- API RP 500 RECOMMENDED PRACTICE FOR CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS AT PETROLEUM FACILITIES FIRST EDITION Copyright Material IEEE Paper No. PCIC-92-05 Paul S. Hamer, Senior Member, IEEE Chevron Research and Technology Company 100 Chevron Way Richmond, CA 94802-0627 David N. Bishop Chevron U.S.A. Inc. 935 Gravier Street New Orleans, LA 70112 Frederick Bried, Senior Member, IEEE Shell Oil Company Two Shell Plaza Houston, TX 77252-2099 Abstract- API Recommended Practice 500 (RP 500), Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities, provides guidelines for classifying locations at petroleum refineries, production and drilling areas, and pipeline transportation facilities for the selection and installation of electrical equipment. It has combined the previously separate recommended practices RP 500A, RP 500B and RP 500C. This paper highlights the changes effected by the new document. Particular attention is given to the document sections on ventilation and the use of combustible gas detectors. Introduction 500" was formed. This task force was comprised of the following six members, two from each of the API Departments(Refining, Production,and Transportation): David N. Bishop, Chevron (Production) Frederick Bried, Shell (Transportation) Paul S. Hamer, Chevron (Refining) Floyd Lazenby, Exxon (Transportation) Tom P. Pearson, Arc0 (Production) John H. Rannells, Amoco (Refining) The task force was charged with combining the three documents into one that would be acceptable to all three API departments -- a seemingly formidable task. The initial and subsequent seven drafts of RP 500 were edited by this group and the larger task forces originally responsible for RP 500A, B, and C. The final document was sent simultaneously to all three department's standardization committees for letter ballot. The ballot was unique in that each of the departments voted on the general sections (Sections 1 through 5 and the Appendices of RP 500)and its respective "Section" of RP 500: "A" for Refining, "B" for Production, or "C" for Transportation. The six-member task force was responsible for resolving all ballot comments and negative votes. Differences between each department that could not be resolved meant that the unique requirements each of the three departments be integrated into RP 500 via Sections A, B, or C (Refining, Production,and Transportation, respectively) in RP 500. The approved RP 500 [6] was issued on June 1, 1991. In order to comply with API policy, RP 500 must be reaffirmed, revised, or withdrawn at least every five years, or by June 1,1996. The procedures for updating RP 500 will be similar to those initiated in 1988, and the schedule could be accelerated if there are significant changes in underlying codes or standards (e.g., the NEC). - History of the API RP 500 Series While the National Electrical Code (NEC) (11 defines rules on the selection and installation of electrical equipment in classified areas, it provides only general guidance on the extent of classified areas. The American Petroleum Institute (API) RP 500 series (RP 500A, RP 5006, and RP 500C) have served for decades as the petroleum industry's recommended practices on the extent of classified areas. The first document published by API on classificationof locations also was designated RP 500, without a suffix, and was issued by the Refining Department of API in 1955. This document was further updated in 1957, issued as RP 500A in 1966, and updated in 1982 [2]. Since the initial API document's scope included only refineries, the Production Department of API created a document for guidance in classifying production and drilling facilities. Initially issued as RP 11J in 1961, it was designated RP 5006 in 1966 and updated in 1973 and 1987 [3][4]. Similarly, the Transportation Department of API issued RP 500C covering pipelines in 1966, with updates in 1974 and 1984 [5]. The following includes highlights of RP 500. It is a significant recommended practice for use by the entire petroleum industry. Interpretationsof the recommended practice are not intended. The three documents were created and balloted by the three separate departments within API, with minimal liaison among their task forces writing the recommended practices. In 1988, at the request of the three Departmenttask forces, an "Advisory Task Force on RP - 37 - 92-CH3186-4/1/92/0000-0037 $03.00 @ 1992IEEE Highlights of API RP 500 "General" Sections, Sections 1 Through 5 Several methods of achieving adequate ventilation are listed. All methods must assure that areas where heavier-than-air vapors or lighter-than-air vapors may collect are ventilated. Although not all-inclusive, the methods listed follow: Section 1 Section 1 emphasizes that the NEC [l] provides the basic definitions and that RP 500 provides guidelines for classifying locations at petroleum facilities for the selection and application of electrical equipment. Its electrical equipment applications. scope includes&o Specific recommendations for the degree and extent of classified areas unique to refineries, production facilities, and pipeline facilities are given in Sections A, B,and C, respectively. 1) ventilation at a minimum rate of one cubic foot of air volume flow per square foot of floor area, but at least six air changes per hour; 2) natural ventilation of enclosed areas (recommended only for areas of 1000 cubic feet or less) using the natural draft "stack effect" with a safety factor of two, increasing the air flow requirements to at least twelve air changes per hour. Reference sample calculations in RP 500, Appendix A. Section 2 The "fire triangle" components are summarized in Section 2. That is, for a fire to exist: 3) natural ventilation by the inherent construction of the building or partially enclosed area: or, 1) the flammable gas or vapor must be present: 2) the gas or vapor must be mixed with air or 4) ventilation rates determined by the fugitive emissions method described in RP 500, oxygen in the proper quantities and proportions; and, 3) the mixture must be ignited. Appendix B. Prior to this edition of RP 500, the general recommendationwas to ventilate at a rate of twelve air volume changes per hour for an area to be adequately ventilated. In cold-weather climates, this imposed severe requirements for enclosed areas where the ventilation air had to be heated. The NFPA 30 Technical Committee considered the successful experiences of the petroleum industry in making changes to the 1990 edition of NFPA 30. Section 3 Descriptions of flammable and combustible liquids, highly volatile liquids, and flammable gases are presented in Section 3. Also, the basis for the NEC [I] "Grouping" of atmospheric mixtures is given. With the new recommendations of RP 500, one has choices based on the fundamental definition of adequate ventilation rather than arbitrary or conservative ventilation rates. The "fugitive emissions method" provides a method of calculatingthe requiredventilation rate based on the typical leakage rate from components such as pump seals, valve packing, and flange gaskets. Typically, this calculation method will result in required minimum ventilation rates of less than three air changes per hour for "adequate ventilation." For such low rates, however, gas monitoring is recommendedto assure that flammable gas concentrations of less than 25 percent LFL are maintained.Applicationof the fugitive emissions method requires an accurate count of all the potential hydrocarbon leak sources in an enclosed area and extensive calculations. Section 4 One of the most significant parts of the document is Section 4, "Classification Criteria." The definitions of Class I, Division 1 and Class I, Division 2 are restated from the NEC [I],except for editorial changes to improve clarity for those involved with petroleum operations. Considerations for classifying an area Division 1 or Division 2 are included, and specific locations that may be considered unclassified, regardless of the degree of ventilation, are listed. "Ventilation," Section 4.6, is significantly changed from previous editions of the RP 500 series. A reason for this change is the change in the NFPA 30, 1990 Edition [7], definition of adequate ventilation. Reference Appendix A of this paper. Although API RP 500 does not totally embrace all the information in NFPA 30, particularly the "sampling" provision of 5-3.3.1(b), RP 500 accepts the methodology of using "fugitive emissions" to verify adequate ventilation. Appendices B and C of RP 500 cover this subject. The use of combustible gas detection equipment (Section 4.8) can be the basis for classifying an inadequatelyventilated areas containing equipment that could release a flammable gas or vapor Division 2, but never to make the area unclassified. Also, the interior of vapor-tight rooms or buildings not containing a gas source can be considered unclassified if detection equipment is installed and maintained within the stringent requirements outlined in RP 500. The detectors are required to be of the stationary type, approved or listed by a nationally recognized testing laboratory, applied to ensure that all areas where flammable gas might accumulate are monitored, and The fundamental definition of adequate ventilation given by RP 500 is as follows: "...ventilation (natural or artificial) that is sufficient to prevent the accumulationof significant quantities of vapor-air mixtures in concentrationabove 25 percent of their lower flammable (explosive) limit (LFL)..." [6]. 38 - calibrated at a frequency in accordance with the manufacturer's recommendation, but at least every three months. An alarm should be activated upon sensing 20 percent LFL and power should be disconnected from devices in the area, if those devices are not suitable for the area classification without gas detectors, when 40 percent LFL gas concentration is sensed. The use of combustible gas detectors provides one with a new approach to design. However, if the area being considered for the use of gas detectors contains equipment that may release flammable gases or vapors dugng normal operations, gas detectors are not a feasible option unless some degree of ventilation is provided. Otherwise, frequent alarms or equipment shutdowns can occur. Highlights of Section 8, Production The last edition of RP 500B introduced the "limited ventilation" concept. This was dropped in RP 500, and the figures of Section 6 reflect this change, referring only to "adequate" or "inadequate" ventilation. Productionoperations, particularly offshore, have severe space restrictions. For this reason, many specific pieces of equipment are illustrated in the figures. Paragraphs on sumps, drains, valves, and valve actuators were added to RP 500. Recommendations for hydrocarbonfueled prime movers have been expanded. Highlights of Section C, Pipeline Transportation Section 5 In 1989, a task force was organized to review the RP 500C in accordance with APl's five year review cycle requirement. The formation of this task force took place at about the same time as the "Advisory Task Force on RP 500" initiated work combining RP 500 A, B and C. Rather than revise the second edition of RP 500C (1984) for letter ballot, the RP 500C task force felt that RP 500C should be reaffirmed, allowing the task force to focus their efforts reviewing and commenting on the various RP 500 drafts from a transportation viewpoint. Section 5 covers the extent of a classified location based on the amount of release and whether the location is outdoors or indoors. Statements on gas density and the degree of air movement are included in this section. An outline of the procedure for classifying a location is part of RP 500 (Appendix F) and is included as Appendix B to this paper. It serves as a general description of the steps required to classify an area. The three categories or levels developed in the second edition of RP 500C, were retained in Section C of RP 500. Since the potential spread of a liquid, vapor or gas release depends in part upon the operating pressure and type of material involved, distances are assigned for the difference in potential spread by using separate dimensions for: Highlights of Section A, Refining Experience within refineries during the evolution of RP 500A had shown that occurrences of flammable material liberation from some operations and apparatus is so infrequent that it is not necessary to classify the surrounding areas. An example cited in RP 500 is an adequately ventilated location where flammable substances are contained in suitable, well-maintained (italics added) closed piping systems that include only the pipe, fittings, flanges, meters, and small valves. This area doesnoJ require classification. This is an exception to the general Division 2 requirement that excludes only "... all-welded closed piping systems without valves, flanges or similar devices, or continuous metallic tubing without valves, fittings, flanges, or similar devices..." (italics added) and considers these locations to be unclassified. Sound engineering judgement must be applied to the "small valve" term, remembering that RP 500 is only a guide. 1) gas or liquids at an operating pressure of 275 psig or less, 2) gas or liquids at an operating pressure above 275 psig, and 3) highly volatile liquids (HVL) as defined by the Department of Transportation (DOT). Additional figures that were developed or added to Section C are the tank carhank truck figures from NFPA 497A [8] and below-grade vaults. The major changes to the figures include a drainage path from tanks; expansion on the figure for separators, dissolved air floatation units, and biological oxidation units; and extension of Division 2 for cooling towers and designating the pump pit as Division 1. Additional tank carltank truck reference figures from NFPA 497A [8] are included. - 39 - Conclusion References The merging of RP 500A, B, and C into a single RP 500 is a major benefit to the petroleum industry. It required the hard work and review of many people in the various technical subcommittees and task forces of API. The result is a document that can be used by the entire petroleum industry in a consistent manner. [ l ] NFPA 70, National Electrical Code. Quincy, MA: National Fire Protection Association. 1990. [2] API RP 500A. ClassificationofLocationsfor Electrical Installations in Petroleum Refineries. 4th Ed. Washington, DC: American Petroleum Institute, 1982. The document can be improved with input from those who use it. For example, in future issues of RP 500, one could expect to see similar figures from Sections A, B, or C to be grouped in a section of common figures. Figures unique to the refining, production, or transportation segments of the petroleum industry would remain in the existing Sections A, B, and C. Examples that might be included in a "common figure" section would be storage tanks, tank truck and rail car loading areas, marine loading facilities, and compressor buildings with lighter-than-air gas or vapor sources. Comments or suggestions should be addressedto API. Copies of RP 500 are available from: American Petroleum Institute, Publications and Distribution Section, 1220 L Street NW, Washington, DC 20005, phone (202) 682-8375. [3] API RP 5008, Recommended Practice for Classificationof Locations for Electrical Installations at Drilling Rigs and Production Facilities on Land and on Marine Fixed and Mobile Platforms, 3rd Ed. Washington, DC: American Petroleum Institute, 1987. [4] R. J. Gobrick, M. W. Wedel, "The New API RP 5008 - One Year Later," in Conf. Rec. 1988 35th Annual IEEE Petroleum and Chemical Industry Conference, pp. 119-124. [5] API RP 500C, Classificationof Locationsfor Electrical Installations at Pipeline Transportation Facilities. 2nd Ed. Washington, DC: American Petroleum Institute, 1984. [6] API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities. 1 st Ed. Washington, DC: American Petroleum Institute, 1991. (71 NFPA 30, Flammable and Combustible Liquih Code. Quincy, MA: National Fire Protection Association, 1990. [8] NFPA 497A, Recommended Practice for Cla,ss$cation of Locations of Class I Hazardous (Classified)Locations for Electrical Installations in Chemical Process Areas. Quincy, MA: National Fire Protection Association, 1986. - 40 - - APPENDIX A VENTILATION (From NFPA 30 [7]) APPENDIX B (Appendix F from API RP 500 [SI) PROCEDURE FOR CLASSIFYING LOCATIONS 5-3.3 Ventilation. 5-3.3.1 Enclosed processing areas handling or using Class I liquids or Class II or Class Ill liquids at temperatures above their flash points shall be ventilated at a rats sufficient to maintain the concentration of vapors within the area at or below 25 percent of the lower flammable limit. This shall be confirmed by one of the following: This Appendix is intended to provide an outline of the basic procedures requiredto classify a location. It is not all inclusive but should offer guidance to inexperienced individuals. Combined with sound engineering judgement it will provide a good start toward area classification. F.l Introduction. The following procedure requires answering a series of questions. An affirmative answer to either question in Paragraph F.2 verifies the likely existence of a hazardous (classified) location. Boundaries of locations may be determined by applying the recommendations of the preceding sections and referring to appropriate figures in Sections A, B and C, as applicable. Each room, section, or area should be considered individually in determine its classification. Initial planning should focus on grouping of sources and allowing unclassified areas for electrical equipment installation. (a) Calculations based on the anticipated fugitive emissions (see Appendix F for calculation method), or (b) Sampling of the actual vapor concentration under normal operating conditions. The sampling shall be conducted at a 5-ft (1.5-m) radius form each potential vapor source extending to or toward the bottom and the top of the enclosed processing area. The vapor concentration used to determine the required ventilation rate shall be the highest measured concentration during the sampling procedure. NOTE: Final &terminations of classification may require coordination with process engineers, facility design engineers,fire and safety specialists, instrument engineers, and electrical engineers. NOTE: Equipment in enclosed processing areas may deteriorate over time, and periodic sampling should be conducted to ensure that leakage rates have not increased or that the ventilation rate is adequate for any increase in leakage rates. - F.2 Step 1 Need for Classification. The need for classification of a location is indicated by an affirmative answer to either of the following two questions: An acceptable alternate is to provide ventilation at a rate of not less than 1 cu ft per minute per sq ft of solid floor area (0.3 m’ per min per m*). Ventilation shall be accomplished by natural or mechanicalventilation, with discharge or exhaust to a safe location outside the building, without recirculation of the exhaust air. 1. Are flammable liquids, gases, or vapors handled, processed or stored in or adjacent to the area? 2. Are combustible liquids likely to be handled, processed or stored in or adjacent to the area at temperatures above their flash points? Exception: Recirculation is permitted where it is monitored continuously using a fail-safe system that is designed to automatically sound an alarm, stop recirculation, and provide full exhaust to the outside in the event that vapor-air mixtures in concentration over one-fourth of the lower flammable limit are detected. - F.3. Step 2 Assignment of Classification. Assuming an affirmative answer from Step 1, the question in F.3.1 and F.3.2 should be answered to determine the degree of classification (Division 1 or Division 2). Provision shall be made for introduction of make-up air in such a manner as to avoid short-circuiting the ventilation. Ventilation shall be arranged to include all floor areas or pits where flammable vapors may collect. Where natural ventilation is inadequate, mechanical ventilation shall be provided and shall be kept in operation while flammable liquids are being handled. Local or spot ventilation may be needed for the control of special fire or health hazards. Such ventilation, if provided, can be utilized for up to 75 percent of the required ventilation. (NFPA 91, Standard for the Installation of Blower and Exhaust Systems for Dust, Stock, and Vapor Removal or Conveying, and NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, provide information on this subject.) F.3.1 Division 1 locations normally are dictated by an affirmative answer to any one of the questions that follow: 1. Is an ignitible atmospheric concentration of gas or vapor likely to exist in the location under normal operating conditions? 2. Is an ignitible atmospheric concentration of gas or vapor likely to occur in the location frequently because of maintenance, repairs, or leakage? 3. Would a failure of process, storage, transfer or similar equipment likely cause an electrical system failure that would create an ignition source (e.g., arcing) simultaneously with the release of ignitible concentrations of gas or vapor? - 41 - 4. Is flammable liquid or gas handled, processed or stored in an inadequately ventilated location? NOTE: Specific piping and tubing systems described in Paragraph 4.5.1 are excluded from this consideration. 5. For flammable liquids with heavier-than-airvapors, is ventilation inadequate to ventilate all areas (particularly floor areas) where flammable vapors might collect? 6. For lighter-than-air gases, are roof or wall openings inadequately arranged to ventilate all areas (particularly ceiling areas) where gases might collect? F.3.2 After Division 1 locations have been determined, Division 2 locations usually may be distinguished by an affirmative answer to any one of the following questions: 1. In a system containing flammable liquids or gases in an adequately ventilated location, can the liquid or gas escape from potential sources (such as valve packing, flanges, or pump seals) as a result of an abnormal condition? NOTE: Specijic piping and tubing systems described in Paragraph 4.5.1. are excluded from this consideration. 2. Is the location adjacent to a Division 1 location without separation by vaportight walls or barriers? NOTE: In some cases communications ofjlammable gases or vapors between adjacent locations can be prevented by adequate positive-pressure ventilation from a source of clean air. Reference Par. 4.43. 3. If a positive mechanical ventilation is provided, could failure or abnormal operation of the ventilating equipment permit ignitible concentrations of gas or vapor to enter or accumulate in the location? - F.4 Step 3 Extent of Classified Locations. Reference Paragraph 4.7 and Section 5. Reference also Sections A, B or C, as applicable. - F.5 Step 4 Determination of Group. Reference Paragraph 3.5 to determine the proper group. F.6 Documentation. It is recommended that area classifications be documented. Electrical area classification drawings are used as a guide by designers, constructors, and inspectors of electrical installations, and all classified locations should be indicated. This documentation will serve as a record of the original classifications and will serve as a guide when future additions or revisions are considered. - 42 -