Real-Time Building Energy Modeling and Fault Detection and Diagnostics for a DoD Building Bing Dong1, Zheng O’Neill2 1 University of Texas, San Antonio, TX, USA 2 University of Alabama, AL, USA The work was done at the United Technologies Research Center ME 4343 HVAC Design Introduction • Motivation Source: NBI report 2008 Energy Performance of LEED For New Construction Buildings Introduction • HVAC systems consume >20% more energy than design intent – Equipment performance degradation, and interact with other systems. – Existing control and information systems do not make visible system level energy consumption. • Need for a scalable building energy management system that includes whole building energy diagnostics and visualization – Better HVAC operational controls and energy diagnostics – Raises the visibility of energy performance to help decision making Building Facts • Each 150K sf2 Barrack – Compartments, classrooms and cafeteria/galley 7114 7113 • Cooling – Two absorption chiller: 450 ton – Chilled water loop with fixed-speed primary pump • Heating – Steam from the base wide central heating plant – steam to water heat exchanger • 5 AHUs for each building • More than 200 VAV boxes with reheat coil • A distributed Direct Digital Control System (DDC) 4 Technology Approaches • Overview of the Integrated Infrastructure PC Running EMS PC Running Integrated infrastructure Ethernet BACnet Gate Way Energy Visualization BIM Based Database Core Layer: BIM-based Database BIM to BEM Revit Core Real-time Data Acquisition Application Layer: Real-time energy simulation, visualization and diagnostics 1000 800 600 400 Simulated Measured 200 0 00:00 BLDG7114 Water Side Load (kW) HVAC Lighting Weather BLDG7114 Water Side Load (kW) BCVTB 06:00 12:00 18:00 00:00 Building Reference Model 0.1 0 -0.1 03:00 06:00 09:00 12:00 15:00 18:00 21:00 Energy Diagnostics Applications 5 Technology Approaches • Integrated Energy Modeling Approach Real-Time Data Acquisition Rwin Tamb Tosur Tisur Tzone 1/hoA 1/hiA Qstructure R Qsurfi Qsurfo C Architectural Model Envelope Model 40000 Fan Speed Measured Power Poly. (Fan Speed) Fan Power (w) 35000 30000 Calibration Electric Energy Deviation BIM Database y = 6.4017x2 - 331.03x + 3355.6 R² = 0.9715 25000 20000 15000 10000 5000 0% -5% -10% -15% Mechanical Model 10 20 30 40 50 60 Fan Speed (%) 70 80 90 HVAC Equipment Models Target ±10% at rated conditions -20% -25% 0 0 Model Integration and Validation C 100 Dev Total Pumps -5% -4% Cooling AHU Tower Supply Fans Fans -13% -4% AHU Exhaust Return Fans Fans -3% -12% Calibration Technology Approaches BIM to BEM automatic code generation Traditional Approach Building 7114 Architectural Model Building 7114 Mechanical Model Rwin Tamb Tosur 1/hoA Tisur Tzone 1/hiA Qstructure R Qsurfi Qsurfo C C BEM (Thermal Network Model) One Week 7 Technology Approaches BIM to BEM automatic code generation Traditional Approach Building 7114 Architectural Model Our Approach Building 7114 Architectural gbXML Model IFC Automatic data extract BIM Database Automatic data extract Building 7114 Mechanical Model 1/hoA Rwin Tamb Tosur Rwin Tamb Tosur Building 7114 Mechanical Model Tisur Tzone 1/hiA Qstructure R 1/hoA Tisur Tzone 1/hiA Qstructure R Qsurfi Qsurfo C C BEM Input files Qsurfi Qsurfo C C BEM (Thermal Network Model) One Week BEM (Thermal Network Model) < 5 minutes!! 8 Technology Approaches Real-time Data Acquisition Outside view cafeteria sleeping area classroom Building Control Virtual Test Bed (BCVTB) Extend BCVTB BACnet actors: 1) BACnet reader utility: Automatically generate a.xml configuration file and a .csv point description file based on the file created by Simens EMS Naval Station Great Lakes (Bldg 7114) 2) Simens EMS Our DAQ 3) StoreBACnetDatatoBIMDatabase: Based on the .csv file, automatically create SQL statements based on the raw data received from EMS DatabaseManager Establish the connection between BCVTB and BIMbased database 9 Results Real-time Energy Performance Visualization Energy Statistics Pie Chart Interface Building Hierarchy Interface Time-Series Energy Flows Interface 10 Instant Error BLDG7114 Water Side Load (kW) Results Real-time Energy Simulation 1000 Simulated Measured 500 0 07/06 07/07 07/08 07/09 07/10 07/11 0.1 0.05 Q fan a_r m a _ ex m 3 2 a _ rm m 0 -0.05 3 8 5 -0.1 QCC QHC 07/07 07/08 07/09 07/10 07/11 T , m a _ amb Building 7114 Real-Time Simulation Results from 07/06/2011 to 07/11/2011. 4 3 Qz 2 , Ta _ r , 2 Q fan a _ mix T,m w_ s T, m 5 2 7 w_ r T, m a_s T,m Qz 3 , Ta _ r ,3 Qz , Ta _ r 6 Qz 4 , Ta _ r , 4 12 1 9 13 10 2 3 4 14 Qz1 , Ta _ r ,1 1 11 5 6 7 8 Zone mode Supply/Return fan Mixed air Economizer Heating coil Cooling coil DAT set-point Zone reheat coil 9 10 11 12 13 14 15 Secondary loop pumps Bypasss loop Primary loop pumps Hotwater loop pumps Chiller S/R water temp Condenser pumps Cooling tower 15 Building 7114 AHU3 secondary and primary system diagram 11 Results Building 7114 Energy Diagnostics: Economizer fault identified and corrected OA Damper Position Reference ROM 3 0.8 Q fan a_r m a _ ex m 8 5 3 a _ mix T,m 7 w_ s T, m 5 w_ r T, m Qz1 , Ta _ r ,1 1 QCC QHC 4 Actual Expected OA Damper Position AHU network 2 a _ rm m 3 a _ amb T,m 1 2 Qz 2 , Ta _ r , 2 Q fan a_s T,m Qz 3 , Ta _ r ,3 Qz , Ta _ r 1 OAT Train OAD 0.6 0.8 6 Qz 4 , Ta _ r , 4 1 2 3 4 5 6 7 8 Airflow 0.4 Zone mode Supply/Return fan Mixed air Economizer Heating coil Cooling coil Discharge air temp set-point Zone reheat coil 07/17 0.6 07/24 Building Operation data 07/31 0.4 07/17 AHU energy 07/24 Anomaly Score Damper 1000 Inference 1000 500 Valve 500 0 0 07/31 Anomaly Score 07/17 07/24 07/17 07/24 07/31 07/31 Building 7114 Energy Impact Operation data MAT OA Damper DAT DATS OAT 95 90 85 OA damper 100% 80 75 70 65 60 55 07/21 07/26 Times 07/31 DAT setpoint cannot be maintained Economizer faults: Enthalpy calculation in control sequences is wrong B7114 CHW Average BTU/hr Temperature (F) / Damper Position (%) 100 3,000,000 2,500,000 2,000,000 1,500,000 With Faults 1,000,000 Faults Corrected 500,000 0 OAT BINS (F) Faults was corrected on Aug 3rd , 2011. Measured chilled water energy consumption shows 18% savings were achieved Conclusion • This study has demonstrated an integrated infrastructure which integrates design information, database and realtime data acquisition in a real building to support energy modeling, visualization and FDD. Observations and Lessons learned: • Manually mapping BMS points of each HVAC component. • The designed control logic in the HVAC control system is usually different from what is actually implemented locally. Communication with field people is necessary to get an accurate baseline model. 13 Thank you! • Acknowledgements: – DoD ESTCP program manager: Dr. Jim Galvin – UTRC: Dong Luo, Madhusudana, Shashanka ,Sunil Ahuja, Trevor Bailey – Naval Station Great Lakes • Energy manager: Peter Behrens • Mechanical Engineer: Kirk Brandys • Facility team • Questions? 14