Uploaded by esalumbides

ag1016 (1)

advertisement
ACI/CRSI COMMITTEE CORRESPONDENCE
Address writer at:
Concrete Reinforcing Steel Institute
933 N. Plum Grove Road
Schaumburg, IL 60173-4758
Tel: (847) 517-1200 Ext. 15
Fax: (847) 517-1206
E-mail: afelder@crsi.org
October 18, 2016
To:
Members ACI/CRSI Committee 315 - Details of Concrete Reinforcement
Voting Members:
Mark Agee
Gregory P. Birley
Richard H. Birley
David A. Grundler
Robert W. Hall
Todd R. Hawkinson
Dennis L. Hunter
David W. Johnston
Mahmoud E. Kamara
William M. Klorman
Douglas D. Lee
Mustafa A. Mahamid
Javed B. Malik
Christopher J. Perry
Curtis Yokoyama
Peter Zdgiebloski
Associate/Consulting/Subcommittee Members:
Paul J. Brienen
Larry Campbell
Grant Doherty
Pedro Estrada
Christopher Evans
Dennis J. Fontenot
Peter Fosnough
David P. Gustafson
Garrick N. Goldenberg
Paul Gordon
James S. Lai
Amadeus L. Magpile
Harold E. Reed
Dale Rinehart
From:
Anthony L. Felder
Secretary
Subject:
Meeting Notice and Agenda
October 23, 2016
Philadelphia Marriott Downtown
Philadelphia, PA
Thomas G. Schmaltz
William G. Sebastian
Avanti C. Shroff
Richard W. Stone
Richard D. Thomas
Farahad Zahedi
Our next meeting will be held on Sunday, October 23, 2016 from 2:00 p.m. to 5:00 p.m. in
Independence Ballroom 1 of the Philadelphia Marriott Downtown in Philadelphia, PA.
A proposed agenda is attached.
Copy to:
Harry A. Gleich, TAC Contact
Matthew R. Senecal, ACI Engineering Manager
c:\users\afelder\documents\aci\315\agnd\ag1016.doc
AGENDA
ACI/CRSI COMMITTEE 315 - DETAILS OF CONCRETE REINFORCEMENT
Philadelphia Marriott Downtown, Philadelphia, PA
October 23, 2016
2:00 – 5:00 p.m.
Independence Ballroom 1
1. 2:00 p.m. - Call Meeting to Order
2. Self-Introductions
3. Approval of Minutes of Last Meeting, April 17, 2016, Distributed June 1, 2016
4. Review Committee Membership. See First Exhibit, Current Roster.
5. Review Purpose of “Designer’s Guide to Reinforcing Bar Detailing”
6. Status Reports
a. ACI 131 BIM / CRSI BIM - David Grundler / Dennis Fontenot
b. CRSI Detailing - Robbie Hall
c. CRSI Standards (Placing, Fabrication, Supports) - Robbie Hall
7. Review Table of Contents
8. Documents for Review (Exhibits Attached)
a. Chapter 1 – Introduction and Scope
b. Chapter 2 – Notation and Definitions
c. Chapter 3 – General Considerations
d. Chapter 4 – Structural Drawings
e. Chapter 5 – Designing for Constructability
f. Chapter 6 – Review of Placing Drawings
9. Review of Task Group
10. Discuss Steps Going Forward
11. New Business
12. Motion to Adjourn
ACI/CRSI COMMITTEE 315 ROSTER
October 2016
Richard H. Birley, Chairman
Retired
24520 Fraser Hwy
Langley, British Columbia V2Z 2L1
Tel: 604/318-6750
Fax:
E-mail: dick.birley@gmail.com
Paul J. Brienen*
Brienen Structural Engineers, PS
1316 Central Ave S
Kent, WA 98032-7431
Tel: 206/397-0000
Fax:
E-mail: pbrienen@bse-ps.com
Anthony L. Felder, Secretary
Concrete Reinforcing Steel Institute
933 N. Plum Grove Road
Schaumburg, IL 60173-4758
Tel: 847/517-1200
Fax: 847/517-1206
E-mail: afelder@crsi.org
Larry Campbell*
CMC Construction Services
5913 Diamond Oaks Ct
Haltom City, TX 76117-2802
Tel: 214/920-2799
Fax:
E-mail: larry.campbell@cmc.com
Harry A. Gleich, TAC Contact
Metromont Corporation
PO Box 2486
Greenville, SC 29602-2486
Tel: 864/605-5063
Fax:
E-mail: hgleich@metromont.com
David H. DeValve*
Oklahoma Steel & Wire
1041 S. 1st
Madill, OK 73446-0220
Tel: 580/795-6007
Fax: 580/795-7422
E-mail: ddevalve@oklahomasteel.com
Mark D. Agee
Whitacre Engineering Co.
8215 Hidden Glen Ave NE
Cnton, OH 44721-1746
Tel: 330/455-8503
Fax:
E-mail: magee@werebar.com
Grant Doherty*
Martin Martin Inc.
12499 W. Colfax Ave
Lakewood, CO 80215-3720
Tel: 303/ 431-6100
Fax:
E-mail: gdoherty@martinmartin.com
Gregory P. Birley
Condor Rebar Consultants
800-885 Dunsmuir St
Vancouver, British Columbia V6C 1N5
Tel: 604/692-2168
Fax: 604/689-9206
E-mail: greg.birley@condor-rebar.com
Pedro Estrada*
PEG Ingenieria C A
88-60 Calle Los Guayos
Urb Trigal Centro
Valencia 2001 Venezuela
Tel: 58-241 8428964
E-mail: pestradag@gmail.com
* - Associate Member
** - Consulting Member
*** - Subcommittee Member
ACI/CRSI Committee 315
October 2016
Page 2
Dennis J. Fontenot*
Commercial Metals Company
12001 Mystic Forest Ln
Austin, TX 78739-4813
Tel: 512/523-3398
Fax:
E-mail: dennis.fontenot@cmc.com
Robert W. Hall
Gerdau
1255 Lakes Parkway, Ste. 325
Lawrenceville, GA 30043-5818
Tel: 678/367-6036
Fax: 678/367-6001
E-mail: Robbie.Hall@gerdau.com
Peter Fosnough*
Harris Rebar
1342 S Grandstaff Dr.
Auburn, IN 46706-2661
Tel: 260/572-1227
Fax: 260/925-3152
E-mail: pfosnough@harrisrebar.com
Todd R. Hawkinson
Wire Reinforcement Institute
323 Fox Briar Lane
Ballwin, MO 63021-6151
Tel: 314/807-4386
Fax: 636/227-3776
E-mail: todd@hawkinsonassociates.com
Garrick N. Goldenberg*
Chappell Engineering Associates LLC
26 Tisdale Dr.
Dover, MA 02030-1600
Tel: 508/481-7400
Fax: 508/481-7406
E-mail: garrickg@wit.edu
Dennis L. Hunter
Gerdau
3915 Riga Blvd
Tampa, FL 33619-1345
Tel: 813/740-3301
Fax: 813/740-3401
E-mail: dennis.hunter@gerdau.com
David A. Grundler
Applied Systems Associates
5270 Logan Ferry Road
Murrysville, PA 15668-9727
Tel: 724/733-8700
Fax: 724/325-5553
E-mail: David.Grundler@asahq.com
David W. Johnston
North Carolina State University
Civil Engineering Department
Raleigh, NC 27695-0001
Tel: 919/515-7412
Fax: 919/515-7908
E-mail: johnston@ncsu.edu
David P. Gustafson
Consultant
42845 N Berrong Ct
Winthrop Harbor, IL 60096-1013
Tel: 847/731-3585
Fax:
E-mail: davidgustafson1@att.net
Mahmoud E. Kamara
StructurePoint
2021 N Charter Point Dr.
Arlington Heights, IL 60004-7258
Tel: 847/259-5499
Fax:
E-mail: mekamara10@hotmail.com
* - Associate Member
** - Consulting Member
*** - Subcommittee Member
ACI/CRSI Committee 315
October 2016
Page 3
William M. Klorman
W M Klorman Const Corp.
23047 Ventura Blvd, 2nd Floor
Woodland Hills, CA 91364-1146
Tel: 818/591-5969
Fax: 818/591-5926
E-mail: bklorman@klorman.com
Javed B. Malik
Jacobs Engineering Group
5985 Rogerdale Rd
Houston, TX 77072-1601
Tel: 281/776-2540
Fax: 281/776-2501
E-mail: javed.malik@jacobs.com
James S. Lai*
Lai Associates
PO Box 517
La Canada Flintridge, CA 91012-0517
Tel: 818/790-5475
Fax:
E-mail: jslai@sbcglobal.net
Christopher J. Perry
Perry & Associates, LLC
221 N LaSalle St., Ste. 3100
Chicago, IL 60601-1513
Tel: 312/364-9112
Fax: 312/364-9163
E-Mail: cjperry@PerryLLC.com
Douglas D. Lee
Douglas D. Lee & Associates
6150 Foxglove Court
Fort Worth, TX 76112-1106
Tel: 817/457-7030
Fax: 817/457-8970
E-mail: ddlee4836@sbcglobal.net
Harold E. Reed***
Davis Wire
85139 Appletree Dr.
Eugene, OR 97405-9702
Tel: 541/912-3195
Fax:
E-mail: halreed9@gmail.com
Amadeus L. Magpile**
Barlines Rebar Est. & Det.
2871 W. Carson St.
Torrance, CA 90503-6068
Tel: 310/618-8402
Fax: 310/618-8394
E-mail: amagpile@barlines.com
Dale Rinehart**
Sierra Rebar LLC
10480 E 96th Ave.
Henderson, CO 80640
Tel: 303/558-0015
Fax: 720/358-4101
E-mail: drinehart@sierrarebar.com
Mustafa A. Mahamid
University of Illinois at Chicago
842 W Taylor St
Chicago, IL 60607-7021
Tel: 312/355-0364
Fax:
E-Mail: mmahamid@uic.edu
Thomas G. Schmaltz**
Precision Rebar & Accessories, Inc.
1712 NE 99th Street
Vancouver, WA 98665-9018
Tel: 360/574-1022
Fax: 503/224-7414
E-mail: jerry@precision-rebar.com
* - Associate Member
** - Consulting Member
*** - Subcommittee Member
ACI/CRSI Committee 315
October 2016
Page 4
William G. Sebastian**
American Rebar Detailing, LLC
543 Wright Loop
Williamstown, NJ 08094-1224
Tel: 856/728-6645
Fax: 856/728-0088
E-mail: wsebastian@comcast.net
Farshad Zahedi*
Babol Noshirvani University of Tech
Shariati Avenue, Moalem 4, White House
Babol, Mazandaran Iran
Tel: +9809111170600
Fax:
E-mail: farshad.zahedi@gmail.com
Avanti C. Shroff**
Iffland Kavanagh Waterburry
2 Penn Plaza, Ste 603
New York, NY 10121-0101
Tel: 212/946-2300
Fax: 212/302-4645
E-mail: avantishroff@comcast.net
Peter Zdgiebloski
CMC Rebar
300 SMI Way
Farmville, VA 23901-3180
Tel: 434/522-8311
Fax: 434/929-1964
E-mail: peter.zdgiebloski@cmc.com
Richard W. Stone*
Richard W. Stone, PE Inc.
1523 Richard Dr.
West Chester, PA 19380-6332
Tel: 484/639-5511
Fax:
E-mail: rwstone1523@gmail.com
Richard D. Thomas**
CMC Rebar Florida
2665 Prince St.
Fort Myers, FL 33916-5527
Tel: 239/337-3480
Fax: 239/337-3542
E-mail: dale.thomas@cmc.com
Curtis R. Yokoyama
Fluor
23 Danta
Rancho Santa Margarita, CA 92688-1514
Tel: 949/349-4118
Fax:
E-mail: curtis.yokoyama@fluor.com
* - Associate Member
** - Consulting Member
*** - Subcommittee Member
AMENDED Working Draft
ACI Committee 315
Details of Concrete Reinforcement
Oct 5, 2016
CHAPTER 1 – INTRODUCTION AND SCOPE
1.1—General
1.2—Scope
(Mandated by TCM)
CHAPTER 2 – NOTATION AND DEFINITIONS (Mandated by TCM)
2.1—Notation
2.2—Definitions
CHAPTER 3 – GENERAL CONSIDERATIONS
3.1—Building Information Modeling (BIM)
3.1.1—Introduction to Building Information Modeling
3.1.2—Level of Development
3.1.3—Benefits of BIM
3.1.4—IFC Files and BIM File Transfers
3.1.5—State of the Technology
3.2—Tolerances
3.2.1—Introduction and ACI 117
3.2.2—Concrete Cover for Reinforcement
3.2.3—Spacing of Reinforcement
3.2.4—Placing of Reinforcement
3.2.4.1—General Information
3.2.4.2—Tolerance Cloud
3.2.4.3—Design Considerations
3.2.5—Reinforcing Bar Fabrication
3.2.5.1—General Information
3.2.5.2—Restrictive Tolerances
3.2.5.3—Fabrication Tolerance Clouds
3.2.5.4—Design Considerations
3.2.6—Forming Tolerances
3.2.6.1—General Information
3.2.6.2—Forming Tolerance Clouds
3.2.7—Confined Reinforcing Bars
3.2.8—Accumulated (Combined) Tolerances
3.3—General Cautions
3.3.1—Revisions of Drawings
3.3.2—Dimensioning
3.3.3—Field Cutting of Bars
3.3.4—Field Bending of Bars
3.3.5—Mechanical Connectors
3.3.6—Mixing Grades of Steel on a Project
CHAPTER 4 – STRUCTURAL DRAWINGS
4.1—Scope
4.2—General
4.3—Order of Sheets
4.4—General Notes Sheets
4.4.1—Codes and Standards
4.4.2—Design Loads
4.4.3—Specifications
4.4.4—Concrete Notes
4.4.5—Reinforcement Notes
4.4.5.1—ACI 318 Reinforcing Requirements
4.4.5.2—Development and Splices
4.4.5.3—Supports for Reinforcing Bars
4.4.5.4—Weldability of Bars
4.4.5.5—Hooks and Bends
4.4.5.6—Welded Wire Reinforcement
1 of 3
AMENDED Working Draft
ACI Committee 315
Details of Concrete Reinforcement
Oct 5, 2016
4.4.6—Construction Notes
4.4.7—Inspection Notes
4.5—Plan Sheets
4.5.1—Plan Graphics and Member Geometry
4.5.2—Reinforcement on Plan Views
4.6—Elevation Sheets
4.7—Section Sheets
4.8—Large Scale View Sheets
4.9—Detail Sheets
4.10—Schedule and Diagram Sheets
4.10.1—Slab Schedules
4.10.2—Beam and Girder Schedules
4.10.3—Column Schedules
4.10.4—Wall Schedules
4.11—Foundation Sheets and Schedules
4.12—User Defined Sheets
4.13—3D Representations
CHAPTER 5 – DESIGNING FOR CONSTRUCTIBILITY
5.1—Defining Requirements for Cover, Development, Splices and Clearance
5.1.1—Clear Cover
5.1.2—Bar Development
5.1.3—Bar Splices
5.1.4—Clearance Between Bars
5.2—Defining Bar Placing Configuration
5.2.1—Staggered Laps
5.2.2—Embedment into Support
5.2.3—Bar Dimensioning
5.2.4— Skewed Bars
5.2.5—Termination of Vertical Bars
5.2.6—Beam Stirrups
5.3—Foundations
5.3.1—Types
5.3.2—Bar Arrangements
5.3.3—Layering
5.3.4—Construction and Expansion Joints
5.4—Walls
5.4.1—Introduction
5.4.2—Scope
5.4.3—General
5.4.4—Considerations
5.4.5—Best Practices
5.4.5.1—Footing to Wall Connections
5.4.5.2—Corners and Intersections
5.4.5.3—Steps and Sectional Transitions
5.4.5.4—Multiple Curtains and Layers
5.4.5.5—Construction Joints, Contraction Joints, Expansion Joints and Waterstops
5.5—Columns
5.5.1—Vertical Bar Arrangement
5.5.2—Ties
5.5.3—Detail at Steps and Transitions
5.5.4—Laps
5.5.5—Termination of Vertical Bars
5.6—Beams
5.6.1—Layering of Beam Bars at Intersections
5.6.2—Layering of Slab Bars at Beam Intersections
5.6.3—Depth of Beams at Intersections
5.6.4—Tie Arrangements
5.6.5—Arrangement of Longitudinal Bars
2 of 3
AMENDED Working Draft
ACI Committee 315
Details of Concrete Reinforcement
Oct 5, 2016
5.6.6—Beam Steps
5.6.7—Special Details
5.6.8—Beam Schedules
5.7—Slabs
5.7.1—Bottom Bars
5.7.2—Top Bars
5.7.3—One-Way Slabs
5.7.4—Two-Way Slab
5.7.5—Edges and Openings
5.7.6—Steps and Depressions
5.7.7—Stud Rails, etc.
CHAPTER 6 – PLACING DRAWINGS
6.1—Definition
6.2—Overview
6.3—Procedure
6.4—Reviewing Placing Drawings
6.4.1—Benefits of Review
6.4.2—Review Process
6.4.3—Checklists for Review of Placing Drawings
6.5—Levels of Approval
REFERENCES
APPENDIX A – REPRESENTATIVE DRAWINGS
A.1—Building Foundation
A.2—Building Superstructure
A.3—Building Seismic Example
A.4—Maybe Some Other Example
3 of 3
1
CHAPTER 1—INTRODUCTION AND SCOPE
2
1.1—General
3
“ACI Designer’s Guide to Reinforcing Bar Detailing” is not intended to instruct the LDP how to detail
4
rebar. Its purpose is to show LDPs the information a reinforcing bar detailer needs to properly detail rebar and
5
how to present that information on their structural drawings so that his design intent is effectively and accurately
6
conveyed.
7
It is hoped that information in this guide on structural members of reinforced concrete structures will
8
advance standardization through the detailing, fabrication, and installation of concrete reinforcement. The
9
information presented herein complies with the requirements of the following ACI committees:
10

ACI 318 – Building Code Requirements for Structural Concrete
11

ACI 301 – Specifications for Structural Concrete
12

ACI 117 – Tolerances
13

ACI 131 – Building Information Modeling for Concrete Structures
14

ACI 132 – Responsibilities in Concrete Construction
15
16
This guide is intended to facilitate clear communication between LDP’s, reinforcing bar detailers,
fabricators, and placers by encouraging standard presentation of details and information.
17
18
19
1.2—Scope
This guide provides both general and specific information and illustrative details that are required by
20
reinforcing steel detailers in steel reinforced concrete members such as slabs, beams, and columns. It stresses the
21
importance of this information to ensure that the detailer effectively and accurately captures the intent of the LDP
22
and presents it in a manner that is clear and unambiguous to the rebar fabricator and placer.
1
1
CHAPTER 2—NOTATION AND DEFINITIONS
2
1.1—Notation
3
4
5
2.0—Definitions
6
ACI provides a comprehensive list of definitions and terminology through an online resource:
7
“CT-13: ACI Concrete Terminology - An ACI Standard”
8
It can be downloaded without charge from the ACI website at :
9
https://www.concrete.org/store/productdetail.aspx?ItemID=CT13
1
1
CHAPTER 3—GENERAL CONSIDERATIONS
2
3.1 —Building Information Modeling (BIM)
3
4
3.1.1 Introduction to Building Information Modeling
5
Building information modeling (BIM) is a 3D process used to generate and manage digital
6
models of buildings and other constructed infrastructure. This process is used by those who plan,
7
design, construct and manage facilities. The process involves creating and maintaining intelligent
8
models that represent physical characteristics of a facility, and also contain parametric data about the
9
elements within the model. Numerous software packages exist that fall within the definition of BIM,
10
and each of these have distinct advantages to different parts of the life cycle of a facility, from the design
11
to construction through operation.
12
13
Although the focus of most BIM discussions centers on the 3D model, the information contained
within is of equal importance. The following is from NBIMS 2007:
14
“(A) Building Information Model, or BIM, utilizes cutting edge digital technology
15
to establish a computable representation of all of the physical and functional
16
characteristics of a facility and its related project/lift-cycle information, and is
17
intended to be a repository of information…”
18
In general, what makes BIM more than a simple 3D model is the information. BIM should be
19
thought of not only as a full size virtual mock-up of a structure, but also as a database of included
20
information.
21
BIM is applied to the details of concrete reinforcement in both the design and construction
22
phases of a facility. In the design phase, BIM is often used by the design team to define the physical
23
characteristics of the concrete to be reinforced by defining concrete edges in physical space, and
1
24
reinforcement information by the use of either data within the concrete elements or physical
25
representations of the reinforcement. This definition of concrete and reinforcement information is often
26
to a ‘design intent’ level of modeling. In the construction phase, the concrete geometry is often defined
27
to a construction level of detail, and the reinforcement is defined to a level from which it can be
28
fabricated and installed.
29
30
3.1.2 Level of Development
31
The content and reliability of a Building Information Model is defined by an industry standard referred
32
to as the Level of Development (LOD).
33
Specification to standardize these definitions. From BIMForum [Provide Reference]:
The AIA and BIMForum have developed the LOD
34
“The Level of Development (LOD) Specification is a reference that enables
35
practitioners in the AEC Industry to specify and articulate with a high level of
36
clarity the content and reliability of Building Information Models (BIMs) at various
37
stages in the design and construction process. The LOD Specification utilizes the
38
basic LOD definitions developed by the AIA for the AIA G202-2013 Building
39
Information Modeling Protocol Form[1] and is organized by CSI Uniformat
40
2010[2]. It defines and illustrates characteristics of model elements of different
41
building systems at different Levels of Development. This clear articulation allows
42
model authors to define what their models can be relied on for, and allows
43
downstream users to clearly understand the usability and the limitations of models
44
they are receiving. The intent of this Specification is to help explain the LOD
45
framework and standardize its use so that it becomes more useful as a
46
communication tool. It does not prescribe what Levels of Development are to be
2
47
reached at what point in a project but leaves the specification of the model
48
progression to the user of this document.”
49
50
51
52
53
3.1.3 Benefits of BIM
The benefits of using BIM are numerous and vary from project to project and depending on
where in the design/construction process it is utilized. Potential benefits include:

Design and Detailing
54
o Better visualization, especially when dealing with complex structures.
55
o Improved coordination between trades through the sharing of information, which is
56
one of the tenets of BIM.
57
o Ability to easily provide multiple ‘what-if’ scenarios.
58
o Improved communications and efficiency and reduced errors through:

59
60
Addressing items earlier in the process, thereby reducing the number of RFI’s
and issues in the field.

61
Clearer communication of structural geometry and design intent from the
62
engineer to the reinforcement detailer than that which is possible using
63
traditional 2D documents.
64

Reinforcing details presented in 3D at a construction level of development.
65

Better communication of reinforcement fabrication and placement information
66
67
68
69
to downstream entities.

Construction
o Enhanced project visualization made possible my having full building models and
related information at your fingertips.
3
70
o More accurate material take-offs, leading to less waste and reduced overall project
71
costs.
72
o Improved project coordination, clash detection and resolution achieved by combining
73
3D models from various sub-contractors into a single consolidated model.
74
o 4D Schedule simulation animations produced by combining the 3D model with a
75
76
77
78
79
80
81
82
83
construction schedule.

Operation
o Better ‘as-built’ documentation than conventional 2D drawings, leading to easier
remodels, rebuilds and additions.
o Improved management of a building’s lifecycle achieved by using the 3D model as a
central database of all of the building’s systems and components.
o Enhanced tracking of building maintenance needs.
3.1.4 IFC Files and BIM File Transfers
Numerous BIM software packages exist that are capable of defining concrete geometry and data,
84
detailing reinforcement, or both.
Most BIM software is compatible with an open file format
85
specification know as Industry Foundation Classes (IFC) data models. This is an object-based file
86
format that allows ease of interoperability between software platforms. IFC files are able to be exported
87
from and imported into most BIM software platforms, allowing model content created in different
88
software to be viewed and used in other software.
89
90
3.1.5 State of the Technology
91
BIM has been around since the late 1990s , but one characteristic makeing it different from past
92
technologies is its openness to continuous change and evolution. The State of BIM adoption and use
4
93
varies with companies, industry segments and regions, but it has been expanding. The introduction of
94
tablet computers, laser scanning, drones, 3D printers, and more all have had a role in shaping where
95
BIM is today and where it is going. One large focus for the evolution of BIM is improving the ability of
96
different users applying different tools to utilize the information in the database. Most BIM software
97
products are compatible with opening IFC format databases, but each still interprets the data differently
98
leading to differences and errors when applying this method at this time. The improvement focus is not
99
only intended for designer to designer transfer, there has also been much effort in developing ways to
100
transfer the data for downstream fabrication uses allowing structural steel, pipe and duct, and even rebar
101
fabricators the ability to seamlessly utilize the information from the BIM directly on the fabrication line
102
of these elements.
103
104
3.2 —Tolerances
105
3.2.1 Introduction and ACI 117
106
ACI 301 requires that construction tolerances comply with ACI 117.
ACI 117 provides
107
tolerances for concrete construction, including tolerances for concrete forming, reinforcing bar
108
fabrication and placement. These tolerances can have an effect on cover, strength, constructability, and
109
serviceability but are required to make concrete construction physically possible and economically
110
practical. If more restrictive tolerances are required than those shown in ACI 117, they need to be
111
clearly indicated in the construction documents.
112
In areas of potential congestion, the LDP must consider combinations of tolerances, namely
113
reinforcing bar fabrication, reinforcing bar placement and formwork.
114
tolerances can result in conflicts that are not simple to remedy in the field. For instance, the “+”
115
tolerance for a bent bar may cause the bar to encroach into the concrete cover and exceed the “-”
5
Certain combinations of
116
tolerance for that cover. The design/construction team must be aware of tolerances and work to identify
117
and remove conflicts prior to construction.
118
3.2.2 Concrete cover for reinforcement
119
ACI 301 and ACI 318 define concrete cover requirements for reinforcement. Concrete cover as
120
protection of reinforcement against weather and other effects is measured from the concrete surface to
121
the outermost surface of the steel to which the cover requirement applies. ACI 117 defines tolerances for
122
concrete cover (measured perpendicular to the concrete surface). There are two measurements for
123
concrete cover as shown in Fig. 3.2.2:
124

Face Cover – measured from the face or surface of a bar to the concrete surface
125

End Cover – measured from the end of a bar (straight or hooked) to the concrete surface
126
127
Fig. 3.2.2—Face cover and end cover for reinforcement
128
Face cover values defined by ACI 301 and ACI 318 vary based on exposure conditions and the
129
concrete element the bar is in. End cover values are simplified in industry practice based on code
130
definition, rather than an actual code definition. Generally, end cover provided in practice is 2 in. unless
131
required to be to be 3 in. (3 in. when cast against earth, 2 in. everywhere else).
132
Where concrete cover is prescribed for a class of structural members, it is measured to the outer
133
edge of stirrups, ties, or spirals if transverse reinforcement encloses main bars; to the outermost layer of
134
bars if more than one layer is used without stirrups or ties; to the metal end fitting or duct on post6
135
tensioned prestressing steel; to the outer edge of mechanical splices; or to the outermost part of the head
136
on headed bars.
137
The condition “concrete surfaces exposed to earth or weather” refers to direct exposure to
138
moisture changes and not just to temperature changes. Slab or thin shell soffits are not usually
139
considered directly exposed unless subject to alternate wetting and drying, including that due to
140
condensation conditions or direct leakage from exposed top surface, run off, or similar effects.
141
142
143
3.2.3 Spacing of reinforcement
144
The spacing of reinforcement needs to comply with the project drawings, but there are times
145
where the spacing will need to differ due to field conditions, accumulating tolerances and/or
146
coordination of concrete reinforcement and other embedded items. ACI 117 defines tolerances for the
147
spacing of reinforcement.
148
The reinforcement spacing tolerance consists of an envelope with an absolute limitation on one
149
side of the envelope determined by the limit on the reduction in distance between reinforcement. In
150
addition, the allowable tolerance on spacing should not cause a reduction in the specified number of
151
reinforcing bars used.
152
Designers are cautioned that selecting element sizes that exactly meet their design requirements
153
may not allow for reinforcement placement tolerance. This sometimes happens when lap spliced bars
154
take up extra space and cannot accommodate the placement tolerance. Where reinforcement quantities
155
and available space are in conflict with spacing requirements, the contractor and designer might consider
156
bundling a portion of the reinforcement. Bundling of bars requires approval of the designer.
157
3.2.4 Placing of reinforcement
7
158
159
3.2.4.1 General information
Just as there are tolerances in the fabrication of a bar, there are also tolerances in the placement
160
of a bar in a concrete member—creating potential “placement tolerance clouds.”
161
Because LDP’s and reinforcing bar detailers may overlook the impact of placement tolerances on
162
constructability, it’s worthwhile to use a couple of examples to take a brief look at what can occur.
163
3.2.4.2 Tolerance cloud
164
The tolerances for reinforcement location are found in ACI 117. Cover tolerances vary from 1/4
165
in. for member sizes of 4 in. or less to 1 in. when member size is over 2 ft. The maximum reduction in
166
cover is limited to 1/3 of the specified cover. In slabs and walls, the spacing tolerance is 3 in. for
167
reinforcement other than stirrups and ties. As an example, consider the simple 14 x 14 in. concrete
168
column shown in Fig. 3.2.4.2a.
169
170
Fig. 3.2.4.2a—Column the designer defined
171
8
172
The column is reinforced with 4 #8bars enclosed within #4 ties. The normal concrete cover to the
173
ties of this column would be 1-1/2 in. The cover tolerance is ±1/2 in. If the reinforcement was placed to
174
the minimum tolerance in two directions, the column could appear as in Fig. 3.2.4.2b.
175
176
Fig. 3.2.4.2b—Column that could be placed within the specified tolerances
177
However, the reinforcement could be placed to minimum tolerance in any of the four directions.
178
Thus, the placement tolerance clouds would appear as in Fig. 3.2.4.2c. This could be quite a different
179
image than the precise image one might have had in mind at the outset.
180
9
181
Fig. 3.2.4.2c—Column with “placement tolerance clouds”
182
For a second example, consider the case of a simple 14-in.-thick wall reinforced with #8 vertical
183
bars at 12 in. on center each face and #4 horizontal bars at 12 in. on center each face (Fig. 3.2.4.2d).
184
185
Fig. 3.2.4.2d—Wall the designer defined
186
187
The outside face cover is 1-1/2 in. and inside face cover is 3/4 in. The cover tolerance for the
188
bars on the outside face is ±1/2 in. For the inside face cover, the maximum cover reduction is limited to
189
1/3 of the specified cover, resulting in a cover tolerance of +1/2 or –1/4 in. Thus the outside face cover
190
could be as little as 1 in. and the inside face cover as little as 1/2 in. (Fig. 3.2.4.2e).
10
191
192
Fig. 3.2.4.2e—Wall that could be placed within the specified tolerances
193
194
195
If we also consider that any one of the vertical and horizontal bars may be located as far as 3 in.
either way from its designated location, the tolerance cloud would appear as in Fig 3.2.4.2f.
196
197
Fig. 3.2.4.2f—Wall with “placement tolerance clouds”
198
199
3.2.4.3 Design considerations
11
200
As in the instance of the fabrication tolerance cloud of a single bar, the placement cloud of a
201
group of placed bars presents quite a different image than the one probably envisioned by the designer
202
or reinforcing bar detailer. If the placement tolerances are factored into the design, they would realize
203
that the available space they expected (to pass beam bars through a column or to place a vertical embed
204
in a wall) might not be what is actually available, especially if they consider that the beam bars and the
205
embed also have fabrication and placement tolerances of their own. Awareness of placement tolerance
206
clouds may lead to design options that make these tolerances no longer a factor.
207
3.2.5 Reinforcing bar fabrication
208
3.2.5.1 General information
209
Practical limitations of equipment and production efficiency have led to the establishment of
210
certain fabrication tolerances that can be met with standard shop equipment. These standard tolerances
211
are shown in both ACI 117 and in the CRSI Manual of Standard Practice for both straight and bent bars.
212
Where more restrictive tolerances are required than those shown in the referenced figures, they shall be
213
clearly indicated in the contract documents.
214
3.2.5.2 Restrictive tolerances
215
Tolerances more restrictive than those reported by CRSI in ACI 117 should be used sparingly. If
216
more restrictive tolerances are required, this is generally characterized as special bending by the
217
reinforcing bar fabricator and requires special arrangements in the production shops. These special
218
arrangements include, but are not limited to: additional equipment, modifications to existing equipment,
219
additional staff, inspection devices, etc. Special bending is generally more time consuming than normal
220
bending, may be subject to additional costs, and may create delays in material deliveries to the jobsite.
221
222
3.2.5.3 Fabrication tolerance clouds
12
223
LDP’s need to be aware of the tolerance cloud that exists for fabricated reinforcing bar. As a
224
simple example, let’s consider the fabrication tolerances for a simple reinforcing bar with 90-degree
225
bends (Fig. 3.2.5.3a). For the purposes of our example, let’s assume that the bar is a #8 bar and that Side
226
A is anchored in the (idealized) plane ABG. For this bar size, the standard hook is 16 in. long, and the
227
linear and angular tolerances are ±1 in. and ±2.5 degrees, respectively.
228
Now, let’s examine the potential effects of these tolerances. First, note that Sides A and G can be
229
as short as 15 in. (red to black zone interface) or as long as 17 in. (end of blue zone) and still be within
230
allowable tolerances (Fig. 3.2.5.3b).
231
Because we have assumed Side A to be anchored in ABG, we will not need to consider out-of-
232
plane angular deviation for Side A. However, we will need to consider in-plane angular deviation. When
233
we add this angular deviation of ±2.5 degrees to Side A, the tolerance envelope (cloud) will appear as
234
shown in Fig. 3.2.5.3c. (Note: To simplify the illustrations, the effects of the angular tolerances are
235
shown as one-bar-diameter deviations in the position of the ends of the 16 in. hooks. Actual deviations
236
will be about 70% of a bar diameter.)
237
Next, we add the dimensional tolerance of ±1 in. for Side B (Fig. 3.2.5.3d) and the in-plane
238
angular deviation of ±2.5 degrees to Side G (Fig. 3.2.5.3e). Finally, we add the out-of-plane angular
239
deviation of ±2.5 degrees to Side G. The resulting tolerance cloud is as shown in Fig. 3.2.5.3f.
240
13
(a)
(a)
(b)
(b)
Fig. 1: Standard (theoretkaO hooked bar with Sides A, B, and G:
(a} plan view, and (b) Isometric view
fig. 4: Hooked bar with :tt in. tolerance envelope on Sides A
and G, :t2.5 degrees in-plane angular tolerance envelope at
Side A, and :tt in. tolerance envelope on Side B
(a)
(a)
(b)
(b)
Fig. 2: Hooked bar with :ttln. tolerance envelope on Sides A and G
fig. s: Hooked bar with :t1 in . tolerance envelope on Sides A, B,
and G and :t2.5 degrees in-plane angular tolerance envelope at
Sides A and G
(a)
(b)
241
242
Fig. 3: Hooked bar with .1:1 in. tolerance envelope on Sides A and G
and ::t2.5 degrees in-plane angular tolerance envelope at Side A
fig. 6: Hooked bar with :u in. tolerance envelope on Sides A, B,
and G: :t2.5 degrees in-plane angular tolerance envelope at
Sides A and G; and :t2.5 degrees out-of-plane angular tolerance
envelope at Side G
14
243
3.2.5.4 Design considerations
244
Clearly, the fabricated bar arriving on the construction site can be quite different from the bar the
245
LDP or reinforcing bar detailer might have envisioned. Keeping this in mind during design could
246
significantly reduce constructability problems. For instance, if our example bar were replaced with two
247
hooked bars lapped in the middle (Fig. 3.2.5.4a), the only tolerance that might introduce problems would
248
be in-plane angular deviation.
249
250
Fig. 3.2.5.4a—Reducing tolerance problems by replacing single bar with lapped bars (lap splice
251
shown offset for clarity only)
252
Because both hooks could be rotated, there would be no out-of-plane deviations. Further,
253
because the lap length could be adjusted slightly in the field, there would be little chance of problems
254
with the length of Side B.
255
256
Consideration of tolerances becomes even more of an issue when two or more bars are being
assembled together in a structure. In such cases, one must deal with an accumulation of tolerances.
15
257
ACI 318 Section 25.3 restricts the minimum inside bend diameter of standard hook geometry for
258
deformed bars in tension and the minimum inside bend diameters and standard hook geometry of
259
stirrups, ties, and hoops. The primary factors affecting the minimum bend diameter are feasibility of
260
bending without breakage and avoidance of crushing the concrete inside the bend. ACI 117 tolerance on
261
these minimum inside bend diameters is -0 in. Thus, bars cannot be requested, or expected, to be bent to
262
a tighter diameter to solve a fit-up or congestion problem. Furthermore, there is not a + tolerance for
263
minimum bend diameter and the bend diameter may be larger than the minimum due spring-back and
264
other factors. Design drawings sometimes illustrate hooks wrapping tightly around another bar with
265
assumed bar positions based on the sum of the required cover, the diameter of one bar and the half
266
diameter of the other bar. A comparison of that incorrect assumption to the reality with a 6db minimum
267
bend diameter is shown in Fig. 3.2.5.4b, and for larger bars the minimum bend diameter may be 8db or
268
10db.
Incorrect 1d bend diameter
illustration in drawing
Correct 6db bend diameter
when placed
269
270
Fig. 3.2.5.4b—Comparison of minimum bend diameter position effect for a #7 bar
271
3.2.6 Forming tolerances
272
3.2.6.1 General information
16
273
The last two sections discussed tolerance clouds associated with fabrication and placement of
274
reinforcing bars. While every builder strives to cast concrete to the precise dimensions indicated by the
275
designer, the reasonable constraints of time, technology, and economy make this impractical. That’s
276
why it is important for designers to understand the forming tolerances associated with concrete
277
construction.
278
3.2.6.2 Forming tolerance clouds
279
Tolerances for forming concrete are found in ACI 117. The tolerances for cross-sectional
280
dimensions of cast-in-place members vary with the overall dimension. Using the example from the
281
previous section of a 14 x 14 in. column, the tolerance is +1/2 in. or –3/8 in. Ignoring vertical
282
alignment, this produces the forming tolerance cloud shown in Fig. 3.2.6.2a, with a column having
283
acceptable dimensions as large as 14-1/2 x 14-1/2 in. or as small as 13-5/8 x 13-5/8 in.
284
While it is highly unlikely that these small variations would create any constructability or design
285
concerns with everything else being perfect, a very different picture arises when we consider them in
286
conjunction with the other possible tolerances.
287
17
288
Fig. 3.2.6.2a—Forming . . . .
Fig. 3.2.6.2b—Combining . . .
289
With 1-1/2 in. cover, the design width for the column ties is 11 in., and the tolerance is ±1/2 in.
290
Combining the maximum acceptable tie dimensions with the minimum acceptable column dimensions
291
produces the configuration shown in Fig. 3.2.6.2b. With the reinforcing cage centered, the cover is
292
reduced from the design value of 1-1/2 in. to 1-1/16 in. on all four sides. Recalling that the placement
293
tolerances allow the cover to decrease to 1 in. minimum, the cage must be placed within ±1/16 in. of the
294
center of the column in both directions if it is to meet tolerance requirements. Considering the
295
straightness of the bars and the straightness of the forms, this could be very difficult for the Contractor
296
to do.
297
For the example of a 14-in.-thick wall that we discussed in previous sections, the situation is
298
somewhat different because there are no tie tolerances to contend with. However, as we will see in the
299
following example, other issues arise that must be dealt with. The forming tolerance for the wall
300
thickness allows the wall to be between 14-1/2 in. and 13-5/8 in. thick as shown in Fig. 3.2.6.2c.
301
302
Fig. 3.2.6.2c—Forming tolerance cloud for the wall
18
303
Reinforcing placement tolerances allow the 1-1/2 in. design cover on the outside face to be
304
between 1 and 2 in. and the 3/4 in. design cover on the inside face to be between 1/2 and 1-1/4 in. The
305
minimum wall thickness combined with the maximum cover on the outside face reinforcing is shown in
306
Fig. 3.2.6.2d.
307
308
Fig. 3.2.6.2d—Minimum acceptable …
309
310
In this situation, the original effective depth of 12 in. for the vertical No. 8 bars on the outside
311
face has decreased to only 11-1/8 in. Assuming 4000-psi concrete and Grade 60 reinforcement, this
312
reduction in effective depth would result in a decrease in nominal moment capacity from the original
313
45.1 kip·ft/ft to 41.6 kip·ft/ft —a 7.7% reduction due to forming and placement tolerances alone. The
314
effect on moment strength would be even more drastic for thinner walls. To guard against this, Section
315
7.5.2.1 of ACI 318 places a tolerance on effective depth d of ±3/8 in. for d ≤ 8 in. and ±1/2 in. for d > 8
316
in. These tolerances would produce a 4.4% reduction in nominal moment strength for the example wall
19
317
considered here; however, designers should realize that effective depth is not checked in the field. Bars
318
are placed and tolerances checked relative to the formwork surfaces.
319
3.2.7 Confined reinforcing bars
320
Confined reinforcing bars add one more level of complexity to the tolerance issues described in
321
previous sections. In the context of detailing and placing reinforcing steel, a confined bar is one that is
322
restricted by face cover requirements at both ends. The best example of a confined reinforcing bar is a
323
bar with hooks at each end, as would be seen in an elevated beam as shown in Fig. 3.2.7a.
324
325
Fig. 3.2.7a—Single bar with hook at both ends
326
On the surface this does not seem to be a big deal, other than the tolerance issues previously
327
discussed. However, when considering the fact that in most cases there is adjacent reinforcing for a
328
beam, column or wall, this double-hooked bar needs to fit within, the situation becomes much more
329
complicated as shown in Fig. 3.2.7b.
330
331
Fig. 3.2.7b—Single bar with hook at both ends and intersecting reinforcement
332
The designer needs to consider that a bar with hooks at each end creates a situation where the bar
333
is extremely restricted and must be exactly right, otherwise the ironworker may not be able to place it.
20
334
The reality is even if the reinforcing bar detailer details this double hooked bars as shown in the design
335
drawings with the correct concrete cover, it will almost never fit during field installation.
336
337
Since there is no flexibility with this bar, if it doesn’t fit it will most likely need to be replaced,
causing delays on the jobsite. There are two ways to address this situation.
338
The first and most preferred way would be to allow the use of a lap splice. This allows the
339
ironworker the flexibility to place the bars in their intended position within the beam while avoiding
340
conflicts with the adjacent steel.
341
342
Fig. 3.2.7c—Substitution of two hooked bars with lap splice (lap splice shown offset for clarity only)
343
[Should hooks be on outside here? see next figure discussion]
344
The second way to address this situation if a lap splice is not permissible, is for the designer to
345
understand and accommodate the end of the bar being held inside the adjacent steel, increasing the end
346
cover measured from the edge of the concrete to the end of the bar.
347
348
Fig. 3.2.7d—Single bar with hook at both ends placed within beam cages
349
This situation needs to be addressed by the reinforcing bar detailer and shown in one of these
350
ways on the placing drawings. Notating this practice on the design drawings will provide clear direction
21
351
to the detailer and the ironworker and avoid confusion during the detailing process and during
352
installation in the field.
353
354
355
Fig. 3.2.7e—Confined hooked bars in slabs and beams
356
These scenarios are commonly seen as shown in the following examples.In Fig. 3.2.7e, the left
357
illustration shows the end of a confined bar where no adjacent steel is present and the the right
358
illustration shows the end of a confined bar with adjacent steel that must be accounted for in the design,
359
detailing and installation processes.
360
361
362
363
Fig. 3.2.7e—Confined hooked bars in columns and walls
364
Fig. 3.2.7f shows situations where the end position of a confined bar (in the last lift of a column or wall)
365
with adjacent slab steel must be accounted for in the design, detailing and installation processes.
366
22
367
3.2.8 Accumulating (combined) tolerances
368
The effects of tolerances on cover, strength, constructability, and serviceability of the structure
369
should be considered by the LDP. Casting of concrete always involves the fabrication, placement, and
370
forming tolerance clouds. While these instances are not encountered every day, they occur frequently
371
enough to create constructability problems. Any combination of tolerances, as discussed in this section,
372
working against each other has the potential to create a constructability concern that quite often is
373
difficult to reconcile, especially if it involves two different trades, each within their own acceptable
374
tolerances. The designer must always assess the risk of this kind of problem arising in critical areas of
375
the structure and consider options that mitigate or eliminate the possible constructability problem.
376
3.3—General Cautions
377
3.3.1—Revisions of drawings
378
3.3.2—Dimensioning
379
3.3.3—Field cutting of bars
380
3.3.4—Field bending of bars
381
3.3.5—Mechanical connectors
382
3.3.6—Mixing grades of steel on a project
23
1
CHAPTER 4 — STRUCTURAL DRAWINGS
2
4.1—Scope
3
This chapter describes information that is typically found on structural drawings. In US
4
engineering practice each design office usually develops an “office standard” sheet order and
5
naming convention. This guide, as an example, presents the project sheet order found in the
6
United States National CAD Standard – V6, as outlined in 4.3.
7
4.2—General
8
9
Structural drawings are those prepared for the owner or purchaser of engineering services
and along with the project specifications form a part of the contract documents. Structural
10
drawings must contain an adequate set of notes, instructions and information necessary to permit
11
the reinforcing steel detailer to produce reinforcing steel placing drawings. Each sheet should
12
have a title block, production data, and a drawing area as shown in Fig. 4.2.
13
The drawing area is the largest portion of the sheet where technical information is
14
presented. Examples of technical information are the overall framing plan, sections and details
15
needed to illustrate information at specific areas, and additional notes as required.
16
The production data area is located in the left margin of the sheet and includes
17
information such as the CAD filename and path to the file, default settings, pen assignments,
18
printer/plotter commands, date and time of plot, overlay drafting control data, and reference files.
19
The title block area is located at the right side of the sheet. It usually includes the
20
designers name, address, and logo; basic information about the project including location of the
21
worksite, owner, and project name; an information block regarding issue type (addendum, design
22
development, bidding, bulletin, etc.) of this sheet; a sheet responsibility block that indicates the
1
23
project manager, engineer, draftsman and reviewer of the information on the drawing; a sheet
24
title block; and a sheet numbering block.
25
26
Fig. 4.2- United States National CAD standard overall sheet layout
27
28
29
30
31
4.3—Order of sheets
The order of drawings shown in the United States National CAD Standard – V6 is as
listed in Table 4.3.
Table 4.3—NCS drawing sheet numbering
2
Sheet
number
0
1
2
3
4
Sheet title
General notes
Plans
Elevations
Sections
Large-scale views
5
6
7
Details
Schedules and diagrams
User defined
8
User defined
9
3D Representations
Information included
Symbols legend, general notes
Horizontal views of the project
Vertical views
Sectional views, wall sections
Plans, elevations, stair sections, or
sections that are not details
For types that do not fall in other
categories, including typical detail sheets
For types that do not fall in other
categories
Isometrics, perspectives, photographs
32
33
If more than one sheet is required within the listed order, then decimal sheet numbers are used,
34
e.g., 5.0, 5.1, 5.2, 5.3.
35
4.4 General notes sheets
36
A general notes sheet presents project design loads, the codes and standards that are the
37
basis of design, material and product requirements, and construction directions. The notes can be
38
the entire project structural specifications, act as an extension of the project structural
39
specifications, or simply duplicate important aspects of the project structural specifications.
40
4.4.1 Codes and standards
41
The general building code, referenced standards, and/or the authority having jurisdiction
42
requires specific information to be included on the construction documents and the general notes
43
sheet(s) present this information. ACI 318 also requires that all applicable information from
44
Chapter 26 related to construction be included in the construction documents.
45
4.4.2 Design loads
3
46
Section 1603.1 of the 2012 IBC states: “The design loads and other information pertinent to
47
the structural design required by Sections 1603.1.1 through 1603.1.9 shall be indicated on the
48
construction documents." The titles of these 9 referenced sections are listed below:
49
1603.1.1 Floor live load
50
1603.1.2 Roof live load
51
1603.1.3 Roof snow load data
52
1603.1.4 Wind design data
53
1603.1.5 Earthquake design data
54
1603.1.6 Geotechnical information
55
1603.1.7 Flood design data
56
1603.1.8 Special loads
57
1603.1.9 Systems and components requiring special inspections for seismic resistance
58
59
Design loads are presented on the general notes sheet. Floor live loads, roof live loads,
60
snow loads, and other simple gravity loads are commonly shown in a table. Basic wind load
61
criteria assumptions and, when necessary, wind loading diagrams are included. Earthquake
62
design data is usually presented as a list of the different criteria used to develop the design
63
earthquake loads. It is desirable to indicate if and where live load reductions were applied.
64
Geotechnical design information shown is usually supplied to the structural designer in a
65
geotechnical report. It can be presented as a note if the soil and water table on site is relatively
66
consistent or in a table format if there is significant soil or water table variability.
67
68
Flood design data and criteria used to determine the flood design loads are typically
shown using notes.
4
69
Special loads not included in the code-required live loads are also noted in the table that
70
includes the live loads. Examples of such loads are architectural features, partition live loads,
71
ceiling and hanging loads, and super-imposed dead loads. A diagram may be needed for heavy
72
pieces of equipment, such as forklifts, with their assumed wheel spacing and axle loads.
73
Showing the self-weight of the structure is not a requirement of the code. However, the
74
concrete density should be provided on the drawings so that the self-weight of the structure can
75
be accurately determined by the formwork engineer.
76
4.4.3 Specifications
77
The first concrete general note is commonly a reference to require construction to be in
78
accordance with ACI 301. The LDP ensures that the construction documents meet code
79
provisions; therefore, requiring the contractor to conform to ACI 318 is not appropriate as it
80
provides code requirements to the LDP and not the contractor or materials supplier. By
81
incorporating ACI 301 by reference into the construction documents and using the ACI 301
82
mandatory and optional checklists, the concrete materials and construction requirements will
83
satisfy ACI 318. In addition ACI 301 also specifies that fabrication and construction tolerances
84
shall comply with ACI 117.
85
ACI 301 contains the following three checklists: mandatory, optional requirements, and
86
submittals. The LDP is often also the specifier on a project and must go through these checklists
87
and make necessary exceptions to ACI 301 in the construction documents. The general notes
88
sheet is a convenient way to communicate any necessary exceptions to ACI 301.
89
4.4.4 Concrete notes
90
91
ACI 301 Mandatory Requirements Checklist items related to concrete can be specified in
the general concrete notes and indicate that the construction documents include:
5
92

Exposure class and specified compressive strength f'c for different elements
93

Handling, placing and constructing requirements
94

Designations and requirements for architectural concrete, lightweight concrete, mass
95
concrete, post-tensioned concrete , shrinkage-compensating concrete, industrial floor
96
slabs, tilt-up construction and pre-cast concrete
97
Concrete general notes can show these with a table with each element type along with its
98
99
corresponding exposure class, specified compressive strength and other requirements.
The construction documents should also indicate any exceptions to the default requirements
100
of ACI 301. ACI 301 lists possible exceptions in the Optional Requirements Checklist.
101
Concrete general notes often contain the following optional requirements checklist exceptions to
102
ACI 301 default requirements:
103

Air entrainment in percentage (%), along with the respective tolerance
104

Slump in inches (in), along with the respective tolerance
105

When high-range-water-reducing admixtures are allowed or required
106

Additional testing and inspection services
107
When proprietary concrete products are required on a project, they can be specified in the
108
general notes.
109
4.4.5 Reinforcement notes
110
ACI 301 Mandatory Requirements Checklist items related to reinforcing steel can be
111
specified in the general reinforcement notes and indicate that the construction documents
112
include:
113

Type and grade of reinforcing bars
114

Bar development and splice lengths and locations
6
115

Types of reinforcement supports and locations used within the structure
116

Specify the cover for headed shear stud reinforcement and headed reinforcing bars
117
The construction documents must indicate any exceptions to the default requirements of ACI
118
301. ACI 301 lists possible exceptions to the default requirements in the Optional Requirements
119
Checklist. Some exceptions to ACI 301 default requirements may include the following:
120

Weldability of bars
121

Concrete cover to reinforcement
122

Specialty item type and grade
123

Coatings such as epoxy or galvanized and where applicable
124

Permitting field cutting of reinforcement and the cutting methods
125
Reinforcing bars require concrete cover to protect the steel from corrosion. ACI 301 shows
126
concrete cover requirements for specific members in Table 3.3.2.3. The concrete cover
127
requirements for a project are typically shown in a table or list showing the type of member, the
128
concrete exposure, the type of reinforcement and the concrete cover requirements for each. If
129
there are locations on a specific project that are questionable, the LDP should indicate which
130
concrete cover requirement controls at each location (i.e. fire rated elements).
131
When proprietary reinforcement products are required on a project, they can be specified in
132
the general notes.
133
4.4.5.1 ACI 318 reinforcing requirements
134
Reinforcing bars, spirals, wires and bar mats in conformance with ASTM International
135
specifications are accepted for construction in the United States and are required by ACI 318.
136
Type and grade of reinforcing are typically shown in a note. When there are more than one type
7
137
and/or grade of reinforcing used on a project, it may be easier to show this information in a table
138
indicating what type and grade is used in what parts of the structure (Table 4.4.5.1).
139
Table 4.4.5.2—Example table of reinforcing bar locations and grades
Insert table of locations and grades.
(indicate it’s an example)
(indicate the ASTM types and grades, locations)
140
141
142
4.4.5.2 Development and splices
ACI 318 requires that the development length/embedment of reinforcement and location and
143
length of lap splices be shown on the construction documents. Bar development and lap splice
144
lengths and locations can be shown using tables, but the preferred method for showing
145
development and lap splice length and location is graphically in plan, elevation, section, or detail
146
with dimensions provided. This allows the fabrication detailer to more accurately read this
147
information from the drawings. Where lap splice location and length have structural safety
148
implications, the lap splice lengths should be shown graphically. When engineering judgment
149
indicates that lap splice location and length are less critical, a table can be used (refer to Table
150
4.4.5.2). Structural calculations should not be required of the fabrication detailer to determine
151
the lap splice length or development lengths. Lap and development lengths calculated by the
152
LDP should be shown on the design drawings. The LDP should verify that all possible bar
153
development and lap splice length arrangements that are on the project can be found on the
154
drawings. (MENTION THE CONCRETE STRENTH APPLICABLE; CURTIS WILL GIVE
155
US THE BEST TABLE; AND STEEL GRADE)
156
Table 4.4.5.2a—Example reinforcing bar lap schedule
8
157
158
Photo 1: Perry Internal Standards
159
Table of lap lengths ideally customized for the project.
160
161
162
If mechanical splices are permitted or required on a project, a note is needed on the general
163
notes sheet or project specifications to permit them as well as the required type of splice. The LDP
164
should also include a typical detail or specific details on where mechanical splices are required or
165
permitted (refer to Table 4.4.5.2b).
166
Table 4.4.5.2b—Example table of mechanical splices
Table of mechanical splices and splice locations and stagger.
EXPLAIN THE PROPER WAY TO CALL OUT A MECHANICAL SPLICE. SHOW A
GOOD DESIGN DETAIL.
LOCATION AND TYPES AND STAGGER
167
9
168
If headed bars are permitted or required on a project, a note is needed on the general notes
169
sheet or project specifications to permit them as well as the required bearing area, cover and
170
embedment lengths. The LDP should also include a typical detail or specific details on where
171
headed bars are required or permitted (refer to Table 4.4.5.2c). USE AN ILLUSTRATION ON
172
HOW WE WANT TO SEE IT.
173
Table 4.4.5.2b—Example table of headed bars
174
175
Table of locations and table of headed bars.
176
177
4.4.5.3 Supports for reinforcing bars
178
Before and during concrete casting, reinforcing bars should be supported and held firmly in
179
place at the proper distance from the forms. The LDP specifies acceptable materials and corrosion
180
protection for reinforcing bar supports, side form spacers, and supports or spacers for other
181
embedded structural items or specific areas. Specifications for reinforcing bar supports and
182
spacers usually are consistent with established industry practice.
183
184
If the construction documents only state that reinforcing bars need to be accurately placed,
adequately supported, and secured against displacement within permitted tolerances, the contractor
10
185
selects the type and class of wire bar supports, precast blocks, composite (plastic), or other
186
materials to use for each area.
187
There are three common material types of bar supports: wire bar supports, precast concrete
188
block bar supports, and composite (plastic) bar supports. A common sub-type of wire bar supports
189
is plastic-tipped wire bar supports which are often used when aesthetics are a concern. CRSI RB4
190
describes the various types of wire, composite and precast bar supports. Examples of bar supports
191
are shown in Fig. 4.4.5.3a.
192
As mentioned above, certain support types can cause aesthetic issues. For example, if
193
precast blocks are used and the surface has a sand-blasted finish, the different texture and color
194
between the precast blocks and the cast-in-place concrete may be objectionable. Another example
195
of aesthetic issues is that Class 3 wire bar supports may leave rust stains on the exposed concrete
196
surfaces. The LDP and contractor should work together to help prevent these issues from
197
occurring because repair for aesthetic issues can be costly.
198
Beam bolsters support bottom beam reinforcement and are placed in the beam form,
199
usually perpendicular to the axis of the beam under the stirrups. Beams may also be supported
200
with individual chairs or blocks placed under the beam stirrups.
201
11
202
203
204
205
Typical Wire Beam Bolster
RECONSIDER THIS FIGURE/EXAMPLE – maybe more examples.
Photo 2: CRSI 2009 Table 3-1
206
207
208
Bar supports are furnished for bottom bars in grade beams or slabs-on-ground (Fig.
209
4.4.5.3b) only if required by the LDP in the construction documents. For a structural element, it is
210
recommended that the LDP specify bar supports for the bottom bars in grade beams or slabs-on-
211
ground. Aesthetics are not a concern in the bottom of a slab-on-ground or grade beam which
212
allows the use of precast blocks for bar supports.
Fig. 4.4.5.3a—Example bar supports
Label and annotate this photo.
Perhaps a better photo is in
order. (NEED CLEARER
PICTURE)
213
12
214
215
216
Fig. 4.4.5.3b—Bar supports for slab-on-ground reinforcement
Side form spacers (Fig. 4.4.5.3c) may be specified for use, but are usually selected by the
contractor.
Label and Annotate This Photo
CHECK RESOLUTION, but
GOOD PIC
217
218
Fig. 4.4.5.3c—Side form spacers to maintain reinforcement cover in a wall form
219
220
4.4.5.4 Weldability of bars
221
The weldability of steel is established by its chemical composition. AWS D1.4 sets the
222
minimum preheat and interpass temperatures and provides the applicable welding procedures.
223
Carbon steel bars conforming to ASTM A615/A615M are weldable with appropriate preheating.
224
Only reinforcing bars conforming to ASTM A706/A 706M are pre-approved for welding without
225
preheating. Welding of rail-and axle-steel bars is not recommended.
226
227
4.4.5.5 Hooks and bends
228
It is standard practice in the industry to show all bar dimensions as out-to-out and consider the
229
bar lengths as the sum of all detailed primary dimensions, including Hooks A and G. It is
230
important to note the difference between “minimum” bend diameter and “finished” bend
13
231
diameter. “Finished” bend diameters includes a “spring back” effect when bars straighten out
232
slightly after being bent and are slightly larger than “minimum” bend diameters.
233
Standard bend shapes will have not more than six bend points in one plane, bent to
234
normal tolerances. Shapes with more than six bends, or bent to special tolerances or bent in
235
more than one plane involve greater difficulty and are subject to added costs.
236
Bar hooks and bends are occasionally not shown on the drawings, but a note is placed
237
stating that certain bars are required to end in a standard hook. Specifications that require a non-
238
standard hook should be used with caution because non-standard hooks may be difficult to achieve.
239
If the LDP shows a hook but does not dimension the hook, the reinforcing bar detailer will use an
240
algorithm similar to the Block Flow diagram in Fig. 4.4.5.5 to determine the proper hook to use.
Are hooks dimensioned on
plan?
Yes
Use plan dimensions
Yes
Use a standard 90 degree
hook
Yes
Use a standard 90 degree
hook rotated 45 degrees
Does a standard 180 degree
hook fit?
Yes
Use a standard 180 degree
hook
No
Does a standard 180 degree
hook rotated 45 degrees fit?
Yes
Use a standard 180 degree
hook rotated 45 degrees
No
Does a standard 90 degree
hook fit?
No
Does a standard 90 degree
hook rotated 45 degrees fit?
No
No
RFI
241
242
Fig. 4.4.5.5—Block flow diagram to determine hook type and size
243
To avoid RFI’s, the design might consider … For this reason, it is prudent for the LDP to
244
check hooks throughout the project during the constructability check suggested in chapter 8,
14
245
especially if rotating the hooks causes issues with design. A standard hook only defines
246
dimensions of the bend shape. This is not an indicator of development strength. See Fig.
247
XXXXXXX CJP passive. (TASK GROUP REVISE)
248
4.4.5.6 Welded wire reinforcement
249
Welded wire reinforcement consists of a series of cold-drawn steel wires arranged at right
250
angles to each other and electrically welded at all intersections. Welded wire reinforcement has
251
many uses in reinforced concrete construction. It can be used in slabs-on- ground, joist and
252
waffle slab construction, walls, pavements, box culverts and canal linings.
253
The general notes or the specifications will specify the welded wire reinforcement
254
required. Welded wire reinforcement can be in the form of flat sheets normally 8 ft. 0 in. by 20
255
ft. 0 in. or rolls which are usually 5 ft. 0 in. by 150 ft. 0 in. The wire may be plain or deformed.
256
Welded wire reinforcement in conformance with ASTM International specification A1064
257
is accepted for construction in the United States and is required by ACI 318. Table 4.4.5.6 gives
258
common styles of welded wire reinforcement in the U.S. .
259
Table 4.4.5.6—Common stock styles of welded wire reinforcement
15
260
261
262
263
4.4.6 Construction notes
Construction notes are general notes that discuss many of the miscellaneous aspects of
264
construction not covered by the other types of notes. These notes may include information
265
pertinent to detailing. For example:
266

Procedure for resolution of discrepancies
267

Storage of material on site
268

(NEEDS DEVELOPMENT)
269
270
4.4.7 Inspection notes
The general notes sheet should indicate the level of inspection required for the project. If
271
the structure includes members that require special inspection, such as a special seismic force
272
resisting system they should be identified (Fig. 4.4.7).
16
273
274
Photo 3: Perry Internal Standards
275
276
277
278
Fig. 4.4.5.5—Example special inspection notes
4.5 Plan sheets
Section 1603.1 in the 2012 IBC states: “Construction documents shall show the size,
279
section, and relative locations of structural members with floor levels, column centers, and
280
offsets dimensioned.” A plan drawing provides information about an identified building floor,
281
including overall geometry and dimensions, concrete member width and thicknesses (either
282
directly or by a designation keyed to a schedule), and reinforcement information for concrete
283
members (either directly or by a designation keyed to a schedule). A plan drawing can include a
284
general reference to other sheets, such as an elevation sheet or a detail sheet. A floor plan also
285
includes orientation information, such as column line numbers, a north arrow, top of concrete
286
relative to a datum, and general notes specific to the floor plan.
287
288
Member reinforcement such as beams can be directly shown on the plan or indirectly
provided through use of schedule marks, such as beam numbers. <a small figure may be
17
289
helpful> Plan drawings are usually drawn to 1/16 or 1/8 inch scale. For small floor plans larger
290
scales may be used. The primary consideration for scale to be used is the complexity of the plan.
291
Clarity should be maintained by using a larger scale if a large amount of information needs to be
292
conveyed in a small area of the plan. If the designer needs to break up the plan into several parts
293
for a floor, they should take into account portions of the structure, assumed placement sequences,
294
or some other easily readable way of breaking the plan into smaller pieces.
295
Because plans only provide information in the horizontal direction, section cuts and
296
elevations are needed to clarify geometric and reinforcement information in the vertical
297
direction. A section cut is indicated by a directional mark or cut drawn on the floor plan. <a
298
small figure may be helpful>
299
4.5.1 Plan graphics and member geometry
300
The assumed view point for a plan drawing is above the slab on each floor level of a
301
structure. Therefore, slab edges are usually shown as solid lines on the plan drawings
302
(Fig.4.5.1a). Beam and girder locations are typically shown as hidden on the plan drawings
303
because they are typically below the slab.
18
304
305
306
307
308
Photo 4: http://www.nist.gov/el/building_materials/images/ew2_1.jpg (could find better quality)
Fig. 4.5.1a—Floor plan
Columns and walls that are shown solid extend above the slab on the plan. These vertical
309
members of the structure will be shown on all of the plans from their lowest elevation in the
310
structure, usually the foundation but occasionally a transfer girder or slab, to their highest
311
elevation in the structure, usually the top tier where they will be drawn as hidden.
312
Foundations are drawn as hidden when they are below the slab on grade and solid when
313
not covered by structural members or slab on grade concrete. Soil is not considered a structural
314
member for this purpose. Slabs, beams, girders, columns, walls, and foundations are sometimes
315
given schedule marks on the plan drawings (Fig. 4.5.1b) to indicate the type of member, size of
316
concrete member, and reinforcement required.
317
318
319
Fig. 4.5.1b—Floor plan with member schedule marks
4.5.2 Reinforcement on plan views
19
320
Reinforcement that is not typical, such as slab reinforcement required where a varied
321
column layout or a large slab opening occurs, is often shown on the plan drawings instead of
322
using slab marks (Fig. 4.5.2).
323
324
325
Photo 5: Perry Project 15121.00 2/S1.0
326
Fig. 4.5.2—Supplementary reinforcement shown on floor plan
327
When the amount of slab reinforcement being shown on a plan drawing becomes so large
328
that the plan is difficult to read, it is acceptable to make additional plans. These additional plan
329
sheets can be used so that one shows the bottom reinforcement, one shows the top reinforcement,
20
330
and another that shows additional steel such as that required around openings and should be
331
properly labeled. Additional beam and girder reinforcement is not typically shown on the plan
332
drawings because it can cause confusion. If additional reinforcement is required for beams and
333
girders, it is typically shown in a note or remark in the beam schedule and a corresponding detail
334
or section cut will be provided to show the additional reinforcement.
335
4.6 Elevation sheets
336
An elevation sheet contains drawing information about identified concrete members from
337
an elevation view (Fig. 4.6a). Elevation drawings do not require a set scale, so an appropriate
338
scale is chosen based on the height of the elevation being drawn and the level of detail needed.
339
Similar to plan drawings, the scale is often based on the complexity of the structure and the
340
elevation can be split into several drawings as required to show enough detail.
341
342
343
344
Photo 6: Perry Project 15030.00 – Pricing Drawings – 2/S1.0
Fig. 4.6a—Building elevation with detail call-outs
21
345
The elevation drawing provides orientation information, such as column lines or floor
346
levels, and is connected to the plan drawings by noted concrete elevations relative to a datum,
347
section references, and orientation information.
348
An elevation drawing that provides member dimensions can also provide member
349
reinforcement. This information can be provided directly or by a designation referenced to a
350
schedule.
351
When beams, columns, walls, or all are part of a seismic lateral load resisting system,
352
elevations are often used to show all of the reinforcement in the members that are part of that
353
system (Fig. 4.6b). Ordinary moment frames, intermediate moment frames, and special moment
354
frames and shear walls all have seismic detail requirements in ACI 318. ASK PAUL [INSERT
355
FIGURE]
356
357
358
Fig. 4.6b—Building elevation with detail call-outs for lateral load resisting system
4.7 Section sheets
A section sheet is used for most projects. Sometimes, a single sheet combines sections,
359
details (3.4.6), and schedules (3.4.7). Most sections are drawn at 3/4 inch scale but larger scales
360
may be used, if more detail is needed for clarity. Sections are usually drawn from a point of view
361
perpendicular to that of the drawing that calls out for the section, and is oriented by pointers on
362
the section call out (Fig.4.7). A section cut will show the geometry and reinforcement details at
363
the cut plane, and may be drawn on a plan sheet, a sections sheet, or on a details sheet. The cut
364
identifies the section number and the sheet number where the section is drawn.
22
365
366
Photo 7: Perry Project 15121.00 – Permit Drawings 2015-09-30
367
Fig. 4.7—Example plan sheet section cut call out and section sheet section cut detail
368
369
4.8 Large scale view sheets
Large scale views are used if a dramatically increased scale of a section or detail is
370
needed to show additional clarity in an area of a structure. They are used to clarify
371
reinforcement detailing in an unusual element, such as a curved stair case, complex elevator
372
core, or heavily reinforced link beam. These sheets are rarely titled "large scale views" but are
373
usually titled by what is being shown on the sheet. For example, "Stairs – Plans and Sections"
374
could be an example title for a large scale view sheet for a stair tower. See Fig. XXXXXXX
375
4.9 Detail sheets
376
377
Details are usually drawn from the same point of view as the drawing that calls out the
detail (Fig. 4.9a).
23
378
379
Photo 8: Perry Project 15121.00 – Drawings Issued for Permit 2015-09-30
380
Fig. 4.9a—Example plan detail call out and detail on detail sheet
381
A separate detail sheet is usually used on a project. However, small projects may have a
382
single sheet that combines sections (4.7), details, and schedules (4.10).
383
Many details are drawn at 1/2 inch to 1 inch scales, but larger scales are used if needed for
384
clarity. In heavily congested areas, using full scale drawings is suggested to help with checking
385
constructability. <a couple of figures will be helpful to show this>
386
Details that are applicable to commonly encountered conditions are usually placed on
387
“typical details” sheets. Often the typical details are schematic only and are not drawn exactly.
388
When the typical details are schematic only, the information regarding the detail is shown in a
389
separate table or given in the notes. If not, it is typically shown just as an example of what needs
390
to be done and the contractor has some freedom to choose the best means and methods for
391
building the detailed item as shown.
392
393
For example, trim reinforcement around a slab or wall opening is often standard for a
certain range of opening sizes, and this arrangement is shown in a typical detail. This allows the
24
394
contractor to trim any opening within the stated range without asking the engineer for a specific
395
solution. Other typical details include reinforcement around an in-slab conduit, a mechanical chase
396
through a concrete slab, openings through a beam, reinforcement termination details at edges of
397
concrete, contraction joints in slab-on-ground, and construction joints.
398
Bundling bar details for splice and special development lengths that affect many different
399
types of members, such as heavily reinforced slabs, beams, columns, and walls is best shown in a
400
typical detail on the respective member schedule sheet because the information is member specific
401
and should be shown in the typical details sheets. See Fig. XXXXXXX – what’s the offset at
402
laps?
403
Shear reinforcement in a one-way slab is rarely used, but if it is, the shear reinforcement
404
area is typically shaded or hatched on the plan drawing. A detail should be included and
405
sometimes on the slab schedule sheet to indicate bar size, spacing of shear reinforcement, and
406
shape of bent bar. Headed shear studs may also be a viable option and a detail should be drawn if
407
chosen. See Fig. XXXXXXX
408
4.10 Schedule and Diagram Sheets
409
Schedule sheets provide reinforcement information for various members, such as slabs,
410
beams, columns walls and foundations. A diagram to explain the information in the schedule is
411
usually provided (Fig. 4.10).
25
412
413
Photo 9: Perry Project 14146.00 – Drawings Issued for Permit Corrections 2014-10-29 – 3/S1.0
414
Fig. 4.10—Diagram provided to explain schedule information
415
Member schedules usually contain the following:
416

417
Member mark which should have a standard naming convention and be identified on plans
an elevations
418

Member dimensions
419

Member reinforcement
420
421
422
423
424
425
426

Remarks or notes describing atypical reinforcement patterns, elevation, concrete
strength etc.
4.10.1 Slab Schedules
Slab schedules usually contain the slab mark, thickness of slab, bottom reinforcement and
top reinforcement, and any notes or remarks necessary for that slab. See Fig. XXXXXXX
For one-way slabs, the LDP can use the termination rules to use material more efficiently.
Please see Figure X.XX for example details.
26
427
Two-way slabs supported by edge walls or by edge-beams require reinforcement in the top
428
and the bottom of the slab at the intersection of the two-way slab and edge members. This
429
reinforcement is shown using typical details if it occurs throughout the structure or the information
430
is shown right on the plan drawings if it is not a prevalent detail. Please see Figure X.XX for
431
example details.
432
Two-way slab structural integrity reinforcement requirements can be shown in different
433
ways. The splicing requirements for structural integrity reinforcement can be shown on the slab
434
schedule diagram. The requirement of two column strip bottom bars or wires that are required to
435
go through the columns can also be shown on the plan or in a typical detail. The typical detail
436
option is probably used most often because other information can be shown on the same detail if
437
the designer wishes. When using shearheads, the two column strip bottom bars or wires should be
438
shown in a typical detail. Please see Figure X.XX for example details.
439
Two-way shear reinforcement in slabs could be headed shear studs, typical stirrups, or
440
structural steel members. Headed shear studs are used most often and a detail should be drawn to
441
show the layout of the headed shear studs especially at a column. When several different layouts
442
of headed shear studs are needed in a structure, it may be clearer to use a series of headed shear
443
stud diagrams, possibly in a table, to show their layouts as they vary throughout the structure. The
444
plan drawings should be marked at each column to indicate which particular headed shear stud
445
diagram should be used at that location. While stirrups are not used as regularly as headed shear
446
studs for two-way shear reinforcement, they are permitted by the ACI 318 Code. When stirrups
447
are used for two-way shear reinforcement, they should be shown using the methods described
448
above for showing headed shear studs. Structural steel members are rarely used and if used their
449
locations should be identified and special details provided. See Fig. XXXXXXX
27
450
451
4.10.2 Beam and girder schedules
Beams and girders are often shown in the same schedule and the information presented is
452
similar. For simplicity of wording, the term beam and beam schedule will be used here to include
453
both. Beam schedules contain the beam mark, beam width and depth, top and bottom
454
reinforcement and extent, post-tensioning reinforcement when applicable, and stirrup size and
455
spacing (Fig. 4.10.2).
456
457
Photo 10: https://sites.google.com/site/ae390final/gradebeamchedule.JPG
458
459
Fig. 4.10.2—Example grade be schedule
Along with the beam schedule, there should be a diagram to show the basic layout of the
460
reinforcing steel in a beam. For clarity, this often requires two diagrams with one showing the
461
longitudinal reinforcing steel and the other showing the shear reinforcing steel. The diagrams are
462
often split into the following different types of beams: single span, multiple spans, and cantilever.
463
464
465
When applicable, the post-tensioning is typically specified using the assumed effective
force that is expected to be applied to the beam or using the number of tendons from the design. .
Typical shear reinforcing stirrup sizes and spacing are shown in the schedule by specifying
28
466
each group of stirrups. For example, a beam may need 6-#4 stirrups at 2"o.c. and then 6-#4
467
stirrups at 6"o.c. at each beam end and the remainder along the length of the beam at 12" o.c.
468
Often, this type of shear reinforcement spacing at the ends of the beams or at other special shear
469
reinforcing locations is shown in a typical diagram on the beam schedule sheet. The LDP should
470
provide a detail of stirrups showing the shape of the stirrup.
471
4.10.3 Column schedules
472
Column schedules usually contain the column mark, a vertical reinforcement, and the size
473
and spacing of shear reinforcement. See Fig. XXXXXXX Along with the column schedule,
474
typical layout information for the column reinforcement from the bottom of one level to the bottom
475
of the next or the top of the column is often shown in section cuts or diagrams. These diagrams
476
should show splice locations, including locations of staggered splices and reinforcement
477
termination requirements. Often, the spacing of the shear reinforcement at the tops and bottoms of
478
columns varies and is shown in a typical diagram on the column schedule sheet. If applicable, the
479
following diagrams also should be included with the column schedule: basic transition from floor
480
to floor, offset transitions, sloped transitions, and top of column terminations..
481
4.10.4 Wall schedules
482
Wall schedules usually contain the wall mark and the amount of vertical and horizontal
483
reinforcement for each curtain of reinforcement required.
484
Along with the wall schedule, typically there will be a diagram of the wall from the bottom of the
485
wall to the top of the wall sometimes with section cuts showing the layout information for the wall
486
reinforcement. These diagrams should show splice locations, including locations of staggered
487
splices if necessary. Placing location of the reinforcement should be clearly shown, such as VEF,
488
HIF, HOF, caps, etc. See Fig. XXXXXXX See Chapter 3 for other abbreviations. [Johnston
29
489
comment: ACI style is to define acronyms where they first appear in the text. If there is a need to
490
provide acronyms or abbreviations commonly used in concrete reinforcing steel drawings, we
491
should consider adding a table of abbreviations in Chapter 3, perhaps in a Section “3.3
492
Abbreviations”.]
493
4.11 Foundation sheets and schedules
494
Foundations are sometimes treated separately from the remainder of the structural systems
495
because of their unique characteristics and in general, the fact that foundation systems are used for
496
many various superstructure types. Foundation drawings may be issued separately from the
497
superstructure drawings or may be the only reinforced concrete drawings on a project. Foundation
498
sheets are commonly used for shallow foundations (Fig. 4.11a) such as strip footings, isolated
499
footings, combined footings, mat foundations and grade beams or for deep foundation systems that
500
may include pile caps, piles, drilled piers and caissons.
501
502
Photo 11: Perry Project 15121.00 – Permit Drawings 2015-09-30
30
503
504
505
Foundation drawings can be individualized or used with schedules and foundation marks used to
506
represent the foundation type are usually identified by the first letter of the foundation member
507
represented. For example, P1 is usually related to a pile cap over piles, while F1 is often used to
508
describe a shallow footing and GB1 is often used to mark grade beams. In any case, it is
509
recommended that an Abbreviation and Notation Legend be included in the drawing sheet for
510
clarity and ease of identification. Grade beam schedules are similar to elevated beam schedules
511
and guidelines regarding beam schedules are shown in 3.4.7.2. Pile cap schedules should include
512
the dimensions of the pile cap and the required reinforcement in each one. Footing schedules are
513
usually similar, with the schedule containing footing dimensions and the required reinforcement in
514
each direction. Drilled piers are often not scheduled by mark, but by shaft and bell diameters. The
515
schedule should include a listing of vertical reinforcement, tie reinforcement, and minimum
516
distance that the reinforcement must extend into the top of the pier. See Fig. XXXXXXX
517
Fig. 4.11a—Foundation plan drawing
Each different type of foundation element on the project should have a corresponding
518
typical diagram that is referenced from the schedule. This typical diagram will show a typical
519
layout of the member with typical locations of the reinforcement inside of it. See Fig. XXXXXXX
520
Shear reinforcement in a foundation is not frequently used, but when it is, it is typically
521
detailed in a manner similar to a beam. When stirrups are used for shear reinforcement, they should
522
be shown on the foundation schedule and a separate detail or section should be considered.
523
4.12 User defined sheets
524
User defined sheets are used to show information that is not presented on other sheets,
525
List of examples needed.
526
4.13 3D Representations
31
527
3D representations or isometric sketches are not commonly used but can be very helpful
528
to show an especially complicated connection or joint or to coordinate among different
529
disciplines to prevent clashes between different systems. (Sample needed.)
32
1
CHAPTER 5—DESIGNING FOR CONSTRUCTIBILITY
2
5.1—Defining requirements for cover, development, splices and clearance
3
5.1.1—Clear Cover
4
5.1.2—Bar development
5
5.1.3—Bar Splices
6
5.1.4—Clearance between bars
7
5.2— Defining Bar Placing Configuration
8
5.2.1—Staggered laps
9
General Notes should never just state, “Stagger all laps”. Staggering laps can add extra costs to a project in
10
terms of detailing, greater number of different bar lengths, and placing. The LDP should note possible exceptions
11
such as for temperature steel and wall horizontals.
12
The LDP should clearly indicate the nature of the stagger. Is the stagger one lap length, a double lap length,
13
or a specified dimension between the laps? A detail such as shown in Fig. 5.2.1 is the best way to show the intent.
14
Figure 5.2.1
15
Lap locations should be clearly indicated, as well areas where laps are not allowed. Staggering of couplers
16
should be equally defined and indicated.
17
5.2.2—Embedment into support
18
Tables of embedment requirements are usually sufficient (see Table 5.2.2). Care should be taken to clearly
19
indicate special embedment locations and appropriate instructions given to ensure they are correctly placed.
20
Figure 5.2.2
21
5.2.3—Bar dimensioning
22
The most common bar dimensioning issue involves hooks. When the LDP dimensions hooked bars, he
23
should be sure to indicate at least in the General Notes whether the dimension does or does not include the hook.
24
(Insert Fig.)
1
25
Rebar detailers will assume that all hooks are standard hooks unless indicated otherwise. Often drawing
26
sections of raft footings show the bottom and top bars hooked and lapping. If standard hooks are detailed there
27
will be no lap. The LDP should clearly indicate if a lap is intended and if so, dimension the lap. (Insert Fig.)
28
Where standard hooks are too long to fit with the concrete member, the hook should be clearly dimensioned
29
on the drawing.
30
5.2.4— Skewed bars
31
In trapezoidal shaped slabs, the LDP should clearly indicate if the main bars are perpendicular to the parallel
32
sides or parallel to the sloped sides. He should also indicate if the spacing of the bars is measured at right angles
33
to the main bars or along the skew. These points should also be made clear for triangular or other irregular
34
shaped slabs. (Figures may be beneficial).
35
Top steel over beams in skewed slabs may conflict with top bars from adjacent regular shaped slabs and may
36
cause layering and clearance problems. These should be considered and addresses by the LDP.
37
5.2.5—Termination of vertical bars
38
The LDP should always indicate how vertical bars are to be terminated. If the bars are to be hooked there are
39
several things to be considered. If the hook is not a standard hook the length should be indicated. Is the hook
40
located in either of the top layers or beneath both layers? Is the member into which the hook is to be embedded
41
sufficiently deep to accommodate the curvature of the bend? If the direction of the hook is critical this should be
42
clearly indicated. Member intersections may require additional consideration of bar interferences.
43
5.2.6—Beam Stirrups
44
On a beam schedule it should be clear whether a stirrup callout, for example, for 3 @ 6”; 5 @ 9”; rem @ 12”,
45
is referring to the number of stirrups or the number of spaces. If spacing of the first stirrup from a support is
46
critical it should be indicated, otherwise it will be located one-half space from the support.
47
In multiple tie sets, indicate if these are to be a series of nested stirrups or a series of interlocking stirrups. If
48
open stirrups are indicated try if possible to provide a continuous top bar in each stirrup hook. Consider a greater
49
quantity of smaller bars rather than fewer larger bars.
2
50
In very narrow beams consider if the stirrup hooks will allow the top bars to fit within the tie. If critical,
51
indicate if longitudinal bars are to be lapped in a vertical or horizontal plane. At intersecting beams indicate if the
52
stirrups run through one beam or the other, or through both beams.
53
5.3 – Foundations
54
This section applies to non-prestressed steel reinforcement of shallow and deep structural foundations as
55
defined by ACI 318 Chapter 13. See Section 5.6 for supplemental requirements for deep foundations in structures
56
assigned to Seismic Design Categories D, E, and F as prescribed by ACI 318 Section 18.13.
57
5.3.1 Types
58
Foundation systems can be categorized as either shallow foundations or deep foundations. Shallow
59
foundations include types such as strip footings; isolated, spread, or pad footings; mat foundations, and grade beams.
60
Deep foundation types include piles, drilled piers, and caissons as described in ACI 336.3R and ACI 336.3R. Pile
61
caps are shallow elements transferring load to deep foundations.
62
5.3.2 Bar Arrangements
63
Bar arrangements vary widely based on both the foundation type and the lateral, gravity, and torsion
64
loadings imposed on the foundations. The bar arrangements described in this section are general and common
65
arrangements. The LDP should specify needed bar arrangements for the appropriate conditions.
66
Shallow foundations such as strip, isolated, and mat foundations often have a bar arrangement similar to
67
that of a slab having a top and/or bottom mat of reinforcement with bars in each direction. In some instances, the
68
bars may be required to be hooked at ends for development as prescribed by the LDP. Grade beams and tie beams
69
sometime span between foundation elements such as pile caps. Grade beams usually project above grade to support
70
walls; tie beams are usually below grade and spread lateral loads to multiple deep foundations. Grade beams and
71
tie beams have two primary reinforcement arrangements. The first is similar to a beam with reinforcing ties or
72
stirrups around the perimeter of the beam, top and bottom longitudinal steel, and in some cases side longitudinal
73
steel. The second arrangement is still similar to a beam, however may only have top and bottom reinforcement.
74
Ties in the second arrangement may only be required for constructability as a method to hang the top reinforcement.
75
See Fig. 5.3.2a and 5.3.2b for examples.
3
76
Deep foundations are often circular and thus have a bar arrangement similar to that of a circular column
77
with a tie around the perimeter and longitudinal steel spaced around the perimeter inside the tie. Smaller drilled
78
piers may only have longitudinal steel that is centered in the drilled pier; in these cases, reinforcement may be added
79
for constructability to keep the reinforcement centered in the shaft. Though reinforcing in piers is similar to that of
80
columns, it is not fully prescribed by ACI 318 and therefore is often excluded from the ACI 318 Section 25.7.2.4.1
81
requirement for standard hooks at the ends of ties except for the case of piers in seismic design categories D, E, and
82
F. See Fig. 5.3.2a and 5.3.2b for examples.
83
5.3.3 Layering
84
Layering in foundations primarily only applies to non-grade beam shallow foundations as grade beams are
85
typically reinforced similar to beams and deep foundations are typically reinforced similar to columns as noted in
86
5.3.3. For strip footings, the layering is most commonly found with longitudinal reinforcement running flush to the
87
top and bottom covers and any transvers reinforcement inset from the longitudinal reinforcement. Isolated pad
88
footing layering most often depends on the geometry of the pad footing. For square pad footings, layering can go
89
either way, and for rectangular pad footings reinforcement along the larger dimension should be pushed to the
90
bottom and top cover and the reinforcement along the shorter dimension should be inset. For mat foundations not
91
supported by deep foundations, the layering will be similar to that of a rectangular pad footing with the
92
reinforcement running along the larger dimension placed at cover and the transvers reinforcement inset. Each case
93
discussed above are typical layering conditions for foundations; however, each is also dependent on the design of
94
the foundation. One should always refer to the contract documents for specific requirements. Contract documents
95
should specifically note the layering arrangement when it is critical to the design. See Fig. 5.3.3a and 5.3.3b for
96
examples.
97
All reinforcement layering should be properly supported to keep the reinforcement at the correct location
98
in the element. For bottom reinforcement cast against the earth, concrete or masonry blocks also known as “dobies”
99
are most commonly used. Bar supports with feet can dig into the soil causing a loss of cover and should be avoided
100
when on earth. For bottom layers on voids, wire bolsters and chairs can also be used. The support of top mats of
101
reinforcement can be supported by bolsters, chairs, or standees depending on the supporting height. Cover for
4
102
drilled piers can be obtained with alignment bars, alignment wheels, or in the case of centered reinforcement without
103
ties by using crossing reinforcement.
104
5.3.4 Construction and Expansion Joints
105
When construction and expansion joints are not specifically shown on the contract documents, the LDP
106
should give guidance for construction and expansion joint locations and spacing and should review joint locations
107
provided by contractor for compliance.
108
5.4—Walls
109
5.4.1—Introduction
110
In ACI 318, Chapter 2, Section 2.3, a wall is defined as “a vertical element designed to resist axial
111
load, lateral load, or both, with a horizontal length-to-thickness ratio greater than 3, used to enclose or
112
separate spaces”.
113
Concrete walls are structural elements that are generally used as vertical and lateral force-resisting
114
members. Walls may be used in underground or above grade tanks to contain liquids, as retaining walls or for
115
providing one-sided lateral confinement for soil or other materials and for providing continuous support for floor
116
or roof systems, in which case they must absorb and resist all reactions from the these systems.
117
5.4.2—Scope
118
This section shall apply to steel reinforcement of nonprestressed ordinary structural walls, including:
119
cast-in-place, precast in-plant and precast on-site, including tilt-up construction, as defined in ACI 318 Chapter
120
11. This section shall also apply to retaining walls and walls that are part of underground or above ground
121
tanks designed for the purpose of containing liquids or granular materials. For steel reinforcement in special
122
structural walls see Section 5.6 of this Manual.
123
5.4.3—General
124
Steel reinforcement shall be provided in walls to resist all in-plane and out-of-plane forces acting on
125
ordinary structural walls, as shown in Figure 5.2.1. Walls subjected to these forces will require longitudinal and
126
transverse reinforcement, as well as additional reinforcement around openings. Design requirements are contained
127
in ACI 318-14, Sections 11.3, 11.4 and 11.5.
5
128
129
Design of cantilever retaining walls shall be designed in accordance with ACI 318-14, Sections 22.2
through 22.4, with minimum horizontal reinforcement in accordance with ACI 318-14, Section 11.6.
130
131
132
Figure 5.2.1: In-plane and out-of-plane forces.
133
(Source: ACI 318-14. Chapter 11)
134
5.4.4—Considerations
135
Reinforcement limits for vertical and horizontal bars are indicated in Section 11.6 (Sub-Sections 11.6.1
136
and 11.6.2) of ACI 318, for relative values of Vu (factored shear force). General bar detailing should conform to
137
ACI 318 Section 11.7. Concrete cover for reinforcement shall conform to Table 20.6.1.3.1 of ACI 318, Chapter
138
20. Development lengths and splice lengths of reinforcement shall be in accordance with ACI 318, Sections 25.4
139
and 25.5, respectively. Distribution and spacing of transverse and longitudinal reinforcement shall conform to
140
ACI 318, Sub-Sections 11.7.2 and 11.7.3. In ordinary structural walls, if longitudinal reinforcement is required
141
for axial strength or if Ast exceeds 0.01Ag, longitudinal reinforcement shall be laterally supported by transverse
142
ties. In all walls, reinforcement is required around wall openings and shall comply with ACI 314 Section 11.7.5.
143
5.2.5—Best Practices
144
It is generally recommended, for constructability purposes, that steel reinforcement on both faces of a
145
wall be placed with equal spacing or that spacing of reinforcing bars of one face be a multiple of the other or that
146
spacing of bars at each face be multiple of a common value, for example: 2”, 3” or 4”, etc. Transverse or
6
147
horizontal reinforcing bars should be placed closest to wall face and conform to cover limits mentioned in Table
148
20.6.1.3.1 of ACI 318, Chapter 20. Reinforcement is required in both directions and also diagonally at the
149
corners, around wall openings. This reinforcement shall consist of at least 2 No. 5 bars, anchored to develop fy in
150
tension, and as a rule of thumb, should be at least equal in area to the bars interrupted by the openings.
151
5.4.5.1—Footing to wall connections
152
In cantilever retaining walls, vertical reinforcement should extend through the height of the wall
153
foundation and be anchored on top of the foundation slab bottom reinforcement. The slab height dimension
154
should be such as to permit the vertical reinforcement bar standard hooks to be correctly anchored a distance ldh.
155
5.4.5.2—Corners and intersections
156
Horizontal wall reinforcement must be anchored in vertical wall corners and intersections, preferably with
157
standard 90 degree hooks. To achieve proper anchorage, the bar must be extended across the intersection so that
158
the end hook will be placed at the opposite (outer) face of the intersecting wall, at corners and mid intersections.
159
When additional diagonally placed horizontal reinforcement is needed, to resist shear forces and to help
160
avoid cracking and opening at the corner or intersection, it should also be extended to the opposite face of each
161
intersecting wall and terminate with a bar bend at least equal to the bar Development Length (ld).
162
A typical detail of the correct bar arrangement at wall corners and mid length intersections will clarify the
163
information for the detailer, for correct bar dimensioning and placing of reinforcing bars and will help avoid
164
errors that may compromise the structural integrity of the walls.
165
5.4.5.3—Steps and sectional transitions
166
Steps and sectional transitions at base of walls should be correctly detailed, showing the transitional
167
reinforcement bars. Steel reinforcement across wall steps or sectional transitions shall comply with ACI 318-14
168
Chapter 25. Special attention should be given to bar anchorage, development lengths, and to providing
169
continuous and correctly anchored reinforcement across any section change.
170
5.4.5.4—Multiple curtains and layers
171
172
7
173
174
5.4.5.5—Construction Joints, Contraction Joints, Expansion Joints and Waterstops
175
Construction Joints: Can be vertical or horizontal joints that are left in place between two successive
176
pours of concrete. Shear Keys can be used to increase the shear resistance at the joint. If keys are not used, the
177
surface of the first pour must be cleaned and roughened previous to the next concrete pour. Keys are more usually
178
formed in the wall base to give the stem more sliding resistance. Wall reinforcement is placed continuously across
179
the joint.
180
Contraction Joints: Vertical joints formed or cut into the wall that allow the concrete to shrink without
181
noticeable cracking. Contraction joints can usually be about 5-6 mm. (1/4”) wide and about 12 to 20 mm. (1/2” to
182
3/4”) deep, and are provided at various intervals, depending on wall height, thickness and amount of
183
reinforcement, but usually not exceeding 9 to 10 m. (around 30 ft.). Wall reinforcement is placed continuously
184
across the joint.
185
Expansion Joints: Vertical expansion joints are placed into the wall to permit expansion due to temperature
186
changes. These joints should be filled with flexible joint fillers to impede passage of water or other liquids.
187
Horizontal greased steel dowels are usually placed across the joint to tie adjacent sections together. Expansion
188
joints are located at various intervals, depending on wall dimensions, but should not be separated more than 25 to
189
30 m. (75 to 90 ft.) apart. Wall reinforcement is discontinuous across the joint (not placed across the joint but
190
rather terminated at each joint face).
191
Waterstops: These are continuous molded sections, traditionally made of rubber, neoprene or PVC, that are
192
placed along the joint, embedded equally in each adjacent section, with the purpose of making the joint
193
watertight. There are various sections that can be used for the different types of joints named above. Steel
194
reinforcement should be detailed with consideration to the required waterstop to be used in the joint.
195
References
196
1. Building Code Requirements for Structural Concrete ACI 318-14.American Concrete Institute. USA. 2014
197
2. Concrete Network.com
198
(http://www.concretenetwork.com/concrete/poured_concrete_retaining_walls/provisions.htm)
8
199
3. http://www.chemstop.com/SubPacks/General_Waterstop_Brochure.pdf
200
5.5—Columns
201
This section applies to non-prestressed and steel reinforcement of structural columns as defined by ACI
202
318 Chapter 10 and portions of deep foundations described by ACI 318 Section 13.4.3.1 as portions of deep
203
foundation members in air, water, or soils not capable of providing adequate restraint throughout the member
204
length to prevent lateral buckling.
205
206
207
5.5.1—Vertical Bar Arrangement
Vertical bar arrangement is prescribed by ACI 318 Section 10.7.3 requiring a minimum of (3) vertical
208
bars with a triangular tie, (4) vertical bars with in rectangular and circular ties, and (6) vertical bars enclosed by
209
spiral ties or for columns in special moment frames enclosed by circular ties. Vertical reinforcement is most
210
commonly arranged equally spaced around the perimeter of the column and enclosed by tie reinforcement, and
211
includes at least a vertical bar in each corner of non-circular columns.
212
213
5.5.2—Ties
214
Tie reinforcement is prescribed by ACI 318 Section 10.7.6 and Section 25.7.2. As noted in in ACI 318
215
Section 25.7.2 ties should have a minimum clear spacing of four-thirds the nominal maximum coarse aggregate
216
size and a maximum of the lesser of sixteen longitudinal bar diameters, forty-eight tie bar diameters, and the
217
smallest dimension of the column. Spirals should be spaced continuously with the clear spacing being at least the
218
greater of one inch and four-thirds the nominal maximum coarse aggregate size and a maximum of three inches.
219
The smallest tie size should be #3 for longitudinal bars #10 and smaller and #4 for ties enclosing #11 bars and
220
larger. Alternatively, typical tie reinforcement can be replaced by welded wire reinforcement of an equivalent
221
area except for spiral ties and special seismic systems. For rectangular ties, the tie arrangement must provide
222
lateral support for every corner and alternate longitudinal bar with a hook of a tie no more than 135 degrees. Tie
223
reinforcement must provide lateral support for every longitudinal bar enclosed by a rectangular tie when the clear
224
spacing between laterally supported longitudinal bars exceed six inches on each side. Circular tie reinforcement
9
225
must lap by a minimum of six inches, terminate with standard hooks at each end that enclose a longitudinal bar,
226
and laps must be staggered around the perimeter.
227
228
Per ACI 318 Section 10.7.6, at member ends or transitions the bottom tie must be located at most one-half
229
the tie spacing above the top of footing or slab. The top tie should also not be located more than one-half the tie
230
or spacing below the lowest horizontal reinforcement in the slab, drop panel, or shear cap above. In the case of
231
beams or brackets framing into all sides of a column the top tie must be located within three inches below the
232
lowest horizontal reinforcement in the shallowest beam or bracket. For spiral reinforcement, the bottom of the
233
spiral should be located at the top of the footing or slab and the top should conform to ACI 318 Table 10.7.6.3.2
234
shown below.
235
236
Anchor bolt confinement must also be provided by tie reinforcement per ACI 318 Section 10.7.6.1.6
237
requiring that anchor bolts must be enclosed by transvers reinforcement that also surrounds at least four
238
longitudinal bars with in the column. The transvers should be distributed within the top five inches of the top of
239
the column and consist of at least two #4 bars or three #3 bars.
240
5.5.3—Detail at Steps and Transitions
241
At steps and transitions, the longitudinal reinforcement often is detailed with an offset bend, covered in
242
ACI 318 Section 10.7.4. The slope of this transition should not exceed one to six. If there is a column offset
243
greater than three inches this transition is not allowed and must be made with separate dowels adjacent to the
244
offset column faces. Where longitudinal bars are offset, horizontal support should be provided throughout by
245
either ties, spirals, or parts of the floor construction. If transverse reinforcement is provided, they should be
246
placed no more than six inches from the points of the bend per ACI 318 Section 10.7.6.4. See below for detail
247
examples at column steps and transitions.
248
249
Offset bend locations should be specifically noted by the LDP?
250
5.5.4—Laps
10
251
Column lap lengths should be specifically noted by the LDP. Guidance should be given through
252
schedules, notes, or other methods to accurately prescribed lap requirements per column. Generally, compression
253
laps can be allowed in gravity columns. These splices lengths can be factored by .83 when the effective area of
254
tie reinforcement through the lap zone meets the requirements of ACI 318 10.7.5.2.1(a) or can be factored by .75
255
when spiral reinforcement is provided in accordance to ACI 318 Section 25.7.3. Special attention should be given
256
to areas of laps due to congestion.
257
258
ACI 318 Table 25.7.3.6 dictates spiral reinforcement laps where the most common lap length is forty-
259
eight bar diameters. See below for ACI 318 Table 25.7.3.6. Spiral reinforcement shall be anchored by 1 1/2 extra
260
turns of the spiral bar per ACI 318 Section 25.7.3.4.
261
262
263
264
5.5.5—Termination of Vertical Bars
Termination of vertical column reinforcement into beams and slabs is prescribed by ACI Chapter 15.
Termination of vertical column reinforcement into foundations is prescribed by ACI Section 16.3.
265
266
5.6—Beams
267
[DWJ Comments: Some statements in Chapter 6 sections may be overlapping statements in other chapters – needs
268
to be sorted out when drafts are more complete. The detailer and contractor should not be referenced to ACI 318.
269
The use of the words “details” and “detailing” sometimes leads to uncertainty about whether the reference is to
270
design drawings vs. placing drawings. Also, can’t use “shall” and “must” in an ACI report document.]
271
272
This section applies to steel reinforcement of non-prestressed beams, as defined in ACI 318 Section 9.1.1.
273
General reinforcement bar detailing should conform to ACI 318 Sections 9.6 and 9.7. Bundled bars should be in
274
accordance with ACI 318 Section 25.6. Development lengths and splices of deformed reinforcement should be in
275
accordance with ACI 318 Sections 25.4 and 25.4, respectively. Reinforcement detailing for beams that are part of
276
a seismic force resisting system is covered in Chapter XX of this Manual.
11
277
Code requirements often refer to minimum or maximum values. Being equal to or greater than a minimum
278
value is acceptable; being equal to or less than a maximum value is acceptable. A good design should avoid issues
279
that may arise due to the indiscriminate use of minimum code values without considering other factors. For
280
example, it is important to avoid or reduce constructability issues due to interference between or overcrowding of
281
steel reinforcement and loss of concrete cover or spacing problems between reinforcing bars due to incremental
282
tolerance buildup. The LDP should also present clear information in design drawing details and schedules, which
283
will aid the detailer in correctly understanding the essence and intent of the design, thus saving time in additional
284
consultations and revisions. These considerations will help the process of producing good detailing drawings for
285
construction.
286
287
5.6.1—Layering of beam bars at intersections
288
ACI 318 Sections 15.2 and 15.4 provide requirements for steel reinforcement at beam-column joints.
289
Longitudinal beam reinforcement in beam to beam and beam to girder connections should be detailed in such a way
290
that the beam’s top and bottom steel bar layers will be contained between the girder’s top and bottom longitudinal
291
reinforcing bars. Consideration should be given to intersecting beam depth dimensions and concrete cover for each
292
of intersecting members. Special attention should be given to ACI 318 Sections 9.7 and 25.4.
293
5.6.2—Layering of slab bars at beam intersections
294
ACI 318 Section 7.7 provides reinforcement detailing requirements for slabs. Slab longitudinal top layer
295
reinforcement is placed on top of beam top layer reinforcement and properly secured directly to beam bars. Slab
296
longitudinal bottom layer reinforcement runs continuously through the beam web in intermediate connections and
297
at end supports is anchored in the beam web width. In one-way joist systems, consideration for structural integrity
298
should be given in compliance with ACI 318 Section 9.8.
299
Figures
300
5.6.3—Depth of beams at intersections
301
Generally, principal beams or girders will be dimensioned for greater loads than secondary intersecting beams,
302
thus will normally be larger in both width and depth. In any case, dimensioning different depths for members in
12
303
beam to beam and beam to girder connections will facilitate passage of longitudinal reinforcing rebar layers through
304
the intersection without affecting specified concrete cover. As discussed in Section 6.6.1, special attention should
305
be given to ACI 318 Sections 9.7 and 25.4.
306
Figures
307
5.6.4—Tie arrangements
308
ACI 318 Sections 25.7.1 and 25.7.2, respectively, provide requirements for stirrups and ties. Both should
309
extend as close to the compression and tension surfaces of the member as cover requirements and proximity of other
310
reinforcement permit and are to be anchored at both ends. Stirrups can be used to resist shear and torsion forces in
311
a beam member and can consist typically of deformed bars, deformed wires, or welded wire reinforcement either
312
single leg or bent into L, U, or rectangular shapes and located perpendicular to, or at an angle to, longitudinal
313
reinforcement. Ties should consist of a closed loop of deformed bar with spacing in accordance with 25.7.2.1. Tie
314
bar diameter should be at least No. 3 for enclosing bars No. 10 or smaller and No. 4 for enclosing bars No. 11 or
315
larger and bundled longitudinal bars. Rectilinear ties should be arranged to satisfy 25.7.2.3. Stirrups used for torsion
316
or integrity reinforcement can be either closed stirrups placed perpendicular to the beam axis, as specified in 25.7.1.6
317
or can be made up of two pieces of reinforcement when conditions in 25.7.1.6.1 are met.
318
For large beams with long spans and heavy reinforcement, closed stirrups may reduce constructability. The
319
long bars should be threaded into the beams through column verticals and other obstructions. With open stirrups
320
the long bars are simply lifted and dropped into place without any threading being required. This significantly
321
reduces the labor cost of installation. Once the bars are installed the stirrups may be capped as necessary.
322
If closed stirrups are the only option shown on the design documents, the detailer should issue an RFI requesting
323
a change of stirrup configuration to open/capped style. This process may delay the detailer days or even weeks
324
depending on the turn-around time for RFI’s. This is usually an unnecessary interruption since in most cases the
325
open/capped tie option is approved. Design documents that clearly show both options whenever open ties are
326
acceptable speeds up the detailing process and reduces the document flow required by the designer, contractor, and
327
detailer and constructability is enhanced.
328
Figures
13
329
5.6.5—Arrangement of longitudinal bars
330
ACI 318 Chapters 9 and 25 provide requirements for longitudinal reinforcement bars in beams. Clear spacing
331
in a horizontal layer should be at least the greatest of 1 in., db, and (4/3) dagg. For parallel nonprestressed
332
reinforcement placed in two or more horizontal layers, reinforcement in the upper layers should be placed directly
333
above reinforcement in the bottom layer with a clear spacing between layers of at least 1 in. Standard hooks for the
334
development of deformed bars in tension should conform to ACI 318 Table 25.3.1. Reinforcement limits should be
335
in accordance with ACI 318 9.6. Attention should be given to ACI 318 9.7.2.3, for detailing skin reinforcement in
336
beams with depth h exceeding 36 in. Design of longitudinal reinforcement should comply with ACI 318 9.7.3.
337
Requirements for structural integrity are contained in ACI 318 9.7.7.
338
In general, especially with multi-leg tie arrangements, a number of continuous longitudinal top and bottom bars
339
should be placed so as to occupy the necessary positions required for every corner or leg of the tie set and the rest
340
of the bars will be spaced across the remaining space, in one or more layers. This will permit the secure fastening
341
in position of the ties that will guarantee their correct shear resisting function and also to provide lateral confinement
342
for the longitudinal bars.
343
Figures
344
5.6.5—Beam steps
345
ACI 318-14 Chapters 9 and 25 provides requirements for steel reinforcement across beam steps or along beam
346
section changes. Special attention should be given to bar anchorage, development lengths, and providing continuous
347
and correctly anchored reinforcement across any section change.
348
Figures
349
5.6.6—Special details
350
Requirements of special details for steel reinforcement in beams are subject to the LDP’s judgement where non-
351
typical conditions, either geometrical or for other reasons, cannot be fully and correctly represented by only typical
352
details such as Elevations and Sections. The governing criteria should be to present clear and precise information
353
for the detailer to help avoid misinterpretation of design drawings and delays in the detailing process.
354
Figures
14
355
5.6.7—Beam schedules
356
Beams with similar geometry and steel reinforcement distribution can be represented with typical details and a
357
beam schedule containing the specific information for bar diameters and dimensions, development and cut-off
358
lengths, etc. Clarity in identifying the different beams and their corresponding reinforcement is important for the
359
detailer to be able to correctly specify and detail the steel reinforcement in the placing drawings.
360
Figures
361
Section 5.7—Slabs
362
This section applies to steel reinforcement of non-prestressed slabs, as defined in ACI 318 Chapters 7 and 8
363
and ACI 421.1R.
364
5.7.1 Bottom Bars
365
366
The construction documents should include the minimum cover from the bottom, sides and or top of concrete
in sections or details along with the suggested bar support types to be used.
367
ACI 318 Section 25.5 provides reinforcement design requirements for splices. The drawings should include the
368
minimum splice lengths and embedment lengths into beams, columns, pilasters or other supporting elements. These
369
lap lengths should be shown in details, sections, plan or schedules.
370
Standard hooks for the development of deformed bars in tension should conform to ACI 318 Table 25.3.1 If
371
hooks are required at discontinuous end, the LDP should verify the hook dimension can be placed within the
372
specified slab thickness.
373
Figures
374
5.7.2 Top bars
375
The construction documents should include the minimum cover from the top and sides of concrete in sections
376
or details along with the suggested bar support types to be used. Support bar details with bar size and spacing should
377
be included on the drawings.
378
ACI 318 Section 25.5 provides reinforcement design requirements for splices. The drawings should include the
379
minimum splice lengths and embedment lengths into beams, columns, pilasters or other supporting elements. These
380
lap lengths should be shown in details, sections, plan or schedules.
15
381
Standard hooks for the development of deformed bars in tension should conform to ACI 318 Table 25.3.1 If
382
hooks are required at discontinuous ends, the LDP should verify the hook dimension can be placed within the
383
specified slab thickness.
384
Figures
385
5.7.3 One-Way slabs
386
ACI 318 Section 7 provides reinforcement design requirements for one-way slabs.
387
Transverse bottom layer reinforcement runs continuously across the span and is anchored in the beam web a
388
minimum of 6 inches. If using the 50% method, every other bar in the intermediate connection will be held back
389
from the beam face 0.125 of the clear span distance.
390
Transverse top layer reinforcement is placed on top of beam top layer reinforcement and properly secured
391
directly to beam bars and shall end with a standard hook at discontinuous ends. Support bar details with bar size
392
and spacing or use of temperature bars should be included on the drawings.
393
394
Longitudinal temperature bars run continuously with the specified lap and shall run through the beam web in
intermediate connections and at end supports is anchored in the beam web a minimum of 6 inches.
395
Specific details for projections of top bars and bars at openings and varying span widths should be included in
396
the contract documents. The support lines should be clearly marked to insure that the intent of the design drawings
397
are met. The calculations used for the top bar projections should be based on the clear distance between supports.
398
Construction, contraction, isolation and expansion joints should be located and dimensioned on the contract
399
documents to insure accurate placing of the reinforcement and required dowels. Standard hooks for the development
400
of deformed bars in tension should conform to ACI 318 Table 25.3.1. If hooks are required at discontinuous end,
401
the LDP should verify the hook dimension can be placed within the specified slab thickness.
16
402
403
5.7.4 Two-Way Slab
404
ACI 318 Section 7 provides reinforcement design requirements for two-way slabs.
405
Slab bottom layer reinforcement is placed in both directions and runs continuously across the span and is
406
anchored in the beam web a minimum of 6 inches.
407
Slab top layer reinforcement is placed in both directions on top of beam top layer reinforcement and properly
408
secured directly to beam bars and shall end with a standard hook at discontinuous ends. Support bar details with bar
409
size and spacing should be included on the drawings.
410
Specific details for bar layering and bars at openings and varying span widths should be included in the contract
411
documents. Construction, contraction, isolation and expansion joints should be located and dimensioned on the
412
contract documents to insure accurate placing of the reinforcement and required dowels. Standard hooks for the
413
development of deformed bars in tension should conform to ACI 318 Table 25.3.1. If hooks are required at
414
discontinuous end, the LDP should verify the hook dimension can be placed within the specified slab thickness.
17
415
416
417
5.7.5 Edges and Openings
418
Standard hooks for the development of deformed bars in tension should conform to ACI 318 Table 25.3.1. If
419
hooks are required at discontinuous end, the LDP should verify the hook dimension can be placed within the
420
specified slab thickness. Details of bar conditions at slab edges and openings should be included in the contract
421
documents. Trim bars should be shown in specific details on the drawings.
422
Figures
423
5.7.6 Steps and Depressions
424
Details for slab steps and depressions should include separate details for different step dimensions. This should
425
include directions for draping the main reinforcing, hooking and lapping or furnishing a bent bar. Special attention
426
should be given to bar anchorage, development lengths, and providing continuous and correctly anchored
18
427
reinforcement across any section change. Dimensions to steps and depressions should be clearly shown on the
428
structural drawings and be located from column lines or from edge of concrete.
429
Figures
430
5.7.7 Stud Rails, etc.
431
Stud rails should conform to ACI 421.1. They are an effective way of increasing punching shear capacity and
432
minimizing congestion around the slab-column connections. The LDP should furnish specific details, dimensions
433
and information on the number of rails required at each column with the diameter of studs, number of studs per rail,
434
overall height, distance to the first stud and between studs and the clear cover from top and bottom of slab.
435
NOTE: We will discuss whether or not to include Stud Rails in this document at the meeting in Philadelphia.
436
19
1
2
CHAPTER 6—PLACING DRAWINGS
The information found in this chapter is intended to provide a general overview of the
3
definition, purpose, review process and use of reinforcing steel placing drawings. For more
4
specific information and guidelines, refer to the Detailing section of the “CRSI Manual of
5
Standard Practice”. Additionally, for a better understanding of the fundamentals and best
6
practices in the preparation of reinforced concrete placing drawings, refer to the “CRSI
7
Reinforcing Bar Detailing Handbook”.
8
9
6.1—Definition
10
Placing drawings are working documents that show the quantity, bar size, dimensions and
11
location of reinforcing steel as required for fabrication and placement. Placing drawings may
12
comprise plans, details, elevations, schedules, material lists, and bending details. They can be
13
prepared manually or by computer.
14
15
16
6.2—Overview
Placing drawings are the fabricator’s interpretation of the LDP’s design intent as covered in
17
the contract documents. The purpose is to assure proper fabrication and placement of reinforcing
18
steel. The contract documents plus changes issued by the LDP (per terms agreed upon in the
19
contract if issued after the contract is made), constitute the sole authority for information in
20
placing drawings. Because no new design intent is added during the creation of placing
21
drawings, they do not require and engineer’s seal. The LDP must furnish a clear statement of the
22
design requirements in the project specifications and structural drawings and may not refer to an
23
applicable building code or other codes for information necessary to prepare the placing
24
drawings. Such information must be provided by the LDP in the form of specific design details
25
or notes.
26
Necessary additional information such as field conditions, field measurements, location of
27
construction joints, and sequence of placing concrete must be supplied by the contractor.
28
Commonly this information is only becomes available just prior to construction, making it
29
impractical to complete placing drawings within submittal date deadlines required of shop
30
drawings for reinforcement fabrication. It is more important that placing drawings be prepared
31
based on construction ready data and that all parties work together in order to complete
1
32
submittal, review and approval processes in a timely manner as to not impact construction
33
schedules. After approval by the LDP, including necessary revisions, the drawings may be used
34
for fabrication and placing of reinforcing steel.
35
36
37
6.3—Procedure
Placing drawings are most commonly prepared by a detailer, typically employed or
38
contracted by the reinforcing steel fabricator. General steps for producing and utilizing placing
39
drawings are as follows:
40
1) Detailer prepares placing drawings based on information found in the project
41
specifications and structural drawings as well as information related to construction
42
requirements obtained from the contractor.
43
2) Placing drawings are submitted to the contractor or their designee for review and
44
approval. On many projects the contractor will also forward the placing drawings to the
45
LDP for their review and approval. Refer to sections 6.4 and 6.5 for detailed
46
explanations of placing drawing review and approval processes.
47
3) Once placing drawings have been approved, bar fabrication releases are prepared from
48
the bar lists on the placing drawings, based upon a delivery sequence agreed upon
49
between the fabricator and the contractor.
50
4) Releases are submitted for fabrication in accordance with the current delivery schedule.
51
5) Reinforcing steel is cut, bent, tagged, bundled and delivered to the job site along with
52
53
54
other material, such as bar supports, as specified in the contract.
6) Reinforcing steel is installed based on details found on the placing drawings and in
accordance with requirements of the contract documents.
55
56
57
6.4—Reviewing placing drawings
In some areas of North America, review of placing drawings by the contractor and LDP is
58
not required and is rarely done. LDP’s in these areas take the view that since their inspection of
59
installed reinforcing steel is made using their contract design drawings, placing drawings serve
60
no purpose in the inspection process and therefore require no review. Errors are picked up and
61
corrected at inspection time. The downside to this approach is that correcting errors in the field
62
can cause delays and increase costs.
2
63
For this reason, most areas of North America encourage review of placing drawings by the
64
contractor and LDP.
65
66
6.4.1 Benefits of review
Review is deemed to have a number of worthwhile benefits such as:
67
a) Tends to include the LDP as part of the team effort
68
b) Verifies conformance with general design intent
69
c) Verifies that the most recent revised contract drawings have been used
70
d) Catches and corrects small errors or omissions that would otherwise delay the project if
71
72
73
74
75
76
77
left to be discovered during inspection in the field
e) Provides an opportunity for the LDP to make small changes or corrections to the design
“on the fly”
f) Provides assurance that the detailer understands the design concepts and is proceeding
correctly
g) Allows reviewed placing drawings to form a large part of the “As Built” documents
package
78
Most project specifications allow a given period of time for the LDP review of placing
79
drawings, in most cases two weeks. The detailer and construction team factor this review time
80
into their schedules. It is therefore important for the LDP to work within this constraint to help
81
keep the project on schedule.
82
83
6.4.2 Review process
84
Ideally the process for submission and review of placing drawings should be outlined in the
85
contract documents. The process varies from project to project but generally will include the
86
following steps:
87
1) Detailer submits the placing drawings to the contractor or their designee
88
2) Contractor or their designee reviews the drawings and forwards them to the LDP
89
3) LDP completes their review and returns the drawings to the contractor in a timely manner
90
4) Reviewed drawings are returned to the detailer
91
5) Detailer makes all necessary amendments and either resubmits if required, or authorizes
92
the detailed reinforcing steel for fabrication
3
93
94
6.4.3 Checklists for review of placing drawings
Each LDP will have their own check list but generally will include at least the following items:
95
a) Verify latest issue of contract drawings
96
b) Verify latest issue of addenda and supplementary documents such as requests for
information (RFI’s), design change notices (DCN’s), and field change notices (FCN’s)
97
98
c) Verify grades, coatings, and sizes of reinforcing steel
99
d) Verify that all reinforcing steel has been included and properly located
100
101
102
6.5—Levels of Approval
There are many variations of approval levels. Each LDP usually develops one that suits their
103
requirements. Although the terms may vary, most will include as a minimum the following
104
levels:
105
106
a) Approved – these drawings meet all design requirements and are approved for fabrication
and installation.
107
b) Approved as Noted – these drawings require small corrections that do not impact the
108
design intent. Once corrections are completed they are approved for fabrication and
109
installation. Resubmittal is not required.
110
c) Revise and Resubmit – these drawings have significant errors that impact the design
111
intent. The LDP must review them again before he can approve them. Resubmittal is
112
required.
113
d) Not Approved – These drawings do not meet the design intent. Alternately, perhaps, the
114
LDP is aware that new or revised design documents are about to be issued that will
115
supersede previous contract drawings. In either case completely new detailing is required
116
and submitted.
117
It must be noted that by approving reinforcing steel placing drawings for fabrication and
118
installation, the LDP does not incur any responsibility for delays and costs associated with errors
119
or omissions on those drawings. These delays and costs remain the responsibility of the
120
contractor, fabricator, and the placer.
4
Download