Conduit Fabrication, Level II Lesson 3 Use for Questions 20 through 37 For the remaining problems in this lesson, you will use the bender chart shown. Allow an additional half-inch of length for the threads in any of the problems which require an additional length of conduit to go into a junction box or conduit fitting. Keep in mind that in the field it might be necessary to add significantly more than this amount. TRAVEL Degrees 90 45 30 22.5 15 10 5 Take-Up - Gain = Setback Radius Adj. 45° ½" RMC 615/16" 3 ½" 2 5/16" 1¾" 11/8" ¾" 3 /8" 8¼" 3 5¼" 4" Greenlee 555 ¾" RMC 7 3/16" 3 9/16" 2 3/8" 113/16" 13/16" 13 /16" 3 /8" 8¼" 3¼" 5" 41/8" 1" RMC 9 1/8" 4 9/16" 31/16" 2¼" 1½" 1" ½" 13 9 /16" 4 1/8" 511/16" 4¼" 1¼" RMC 117/16" 5 ¾" 313/16" 2 7/8" 17/8" 1¼" 5 /8" 12 9/16" 5 ¼" 7 5/16" 5½" ©NJATC