LS/LT GSM/GPRS Data Logger range V3.10 Constraints and demands of District Metering Little water networks installations Man-hole/chambers of water networks Strom overflow sewers Installations without mains power… Demanding environment Flooded or humid plants Sites with no mains power Isolated or hard to reach plants Dedicated Applications Leak detection through sectorisation Detection of Storm water overflow. Key Customer Meter Remote reading. Remote control of secondary plants. #2 LS/LT GSM/GPRS Data Logger range V3.10 Sofrel Solution : LS-LT Data Loggers range Hardware for a tough environment « Field » tools High performance GSM Antenna GSM Reception level indicator Reenforced watertightness Easy access, by end-user, to SIM and battery Battery Life-time : up to 10 days Commissioning through Bluetooth Inputs : Pulse, AI, DI Calculations : flow, thresholds, daily reports. Time-stamping in Data Logger Alarm SMS Daily historical values collections Data viewing through WEB server On-site data-handling and GSM/GPRS Communications #3 LS/LT GSM/GPRS Data Logger range V3.10 Available data Physical data 1 to 4 pulse or signalisation inputs Pulse : Pulse meter, standard or « two ways» Signalisation : Normaly open or normaly closed. Appearance and disapearance settable timer. 2 measurements 4-20 mA inputs (option) SOFREL sensor very low consumption (8V) Standard Sensor, powered by LS/LT (12V) m3 / h Calculated data Meter average flow-rate. Threshold on average flow-rates Two time-windows per day Threshold Value and logic settable for each time-window Low threshold #4 LS/LT GSM/GPRS Data Logger range V3.10 Data Handling Daily reports Metering Index, Volume, min & max Flow-rate Night flow in a settable time-window. M³/H m³/ h Signalisation (DI, threshold) 24 h Number of activations. Duration of active status. Historical values Periodic (1, 3, 5, 10, 15, 30 and 60 minutes) Index and average flow-rate. Measurments Signalisation status changes. Daily reports Memory extended to 50 000 records #5 LS/LT GSM/GPRS Data Logger range V3.10 On-site data handling With Softools through Bluetooth connection « Information » screen Real-time values of all information Selection of 10 information for Curves Excel Transfert Curves Meters , flow, measurments, signalisations, thresholds reports, battery,… Time-frame : Day / Week / Month Y scale adjutment X Zoom Excel Transfer #6 LS/LT GSM/GPRS Data Logger range V3.10 Communication with SCADA GPRS or SMS (LS) communication 1 or 2 Central Stations Automatic clock up-date Transfered data : Historical values – daily reports Diagnostic : power, reception level... Multiple choices of data transmission Scheduled transmission : 1 to 6 daily calls. Periodic transmission (every 15 minutes to 8 hours (GPRS mode)) Transmition when alarm appears (threshold, DI) Network Diagnostic after on-site visit. Periodic transmission for a limited period of time (Max 1 day) GPRS Communication SCADA or WEB server with static IP @ « Low –cost » communication Optimized volume of data - No roaming #7 LS/LT GSM/GPRS Data Logger range V3.10 Alerts Alerts to SCADA Central Station Can be activated on all the Dis and Thresholds On appearance and disappearance Send available data Current data status Historical values Cuurent data status Archiving Alert to mobile Can be activated on DIs or Thresholds On appearance A « signaling » SMS is sent immediately. Paris Sector 12 Open manhole cover Configurable text message #8 LS/LT GSM/GPRS Data Logger range V3.10 Hardware features High-performance built-in antenna Specifically designed to be used in man-holes Optional watertight External Antenna. IP68 watertightness Case with double O-ring seal Uniform distribution of sealing pressure Military-type « inputs » connector Battery life Ultra low-power technology Standard/high capacity battery : Standard battery : Up to 5 years High-capacity battery : Up to 10 years Power consumption Measurement Transmitted to the SCADA Central Station #9 LS/LT GSM/GPRS Data Logger range V3.10 Hardware features Wall mounting Easy to mount and remove User access To insert SIM card and change battery Bluetooth port Local wireless link 4 control LEDs Immediat visual inspection V J B Local wake-up with key Activation of LED, Bluetooth, SMS # 10 LS/LT GSM/GPRS Data Logger range V3.10 Configuration through Softools Application wizard For LS application Only one configuration screen Direct access to all functions Full view of settings Remote transfer of configuration Read/Write via Bluetooth LS/LT ID Card Geographical coordinates Serial number – Versions – Options.. # 11 LS/LT GSM/GPRS Data Logger range V3.10 Diagnostic tools 4 complementary diagnostic tools Control LED Softools commands via Bluetooth link SMS commands from a mobile # 12 LS/LT GSM/GPRS Data Logger range V3.10 LED Diagnostic Direct and Integrated diagnostics Data Logger, SIM card, GSM Network status GSM signal strength Assistance to installation Assistance to maintenance GSM network logon & SIM card OK V Data Logger activated GSM signal strength J B Wake-up # 13 LS/LT GSM/GPRS Data Logger range V3.10 SMS & Bluetooth Diagnostic Communication tests Best-operator selection Signal strength Triggering Send SMS to mobile Transmitted to the SCADA Central Station Deferred transmission Test in real conditions man-hole cover closed Input wiring test Meter indexing Energy reading Remaining battery life # 14 LS/LT GSM/GPRS Data Logger range V3.10 SOFREL LS/LT range A comprehensive range Applications SOFREL LS for Water Netwok District Metering SOFREL LT for Storm Overflow Sewers Equipment SOFREL LS/LT42 Core part of the range 2 optional AI SOFREL LS/LT42-EA Version dedicated to tough GSM signal conditions External antenna SOFREL LS10 Simplified version 1 Pulse # 15 LS/LT GSM/GPRS Data Logger range V3.10 Sofrel LS « Leak detection through District Metering » application « Volume and flow » function Volume counting Reports Average flow-rate. Night-flow in a settable time-window. Archiving Mecanical meter –Electromagnetic flow-meter. Periodically : index and flow Daily : index, volume, min/max flow, night-flow. Daily transmission to Central Station Additional Information Handling of two-way meters. Pressure measurement Signalisation : man-hole cover opening, flow-meter default… Alerts on flow and measurement thresholds # 16 LS/LT GSM/GPRS Data Logger range V3.10 Sofrel LT « Storm overflow sewer » application « Overflow » function Connection to an « overflow sensor » Level measurement Calculations Number and duration of overflows Archiving Ultrasonic 4-20 mA sensor. Overflow time-stamping Number and duration of daily overflows Variable frequency depending on overflow status (Ultrasnic sensor) Daily transmission to Central Station Additional information Signalisation : sensor default Alerts on level threshold # 17 LS/LT GSM/GPRS Data Logger range V3.10 Sum-up LS/LT Range: THE industrial solution for water networks little plants Fully IP68 waterproof High-performance GSM Antenna Up to 10-year battery life-time Field installation « tools » # 18