Heat Load Calculation The highest potential heat load of any room or space that needs to be conditioned is calculated in order to maintain a desired interior air temperature, assuming external weather conditions. This will allow you to calculate the building's heat load by looking at the heat generation source and heat balance. The sum of the sensible and latent heat loads can be used to calculate the building's overall heat load. All heat load calculations will be done using the indoor design temperature of 25°C and the outdoor average temperature of 37°C. The exterior wall of the building is cream with a K correction for wall color of 0.5. HEAT LOAD COMPONENTS PER FLOOR Transmission Heat Load a. External Wall Table 7 External Heat Wall for First Floor Orientation S A πΌπ 19.8684 3.4482 TOTAL πͺπ³π»π«πππ LM K πΈπ 19 -3.33 0.5 940.325874 940.325874 Table 7 shows the values for each parameters needed to calculate the external wall heat load of first floor for south portion of the building. The heat transfer coefficient, Uw, can be obtained by getting the reciprocal of the thermal resistance, R. Since the external wall is made of concrete block, sand, and gravel aggregate, it has a thermal resistance of 0.29 m2 -K/W which results to a heat transfer coefficient of 3.4482 W/ m2 -K. The table also displays the computed sensible heat load for the external wall of first floor. Table 8 External Heat Wall for Second Floor Orientation S A πΌπ πͺπ³π»π«πππ 65.665096 3.4482 19 LM K -3.33 0.5 TOTAL πΈπ 3107.769925 3107.769925 Table 8 presents the results of the calculation for external wall heat load of second floor which is the sensible heat load, for different orientation of the building. Table 9 External Heat Wall for Third Floor Orientation A πΌπ πͺπ³π»π«πππ LM K πΈπ S 15.556 3.4482 19 -3.33 0.5 736.2256 TOTAL 736.2256 Table 9 displays the values of each parameter needed to calculate for the heat load of the external wall of third floor. Table 10 Summary of External Wall Heat Load Floor Sensible Heat Load (πΈπ ) First 940.325874 Second 3107.769925 Third 736.2256 TOTAL: 4784.32137 Table 10 shows the total external wall heat load for each floor of the building. The preceding tables display the values per orientation of the building that are needed to solve for the external wall heat load. Thus, the total external wall heat load of the building is 4784.3217 W. b. Roof Load Table 11 Heat Load of Roof Room πΌπΉ A Chem Lab 1-3 3.44827 210.93 πͺπ³π»π«πππ LM K f πΈπ 30 -0.55 1 1 27239.017 Chem Fac 3.44827 34.61 30 -0.55 1 1 4469.4562 Chem Stock 3.44827 22.48 30 -0.55 1 1 2903.0157 TOTAL: 34611.489 Table 11 presents the necessary values to solve for the roof load of the building. The sensible heat load of the roof is 34,611.489 W as presented in the table. c. Glass Load Table 12 Glass Load for First Floor Orient. SHGF S 115 SC Ag 0.55 1.4375 CLF 0.81 π―ππ π―ππ 8273.89 76.331 U βπ» πΈπ 5.9 9 1349.81 Table 12 shows the necessary values for solar heat gain and thermal heat gain to compute the total glass load of the first floor, as well as the results of the calculation. By getting the summation of the calculated sensible heat load of solar heat gain and thermal heat gain, the total glass load of the first floor is 75,151.99 W. Table 13 Glass Load for Second Floor Orient. SHGF S 115 SC Ag 0.55 1.4375 CLF 0.81 π―ππ π―ππ 8273.89 76.331 U βπ» πΈπ 5.9 9 1349.82 Table 13 presents the calculated solar heat gain and thermal heat gain of the glass for second floor. The total glass load of second floor as displayed in the table is 75,151.99 W which is the same with first floor glass load. Table 14 Glass Load for Third Floor Orient. SHGF S 115 SC Ag 0.55 1.4375 CLF 0.81 π―ππ π―ππ 8273.89 76.331 U βπ» πΈπ 5.9 9 1349.82 Table 14 displays the total glass load of the third floor which is the summation of the calculated sensible heat load. This glass load is the same as on the second floor which is 75,150.6 W. Table 15 Summary of Glass Load Floor Sensible Heat Load (πΈπ ) First 1349.81 Second 1349.82 Third 1349.82 TOTAL: 4,049.86 Table 15 shows the total glass load of each floor. It was calculated by getting the summation of solar heat gain and thermal heat gain of glass. The total glass load of the whole building is 225,454.58 W. d. Partition Load Table 16 Partition Load Per Floor Floor First Second Third Partitions U (W/ππ . π²) Area π»π π»π πΈπ Door 0.00603 20.79 25 37 1.12977 Wall 3.44827 189.0603 25 37 2663.39 Door 0.00603 15.12 25 37 0.82165578 Wall 3.44827 127.1493 25 37 3946.0138 Door 0.00603 17.01 25 37 0.924363 Wall 3.44827 179.990284 25 37 5585.905 TOTAL: 12,198.18459 W Table 16 presents the different partitions with the necessary parameters and values to evaluate the partition load of each floor. These include the area of each partition, the heat transfer coefficient, and the temperature of the inside and outside space. The partition load of each component per floor was also presented in table. The total partition load of the whole building is 12,198.18459 W. Infiltration Load Table 17 Infiltration Load per Floor No. of air changes/ hr 0.46925 ππ ππ ππ (πππ / πππ π ) Amphitheater Wind Velocity (m/s) 6.75 25 37 Offices/Dressing 6.75 0.46925 25 Nutrition Lab 6.75 0.46925 Skills Lab 6.75 0.46925 Rooms Q (Li/s) Sensible Heat Latent Heat 0.009883 ππ (πππ / πππ π ) 0.02633 21.2466 313.5997 855.5810 37 0.009883 0.02633 6.9631 205.552 279.1246 25 37 0.009883 0.02633 13.9041 205.2250 559.906917 25 37 0.009883 0.02633 42.8339 632.0670 1724.8849 FIRST FLOOR: 1355.4437 3419.497417 Anatomy, Biology and Physics Lab Faculty Office 6.75 0.46925 25 37 0.009883 0.02633 21.2622 941.491 2568.6324 6.75 0.46925 25 37 0.009883 0.02633 10.4668 154.4911 421.4917 Biology and Physic Storage Room 6.75 0.46925 25 37 0.009883 0.02633 10.3965 153.4522 418.6573 1249.4343 3408.7814 941.4918 2568.6327 SECOND FLOOR: Chem Lab 1-3 6.75 0.46925 25 37 0.009883 0.02633 21.2622 Chem Faculty 6.75 0.46925 25 37 0.009883 0.02633 10.4669 154.4911 421.4917 Chem Stock Room 6.75 0.46925 25 37 0.009883 0.02633 6.7976 100.3326 273.7334 THIRD FLOOR: 1196.3155 3263.8578 TOTAL INFILTRATION LOAD: 3801.1935 10092.1366 The values for the various parameters needed to calculate the infiltration heat load for each level are shown in Table 17. The sum of the sensible heat load and latent heat load determines the total infiltration heat load for each floor. The ventilation heat load and infiltration load calculations will aid in choosing the type of air distribution system to be utilized when designing the air conditioning system. Ventilation Heat Load Table 18 Ventilation Heat Load per Floor Rooms Occupancy Category Amphitheater Educational Facilities Offices/Dressing Office Buildings Nutrition Lab Educational Facilities Skills Lab Educational Facilities Anatomy, Biology and Physics Lab Faculty Office Biology and Physic Storage Room Chem Lab 1-3 Chem Faculty Educational Facilities Office Buildings Occupiable Storage Room Educational Facilities Office Buildings No. of occupant ππ ππ ππ (πππ / πππ π ) Q (Li/s) Sensible Heat Latent Heat 0.009883 ππ (πππ / πππ π ) 0.02633 60 25 37 196.078 2894.1112 7895.8815 4 25 37 0.009883 0.02633 19.406 572.865 1562.9237 38 25 37 0.009883 0.02633 166.382 2455.7983 6700.0508 38 25 37 0.009883 0.02633 252.458 3726.2800 10,166.2525 26325.1085 7581.8229 FIRST FLOOR: 38 25 37 0.009883 0.02633 188.279 6249.0545 2778.9980 4 25 37 0.009883 0.02633 22.883 337.7530 921.4774 2 25 37 0.009883 0.02633 10.3965 452.6892 1235.0528 9738.3531 22745.4687 921.47746 SECOND FLOOR: 38 25 37 4 25 37 0.009883 0.02633 188.279 3569.4402 8336.994 0.009883 0.02633 22.883 337.7530 Chem Stock Room Occupiable Storage Room 2 25 37 0.009883 0.02633 THIRD FLOOR: TOTAL VENTILATION LOAD: 6.744 99.5414 271.5740 8774.2884 18592.783 23938.4861 60001.947 The parameters required to assess the ventilation heat load of each floor are shown in Table 18. Additionally, it shows the calculated sensible and latent heat loads, which when added together yield the total ventilation heat load. Total sensible and latent heat loads determined by the calculation were 18592.783 W and 60001.947 W, respectively. The fact that the total latent heat load is greater than the total sensible heat load shows that the total ventilation heat load of the building is significantly impacted by the variation in air humidity ratio. Occupant Load Table 19 Ventilation Heat Load per Floor Rooms Activity Amphitheater Offices/Dressing Nutrition Lab and Skills Lab Seated, quietly Teaching Office Work Seated, quietly Teaching Anatomy, Biology and Physics Lab Faculty Office Biology and Physic Storage Room Chem Lab 1-3 Chem Faculty Chem Stock Room Seated, quietly Teaching Office Work Standing Heat %SHG %LHG No. of Gain/person Occupant 100 60 40 60 175 50 50 1 150 55 45 4 100 60 40 37 175 50 50 1 FIRST FLOOR: 100 60 40 37 175 50 50 1 150 150 SECOND FLOOR: Seated, quietly 100 Teaching 175 Office Work 150 Standing 150 55 50 60 50 55 50 THIRD FLOOR: TOTAL OCCUPANT LOAD: 45 50 40 50 45 50 4 2 37 1 4 2 CLF Latent Heat 0.68 Sensible Heat 2507.5 0.765 0.68 504.9 3138.2 413.18 2114.8 0.68 6150.6 4707.3 4219.48 3197.7 0.765 0.49 252.45 294 206.55 294 0.68 5253.75 4707.3 3698.25 3197.7 0.765 0.49 252.45 147 206.55 147 5106.75 16,511.05 3551.25 11,468.98 1691.5 The various parameters and their related values are shown in Table 19 in order to calculate the occupant heat load for each floor of the building. To calculate the proportion of latent heat gain, subtract the percentage of perceptible heat gain from 100%. According to the table, there are 16511.05 W of sensible heat load and 11468.98 W of latent heat load overall. Lighting Load Table 20 Lighting Load per Floor ππ ππ CLF Sensible Heat 54 Summation of Lamp Rating 2430 1.2 0.5556 0.90 1458 W 40 1800 1.2 0.5556 0.90 1080 40 1800 1.2 0.5556 0.90 1080 Floors Description Type Quantity First Fluorescent Light, vented Fluorescent Light, vented Fluorescent Light, vented Second Third TOTAL LIGHTING LOAD: 3618 W Table 20 presents the values needed in the evaluation of the lighting load of the building. The light time is 5 hours and the total operation hours per day is 9 hours. This result to a utilization factor of 0.556 for each type of lighting. The cooling load factor depends on the type of lighting used and the total operation hours. Equipment/Miscellaneous Load Table 21 Equipment Load per Floor ` First Second Third Summation ππ of Equipment Rating Ceiling Fans 6 420 0.556 Laptop 2 200 0.222 Oven 2 1200 0.222 Refrigerator 2 1500 0.556 Water Dispenser 1 100 1 Stand Fan 1 60 0.556 FIRST FLOOR: Ceiling Fan 6 420 0.556 Biology Refrigerator 1 100 0.556 Laptop 4 400 0.222 SECOND FLOOR: Ceiling Fans 11 770 0.556 Incubator 9 `1080 0.111 Equipment Drying Oven 6 8700 0.111 Refrigerator 3 300 0.556 Fume Hood 3 45 0.111 Fuming Cabinet 3 150 0.111 Laptop 4 400 0.222 THIRD FLOOR: TOTAL EQUIPMENT/MISCELLANEOUS LOAD: Description Type Quantity CLF Sensible Heat 0.90 0.90 0.81 0.90 0.96 0.90 210.168 39.96 215.784 750.6 96 30.024 1372.56 210.168 50.04 79.92 340.128 385.308 91.1088 0.90 0.90 0.90 0.90 0.76 0.76 0.90 0.76 0.76 0.90 733.932 150.12 3.7962 12.654 79.92 1456.839 3169.527 W The parameters needed to determine the sensible heat load of the equipment employed for each floor are shown in Table 21. The ratio of equipment time to the total number of operation hours per day was used to calculate the utilization factor, or Fu. ASHRAE Table 4-6 was used to estimate the cooling load factor, or CLF, values, which were based on the equipment's operational hours. The table displays the various load results by floor. The total miscellaneous load of the entire structure, as can be observed, is 3169.527 W. Summary of Heat Load per Floor Table 22 Summary of Heat Load for Ground Floor TRANSMISSION Wall Partition Glass VENTILATION INFILTRATION HEAT GENERATING LOADS Occupant Lighting Miscellaneous/Equipment Load TOTAL HEAT LOAD: GROUND FLOOR Sensible Heat Latent Heat 940.325 2664.51977 75151.99 6249.0545 1355.4437 W 26325.1085 3419.497417 6150.6 W 1458 W 1372.56 4219.48 101342.49297 QT= 135.5595975 Table 22 presents the summary of heat load calculation for first floor of the building. The sensible heat load and latent heat load per component was tabulated as shown. Based on the table, the total heat load of first floor is 135.559575 kW. Table 23 Summary of Heat Load for Second Floor TRANSMISSION Wall Partition Glass VENTILATION INFILTRATION SECOND FLOOR Sensible Heat Latent Heat 3107.769925 3946.840358 75151.99 3569.4402 1249.4343 9738.3531 3408.7814 HEAT GENERATING LOADS Occupant Lighting Miscellaneous/Equipment Load TOTAL HEAT LOAD: 5253.75 W 1080 W 340.128 3698.25 94.0710244 QT= 125.8813909 Table 23 presents the summary of heat load calculation for second floor of the building. The sensible heat load and latent heat load per component was tabulated as shown. Based on the table, the total heat load of first floor is 125.8813909 kW. Table 24 Summary of Heat Load for Third Floor TRANSMISSION Wall Roof Partition Glass VENTILATION INFILTRATION HEAT GENERATING LOADS Occupant Lighting Miscellaneous/Equipment Load TOTAL HEAT LOAD: THIRD FLOOR Sensible Heat Latent Heat 736.2256 34611.489 5586.829363 75150.6 8774.2884 1196.3155 23938.4861 3263.8578 5106.75 1080 W 1456.839 3551.25 115,269.5395 QT= 145.9472637 Table 24 shows the summary of heat load calculation for third floor of the building. The total heat load for third floor is 145.9472637 kW.