GEN-SET CONTROLLERS RGK700 – RGK800 1 GEN-SET CONTROLLERS RANGE NOT EXPANDABLE AMF STAND ALONE RGK700 RGK700SA RGK800 RGK800SA EXPANDABLE 2 GEN-SET CONTROLLERS Auxiliary power supply • • • Nominal voltage: 12-24VDC (max consumption 4.8W) Continuos working range: 7…33VDC Minimum value during cranking: 5.5VDC Voltage inputs • • • • 4 inputs (L1, L2, L3, N) for mains 4 inputs (L1, L2, L3, N) for generator Nominal voltage: 600VAC (L-L) Voltage range: 50…720VAC (L-L) Current inputs • • • • cULus omologation pending Built-in connections • • • • • • Resistive analog inputs Engine speed inputs: Hz, pick-up and W CANbus J1939 Remote alarms/status signal output RS232 (RGK700) RS485 (RGK800) 3 inputs on RGK700 4 inputs on RGK800 CT secondary nominal current: /5A or /1A (selectable) Current range: 10mA…6A (/5A), 10mA…1.2A (/1A) 3 GEN-SET CONTROLLERS DIFFERENCES BETWEEN RGK700… AND RGK800… RGK700… RGK800… Digital input number 6 negative + 1 positive 8 negative + 1 positive Digital output number 4 static + 3 relay 6 static + 3 relay + 1 pulse Analog input number 3 resistive 4 resistive EXP module compatibility - 3 Current input number 3 4 Earth losses check - ● 400Hz compatibility - ● Built-in serial ports RS232 RS485 - ● Real time clock 4 GEN-SET CONTROLLERS REMOVABLE LABEL Label for name customisation or plant name indication OPTICAL PORT ON FRONT PC link through • USB (CX01) • WiFi (CX02) CX01 CX02 5 GEN-SET CONTROLLERS OPTICAL PORT ON FRONT Advantages • No need to disconnect the panel power supply to connect with the device • Electrical safety (no physical connection) • • IP65 protection degree Comfortable access to the unit from the front 6 GEN-SET CONTROLLERS OPTICAL PORT ON FRONT CX01 PC link through USB (CX01) or WiFi (CX02) for: • Programming • Diagnostics • Data downloading • Firmware upgrade Using CX02 (WiFi), the following is possible: • Project upload/download • Controller cloning CX02 7 GEN-SET CONTROLLERS PROFILE Low profile and reduced depth help to install the controller even in very compact electrical panels. 8 GEN-SET CONTROLLERS INSTALLATION Expandability with EXP… series Holes for plastic ties let a well ordered cabling. IP65 rubber gasket Metallic elements with screws for long-lasting fixing. 9 GEN-SET CONTROLLERS IP65 TEST ACCORDING TO IEC60947-1 10 GEN-SET CONTROLLERS REMOTE ACCESS DEVICES FOR RGK800 “MIRRORS” of the main controller: the user acts from a remote site as in front of the device. RS485 “Mirror” installed in the control room Local controller next to the generator RGK 800 RD SA: remote display for RGK 800 SA RGK 800 RD: remote display for RGK 800 Power supply: 12-24VDC Built-in serial port: RS485 4 inputs 1 changeover relay output 1 static output 11 GEN-SET CONTROLLERS REMOTE ACCESS DEVICES FOR RGK800 RS485 RGK RA (Remote Annunciator) It is possible to display on a remote screen the active alarms and to silent them. Power supply: 12-24VDC Built-in serial port: RS485 12 GEN-SET CONTROLLERS ACCESSORIES CODED PULSES Long distances (1000m) Refresh time 2.5s CANBUS (parallel with ECU) Short distances (40m) Refresh time 10ms RGK RR • • • RGK status (alarms, automatic mode, etc.) remote relays Each relay (8 NO + 4 CO) corresponds to a status or a logic combination of different status Up to 4 units connected together (48 relays) 13 GEN-SET CONTROLLERS EXP… EXPANSION MODULES • • • • Plug-in connection at the back of the base unit Power supplied by the base unit Up to 3 modules Plastic retainer for applications with strong vibrations ADVANTAGES • • • • Configuration flexibility Only one code for the base unit Possibility to add functions even after the first installation RGK800 RGK800SA 14 GEN-SET CONTROLLERS EXP… EXPANSION MODULES Digital inputs/outputs • EXP1000 - 4 digital inputs • EXP1001 - 4 digital outputs • EXP1002 - 2 digital inputs + 2 static outputs • EXP1003 - 2 relay outputs Analog inputs/outputs • EXP1004 - 2 multifunction analog inputs • EXP1005 - 2 multifunction analog outputs Communication modules • EXP1010 – USB • EXP1011 – RS232 • EXP1012 – RS485 • EXP1013 – Ethernet • EXP1014 – Profibus®-DP • EXP1015 – GSM/GPRS Modem Plug&Play! Save Retry The controller is capable of recognising the new system configuration. User is asked to confirm or retry. Parameters of expansion modules need to be programmed to take advantage of new features. 15 GEN-SET CONTROLLERS EXP1015 MODEM GSM/GPRS EXPANSION MODULE TRADITIONAL CONFIGURATION (external GSM modem) Requirements: • RS232 serial communication port available on the device (built-in or added by installing an expansion module) • external GSM modem with RS232 port. Operations: • configuration of the serial ports both for the device and the modem • modem programming using AT commands (for expert only!). CONFIGURATION WITH EXP1015 Requirements: • support of EXP1015 module. Operations: • plug&play installing of the module (no configuration required!). 16 GEN-SET CONTROLLERS INSTALLATION without EXP1015 GSM Antenna 12-24VDC Supply with EXP1015 + CX03 EXP1015 CX03 CABLE 51C7 17 GEN-SET CONTROLLERS CONFIGURATION WITHOUT EXP1015 Serial port setup AT commands Nothing to do with EXP1015 18 GEN-SET CONTROLLERS FUNCTIONS • • • • SMS sending and receiving E-mail sending with data and diagnostic informations FTP client (log file transferring to a remote FTP server) Modem link with the Remote Control software. 19 GEN-SET CONTROLLERS SCREENSHOTS User-friendly interface with complete descriptions during programming (5 languages) Easy browsing through measurements and full description texts (5 languages) Customised pages with free text description. Free messages for alarms Graphs (waveform, stem). 20 GEN-SET CONTROLLERS FUNCTIONS Load management Dummy loads: • Threshold and delay for activation • Threshold and delay for deactivation • 4 steps Load shedding (non-priority loads): • Threshold and delay for non priority load connection • Threshold and delay for disconnection • Maximum configuration: 4 sets of non priority loads 21 GEN-SET CONTROLLERS FUNCTIONS Digital inputs and outputs Programmable (functions and properties) inputs Programmable (functions and properties) outputs Pulse output (energy and status remoting) Pulse output 22 GEN-SET CONTROLLERS FUNCTIONS Analog inputs and outputs Programmable resistive analog inputs Analog inputs: 0…10VDC, 0/4…20mA, PT100 Analog outputs: 0…10VDC, 0/4…20mA 23 GEN-SET CONTROLLERS FUNCTIONS Alarms More than 50 alarms ready to use 8 user’s alarms: • Programmable source (inputs, outputs, limits, remote variables, PLC variables, remote alarms) • Free text Programmable properties Acoustic signals: • Buzzer • Siren • Buzzer + siren 24 GEN-SET CONTROLLERS FUNCTIONS Fuel status Level: • Autonomy monitoring • 2 thresholds for minimum level • Fuel theft function Filling pump: • Start and stop thresholds • Manual command. Current protection Thermal protection Earth fault current monitoring 25 GEN-SET CONTROLLERS FUNCTIONS Engine operation Engine working hour monitoring 3 maintenance periods: • Independent periods • Total, engine running, load connected hour counting. Rent management • Total, engine running, load connected hour counting • Programmable alarm generation 26 GEN-SET CONTROLLERS FUNCTIONS Event list • 250 events • Reading of the measurement causing the event Configurations • 4 alternative preset configurations • Selection through digital inputs. Information pages • 1 completely free page • 1 system page with free generator description 27 GEN-SET CONTROLLERS FUNCTIONS Automatic test 4 operative modes: • Test • Auto • Man • Off 4 user’s pages • Selection of 3 measurements • Free title • The page can be set as the main page 28 GEN-SET CONTROLLERS FUNCTIONS Limit thresholds Remote variables (virtual inputs) Password • 2-level software password • 1 locking digital input Harmonic analysis and waveforms 29 GEN-SET CONTROLLERS FUNCTIONS Mutual standby • Exchange by time • Exchange by starts • Mutual help RS485 RS232 Status Alarms Changeover operation • Contactors (2 outputs) • Motorised changeover (3 outputs) • Motorised breakers (4 outputs) Generic counters • Source selection • Weight setup • Free title text 30 GEN-SET CONTROLLERS BUILT-IN CANBUS J1939 Capability of • Measurement reading • Alarm reading • Alarm reset • Command sending J1939 Status Alarms Commands Supported ECU • Generic J1939 • Volvo (EDC, EMS, EMS2) • Scania (S6) • Deutz (EMR2) • Perkins (2800) • John Deere • Iveco (Nef, Cursor) 31 GEN-SET CONTROLLERS PLC logic 32 GEN-SET CONTROLLERS CUSTOMISATION MANAGER – Setup software 33 GEN-SET CONTROLLERS RGK REMOTE CONTROL – Monitoring software 34 GEN-SET CONTROLLERS WEB SERVER FUNCTION FOR RGK800 Requirements 1) Installation of EXP1013 on RGK800 2) PC with: - Web client (IEXPLORER, CHROME, FIREFOX) - Java installed and enabled (free download from www.java.com). Actions 1) EXP1013 setting up with specific software tool available at Lovato web site (www.lovatoelectric.com) 2) When running for the first time, the web client asks the user for installing of Java module. 35 GEN-SET CONTROLLERS NEW RGKs IN LOVATO ELECTRIC CONTROLLER RANGE RGAM40 RGAM42 RGAM41 RGK60 RGK700 RGK800 RGK40 RGK50 RGK700SA* RGK800SA * No built-in key selector for starting 36 GEN-SET CONTROLLERS INSTALLATIONS 37 GEN-SET CONTROLLERS Thankyou for your attention! RGK700 – RGK800 www.LovatoElectric.com 38