(AP) 6 Application Notes 4.5 Current Transformer Requirements Low Impedance REF For accuracy, class X or class 5P Current Transformers (CTs) are strongly recommended. The CT requirements for low impedance REF protection are generally lower than those for differential protection. As the line CTs for low impedance REF protection are the same as those used for differential protection the differential CT requirements cover both differential and low impedance REF applications. The CT knee-point voltage requirements are based on the following settings for transformer REF protection; IS1 = 27, IS2 = 270, K1 = 0%, K2 = 150%. A series of internal and external faults were performed to determine the CT requirements for the REF function. These tests were performed under different X/R ratios, CT burdens, fault currents, fault types and point on wave. The K dimensioning factor for the REF function is smaller than that for the transformer differential protection. Since the highest K factor must be considered, the CT requirements for transformer differential must be considered. 4.5.1 One Breaker Application According to the CT requirements test results, to achieve through fault stability the K dimensioning factor must comply with the following expression: System conditions 2In < IF 64In 5 120 X/R K (CT dimensioning factor) K = 12 Knee point voltage VK 12 In (RCT + 2RL + Rr) Where: VK = Minimum current transformer knee-point voltage K = CT dimensioning factor Rct = Resistance of current transformer secondary winding ( ) RL = Resistance of a single lead from relay to current transformer ( ) Rr = Resistance of any other protective relays sharing the current transformer ( ) In = CT secondary nominal current (either 1A or 5) IF = maximum external single phase fault Table 21 - CT dimensioning factor To ensure that the quoted operating times and through fault stability limits are met the following ratios should not exceed a maximum disparity ratio of 7:1: Vk-HV / Rtot-HV : Vk-TN1 / Rtot-TN1 Vk-LV / Rtot-LV : Vk-TN2 / Rtot-TN2 Vk-TV / Rtot-TV : Vk-TN3 / Rtot-TN3 This ensures that during a through fault condition the flux density in the current transformers is not greatly different. Where: Vk-HV = Knee point voltage of CT at HV side Rtot-HV = Total burden connected to CT at HV side = (R CT + 2Rl + Rr) Vk-LV = Knee point voltage of CT at LV side Rtot-LV = Total burden connected to CT at LV side = (RCT+ 2Rl + Rr) Vk-TV = Knee point voltage of CT at TV side Rtot-TV = Total burden connected to CT at TV side = (RCT+ 2Rl + Rr) Vk-TN1 = Knee point voltage of TN1 CT Rtot-TN1 = Total burden connected to TN1 CT = (RCT + 2Rl + Rr) Vk-TN2 = Knee point voltage of TN2 CT Rtot-TN2 = Total burden connected to TN2 CT = (RCT + 2Rl + Rr) Page (AP) 6-146 P64x/EN AP/A62 (AP) 6 Application Notes Current Transformer Requirements Vk-TN3 = Knee point voltage of TN3 CT Rtot-TN3 = Total burden connected to TN3 CT = (RCT + 2Rl + Rr) 4.5.2 One and a Half Breaker Application and Autotransformer Application According to the CT requirements test results, to achieve through fault stability the K dimensioning factor must comply with the following expression: System conditions 2In < IF 64In 5 120 X/R Where: VK = K = Rct = RL = Rr = In = IF = K (CT dimensioning factor) K = 27 Knee point voltage VK 27 In (RCT + 2RL + Rr) Minimum CT knee-point voltage CT dimensioning factor Resistance of CT secondary winding ( ) Resistance of a single lead from relay to CT ( ) Resistance of any other protective relays sharing the CT ( ) CT secondary nominal current (either 1A or 5) maximum external single phase fault Table 22 - CT dimensioning factor To ensure that the quoted operating times and through fault stability limits are met the following ratios should not exceed a maximum disparity ratio of 4:1: Vk-HV / Rtot-HV : Vk-TN1 / Rtot-TN1 Vk-LV / Rtot-LV : Vk-TN2 / Rtot-TN2 Vk-TV / Rtot-TV : Vk-TN3 / Rtot-TN3 This ensures that during a through fault condition the flux density in the current transformers is not greatly different. Where: Vk-HV = Knee point voltage of CT at HV side Rtot-HV = Total burden connected to CT at HV side = (RCT + 2Rl + Rr) Vk-LV = Knee point voltage of CT at LV side Rtot-LV = Total burden connected to CT at LV side = (RCT+ 2Rl + Rr) Vk-TV = Knee point voltage of CT at TV side Rtot-TV = Total burden connected to CT at TV side = (RCT+ 2Rl + Rr) Vk-TN1 = Knee point voltage of TN1 CT Rtot-TN1 = Total burden connected to TN1 CT = (RCT + 2Rl + Rr) Vk-TN2 = Knee point voltage of TN2 CT Rtot-TN2 = Total burden connected to TN2 CT = (RCT + 2Rl + Rr) Vk-TN3 = Knee point voltage of TN3 CT Rtot-TN3 = Total burden connected to TN3 CT = (RCT + 2Rl + Rr) P64x/EN AP/A62 Page (AP) 6-147