1 Grid-Forming Inverters: A Critical Asset for the Power Grid Robert Lasseter, Life Fellow, IEEE, Zhe Chen and Dinesh. Pattabiraman, Student Members IEEE Abstract— Increasing inverter-based sources the system’s inertia is reduced and frequency stability becomes a concern. Understanding low-inertia systems and their stability properties is of crucial importance. This work introduces fundamental ways to integrate high levels of RE and DER in the power system while creating a more flexible power system. Using RE and DER in the distribution system has many advantages such as; reducing the physical and electrical distance between generation and loads, bringing sources closer to loads contributes to enhancement of the voltage profile, reduction to distribution and transmission bottlenecks, improved reliability, lower losses and enhances the potential use of waste heat. A basic issue for high penetration of DER is the technical complexity of controlling hundreds of thousands to millions of inverters. This is addressed through autonomous techniques using local measurements eliminating the need for fast control systems. The key issues addressed in this paper includes using inverter damping to stabilize frequency in systems with low or no inertia, autonomous operation, methods for relieving inverter overload, energy reserves and their implementation in PV systems. This work provides important insight to the interactions between inverter bases sources and the high-power system. The distinction between GFM inverter and GFL inverter is profound. GFM inverters provides damping to frequency swings in a mixed system while GFL inverter can aggravate frequency problems with increased penetration. Rather than acting as source of inertia, the GFM inverter acts as a source of damping to the system. On the other hand, application of inverters in the power system have two major issues. One is the complexity of controlling hundreds of thousands to millions of inverters. This is addressed through autonomous techniques using local measurements. The other is the potential of high overcurrent in GFM inverters and techniques for explicitly protecting against overloading. To exploit the innate damping of GFM inverters energy reserves are critical. Index Terms— Grid-following, Grid-forming, Inverter damping, Low-inertia power systems, Reserves, Renewables I. I NTRODUCTION Massive penetration of variable renewable energy (RE) in addition to other distributed energy resources (DER), poses major operational challenges to utility system operators. Power system operation traditionally assumes synchronous generators provide frequency stability via their stored kinetic energy. With increasing inverter-based sources the system’s inertia is reduced and frequency stability becomes a concern. For example, operators in Ireland [1], Texas [2] and South Australia This paper was submitted for review 21 September 2019. This work is supported in part by the U.S. Dept. of Energy Office of Energy Efficiency and Renewable Energy and the Office of Electricity through contracts administered by the Lawrence Berkeley National Laboratory. Additional support through Wisconsin Electric Machines and Power Electronics Consortium (WEMPEC). The authors are with the Electrical and Computer Engineering Department, University of Wisconsin, Madison, WI 53706 USA. Robert Lasseter (email: rlasseter@gmail.com). Zhe Chen (e-mail: zchen275@wisc.edu). Dinesh Pattabiraman (e-mail: dinesh.pattabiraman@wisc.edu) [3] are already facing obstacles regarding high penetration of inverter-based sources during certain periods of the day. Understanding low-inertia systems and their stability properties is of crucial importance. We need to find fundamental ways to integrate high levels of RE and DER in the power system while creating a more flexible power system. Traditionally, inverter-based-sources such as photovoltaics (PV) and Wind have been deemed to possess zero inertia; they are typically operated at their rated power output and are not expected to respond dynamically to frequency changes [4]. With increasing inverter penetration levels due to growth in installations of variable renewable energy sources, the total stored mechanical energy is reduced. This can result in larger frequency swings as a larger fraction of kinetic energy storage is decommissioned. Larger deviations can cause reliability issues such as frequency-based tripping of loads and legacy equipment in the system. Smaller islanded power systems such as Australia, Hawaii, face imminent low inertia related issues. This does not need to be the case. Inverters can be controlled to increase frequency damping with increased penetration. Fundamentally grid-forming inverter frequency control could be very advantageous particularly for islanded power systems with frequency issues. Compared to large synchronous machines, inverter-based resources are able to change their output much faster arresting system’s frequency changes before any load shedding is triggered. DER and RE bring a level of variability and nuance never before seen by network operators. This tangible convergence of DER interconnections to networks ill-suited to integrate variable demand side behaviors represents ground zero for the disruption of the global energy landscape caused by DER. We need to rethink our distribution system including the integration of high levels of DER, to provide a smarter and more flexible distribution system. Our overarching objective is to transform the installation of a very large number of inverter based sources from a major potential liability to a critical asset for both the power grid and utility customers. Using RE and DER in the distribution system reduces the physical and electrical distance between generation and loads. The benefits include enhanced voltage profiles, reduced distribution and transmission bottlenecks, improved reliability, enhanced potential use of waste heat and lower losses. The basic issue for high penetration of DER is the technical complexity of controlling hundreds of thousands to millions of inverters. This complexity is greatly reduced using autonomous techniques to eliminate the need for fast control systems. The key issues addressed in this paper includes inverter damping to stabilize frequency in systems with low or no inertia, autonomous techniques for relieving inverter Digital Object Identifier: 10.1109/JESTPE.2020.2959271 2168-6785 c 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications standards/publications/rights/index.html for more information. 2 Fig. 2. Fig. 1. Block Diagram of a typical Grid Forming Inverter Block Diagram of a typical Grid Following Inverter overload, use of energy reserves and implementation of PV systems. II. GFL AND GFM I NVERTERS There are two basic control technologies for utility-based inverters. They are grid-following (GFL) and grid-forming (GFM). Grid-following inverters control the output of real and reactive power by injecting a current at a given phase angle. A phase locked loop (PLL) is used to track the grid phase angle in real time. The grid-following inverter cannot directly provide regulate system voltage and frequency. Voltage and frequency reference is provided externally either by a gridforming inverter or the power system. Fundamentally if the GFL inverter loses a voltage/frequency source it must shut down. Grid-forming inverters are intrinsically different from gridfollowing inverters. A grid-forming inverter is a controllable voltage source behind a coupling reactance much like grid tied synchronous generators. Voltage source inverters with droop characteristic allows for direct control of voltage and frequency. During contingencies the droop-controlled gridforming sources will increase or decrease their output power instantaneously to balance loads and maintain local voltage and frequency. There is no significant delay between the change of output power and the change of output frequency in droop-controlled grid-forming inverters. Therefore, GFM sources respond much faster to any contingencies than the response of the GFL sources. Providing primary frequency control from inverter-based resources could be very advantageous particularly for “low-inertia” power systems. Compared to large synchronous machines, inverter-based resources are able to change their output much faster thus arresting system’s frequency changes before any load shedding is triggered. An excellent example is the O’ahu, power system in Hawaii [5]. Peak load summer case with a total load of about 1080 MW was used in this example. The system has 16 synchronous generators with a total output of 660 MW and transmissionconnected renewable sources of 80 MW. The rest of the generation fleet is comprised of distributed PV with a total of 360 MW. The initiating contingency is the loss of a 200 MW synchronous generator unit in the system. The response Fig. 3. System frequency regulation with grid-following and grid-forming inverters with PV grid-following inverters incorporating FrequencyWatt function is indicated in the red “FW” trace in Fig. 3. The response of grid-forming inverters with droop control is indicated in the blue “CERTS” trace. The frequency damping provided by the GFM inverters is stunning. Magnitude of the imbalance between generation and load, implies a sufficient level of untapped capacity or headroom for frequency control. This can take the form of storage, spinning reserves, and/or variable renewable energy sources that are operated sufficiently below maximum available power level. Inverter-interfaced batteries can also be deployed. A drawback is that unused capacity may impose additional operating costs. III. G ENERATORS /I NVERTER DYNAMICS . 1) Generator Model: As demonstrated in the earlier work [6] using small signal analysis, the inertia dependent slow electromechanical mode is responsible for the swing type response observed in power systems. A simple mathematical formulation is presented to satisfactorily capture this behavior in a system with all generators. This approach is later expanded to accommodate mixed source behavior in the following sections. The slow frequency dynamic response is predominantly affected by the mechanical inertia and turbine-governor dynamics of generators. In this time scale, the inter-generator oscillatory modes can be ignored as they are typically faster. A 3 TABLE I T HEORETICAL S TUDY PARAMETERS Fig. 4. Aggregate generator model for slow frequency dynamics studies simple aggregate model can capture the frequency dynamics by assuming that the transient frequency change is same at all buses [7], which is justifiable at quasi-steady state in this relatively slower timescale. This power system inertial aggregate model can be developed by summing up generator rotor speed differential equations. The aggregated inertia constant and damping values are then written as Mg,a = Dg,i (Note- M 2H /ωs ). The Mg,i and Dg,a = aggregate mechanical power PM,a = PM,i is written as a function of frequency change PM,a (ω). The governorturbine system can be reduced to an aggregate equivalent structure. This approach is proposed in the model reduction package “DYNRED” to aggregate turbine-governor transfer functions of coherent machines by summing up individual mechanical power output responses by perturbing a speed input [8]. Such an approach is also used in [9] to aggregate governor turbine dynamics. An equivalent linearized and per-unitized aggregate transfer function is used here for studying the frequency dynamics. In this work, a simple aggregated first order transfer function with one pole and zero and a 5% governor speed droop (M p,gen ) is used for the turbine-governor response of the aggregated system. This results in a convenient second order transfer function model, enabling derivation of simple closed form expressions. The transfer function model for the aggregate generator is shown in fig. 4. Assuming negligible mechanical damping (Dg,a = 0), the characteristic equation can then be derived from the system transfer function as, 1 1 TB 2 s+ (1) + s + TA Mg,a T A M p,gen Mg,a T A M p,gen The roots of the second order characteristic equation give the dominant electromechanical mode that affects the frequency dynamics. The oscillation frequency and damping values can be calculated as, 1 ωn = Mg,a T A M p,gen Mg,a M p,gen 1 TB ζ = + √ 2 Mg,a T A M p,gen TA (2) For a nominal choice of parameters given in Table I at 1pu power output, one can calculate ωn ≈ 0.6r ad/s and ζ ≈ 0.37, which indicate a slow and poorly damped response. It is clear from the expressions a lower value of inertia would yield a Fig. 5. GFM inverter model and its inertia equivalent structure higher oscillation frequency and smaller damping factor value (hence, a faster and poorly damped response). 2) GFM Inverter Model: Only the frequency/power dynamics of the GFM inverter are modeled, with a first-order power measurement filter as in Fig. 5 [10]. Voltage control and other dynamics are relatively fast and can be ignored. Limit controls are ignored in the theoretical model. GFM inverter equations can be simply rewritten to obtain structural resemblance to a generator unit, with inertia and damping coefficients [11], where Mi TM /M p,inv Di 1/M p,inv (3) Typical values of these virtual terms at unit power output (=1pu) are significantly different from their generator counter parts (Mi = 0.16 ωs Di = 20/ωs pu), with significantly lower inertia and higher damping. 3) GFL Inverter Model: The GFL inverter model is simplified for the relevant timescales. Voltage related dynamics are not modeled for the theoretical study. Delays due to frequency measurement (phase-locked-loop), current control loop etc. are not included as they are relatively fast and do not to play a role in this timescale. PLL is not as fast as the other faster control blocks such as current control, they are still slower than the power controller modeled in this work. In general, such PLL models are often ignored in bulk-system transient stability simulation tools for this reason. However, they are generally used for studying voltage stability issues which can occur under weak grid conditions. The terminal 4 Fig. 6. GFL inverter model for theoretical study voltage angle is used as the feedback input to determine the frequency and determine a power command using the frequency-watt function (droop). Consequently, a simple firstorder response to approximate the power control response (Fig. 5). TL = 0.5s is used as the time constant for the power response in this work. TL is sometimes set based on requirements by applicable standards or can be limited by inverter power response bandwidth. The GFL case is structurally different from a generator or a GFM inverter; the inputs and outputs are switched in the GFL case. Hence, the inertia equivalent structure cannot be formulated for the GFL case. However, the same definition for damping as in the GFM case is adopted (Di 1/M p,inv ). 4) Mixed Generator/Inverter Model: In the mixed source case, generators and inverters are each aggregated into respective equivalent units and modeled as a two-source structure. Each aggregated unit is connected through a line impedance to the aggregate load modeled as an impedance. The linearized mixed source system model for the GFM case is constructed as shown in Error! Reference source not found.7 using the aggregate generator and inverter models. The model is derived as function of inverter penetration level(x); the generator power rating reduces to (1-x) pu and the inverter rating to ‘x’ pu to meet a constant 1pu system load. This scales the generator inertia and damping values by (1-x) and the inverter inertia and damping terms by a factor of x. The Kx coefficient terms are obtained from the small signal power-angle relationship based on external connections between the generator and inverter. Pg Pi = K1 K3 K2 K4 δg δi (4) A similar approach can be used to develop the mixed source system model for the GFL case. As mentioned earlier, the inputs and outputs are reversed with inverter power being the output and the terminal inverter angle being a feedback input [11]. 5) Reduced Order Mixed Source System Models: The aggregate model for the GFM case in Fig. 7, can be simplified due to the fast time constants involved in the inverter dynamics. Time constant Tm = Mi Di ≈ 8ms is insignificant compared to the generator inertia and other time constants in Table I and can be ignored. The K matrix values is a rank 1 matrix and is related by K 1 K 4 = K 2 K 3 . Further, in the two-source case it turns out that K 1 ≈ K 4 and K 2 ≈ K 3 for a wide range of interconnecting impedance values. These simplifications lead to the reconstructed block diagram in Fig. 6, where the inverter is represented by a linear function x Di and a first order response with time constant T . The value can be derived as T = x Di K 4 , which can be considered a delay in feedback path due to network connections. The value of K4 is dependent Fig. 7. Mixed Source System with GFM Inverter Fig. 8. Reduced order model of the mixed source (GFM or GFL) on the load and network admittances and is in the range of 0.5 to 1.5 at varying penetration levels. In general, this network delay value |x Di /K 4 | < 0.05s is insignificant at all penetration levels and can be ignored (T = 0). The model for the mixed source case with GFL inverter can be developed using a similar procedure. Surprisingly, simple algebraic manipulations lead to the same model structure in Fig. 6, albeit the value of time constant T . The time constant for the first order inverter response can be derived as, T = TL + x Di ≈ TL K4 (5) In this case, the time constant is affected by the added delay due to the inverter power response which can be much larger than the network delay. Again, this network delay value |x Di /K 4 | is considered insignificant at all penetration levels and can be ignored. Hence, both GFM and GFL cases lead to a similar structure except for the values of the T. In the mixed source GFM case, T → 0 and the first order delay is effectively neglected. Hence, the GFM inverter can be represented by a simple linear damping feedback for the generator frequency and is an indicator for virtual damping provided by GFM inverters. The damping and oscillation frequency of electromechanical modes are shown in Fig.9, which indicates overdamped response (ζ >1) beyond 25% penetration. See Appendix for 5 the closed form expressions. For the GFL case, time response is dominated by TL and cannot be ignored as it is comparable to generator time constants. This results in attenuating the damping feedback on the generator frequency that can be provided by the inverter. Qualitatively, the attenuation of damping power feedback due to GFL inverter is clear, when evaluated at the value of oscillation frequency (ωn ) of the electromechanical mode. De f f ( j ωn ) ≈ x Di 1 2 TL ωn2 + 1 (6) For a finite value TL, the damping term on generator frequency is reduced along with the generator inertia. 6) System Dynamics: Variation of oscillation frequency and damping of electromechanical mode with variation in inverter penetration level is shown Fig. 9. As the penetration level of GFL inverters increases, increase in damping is initially observed up to ∼20%, beyond which the damping declines. Theoretically, the oscillation frequency, (ωn ), is small at lower penetration levels, and damping feedback from (6) is effective. With increasing penetration levels, ωn increases significantly in the GFL case, and attenuates the damping feedback. From this study, it is quite clear that such delays result in reduced damping from inverters and contribute negatively to the system frequency response. The GFL inverter plot of damping vs penetration level in Fig.9(b), is sensitive to system inertia (H ) and the power response time constant (TL ). For larger inertia values, the peak point at which the decline in damping begins shifts right, occurring at higher penetration levels and a higher value of damping. For values of TL (slower power response), the peak damping value decreases, but the penetration level at which the decline begins remains roughly the same. Comparisons of GFM and GFL models derived earlier are simulated to verify the frequency dynamics. The aggregated two-source system case is simulated, for a 5% load decrease event and the generator frequency plots are shown in Fig.10. Simulations are repeated at inverter penetration levels of 20%, 50% and 80% for GFM and GFL cases. Time domain responses with the aggregate GFM model (Fig. 7), visibly overlaps with that of the simplified reduced model from Fig. 8, (with T = 0). Minor differences in the fast transient are observed at 80% GFM penetration, which is relatively insignificant and is inconsequential for the frequency dynamic response. It is clear that the aggregate GFM inverter provides damping feedback on the generator frequency to the system. Rather than acting as source of inertia, the GFM inverter acts as a source of damping to the system. This helps clarify concerns regarding low system inertia or emulating virtual inertia through inverters. Improvement in frequency dynamic performance can be directly achieved by using inverters for damping the inertial response, rather than adding inertia to the system. Artificially introducing delays in the form of inertia is unnecessary and may not be as helpful. Fig. 9. Variation of oscillation frequency and damping function of Inverter penetration level IV. GFM I NVERTER : C OMPLEXITY AND OVERLOAD C ONTROL 7) Generalized Overload Control: Application of inverters in the power system has two major issues. One is the complexity of controlling hundreds of thousands to millions of inverters. The other is the potential of high over current since GFM inverters have no direct control of current. The complexity issue requires designs that allow each GFM inverter to operate as an autonomous energy source. This concept is not new to the bulk-power system. Most large generators track fast load changes autonomously using frequency droop, not signals from a centralized controller. Relative to microgrids these autonomous concepts have been demonstrated in the CERTS microgrid at the American Electrical Power’s test site [12]. Autonomous GFM sources can also use frequency to explicitly protect themselves from self-overloading [13]. A load increase or fault can cause a GFM source to exceed its power rating (Pmax ). A sustained overload can stall prime movers, collapse PV dc bus voltage or cause the inverter to shut down on overcurrent. In systems with massive penetration of GFM inverters we must expect that some sources will reach their power limits before other sources. Step loads result in all GFM sources instantaneously increase their output to compensate for the extra load. However, the sources which have reached their power limits must restrict their overload. 6 Fig. 10. Simulation of aggregated system response to 5% load decrease This is achieved by the overloaded inverter rapidly decreasing its output frequency changing the loading between sources due to the change in system phase angles. If there are no adequate reserves, relief comes from frequency load tripping. The basic overload function is to force the overloaded source’s frequency down faster than the droop for power levels greater than its Pmax . An overload mitigation controller is shown in Fig 11. The top half are the droop controls, where Mp and Mq are the slopes of P vs. f droop, and Q vs. V droop, respectively. The dotted box in Fig 9 contains the overload mitigation controller. Pmax is the maximum power of the source, the error between Pmax and P is the input of the PI controller, where Kppmax and Kipmax are the proportional and integral gains, respectively. Fig. 11. Overload mitigation controller Fig. 12. state. Demonstration of the overload issue of microsources in transient The output of the PI controller will regulate the frequency. When the droop-controlled source becomes overloaded, the PI controller will reduce the frequency rapidly to mitigate its overload. The basic overload function is demonstrated in a two-source microgrid, Fig. 12. The two sources initially operate at 60 Hz with unit-1 near its maximum power P1max , and unit-2 well below its rating. Loss of the grid at 0.2 seconds results in overloading of unit-1. To prevent this overload, unit-1 rapidly decreases the frequency command in order to transfer the extra power to the unit-2. After the transient, the system’s new frequency is fb . Unit-1 is at its maximum value while unit-2 has increased its output power to accommodate the load increase. The frequency of unit -1 drops faster than unit2, resulting in a needed power-angle change for the loading transfer, Fig 12(b). Overload power is transferred to unit 2 in less than 0.2 seconds. An alternative to frequency-based overload control is for the overloaded GFM sources to switch to GFL mode. This will force unit-2 to provide the extra power. The problem with this approach occurs when all sources are overloaded resulting in no voltage or frequency control forcing the system to shut down. In contrast GFM’s frequency-based overload control will continue to force frequency down until frequency-based shedding of non-critical loads provides relief. At this point the microgrid can recover with reduced loads while maintaining stable voltage and frequency [14]. Inverter fault protection 7 is ultimately a manufacture’s design issue, but there are techniques that can be used to reduce the likelihood of inverter tripping on overcurrent. They include wye delta transformers, local protection design and the droop controllers. Overcurrent due to power is mitigated by the overload controller discussed in this section. Over current due to reactive power is reduced by the reactive power droop vs. voltage by reducing the output voltage with increase reactive power [22]. 8) PV Overload Control: Using GFM inverter with a PV panel implies that the Pmax in Fig. 11 is also the Maximum Power Point, [15]. Setting the maximum power limit at the MPP protects the PV source from trying to delivering more power than is available. When demand exceeds the MPP the frequency decreases rapidly. This frequency drop causes a rapid change in the PV source’s phase angle that causes other sources that have not reached their limits to automatically assume load tracking responsibilities. The maximum power limit is designed to respond to dynamic changes in the PV power capacity caused by varying insolation and temperature. The interaction between synchronous generators and PV operating at the MPP can be illustrated using the mixed two-source power system introduced in Table I. For 50% penetration the expected response to a 5% load increase would be for both sources to equally share the increased load. When the PV inverter is operating at its MPP this sharing is not possible and all the load increase must be provided by the synchronous generators. Details shown in Fig. 13 are the power outputs from each source, the load voltage and the PV inverter’s dc voltage. The power plots show not only how the transient overload of the PV source has been transferred to the generator, but also the frequency swings caused by the transient PV overloading. With application of the 5% load increase, both sources increase their output power instantaneously to meet this positive load step, resulting in transient overloading of PV source. The Pmax controller shifts the excess load of PV source to the generator. The PV dc bus voltage recovers to its initial value to restore delivery of its maximum power. In the new steady-state operating points, the generator compensates for the load change by increasing its output power by 5%. Since the PV source operates at the MPP, the steady-state frequency of the system is determined by the generator’s droop characteristic, which changes from 60 Hz to 59.7 Hz in this case. However, it is found that the system including the PV source needs more than 20 seconds to reach steady state. The dynamic damping seen in Fig. 10 is not possible for PV operating at MPP since there is no reserves. V. R ESERVES FOR L OW I NERTIA S YSTEMS 9) Damping Reserves: It is clear from Figs 9, and 10 that aggregated GFM inverters can provide damping feedback to the system. Rather than acting as a source of inertia, the GFM inverter acts as a source of damping to the system. Tradition power system relies on spinning reserve to compensate for power shortages or frequency drops within a given period of time. Traditionally, spinning reserve is a concept for systems with large synchronous generators. If the largest generator in Fig. 13. Simulated dynamic responses of the mixed-source system operating at the MPP for a positive 5% load step. the power system is tripped, the remaining generators need to increase their output to recover the power shortage. However, leveraging traditional generation assets for creating reserved capacity creates a number of inefficiencies. For example, because these generators are operated below their rated values, the utility is not maximizing their power output that could be used for base load supply. Also, it requires the use of additional fuel to ramp these generators up in the event that their reserved generation potential is needed, which increases emissions while reducing the net efficiency of the power system [16]. In principle, GFM distributed energy resources can be implemented with “spinning reserve” assets. In autonomous operation the reserve allocation between DERs and synchronous generators is dependent on the penetration ratio and the percent droop. Let us return to the mixed two-source power system. In a system with 50% penetration and 5% droop the autonomous response to a 5% step load is for each source to increase its output by 2.5% or one half of the applied load. In a more complex bulk power system this distribution is also dependent on load and source locations and the impedance distribution. In this mixed two-source system the synchronous generator and grid-forming inverter both need to have reserves greater than 2.5%. Communication would allow different allocations, but the complexity could be enormous. The bulk system could easily have hundreds of thousands to millions of inverters throughout a large geographic area making centralized, secondary and tertiary control impractical without appropriate aggregate-control schemes and system partitioning. An alternative is to operates each source autonomously. In this case each autonomous PV source must have the necessary reserve capacity to ensure that it does not exceed its maximum available power. Generally, for a mixedsource system with n source, each inverter or generator may have a unique penetration level, x j , with a droop of M p, j so that the power change in each source Pi after the load 8 change is determined as follows: Pi = PL xi n m=1 xm n j =1, j =i M p, j n j =1, j =m M p, j where n is the source number, the subscripts m, i , and j represent the source m, i , and j , respectively. The power change constraint is: ω = P1 M p,1 M p,n = . . . = Pn x1 xn where x m is the instantaneous source penetration, nm=1 x m = 1. For our mixed two-source power system the distribution of the load change between the generator and inverter are a function pentation and droop. For equal droops and 50% penetration the load allocation is equal. For a 1% inverter droop and 5% generator droop the allocation of the load is 5/6 for the inverter and 1/6 for the generator radically changing the required reserves. For the first example the reserves requirements are equal. For the second example the inverter reserve need is 5 time that of the generator. For the example shown in fig.13 the generator’s reserves requirement is the full load increase. 10) Grid-forming PV Sources with Reserves: The frequency dynamics seen in Fig. 13. can be improved by introducing power reserve margins to the PV source, [17]. This reserve is achieved by dispatching the PV power below its MaximumPower-Point. Using the same initial conditions and load step used in the above simulation Fig. 14(a) presents the time response of the system having adequate power reserve capabilities for the PV source. In this case droop and penetration are equal. These two sources evenly share the 5% load increase. Compared to Fig. 13, the dynamic performance is obviously improved. The frequency reduction is less than half and the system achieves steady-state in half the time. Clearly better system dynamic performance is achieved using PV power reserves. In fig.14(b) the penetration levels remain equal but the inverter droop is changed from 5% to 1%. The allocation of the load seen in fig. 14(b) is far from equal. The inverter provides 5/6 of the need power for the load increase while the generator provides 1/6. The change in frequency is defined by the 1% droop achieving steady state is less than a second. This event needs to be followed with local re-dispatch of the generator to return the PV to a state with necessary reserves. VI. I MPLEMENTATION OF PV P OWER R ESERVE C ONTROL The concept of PV power reserve is to operate the PV at a power level lower than the available maximum power from the PV array. The reserve power value is P = Pmpp − Ppv,o (7) where P is the amount of reserved power and Ppv,o is the value of output power from the PV source. It is implemented by adjusting the power setpoint of the PV source to insure needed reserved power. It also needs to point out that due to the non-monotonic characteristics of the PV array’s P-V Fig. 14. reserves Fig. 15. Simulated dynamic responses of the mixed-source system with Single-diode electrical equivalent circuit of the PV panel curve, there are two possible operating points associated with the desired PV power Ppv,o . The operating point with voltage less than MPP can introduce over-modulation issues and instability for grid-forming PV sources. The control system must insure operation over the entire range of available needed reserved power at a voltage higher than the MPP. In order to implement the power reserve concept on grid-forming PV sources, tracking the time-variant maximum available power is a key requirement. A model-based MPP estimation is proposed that avoids the need for irradiance and temperature sensors [18] and requires much less complexity than control-based methods [19] and curve-fitting algorithms [20]. The equivalent circuit of the PV panel in Fig. 15 is described 9 by the well-known nonlinear current-voltage equation [21] as V panel +Rs I panel V panel + Rs I panel N BVT −1 − I panel = I ph − Is e (8) Rsh where Is = K panel AT 3 e −E g VT (9) is the diode’s saturation current [A], I ph is the photocurrent source [A], N represents the number of series-connected cells, B is the diode ideality factor, and Rs and Rsh are the series and shunt resistances [], respectively. In (8), K panel is the thermal coefficient [A/(m2 ·deg-K3)], A is the surface area of a single cell [m2 ], E g is the energy gap for silicon [eV], and VT = kT /q is the temperature equivalent voltage [V], where k is the Boltzmann constant [eV/deg-K], q is the electron charge [coulomb], and T is the temperature [deg-K]. This equation can also be expressed as voltage in terms of current using the Lambert-W function. Without additional hardware requirements, model-based MPP estimates can be derived by manipulating this current-voltage equation. Using PV voltage and current measurements, the PV panel equivalent circuit can be used to play the role of light irradiation and temperature sensors. First, with voltage and current measurements at the PV panel terminals, operation region on the PV I-V curve can be decided. If measurements are made to the right of the MPP, the PV panel’s open-circuit voltage Voc can be estimated to be the intercept of the curve-fitted voltage-source region of the I-V curve with the voltage axis. The short-circuit current Isc can also be estimated using a similar process if measurements are made to the left of the MPP. (8) can be expressed in terms of the PV panel’s opencircuit voltage Voc as: V oc Voc N BV T I ph = Is e −1 + (10) Rsh And the short-circuit current Isc can be estimated by solving the following rearrangement of (8): RI s sc Rs N BVT Isc = I ph − Is e −1 − Isc (11) Rsh (9)-(11) and equations in [21] used for translation of parameters that are dependent on atmospheric conditions can be used to roughly estimate likely ranges of the temperature and irradiance values to reduce the search time. Furtherly, by substituting (9) into (8) and replacing V panel and I panel with a few sets of sampled voltage and current readings, the temperature and irradiance values can be estimated. This process can be accelerated using the Newton-Raphson method. Next, circuit parameters that are relevant to the temperature and irradiance, such as I ph , Is , Rsh , and VT , are updated and full P-V /I -V curve can be generated. Since the MPP current (Impp ) has a nearly proportional relationship with Isc , Impp can be approximately expressed as: Impp = K Isc Isc wher e 0.78 < K Isc < 0.92 (12) where the value of K I sc is essentially constant, and its value can be estimated from the specified PV panel’s datasheet. The Fig. 16. June 7th , 2019 MPP voltage (Vmpp ) can be approximately expressed by using the nonlinear Lambert-W function based on [21]: ⎫ ⎧ √ Rs + Rsh Rs +Rs2 ⎪ ⎪ ⎪ ⎪ I 1 + ⎨ mpp ⎬ Rsh ∼ Vmpp = N BVT W − Rs Impp ⎪ ⎪ Is ⎪ ⎪ ⎩ ⎭ (13) After Impp and Vmpp are estimated using (12) and (13), respectively, the MPP power (Pmpp ) can be calculated from their product [23]. The performance of the MPP estimation has been evaluated for a PV array consisting of series- and parallel-connected SunPower X21-345 PV panels that are installed on the rooftop of the Wisconsin Energy Institute at UW-Madison. Circuit parameter characterization that accounts for deviations from datasheets due to a variety of reasons such as aging, degradation, cable resistances, and so on is determined using curve scan operation. Fig 16 plots the estimation performance for this PV array operating in MPPT mode during two different days, which is compared with measured MPPs. These figures demonstrate that the MPPs can be estimated with acceptable errors by using this proposed method in hardware PV source equipment in the presence of real-world disturbances such as measurement noises. VII. C ONCLUSION This work provides important insight to the interactions between inverter bases sources and the bulk-power system. The distinction between GFM inverter and GFL inverter is profound. GFM inverters provides damping to frequency swings in a mixed system while GFL inverter can aggravate frequency problems with increased penetration. Rather than acting as source of inertia, the GFM inverter acts as a source of damping to the system. On the other hand, application of inverters in the power system have two major issues. One is the 10 TB . Hence, the damping factor (ζ ) improves significantly with increasing inverter penetration. As we have seen GFM inverters can damp frequency swings for changes in load or generation. R EFERENCES Fig. 16. June17th, 2019 complexity of controlling hundreds of thousands to millions of inverters. This was addressed through autonomous techniques using local measurements. The other is the potential of high over-current in GFM inverters and techniques for explicitly protecting against overloading. To exploit the innate damping of GFM inverters energy reserves was shown to be critical. In autonomous operation the reserve allocation between GFM sources and synchronous generators is shown to be approximately equal to the penetration ratio with equal droops. If was seen that unequal droops can have profound effects on the needed reserves and can greatly reduce frequency swings. The last section derives and test a reserve allocation algorithm for PV sources. The test demonstrates that the MPPs can be estimated with acceptable errors by using this proposed method. A PPENDIX Closed form expressions for the mixed source GFM case can be easily obtained due to the second order nature of the system model. The characteristic equation for the mixed source GFM case can be derived from the transfer function as, Di 1 TB x 2 + + s + TA Mg,a T A Rg 1 − x Mg,a x 1 1 Di + + (1) Mg,a T A Rg 1−x Closed form expressions are obtained for oscillation frequency and damping, as a function of inverter penetration level (x). 1 Mg,a T A Rg (1 − x) √ TB x TA ζ ≈ 1−x + (2) √ TB 1 − x 2 Mg,a T A Rg √ With √ increasing values of x from 0 to 1, 1 − x decreases and 1/ 1 − x increases and leads to an increase in ωn , indicating √ a faster response. The increase in x/ √1 − x term more than compensates for the decrease due to 1 − x term as T A ≫ ωn = [1] EirGrid and SONI, “DS3: System services review TSO recommendations,” EirGrid, Tech. Rep., May 2013. [2] J. Matevosyan and P. Du, “Wind integration in ERCOT,” in Integration of Large-Scale Renewable Energy into Bulk Power Systems. Springer, 2017, pp. 1–25 [3] Australian Energy Market Operator, “Black System South Australia 28 September 2016 - Final Report,” Tech. Rep., March 2017. [4] T. Ackermann, T. Prevost, V. Vittal, A. J. Roscoe, J. Matevosyan, and N. Miller, “Paving the Way: A Future Without Inertia Is Closer Than You Think,” IEEE Power Energy Mag., vol. 15, no. 6, pp. 61–69, Nov. 2017. [5] M. E. Elkhatib, W. Du, and R. H. Lasseter, “Evaluation of Inverterbased Grid Frequency Support using Frequency Watt and Grid-Forming PV Inverter,” presented at the IEEE Power and Energy Society General Meeting, Portland, OR, 2018. [6] D. Pattabiraman, R. H. Lasseter, and T. M. Jahns, “Comparison of Grid Following and Grid Forming Control for a High Inverter Penetration Power System,” in 2018 IEEE Power Energy Society General Meeting (PESGM), 2018, pp. 1–5. [7] P. W. Sauer, M. A. Pai, and J. H. Chow, Chapter 10 - Power System Dynamics and Stability: With Synchrophasor Measurement and Power System Toolbox. John Wiley & Sons, 2017. [8] “Power System Coherency and Model Reduction | Joe H. Chow | Springer.” [Online]. Available: https://www.springer.com/us/book/9781461418023. [Accessed: 03Jun-2019]. [9] D. Pattabiraman, J. Tan, V. Gevorgian, A. Hoke, C. Antonio, and D. Arakawa, “Impact of Frequency-Watt Control on the Dynamics of a High DER Penetration Power System,” in 2018 IEEE Power Energy Society General Meeting (PESGM), 2018, pp. 1–5. [10] P. J. Hart, R. H. Lasseter, and T. M. Jahns, “Reduced-order harmonic modeling and analysis of droop-controlled distributed generation networks,” in 2016 IEEE 7th International Symposium on Power Electronics for Distributed Generation Systems (PEDG), 2016, pp. 1–9. [11] S. D’Arco and J. A. Suul, “Equivalence of Virtual Synchronous Machines and Frequency-Droops for Converter-Based MicroGrids,” IEEE Trans. Smart Grid, vol. 5, no. 1, pp. 394–395, Jan. 2014. 14] [12] R. Lasseter, J. Eto, B. Schenkman, J.Stevens, H. Volkmmer, D. Klapp, E. Linton, H. Hurtado, J. Roy, “CERTS Microgrid Laboratory Test Bed,” IEEE Transactions on Power Delivery vol. 26, no. 1, pp. 325-332, Jan. 2011. [13] W. Du and R. H. Lasseter, "Overload mitigation control of droopcontrolled grid-forming sources in a microgrid," 2017 IEEE Power & Energy Society General Meeting, Chicago, IL, 2017, pp. 1-5. [14] W. Du, R. H. Lasseter and A. S. Khalsa, "Survivability of Autonomous Microgrid During Overload Events," in IEEE Transactions on Smart Grid, vol. 10, no. 4, pp. 3515-3524, July 2019. [15] W. Du, Q. Jiang, M. J. Erickson and R. H. Lasseter, "Voltage-Source Control of PV Inverter in a CERTS Microgrid," in IEEE Transactions on Power Delivery, vol. 29, no. 4, pp. 1726-1734, Aug. 2014. [16] Allen J Wood and Bruce F Wollenberg, “Power Generation, Operation and Control,” 2nd edition, Wiley Interscience, 1996. [17] B. Crăciun, T. Kerekes, D. Séra and R. Teodorescu, "Frequency Support Functions in Large PV Power Plants With Active Power Reserves," in IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 2, no. 4, pp. 849-858, Dec. 2014. [18] Gevorgian, Vahan. 2019. Highly Accurate Method for Real-Time Active Power Reserve Estimation for Utility-Scale PV Power Plants. Golden, CO: National Renewable Energy Laboratory. NREL/TP-5D00-73207. [19] E. Batzelis, G. Kampitsis, and S. Papathanassiou, "Power Reserves Control for PV Systems With Real-Time MPP Estimation via Curve Fitting," in IEEE Trans. on Sustain. Energy, vol. 8, no. 3, pp. 12691280, July 2017. [20] S. Kolesnik et al., "Solar Irradiation Independent Expression for Photovoltaic Generator Maximum Power Line," in IEEE Journal of Photovoltaics, vol. 7, no. 5, pp. 1416-1420, Sept. 2017. [21] W. De Soto, S. A. Klein, andW. A. Beckman, “Improvement and validation of a model for photovoltaic array performance,” Sol. Energy vol. 80, no. 1, pp. 78–88, Jan. 2006. 11 [22] J. Eto, R. Lasseter, B. Schenkman, J. Stevens, H. Volkommer, D. Klapp, E. Linton, H. Hurtado, J. Roy and N. Lewis, “ CERTS Microgrid Laboratory Test Bed: Appendix J,” California Energy Commission PIER Final Report, CEC-500-2009-004 February 2009 [23] R. Lasseter, and T. Jahns, “Active Power Reserve for Grid Forming PV Sources in Microgrids using Model-based Maximum Power Point Estimation,” (ECCE), Baltimore, MD, 2019, pp. 1-8. Robert H. Lasseter (F’s 92) received the Ph.D. in Physics from the University of Pennsylvania, Philadelphia in 1971. He was a Consulting Engineer at General Electric until he joined the Department of Electrical and Computer Engineer at University of Wisconsin-Madison in 1980. Dr. Lasseter is internationally recognized as one of the earliest and most influential pioneers in the microgrid field. His professional career during the past 40 years has been dedicated to applying power electronics to utility systems. He is the technical lead for the Consortium for Electrical Reliability Technology Solutions’ (CERTS) Microgrid Project. CERTS’s microgrid architecture is widely implemented and recognized for its plug-and-play flexibility. Zhe Chen (S’14) received the B.S. degree in Electrical Engineering and Automation from the Nanjing University of Aeronautics and Astronautics, Nanjing, China, in 2012, and the M.S. degree in Electrical Engineering from the University of Wisconsin-Madison, WI, USA, in 2016, where she is currently working toward the Ph.D. degree in Electrical Engineering. Her research interests include modeling, analysis, and control of renewable energy sources, microgrids, power electronics, and electric machines. Dinesh Pattabiraman received his B.Tech. degree in electrical engineering from the National Institute of Technology, Tiruchirappalli, India and his M.S degree from the University of Wisconsin, Madison, USA. Currently, he is pursuing his Ph.D. in Electrical Engineering at the University of Wisconsin, Madison. His research interests include utility applications of power electronics, inverter control, power system dynamic response, microgrid control etc.