©ISTOCKPHOTO.COM/SERGEYRYZHOV IMPROVEMENTS TO FAN EFFICIENCY OFFER ATTRACTIVE ROIs Examining the Benefits of Retrofitting Centrifugal Fan Rotors By Eranga Devasurendra THIS ARTICLE EXPLAINS HOW DIFFERENT FLOW CONtrol methods, inlet dampers versus variable frequency drives (VFDs), affect a fan’s efficiency and plant operating costs. Case studies provide an understanding of the data required to assess eligibility for fan efficiency retrofits. Opportunities for retrofit are practical when fans are oversized, processes are changed, or equipment is being added to the system. Benefits of energy-efficiency retrofits can be predicted from field studies and a return on investment (ROI) determined. Whether fan casing, ductwork, Digital Object Identifier 10.1109/MIAS.2018.2875211 Date of current version: 4 September 2019 and existing motors and motor components can be reused is considered in the cost analysis. Rebates and incentives from local utilities that can contribute funding to help provide the necessary returns are also explored. This article compares predicted ROI to actual field results. Nomenclature used throughout the article is given in Table 1. In an increasingly competitive marketplace, industrial facilities are constantly looking for an edge regarding production costs and reliability. Over the last few decades, this has manifested itself in various forms, with one of the primary buzzwords being energy-efficiency. The term itself conjures up images of wholesale changes to equipment, systems, and processes. However, there are steps that can 1077-2618/19©2019IEEE V E M B Eat R /D E C E M BE R 2 01from 9 IEEE IEEEXplore. IndustryRestrictions Applicationsapply. Magazine Authorized licensed use limited to: Technological Inst of the Philippines. Downloaded on OctoberNO 27,2023 10:16:31 UTC 55 Table 1. Nomenclature ACFM Actual cubic feet per minute; the volume of air moved per minute. AMCA Air Movement and Control Association International, Inc. Brake horsepower (BHP) A measure of the rate of energy expended. One BHP is equivalent to mechanical energy consumed at a rate of 33,000 ft lb/min. Fan damper An accessory installed at the fan inlet or outlet to modulate air volume. Impeller Another term for fan wheel. This is the rotating portion (less the shaft) of the fan designed to increase the energy level of the gas stream. Inches of water column (in-wc) A unit of measure of static pressure. ROI A measure of the amount of profit on an investment relative to the investment’s cost. Static efficiency Ratio of the fan power output to the power supplied to the fan. Static efficiency uses static pressure, which does not include the kinetic energy, to calculate the efficiency. It can be found by multiplying the mechanical efficiency by the ratio of fan static pressure to fan total pressure. Static pressure The measure of the potential energy of the airstream. In simpler terms, this is the resistance to airflow caused by air moving through a duct. relatively small investments that are paired with readily measurable metrics and highly desirable ROIs. Table 2 shows consolidated data from a survey by the U.S. Department of Energy and U.S. Census Bureau that highlight the potential annual savings at individual facilities in a wide cross section of industries [1]. This estimate examines only fan retrofits and does not include savings associated with improving the efficiency of the motors driving these systems or using VFDs instead of fan dampers for volume control. Factoring motor replacement and VFDs into the equation may increase project cost but could provide a significant boost to overall savings. Fans and System Resistance Fans are designed to deliver a specific amount of airflow at a designated static pressure. This required static pressure (or resistance to flow) is tied in to process ductwork and other equipment upstream and downstream of the fan. For a fan system, a value for airflow delivery cannot be discussed in a bubble without correlating it to a given static pressure. Figure 1 shows a typical fan performance curve including (a) airflow versus BHP and (b) airflow versus static pressure. Point A 1 simulates a duct system where there is no resistance to flow, which is referred to as wide 49-in Single-Width Backward-Inclined 700 r/min ρ = 0.075 lb/ft3 30 BHP be taken to address inefficiencies on the equipment side that do not require complete overhauls or disturbing the surrounding manufacturing ecosystem. Older centrifugal fans have proven to be one piece of the puzzle, requiring Table 2. The estimated annual power savings available per industry based on fan retrofits [1] Annual Savings per Facility for Fan Upgrades Paper mills US$695,000 Petroleum refining US$946,000 Industrial inorganic chemicals US$283,000 Paperboard mills US$492,000 Blast furnaces and steel mills US$358,000 Industrial organic chemicals US$91,000 Industrial gases US$116,000 Plastic material and resins US$121,000 Cement US$219,000 Pulp mills US$483,000 D2 C2 B2 A2 20 10 F2 (a) E1 5 F1 4 Static Pressure Industry E2 D1 3 C1 2 B1 1 0 A1 0 1 2 3 4 10,000 CFM (b) 5 6 FIGURE 1. Two graphs showing (a) airflow versus BHP and (b) airflow versus static pressure. Points A1 to F1 lie along the fan performance curve. Each point has a unique system resistance curve associated with it. 56 licensed IEEE use Industry Applications MagazineInst of Nthe OVPhilippines. EM B ER / D E C EDownloaded M BE R 2 01 9 on October 27,2023 at 10:16:31 UTC from IEEE Xplore. Restrictions apply. Authorized limited to: Technological open volume or free delivery. A fan will operate at the point where the system line intersects the fan curve. To generate the different test points shown (B 1 through F1), the system resistance had to be modulated by simulating resistance (i.e., back pressure in the test duct). Connecting the test points generates the fan performance curve. Point F1 is the point where the fan delivers no airflow and is purely generating pressure. This point is sometimes referred to as shut off or no delivery. As a result, each test point has a unique system resistance curve associated with it, and there is an infinite number of system lines between points A 1 and F1 . Oversized Fans and How to Identify Them performance (airflow, static pressure, and BHP) and comparing these results to the original fan curve. Finding the operating point and then comparing it to the as-designed fan curve will provide all the indicators necessary for determining the variations from design and the path to right-sizing the fan. How Oversized Fans Affect Power Consumption Once the conditions leading to oversized fans and how to identify them in operation are understood, it is important to consider the effect they have on power consumption. Table 3 summarizes the performance conditions of the installed fan shown in Figure 2. Although the increase in BHP may be considered minimal, the delivered flow is too high for the system, so an inlet damper is used to bring the flow back to Static Pressure (in-wc) Oversized fans are one of the biggest culprits in high operating costs and considered energy vampires in the industry. Although there are various reasons for fans being oversized (including process and equipment 50 changes over time), the biggest 45 System Resistance Curve contributor is conservative-design (as Designed) 40 engineering practices. These pracFan Curve System Resistance Curve 35 tices often lead to the specifica(as Installed) tion, purchase, and installation of 30 fans that exceed system require25 ments. Engineers include a margin 20 of safety in sizing fans to compen15 sate for uncertainties in the design process. Built-in contingencies for 10 Expected future system capacity increases Performance Actual Performance 5 that never actually materialize are 0 present as well. Figure 2 highlights 0 100,000 200,000 300,000 400,000 500,000 600,000 700,000 the effects of oversizing on a fan Airflow (ACFM) curve by showing how less-thananticipated static pressure require- FIGURE 2. A graph showing as-designed and as-installed system resistance curves for an ments shift the system resistance oversized fan installation. 50 45 Static Pressure (in-wc) to the right of the calculated values, producing more airflow during wide-open damper operation. A way to identify an oversized fan is to observe the operation of its inlet flow control devices. If inlet vanes and dampers remain partially closed through the lifetime of the fan, it is a glaring indication that the fan is producing more airflow than required. As a result, the system continually operates against an excessive load, and the fan’s operational cost is unnecessarily high [2]. Figure 3 shows the same fan from Figure 2 but dampered back to hit the flow required in the original design. Other ways to identify oversized fans involve air performance testing to get a snapshot of fan 40 Fan Curve 35 30 25 20 15 10 5 0 Damper Curve 0 100,000 200,000 300,000 400,000 500,000 600,000 700,000 Airflow (ACFM) FIGURE 3. A graph of the fan from Figure 2 with the addition of the performance curve resulting when an inlet damper is used to achieve original fan performance. V E M B Eat R /D E C E M BE R 2 01from 9 IEEE IEEEXplore. IndustryRestrictions Applicationsapply. Magazine Authorized licensed use limited to: Technological Inst of the Philippines. Downloaded on OctoberNO 27,2023 10:16:31 UTC 57 desirable system levels. As shown in Table 4, the use of an inlet damper to achieve this condition reduces the static efficiency from 84 to 66%. A common misconception here may cause one to say that the horsepower is only 1,560 BHP, so it’s actually lower than the estimated design horsepower of 1,800 BHP, and we’re saving money! While the point about horsepower is technically true, it neglects the underlying problem, which is that 8 in-wc of static pressure is absorbed by the damper operation to move the flow back from 360,000 to 310,000 ACFM. It’s this misuse of the static pressure that causes the large drop in static efficiency of the fan. Table 3. The performance comparison of fan as-designed versus installed with miscalculation of system resistance As-Designed Conditions As-Installed Conditions Flow (ACFM) 310,000 Flow (ACFM) 360,000 Static pressure (in-wc) 31 Static pressure (in-wc) 28 BHP 1,800 BHP 1,900 Static efficiency (%) 84 Static efficiency (%) 83 50 Static Pressure (in-wc) 45 40 Methodology for Improving Fan Efficiency To reduce the required flow, a new fan must be selected to match the new operating conditions. Once an efficiency opportunity has been identified, a full air performance test is conducted to benchmark the maximum requirements for the fan. At this point in the timeline, the estimates shown in Table 4 can be confirmed. The AMCA has helpful standards to assist in field-testing centrifugal fans, and most test contractors follow these guidelines to ensure consistency and repeatability of results. With this real-world data in hand, a fan manufacturer can start the process of identifying the required component changes. In the majority of cases, this can be done without replacing the entire fan assembly, which comes with its own set of challenges, including foundation and ductwork modifications. A new rotor with blades and dimensions that are conducive to the most efficient operation can be selected. Most of this modified operation is achieved by changes to the geometry of impeller components such as diameter, width, and blade angles. Figure 4 shows data from such a selection operating inside the original host fan casing. In this example, selecting the correct fan for this application revises the efficiency to the original intended design, and the resultant power consumption is lower than in the previous field operation that used an inlet damper. Table 5 is a summation of this new performance. The difference of 344 BHP (1,560−1,216) results in real energy savings. Assigning a Value to EnergyEfficiency Improvements Original Fan Curve 35 30 Original Damper 25 Curve New Retrofit Fan Curve 20 15 10 5 0 0 100,000 200,000 300,000 400,000 500,000 600,000 700,000 Airflow (ACFM) FIGURE 4. A graph of the fan from Figures 2 and 3 showing the performance curve after a rotor retrofit to resize the fan to match the original design flow. When touting energy-efficiency numbers, it’s important to be able to correlate them to real-world implications: namely, in megawatthours (MWh) per year. In the case of the fan under discussion, Table 6 illustrates this by demonstrating the annual energy consumption of the original fan system and the estimated savings from the retrofit. Right-sizing this fan would lead to a reduction of 2,135 MWh per year, which translates to a cost savings of US$143,045 Table 4. The performance condition using an inlet damper to restrict flow Table 5. The performance conditions after fan rotor retrofit Flow (ACFM) 310,000 Flow (ACFM) 310,000 Static pressure (in-wc) 21 Static pressure (in-wc) 21 BHP 1,560 BHP 1,216 Static efficiency (%) 66 Static efficiency (%) 84 58 licensed IEEE use Industry Applications MagazineInst of Nthe OVPhilippines. EM B ER / D E C EDownloaded M BE R 2 01 9 on October 27,2023 at 10:16:31 UTC from IEEE Xplore. Restrictions apply. Authorized limited to: Technological Table 6. The annual energy consumption and cost savings based on US$0.067/kWh [3] Table 7. A comparison of fan BHP to percentage of motor full load Existing System New System After Retrofit Case BHP Percentage of Motor Full Load Hours in operation per year 8,322 8,322 Original design 1,800 90 Fan energy usage (MWh/year) 9,681 7,546 As installed 1,900 95 Annual operating cost of fan $648,627 $505,582 Postretrofit 1,216 61 Energy savings from retrofit – 2,135 MWh/year Energy cost savings from retrofit – $143,045 a­ nnually. This savings can be used to calculate the ROI for such a project. Role of Motors and Variable Frequency Drives in Variable Load Operations motors, this is not usually a concern since the efficiency doesn’t drop off appreciably until the load percentage drops below 25% [4]. This does become an issue, however, when the full-load condition represents 61% of motor full load, and this percentage continues dropping for lower-load conditions. In such cases, the ideal solution with regard to efficiency and long-term operation is to replace the existing motor with one that is appropriately sized for the maximum operating condition. Static Pressure Power (in-wc) Power (hp) The discussion so far has focused on fans operating at peak load. However, for most facilities, there are variable load requirements dependent on factors such 1,400 100% as production demand. In these 1,200 instances, fans can operate in a 80% 1,000 high-/low-load capacity, or they can P1 60% 800 have a multitude of conditions in 40% P2 20% between. The go-to method for con600 0% trolling these variable loads is the 400 use of inlet and outlet dampers. As 200 noted from the preceding examples, 0 static efficiency drops off drastically 30 once a damper moves away from a completely open operation. As a 25 result, the annual energy cost sav20 ings will need to be recalculated with the values of power consump15 tion tied to number of hours of operP1 10 ation at that given load. Depending P2 on how often the fan runs at reduced 5 loads, the estimated annual savings 0% 20% 40% 60% 80% 100% 0 from Table 6 will be lower. 0 100,000 200,000 300,000 400,000 500,000 While the role of electrical effiVolume (ACFM) ciency has been downplayed in Power System Resistance Static Pressure this analysis, it does come into play once we start looking at low-load conditions after a retrofit in which Ratings: Rating Point P1 P2 the original motor was not downVolume (ACFM) 310,000 260,000 215,000 Static Pressure (in-wc): 21 15 10 sized. Table 7 compiles this informaDensity (lb/ft3): 0.046 0.046 0.046 tion using an assumed motor size of Temperature (°F): 320 320 320 2,000 hp for the original fan. Speed (r/min): 1,180 1,180 1,180 As evident in Table 7, the mechanBHP: 1,216 987 829 ical efficiency of the retrofit is 84%, Static Efficiency (%): 84 62 41 but the motor is actually operating at only 61% of its full-load capability. For larger, high-efficiency FIGURE 5. Two graphs showing performance curves for a fan operating with inlet box dampers. V E M B Eat R /D E C E M BE R 2 01from 9 IEEE IEEEXplore. IndustryRestrictions Applicationsapply. Magazine Authorized licensed use limited to: Technological Inst of the Philippines. Downloaded on OctoberNO 27,2023 10:16:31 UTC 59 Conclusions 1,400 Power (hp) 1,200 1,180 r/min 1,000 800 1,010 r/min P1 600 829 r/min 400 P2 Static Pressure Power (in-wc) 200 0 30 25 20 15 P1 10 P2 5 0 829 r/m 0 100,000 in 1, 10 18 r/m in 200,000 300,000 400,000 Volume (ACFM) Static Pressure Ratings: Volume (ACFM) Static Pressure (in-wc): Density (lb/ft3): Temperature (°F): Speed (r/min): BHP: Static Efficiency (%): 1,0 Power Rating Point 310,000 21 0.046 320 1,180 1,216 84 0 r/m in 500,000 System Resistance P1 260,000 15 0.046 320 1,010 758 81 P2 215,000 10 0.046 320 829 418 81 Fan systems are critical components in industrial plant operations. A significant portion of all energy consumed by motor-driven equipment in manufacturing facilities is for process fans and air distribution [1], [2]. Because of their critical nature in supporting production, many of these industrial fans operate continuously, with their only downtime being scheduled maintenance. Run times of this nature mean that they contribute heavily to energy consumption and the overall annual operating expenditure for a plant. With electricity costs being a quantity that’s relatively easily measured, improvements to fan efficiency reduce plant operating expenditures. Retrofitting an existing fan versus replacing the entire unit yields a payback period that is not just attractive but a repeat source of savings for years to come. Finally, variable speed operation of the fan system offers additional energy-efficiency gains by eliminating the dampers needed for reduced flow operating points. Author Information Eranga Devasurendra (edevasuren dra@clarage.com) is with Twin City FIGURE 6. Two graphs showing performance curves for the fan from Figure 5 operating with a Clarage, LLC, Pulaski, Tennessee. This VFD instead of inlet box dampers. article first appeared as “Consider the Benefits of Retrofitting Centrifugal To further fine-tune the efficiency calculation, it be­­ Fan Rotors” at the 2018 IEEE-IAS/PCA Cement Industry comes necessary to address the inefficiency of continuing Conference. It was reviewed by the IAS Cement Industo use inlet dampers after a retrofit to control flow. To try Committee. recap: we’ve been able to resize the fan at its high-load point to 84% mechanical efficiency but forced to settle for References [1] U.S. Office of Energy Efficiency and Renewable Energy. (2002) “United lower efficiencies at low-load conditions. This is where States industrial electric motor systems market opportunities assessthe use of variable speed, specifically a VFD, enters the ment: Executive summary.” U.S. Dept. of Energy Office of Industrial Tech. discussion. A VFD can modulate the speed of a motor to Olympia, WA. [Online]. Available: http://tinyurl.com/nacewxn [2] U.S. Department of Energy’s Industrial Technologies Program and achieve results identical to those of an inlet damper. The Air Movement and Control Association International, Inc., “Improving one glaring difference is that there is no wasted static presfan system performance: A sourcebook for the industry,” U.S. Dept. of sure loss across the operation of the damper. Figures 5 Energy, Washington, DC, Rep. DOE/GO-102003-1294, 2003. [Online]. Available: https://www.energy.gov/sites/prod/files/2014/05/f16/fan and 6 show curves that contrast a retrofit option operating _sourcebook.pdf with inlet box dampers to one operating with a VFD. [3] T. Persful and E. Rogers, “Opportunities and financial incentives Although there is no variation in the high-load efficienabound for industrial fan retrofits,” ASHRAE J. Suppl. AMCA Intl. Inmotion, pp. 8–11, July 2014. cy, it’s clear that speed control yields superior efficiency [4] U.S. Department of Energy, “Determining electric motor load and across the operating range for low loads. Coupled with efficiency,” 1997. Accessed on: Dec. 12, 2017. [Online]. Available: https:// the appropriately sized motor, the gains in both mechaniwww.energy.gov/sites/prod/files/2014/04/f15/10097517.pdf cal and electrical efficiency are vastly greater when using speed control with a rotor retrofit. 60 licensed IEEE use Industry Applications MagazineInst of Nthe OVPhilippines. EM B ER / D E C EDownloaded M BE R 2 01 9 on October 27,2023 at 10:16:31 UTC from IEEE Xplore. Restrictions apply. Authorized limited to: Technological