range Possible action to resolve the problem: – – – – Check connector Check resistance value Replace thermistor. Outdoor PCB 26 Outdoor heat exchanger • • • • • Code: J6 Part: Thermistor Location Activation failure: Resistance value out of range Possible action to resolve the problem: – – – – Check connector Check resistance value Replace thermistor. Outdoor PCB 27 Electrical box temperature rise • • • • • Code: L3 Part: Radiation fin thermistor Location: Outdoor PCB Activation failure: failure if temperature > 85°C and compressor OFF Possible action to resolve the problem: – – – – Defective outdoor fan Defective Fin thermistor Defective Outdoor PCB Heat conductive paste 29 Radiation fin temperature rise • • • • • Code: L4 Part: Radiation fin temperature rise Location: Outdoor PCB Activation failure: failure if temperature > 105°C and compressor ON for 4 times Possible action to resolve the problem: – – – – Defective outdoor fan Defective Fin thermistor Defective Outdoor PCB Heat conductive paste 30 Thank you for your attention! 36