ME 322a Refrigeration Systems
Topic 1: Reversed Carnot & Heat Pump
REFRIGERATION
Refrigeration – means maintaining a system at a temperature less than the temperature of the
surroundings. This means the removing of the heat from a substance to be cooled.
The Clausius statement: It is impossible to construct a device that operates in a cycle and
produces no effect other than the transfer of heat from a cooler-body to a hotter body.
This statement is related to the refrigerator or heat pump, and in effect states that it is impossible to
construct a refrigerator that operates without an input of work.
Refrigerants- is the substance used for heat transfer in a refrigerating system. It picks up heat
by evaporating at a low temperature and pressure and gives up this heat by condensing at a
higher temperature and pressure.
Refrigerants of commercial refrigeration units:
1. Ammonia
2. Freon 12
3. Methyl chloride
4. Carbon dioxide
Refrigerating Machine – will either cool or maintain a body at a temperature below that of its
surroundings.
T2
Surroundings
QR
W
R
QA
Cold body
T1
This machine R absorbs heat QA from the cold body at temperature T1 and rejects heat QR to
the surroundings at temperature T2 and, during the process, requires W to be done on the
system. The performance of a refrigerating machine, COP, and is defined as the heat
supplied (the desired effect) divided by the net work (what is costs):
QA
COP = W
QA
=Q -Q
R
A
Reversed Carnot Cycle
QR
3
2
Condenser
Expander
Compressor
ot
Wnet
Evaporator
4
1
QA
Prepared by: Leonel L. Pabilona, D.Eng
1
ME 322a Refrigeration Systems
Topic 1: Reversed Carnot & Heat Pump
The reversed Carnot cycle consists of the following processes:
Process 1-2: isentropic compression, s1 = s2
Process 2-3: isothermal heat rejection, T2 = T3
Process 3-4: isentropic expansion, s3 = s4
Process 4-1: isothermal heat absorption, T4 = T1
The T-S diagram for a reversed carnot cycle
T
3
T2
2
S3 = S 4
S1 = S 2
T1
4
1
S
Heat Added
QA = T1(S1 - S4)
Heat Rejected
QR = T2(S2 - S3)
= T2(S1 - S4)
Work Net, Wnet
QA + W = QR
W = T2(S1 - S4) - T1(S1 - S4)
= (T2 - T1) (S1 - S4)
Therefore, COP in terms of temperature
T1(S1 - S4)
(T2 - T1) (S1 - S4)
T1
= T -T
2
1
COP =
Performance Factor of Carnot Heat Pump, PF
High Temperature
Reservoir, T2
QA
PF = W
QA
T2
= T -T
2
Heat Pump
Wnet
1
QR
Low Temperature
Reservoir, T1
Prepared by: Leonel L. Pabilona, D.Eng
2
ME 322a Refrigeration Systems
Topic 1: Reversed Carnot & Heat Pump
Unit for refrigerating effect:
The historical definition of a capacity unit is the amount of heat that must be extracted
to freeze 1 ton of water at 32oF in ice at 32oF ( at 1 atm ) in 24 hours .Since the latent heat of
water is closely 144 Btu/lb.
Btu
2000 lb
Energy produced in 1 day = 144 lb (1 ton) ton
Btu
= 288 000 day
This steady rate of refrigeration is called a ton of refrigeration ( TR ).
Btu 1 day 1 hr 1.055 kJ
TR = 288 000 day 24 hrs 3600 sec 1 Btu
= 3.52 kW
Sample Problems
1. A refrigeration system operates on the reversed Carnot Cycle. The minimum and
maximum temperatures are minus 25oC and plus 72oC, respectively. If the heat rejected at
the condenser is 6000 kJ/min, draw the TS diagram and find,
a. power input required
b. tons of refrigeration developed
Solution:
(a)
(b)
Prepared by: Leonel L. Pabilona, D.Eng
3
ME 322a Refrigeration Systems
Topic 1: Reversed Carnot & Heat Pump
2. A reversed Carnot cycle has a refrigerating COP of 4.
a. What is the ratio Tmax/Tmin?
b. If the work input is 6 kW, what will be the maximum
refrigerating effect, kJ/min and tons?
Solution:
Tmin
(a) COP = Tmax - Tmin
1
Tmax - Tmin Tmax
=
=
-1
COP
Tmin
Tmin
Tmax
1
1
=
+
1
=
Tmin COP
4 + 1 = 1.25
(b) QA = W (COP) = (6) (4) = 24 kW
In kJ/min,
QA = (24)(60) = 1440 kJ/min
In Tons,
24
QA = 3.516 = 6.826 TR
3.
A house should be heated by a heat pump, PF= 2.2, and maintained at 20oC at all times.
It is estimated that it looses 0.8 kW per degree the ambient is lower than the inside.
Assume an outside temperature of –10oC and find the needed power to drive the heat
pump?
Prepared by: Leonel L. Pabilona, D.Eng
4
ME 322a Refrigeration Systems
Topic 1: Reversed Carnot & Heat Pump
4. Refrigerant-12 at 95°C, x = 0.1 flowing at 2 kg/s is brought to saturated vapor in a
constant-pressure heat exchanger. The energy is supplied by a heat pump with a
coefficient of performance of PF= 2.5. Find the required power to drive the heat pump.
Methods of Refrigeration
1. Mechanical refrigeration
2. Absorption refrigeration
3. Ice refrigeration
Prepared by: Leonel L. Pabilona, D.Eng
4. Steam jet refrigeration
5. Air cycle refrigeration
5