ELEVATION AND DETAILS PLAN FOR THE CONFINED
MASONRY WALL
The plan should contain:
- the elevation of the computed wall, from the ground floor (-0.05m level) to the
top story (scale 1:20) together with the detailed reinforcement from the columnties;
- the cross-section of the wall (scale 1:20), containing the web and the flanges
(the flanges should be defined from the web to the first opening or 6*thickness,
using the interruption sign) and the reinforcement from the mortar bed joints;
- the cross-section of the column-ties (scale 1:10) indicating the longitudinal
reinforcement and the stirrups;
- the cross-section of the beam-ties (scale 1:10) indicating the longitudinal
reinforcement and the stirrups;
The reinforcement of the column-ties, beam-ties and of the bed joints
should be done accordingly to the minimum conditions foreseen in the in-force
Design Codes P100-1/2013 and CR6-2013 and to the results of the wall design
checks.
For the column-ties, the minimum conditions provided by the P1001/2013 Code are:
- Cross section should have aria ≥ 625 cm2 and one side ≥ 25 cm;
- Minimum longitudinal reinforcement should be ≥1% for ag≥0.25g, ≥0.8% for
ag=0.15g and ag=0.20g, ≥0.6% for ag=0.10g;
- Minimum longitudinal bars diameter Φ=12mm;
- The minimum overlapping length of the longitudinal bars is 60*Φ at the
-0.05m level and 50*Φ for the rest of overlappings;
- Minimum diameter of the stirrups Φ=6mm.
- Maximum distance between stirrups 15cm, excepting the overlapping length
of the longitudinal bars, the intersection with the beam-ties and 60cm above and
below the beam-ties, where the maximum span is 10 cm;
For the beam-ties, the minimum conditions provided by the P100-1/2013
Code are:
- Cross section should have aria ≥ 500 cm2, the width ≥ 25 cm, the height larger
than the height of the slab and twice larger for the exterior walls and for the
stairs area;
- Minimum longitudinal reinforcement should be ≥1% for ag≥0.25g, ≥0.8% for
ag=0.15g and ag=0.20g, ≥0.6% for ag=0.10g;
- Minimum longitudinal bars diameter Φ=12mm;
- The anchoring of the longitudinal bars should be done in the perpendicular
beam-ties, in horizontal plan, at least 60*Φ
- Minimum diameter of the stirrups Φ=6mm
- Maximum distance between stirrups 15cm, excepting the overlapping length
of the longitudinal bars and the intersection with the column-ties where the
maximum span is 10 cm;
For the bed joints, the reinforcement is necessary for:
- the intersections and corners, where the connection reinforcement should have
at least 1.00m in the mortar joint, minimum 1cm2 (2 bars of 8mm), vertical span
of max 3 courses (brick rows); the bed joints reinforcement should be placed
in consecutive joints (avoid two rows of reinforcement in the same joint).
- the shear force, if the shear check result shows the VRd3 reinforcement is
necessary.