ECE 476 – Power System Analysis Fall 2017 Homework 2 In-class quiz: Thursday, September 14, 2017 Problem 1. A three-phase line, which has an impedance of (2 + j4) Ω per phase, feeds two balanced three-phase loads that are connected in parallel. One of the loads is Y-connected with an impedance of (30 + j40) Ω per phase, and the other is ∆-connected with an impedance of (60 – √ j45) Ω per phase. The line is energized at the sending end from a 60-Hz, three-phase, balanced voltage source of 120 3 V (rms, line-to-line). Determine: First, convert the ∆-connected load to its Y -connected equivalent: 60 − j45 = 20 − j15 Ω 3 1. The current, real power, and reactive power delivered by the sending-end source. Z̄2 = The per-phase total impedances of the line and loads is −1 1 1 + = 24∠0◦ Ω. Z̄ = Z̄line + Z̄1 ||Z̄2 = 2 + j4 + (30 + j40) (20 − j15) Then, the source current is 120∠0◦ V̄ = = 5∠0◦ A. I¯s = 24◦ Z̄ The complex power delivered by the source is S̄s = 3V̄ I¯∗ = 3(120∠0◦ )(5∠0◦ ) = 1800∠0◦ VA, with Ps = 1800 W and Qs = 0 MVar. 2. The line-to-line voltage at the load. The phase voltage at the load is V̄L = V̄s − Z̄line I¯s∗ = 120∠0◦ − (2 + j4)(5∠0◦ ) = 110 − j20 V = 111.80∠ − 10.3◦ V. Therefore the line-to-line voltage at the load is √ √ V̄L,L−L = 3V̄L ∠30◦ = 3111.80∠ − 10.3◦ + 30◦ = 193.65∠19.7◦ V 3. The current per phase in each load. The per-phase current through the Y -connected load is V̄L 111.80∠ − 10.3◦ I¯1 = = = 2.236∠ − 63.4◦ A. 30 + j40 Z̄1 The per-phase current through the Y -connected equivalent of the ∆-connected load is V̄L 111.80∠ − 10.3◦ I¯2,φ = = = 4.472∠26.57◦ A. 20 − j15 Z̄2 So the per-phase current of the ∆-connected load is I¯2,φ 4.472 I¯2,∆ = √ ∠30◦ = √ ∠26.57◦ + 30◦ = 2.582∠56.57◦ A. 3 3 1 4. The total three-phase real and reactive powers absorbed by each load and by the line. The 3φ complex power absorbed by the Y -connected load is S̄1 = 3V̄L I¯1∗ = 3(111.80∠ − 10.3◦ )(2.236∠ − 63.4◦ )∗ = 450.3 + j599.7 VA. The 3φ complex power absorbed by the ∆-connected load is ∗ S̄2 = 3V̄L,L−L I¯2,∆ = 3(193.65∠19.7◦ )(2.582∠56.57◦ )∗ = 1200 − j900 VA. The complex power absorbed by the line impedance is S̄line = 3Z̄line I 2 = 3(2 + j4)52 = 150 + j300 VA. The sum of the three quantities above is 1800 + j0 VA, which matches the value obtained in Part 1. Check that the total three-phase complex power delivered by the source equals the total three-phase power absorbed by the line and loads. Problem 2. Two three-phase generators supply a three-phase load through separate three-phase lines. The load absorbs 30 kW at 0.8 power factor lagging. The line impedance is (1.4 + j1.6) Ω per phase between generator G1 and the load, and (0.8 + j1) Ω per phase between generator G2 and the load. If generator G1 supplies 15 kW at 0.8 power factor lagging, with a terminal voltage of 460 V line-to-line, determine: 1. The voltage at the load terminals. The complex power supplied by G1 is S̄1,3φ = 15 ∠ cos−1 0.8 = 18.75∠36.87◦ kVA. 0.8 The current supplied by G1 is S̄1,3φ I¯G1 = 3V̄G1 ∗ = ◦ ∗ 18.75∠36.87 = 23.53∠ − 36.87◦ A. 460 ◦ 3 √3 ∠0 So the phase voltage at the load is 460 ∠0◦ − (1.4 + j1.6)(23.53∠ − 36.87◦ ) = 216.9∠ − 2.74◦ V, V̄L = V̄G1 − Z̄l1 I¯G1 = √ 3 and the line-to-line voltage at the load is V̄L,L−L = √ 3(216.9)∠27.26◦ V, 2. The voltage at the terminals of generator G2. The complex power absorbed by the load is S̄L,3φ = 30 ∠ cos−1 0.8 = 37.5∠36.87◦ kVA. 0.8 The current into the load is ∗ ∗ 37.5∠36.87◦ S̄L,3φ ¯ = IL = = 57.63∠ − 39.61◦ A. 3(216.9∠ − 2.74◦ ) 3V̄L The current into the load is the sum of the currents supplied by the two generators, so I¯G2 = I¯L − I¯G1 = 57.63∠ − 39.61◦ − 23.53∠ − 36.87◦ = 34.15∠ − 41.5◦ A. And finally the voltage at the terminal of G2 is the sum of the voltage drop across the load and Z̄l2 : V̄G2 = V̄L + Z̄l2 I¯G2 = 216.9∠ − 2.74◦ + (0.8 + j1)(34.15∠ − 41.5◦ ) = 259.8∠ − 0.638◦ V. And the line-to-line voltage at the terminal of G2 is √ V̄G2 ,L−L = 3(259.8)∠29.36◦ V. 3. The real and reactive power supplied by generator G2. The complex power supplied by G2 is ∗ = 3(259.8∠ − 0.638◦ )(34.15∠41.5◦ ) = 20.1 + j17.4 kVA. S̄G2 ,3φ = 3V̄G2 I¯G 2 Hence, the real power supplied is PG2 ,3φ = 20.1 kW and the reactive power supplied is QG2 ,3φ = 17.4 kVar. Problem 3. An unbalanced three-phase, Y -connected power system is shown in the figure below. The three phases have voltages V a = 100∠0◦ V, V b = 100∠ − 120◦ V, V c = 100∠120◦ V. The impedances of loads A, B, C are Z a = 10 Ω, Z b = −j10 Ω, Z c = j10 Ω. 1. What are the currents of each phase I a , I b , I c ? Ia = Va Za = 100∠0◦ 10 = 10∠0◦ A, I b = Vb Zb = 100∠0◦ −j10 = 10∠ − 30◦ A, I c = Vc Zc = 100∠0◦ j10 = 10∠30◦ A 2. What is the current on the neutral line I n ? √ I n = I a + I b + I c = 10∠0◦ + 10∠ − 30◦ + 10∠30◦ = (10 + 10 3)∠0◦ = 27.3∠0◦ A 3. What are the line voltages V ab , V bc , V ca ? √ √ √ V ab = 100 3∠30◦ = 173∠30◦ V, V bc = 100 3∠ − 90◦ = 173∠ − 90◦ V, V ca = 100 3∠150◦ = 173∠150◦ V 4. Provide the phasor diagram of the phasors including the phase voltages, line voltages, phase currents and the current on the neutral line. Figure 1: phasor diagram