Lighting Guide 5: Lighting for education The Society of Light and Lighting 222 Balham High Road, London SW12 9BS, UK Tel: 020 8675 5211. Fax: 020 8673 3302. e-mail: sll@cibse.org. www.sll.org.uk The Society of Light and Lighting is part of the Chartered Institution of Building Services Engineers This document is based on the best knowledge available at the time of publication. However, no responsibility of any kind for any injury, death, loss, damage or delay however caused resulting from the use of these recommendations can be accepted by the Chartered Institution of Building Services Engineers, the Society of Light and Lighting, the authors or others involved in its publication. In adopting these recommendations for use each adopter by doing so agrees to accept full responsibility for any personal injury, death, loss, damage or delay arising out of or in connection with their use by or on behalf of such adopter irrespective of the cause or reason therefore and agrees to defend, indemnify and hold harmless the Chartered Institution of Building Services Engineers, The Society of Light and Lighting, the authors and others involved in their publication from any and all liability arising out of or in connection with such use as aforesaid and irrespective of any negligence on the part of those indemnified. The rights of publication or translation are reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means without the prior permission of the publisher. © February 2011 The Society of Light and Lighting The Society is part of CIBSE which is a registered charity, number 278104. ISBN 978-1-906846-17-6 Layout and typesetting by CIBSE Publications. Printed in England by Charlesworth Press, Wakefield, West Yorkshire WF2 9LP Cover illustrations (clockwise from upper left): Warsaw University (photograph courtesy of Thorn Lighting); Southwell Minster School, Southwell, Nottinghamshire (photograph courtesy of Thorn Lighting); Excelsior Academy, Newcastle Upon Tyne (photograph courtesy of Cundall Light4); Usworth Sixthform College, Washington, Tyne And Wear (photograph courtesy of Thorn Lighting). Note from the publisher This publication is primarily intended to give guidance. It is not intended to be exhaustive or definitive, and it will be necessary for users of the guidance given to exercise their own professional judgement when deciding whether to abide by or depart from it. Any commercial products depicted or described within this publication are included for the purposes of illustration only and their inclusion does not constitute endorsement or recommendation by the Society. Printed on recycled paper comprising at least 80% post-consumer waste Foreword In 1963 the Illuminating Engineering Society published a remarkable monograph entitled Lecture theatres and their lighting, which became a standard work of reference. An updated edition was published in 1973 and then in 1991 it was updated and published as CIBSE Lighting Guide LG5: The visual environment in lecture, teaching and conference rooms. Within a very short period of time there were a vast array of CIBSE and Department for Education and Schools (DfES) guides available covering all manner of lighting in schools, teaching spaces, lecture theatres and the like, including documents such as Building Bulletin 90: Lighting design for schools. In 1995 an addendum to LG5 was issued to deal with changes in government funding for schools projects and changes in European legislation for workplace lighting. The Department for Children, Schools and Families (previously the DfES) decided in 2008 that it would join with the SLL in updating LG5 to include schools. This Lighting Guide covers not only lecture theatres, but also all teaching spaces and rooms specific to educational premises across schools and further education, and extends to committee rooms, conference and multipurpose rooms. It represents a complete revision but includes relevant material from the original LG5 and BB90 working groups. Our thanks go to many of the original authors whose work is included here, which include R Aldworth, R Anderson, J Baker, L Bedocs, R Bell, C Bissell, K Gofton, J Lambert, D Loe, J Lynes, I MacLean, K Mansfield, J Mardaljevic, M Patel, V Rolfe, P Ruffles, A Tarrant, R Venning, L Watson and Professor A Wilkins. LG5 Task Group I D Macrae (Thorn Lighting) (Chairman) A Bissell (Cundall LLP) R Daniels (Department for Education) B Etayo (Fulcrum First LLP) S Fotios (Sheffield University) P Raynam (University College London) T Ramasoot (Sheffield University) Director of Information Jacqueline Balian Secretary to the Society of Light and Lighting Liz Peck Editor Ken Butcher Acknowledgement Permission to reproduce extracts from BS EN 15193, BS EN 12464-2, BS EN 1838 and BS EN 12464-1 (draft) is granted by BSI. British Standards can be obtained in PDF or hard copy formats from the BSI online shop: www.bsigroup.com/Shop, or by contacting BSI Customer Services for hardcopies only: tel: +44 (0)20 8996 9001, e-mail: cservices@bsigroup.com. Foreword In 1963 the Illuminating Engineering Society published a remarkable monograph entitled Lecture theatres and their lighting, which became a standard work of reference. An updated edition was published in 1973 and then in 1991 it was updated and published as CIBSE Lighting Guide LG5: The visual environment in lecture, teaching and conference rooms. Within a very short period of time there were a vast array of CIBSE and Department for Education and Schools (DfES) guides available covering all manner of lighting in schools, teaching spaces, lecture theatres and the like, including documents such as Building Bulletin 90: Lighting design for schools. In 1995 an addendum to LG5 was issued to deal with changes in government funding for schools projects and changes in European legislation for workplace lighting. The Department for Children, Schools and Families (previously the DfES) decided in 2008 that it would join with the SLL in updating LG5 to include schools. This Lighting Guide covers not only lecture theatres, but also all teaching spaces and rooms specific to educational premises across schools and further education, and extends to committee rooms, conference and multipurpose rooms. It represents a complete revision but includes relevant material from the original LG5 and BB90 working groups. Our thanks go to many of the original authors whose work is included here, which include R Aldworth, R Anderson, J Baker, L Bedocs, R Bell, C Bissell, K Gofton, J Lambert, D Loe, J Lynes, I MacLean, K Mansfield, J Mardaljevic, M Patel, V Rolfe, P Ruffles, A Tarrant, R Venning, L Watson and Professor A Wilkins. LG5 Task Group I D Macrae (Thorn Lighting) (Chairman) A Bissell (Cundall LLP) R Daniels (Department for Education) B Etayo (Fulcrum First LLP) S Fotios (Sheffield University) P Raynam (University College London) T Ramasoot (Sheffield University) Director of Information Jacqueline Balian Secretary to the Society of Light and Lighting Liz Peck Editor Ken Butcher Acknowledgement Permission to reproduce extracts from BS EN 15193, BS EN 12464-2, BS EN 1838 and BS EN 12464-1 (draft) is granted by BSI. British Standards can be obtained in PDF or hard copy formats from the BSI online shop: www.bsigroup.com/Shop, or by contacting BSI Customer Services for hardcopies only: tel: +44 (0)20 8996 9001, e-mail: cservices@bsigroup.com. 90 Lighting Guide 5: Lighting for education Table 10.2 Recommended minimum controls provision Type of space Description Recommended minimum controls Owned space A space such as a small room for one or two people who control the lighting, e.g. a cellular office or tutorial room. Shared space A multi-occupied area, e.g. classroom, common room, an open-plan office or craft area. Temporarily owned space A space where people are expected to operate the lighting controls while they are there, e.g. a lecture or meeting room. Occasionally visited space A space where people generally stay for a relatively short period of time when they visit the space, e.g. a storeroom or toilet. A space where individual users require lighting but are not expected to operate the lighting controls, e.g. a corridor or atrium. Manual switch by the door with absence* override. Separate circuit for daylight dimming, or switching, of luminaires close to the window in daylight spaces. Manual switch by the door with absence* override. Separate circuits for daylight dimming or switching of luminaires in appropriate zones according to the amount of daylit for daylight spaces. Local manual control with absence* override. Sensor(s) should be suitably mounted to pick up the movement of occupants and speaker. Manual on with absence* override. Presence detection may be acceptable provided sensors use no more than 0.5 W. Time switching, or manual on with absence* override, or presence provided individual sensors use no more than 0.5 W. Separate circuits for daylight dimming or switching of luminaires in appropriate zones according to the amount of daylight for daylit spaces. Time switching, scene setting or central switching by a responsible person. Un-owned space Managed space A space where lighting is under the control of a responsible person, e.g. a conference room, theatre or sports hall. Separate circuits for daylight dimming or switching of luminaires in appropriate zones according to the amount of daylight for daylit spaces. * Absence sensors should be circuited such that they switch themselves off and hence use zero power when the lighting is off. 11 Glossary The definitions and explanations given in this glossary are intended to help readers to understand this Lighting Guide. They are based on BS EN 12665: Light and lighting. Basic terms and criteria for specifying lighting(67), which should be consulted if more precise definitions are needed. adaptation The process by which the state of the visual system is modified by previous and present exposure to stimuli that may have various luminances, spectral distributions and angular subtenses. adjoining spaces Foyers, ante-rooms, lobbies and corridors immediately adjoining teaching spaces listed in this Lighting Guide. chromaticity The property of a colour stimulus defined by its chromaticity coordinates, or by its dominant or complementary wavelength and purity taken together. Glossary 91 colour appearance (see also colour temperature) A term used of a light source. Objectively the colour of a truly white surface illuminated by the source. Subjectively, the degree of warmth associated with the source colour. Lamps of low correlated colour temperature are usually described as having a warm colour appearance and lamps of high correlated colour temperature as having a cool appearance. colour rendering The effect of an illuminant on the colour appearance of objects by conscious or subconscious comparison with their colour appearance under a reference illuminant. CIE 1974 general colour rendering index (Ra) The mean of the CIE 1974 special colour rendering indices for a specified set of eight test colour samples. In some cases R8 or R14 references are quoted indicating use of the original 8 reference colour or a wider range of 14 reference samples. colour temperature (Tc ) The temperature of a Planckian radiator whose radiation has the same chromaticity as that of a given stimulus (unit: K). correlated colour temperature (Tcp ) The temperature of the Planckian radiator whose perceived colour most closely resembles that of a given stimulus at the same brightness and under specified viewing conditions (unit: K). committee rooms Rooms used for meetings capable of seating up to roughly 30 persons. contrast In the perceptual sense: assessment of the difference in appearance of two or more parts of a field seen simultaneously or successively (hence brightness contrast, lightness contrast, colour contrast, simultaneous contrast, successive contrast etc.) contrast rendering factor The ratio of the contrast of a task under a given lighting installation to its contrast under reference lighting conditions. cut-off The technique used for concealing lamps and surfaces of high luminance from direct view in order to reduce glare. cut-off angle (of a luminaire) The angle, measured up from nadir, between the vertical axis and the first line of sight at which the lamps and the surfaces of high luminance are not visible. cylindrical illuminance (at a point, for a direction) (Ez ) The total luminous flux falling on the curved surface of a very small cylinder located at the specified point, divided by the curved surface area of the cylinder. The axis of the cylinder is taken to be vertical unless stated otherwise (unit: lux). 92 Lighting Guide 5: Lighting for education It is defined by the formula: Ez = 1 π ∫ 4 πs r L sin ε dΩ where Ω is the solid angle of each elementary beam passing through the given point, L is the luminance at that point and ε is the angle between the elementary beam passing through the given point and the given direction (unless otherwise stated, that direction is vertical). daylight factor (D) The ratio of the illuminance at a point on a given plane due to the light received directly or indirectly from a sky of assumed or known luminance distribution, to the illuminance on a horizontal plane due to an unobstructed hemisphere of this sky, excluding the contribution of direct sunlight to both illuminances. diffused lighting Lighting by means of luminaires having a distribution of luminous intensity such that the fraction of the emitted luminous flux directly reaching the working plane, assumed to be unbounded, is 40–60%. direct lighting Lighting by means of luminaires having a distribution of luminous intensity such that the fraction of the emitted luminous flux directly reaching the working plane, assumed to be unbounded, is 90–100%. directional lighting Lighting in which the light on the working plane or on an object is incident predominantly from a particular direction. emergency lighting Lighting provided for use when the supply to the normal lighting fails. emergency escape lighting That part of emergency lighting that provides illumination for visibility for people leaving a location or attempting to terminate a potentially dangerous process before doing so. flicker The impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctuates with time. fusion frequency The frequency of alternation of stimuli above which flicker is not perceptible. general lighting Substantially uniform lighting of an area without provision for special local requirements. glare The discomfort or impairment of vision experienced when parts of the visual field (e.g. sky or lamps) are excessively bright in relation to the general surroundings. Glossary 93 glare, disability Disability glare may be expressed in a number of different ways. If threshold increment (TI) is used the following values of TI shall be used (see CIE 31(68)): 5%, 10%, 15%, 20%, 25%, 30%. If glare rating (GR) is used the following values of GR shall be used (see CIE 112(69)): 10, 20, 30, 40, 45, 50, 55, 60, 70, 80, 90. glare, discomfort Discomfort glare may be expressed by means of a ‘psychometric scale’ derived from psychophysical experiments. If it is expressed using the unified glare rating the following values of UGR shall be used (see CIE 117(70)): 10, 13, 16, 19, 22, 25, 28. illuminance (at a point of a surface) (E) The quotient of the luminous flux dφ incident on an element of the surface containing the point, by the area dA of that element (unit: lm·m–2). illuminance, average (E) The illuminance averaged (mean average) over the specified area (unit: lx). illuminance, maximum (Emax ) The highest illuminance at any relevant point on the specified surface (unit: lx). maintained illuminance (Em ) The value below which the average illuminance on the specified area should not fall (unit: lx). It is the average illuminance at the time maintenance should be carried out. illuminance, minimum (Emin ) The lowest illuminance at any relevant point on the specified surface (unit: lx). illuminance, initial (Ei ) The average illuminance on the specified surface when the installation is new (unit: lx). illuminance uniformity In this Lighting Guide this is taken as the ratio of minimum illuminance (luminance) to average illuminance (luminance) on (of) a surface. immediate surrounding area A band with a width of at least 0.5 m surrounding the task area within the field of vision. indirect lighting Lighting by means of luminaires having a distribution of luminous intensity such that the fraction of the emitted luminous flux directly reaching the working plane, assumed to be unbounded, is 0–10% intensity. installed loading The installed power of the lighting installation per unit area (for interior and exterior areas) or per unit length (for road lighting) (unit: W·m–2 for areas; kW·km–1 for road lighting). 94 Lighting Guide 5: Lighting for education keystone effect The distortion of an image caused by projection onto a surface not at right angles to the projector beam. It commonly occurs when a projector is tilted upwards to throw an image on a vertical screen, causing the top of the image to become wider than the bottom and can be easily corrected on most modern projectors. lamp lumen maintenance factor The ratio of the luminous flux of a lamp at a given time in its life to the initial luminous flux. lamp survival factor The fraction of the total number of lamps that continue to operate at a given time under defined conditions and switching frequency. large conference rooms Rooms used mainly for conferences and meetings at which people may address the audience from almost any point in the room. Such rooms will usually have a seating capacity of more than 60. lecture rooms Rooms used mainly for the delivery of formal lectures, with basically flat floors and fixed seating. This category includes rooms with a raised step or podium for the lecturer, and rooms with one or two raised steps towards the rear of the seating. lecture theatres Rooms used for the delivery of formal lectures with raked floors and/or balconies or galleries and with fixed seating. lighting energy numeric indicator (LENI) A numeric indicator of the total annual lighting energy required in the building (unit: kW·h.m–2 per annum). light output ratio (of a luminaire) The ratio of the total flux of the luminaire, measured under specified practical conditions with its own lamps and equipment, to the sum of the individual luminous fluxes of the same lamps when operated outside the luminaire with the same equipment, under specified conditions. local lighting Lighting for a specific visual task, additional to and controlled separately from the general lighting. localised lighting Lighting designed to illuminate an area with a higher illuminance at certain specified positions, for instance those at which work is carried out. luminance (L) Luminous flux per unit solid angle transmitted by an elementary beam passing through a given point and propagating in a given direction, divided by the area of a section of that beam normal to the direction of the beam and containing the given point (unit: cd·m–2). Glossary 95 luminaire lighting fitting (deprecated) Apparatus that distributes, filters or transforms the light transmitted from one or more lamps and which includes (except the lamps themselves) all the parts necessary for fixing and protecting the lamps and, where necessary, circuit auxiliaries together with the means for connecting them to the electrical supply. luminaire maintenance factor The ratio of the light output ratio of a luminaire at a given time to the initial light output ratio. mounting height The vertical distance between the luminaire and the ground or floor, or between the luminaire and a defined task plane (working plane). multi-purpose rooms Rooms used for a wide variety of purposes, such as school halls, assembly rooms, and function rooms. reflectance (ρ) The ratio of the reflected radiant or luminous flux to the incident flux in the given conditions. room index An index related to the dimensions of a room, and used when calculating the utilisation factor and other characteristics of a lighting installation: L×W K = —————– Hm (L + W) where K is the room index, L is the length of the room, W is the width of the room and Hm is the height of the luminaires above the floor or other relevant horizontal plane. Consistent units must be used for the dimensions. rooms for practical work Rooms used regularly for class teaching purposes, without large permanent pieces of apparatus set up. Such rooms will usually have a seating capacity of less than 60. This category will include many teaching laboratories. semi-direct lighting Lighting by means of luminaires having a distribution of luminous intensity such that the fraction of the emitted luminous flux directly reaching the working plane, assumed to be unbounded, is 60–90%. semi-indirect lighting Lighting by means of luminaires having a distribution of luminous intensity such that the fraction of the emitted luminous flux directly reaching the working plane, assumed to be unbounded, is 10–40%. spacing/height ratio The ratio of spacing of the geometric centres of the luminaires to their height above the reference plane. 96 Lighting Guide 5: Lighting for education stroboscopic effect The apparent change of motion of an object when illuminated by periodically varying light of appropriate frequency. This periodic motion is especially noticeable in the light from discharge lamps with clear bulbs operating on alternating current. teaching rooms Rooms used mainly for class teaching purposes, with flat floors and no fixed furniture except possibly chalkboards and projection screens. Such rooms will usually have a seating capacity of less than 60. uniformity See illuminance uniformity veiling reflections Specular reflections that appear on the object viewed and that partially or wholly obscure the details by reducing contrast. visual acuity The capacity for seeing distinctly fine details that have very small angular separation. visual comfort A subjective condition of visual well-being induced by the visual environment. visual field The area or extent of physical space visible to an eye at a given position and direction of view. visual performance The performance of the visual system as measured for instance by the speed and accuracy with which a visual task is performed. References 1 The Construction (Design and Management) Regulations 2007 Statutory Instruments No. 320 2007 (London: The Stationery Office) (2007) (available at http://www.opsi.gov.uk/si/si200703) (accessed October 2010) 2 The Building Regulations 2000 Statutory Instruments 2000 No 2531 as amended by The Building (Amendment) Regulations 2001 Statutory Instruments 2001 No. 3335 and The Building and Approved Inspectors (Amendment) Regulations 2006 Statutory Instruments 2006 No. 652) (London: The Stationery Office) (dates as indicated) (London: The Stationery Office) (2007) (available at http://www.opsi. gov.uk/stat.htm) (accessed October 2010) 3 The Building (Amendment) Regulations (Northern Ireland) 2006 Statutory Rules of Northern Ireland No. 355 2006 (London: The Stationery Office) (2006) (available at http://www.opsi.gov.uk/sr/sr200603) (accessed October 2010) 4 The Building (Scotland) Amendment Regulations 2009 Scottish Statutory Instruments No. 119 2009 (London: The Stationery Office) (2009) (available at http:// www.opsi.gov.uk/legislation/scotland/s-200901) (accessed October 2010) 5 The Education (School Premises) Regulations 1996 Statutory Instruments 1996 No. 360 (London: Her Majesty’s Stationery Office) (1996) (available at http://www.opsi.gov.uk/si/si199603.htm) (accessed October 2010) 6 Standards for School Premises (London: Department for Education and Schools) (undated) (available at http://www.teachernet.gov.uk/docbank/index.cfm?id=3928) (accessed October 2010) 96 Lighting Guide 5: Lighting for education stroboscopic effect The apparent change of motion of an object when illuminated by periodically varying light of appropriate frequency. This periodic motion is especially noticeable in the light from discharge lamps with clear bulbs operating on alternating current. teaching rooms Rooms used mainly for class teaching purposes, with flat floors and no fixed furniture except possibly chalkboards and projection screens. Such rooms will usually have a seating capacity of less than 60. uniformity See illuminance uniformity veiling reflections Specular reflections that appear on the object viewed and that partially or wholly obscure the details by reducing contrast. visual acuity The capacity for seeing distinctly fine details that have very small angular separation. visual comfort A subjective condition of visual well-being induced by the visual environment. visual field The area or extent of physical space visible to an eye at a given position and direction of view. visual performance The performance of the visual system as measured for instance by the speed and accuracy with which a visual task is performed. References 1 The Construction (Design and Management) Regulations 2007 Statutory Instruments No. 320 2007 (London: The Stationery Office) (2007) (available at http://www.opsi.gov.uk/si/si200703) (accessed October 2010) 2 The Building Regulations 2000 Statutory Instruments 2000 No 2531 as amended by The Building (Amendment) Regulations 2001 Statutory Instruments 2001 No. 3335 and The Building and Approved Inspectors (Amendment) Regulations 2006 Statutory Instruments 2006 No. 652) (London: The Stationery Office) (dates as indicated) (London: The Stationery Office) (2007) (available at http://www.opsi. gov.uk/stat.htm) (accessed October 2010) 3 The Building (Amendment) Regulations (Northern Ireland) 2006 Statutory Rules of Northern Ireland No. 355 2006 (London: The Stationery Office) (2006) (available at http://www.opsi.gov.uk/sr/sr200603) (accessed October 2010) 4 The Building (Scotland) Amendment Regulations 2009 Scottish Statutory Instruments No. 119 2009 (London: The Stationery Office) (2009) (available at http:// www.opsi.gov.uk/legislation/scotland/s-200901) (accessed October 2010) 5 The Education (School Premises) Regulations 1996 Statutory Instruments 1996 No. 360 (London: Her Majesty’s Stationery Office) (1996) (available at http://www.opsi.gov.uk/si/si199603.htm) (accessed October 2010) 6 Standards for School Premises (London: Department for Education and Schools) (undated) (available at http://www.teachernet.gov.uk/docbank/index.cfm?id=3928) (accessed October 2010) References 97 7 Registration of independent schools — information pack (London: Department for Education) (2010) (available at http://www.dcsf.gov.uk/reg-independent-schools) (accessed October 2010) 8 Code for Lighting (CD-ROM) (London: Society of Light and Lighting) (2009) 9 SLL Lighting Handbook (London: Society of Light and Lighting) (2009) 10 Boyce P R Human factors in lighting ch. 4 (Oxford: CRC) (2003) 11 Hawkes R J, Loe D L and Rowlands E A note towards the understanding of lighting quality’ J. Illum. Eng. Soc. 8 111–120 (1979) 12 Loe D L, Mansfield K P and Rowlands E ‘Appearance of a lit environment and its relevance in lighting design: Experimental study’ Light. Res. Technol. 26 119–133 (1994) 13 Loe D L, Mansfield K P and Rowlands E ‘A step in quantifying the appearance of a lit scene’ Light. Res. Technol. 32 213–222 (2000) 14 Heschong L Daylighting in Schools: An Investigation into the Relationship between Daylighting and Human Performance (Fair Oaks, CA: Heschong Mahone Group) (1999) 15 Daylighting and window design CIBSE Lighting Guide LG10 (London: Chartered Institution of Building Services Engineers) (1999) 16 Loe D L ‘Quantifying lighting energy efficiency: a discussion document’ Light. Res. Technol. 35 319–329 (2003) 17 Directive 2005/32/EC of the European Parliament and of the Council of 6 July 2005 establishing a framework for the setting of ecodesign requirements for energy-using products and amending Council Directive 92/42/EEC and Directives 96/57/EC and 2000/55/EC of the European Parliament and of the Council Official J. of the European Union L191 29–58 (22.07.2005) (available at http://eur-lex.europa.eu/LexUriServ/ LexUriServ.do?uri=CELEX:32005L0032:EN:HTML) (accessed October 2010) 18 Conservation of fuel and power in new buildings other than dwellings Building Regulations 2000 Approved Document L2A (London: The Stationery Office) (2006) (available at http://www.planningportal.gov.uk/england/professionals/en/1115314231806.html) (accessed August 2008) 19 Conservation of fuel and power in buildings other than dwellings The Building Regulations (Northern Ireland) 2000: Technical booklet F2 (London: The Stationery Office) (2006) (available at http://www.opsi.gov.uk/legislation/northernireland/ni-srni.htm) (accessed October 2010) 20 The Scottish Building Standards — Technical Handbook: Non-Domestic (Edinburgh: Scottish Building Standards Agency) (2008) (available at http://www.sbsa.gov.uk/ tech_handbooks/tbooks2008.htm) (accessed October 2010) 21 Directive 2002/91/EC of the European Parliament and of the Council of 16 December 2002 on the energy performance of buildings (‘The Energy Performance of Buildings Directive’) Official J. of the European Communities L1 65–71 (4.1.2003) (Brussels: Commission for the European Communities) (2003) (available at http:// ec.europa.eu/energy/demand/legislation/buildings_en.htm) 22 BS EN 15193: 2007: Energy performance of buildings. Energy requirements for lighting (London: British Standards Institution) (2007) 23 BREEAM: the environmental assessment method for buildings around the world (website) (Garston: BRE Global) (2009) 24 Conservation of fuel and power in buildings other than dwellings Building Regulations 2000 Approved Document L2 (London: The Stationery Office) (2002) (superseded; see reference 18) 25 The Waste Electrical and Electronic Equipment Regulations 2006 Statutory Instruments no. 3289 2006 (London: The Stationery Office) (2006) (available at http://www.opsi.gov.uk/si/si200632) (accessed October 2010) 26 Hathaway W E ‘A study into the effects of types of light on children — a case of daylight robbery’ Proc Conf. 101st Annual Convention of the American Psychological Association, Canada, August 1993 (1993) 27 Mass J, Jayson J and Kleiber D ‘Quality of light is important, not just quantity’ American School and University 46(12) 31 (1974) 28 Küller R and Lindsten C ‘Health and behaviour of children in classrooms with and without windows’ J. Environmental Psychology 12 305–317 (1992) 98 Lighting Guide 5: Lighting for education 29 Heschong L Daylighting in Schools: Reanalysis Report (Sacremento CA: California Energy Commission) (2003) (available at http://newbuildings.org/ daylighting-schools-reanalysis-report) (accessed October 2010) 30 Littlefair P Site layout planning for daylight and sunlight — a guide to good practice (Garston: BRE) (1998) 31 09/30206726 DC: BS EN 12464-1: Light and lighting. Lighting of work places. Part 1. Indoor work places (draft for public comment) (London: British Standards Institution) (2009) 32 BS EN 12193: 2007: Light and lighting. Sports lighting (London: British Standards Institution) (2008) 33 BS 8206-2: 2008: Lighting for buildings. Code of practice for daylighting (London: British Standards Institution) (2008) 34 Littlefair P Site layout planning for daylight and sunlight: a guide to good practice (Garston: BRE Press) (1991) 35 Tregenza P R ‘Modification of the split-flux formulae for mean daylight factor and internal reflected component with large external obstructions’ Lighting Res. Technol. 21(3) 125–128 (1989) 36 Winterbottom M and Wilkins A ‘Lighting and discomfort in the classroom’ J. Environ. Psychology 29(1) 63–75 (2009) 37 Passive solar schools — a design guide Department for Education Architects and Building Division Building Bulletin 79 (London: Her Majesty’s Stationery Office) (1994) 38 Visual environment for display screen use CIBSE Lighting Guide LG3 (London: Chartered Institution of Building Services Engineering) (1996) (out of print) 39 Office lighting SLL Lighting Guide LG7 (London: Society of Light and Lighting) (2005) 40 The Ecodesign for Energy-Using Products Regulations 2007 Statutory Instruments 2007 No. 2037 (London: The Stationery Office) (2007) (available at http://www.opsi. gov.uk/si/si200720) (accessed October 2010) 41 Ramasoot T and Folios S A ‘Acceptability of screen reflections: lighting strategies for improving quality of the visual environment in classrooms of the future’ Proc. conf. PLEA Dublin 2008: Towards zero energy building, University College Dublin, October 22–24 2008 (2008) 42 Lighting CIBSE Commissioning Code L (London: Chartered Institution of Building Services Engineers) (2003) 43 Daylighting and window design CIBSE Lighting Guide LG10 (London: Chartered Institution of Building Services Engineers) (1999) 44 BS EN 12464-1: 2002: Light and lighting. Lighting of work places. Indoor work places (London: British Standards Institution) (2002) 45 Guidelines for specification of LED lighting products (Society of Light and Lighting/Institution of Lighting Engineers/Lighting Industry Federation/ International Association of Lighting Designers/Professional Lighting Designers Association/Highway Electrical Suppliers & Designers Association) (2009) (available at http://www.cibse.org/index.cfm?go=page.view&item=369) (accessed October 2010) 46 BS 5266-1: 2005: Emergency lighting. Code of practice for the emergency lighting of premises (London: British Standards Institution) (2005) 47 BS EN ISO 9241-307: 2008: Ergonomics of human-system interaction. Analysis and compliance test methods for electronic visual displays (London: British Standards Institution) (2010) 48 ISO 2603: 1998: Booths for simultaneous interpretation — General characteristics and equipment (Geneva, Switzerland: International Organization for Standardization) (1998) 49 Sports lighting SLL Lighting Guide LG4 (London: Society of Light and Lighting) (2006) 50 Fotios S and Ramasoot T ‘Developing a model to predict user acceptability of display screen reflections’ Proc. Conf. Lux Europa, Istanbul, 9–11 September 2009 513–520 (2009) References 99 51 Industry SLL Lighting Guide LG1 (on Code for Lighting (CD-ROM)) (London: Society of Light and Lighting) (2009) 52 BS EN 12464-2: 2007: Lighting of work places. Outdoor work places (London: British Standards Institution) (2007) 53 BS 5489-1: 2003 + A2: 2008: Code of practice for the design of road lighting. Lighting of roads and public amenity areas (London: British Standards Institution) (2003/2008) 54 BS EN 13201-2: 2003: Road lighting. Performance requirements (London: British Standards Institution) (2003) 55 BS EN 13201-3: 2003: Road lighting. Calculation of performance (London: British Standards Institution) (2003) 56 The Regulatory Reform (Fire Safety) Order 2005 Statutory Instruments No. 1541 2005 (London: The Stationery Office) (available at http://www.opsi.gov.uk/si/ si200515)(accessed October 2010) 57 BS 5499-4: 2000: Safety signs, including fire safety signs. Code of practice for escape route signing (London: British Standards Institution) (2000) 58 BS 5499-1: 2002: Graphical symbols and signs. Safety signs, including fire safety signs. Specification for geometric shapes, colours and layout (London: British Standards Institution) (2002) 59 09/30197377 DC: BS ISO 3864-1: Graphical symbols. Safety colours and safety signs. Part 1. Design principles for safety signs and safety markings (draft for public comment) (London: British Standards Institution) (2009) 60 BS EN 1838: 1999, BS 5266-7: 1999: Lighting applications. Emergency lighting (London: British Standards Institution) (1999) 61 BS EN 50172: 2004, BS 5266-8: 2004: Emergency escape lighting systems (London: British Standards Institution) (2004) 62 BS EN 62034: 2006: Automatic test systems for battery powered emergency escape lighting (London: British Standards Institution) (2007) 63 ISO 30061: 2007 (CIE S 020/E:2007): Emergency lighting (Geneva, Switzerland: International Organization for Standardization) (1998) 64 BS 4533-102: Luminaires. Particular requirements (4 sections) (London: British Standards Institution) (1990) 65 BS EN 60598-1: 2008: Luminaires. General requirements and tests (London: British Standards Institution) (2009) 66 BS 7671: 2008: Requirements for electrical installations. IEE Wiring Regulations. Seventeenth edition (London: British Standards Institution) (2008) 67 BS EN 12665: 2002: Light and lighting. Basic terms and criteria for specifying lighting requirements (London: British Standards Institution) (2002) 68 Glare and uniformity in road lighting installations CIE 31 (Vienna, Austria: International Commission on Illumination) (2002) 69 Glare evaluation system for use within outdoor sports and area lighting CIE 112 (Vienna, Austria: International Commission on Illumination) (1994) 70 Discomfort glare in interior lighting CIE 117 (Vienna, Austria: International Commission on Illumination) (1995) Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 2 Components of lighting design . . . . . . . . . . . . . . . . .1 3 4 5 2.1 Objectives and constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 2.2 Lighting for visual function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.3 Lighting for visual amenity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.4 Lighting and architectural integration . . . . . . . . . . . . . . . . . . . . . . .4 2.5 Lighting and energy efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 2.6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 2.7 Lighting costs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 2.8 Lighting for health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Lighting options . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 3.1 Natural lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 3.2 Electric lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 3.3 Integrated daylighting and electric lighting . . . . . . . . . . . . . . . . . .17 3.4 Lightness of the interior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 3.5 Room surface reflectance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 3.6 Lighting the interior space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 3.7 Mean cylindrical illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 3.8 Modelling index and directional light . . . . . . . . . . . . . . . . . . . . . . .22 Lighting design guidance . . . . . . . . . . . . . . . . . . . . .22 4.1 Daylighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 4.2 Electric lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 4.3 Integrated daylight and electric lighting . . . . . . . . . . . . . . . . . . . .35 4.4 Aids to lighting design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 Lighting for particular applications . . . . . . . . . . . . .37 5.1 Classification of teaching and conference spaces . . . . . . . . . . . . .37 5.2 General performance requirements for learning spaces . . . . . . . . .37 5.3 Lecture theatres and lecture rooms . . . . . . . . . . . . . . . . . . . . . . . .39 5.4 Teaching rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 5.5 Large conference rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 5.6 Committee and meeting rooms . . . . . . . . . . . . . . . . . . . . . . . . . . .52 5.7 Multi-purpose rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53 5.8 Adjoining spaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 5.9 Waiting areas and lobbies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 5.10 Areas with display screen equipment . . . . . . . . . . . . . . . . . . . . . . .57 5.11 Laboratories, work shops and other practical learning spaces . . . .59 5.12 Libraries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 5.13 Sports halls and gymnasia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 5.14 General purpose halls, and drama and dance studios . . . . . . . . . .62 5.15 Lighting for whiteboards and projection screens . . . . . . . . . . . . . .63 5.16 Lighting and visual aids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 5.17 Lighting for pupils with visual and hearing impairments . . . . . . . .65 5.18 Local task lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 6 5.19 Exterior lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66 5.20 Emergency lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 Checklist for lighting design . . . . . . . . . . . . . . . . . .77 6.1 Task/activity lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77 6.2 Lighting and energy efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . .79 7 Lighting maintenance . . . . . . . . . . . . . . . . . . . . . . . .80 8 Management of lecture and conference spaces . . .81 9 10 11 8.1 Visual clutter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81 8.2 Lecture attendants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81 8.3 Communication between lecturer and projectionist or projector . .82 8.4 Projection rooms and booths . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82 8.5 Preparation and equipment rooms . . . . . . . . . . . . . . . . . . . . . . . .82 8.6 Problems for visiting lecturers . . . . . . . . . . . . . . . . . . . . . . . . . . . .82 8.7 Lectures involving demonstrations . . . . . . . . . . . . . . . . . . . . . . . . .83 Lighting costs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 9.2 Emergency lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 10.1 Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 10.2 Control gear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 10.3 Lighting controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86 10.4 Disposal of used lighting equipment . . . . . . . . . . . . . . . . . . . . . . .88 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98 Appendix A1: luminance limits and . . . . . . . . . . .100 display screen equipment Introduction 1 1 Introduction Learning, whether by discussion, interaction, practical application or formal lecture, requires sufficient light to enable the pupils to see the visible information presented around them. Whether in a primary school classroom or a professional lecture theatre, whether for young or old, the quality of light we choose to provide in the learning environment will directly affect our learning experience and indeed our motivation to learn. If we cannot see clearly what is written on the board, identify true colours, or read the facial expression and body language of our teacher, then our learning and our experience will fail to meet our needs. Above all aspects we can create in a learning space, that of the lighting affects us most. Harsh light creating aggressive facial modelling, or excessive daylight urging the teacher to draw the blinds and use electric light, impact upon us and our environment. More so now than at any other time in the history of lighting, we have to create stimulating and sustainable learning environments. The function of this Lighting Guide is to offer advice on the lighting of educational spaces (specifically those not covered elsewhere), lecture theatres, teaching rooms, conference rooms and multi-purpose rooms, and on the visual problems that may arise. It is therefore necessary to discuss other matters than simply the lighting equipment and its positioning. The decoration and finishes of such rooms, the sightlines, the positioning of lighting controls and access doors all need to be taken into account. The lighting is a vital element in such rooms and requirements of lighting should be taken into account from the first stages of the planning. This point cannot be too strongly emphasised. Light is so important to the functioning of all the premises covered by this Lighting Guide that it must be considered from the very outset of the planning process. As lighting design is such a vital part of the success and performance of both space and student the designer of such spaces must be able to demonstrate clearly their competence in lighting design for such spaces either by qualification or experience. By ‘lighting’ it is important to stress that we mean both natural and electric lighting; experience shows that whilst much thought is given to natural lighting, i.e. window design, planning for electric lighting is often left until far too late in the design process. Equally, developments driving sustainable buildings have often led to natural lighting schemes that introduce other problems such as overheating, glare and so on. That said, natural lighting should be used as far as possible as the primary light source in all teaching environments. There will be exceptions where daylight needs to be excluded but these are few and in most cases simple and functional control of daylight ingress when required will suffice. 2 Components of lighting design 2.1 Objectives and constraints Lighting design can have many different objectives. Ideally, these objectives are determined by the client and the lighting designer in collaboration and cover both outcomes and costs (Figure 2.1). The most common objective for a lighting installation is to allow the users of a space to carry out their work quickly and accurately, without discomfort. However, this is a rather limited view of what a lighting installation can achieve. For educational spaces, the objective of lighting is to facilitate the learning of students by passing on information from the teacher or lecturer and via other media. For these tasks the requirements of the lecturer will often be different from those of the pupils. In lecture theatres the task of presenting may require dimmed lighting to enable clear images on the screen, but the need to take notes may require increased lighting levels, particularly for those with impaired sight. Educational sport facilities are lit at night to encourage their use in the wider community, but in doing so they may impinge upon the residential areas surrounding the school. Most lighting installations have to serve multiple functions. When designing lighting it is always desirable at the outset of the project to identify all the functions that the lighting is expected to fulfil. Introduction 1 1 Introduction Learning, whether by discussion, interaction, practical application or formal lecture, requires sufficient light to enable the pupils to see the visible information presented around them. Whether in a primary school classroom or a professional lecture theatre, whether for young or old, the quality of light we choose to provide in the learning environment will directly affect our learning experience and indeed our motivation to learn. If we cannot see clearly what is written on the board, identify true colours, or read the facial expression and body language of our teacher, then our learning and our experience will fail to meet our needs. Above all aspects we can create in a learning space, that of the lighting affects us most. Harsh light creating aggressive facial modelling, or excessive daylight urging the teacher to draw the blinds and use electric light, impact upon us and our environment. More so now than at any other time in the history of lighting, we have to create stimulating and sustainable learning environments. The function of this Lighting Guide is to offer advice on the lighting of educational spaces (specifically those not covered elsewhere), lecture theatres, teaching rooms, conference rooms and multi-purpose rooms, and on the visual problems that may arise. It is therefore necessary to discuss other matters than simply the lighting equipment and its positioning. The decoration and finishes of such rooms, the sightlines, the positioning of lighting controls and access doors all need to be taken into account. The lighting is a vital element in such rooms and requirements of lighting should be taken into account from the first stages of the planning. This point cannot be too strongly emphasised. Light is so important to the functioning of all the premises covered by this Lighting Guide that it must be considered from the very outset of the planning process. As lighting design is such a vital part of the success and performance of both space and student the designer of such spaces must be able to demonstrate clearly their competence in lighting design for such spaces either by qualification or experience. By ‘lighting’ it is important to stress that we mean both natural and electric lighting; experience shows that whilst much thought is given to natural lighting, i.e. window design, planning for electric lighting is often left until far too late in the design process. Equally, developments driving sustainable buildings have often led to natural lighting schemes that introduce other problems such as overheating, glare and so on. That said, natural lighting should be used as far as possible as the primary light source in all teaching environments. There will be exceptions where daylight needs to be excluded but these are few and in most cases simple and functional control of daylight ingress when required will suffice. 2 Components of lighting design 2.1 Objectives and constraints Lighting design can have many different objectives. Ideally, these objectives are determined by the client and the lighting designer in collaboration and cover both outcomes and costs (Figure 2.1). The most common objective for a lighting installation is to allow the users of a space to carry out their work quickly and accurately, without discomfort. However, this is a rather limited view of what a lighting installation can achieve. For educational spaces, the objective of lighting is to facilitate the learning of students by passing on information from the teacher or lecturer and via other media. For these tasks the requirements of the lecturer will often be different from those of the pupils. In lecture theatres the task of presenting may require dimmed lighting to enable clear images on the screen, but the need to take notes may require increased lighting levels, particularly for those with impaired sight. Educational sport facilities are lit at night to encourage their use in the wider community, but in doing so they may impinge upon the residential areas surrounding the school. Most lighting installations have to serve multiple functions. When designing lighting it is always desirable at the outset of the project to identify all the functions that the lighting is expected to fulfil. 2 Fig. 2.1 Lighting Guide 5: Lighting for education Objectives, outcomes and costs Visual function Architectural integration Visual amenity Lighting design Costs (capital and operating) Energy efficiency Installation maintenance As for constraints, an important aspect of lighting design is the need to minimise the amount of electricity consumed, for both financial and environmental reasons. It is also necessary to consider the sustainability of the lighting equipment. This means using materials that can be easily replaced and considering to what extent the equipment can be recycled at the end of its life. The financial costs, particularly the capital cost, are always an important constraint. No one wants to pay more for something than is absolutely necessary so the lighting designer needs to be able to justify the proposal in terms of value for money. 2.1.1 A holistic strategy for lighting A holistic strategy for lighting design is necessary because without it important benefits will be lost, and money and human resources will be wasted. The starting point is an in-depth conversation with the client and other members of the design team to formulate a design brief. This from a ‘whole building’ design perspective needs to branch out from natural and electric lighting to include the effects on thermal loading, ventilation and acoustics. At such a discussion, it will be necessary to address such fundamental questions as: what do you want to see and what do you not want to see, what is the function of the space, what is the proposed architectural style, and what is the budget? More formally, six distinct aspects of lighting need to be considered. They are: legal requirements, visual function, visual amenity, architectural integration, energy efficiency and sustainability All these aspects will contribute to the success of a design, but they may not all carry equal weight depending on the particular application and situation. Also there is no particular order in which they should be considered. The important issue is that all the elements are considered at the inception of the project and again at each key stage of the design process, perhaps more than once, for a satisfactory solution to emerge. 2.1.2 Legal requirements There are a number of legal requirements that apply to all lighting installations. Some are general, e.g. the Construction (Design and Management) Regulations(1). Some are specific about the type and form the lighting that should be provided, e.g. emergency lighting in buildings (see chapter 9). Others influence lighting design by the limits they place on the type or amount of equipment that can be used, e.g. Building Regulations(2–4). Details of the requirements of the Construction (Design and Management) Regulations can be obtained from Health and Safety Executive publications. It is essential that the designer and the client are aware of the relevant legal requirements. The Education (School Premises) Regulations(5) specify minimum standards for the premises of all maintained schools in England and Wales. The Components of lighting design 3 publication Standards for School Premises(6), provides guidance on the School Premises Regulations. Some of the provisions of the School Premises Regulations also apply to independent schools. Guidance on legislation applying to independent schools is included in the Department for Education’s Registration of Independent Schools Information pack(7). As the UK devolves central government control to individual countries there may be other Regulations under similar titles to be considered. Schools are covered by the Building Regulations(2–4). In some cases, DfES Building Bulletins are referred to in Building Regulations Approved Documents. Except in these cases, or as otherwise stated, these publications are non-statutory. 2.2 Lighting for visual function This aspect is related to the lighting required for doing tasks without discomfort. Recommended illuminance for different tasks is given in the Code for Lighting(8) and the SLL Handbook(9), as well as in chapters 5 and 6 of this Lighting Guide. These values apply to the task area and do not necessarily need to apply to the whole working plane. Establishing which values apply to which task needs to be done with knowledge of how the space will function both now and in the future, where this information is available. Equally it is a decision that needs to be made with cognisance of all other aspects of the lighting and building design. The traditional way of lighting a work place has been a regular array of luminaires. For this approach, minimum task illuminance uniformity (minimum/average task illuminance ≥ 0.7) is recommended. This approach has the benefit that the tasks can be carried out on the horizontal plane anywhere in the work place but does tend to over-light areas not used for the primary task that happen to fall within an imaginary work plane. It should be noted that a more visually appealing and stimulating space can be created with additional energy saving benefits if the lighting is focused where it is needed. See sections 2.3 and 2.5. In some cases the task will have a colour recognition element. In such cases it will be necessary to use lamps with a high colour rendering index (CRI). For such tasks it will is appropriate to use lamps with a CRI ≥ 80 but for tasks with a requirement for very good colour discrimination, lamps with a CRI ≥ 90 will be necessary. The human visual system can adapt to a wide range of luminance but it can cope with only a limited luminance range at any single adaptation state. When this range is exceeded, glare will occur. If a field of view contains bright elements that cause glare it is likely that they will affect performance, or at least cause stress and fatigue which, in turn, will cause problems. To avoid this will mean using luminaires and windows that have limited luminance within the normal fields of view relative to the adaptation level. Glare limits for different tasks are given in the Code for Lighting(8) and the SLL Handbook(9), as well as in chapters 5 and 6 of this Lighting Guide. 2.3 Lighting for visual amenity There is no doubt that lighting can add visual amenity to a space that can give pleasure to the occupants but whether this provides a more tangible performance benefit is uncertain(10). Studies have shown that people respond to the lit appearance of a room on two independent dimensions, visual lightness and visual interest(11–13). Visual lightness describes the overall lightness of the space, which is related to the average luminance of vertical surfaces. Visual interest refers to the non-uniformity of the illumination pattern or the degree of ‘light and shade’. People prefer some modulation in the light pattern rather than an even pattern of illumination, the magnitude of the modulation depending on the application. There is some evidence that visual lightness and visual interest are inversely correlated (Figure 2.2). 4 Map showing the possible locations of three application areas on a schematic diagram linking subjective impressions of visual interest and visual lightness High Visual interest (degree of light non-uniformity) Fig. 2.2 Lighting Guide 5: Lighting for education Leisure Education and commercial Industrial Low Low High Visual lightness (brightness) Although variation in the light pattern is desirable, it has to be seen as meaningful in terms of the application and the architecture. To provide random patches of light in an uncoordinated way for no reason other than to provide light variation would be a poor design solution. Acceptable examples could be highlighting displays within a retail outlet, or a floral display in a hotel lobby. There remains one further area of visual amenity that needs to be considered and that is the colour appearance of the light. A light source with a correlated colour temperature (CCT) ≤ 3000 K will appear warm, and if it has a CCT ≥ 5300 K it will appear cold (see the SLL Handbook(9), section 1.4.3). Where on this scale from warm to cool the colour appearance should fall will depend on the nature of and finishes in the space. In domestic situations a warm colour appearance will be required but in educational interiors a CCT of around 4000 K is appropriate as it blends reasonably well with daylight. The designer should be wary of the names applied to light sources as these can be misleading and differ between manufacturers. The best way to choose colour appearance is through practical trials. There is still much to learn about design for visual amenity but it would be negligent to ignore it. The best way to develop an understanding of visual amenity is though personal observations and trial installations. 2.4 Lighting and architectural integration All elements of a lighting installation form part of the architecture or the interior design of a building. Understanding the space will be important when deciding what sort of lighting is to be employed. The dimensions, finishes, texture, colour, materials and the atmosphere to be created are among some of the attributes that should be considered. The most appropriate place to start is with the daylighting, given the positive impact that well designed sunlit and daylit learning spaces have on the ability for individuals to learn and develop(14). The windows and roof lights are a fundamental element of the fabric of the building. This means considering the amount and pattern of daylight required for the particular application, and hence the size and positions of windows and rooflights. But windows cannot be designed on the basis of the daylighting alone and other visual, thermal, acoustic and privacy issues need to be addressed. There is a clear hierarchy for successful environmental design: (1) Daylight design. (2) Prevention of summertime overheating. (3) Design of ventilation. (4) Acoustic design. Components of lighting design 5 This is an iterative process but daylight design must come first as it affects the form of the building. More information on daylighting design can be obtained from the SLL Lighting Guide LG10: Daylighting and window design(15), section 6.3 of the SLL Handbook(9) and section 3.1 of this Lighting Guide. Simple design tools for classroom design are also available, such as ClassCool and ClassVent produced by the Department for Children, Schools and Families and available from the teachernet website (www.teachernet.gov.uk/iaq). Once the daylighting has been determined then the electric lighting can be planned. To integrate electric lighting with the architecture means considering not only its operation with respect to the daylighting, but the appearance of the luminaires and controls and the way they are incorporated into the fabric of the building, as well as the lighting effect produced. Such integration may include other building services and could be incorporated into acoustic raft type lighting systems where appropriate. Just as the light pattern needs to be meaningful with respect to the building use, the lighting scheme needs to be meaningful with respect to the architecture and colour finishes. Profound effects are claimed in learning spaces from colour choice, see section 3.5. 2.5 Lighting and energy efficiency It is the responsibility of the lighting profession to use energy as efficiently as possible but at the same time to provide lit environments that enable people to operate effectively with comfort. The current estimate for the UK is that approximately 19% of the electricity generated is consumed by lighting. This amounts to around 64 TW·h/annum. In schools the lighting is responsible currently for one third of carbon emissions in primary schools, and nearly half in secondary premises, the figure rising significantly for educational establishments operating outside of normal daylight hours. Energy use involves two components: the power demand of the equipment and its hours of use. The lighting industry has worked hard to develop equipment that has reduced the demand for electricity for lighting by producing more efficient light sources and their related control circuits as well as more efficient luminaires. Then there are design options to be considered, such as the use of task/ambient lighting rather than a blanket provision of light by a regular array of ceiling mounted luminaires. The savings for the task/ambient approach have been estimated to be up to 50 percent(16). Good energy efficient lighting design is not just about equipment; it is also about the use of lighting. Far too often whilst the initial building design seeks to deliver well daylit spaces, as the design progresses other factors such as thermal design, acoustics, cost and ‘buildability’ dominate the solution and reduce the available access to sunlight and daylight. Given the positive impact sunlight and daylight have on the learning environment, and its ability to allow the electric lighting to be switched off, designing for daylight needs to be promoted more vigorously throughout the design process. There are also many examples where lighting is left on when it is not required. This may be because there is adequate lighting through daylighting or because people are not present and therefore the lighting is unnecessary. This aspect of lighting design needs a dramatic change in attitude to improve the energy efficiency of all lighting installations. This requires changes to how the lighting is controlled, both manually and automatically, as well as how lighting is provided in terms of the distribution of light, particularly with respect to the daylighting. It is also necessary to use equipment that is sustainable. This means that wherever possible the materials used should be from renewable sources, provided by ethical and environmentally sustainable methods, and that at the end of its life the redundant equipment is capable of being disposed of safely with most of the base materials being recycled. Equipment should also be ‘ecodesigned’, allowing for designs that make recycling simple and energy efficient, that minimise material waste and that minimise maintenance and lamp requirements through life. Over the next decade legislation such as the Energy- 6 Lighting Guide 5: Lighting for education using Products Directive(17) will drive lamp, gear and luminaire choice and the designer should specify in advance lighting that will meet or exceed requirements. The most efficient lighting solutions should be procured. Lamp–luminaire combinations are now available that easily exceed the minimum targets required by the Building Regulations(2–4), even considering the 2010 levels. Designers should recognise the need to use the most efficient lighting solutions that exceed current energy efficiency targets in documents such as Approved Document L(18) (for England and Wales), Part F(19) (for Northern Ireland) and Part J(20) (for Scotland) and also the Energy Performance in Buildings Directive(21). Where the usage profile of the building is not known, suitable minimum targets for luminaire efficacy are given in Table 2.1. Table 2.1 Energy compliance targets where building usage profiles are not available Energy efficiency grade Luminaire efficacy for stated type of space* (luminaire lumens per circuit watt) Teaching spaces, office, industrial, storage Other spaces Display lighting Pass 55 55 22 Good 55 55 22 Excellent 55 55 22 * Averaged for all these spaces in the building Note: ‘Good’ = a minimum of 60% of the installed lighting load must be under daylight control; ‘Excellent’ = a minimum of 60% of the installed lighting load must be under daylight and absence control Where a new educational building is being provided to replace an existing building, or buildings, it is not acceptable to use the above method except as a rough guide. Measurement of the existing building should be taken in order to provide data for the likely use of the new building and this should be used for the calculation of the lighting energy numeric indicator (LENI) as a measure of the new designs energy efficiency. The above targets are based on the Building Regulations and include targets that recognise the important energy savings available from sensible automatic control of lighting, but they do not include an overall measure of the efficiency of the luminaires in all applications, so as the preferred method the designer should utilise the Energy Performance in Buildings Directive(21) (EPBD) as a target assessment. As the targets and methodology in BS EN 15193(22) are subject to change the designer should consider the British Standard. Generally, as schools should utilise good daylighting, constant illuminance controls make sense and should be combined with automatic absence detection to most spaces. A sensible ‘pass’ grade for the LENI in educational buildings would be taken from Table 2.1 in Annex 5 of BS EN 15193 (see Table 2.2) but the designer should try and improve on these levels (see Tables 2.3 and 2.4). Whilst it is possible to achieve a LENI of near 10 kW·h/m2 per annum in classrooms, the same may not be so easy across a whole building. Similarly, it may be easy to simply achieve 55 luminaire lumens per circuit watt, either with current or emerging light sources, gear and optical design (based on proposed targets for England and Wales of 55 luminaire lumens per circuit watt from October 2010) but this ignores significant savings in use. Hence, the designer must consider the careful use of controls, utilising daylight, absence and constant illuminance measures to limit the use of lighting as well as aspiring to use the best available luminaire designs. Quality class * ** *** Parasitic Parasitic Pn energy, Pem energy, Ppc (W/m2) (kW·h/m2 (kW·h/m2 per year) per year) 1 1 1 5 5 5 15 20 25 tD (h) 1800 1800 1800 tN (h) 200 200 200 FC FO No constant Constant illuminance illuminance 1 1 1 0.9 0.9 0.9 Manual control FD Auto control 1 1 1 0.9 0.9 0.9 Manual control LENI (limiting value) Auto control 1 1 1 0.8 0.8 0.8 No constant illuminance Constant illuminance Manual control Auto control Manual control Auto control 34.9 44.9 54.9 27.0 34.4 41.8 31.9 40.9 49.9 24.8 31.4 38.1 Components of lighting design Table 2.2 ‘Pass’ targets for lighting energy numeric indicator (LENI) for educational buildings (extract from BS EN 15193(22), Annex F, Table F.1, reproduced by permission of the British Standards Institution) Table 2.3 ‘Good’ targets for lighting energy numeric indicator (LENI) for educational buildings Quality class * ** *** Parasitic Parasitic Pn energy, Pem energy, Ppc (W/m2) (kW·h/m2 (kW·h/m2 per year) per year) 1 1 1 5 5 5 10.5 14 17.5 tD (h) 1800 1800 1800 tN (h) 200 200 200 FC FO No constant Constant illuminance illuminance 1 1 1 0.9 0.9 0.9 Manual control FD Auto control 1 1 1 0.9 0.9 0.9 Manual control LENI (limiting value) Auto control 1 1 1 0.8 0.8 0.8 No constant illuminance Constant illuminance Manual control Auto control Manual control Auto control 25.9 32.9 39.9 20.4 25.5 30.7 23.8 30.1 36.4 18.8 23.5 28.1 Table 2.4 ‘Excellent’ targets for lighting energy numeric indicator (LENI) for educational buildings Quality class * ** *** Parasitic Parasitic Pn energy, Pem energy, Ppc (W/m2) (kW·h/m2 (kW·h/m2 per year) per year) 1 1 1 5 5 5 6 8 10 tD (h) 1800 1800 1800 tN (h) 200 200 200 FC FO No constant Constant illuminance illuminance 1 1 1 0.9 0.9 0.9 Manual control 1 1 1 FD Auto control 0.9 0.9 0.9 Manual control 1 1 1 LENI (limiting value) Auto control 0.8 0.8 0.8 No constant illuminance Constant illuminance Manual control Auto control Manual control Auto control 16.9 20.9 24.9 13.7 16.7 19.6 15.7 19.3 22.9 12.8 15.5 18.1 7 8 Lighting Guide 5: Lighting for education Table 2.5 Lighting design criteria class for use with Tables 2.2 to 2.4 (reproduced from BS EN 15193(22) by permission of the British Standards Institution) Criterion Lighting design criteria class * ** *** Maintained illuminance on horizontal visual tasks (Em horizontal) ✓ ✓ ✓ Appropriate control of discomfort glare (UGR) ✓ ✓ ✓ Avoidance of flicker and stroboscopic effects ✓ ✓ ✓ Appropriate control of veiling reflections and reflected glare ✓ ✓ Improved colour rendering ✓ ✓ Avoidance of harsh shadows or too diffuse light in order to provide good modelling ✓ ✓ Proper luminance distribution in the room (Evertical) ✓ ✓ Special attention of visual communication in lighting faces (modelling index, Ecylindrical) ✓ Special attention to health issues (see note) ✓ Must comply with required values from Table 5.3 in BS EN 12464-1 ✓ Must conform to verbally described requirements from BS EN 12464-1 Note: health issues may even require higher illuminances and therefore higher W/m2 ✓ To achieve such an improvement, coupled with much higher requirements for daylight contribution, the designer will need to consider automatically controlled and/or dimmable luminaires for at least 60% of the building space. The targets set by the Building Regulations are considered to be minimum standards of performance but these measures do not reflect the actual use of the space and in some way makes no sense as it allows for efficient lamps and gear in an inefficient luminaire. The designer should use practical control along with efficient luminaires to provide best efficacy. 2.6 Maintenance It must be recognised that both daylight and electric light within a building will depreciate with time. To minimise the effect of this a maintenance programme will need to be designed and implemented. The maintenance programme will also affect the lighting design and the designer will need to state the maintenance programme on which the design has been based, otherwise there could be problems when a client is comparing different design proposals. It is essential for the client to be provided with a maintenance schedule so that they know what will need to be done. Section 7 of this Lighting Guide discusses the various factors that need to be considered when developing a maintenance program. 2.7 Lighting costs Cost is always a major concern for any project and it is of course important to consider these before any work is undertaken. Both the capital cost and the running or operational costs must be considered at the outset. If the two cost elements are not considered together in terms of life cycle costing, then a solution which has a low capital cost but a high operational cost could prove significantly more costly overall than an installation with a more expensive capital cost but a low operating cost. A conflict of interests may arise if the two cost elements are paid for from different budgets or organisations. Here the Components of lighting design 9 designer needs to present a balanced view of the options to enable the client(s) to decide on the best approach. The capital costs include the cost of the design process, the equipment and the installation process, both physical and electrical. It should also include the commissioning and testing of the installation and training for the building occupier/owner. Allowance must also be made for any builders’ work that forms part of the lighting installation and any other costs that are particular to the lighting design need to be included. It is important that the capital cost is agreed at an early stage if a lot of time is not to be wasted. The capital cost should be challenged if the client’s expectations seem to be unrealistic. The operational costs include the cost of the electricity consumed, which comprises items such as standing charges, maximum demand charges and electricity unit costs. They will also include the cost of maintenance, which includes cleaning and relamping throughout the life of the installation. In some cases charges may have to be budgeted for the disposal of redundant equipment although this may be borne by the supplier. Note that all electrical equipment suppliers must be registered as part of the Waste Electrical and Electronic Equipment Directive(25) (WEEE) and the designer should provide proof of this for any electrical equipment supplied as part of their design. The designer should consider the full and true life cycle costs, so called ‘cradle-to-grave’. This includes elements of the luminaires and other building materials from the point their raw materials are sourced, to the point they are recycled into reusable materials. Figure 2.3 shows the elements a design should consider. These include: Fig. 2.3 — Materials: what material is used from the point it is dug out of the ground to the point it is used in a product? For instance, the creation of plastic from crude oil to the point they are moulded into a diffuser whether their type and use makes recycling easy in the future. — Ecology: the impact on sourcing raw materials and processing it into a product on the environment, flora and fauna, plus the impact of the product’s use on the environment. — Life cycle cost: the financial cost of the product from the point of raw material to fully recycled, including any manufacture, transport, use and recycling costs. Considerations for sustainable lighting design Ecology Materials Lifecycle cost Transport Sustainable lighting design Health and wellbeing Passive integration Recycling 10 Lighting Guide 5: Lighting for education — Health and wellbeing: the impact of the lighting on both end users and those close by who may inadvertently come into contact with the scheme, for example those using a school sports field and those residents nearby who may suffer light nuisance from the pitch lighting. — Recycling: the impact of collecting and treating any waste created by the lighting and luminaires, including the possibility that the product may not be suited for complete recycling but may only be down-cycled into other uses. — Passive integration: the impact of luminaires and the energy they use on other services such as heating, cooling and ventilation of a space. For instance adding electric lighting will reduce the heating load required during winter, but may add to the cooling load during hotter periods. — Transport: the impact the product has by transporting it in terms of raw materials and by getting it to site, for instance raw materials made in South America, manufactured into product in the Far East and then installed in the UK would have a high transport impact. Similarly, transport to another country or continent for recycling. Only by considering the true impact of the use of a product can its true cost be understood. 2.8 Lighting and health Continuing research into the effects of light on health has revealed stronger links between access to daylight and effects on both the psychological and physiological well-being of building occupants. These impacts are not yet sufficiently well understood to safely use electric light to mimic daylight, therefore the designer should be careful when applying colour and intensity change for all but entertainment. In all teaching spaces the use of natural light, regulated only by the season, weather and time of day is essential, as it the control of this light when blackout or glare reduction is required. 2.8.1 Regulation of the circadian system The role of the circadian system (which controls daily and seasonal body rhythms) is to link the functions of the body (e.g. the sleep/wake cycle, and changes in core body temperature and in hormone secretion) with the external day/night cycle. Disruption to this system from lack of light can cause problems such as depression and poor sleep quality, which could lead to more serious problems. Therefore, it is important that occupants of buildings are given access to high levels of daylight, particularly in the mornings, to reinforce circadian rhythms. 2.8.2 Mood 2.8.3 Seasonal affective disorder Mood can be modified by lighting. Daylighting is dynamic and variable and is strongly favoured by building occupants. Adequate access to daylight can have a positive impact on mood especially in situations where people are static for long periods of time. A small percentage of people suffer a seasonal mood disorder known as seasonal affective disorder (SAD) with a further number suffering a mild form known as sub-syndromal SAD (S-SAD). Symptoms include depression, lack of energy, increased need for sleep and increased appetite and weight gain, occurring in the winter when there is little daylight. Such symptoms can be reduced by exposure to daylight. The ultraviolet (UV) radiation in sunlight can be damaging to the skin. However, with people spending many daylight hours behind glass in buildings, there is the danger of insufficient exposure to UV radiation to maintain healthy levels of vitamin D. A vitamin D deficiency leads to rickets in children and softening of the bones in adults. The daylight strategy of educational facilities Lighting options 11 should include periods of outdoor learning throughout the year to counteract this. Exposure to sunlight, even through glass, can kill many types of viruses and bacteria and so can be of great value in winter when there is a high incidence of respiratory infections. Recently links have been made between the UV output of some light sources and damage to skin or sight as a result. Designers should note that the luminaires they specify must take due account of these risks in their design, either by use of safe light sources or by other measures that remove any harmful UV component or limit possible exposure to it. In most cases, for instance exposure to UV from a conventional fluorescent lamp, there is less risk than spending a similar amount of time exposed to daylight outdoors, so the user and designer should not be overly concerned. 3 Lighting options 3.1 Natural lighting Fig. 3.1 High level skylights and windows restrict direct glare in this daylit atrium at Brunel University (photograph courtesy of MID Lighting) Evidence from research clearly shows increased learning rates, concentration and comfort amongst students where there is good daylight within the learning environment. Hathaway(26) found significant improvements in health and academic achievement under full spectrum fluorescent lighting, compared to under cool white fluorescent or high pressure sodium lighting, in a study of 327 school children. Mass et al.(27) found that university students doing homework tasks indicated less fatigue and better visual acuity under a daylight simulating lamp than under a ‘cool white’ fluorescent lamp. Two further studies have investigated the effects of daylighting on children, using primary level schools as the children tend to spend all year in the same classroom. Küller and Lindsten(28) examined 83 children in four Swedish classrooms, two with and two without windows. The study measured cortisol, behaviour, body growth and sick leave over a year, and concluded that windowless classrooms should be avoided. Heschong(29) surveyed 8000 to 9000 students in each of three districts within the US, and reported that students in classrooms with the most daylight showed a 21% improvement in learning rates (e.g. the change in maths and reading test scores) compared to students in classrooms with the least daylight. Lighting options 11 should include periods of outdoor learning throughout the year to counteract this. Exposure to sunlight, even through glass, can kill many types of viruses and bacteria and so can be of great value in winter when there is a high incidence of respiratory infections. Recently links have been made between the UV output of some light sources and damage to skin or sight as a result. Designers should note that the luminaires they specify must take due account of these risks in their design, either by use of safe light sources or by other measures that remove any harmful UV component or limit possible exposure to it. In most cases, for instance exposure to UV from a conventional fluorescent lamp, there is less risk than spending a similar amount of time exposed to daylight outdoors, so the user and designer should not be overly concerned. 3 Lighting options 3.1 Natural lighting Fig. 3.1 High level skylights and windows restrict direct glare in this daylit atrium at Brunel University (photograph courtesy of MID Lighting) Evidence from research clearly shows increased learning rates, concentration and comfort amongst students where there is good daylight within the learning environment. Hathaway(26) found significant improvements in health and academic achievement under full spectrum fluorescent lighting, compared to under cool white fluorescent or high pressure sodium lighting, in a study of 327 school children. Mass et al.(27) found that university students doing homework tasks indicated less fatigue and better visual acuity under a daylight simulating lamp than under a ‘cool white’ fluorescent lamp. Two further studies have investigated the effects of daylighting on children, using primary level schools as the children tend to spend all year in the same classroom. Küller and Lindsten(28) examined 83 children in four Swedish classrooms, two with and two without windows. The study measured cortisol, behaviour, body growth and sick leave over a year, and concluded that windowless classrooms should be avoided. Heschong(29) surveyed 8000 to 9000 students in each of three districts within the US, and reported that students in classrooms with the most daylight showed a 21% improvement in learning rates (e.g. the change in maths and reading test scores) compared to students in classrooms with the least daylight. 12 Lighting Guide 5: Lighting for education They also found no connection between physical classroom characteristics such as daylight and student health, although this was measured by recording student attendance, which is not the best indicator of student health. With this in mind and with the essential drive to design low, or zero carbon buildings, the strategy for all schools and colleges must be to use daylight as the primary light source and the building design process should be informed from the outset as to how that can be achieved. Control of daylight ingress should be minimised, such that it is reduced or removed from a space only where privacy, or at specific times when glare or heat gain are issues. In addition where it is necessary to have dark for experimentation or presentation then daylight may need to be completely excluded but only for appropriate periods or time. This of course must be co-ordinated with use of lighting controls and the heating and cooling design for the building form and early stage in the design. 3.1.1 Design considerations Fig. 3.2 Common factors to consider in daylight design Providing a well daylit learning environment requires a design balance between many factors. As such the daylight and lighting strategy must be developed early in the design process, where the lighting designer works closely with the architect and other design team members. Figure 3.2 shows the common factors that must be considered such that the daylighting strategy delivers the required solution without negatively impacting on other functional and aesthetic requirements of the building. Whilst the considerations apply to both new-build and refurbishment, some design elements will be more difficult to achieve with refurbishment projects due to existing building orientation and form. However this does not exclude the designer from reviewing every aspect of the building and creating the best learning environment achievable. Legal and planning Building orientation Building form External building obstructions Acoustics Room function Thermal design Designing for daylight Internal blinds and control End user Sunlight redirection system Building fabric Shading systems Surface reflectance Glazing type Lighting options 13 3.1.1.1 Building orientation Understanding the site and the building orientation on the site allows the placement of room types where the lighting requirements are different, e.g. art rooms that require a higher level of light as opposed lecture theatres or dance studios. The façade design can also progress as the availability of daylight is established and is matched to the requirement of the rooms. Preferred views out and sight lines can also be established. Refer to the BRE Digest 209: Site layout and planning for daylight and sunlight(30). 3.1.1.2 Building form Understanding the form and continuing to progress the façade design allows more detailed examination of the quality and quantity of daylight that penetrates the building and individual rooms. A review of both the light and shadows is required to establish the quality of the light within the building. 3.1.1.3 External building obstructions In city centre locations or on more compact sites, external buildings will reduce the availability of daylight and views. Understanding the quality and quantity of daylight throughout the building will enable one to advise on adjusting the room positions, window dimensions, window angles and furniture arrangements to improve views and daylight levels. The façades of external obstructions also need to be reviewed to identify if a potential reflection discomfort could occur or if there is an opportunity to improve the brightness of the building to improve the view. 3.1.1.4 Room function Typically, art rooms require more daylight and dance studios or lecture theatres require less daylight. Equally, some spaces will require balanced light with little modelling suggesting a northern aspect is preferred. Computer rooms with high heat loads and high density occupancy could occupy areas within the building that have limited daylight as this would reduce external heat gains. 3.1.1.5 End users Different learning environments with their individual types of users will have some specific requirements from the daylight design. A ‘special education needs’ (SEN) school for example will require that some rooms have few distractions and, as such, views may be permanently or temporarily omitted. Higher education students who have more flexibility in their own schedules and travel through a building will manage their own visual comfort based on their own preferences and glare from sunlight will likely be less of an issue, although should not be ignored. 3.1.1.6 Building fabric The thermal design of the building will drive some elements of the building fabric and therefore the wall thickness. The wall thickness will affect the quantity of light which enters the internal space; however it could also act as a shade to reduce heat gains. Where the building fabric creates a wall thickness of more than 300 mm then the lighting designer and architect should consider how to make use of the horizontal element as this could effectively be a light shelf. 3.1.1.7 Glazing The glass is a critical element in delivering daylight to the internal spaces. As the façade solution is progressed to satisfy the architectural intent, the daylight and the thermal requirements of the building, the selection of the glass will be fixed to achieve a required light transmittance, thermal and solar transmittance. Care should be taken to ensure the glazing specification is maintained throughout the design process as value engineering can often deliver alternatives that satisfy, say, the thermal performance, but significantly reduce the light transmittance. In selecting the glazing consideration should also be given to the frame arrangement. Some glazing systems are well designed and utilise small frames that lead to reduced visual and light obstruction. The quantity of glazing and the arrangement of glazing will have an impact both on the quantity and quality of daylight. The sill and head heights designed to accommodate the end users will deliver good views out and satisfy a key element in delivering good quality daylight spaces. Figure 3.3 shows the 14 Fig. 3.3 Lighting Guide 5: Lighting for education Main window types and daylight distribution systems (e) (ii) (d) (iii) (i) (a) (iv) (g) (f) (v) (b) (c) main window types and daylight distribution systems employed. These are described below. 3.1.1.8 Surface reflectance (a) Full height glazing: provides very good views out and the maximum level of daylight available through the facade. The high level glazing delivers light deep into the space thus creating a visually balanced light distribution. Consideration should be given to visual security for the lower section of the glazing. Also if the furniture is placed adjacent to the glazing then the lower level of glazing will not contribute to the useful daylight within the space, therefore any analysis should not include the lower section of glazing. (b) Traditional glazing: a solid section of wall makes up the lower portion of the wall, typically just over desk height, with a solid upper section downstand element. The glazing is horizontal and can be full width or broken by solid sections. The downstand element can impact on light reaching the full depth of the room. (c) Internal glazing (‘borrowed light’): internal glazing will provide views into the atrium as well as secondary daylight via the atrium. Consideration should be given to the potential requirement for privacy into the room or to reduce distraction for some end users. (d) Rooflights: the atrium rooflight can provide the quality and quantity of daylight, both within the atrium and within the adjacent rooms. The design of the rooflight and any required shading is critical in achieving the quantity and quality of daylight. (e) Clerestory: clerestory windows provide light from the highest and brightest part of the sky and will not generally be affected by external obstructions. They allow a view of the sky but not typically a view of the immediate outside area. In allowing a view of the brightest part of the sky the contrast between the inside and outside is likely to be higher than other window types, thus likely to cause glare. They will provide light deep into the space. (f) Lightwell rooflight: where site constraints limit external facades and views, secondary light to a space can be provided via a lightwell. Depending on the depth of the lightwell, the light will typically be diffuse and glare free. The glazing must be acoustically sound to avoid noise transfer to adjacent rooms. (g) Lightwell window: Semi-translucent glazing can provide a sense a brightness of rooms via the lightwell daylight. This is discussed in more detail in section 3.5. The more reflective the surfaces the more light will be distributed around a space. Selecting which surfaces and colours requires care to ensure that a balance and visual quality exists within the space. Window walls should always be light to reduce contrast and thus reduce the risk of glare. Lighting options 3.1.1.9 Shading systems Fig. 3.4 Vertical exterior shading in use at Cardinal Hume Catholic School (photograph courtesy of Cundall Light4) 15 Many types of shading systems exist and are constructed using a variety of materials such as wood, metal, glass, mirrors or a combination of these materials. The units are arranged either as vertical elements or horizontal elements and fixed to the outside of the building façade. A study of the sun path across the facades of the building at midsummer, midwinter and the equinox will show where shading may be required to support other thermal control devices. The shading devices will typically reduce the quantity of light available within a space but, designed appropriately for their orientation to the sun, they will provide a high quality of light within the space. The material selection should be appropriate to reflect as much light into the space without creating glare due to high luminance. The devices illustrated in Figure 3.3 are as follows: (i) Atria shading: with any large glazed roof, at some period of the day and year the sun will penetrate the space and, without appropriate shading, this could be a source of glare (depending on the use of the space and areas adjacent to the atrium). The solution could be motorised or manual blinds fixed within the roof glazing panels, external motorised louvres or internal louvres. If internal louvres are used these could be combined acoustic/shading louvres. The orientation, depth, width and spacing of the louvres will depend on the factors already discussed in this section, such as building orientation and form. (ii) Vertical shading: the shading system comprises vertical ‘planks’ fixed either perpendicular to the façade or at an angle, depending on the design and requirement of the system. The orientation, depth, width and spacing of the louvres will depend on the factors already discussed in this section such as building orientation and form. Vertical louvres are typically used on the east and west facades of a building to manage the low angle sun that occurs on these facades. Motorised louvres provide the ideal control scenario, closing to cut out thermal heat gains when present and then opening to allow daylight into the space when the thermal gain no longer exists. (iii) Vertically stacked shading: the shading system comprises horizontal ‘planks’ stacked one on top of another. This arrangement provides a shading system which sits close to the building façade. The view out is partially obstructed, depending on the detail of the shading system. The orientation, depth, width and spacing of the louvres will depend on the factors already discussed in this section, such as building orientation and form. This type of shading system is typically found on the south façade to manage the high angle sun. (iv) Horizontally stacked shading: the shading system comprises horizontal ‘planks’ stacked one in front of another. This arrangement provides a shading system which is clear of the window itself leaving good views out, however it extends out from the façade making a much more prominent architectural statement. The orientation, depth, width and spacing of the louvres will depend on the factors already discussed in this section such as building orientation and form. This type of shading system is typically found on the south façade to manage the high angle sun. (v) Lightshelf: the function of a lightshelf is twofold; the first is to reflect light onto the ceiling and deep into the space, thus balancing the level of light between the façade and the back of the room. Secondly, as a large solid component, the lightshelf affects the thermal properties of a room. The scale of the lightshelf and materials of which it is composed will depend on the façade, building orientation and room dimensions. 16 3.1.1.10 Sunlight redirection system Lighting Guide 5: Lighting for education Building components that reflect and direct the daylight can be used both to provide a visually brighter space and a numerically brighter learning environment. These systems are typically used where there exists difficulty achieving the appropriate lighting quantity and quality. — Fibre optic light distribution: these system use a series of light collectors either mounted on the roof or walls that feed the light into fibre optic cables that are routed through the building fabric to the room in which the light is required. — Light pipes: these comprise a highly reflective tube with an external and internal lens creating a sealed system. The sunlight enters the top of the unit and reflects multiple times before being emitted into the room. The greater the diameter of the light pipe the greater the quantity of daylight that will be distributed into the room and the greater the length of light pipe feasible. Bends in the light pipe should be avoided as they introduce losses. — Reflective surfaces: semi-specular material can be used for ceiling tiles and wall coverings to create areas of higher brightness or reflect more light into another zone, e.g. on the inside of the lightwell, the walls can be lined with a semi-specular material to increase the quantity of reflected light arriving at the ground floor. — Microstructure prismatic materials: this type of material is manufactured with small prismatic patterns on the surface of a blind or within a glazing unit, to redirect the daylight to reduce or eliminate glare. A common use of these materials is in the upper element of the window system to redirect light onto the ceiling and thus to the back of the room. 3.1.1.11 Internal blinds and control Internal blinds will be required on nearly all external windows and the majority of internal windows. This will allow control of the daylight to allow viewing of presentations and videos. The blinds will also offer privacy when required. The selection of internal blinds is critical as too often they are closed to control glare and then left closed when, if opened, they would provide a higher quality, naturally lit, environment and allow the electric lights to be turned off. Blinds that are easy to control and reliable are more likely to be used. Motorised blinds are expensive and unlikely to be suitable for general use although may be appropriate for high level windows in lecture theatres, halls or drama studios. The transmittance of the blind material should be no more than 10% such that the sky brightness and sunlight luminance is reduced to a comfortable level. Some blinds are classed as ‘retro-reflective’, which means they are designed to reflect some heat gain whilst allowing reflected light through and allowing a view out. They may be appropriate for some areas where the heat gain is not so great as to require an external louvre system. 3.1.1.12 Thermal design Almost all of the components of the building design that affect the daylight design will also affect the thermal design. It is therefore essential at the earliest stage of the project to ensure sufficient time is spent examining the most likely solutions for the site, the building and the spaces within the building. Only through early discussion between the lighting designer, architect and other design team members will all of the opportunities to deliver high quality daylit spaces and energy efficiency be realised. 3.1.1.13 Acoustics Depending on the building design and selection of building materials, additional acoustic control may be required within the classrooms and lecture theatres etc. The position of the acoustic panels/baffles/ceiling tiles must be coordinated with the lighting designer to ensure the installation of the equipment Lighting options 17 does not interrupt the distribution of the daylight. Typically, if acoustic panels are to be suspended in a room then an orientation perpendicular to the façade will have less impact than installation parallel to the façade. 3.1.1.14 Legal and planning The architect must develop accurate elevation drawings as part of the planning submission. It is therefore essential to conclude the daylight strategy, assessment and analysis early in the design process to ensure all window dimensions, frame details, shading systems and roof lights are shown on the elevation details and that the building height is fixed. Changes can be costly and may not be feasible in some circumstances. 3.2 Electric lighting There will be times of the year and times of the day when daylight is insufficient, e.g. on a winters evening for adult education. At such times, or where daylighting is specifically excluded, electric light will need to be introduced. Designers should consider carefully the provision of electric lighting levels according to the tables contained in this Lighting Guide (see Table 5.1). Overprovision should be restricted by careful design and by use of suitable lighting controls that provide for constant illuminance. The addition of electric light to top-up the daylight should be done carefully, minimising energy use as much as practical. Electric light should also be added according to task and, for the major tasks specifically, it would for instance be sensible to light a standard children’s classroom to only 300 lux given that it is in use for over 35 hours per week to teach children, rather than light it to 500 lux simply because it is used for adult education for one or two hours in the evenings. It should also be remembered that in most teaching spaces the working plane is rarely simply a horizontal table surface. The design will have to take into account many vertical and other non-horizontal surfaces and balance carefully the direction or flow of light. Use of measures such as cylindrical and cubic illuminance may provide better indicators of good lighting than conventional horizontal and vertical illuminance or illuminance ratios between a horizontal work plane and other building surfaces. 3.3 Integrated daylighting and electric lighting Without doubt, the best lighting designs take account of natural and electric lighting, balancing one carefully with the other throughout the working day. Careful design should include electric lighting that reacts to daylight at different depths into the room and tries to maximise the penetration of daylight into the space. The designer would do well to think about minimum and average daylight factors in their design and to relate these appropriately to location and orientation of the building, or to use alternative sunlight and daylight metrics such as useful daylight illuminance (UDI). In either case designers must allow for suitable daylight sensing and dimming luminaires throughout with simple user friendly controls. Education buildings are designed to accommodate many diverse activities in different interior spaces. The successful interior space design requires that the designer takes into consideration all the requirements and constraints. Good lighting is an essential part of the interior space design and without it student and staff activity will be seriously impaired and valuable energy will be wasted. Good lighting ensures that students, teachers and other staff can see to carry out their various tasks safely, efficiently and in comfort. It is important to note that the lighting should not only illuminate the tasks but must light beyond the horizontal plane and contribute to the quality of the visual environment and the well-being of the occupants. This needs a holistic or integrated approach to lighting design considering all criteria and bringing together daylight and electric lighting solutions in a well-managed operation. 3.3.1 Climate-based modelling Climate-based daylight modelling is the prediction of various radiant or luminous quantities (e.g. irradiance, illuminance, radiance and luminance) 18 Lighting Guide 5: Lighting for education using sun and sky conditions that are derived from standardised annual meteorological datasets. Climate-based modelling delivers predictions of absolute quantities (e.g. illuminance) that are dependent both on the locale (i.e. geographically-specific climate data is used) and the fenestration orientation (i.e. accounting for solar position and non-uniform sky conditions), in addition to the space’s geometry and material properties. The operation of the space can also be modelled to varying degrees of precision depending on the type of device (e.g. luminaire, venetian blinds etc.) and its assumed control strategy (e.g. automatic, by occupant, or some combination). The term ‘climate-based daylight modelling’ is generally taken to mean any evaluation that is founded on the totality (i.e. sun and sky components) of time-series daylight data appropriate to the locale over the course of a year. In practice, this means sun and sky parameters found in, or derived from, the standard meteorological data files which contain 8760 hourly values for a full year. Given the self-evident nature of the seasonal pattern in sunlight availability, a function of both the sun position and the seasonal patterns of cloudiness, an evaluation period of twelve months is needed to capture all of the naturally occurring variation in conditions that is represented in the climate dataset. Standard climate data for a large number of locales across the world are available for download from several on-line repositories. There are a number of possible ways to use climate-based daylight modelling. The two principal analysis methods are cumulative and time-series. A cumulative analysis is the prediction of some aggregate measure of daylight (e.g. total annual illuminance) founded on the cumulative luminance (or radiance) effect of (hourly) sky and the sun conditions derived from the climate dataset. It is usually determined over a period of a full year, or on a seasonal or monthly basis, i.e. predicting a cumulative measure for each season or month in turn. Evaluating cumulative measures for periods shorter than one month is not recommended since the output will tend to be more revealing of the unique pattern in the climate dataset than of ‘typical’ conditions for that period. The cumulative method can be used for predicting the micro-climate and solar access in urban environments, the long-term exposure of art works to daylight, and quick assessments of seasonal daylight availability and/or solar shading at the early design stage. Time-series analysis involves predicting instantaneous measures (e.g. illuminance) based on each of the hourly (or sub-hourly) values in the annual climate dataset. These predictions are used to evaluate, for example, the overall daylighting potential of the building, the occurrence of excessive illuminances or luminances as inputs to behavioural models for light switching and/or blinds usage, and the potential of daylight responsive lighting controls to reduce building energy usage. A daylight performance metric would need to be based on a time-series of instantaneously occurring daylight illuminances because it is important to capture the full range of illumination conditions to reliably characterise the daylighting potential of the space. Whilst the practicalities of climate-based daylight modelling are fairly well understood, it remains to be seen which of the handful of candidate metrics will be deemed most suitable for compliance purposes. One of the metrics under consideration is called ‘useful daylight illuminance’ (UDI). The useful daylight illuminance scheme was devised to reduce and make readily intelligible the output from a climate-based simulation without sacrificing the vital performance-revealing content of the raw data. Rather than analyse the vast amount of simulated illuminance data using traditional means, e.g. frequency histograms, cumulative plots etc., the rationale behind UDI was to approach the data first from a ‘human factors’ perspective, and then reduce it to compact metrics. Put simply, achieved UDI is defined as the annual occurrence of illuminances across the work plane that are within a range considered ‘useful’ by occupants. The range considered useful is based on a survey of reports of occupant preferences and behaviour in daylit offices with user-operated shading Lighting options 19 devices. Daylight illuminances from 100 lux to the design level value, say 350 lux, are considered effective, either as the sole source of illumination or in conjunction with electric lighting. Daylight illuminances from the design level value up to around 2500 lux are often perceived either as desirable or at least tolerable. UDI achieved therefore is the defined as the annual occurrence of daylight illuminances that are between 100 and 2500 lux. The UDI range is further subdivided into two ranges called UDI-supplementary (or UDI-s) and UDIautonomous (or UDI-a), taking the design level illuminance as the boundary between the two ranges. UDI-supplementary gives the occurrence of daylight illuminances in the range 100 to 350 lux (depending of the design level illuminance). For these levels of illuminance, additional electric lighting may be needed to supplement the daylight for common tasks such as reading. UDIautonomous gives the occurrence of daylight illuminances in the range 350 to 2500 lux where additional electric lighting will most likely not be needed. The UDI scheme is applied by determining at each calculation point the occurrence of daylight levels where: — the illuminance is less than 100 lux, i.e. (or UDI-f) — the illuminance is greater than 100 lux and less than 300–500 lux, i.e. UDI-supplementary (UDI-s) — the illuminance is greater than 300–500 lux and less than 2500 lux, i.e. UDI-autonomous (UDI-a) — the illuminance is greater than 2500 lux, i.e. (UDI-e). UDI ‘fell-short’ UDI-exceeded For those cases where solar gain in summer must be controlled to minimise overheating/cooling, careful attention should be paid to the degree of occurrence of the UDI-e metric. 3.4 Lightness of the interior When glancing around a room, people take more notice of vertical or near vertical planes than of working surfaces. The appearance of an interior is affected by its general brightness, which depends on the distribution of light in the room and the lightness of room surfaces. The way in which the space is illuminated will affect the environment and character of the space and appearance of objects within. This lighting sets the tone or mood of the space and gives it atmosphere and prestige, and provides comfort and stimulation for the occupants. To create a feeling of visual lightness it is necessary to direct light onto room surfaces, particularly those surfaces that are prominent in the normal field of view. Often these will be the walls but the ceiling may also be included, especially in large rooms. Where workstations are employed using vertical partitions, some light on the partitions will be beneficial and without which the room can appear gloomy and under-lit. Table 3.1 below gives the range of illuminance that should be provided on the major surfaces. They will produce acceptable conditions in most situations. For example bright walls will make a room appear large and spacious whilst dark walls make it appear small and cramped. Table 3.1 Recommended reflectance and illuminance values within an educational space Room surface Reflectance range Illuminance Ceiling Walls Task area Floor 0.7 0.5 0.2 0.2 30–90% of task Illuminance or Eh min > 50 lux; Uo > 0.1 50–60% of task Illuminance or Ev min > 100 lux; Uo > 0.1 According to task requirement Maintained value of 30–50 lux to to to to 0.9 0.8 0.6 0.4 20 3.5 Lighting Guide 5: Lighting for education Room surface reflectance Room surface reflectance is the ability of the surface to reflect light that falls on it. The colour appearance of a surface is a function of the surface itself and the type of light source. It is rare that a lighting designer is allowed to select the room surface finishes. But when the opportunity arises the designer should choose the hue (or colour), its lightness or darkness and chroma (or saturation). Subdued colours are often chosen where a restful or dignified atmosphere is required, whilst strong colours and high contrast are normally used to create lively and exciting effects. The recommended reflectance values together with the preferred range of illuminance are shown in Table 3.1. These values not only provide for balanced appearance but also help to generate inter-reflected light making the scheme more energy efficient. Experienced designers will of course be able to achieve desirable results outside of these limits. The primary presentation wall, containing the whiteboard, should be of a different complementary colour and darker hue than the other walls. This helps to reduce eye strain as the viewer looks from desk to board-based tasks and back again. Whilst it may be desirable for lighting efficiency to provide higher reflectance surfaces, a deep tone on one wall will provide visual form to the space and reduce glare. If the presentation wall is not chosen for the different shade, a side wall (not the main window wall) should have the complementary or darker hue. 3.6 Lighting the interior space In addition to lighting the task and room surfaces it is important to fill the volume of space occupied by people with light. It should be remembered that we see the reflected light from surfaces and hence the choice of colour scheme can significantly affect the overall impression of the room. The light will need to illuminate or highlight people and objects, reveal textures and improve the appearance of people within the space. The preferred lighting conditions can be described by the terms ‘mean cylindrical illuminance’, ‘modelling index’ and ‘directional lighting’. 3.7 Mean cylindrical illuminance Good visual communication and recognition of all solid objects and especially people’s faces requires adequate brightness. The objects require light to reach them from many directions, see Figure 3.5. In essence, the volume of space in which people move should be filled with light. The requirement can be met by providing sufficient mean cylindrical illuminance in the space at head height. In teaching and circulation areas the recommended maintained mean cylindrical illuminance (Ez) should be at least 150 lux at 1.2 m above floor level with uniformity of 0.1. Checks should also be made at 0.8 m and 1.6 m above floor level to ensure adequate coverage for all ages of the educational staff and students. 3.7.1 Calculation of mean cylindrical illuminance The cylindrical illuminance in a space can be calculated using proprietary software, often just by selecting the right option so that the calculation surface or grid calculates cylindrical rather than horizontal illuminance. The grid size is defined in BS EN 12464-1(31) (due for updating) and also BS EN 12193(32). Grids approximating a square are preferred; the ratio of length to width of a grid cell should be between 0.5 and 2. The maximum grid size should be: p = 0.2 × 5 log d (3.1) where p ≤ 10 and is the maximum grid cell size (m), d is the longer dimension of the area (m) if the ratio of the longer to the shorter side is less than 2 (otherwise d is the shorter dimension of the area). Lighting options 21 The number of points in the longer dimension is given by the nearest odd whole number of d/p. The resulting spacing between the grid points is used to calculate the nearest odd whole number of grid points in the shorter dimension. This will give a ratio of length to width of a grid cell near to 1. A border of 0.5 m from the walls is excluded from the calculation area except for task areas that are defined and near the wall. For the immediate surround area the same grid spacing as for the task area should be applied. For the background the whole room with a border of 0.5 m from the walls, the grid spacing should be in accordance to the room size. Fig. 3.5 Light falling on the face from all sides rather than just horizontally is a better measure of how well lit the face will be, viewed from any direction This calculation grid should be applied at 1.2 m above floor level, effectively the seated head height of a typical person. Where the calculation is applied in rooms predominantly designed for small children, and where furniture is such that it specifically designed to suit them, it would be wise to check the corresponding mean cylindrical illuminance at about 800 mm. Similarly, where the space is designed for teaching where head height is more commonly at around 1.5–1.8 m, such as for a formal teaching layout with teaching mainly from a lectern or board, then the mean cylindrical illuminance at these positions and height should also be calculated. Approximation of the mean cylindrical illuminance can be made by calculation the average vertical illuminance at the specified position and height for each of the four main vertical planes. In this case: Ez = 0.25 (Ev1+ Ev2 + Ev3 + Ev4 ) 3.7.2 Measurement of mean cylindrical illuminance (3.2) On-site measurement should be carried out at the correct height and to the method in the Code for Lighting(8) using the grid point spacing as calculated above and with the use of a cylindrical illuminance photocell mounted and calibrated against a suitable light meter, see Figure 3.6. Where there is no possibility of obtaining such a photocell the user should measure each of the four main orthogonal vertical planes and average the readings using the formula for Ez above. 3.8 Fig. 3.6 Modelling index and directional light A typical cylindrical illuminance measuring photocell People, and almost everything else in an interior, are three dimensional and need to be illuminated all around. Modelling describes the ability of light to reveal solid form. Modelling may be harsh or flat and the relative strength of modelling is influenced by the directions from which the light comes and the direction from which the object is viewed. Fairly strong and coherent modelling helps to reveal three-dimensional shapes as, for example, in display lighting. Good modelling is essential to sculpture display and similar purposes, and can help to reveal the detail of many textured tasks. The effectiveness of the light for modelling can be defined by the ratio between mean-cylindrical and horizontal illuminance at the point of interest, see Figure 3.7. A ratio > 0.3 will provide for adequate modelling; this may be closer to 0.5 for teaching spaces used by children. For good modelling there is a need for preferential light to come from one direction. This directional ‘flow of light’, as produced by daylight through side windows or asymmetric and batwing distributions of electric light, can create pleasant highlights and shadows to model objects, texture and people. The flow of light determines where shadows will be cast and how dense they will be. The lighting should not be too directional or it will produce harsh shadows, neither should it be too diffuse or the modelling effect will be lost entirely, resulting in a very dull luminous environment. 22 Fig. 3.7 Lighting Guide 5: Lighting for education Examples of modelling index (photographs courtesy of Thorn Lighting) (a) Modelling index = 0.1; highly directional downlight creates harsh shadows (b) Modelling index = 0.3; the limit of acceptable modelling in spaces where good communication is required and still too harsh for some children with special educational needs (c) Modelling index = 0.5; more appropriate for children’s classrooms (d) Modelling index = 1.0; except for theatre lighting, it is difficult to get an index much greater than 1.0 and values higher than this would provide modelling of the face making it difficult to lip read, for example 4 Lighting design guidance Without doubt natural light should be our primary source of light whenever it is available in suitable quantity. The links in research to user performance and comfort and the obvious link to energy saving of electric light are strong and building designers and architects must include daylight design from the initial building concept right through to completion and post occupancy evaluation. However it is difficult to accurately predict daylight contribution using current metrics such as daylight factor, which does not take into account direct sunlight components. Those involved in building design should include in their conceptual design team an expert in daylight design and consider the latest design tools and metrics to include and predict excellent daylight contribution throughout all learning spaces. Failure to do so at the earliest stages of design will result in daylight exploitation being very difficult later on. Once daylight has been incorporated into the building shape and orientation then it should be possible to include electric lighting to complete the overall lighting and lighting controls strategy to ensure learning spaces perform for both the user and the environment. 4.1 Daylighting The use of daylight as the main means of lighting is recommended and should not be compromised in a learning environment, except in circumstances outside the designer’s control. Sometimes site constraints such as adjacent buildings or trees will mean electric lighting will be the main source, but the designer should strive to avoid this. Daylight provides a less stressful environment for pupils and teachers, improves learning rates and saves energy. Where we refer to providing daylight within a space we are referring to both a quality of light and a quantity of light to perform the tasks. The quality of the light relates to both the direct component (sunlight) and the diffuse 22 Fig. 3.7 Lighting Guide 5: Lighting for education Examples of modelling index (photographs courtesy of Thorn Lighting) (a) Modelling index = 0.1; highly directional downlight creates harsh shadows (b) Modelling index = 0.3; the limit of acceptable modelling in spaces where good communication is required and still too harsh for some children with special educational needs (c) Modelling index = 0.5; more appropriate for children’s classrooms (d) Modelling index = 1.0; except for theatre lighting, it is difficult to get an index much greater than 1.0 and values higher than this would provide modelling of the face making it difficult to lip read, for example 4 Lighting design guidance Without doubt natural light should be our primary source of light whenever it is available in suitable quantity. The links in research to user performance and comfort and the obvious link to energy saving of electric light are strong and building designers and architects must include daylight design from the initial building concept right through to completion and post occupancy evaluation. However it is difficult to accurately predict daylight contribution using current metrics such as daylight factor, which does not take into account direct sunlight components. Those involved in building design should include in their conceptual design team an expert in daylight design and consider the latest design tools and metrics to include and predict excellent daylight contribution throughout all learning spaces. Failure to do so at the earliest stages of design will result in daylight exploitation being very difficult later on. Once daylight has been incorporated into the building shape and orientation then it should be possible to include electric lighting to complete the overall lighting and lighting controls strategy to ensure learning spaces perform for both the user and the environment. 4.1 Daylighting The use of daylight as the main means of lighting is recommended and should not be compromised in a learning environment, except in circumstances outside the designer’s control. Sometimes site constraints such as adjacent buildings or trees will mean electric lighting will be the main source, but the designer should strive to avoid this. Daylight provides a less stressful environment for pupils and teachers, improves learning rates and saves energy. Where we refer to providing daylight within a space we are referring to both a quality of light and a quantity of light to perform the tasks. The quality of the light relates to both the direct component (sunlight) and the diffuse Lighting design guidance Figure 4.1 Simple rectangular building designs offer little scope to temper daylight (illustration courtesy of J Mardaljevic) 23 component (skylight). Equally we need to review the quality of the view out of the space. In providing a view, most people prefer a view of the natural environment or where this is not possible, e.g. in built-up areas, then a dynamic view is preferred. Natural light is very variable and in the past the direct component has been excluded from the assessment of daylight quality and quantity. The common measure of daylight has been the daylight factor (an expression of how much outside light on an overcast day arrives at a particular place in the room), where the defined luminance distribution of a CIE (Commission Internationale de l’Eclairage) overcast sky is used in the calculation. Within BS 8206-2: 2008: Lighting for buildings, Code of practice for daylighting(33), the principle of climatebased modelling is introduced in section 3.3.1 As discussed in BS 8206-2: 2008, climate-based modelling is currently being developed and, as such, at this time the daylight factor approach to measuring daylight quantity must be used. However to deliver the best quality of spaces, the designer should have studied and have experience in designing spaces utilising sunlight and skylight and controlling these mediums to deliver bright and well lit spaces. In designing a space with appropriate daylight we are providing a space that allows the reduction in use electric lighting during daylight hours. The savings from automatic dimming controls are directly related to daylight factor. As discussed previously, the building form, materials, glazing, façade etc. will affect the daylight factor. As far as space planning is concerned, natural lighting and natural ventilation are in sympathy. The maximum depths of spaces for natural ventilation are comparable to the maximum depths for effective daylighting. The depths of individual classrooms should generally be limited to around 7 m. Beyond this, greater ceiling heights (>2.7 m), skylights, light wells, clerestory windows etc. will need to be employed to improve daylight penetration. To ensure the focus on daylight as the primary source of light in all educational spaces it will be preferable to include the above elements in all possible cases. A ‘well tempered’ daylit environment is one where the fixed architectural form provides both good daylighting and effective solar protection. Thus minimising — though in practice rarely eliminating — the need for occupants to close blinds/shades. The potential for the fixed form to temper the daylighting of the space depends on the building type, specifically on the richness/variety of the fixed architectural form. For simple rectangular office blocks (Figure 4.1), the scope to temper the daylit environment is limited to a few basic building parameters such as glazing ratio, window transmissivity etc. Optimisation of these will have some beneficial effect, but the occupants will still have to resort to frequent use of the blinds/shades to prevent undue ingress of daylight and to prevent glare. The greater the richness and variety in the architectural form (e.g. brise soleil, atria, self-shading etc.) the greater the opportunity for tempering the daylit environment through an integrated design approach that combines effective solar control with good daylight practice. Often the more successful daylighting designs are those that offer a combination of daylighting strategies. Low-rise buildings such as schools (Figure 4.2) offer the greatest opportunity to realise a ‘well tempered’ daylit environment because the designs can, in principle, accommodate various daylighting features/devices. In addition to the brise soleil and atria noted above, imaginative low-rise building designs can also feature skylights, clerestory windows, light-wells, re-entrant sections, overhangs, deep self-shading reveals etc. Window areas and ceiling heights should be chosen to achieve high daylight factors because the benefit of carbon savings is so significant that the extra cost of larger windows and high ceilings may be effective in terms of cost of carbon abatement compared to renewables. They will also aid natural ventilation. 24 Lighting Guide 5: Lighting for education Figure 4.2 Lower level architectural forms can combine effective solar control with good daylight practice (illustration courtesy of J Mardaljevic) In all cases where daylight introduces a high thermal load the designer should consider carefully the options. The inclusion of interior and exterior sun control is an option that should be considered, carefully linked to all the other factors. Its removal on cost grounds is not acceptable if that decision makes the use of daylight impractical because of its implications for ventilation design and acoustics. In urban and rural locations where noise and air pollution are not significant, daylight design must take priority with a higher degree of natural ventilation used to offset heat gains. In city locations where noise and air pollution may be considerable, the daylight quantity may have to be reduced to allow suitable ventilation strategies. However it should be remembered that often in built-up locations daylight itself will be restricted by surrounding buildings and the designer should take this into account. 4.1.1 Daylight quantity Fig. 4.3 Deep central atrium providing daylight to first floor classrooms with ICT break-out class on lower floor (photograph courtesy of Corby Academy; Foster & Partners) Fig. 4.4 Average and minimum daylight factor should be calculated up to 0.5 m from each wall The average daylight factor is used as the measure of general illumination from skylights. To achieve the appearance that a room is predominantly daylit the average daylight factor should be at least 2%. If the average daylight factor in a space is at least 5% then electric lighting is not normally needed during the daytime, provided the uniformity is satisfactory. If the average daylight factor in a space is between 2% and 5% supplementary electric lighting is usually required. The strategy should be to create spaces that are daylit to improve learning rates and reduce energy consumption. Therefore good practice would be to achieve 5% average daylight factor and a minimum point daylight factor of 2%. When measuring the average and minimum values it is recognised that directly adjacent to walls the daylight level will be at its minimum and if used will disproportionally represent the daylight distribution within the space. Therefore it is recommended to leave a 0.5 m zone around the perimeter of the space to eliminate these values (see Figure 4.4). As with all calculations, due consideration has to be given to furniture layouts. For example, if it is known (and the question should be asked) that desks or task areas will be positioned directly against the walls of the room, then the 0.5 m zone should not apply. The various types of spaces within a school, college or university will require different lighting strategies, e.g. a drama space, sports hall, art room or lecture theatre etc. will have specific needs such as mirrored walls, solid walls and north lights, blackout etc. As such, the 5% average and 2% minimum good practice design must be balanced against these specific needs. However, for general teaching spaces, as discussed previously, only external factors outside 0·5 m 0·5 m 0·5 m L H 0·5 m W Lighting design guidance 25 the designer’s control would justify daylight factors less than the good practice figures. The importance of the uniformity cannot be underestimated. Too high a contrast and a space will look gloomy from some positions and viewpoints and be visually uncomfortable or distracting. Controlling uniformity requires the access of daylight and distribution of daylight within the room to be balanced. Measures that easily identify if this will be achieved include the ‘no sky line’ and room depth criteria. Calculating the daylight factors throughout the space, either manually or by computer, is also appropriate. These methods are discussed below. The figures recommended here aim to improve the learning spaces that are currently constructed in the UK and, as such, aim to push design forward and ensure designers recognise the value of daylight to the staff and pupils within the learning environment. A procedure for calculating the average daylight factors is given in BS 8206-2: 2008(33) and can be used to calculate the average daylight factor targets given above. 4.1.1.1 Calculating daylight factor for windows and rooflights with continuous obstructions of uniform height When external obstructions can be defined adequately by two horizontal lines, i.e. the upper and lower limits of the visible sky, the average daylight factor on –– the working plane ( D), expressed as a percentage, is: T Aw θ –– D = ————– A (1 – R 2 ) (4.1) –– where D is the average daylight factor on the working plane (%), T is the diffuse light transmittance of the glazing including the effects of dirt (see BS 8206-2: 2008(33), section A.1.2 for typical figures), Aw is the net glazed area of the window (m2 ), θ is the angle subtended by the visible sky (degrees) (measured in a vertical plane normal to the glass, from the window reference point, see Figure 4.5), A is the total area of the ceiling, floor and walls, including windows (m2) and R is the area-weighted average reflectance of the interior surfaces (in initial calculations for rooms with white ceilings and mid-reflectance walls, this may be taken as 0.5). Fig. 4.5 Angle of visible sky Window reference point 0° When two or more windows in a room face different obstructions, or differ in transmittance, the average daylight factor should be found separately for each window, and the results summed. To find the window area above the working plane, in square metres, needed to achieve a given average daylight factor, the equation may be inverted, as follows: –– D A (1 – R 2 ) Aw = ————––– Tθ (4.2) 26 Lighting Guide 5: Lighting for education Note that the window area below the working plane does not significantly increase the amount of daylight falling onto the working plane. This is because the light from the lower part of the windows has to bounce off at least two room surfaces before it reaches the working plane, and it is also common for there to be obstructions below the working plane. A study has shown that the area of the window below the working plane is only about 15% as effective at letting light onto the working plane as an equivalent area above the working plane. Limitations of the formula: Equations 4.1 and 4.2 should not be applied where external obstructions cannot be represented by a single angle of elevation, for example where a window faces into a courtyard. For further information, see BRE Report: Site layout planning for daylight and sunlight: a guide to good practice(34) and Modification of the split-flux formulae for mean daylight factor and internal reflected component with large external obstructions(35). 4.1.1.2 Room depth criteria This section recommends a procedure for calculating the maximum depth of a side-lit room. In a room with windows in one wall only, the following inequality should be satisfied: L L 2 —+—< ——— – – W H 1 – Rb (4.3) where L is the depth of the room from window to back wall (m) (see Figure 4.6), W is the width of the room, measured parallel to the window (m) (see Figure 4.6), H is the height of the window head above floor level (m) (see Figure 4.6) and Rb is the area-weighted average reflectance of the interior surfaces (walls, floor and ceiling) in the half of the room remote from the window. Fig. 4.6 Limiting depth of a side-lit room L H W 4.1.1.3 No-sky line The no-sky line divides those areas of the working plane which can receive direct skylight from those which cannot. If a significant area of the working plane lies beyond the no-sky line (i.e. it receives no direct skylight), then the distribution of daylight in the room will look poor and supplementary electric lighting will be required. The working plane height is relative to the tasks being undertaken, e.g. desk height. At least 80% of the working plane should have a view of the sky. 4.1.2 The view through a window, or how we perceive the world outside, is a dynamic experience associated with changes in skylight, sunlight and season. At its lowest level, a view satisfies the physiological need of the eye for a change of focus, and provides an awareness of the environment beyond the building. View will depend on the location, size, shape and detailing of the window. However stimulating the exterior may be, windows that are too small, break up the view, or are at a height that inhibits view from normal positions are less desirable. There are some spaces where external view may be considered Daylight quality and view Lighting design guidance 27 inappropriate as, for example, in a lecture room or theatre where the aim is to encourage occupants to concentrate solely on the task in hand. Nevertheless, there is a general presumption that a view through a window is good, and a daylight strategy that denies a view in any building needs to be questioned. In buildings comprising very large spaces, internal views to other daylit areas may suffice. However in all classrooms a view to the outside should be considered mandatory. The view out must be balanced by privacy and the need to keep the students’ attention. Low level glazing may require privacy glass, and rooms for teaching that look out onto particularly busy environments may need careful view control to remove visual distraction (see Figure 4.7). The question of privacy can be addressed by using curtains or blinds that have the benefit of avoiding the ‘black hole’ appearance of the window at night. They also provide a means of reflecting electric light back into the room rather than losing it to the outside, but this will require a moderately high reflectance of the inside surface and will dramatically affect daylight contribution. Care should be taken to specify materials that reduce daylight glare where needed or eliminate it if complete darkness is required. This need for control for purposes such as interactive whiteboard or image projection should be balanced carefully with the benefits of having some daylight and view present during daytime hours. Fig. 4.7 Top: the classroom shown uses a radiant heating panel to provide privacy but this also reduces slightly the daylight contribution from the windows Bottom: in this classroom desperate measures have been taken either to reduce glare or view at the rear window, where blinds are not available 28 Lighting Guide 5: Lighting for education Fig. 4.8 Variability of daylight across the room is desirable (photograph courtesy of Thorn Lighting) Fig. 4.9 Internally glazed walls allow daylight contribution, a link to the outside conditions and a distant view (photograph courtesy of Philip Smith) 4.1.3 Glare and sunlight control Care should also be taken in specifying blinds that do not disrupt the ventilation strategy. For opening windows, a common strategy is to fix the blind to each window such that the window can be opened and the blind move with the window, thus allowing the required air flow. The quality of the view is clearly of importance. Some views are of exceptional beauty and provide pleasure in themselves, and any experience of the world beyond the window that extends our perception of space should be considered good. In addition to providing the right quantity of light, daylight gives an interior a particular unique character. Some of this is due to the variability of the daylight including sunlight; also, the distribution of the light enhances the visual field. The directional properties of light from side windows (the ‘flow of light’ across the room) are a significant attribute contributing to the modelling of the interior, including objects within it and surface textures, and providing brightness to vertical surfaces, the amount depending on the reflectance. Some variability across room surfaces is also important (see Figure 4.8). Wherever possible, the shape, size and disposition of the windows should be related to the view, and avoid any deprivation or curtailment of it by their position, height or width. A minimum glazed area of 20% of the internal elevation of the exterior wall is recommended for a view. Any serious obstruction to the view can be annoying and appropriate sill and head heights are important (see Figure 4.7). While the view out should preferably have close, middle and distant components, and contain some natural elements, frequently this is not possible and a popular alternative is the use of courtyards. For these to be successful, they must be well maintained, preferably with suitable landscaping and some views of the sky, and have an adequate view dimension across the courtyard of not less than 10 m. In some instances, a reasonable view of the exterior may not be feasible, and in these cases a long internal view is a useful addition — within a large space or possibly through glazed partitions. However, it is preferable to have a feeling of ‘daylight contact’ maybe from roof lights and including atria (see Figure 4.9). On some occasions, a view out can be a disadvantage and cause distraction, and in these circumstances, blinds or curtains should be provided. In addition, there are situations where there is a need for privacy and here the view into the building needs to be considered. External shading such as blinds or brise soleil are particularly effective in reducing solar gain. Mid-pane blinds are also very effective. Internal shades or blinds will reduce internal gains but are less effective because once solar radiation has penetrated the glass it will cause some heating of the interior of the building. The blind finish is important; reflective blinds may (with clear glass) reflect heat back out, while absorbing blinds and curtains will become warm quickly. Fixed devices require careful design for the site to avoid reducing daylight which could lead to increased use of electric light. Adjustable devices have the advantage of allowing maximum daylight penetration while providing sun shading when required. They can be controlled manually or automatically. Manually adjusted blinds or shades can be set by the occupant as required, but there is a tendency for them to be left down which results in unnecessary use of electric light (see Figure 4.10). Automatic blinds overcome this problem, but special attention needs to be given to their control to avoid user annoyance with frequent movement of the blinds. They also need to be silent in operation, and particular attention needs to be paid to automatic blinds where maintenance is concerned. With internal blinds, it is important to take into account potential problems that could undermine their effectiveness. Such problems include interference with the open window, restricting natural ventilation air flow, blind rattle or sway in the airflow, blinds positioned too far back from the pane Lighting design guidance Fig. 4.10 Blinds closed to reduce glare requiring electric lighting though the class is empty (photograph courtesy of Thorn Lighting) Fig. 4.11 Types of external (numbers 1–10) and internal (numbers 11–15) shading devices 29 allowing sunlight to fall on the interior window ledge or poor, inaccessible or inconvenient user controls. Figure 4.11 shows various types of external and internal shading devices. Detailed descriptions and application advice for each of these shading devices can be found in SLL Lighting Guide LG10: Daylighting and window design(15). Designers should be careful in the selection of interior shading devices and the colouration/pattern of the materials used. In recent research the provision of blinds in 23% of classrooms had spatial characteristics appropriate for inducing pattern glare(36) which can be a particular problem to those who suffer from dyslexia and migraine headaches. One of the most important aspects of obtaining a satisfactory interior environment is to provide a balanced luminance distribution — some contrast but not excessive. If the luminance of the sky seen through a window is very high and close to the line of sight of a visual task of much lower luminance, disability glare can occur due to a reduction in the perceived contrast, making details impossible to see and thus reducing task performance. Disability glare will occur where there is a window in a wall on which there is a whiteboard and this must be avoided. Discomfort glare is experienced when some parts of an interior have a much higher luminance than the general surroundings and this may take some time to become apparent. Discomfort glare from daylight can be a more common occurrence than disability glare, and under most circumstances its degree will depend not on the window size or shape, but on the luminance of the sky seen in the general direction of view. Data suggest that, for the UK, an unprotected window will produce uncomfortable glare over a significant period of the year. It has been predicted that skies with an average luminance exceeding 8900 cd/m2 (corresponding to a whole-sky illuminance of 28 000 lux) will cause discomfort glare, and in the UK these are experienced for about 25% of the working year. Teachers recognise that discomfort glare from daylight and windows impinges directly on student concentration citing the phrase ‘when the lighting is bad the students stop listening’, hence designers should take great care to control overall window luminance. 1 Horizontal projection 2 Fixed vertical projection 6 Pivoted non7 Vertical nonretractable louvre retractable woven mesh 11 Venetian blind 12 Vertical louvred retractable blind 3 Fixed vertical screen 8 Retractable louvred blind 13 Fabric roller blind 4 Fixed louvre system 9 Projecting awning or sun blind 14 Fabric curtain 5 Fixed horizontal 10 Vertical roller blind 15 Venetian blind in double window 30 Lighting Guide 5: Lighting for education Some reduction in the sky glare can be achieved by reducing the contrast between the window and its surroundings, for example by the use of splayed light-coloured reveals or increasing the brightness of the window wall by increasing its reflectance, or lighting it from a window in an adjacent wall. Window frames should be as light in colour as possible, whether stained or painted timber, or painted or integrally coloured metal or plastic. However, the reduction of the sky luminance is the major consideration, and where this is likely to be a problem provision should be made for blinds (e.g. horizontal or vertical louvre blinds) or curtains (which can be translucent or opaque, and internal or external), or retractable screens, canopies or awnings. Permanent features such as roof overhangs may also assist in this matter. However, it has been shown that in the UK, overhangs of more than 300 mm over windows serve little purpose in terms of shading or improved daylighting(37). If the underside of the overhang is light in colour, the penetration will be improved and excessive contrast with the sky can be avoided. Rooflights can cause discomfort glare for most of the working year if the glazing can be seen directly from normal viewing positions at angles of less than 35° above the horizontal (see Figure 4.12). The glare can be ameliorated by using measures similar to those for vertical windows (see Figure 4.13). Fig. 4.12 Skylight panels in the field of view can cause discomfort glare 0<35° Fig. 4.13 Shading styles similar vertical glazing can be used to reduce glare 0<35° Contrast between the glazing and its surroundings can be reduced by using coffers with high reflectance sides which also cut off the view of the direct sky and by setting the rooflight in a light-coloured ceiling. The luminance of the sky seen can be reduced by adjustable blinds, shades or louvres. The use of a permanent diffusing panel to close in a coffer at ceiling level can provide unsatisfactory conditions; it may become difficult to appreciate that the source of light is natural and the feeling of ‘daylight contact’ may be lost, particularly if the exterior glazing material is also diffusing. Further, on dull days, there will be a noticeable reduction in the amount of contributed light. While most of the time sunlight is considered to be an amenity in this country, there are occasions particularly in the summer months when it is necessary to provide some protection from its inconveniences, such as excessive direct heat and glare, and shading devices are required. These can usually be designed in conjunction with the devices considered for the reduction of sky glare. Lighting design guidance 31 It may be undesirable, depending on the climate, to design permanently fixed features because they will reduce the amount of daylight entering the room at all times and this could be particularly undesirable in the winter months. The protection can be provided by adjustable screening devices such as curtains and blinds including louvre blinds (Figure 4.11, types 11–15). For optimum sun protection, the solar control devices should be placed outside the window; retractable screens, canopies or awnings can be used here (Figure 4.11 types 1–10). In designing a sunlight control system, it is important that it takes into account the extent of the use of the school during the summer months. 4.2 Electric lighting 4.2.1 Glare α Fig. 4.14 Lamp shielding angle, α Emphasis on glare from electric lighting has for a number of years been focused on the requirements of Lighting Guides LG3(38) and LG7(39), where designers have focused on reducing glare in computer display screens. Technological advances have made some of these recommendations obsolete and designers would be well advised to absorb the most recent guidance and research before reaching a definition of suitable glare limits. The design should also consider that the majority of learning is supported by computers, but not taught via computers; hence the reduction of glare to computer screens whilst growing in importance is not an over-riding factor in most classrooms or lecture theatres. Use of computers will undoubtedly increase over the next decade but their use in the majority of cases will be limited, interrupted by other styles of learning, conventional teaching, and for limited periods. Whilst considering glare to display screens, designers should focus on providing glare control that improves the modelling and lit appearance of the true teaching surface: the face (teacher, lecturer, student or pupil), text, wall displays and presentation board. Long established calculations for unified glare rating (UGR) may provide the designer with a numerical method for calculating glare, but the designer would do well to consider the issues rather than meet a minimum number. Glare calculated at the mid-position of each wall looking from a seated position may indicate a worst case but does not apply well to users who are standing, users of different ages and heights, flexible class or teaching layouts or other teaching spaces outside the norm such as raked lecture theatres. Current research is looking to offer alternative measures for glare using high dynamic range imaging converted to luminance maps, though this is still some way from providing useful metrics. Light sources of high luminance and smaller sizes, including smaller, more intense optics, will need careful consideration so that the light source luminance is not so intense that even at a small size it impinges on a clear and comfortable view of the users. This can be achieved by specifying the minimum shielding angles in the field of vision given in BS EN 12464(31) for the specified lamp luminance, see Figure 4.14. Minimum shading angles for a range of lamp luminance values are given in Table 4.1. The values given in Table 4.1 do not apply to uplighters or to luminaires mounted below normal eye level. Table 4.1 Lamp shielding angle limits Lamp luminance (kcd/m–2) Minimum shielding angle, α 20 to < 50 50 to < 500 –> 500 15° 20° 30° 32 Lighting Guide 5: Lighting for education 4.2.2 Flicker and high frequency operation Research clearly shows flicker from fluorescent and discharge light sources powered by switch start or wire-wound gear does influence the comfort of a significant proportion of the population. To avoid discomfort and hence increase concentration and learning rates, the designer should specify high frequency (HF) unless there is a specific special educational need for other systems. Care should be taken that all control gear should conform to the targets set by the Energy-using Products Directive(17) and, in the UK, by the Ecodesign for Energy-Using Products Regulations(40). Advances in high intensity discharge gear mean that HF gear is becoming more readily available for these light sources. Where practical and efficient, HF gear should also be used in these applications. Where the room being lit contains high speed machinery, such as machine rooms for engineering, industrial technology, or design technology spaces in schools, then HF equipment must be specified on grounds of safety. Here the fast moving machines combined with switch start gear can create stroboscopic effects that may make the work appear stationary. HF gear operating at above 30 kHz should minimize this risk. Even so, the designer should carry out a risk assessment of the processes concerned to ensure that the lighting will not add to any inherent danger. Care must be taken with the specification and use of LED light sources and associated drivers where some poorly designed units have been seen to introduce an over-riding 100 Hz ripple onto the mains, which may be visible to some users. 4.2.3 Veiling reflections Veiling reflections are high luminance reflections that overlay the detail of the task. Such reflections may be sharp-edged or vague in outline but, regardless of form, they may affect the ability to see the task and cause discomfort. Task performance will be affected because veiling reflections usually reduce the contrast of a task, making task details difficult to see. The two contributors to veiling reflections are any part of the task that is glossy to some degree, and parts of the interior that have a high luminance, such as windows or luminaires. Generally methods of avoiding veiling reflections are to use matt finishes or to arrange the geometry of the view so that high luminance is restricted, for example by using curtains or blinds on windows. Gloss finishes should be used with care as they can cause veiling reflections and glare and often when least expected, for instance the use of a gloss whiteboard, designed for written presentation but used as a projection screen. Here the lamp from the projector itself can become a major source of veiling reflection and discomfort glare to students seated at many positions within the room. This is less of a problem in most indoor spaces but small intense light sources such as computer projectors or uncontrolled luminaires such as spotlights can give problems. Such glare will manifest itself in veiling reflections on whiteboards, glossy computer screens and glossy pages in books. The primary complaint in classrooms about visual conditions is that of reflections in display screens(41). This extends to a wider range of media than just computer screens. Modern classrooms have for some time used gloss finished whiteboards rather than chalk-based black or green boards. Inherently the gloss finish is susceptible to veiling reflections that make it difficult to see the writing on the board from certain angles. While this problem can be controlled by the electric lighting, daylight plays a much larger role and suitable control of the luminance from a window will be necessary. Extending this to current technology, it is necessary to include interactive whiteboards dealing not just with the written message, but projected images as well. Whiteboards, like green and blackboards before them, require careful lighting. Luminaires placed in the offending zone may cause veiling reflections for pupils, so position and control is important. Windows should not be provided in either the front wall or back wall of a lecture theatre or lecture room. Lighting design guidance 33 The former would produce intolerable glare to the audience and the latter would cause serious veiling reflections on the board. 4.2.4 Luminance distribution Fig. 4.15 Classroom exploiting the use of colour (photograph courtesy of Concord (Havells Sylvania) and Redshift Photography) The luminance distribution in the field of view controls the adaptation level of the eyes, which affects task visibility. A well balanced adaptation luminance is needed to increase the visual acuity (sharpness of vision), the contrast sensitivity (discrimination of small relative luminance differences), and the efficiency of the ocular functions (such as accommodation, convergence, pupillary contraction, eye movements etc.). The luminance distribution in the field of view also affects visual comfort and there are a number of problems to be aware of. Too high luminance may give rise to glare; too high luminance contrasts will cause fatigue because of constant re-adaptation of the eyes. Too low luminance and too low luminance contrasts will result in a dull and non-stimulating working environment. This can be as much an effect of the light distribution in a space as the choice of colours used on the major surfaces. Figure 4.15 shows a typical classroom where colour is used in the field of view to add interest to an otherwise bland space. Light surfaces, even the floor contribute to the overall brightness of the room. The luminance of all surfaces is important to create a well balanced luminance distribution, and will be determined by the reflectance and the illuminance on the surfaces. Recommended reflectance for the major interior surfaces are discussed in section 3.5. In addition, the reflectance of major objects (e.g. furniture, machinery etc.) should be in the range of 0.2 to 0.7. The surfaces within the room should be effectively lit. For spaces where communication is less important the maintained illuminance on the walls should be ≥50 lux with uniformity >0.1; maintained illuminance on the ceiling should be ≥ 30 lux with uniformity of 0.1. Applications or activity areas such as offices and teaching areas, where facial recognition and communication are much more important, need brighter surfaces. Here the recommended maintained illuminance for walls should be ≥ 100 lx and for ceilings ≥ 50 lx. The designer should consider that illuminance over the complete wall surface will contribute to the illuminance in the field of view and should be considered carefully as a whole. 34 4.2.5 Lighting Guide 5: Lighting for education Choice of lamp and luminaire It is impossible using known technologies to match artificially the properties of daylight. Given the fixed spectrum of all light sources it is not possible to match the change in sky colour through the day or at different locations with the movement of the sun in azimuth and elevation. Even the latest red, green, blue colour mixing techniques using LEDs cannot match the colour content in terms of spectrum; the best that can be achieved is to fool the psyche into thinking that the artificial solution comes close. The appearance of a lighting solution or lamp with a colour temperature close to that of light from a clear sky at midday may seem excessively blue as evening approaches. The light is also coloured by the materials outdoors from which the light it reflects before entering through the window. Discrepancies between the colour of electric light and that of daylight can be reduced by: (a) using lamps of cool or intermediate correlated colour temperature (CCT) class of about 4000 K, or (b) by screening the lamps from the view of occupants. Caution: research is continuing into the effects of biodynamic lighting on people and, until firm research suggests no long-term risk, the lighting designer should be wary of unsubstantiated claims. 4.2.6 Lighting control It becomes apparent to anyone who walks around educational buildings that lights are often switched on in places that have more than adequate daylight. Were lighting to be turned off, the occupants would often not notice the difference. In considering dimming and controls the reasons for switching lights on must be understood. This may be for a number of reasons such as: — All lights are turned on because the row of seats furthest from the windows is at a lower level of illumination than the window seats, and the lights are turned on to equalise the illumination. — The lights were turned on first thing in the morning and, as the day brightens up, the teacher has not noticed they are still on. — Clouds passing have caused brief interludes of dimness that have prompted the teacher to turn lights on. — Glare from the windows has caused the shades or curtains to be drawn — Daylit spaces adjacent to classrooms (e.g. corridors) are brightly illuminated and the classroom appears relatively dim on entering. Lighting design should make the maximum use of daylight and be divided into zones of control relative to the amount of daylight present. Using electric light to complement daylight should be considered only when daylight is insufficient, and designers should ensure energy efficient electric lighting that only operates when it is required (see Figure 4.16). This last point can be covered by the positions of the control devices, by the organisation of the lighting circuits to relate to the daylight distribution and to the function of the space. Automatic controls can provide significant energy savings but it is essential that any controls are ‘user friendly’, and should be based around automatic daylight harvesting where daylight is sufficient and absence control to spaces where lighting is likely to be left on. Absence control requires the user to make the decision to turn on lighting locally and switching circuits and positions should be included with this in mind. Careful design here will reap maximum energy savings, minimise control circuit power losses and provide the user with consistent functionality. Lighting design guidance Fig. 4.16 35 Daylight sensing controls barely visible in the ceiling centre hold off the artificial lighting during times when sufficient daylight is available. (photograph courtesy of Thorn Lighting) There is extensive evidence that users do not like or use complex control systems, hence the designer should keep it simple, avoiding complex building management linked systems (that may be beyond the comprehension of staff and pupils) and use controls that are intuitive in operation and easy to learn. ‘Scene setting’ controls should be used only where absolutely necessary, for instance in conference facilities and lecture theatres, but even here should be limited where possible to a number of simple, practical scenes operated by clear and practically located control panels. In all cases lighting controls should be commissioned (see CIBSE Commissioning Code L: Lighting(42)) by a suitably qualified person and adequate training given to users. 4.3 Integrated daylight and electric lighting In educational buildings most of the spaces should be predominantly daylit, with electric lighting taking over on dull days and at night. There may however be some spaces that have some daylight, but not always sufficient over the whole area. In these cases, it will be necessary to employ a system combining both daylight and electric lighting, which is used as and when required. It is necessary to consider the distribution of daylight together with the complementary electric lighting distribution to ensure they enhance one another. However, it will not be sufficient to provide a combined lighting system that gives only a uniform horizontal plane illuminance. It will also be necessary for the electric lighting installation to create the sensation of brightness in the areas remote from the windows. For this it will be necessary to highlight surfaces, particularly the walls. When the daylight recommendations cannot be achieved throughout the space, a supplement of electric lighting should be provided, but it is usual to require the space to appear predominantly daylit. The first requirement is for the electric lighting to supplement the daylight so that the combined illuminance is suitable for the task or activities being undertaken, and an effective use of controls is necessary to limit the electric light to no more than is required. To achieve a satisfactory appearance the luminance of surfaces should be balanced throughout the space so that surfaces in parts remote from the windows do not seem dim and gloomy. An appearance that is visually acceptable can be achieved by preferentially lighting the wall remote from the windows with lighting that is separate to that required for the task. This wall lighting can be more effective when some variety is incorporated, as described in section 4.2.4. The ceiling will also need to be well lit to avoid a gloomy appearance. Care should be taken when this wall is partly glazed and open to an atrium or corridor. 36 Lighting Guide 5: Lighting for education Bare lamps should, wherever possible, be screened from direct view (see Table 4.1) to reduce glare and to limit the variation that can occur in the colour appearance of daylight. With regard to discomfort glare for combined installations, and to ensure the degree of glare from the two installations operating together is acceptable, it is advised that independently each installation should be designed to be within acceptable limits. 4.4 Aids to lighting design Whilst designing with numbers has its place in quantifying the performance or efficiency of a space, quantifying the lit appearance, the comfort factor is much more difficult. As an aid to developing this aspect of design, the designer should use a number of techniques enabling the design possibilities to be iteratively explored and proved. These methods could include computer-based modelling and architectural models, particularly for daylight and sunlight studies, but also to understand the play of electric light in a space. Architectural models were commonly used to explore daylighting designs, but are often expensive and difficult to achieve given the demands on specialist equipment and model making; further iterations of models may make this impractical. However they do render daylight as perceived and viewed by the eye and therefore are easy to interpret. Computer visualisation (see Figure 4.17), whilst easier to achieve given current technology, is more difficult to interpret, the results being only as good as the software algorithms and the display ability. For example, in order for the screen to render the difference between two joined white surfaces, software is forced to render two versions of grey, where as the eye would actually see two whites of differing luminance. For this purpose it is advised that a scale of not less than 1:20 be used and that models are made from materials that are opaque and have the appropriate surface reflectance and colour. It is obviously important that models are dimensionally correct and that any external obstructions are included. The depth of detail that should be modelled will depend on the purpose of the modelling study and it may or may not be necessary to model, for example, glazing bars. However, where measurements are to be taken, then items such as glazing bars must be taken into account. It is important to include any permanent shading devices including roof overhangs. Using the correct material finishes, and in particular for any shading device, is critical where measurements will be taken. Also external obstructions and their reflectance should be modelled. The model can be used in three ways: to appraise the appearance of the lit space, to measure the daylight distribution and to examine the direct sunlight penetration. For appearance appraisal it will be necessary to provide viewing slots. These need to be placed at a normal head position and can be used under real or artificial sky conditions. It is of course important that no stray light enters the model through the viewing slot. It is often easier and more convenient to use a camera. When the model is to be used for measuring the daylight distribution, usually under an overcast sky condition, it will be necessary to provide entry positions for small photocells, but it must be possible to seal these openings when the measurements are being made to avoid errors due to light leakage. It is useful to measure not only the inside values but also an outside, unobstructed, sky value, which will enable the measurements to be quoted in terms of daylight factor. The measurements can be made under a real overcast sky, but it is more convenient to use an artificial sky to overcome the problem of light level variability. Models can also be used to test sun penetration. In this case the model can be used in conjunction with a spotlamp to represent the sun and a sundial to enable the correct relationship between the model and the spotlight (artificial sun) to be established. With this equipment a range of sun positions can be explored. An alternative is to use the model in conjunction with a heliodon, which enables the sun/site/building relationship to be explored more easily. Lighting for particular applications Fig. 4.17 37 Virtual daylight model created in IES Virtual Environment (images courtesy of A Bissell, Cundell LLP.) Whilst few design practices have their own artificial sky or heliodon, these pieces of equipment are commonly available in schools of architecture, university building departments and research establishments. Calculations for the determination of point daylight factor, illuminance and luminance are described in the SLL Code for Lighting(8) (2009 edition) and Lighting Guide LG10: Daylighting and window design(43), and therefore are not included here. 38 Lighting Guide 5: Lighting for education 5 Lighting for particular applications 5.1 Classification of teaching and conference spaces 5.2 General performance requirements for learning spaces In the last decade a better understanding of learning and changes in teaching methods, plus the increased demand for sustainable building design, has led to some innovative educational buildings that provide stimulating and adaptable places to learn for children and adults. Some school sites combine school and community use with, for example, an ‘early years’ centre, enhanced sports provision, a public library or health centre. Other recent design developments include the use of innovative glazed facades incorporating sun shading. Educational spaces need to be designed for present and future learning and teaching styles and organisation; a difficult task given that a school may last for over 40 years. But learning spaces should be suitable, safe and secure as well as attractive and inclusive places in which to learn and work. Lighting, both electric and natural, plays a key part in the performance of all these buildings and research suggests that it plays a key part in the learning rates of students. Some of the recent design ideas include: classroom shapes other than rectangular; use of innovative facades including sun shading, glazing and modern construction methods; combined buildings that are suitable for pupils and public inside and outside of school hours (and that may incorporate early years care); public library spaces; health centres, extending sports community use and so on, in some cases creating multi-use ground floors with more specialist restricted use upper floors. Modern learning spaces need to have the flexibility to accommodate different activities and teaching methods. This may be by rearranging furniture or by merging spaces (e.g. for two or three classes to work together or for community use after school hours). Some large spaces may be multi-functional, each activity requiring different lighting (for example a space used for both drama performances and exams). There may be large open-plan spaces where more than one teaching activity, formal or informal, takes place at the same time. Lighting, both electric and natural, plays a key part in making these spaces function well; it can also benefit students and other users with a sensory impairment. Lighting or lighting controls need to be functional in every scenario. As teaching experts advocate new methods of interactive learning, perhaps with multi-disciplinary spaces catering for two or three classes and many teaching staff, we may see so-called flexible learning and teaching spaces, a wider range of spaces, more multi-use of spaces, increased community use (and therefore a wider range of activities), increased inclusion (and therefore more with students and users with sensory impairment). Lighting plays a key part in making these spaces function well. Importantly these spaces recognise the benefits teachers and students can gain in having staff close and from being able to adapt the space for the best learning style and interaction. Each learning and teaching method will create different lighting requirements for the space in which they happen. Table 5.1(44) indicates just some of the lighting measures required for learning spaces. However the designer must not take these in isolation from the other measures such as cylindrical illuminance (see section 3.7) and modelling index (see section 3.8) and requirements for children with special educational needs (SEN) (see section 5.17), and will need to consult actively members of the design team dealing with thermal performance, ventilation and acoustics in particular. The illuminance uniformity in the task area should not be less than the minimum uniformity values provided in Table 5.2. The illuminance uniformity in the immediate surrounding and in the background area should not be less than 0.4. Daylighting performance for educational buildings is given in Table 5.3. Lighting for particular applications 39 Table 5.1 Lighting performance for educational premises (reproduced from BS EN 12464-1(31) Tables 5.29, 5.35 and 5.36 by permission of the British Standards Institution) Ref. Type of interior, task or activity Em (lx) UGRL Uo Ra Remarks 1 Nursery school, play school: 1.1 Play room 300 19 0.4 80 1.2 Nursery 300 19 0.4 80 1.3 Handicraft room 300 19 0.6 80 300 19 0.6 80 2 Educational buildings: 2.1 Classrooms, tutorial rooms Lighting should be dimmable General: maintained illuminances on the wall should be 50% of the task area illuminance or Ev = 100 lux, and on the ceiling should be a minimum of 30% of the task illuminance or Eh = 50 lux 2.2 Classroom for evening classes and adults education 500 19 0.6 80 Lighting should be dimmable. The designer should consider very carefully whether an elevated illuminance of 500 lux will offer any benefit or simply be misused when the space is used to teach children General: illuminances on the wall should be 50% of the task area illuminance or Evmin = 100 lux and on the ceiling should be 30% of the task illuminance or Ehmin = 50 lux 2.3 Auditorium, lecture halls 500 19 0.6 80 Lighting should be dimmable to suit various audio visual needs 2.4. Blackboards (see remarks for other colours) 500 19 0.7 80 White and green boards should require less light due to higher reflectance, a luminance of 80–160 cd/m2 is recommended Prevent veiling reflections The teacher should be illuminated with suitable vertical illuminance Where used for projection the surface finish should be carefully considered and lighting should be dimmable 2.5 Demonstration table 500 19 0.7 80 2.6 Art rooms 500 19 0.6 80 2.7 Art rooms in art schools 750 19 0.7 90 2.8 Technical drawing rooms 750 16 0.7 80 2.9 Practical rooms and laboratories 500 19 0.6 80 2.10 Handicraft rooms 500 19 0.6 80 2.11 Teaching workshop 500 19 0.6 80 2.12 Music practice rooms 300 19 0.6 80 2.13 Information technology (IT) rooms 300 19 0.6 80 2.14 Language laboratory 300 19 0.6 80 2.15 Preparation rooms and workshops 500 22 0.6 80 2.16 Entrance halls 200 22 0.4 80 2.17 Circulation areas, corridors 100 25 0.4 80 2.18 Stairs 150 25 0.4 80 2.19 Student common rooms and assembly halls 200 22 0.4 80 2.20 Staff room/office 300 19 0.6 80 2.21 Library: bookshelves 200 19 0.6 80 2.22 Library: reading areas 500 19 0.6 80 2.23 Stock rooms for teaching materials 100 25 0.4 80 In lecture halls 750 lx Colour temperature ≥5000 K For specific industry based teaching in further or higher education additional advice may be sought from Lighting Guide LG1: Lighting for Industry(51) Artificial and natural lighting should comply with the guidance in Lighting Guide LG7: Office lighting(39) 200 lux on the vertical face of the bookshelf Table continues 40 Lighting Guide 5: Lighting for education Table 5.1 Lighting performance for educational premises (continued) Ref. Type of interior, task or activity Em (lx) UGRL Uo Ra Remarks Sports lighting performance requirements are detailed in BS EN 12193(32) 2 Educational buildings (continued): 2.24 Sports halls, gymnasiums, swimming pools 2.25 School/college canteens 2.26 Kitchen 300 22 0.6 80 200 500 22 22 0.4 0.6 80 80 3 Conference and meeting rooms: 3.5 Conference and meeting rooms 500 19 0.6 80 These may be classed as high risk tasks for emergency lighting Lighting should be dimmable Table 5.2 Relationship of illuminances of immediate surrounding and background areas to task area (adapted from BS EN 12464-1(31) Table 1 by permission of the British Standards Institution) Illuminance on the task area (lx) Illuminance on immediate surrounding areas (lx) Illuminance on background area (lx) ≥750 500 300 200 150 ≤100 500 300 200 Etask Etask Etask 100 100 100 100 100 Etask Table 5.3 Daylighting performance for educational premises Ref Type of interior Daylight factor (%) Average Minimum point 1 Entrance, Reception 10% 4% 2 Atrium 5–10% 2–4% 3 5% 2% 4 Classrooms, including standard, science, food preparation, craft and art rooms SEN classroom 5% 2% 5 Lecture theatres 2–4% 1% 6 Libraries 2–5% 1–2% 7 Sports halls 5% 2% 8 Dining hall 4–5% 1–2% 9 Offices and meeting rooms 5% 2% Remarks This area serves as a transition from the external environment to the internal environment and needs to provide a lighting level to allow the eye to adapt. Glare for any permanent staff working in this area must be considered. Classrooms often look into the atria space and as such borrow daylight from the space and use the brightness of the space as part of the view. Glare into classrooms needs to be considered carefully as does privacy. Daylight should be the predominant lighting component for the majority of the day. Due to the nature of SEN children the daylight and view should be considered together, some rooms with daylight and views and some rooms with good daylight but more limited visual stimulation will be required to suit the different needs of the children. Daylight keeps people alert and therefore it is essential for all learning environments. However in a lecture theatre the daylight must be able to be eliminated to suit the presentation style and projection equipment. Delivering good levels of daylight between the shelves is typically difficult; however the reading areas should have good levels of daylight. As sports halls are often used for exams then providing good levels of daylight to keep the students alert is essential. Control of the daylight will be required for some sports. Lighting for particular applications 5.3 Lecture theatres and lecture rooms 41 The choice between a lecture room (basically flat, see Figure 5.1) and a lecture theatre (raked, see Figure 5.2) will be determined by the audience size. If it is less than 60 there is little point in providing a raked room. If it is more than 80, raked seating is essential, unless the lecturer is raised on a stage or podium. Fig. 5.1 Flat seating arrangement using hidden light sources indirectly to audience, speaker and the walls (photograph courtesy of NDYLight) Fig. 5.2 Raked seating arrangements with differing approaches to audience and presenter stage area lighting; harsh downlight is softened by vertical elements to the side of the stage (photograph NDYLight) 5.3.1 Lighting and visual needs The lighting in a lecture space must reveal the lecturer to the audience and the audience to the lecturer, and also provide for the other visual tasks involved. These include observing demonstrations, reading what is projected onto the screen, or written on the whiteboard, and the taking of notes. Note-taking has to continue when presentations, video or interactive presentations are used. The lighting in a lecture theatre may conveniently be thought of in terms of that for the audience area and that for the presentation area (see Figure 5.2) though this distinction should not be pushed too far; in many lecture theatres, especially smaller ones, the audience area lighting may well function as ambient lighting and provide much of the illumination in the demonstration area as well. 5.3.2 Lecture theatres These are rooms used for the delivery of formal lectures with raked floors and/or balconies or galleries and with fixed seating. 5.3.2.1 Lighting the audience For the audience area the basic choice is between incandescent, LED and fluorescent lighting. Incandescent light is readily controllable in intensity and direction, is often preferred on aesthetic grounds, and may have some benefits in terms of reduced noise. However, even in its best form it is inefficient in terms of energy usage and the heat that it introduces to the building has to be removed. Modern fluorescent lamps, with good colour rendering, are very much more energy efficient and offer considerable benefits in lamp life, and in those theatres which are heavily used, e.g. in schools and colleges, maintenance and energy economics will usually dictate their use. LEDs offer the designer a further choice, though at the time of writing the technology is just entering the mainstream. Issues of colour rendering, light source life and efficacy are still inconsistent across the industry and the designer would do well to consider these issues carefully before specifying LED luminaires; further advice can be found in Guidelines for specification of LED lighting products(45), issued in August 2009. That said, there appear to be many manufacturers offering good quality luminaires containing efficient LED sources and this technology may offer a long life and fully controllable solution for many lecture theatres, especially where access may be difficult. Other types of discharge lamp, such as high pressure sodium, are not suitable due to poor colour rendering, run-up and re-strike times, and flicker. 42 Lighting Guide 5: Lighting for education Metal halide sources may offer some benefits when dimming technology is fully developed, but at present still cause problems with re-strike times and lamp life. Whatever type of lighting is used, the luminaires must be positioned so as not to create glare problems either for the audience or the speaker, as shown in Figure 5.3. This means that, unless the ceiling is exceptionally high, the luminaires must be mounted on, or recessed into the ceiling. Figure 5.4 shows that when the ceiling is not a flat horizontal surface, it may be possible to make use of its shape to conceal the luminaires from the direct sight line of the audience provided that they do not become bad glare sources for the lecturer. The UGR at any point of the audience area should not exceed 19. Fig. 5.3 Luminaires at positions such as A and B are close to eye level for back row students and may cause significant discomfort glare Fig. 5.4 Luminaires hidden behind elements of the structure or acoustic treatment will cause less glare to students but may still be a problem to the lecturer A B When incandescent, LED or compact discharge/fluorescent lighting is used, high direct ratio luminaires with a tight beam angle should be avoided. Although these are often used in theatres and concert halls, they produce poor modelling of peoples’ faces, with the result that the lecturer cannot clearly see or interpret the reactions of the audience. When surface mounted luminaires are used, they should not produce a harsh distracting halo on the ceiling around them that may itself become a glare source. Care should also be taken with luminaires mounted close to the walls to avoid high luminance on the wall, which can also be distracting. When fluorescent lighting is used, ceiling mounted luminaires of the recessed or semi-recessed type may be used. The latter are preferred to prevent the ceiling appearing too dark. In order to avoid note-taking shadows, the luminaires should be mounted with their long axis parallel to the rows of seats (see Figure 5.5), though it is not usually practicable to correlate the rows of luminaires with the rows of seats beneath. The average illuminance on the working plane (usually 0.85 m above the floor) should be 500 lux, but should also be controllable to suit the needs of the audience. Bare fluorescent tubes should not be used if they are visible either to the audience or lecturer. If the ceiling is white or of a light colour and is of uncluttered design, pure indirect lighting may be used for the audience area, but the energy costs will be higher. This method produces illumination that is quite free of glare, but is felt by some to produce a soporific effect. In practice the light sources usually have to be concealed in the cornices. Traditional uplighters may cause obstruction to some of the sight lines and psychologically provide a barrier between the lecturer and some parts of the audience and perhaps are best avoided. Lighting for particular applications Fig. 5.5 43 Luminaires orientated with their long axis parallel to the seating with separate lighting oriented perpendicular to the boards to light the demonstration area and speaker (photograph courtesy of Thorn Lighting) Lamps used should be of colour rendering greater than Ra = 80. The common ‘white’ and ‘warm white’ fluorescent tubes do not meet this requirement and under the provisions of the Energy-using Products Directive will be withdrawn from sale in coming years. An efficient solution is offered by triphosphor T26 or T16 fluorescent lamps. 5.3.2.2 Lighting the demonstration area In small lecture theatres and any theatres that have an unbroken horizontal ceiling, it is a good plan to carry the general lighting forward to serve the whole area and to add additional lighting as described below. This technique does not emphasise any division between the demonstration and audience areas. In very large lecture theatres (see Figure 5.5), and especially those where the ceiling height is reduced at the front, it is advisable to use quite separate lighting systems for the demonstration and audience areas. The demonstration area lighting needs to be carefully directionally controlled. In small lecture theatres luminaires designed for display use should be used. In larger theatres luminaires designed for stage lighting may be more appropriate. The lamps or luminaires should preferably be concealed from the view of the audience. They may otherwise become very obtrusive and give the room a theatrical look. The position and angling of luminaires in the demonstration area is critical. The best alignment for ceiling mounted luminaires is about 45° to the vertical, and between 30° and 45° to the side. If the angle is near the vertical it may produce grotesque shadows on the lecturer’s face, and if it is near the horizontal the lecturer may be dazzled when attempting to address the audience. Similar considerations apply to luminaires mounted on the side walls. Illuminance at table-top height in the demonstration area should be higher, but not more than double those of the audience area. The recommended values are 500–750 lux for the demonstration area and 300–500 lux for the audience area. Lighting provided specifically for the lecturer to read notes while the theatre is darkened for the purpose of computer projection needs careful attention. The problems are that light direct from the source, or light reflected from the notes and desk, may fall on the screen and spoil the appearance of the projection; it takes very little stray light to affect the projected image. The best solution is to incorporate carefully shielded low power light sources in the lectern itself. The illuminance of the notes should be kept as low as possible, 5–15 lux is sufficient. 44 Lighting Guide 5: Lighting for education In most modern lecture theatres the speaker will primarily use a screen or laptop computer, which is self-lit. In these cases the lectern is almost always without an in-built light, or it may be desirable to switch off the lectern lighting altogether. However, to enable all members of the audience to see the lecturer clearly and be able to discern body language and facial expression, including importantly lip reading for those with hearing impediment, there should be sufficient light on the speaker. This can be achieved either with theatre lighting positioned specifically for the task or by additional linear fluorescent lamps or LEDs simply controlled with a dimmer and mounted within the lectern itself. 5.3.2.3 Sight lines Fig. 5.6 The first requirements of a lecture space are that the audience shall see the lecturer easily and that the lecturer shall see the audience easily. Lecture theatres should not be raked too steeply, see Figure 5.6, as this makes the audience feel uncomfortable and can present problems with image projection. The seating layout is important in raked theatres; if straight rows are used the seats at the ends of the front rows offer a very oblique view. Steeply raked lecture theatres can cause problems with projection and make the audience feel uncomfortable There can be little social contact between different members of the audience, and this is disadvantageous from two points of view: (a) it discourages audience participation and (b) it does not facilitate or encourage discussion and questions after a lecture. For these reasons, the curved rows in Figure 5.7 are to be preferred using a fan shaped plan. This arrangement has the disadvantage that if the room is only two-thirds filled all the audience may be in the back half. Figure 5.8 shows a good design compromise with at least half the length of the side walls parallel so as to limit the length of rows at the back. It is most important in any lecture theatre that there is an adequate space in the demonstration area. In practical terms, this means that there should be at least 3 m between the front wall and the feet of people sitting in the front row. This not only allows an adequate area for demonstration purposes and improves the sight lines, but it gives the theatre a spacious quality, see Figure 5.9. If the front wall is too close to the seats the theatre will look cramped, and have a claustrophobic atmosphere. Demonstration area Demonstration area Fig. 5.7 Fan shaped lecture theatre Fig. 5.8 Modified fan shape with more practical straight rows Lighting for particular applications Fig. 5.9 Layout of the theatre creates a feeling of space (photograph courtesy of NDYLight) 5.3.3 Lecture rooms Lecture area Fig. 5.10 ‘X’ marks possible positions for spotlights in a small lecture room on ceiling or side walls 5.3.3.1 Lines of sight and glare Fig. 5.11 A good lecture room layout 45 These are rooms used mainly for the delivery of formal lectures, generally with level floors and often with fixed seating. This category includes rooms with a raised step or podium for the lecturer, and rooms with one or two raised steps towards the rear of the seating. Because of the smaller dimensions, the audience area lighting in lecture rooms will usually serve the demonstration area as well. It is desirable that the lecturer and the immediate surroundings are a little brighter than the rest of the room and this can usually be effected by the use of a few spot type luminaires directed towards the lecturer. However they must be carefully positioned so as to avoid glare to the lecturer. Usually this will mean that they have to be mounted either on the side walls, or on the ceiling adjacent to the side walls; the positions are shown in Figure 5.10 If a fixed lecture bench is installed luminaires should not be mounted directly over it for demonstration purposes. In this position they may cause specular reflections from demonstration equipment which makes it very difficult to see what is going on. Lighting from the side is equally effective and spotlights may be mounted in the same position as those to light the lecturer. The general lighting should be arranged to produce an illuminance above 500 lux at desk level in the audience area. It should be reasonably uniform and if fixed seats are installed right up to the walls the illuminance at desk level at the wall should not be below 70% of the average illuminance. If there is an aisle next to the wall this does not apply. The lamps used should be of better than Ra = 80. In order that members of the audience may take notes whilst projected images are shown, a much lower level of general illuminance in the range of 15–30 lux is needed, achieved by dimming. Lecture rooms are usually rectangular in plan and experience shows that the best seating plan is that with the lecturing area at one end of the room with rows of seating parallel to the short dimension as shown in Figure 5.11. Figures 5.12 to 5.14 show sightlines for typical layouts of lecture rooms. In the case of a lecture room that is basically flat the sight lines may be greatly improved by raising the rear half of the audience on one or two steps and raising the lecturer on a step. Lecture rooms in general have a much lower ceiling than lecture theatres, and in the absence of raked seating the sightlines become critical. The lighting equipment should be arranged so that the luminaires do not cause serious glare to the occupants of the rear row of seats, as shown in Figure 5.15, or to the lecturer as shown in Figure 5.16. When fluorescent lighting is used the luminaires should be of the recessed or semi-recessed types; if this is not possible they may be provided with the glare shields illustrated in Figure 5.16. It may sometimes be possible to use ceiling ribs as glare shields. On no account should bare fluorescent tubes be visible to the audience. The UGR at any seat should be less than 19. It should also be remembered that avoiding glare for the audience may create glare for the lecturer; in particular, the lecturer must not be subjected to disability glare. 46 Lighting Guide 5: Lighting for education Fig. 5.12 Sight lines in a lecture theatre with a flat floor Fig. 5.13 Sight lines may be improved by raising the lecturer on a step Fig. 5.14 Sight lines can be improved further by raising the rear seats Fig. 5.15 Back row glare in a lecture room; luminaires at A and B are very close to the students’ sight lines, and will cause intolerable glare Fig. 5.16 Glare shields or louvres will overcome the problem of back row glare 5.3.3.2 Provision of daylight A B Cut off angle Almost all presentations will require controlled lighting. For that reason, lecture theatres and rooms are often built with little or no access to daylight. Equally, people do not like to feel shut in, especially when lectures are given during daylight hours, and there are many who have a preference for working under natural light. In rooms the size of lecture theatres, the provision of natural light in sufficient quantities for working purposes requires very large areas of glazing. This is not only expensive from the point of view of heat loss, but makes it difficult to achieve a good blackout. Furthermore, unless the windows are north facing, or sufficiently shaded externally, there may be severe problems with solar heat gain in summer. Lighting for particular applications 47 The only way in which an adequate blackout can be achieved in such rooms is by the use of completely opaque blinds, running in grooves at the sides to provide a light trap. Curtains or venetian blinds are not adequate. Blinds should be of light colour on the inside, so as not to present a large black area when down, and should be motor operated due to the area of window involved and the need for frequent opening and closing. Blinds should also be of a light colour on the outside, to prevent excessive solar heat gain. It may be desirable to provide occupants a view of the outside world in order to provide some visual escape rather than to provide lighting. The lecture theatre shown in Figure 5.5 illustrates that very much smaller areas of window can be used, and the problems associated with them are consequently much reduced. However, the need for a perfect blackout remains and groove-enclosed blinds are needed, though in such cases they may be hand-operated. Windows should not be provided in either the front wall or back wall of a lecture theatre or lecture room. The former would produce intolerable glare to the audience and the latter would cause serious veiling reflections on the board. Skylights should be provided with care; they require elaborate blackout arrangements and are very difficult to keep clean. From the point of view of presentation, it may be better for lecture theatres and rooms to be windowless as this provides less problem controlling glare from sunlight. Since the occupants rarely have to remain in them for more than an hour without a break, problems of claustrophobia do not arise, although they may well do so in small teaching rooms. Many institutions have made extensive use of windowless lecture rooms with considerable success. However windowless lecture theatres and rooms require forced ventilation that may lead to noise problems, but it should be noted that large theatres with extensive glazing also require forced ventilation. It is preferable, however, that all teaching spaces should allow daylight so the user can retain a link to the time of day and weather. A lack of daylight may adversely affect occupants’ circadian rhythms and hormone production (though further research is needed), as well as increase the electrical load in the space due to electric lighting being used when daylight could be utilised. As with skylights careful and complete blackout blinds should be provided if daylight is permitted. Light traps (e.g. two sets of doors or other effective means for excluding daylight) should be provided in all lecture theatres and rooms to prevent unwanted light getting in when the theatre is darkened for presentation. This is particularly so in the case of entrances at the rear of the theatre, which when opened suddenly by a latecomer may allow full daylight to fall on the projection screen. These light traps should also function as sound traps. Such doors should not be provided with windows, unless essential for fire safety, if it is not possible to provide proper light traps. If automatic door closers are installed they should be of a design that allows the door to be closed quickly and silently. 5.3.3.3 What the audience sees The audience should be able to concentrate on the lecturer, screen or board, and the decoration, furnishings and equipment should not be competing with the lecturer for attention. The lecturer’s desk, board and screen must be so placed that they do not obstruct the view of the audience. If a computer projector is used, great care must be taken to see that it does not obstruct either the audience’s view of the lecturer or the lecturer’s view of the audience. Care should be taken to avoid intense glare to the lecturer from projectors that may lead to eye complaints later in life. Specular reflections of light sources and windows on the board, sounding boards and glazed portraits should be avoided. Also avoid backgrounds with disturbing patterns, and backgrounds full of fussy details. The audience’s view of the front of the lecture room or lecture theatre should be clear and free from visual clutter; in particular the front wall should be kept clear of pipework, 48 Lighting Guide 5: Lighting for education conduits, and ventilation trunking. In some cases the luminaires themselves may provide visual clutter and should be carefully chosen and positioned. 5.3.3.4 Decoration and furnishings It is the decoration and furnishings within a lecture theatre or room which, in combination with the lighting determine its appearance and contribute to that indefinable quality that is usually called ‘atmosphere’ or ‘character’. The choice of colours and finishes should be made at an early stage in conjunction with other decorative finishes and furniture. The use of darker colours on the side walls of theatres will help concentration. The surfaces of the side walls should have some degree of texture, such as that provided by timber panelling, textile covered panels, slightly textured plastics or recessed-pointing brickwork. Shuttered concrete is not recommended as it soon gets dirty and is not easy to clean. In a lecture room without fixed seating it may not be desirable to treat the side walls as a feature, but darker-toned colour can be used behind the lecturer. Ceilings should be white. Care should be taken to provide some light either directly or indirectly onto the ceiling. Walls should be of a different colour from the ceiling in order to define the boundaries of the interior space and avoid a feeling of claustrophobia. Matt or semi-matt surfaces are desirable as high gloss areas will cause specular reflection and be distracting. Colour contrasts of a modest nature are desirable since a bland interior scheme, combined with dim lighting, tends to cause drowsiness amongst the audience. These contrasts can usually be obtained by careful choice of the colours of the seating as this presents a large area of colour; mid-toned colours are best in a definite but not too strong hue. The flooring colour does not contribute a great deal to the scheme in a lecture theatre. Whether carpet or hard finish a neutral colour is the most practical choice. 5.3.3.5 Switches, dimmers and controls In any lecture space the lighting controls need to be as simple and comprehensible as possible — lecturers should be more concerned with their subject matter than light switches. In the main, the only lighting settings needed in a lecture theatre are: (a) full lighting, to about 500 lux, for adult use (b) reduced lighting, to be considered the primary setting, to about 300 lux for child and young adult use (c) audience area lighting reduced to a low level and demonstration area lighting off for the purpose of image/video projection, but allowing enough light for the audience to take notes (d) all lighting off for the projection of specific content, and for the purposes of visual demonstrations. Abrupt changes in the lighting are disturbing to the audience, and lighting controls should enable gradual changes to be made in preference to plain switches. A good system is that in which the only controls are four pushbuttons, corresponding to the states above. On pushing the appropriate buttons the lighting assumes the appropriate scene. In such installations the time taken to go from full-on (a) to full-off (d) should not be too long; about four seconds is sufficient. A lighting scene selection panel should be situated conveniently for the lecturer and any support staff, with some form of override at each entrance, suited to entry and exit from the space. Whilst it may be attractive to include absence detection to ensure lighting is switched off when the theatre is empty, the design should take care to ensure any sensor used covers the space sufficiently and with a suitable level of sensitivity. All lecture theatres should be arranged for one-person operation, as circumstances inevitably arise where a lecturer has to speak without the services of an attendant. Lighting for particular applications 49 5.3.3.6 Audio-visual considerations As most modern lecture spaces use computer based projection, the theatre should be laid out with sufficient consideration for the use of the projector and accompanying laptop computer. Inadvertent spill light onto the screen should be avoided especially where older, less powerful projectors are in use. Similarly the lecturer should have sufficient illuminance onto the computer to enable keyboard detail to be discerned and to ensure that minimal adaption change is required between the view of the audience and the screen in all scenes. 5.3.3.7 Access and movement Access doors should not be in the front wall of the lecture theatre or room, where they add to the visual clutter, and distract attention. The same applies to the doors of preparations rooms, lecturers’ rooms and stores. All lecture theatres and lecture rooms sooner or later become used for purposes other than that to which they were originally dedicated. Consequently all items in the demonstration area should be movable and removable. Hence the lighting and control of the lighting to these spaces should be easy to re-aim or re-commission. Experience shows that when demonstrations are mounted, services other than electricity are rarely, if ever, called for and there is little point in installing a fixed bench simply to provide terminal points for water, gas, and other outlets. If such services are needed, they are much better installed in wall cupboards where they can be kept both locked and out of sight until they are wanted. When members of the public may be present, all exits to a lecture theatre/room be marked with permanently illuminated exit signs, and all exit routes must have sufficient emergency lighting. Light from such signs falling on a projection screen can ruin the effect of presentations or demonstrations, they should therefore be aligned so as to be visible to the audience, but not to throw light onto the projection screen. Additional lighting at low level may also be beneficial to aid access and egress during presentations. The glare from such luminaires must be carefully controlled to avoid presenting problems to the lecturer. 5.3.3.8 Use for theatrical presentations Possibly because they resemble legitimate theatres in shape, and because they often constitute the largest auditorium in a particular institution, lecture theatres are sometimes chosen as the venue for theatrical presentations. Such presentations can be greatly helped by the provision of further special facilities for lighting such as theatre lighting supports and controls. The following paragraphs describe the additional provisions that should be made if the room is to be easily adaptable for these purposes. It is stressed that these are additional, and it is necessary that the requirements of the previous sections are met first. When such rooms are used for theatrical purposes, they will almost certainly be subject to additional legislation such as additional requirements for emergency lighting; the designer should consult local authorities on such matters. Relevant publications and general advice are available from the Association of British Theatre Technicians (www.abtt.org.uk), and detailed advice and planning from members of the Society of Theatre Consultants (www.theatreconsultant.co.uk). The additional provisions needed in the audience area are: — The lighting must be dimmable smoothly and without flicker to 1% of its maximum level. — Exit signs as required by BS EN 5266(46). Luminance and spill light should be restricted to avoid glare and interference with stage lighting effects. — Light and sound traps on all entrance doors (or at least those used by latecomers and for access to toilets). Lighting within a light trap should be primarily from the dimmed house lighting 50 Lighting Guide 5: Lighting for education system, but a low power light from the external system may also be needed, and a maintained emergency light. — Provision for theatrical lighting installation using professional spotlights rigged on standard 48 mm diameter scaffold tube and connected using industry standard theatre plugs and sockets. Essential locations are above the seating parallel to the front curtain at approximately 45° elevation from 1.8 m above the front of the stage. Steeper and shallower positions will also be useful as will positions on the side walls at 45° in plan to centre stage. Safe access for adjustment and relamping must be anticipated. Each socket should be wired suitably for the chosen power and dimming control systems. Additional provisions needed in the stage area: — At least 2 m wing space either side of the stage — Adequate headroom to allow overhead stage lighting to be hidden from sight, i.e. at least 1 m from the upper sightline — Access to both sides of the stage, not through the auditorium, with sound and light traps and silent closing doors — Access to dressing rooms — Access to the auditorium, not via the stage — Access for scenery from delivery vans — Provision for front curtain with winch mechanism — Provision for side and rear masking curtains to hide performers awaiting entrance — Over-stage rigging for hanging scenery and top masking. This can be basic exposed rolled steel joists (RSJs) and scaffold pipes, with manual or motorised winches, or fully counterweighted flying systems requiring two to three times the visible stage height. — Work-lights at both sides, rear and over main stage for setting and changing scenery with local switching and master switch at stage manager position. Fluorescent battens with protective trough reflectors and wire guards are usually used for worklights. Instant operation is essential. Dim, shielded lights are also required for used during performance but these can be rigged as required if full theatrical standards are not specified. — Provision for theatrical lighting installation using professional spotlights rigged on standard 48 mm diameter scaffold tube and connected using theatre lighting industry standard plugs and sockets. Essential locations are above the stage parallel to the front curtain immediately behind the curtain line, 1 m in front of rear wall and between at 1 m to 1.5 m intervals. Each socket should be wired suitably for the chosen power and dimming control systems. Control of the lighting and sound systems may be effected from the projection room or separate lighting and sound control rooms. The lighting in those rooms should be similar to that for a projection room and the rooms should be sound-proofed. A good view of the stage is essential in each case. Loudspeaker reproduction of platform sound is essential, and if a headset communication system is used appropriate wiring should be provided. All systems should be arranged so that they can be operated by a single person if necessary. The control rooms should be of sufficient size to cater for dimmer circuits that may be involved. The sound control room should have connections to tie-lines for microphones and loudspeakers both on stage and in Lighting for particular applications 51 the audience area, and also be connected to the headset communication system, the dressing room sound system and the audience hearing aid induction loop system if one is installed. 5.4 Teaching rooms These are rooms used mainly for class teaching purposes, with flat floors and little fixed furniture except, possibly, cupboards, whiteboards and projection screens. Such rooms will usually have a seating capacity of around 30, but may extend in modern educational buildings for multiple classes with up to 90 occupants. 5.4.1 Lighting and visual needs Lighting for students with sight problems need careful design and suitable aids to reading will need to be considered. Bear in mind that for some impairments higher illuminance, in itself, may not be the solution. More detail is given in section 5.17. 5.4.2 Rooms intended for presentation The designer should still consider the phrase ‘Light the teacher, light the board, light the desk’ but must above all light the face, at whatever height and whatever location in the class. Teaching is a mobile interactive activity even in classrooms designed around formal instruction, and the student should be able to clearly see the teacher’s face, and vice versa, from any position. Well applied measures such as modelling index (section 3.8) and mean cylindrical illuminance (section 3.7) as well as more traditional horizontal task illuminance should be considered throughout the class and at appropriate facial heights. 5.4.3 Rooms intended for interactive learning In learning spaces where there is intended to be a high proportion of use of interactive whiteboards or display screens with touch sensitive surfaces, the designer needs to consider carefully the capabilities of this equipment. Where it is unclear what quality of equipment is to be provided, the designer should assume that equipment will be relatively new and capable of good performance. This is acceptable due to the high rate of change in the technology available for display screens and the slower rate of update of lighting in most buildings. In cases of fully interactive whiteboards, where lit by close offset front projection, it is likely that the screen can cope with significant luminance and lighting, except perhaps display spotlights, should not be considered a concern. For self-lit interactive displays such as plasma or LCD monitors with a touch sensitive front surface, the designer may have to consider limiting the luminaire or daylight luminance to as low as 200 cd/m2. In most cases, based on the use for self-lit screens, the designer should apply luminance limits from BS EN ISO 9241-307(47). Generally, as interactive screens will use positive polarity software, the application of Case A, see section 5.10.1 (Table 5.4), is sensible. Where possible, the specifiers of projection equipment should consider the health and well-being of the presenter or teacher as the glare from poorly placed projectors can cause considerable discomfort, and perhaps long-term eye problems to those using them. Certainly the projector can affect the presenter’s ability to interact with an audience and the layout of any teaching space should give a lecturer room to present without standing in the way of the screen. 5.4.4 Rooms used for practical work These are rooms used regularly for class teaching purposes, without large permanent pieces of apparatus set up. Such rooms will usually have a seating capacity of about 30. This category will include many teaching laboratories. 5.5 Large conference rooms These are rooms used mainly for conferences and meetings at which people may address the audience from almost any point in the room. Such rooms will usually have a capacity of about 60–120. 5.5.1 Basic lighting and visual needs The basic visual needs in a large conference room are that all members of the audience can see the chairman and central officers clearly, and that all persons present should be able to see each other reasonably well in order that a proper dialogue may take place. Many presentations in conference rooms, e.g. the 52 Lighting Guide 5: Lighting for education reading of scientific papers, are essentially formal lectures, and the lighting needs are similar to those of lecture theatres. However conference rooms are also often used as cinemas or theatres and the lighting must be capable of meeting those purposes also. Specifically the lighting must provide adequate illumination for reading or taking notes at any point, good but not excessive modelling and good colour rendering. It must also be flexible and controllable from a single point, must be absolutely silent and produce no thermal discomfort. Careful co-ordination of the lighting design with the interior decoration and with the heating and ventilating system is essential. Absolute blackout facilities will be needed. Large conference rooms have a good deal in common with large lecture theatres, and much of the information in the previous section applies. Conference rooms usually have a clearly defined presentation area, corresponding to the demonstration area of a lecture theatre, and a clearly defined audience area. But the activities in a conference room differ from those in a lecture theatre in these ways: (a) The audience may be present for long periods, often on several successive days. (b) The proceedings although of a formal nature involve interaction between members of the audience and they must be able to see each other clearly. (c) Conference participants must be able to move easily between the demonstration area and the audience area. (d) Simultaneous interpretation facilities may be required. Item (a) above requires that participants should be able to move in and out of the room whilst proceedings are in progress with the minimum of disturbance and the seating should be arranged accordingly, with a greater ratio of gangway space to seating space than is the case in lecture theatres. It is important that participants can both get in and out without disturbing the projector beam if one is in use. In the UK it has always been the custom that those who contribute to a discussion should do so from their seats, but in many countries this is not so. A person wishing to speak must seek the chairman’s approval and then get up from his seat and go to a central podium to speak. The points made in the previous sections relating to the layout of the seating apply equally here. 5.5.2 Lighting systems and controls The lighting requirements of the demonstration area of a large conference room will be similar to those of a lecture theatre and all luminaires should be controllable. Large conference rooms may be used for theatrical performances or entertainment, consequently provision should be made for easily rigging additional lighting equipment. The particular requirement is that appropriate wiring be provided in the form of numerous circuits terminating in socket outlets at the points where additional spotlights are likely to be wanted. These circuits may be controlled from a stage lighting control system operated local to the stage, or from the rear of the room. If it is known that a large conference room will be used for theatrical presentations further special facilities may be advisable. These are described in section 10.3. The lighting of the audience area and the appearance of the whole are crucial in a conference room. The audience must not only be able to see each other clearly, but should not appear grotesque. For that reason downlighters are not recommended as they produce shadows under the eyes, nose and chin which are unacceptable, see Figure 3.7(a). If the ceiling is plain white, then recessed or cornice lighting may be used, provided that there is sufficient direct lighting in the demonstration area to provide a modest degree of ‘sparkle’. If this is not the case, it is worthwhile introducing a few small luminaires for this purpose. The Lighting for particular applications 53 furnishing and decoration should not be too dark, as light reflected from the floor and furniture will significantly improve the modelling of participants' faces. The points made about visual clutter in section 5.3.3.3 apply equally to conference rooms. 5.5.3 Simultaneous interpretation booths Strict specifications are laid down for the lighting of interpretation booths, see ISO 2603(48). Care must be taken that light from them does not cause a nuisance to the audience or speaker, glare or spill onto the projection screen. 5.6 Committee and meetings rooms These are rooms used for meetings capable of seating up to roughly 30 persons. 5.6.1 Visual and lighting needs The basic functions of the lighting, be it daylight or electric are: — to enable the committee members to see each other clearly and without glare — to enable members to read their papers and make notes — to enable committee members to see wall mounted displays. It should be remembered that committees sometimes have to work under some stress, especially when unpleasant or unpopular decisions have to be made. The luminaires should be unobtrusive, and glare kept to a minimum. 5.6.2 Daylight Committee rooms should always have some natural lighting; windowless rooms are unacceptable for committee purposes. The essential problem of natural lighting in a side-lit committee room lies in the fact that occupants on different sides of a table are likely to be exposed to different forms of inconvenience. Those facing a window may suffer glare, and see their colleagues opposite with features in shadow silhouetted against a bright sky. Those with their backs to a window may cast a shadow on their own papers. One possible approach is to ensure that the chairman faces the window and can control both the blinds and the electric lighting. This arrangement ensures that the chairman’s face is clearly revealed, that there is no visual discomfort, and that the faces of other participants can be seen comfortably. If this can be achieved, it is unlikely that others will have difficulty in seeing one or another. Whiteboards and flipcharts should not be placed next to a window since disability glare will make them harder to read, even when discomfort glare is acceptable. They should also not be placed where they may reflect an image of the window. The prescription above, with the chairman facing the window, also deals with these problems. Daylight quantity may need to be strictly limited for computer-projected presentations and video conferencing. In the case of the latter the designer must consider carefully the camera position(s), the modelling of the facial features and the contrast between face and background in both colour and luminance terms 5.6.3 Electric lighting The geometry of lighting should correspond to the geometry of the conference table, defining it as the focus of activity within the room. This does not necessarily mean that the table should be the brightest surface; downlights are particularly unsuitable as they cast harsh shadows, generate shiny reflections in a polished table-top and tend to leave walls and ceilings in relative darkness. The illuminance on the table should be about 500 lux, and the UGR at any point of the room should be below 19. The light distribution should produce a modelling index within the limits recommended in the BS EN 12464-1(44), with suitable cylindrical illuminance at all positions around the meeting table and presentation space. Supplementary display lighting will be required for wall-mounted displays etc. This is governed by the same geometrical constraints as whiteboard lighting. The display lighting should be dimmable. Careful design of a committee room 54 Lighting Guide 5: Lighting for education will remove the need for portable projection screens, and for ad-hoc arrangements of computer projectors and blackout facilities. 5.6.4 Surface finishes The background luminance should ideally be slightly lower than the luminance of the occupants’ faces. A few small pictures or ornaments can do much to improve a committee room, but large and complicated features may distract the attention or affect the exposure of video conference equipment and should be avoided. 5.7 Multi-purpose rooms These are rooms used for a wide variety of purposes, such as school halls, some sports halls, assembly rooms, function rooms, community and church halls. 5.7.1 Lighting needs The lighting designer should be involved with the architect and interior designer from the start of the planning process. In attempting to design a suitable installation for a multi-purpose room the first requirement is for the designer, in consultation with the client, to draw-up a list of the purposes envisaged for the room and an order of priorities of use. The prime lighting needs in terms of illuminance and the controls needed for each separate activity can thus be tabulated and if any common patterns exist they will be evident; thus the lighting can be designed accordingly. However, in many cases no common pattern will emerge and the designer will have to produce a compromise design. Fig. 5.17 Ambient lighting provides for the needs of access, maintenance and some teaching with projector and screen and also with stage lighting for music recital, drama and theatrical shows (photograph courtesy of Thorn Lighting) There are a few basic points, discussed below, that should be considered at the start of the design process. These are the exclusion of daylight, the stage lighting, and accommodating large chandeliers or other lighting supports. The next requirement is for the lighting designer to determine what maximum value of illuminance is required and for how long. This will determine the nature of the main light sources. The designer may also have to consider whether a direct or indirect lighting system is used. Daylight may sometimes be excluded depending on the function of the space. If the multi-purpose room requires lighting that is flexible and controllable to a high degree then daylight may need to be excluded completely. However, given the imperative to utilise minimal energy in lighting all spaces, if windows, roof lights or skylights are to be provided they should be fitted with light-tight blackout blinds of the type described for lecture theatres in section 5.3.3.2. This is particularly so in the case of skylights. If the room has a definable stage area, then the lighting for it should be regarded as stage lighting and designed accordingly. This may include the need for ambient lighting to enable set building and general set-up or cleaning of the stage. Lighting for particular applications Fig. 5.18 55 Sports halls are often design for a multitude of different activities; this may include regimented desk layouts during examination time (photograph courtesy of Thorn Lighting) If large luminaires such as chandeliers are to be used, they should be positioned carefully as they can very easily obstruct both sightlines and the beams of spotlights. Dimming is essential to provide sufficient flexibility in the lit scene. In the case of rooms whose primary use is for sports (see Figure 5.18) the designer may need to consider over-lighting the space for other activities, such as examinations, along with the associated limitations to uniformity, cylindrical illuminance and modelling posed by these different requirements. 5.7.2 General lighting Fig. 5.19 Flexibility in open plan allows the space to be used for any number of tasks; the lighting and controls needs to account for all of these needs and so may be a compromise, in this case perhaps glare. (photograph courtesy of Thorn Lighting) The function of the general lighting in a multi-purpose room is to provide an overall uniform illuminance of acceptable colour rendering that is free from glare, and which may be dimmed. The designer should research and indicate the illuminance needed at working plane height, e.g. 0.85 m above the floor for desk based tasks or floor level for some sports. If no such survey can be made the designer should aim for a value of about 150 lux. If it is known that the room will be used regularly for examinations then the provision should be for 500 lux. The colour rendering should be of R ≥ 80. 56 Lighting Guide 5: Lighting for education With the variety of activities that may take place, sightlines may be anywhere, and it is important to avoid glare. This point is very well met if the general lighting is indirect. If a direct system is to be used the luminaires should preferably be fully recessed. If surface mounted fittings are used they should have opaque or diffusing side surfaces, and in no circumstances should bare lamps be visible. Suspended luminaires should not be used to provide general lighting unless they are suited to the worst case use such as ball sports. Care should be taken in avoiding glare not to overdo it; recessed downlighters in particular give no glare at all but produce both a modelling effect on faces, which is the reverse of what is wanted for a social occasion, and a gloomy atmosphere. The illuminance produced by the general lighting should have a uniformity ratio of a least 0.6 at working plane height, and this may be difficult to achieve with downlighters if the ceiling is low. 5.7.3 Suitable light sources The main lighting will almost certainly be fluorescent. In a few cases high pressure metal halide may be used where less control over illuminance is required. Fluorescent lighting may readily be dimmed but, by the nature of the source, is less flexible. The term fluorescent lighting includes compact source fluorescent lamps that can be used in relatively small luminaires. Fluorescent lamps can be used to advantage in an indirect lighting system, especially where the tubes can be concealed in cornices, coves, or in the structure of a ribbed ceiling. High pressure metal halide lighting has a relatively long warm-up time and is thus of restricted value in multi-purpose rooms. However, for some functions, e.g. exhibitions, it may be useful, especially if used to provide indirect lighting. If used for direct lighting the mounting height should be at least 3.5 m. In those rooms that may be used for sports, especially badminton, care should be taken to see that light sources chosen will not cause flicker or stroboscopic effects; and in most cases HF control gear is essential. Luminaires should be suitably rated for impact resistance with suitable protection of the lamp should it become broken. Lighting Guide LG4: Sports lighting(49) should be consulted for sports applications. 5.7.4 Suspension points and wiring It may be necessary to mount temporary spotlights for many functions and appropriate suspension points should be provided; a space frame ceiling is ideal for this purpose. If the room has a definable stage area then provision should be made for mounting front-of-house spotlights in the shape of wall brackets or spot bars mounted below the ceiling and in smaller rooms that may suffice for all spotlight mounting. Since wall lighting is often needed for exhibition and display purposes, a ceiling track round the entire room 1.2 m in from the wall may be a wise provision if ceiling height is less than 4 m. Where provision is made for spotlight mounting for stage purposes, appropriate wiring runs back to the control point/switchboard must be provided with separate circuits for each outlet point and provision of cables for a suitable control circuit such as DMX512. 5.7.5 Controls Multi-purpose rooms will generally be regarded as places of public use and thus may be subject to specific requirements under legislation such as the Building Regulations. These may require that the lighting controls be placed such that they can only be operated by competent staff, which may prove awkward for the user. All of the lighting controls should be grouped together so that one individual can have charge of all; the controls are best placed in an adjacent room with a window or CCTV monitor into the multi-purpose room. A multiple scene setting control system should be used if possible with a number of scenes suited to the multitude of uses. This allows complete Lighting for particular applications 57 flexibility of control, but also enables pre-set lighting arrangements to be set-up at the push of a button so that it can be used by inexperienced users, such as a simple on/off control for initial entry to the space. 5.8 Adjoining spaces This category includes foyers, ante-rooms, lobbies and corridors immediately adjoining those spaces listed above. 5.8.1 Lighting objectives The functions of the lighting in spaces adjoining teaching and conference spaces are as follows: — to provide for the entrance and exit of the users, bearing in mind that many people may need to get in and out in a short time — to put users, as they approach, in an appropriate frame of mind for the activity in which they are about to take part — in some cases, especially ante-rooms, to provide a social atmosphere (such spaces are often used as tea and coffee spaces) — in some cases, to indicate to visitors the route they should take to reach their destination, e.g. the lecture theatre in a museum; in other cases, e.g. a suite of teaching rooms in a college, this may not be appropriate — finally, in many schools there are ‘heart’ or ‘breakout’ areas for group interaction or project work. The lighting of an adjoining space should therefore be designed in parallel with that of the lecture, teaching or conference spaces which they serve. However, this does not necessarily mean that they should be in the same style, or have the same illuminance values. 5.8.2 Circulation Fig. 5.20 Breakout spaces opening off a central circulation space and stairwell (photograph courtesy of Thorn Lighting) The circulation routes in a school are its main arteries taking pupils, staff and visitors from the main gate through to the particular rooms of interest. They need to be functional in that people need to find their way easily and safely through the building, even when they are unfamiliar with it. Circulation zones are often used for chance or ad hoc meetings or as breakout learning spaces (see Figure 5.20) so these routes also need to incorporate daylight and should be lit so that good face to face communication can take place. They will in most cases need to provide means of escape and this will require emergency lighting according to time of availability and user awareness. As school and college use is not restricted to daylight hours, a careful risk assessment should be carried out to determine which access routes are available for use during hours of darkness and, therefore, whether they require emergency lighting. Lighting can provide guidance for the visitor from entrance to destination, that may be done in two ways. First, the geometry of the luminaires can imply a direction. Secondly, by the phototropic effect whereby people are attracted to bright lights. A lighting designer can exploit this tendency by leading visitors towards brightly-lit areas. Lighting in corridors must provide for safe movement, and should provide an illuminance of at least 100 lux at floor level, with a UGR below 25. There must be appropriate lighting for hazards to be visible; special consideration should be given to those with visual impairment, where colour can be used to provide visual contrast. A particular hazard in corridors with shiny floors is that of water on the floor, which may be present due to spillage, roof leakage, or from melted snow carried in occupants’ shoes. The rule for staircase illumination is to light the treads and not the risers. A lighting level of 150 lux is appropriate and should be provided by positioning luminaires carefully to avoid distraction. The type and position of luminaires over stairs may be determined primarily by the requirements of emergency lighting and thereafter by the proposed installation and aesthetic requirements. 58 Lighting Guide 5: Lighting for education Fig. 5.21 Circulation spaces often double up as informal learning or meeting spaces (photograph courtesy of Thorn Lighting) Fig. 5.22 Adequate illuminance provided in such a way as to cause a maintenance access problem at a later date (photograph courtesy of Thorn Lighting) However, consideration needs to be given to maintenance access where luminaires are mounted at height or over the stairs themselves (see Figure 5.22). Waiting areas and lobbies Waiting areas and lobbies immediately adjoining lecture or conference spaces should be kept tidy and free of visual clutter. As they may be used as social areas, the illuminance should be about 200 lux and lamps of Ra ≥ 80 should be used. Unless the height is greater than 4 m above the floor, downlighters should be avoided as the harsh modelling they create can hinder face to face communication. Because activities of this kind may go on at the same time as lectures or conference proceedings, there should be two sets of doors at the entrance to the teaching or conference space, to act as both light and sound traps. The designer should consider that latecomers may be entering a much darker environment and the entrance lobby and walkways to the seating should be lit with care to allow for the adaption of the eye to the new illuminance level. There should be a rear entrance for latecomers to lecture theatres/rooms and it should be clearly signposted from the main entrance — preferably with a sign illuminated when lectures are in progress. If an ante-room for the lecturer is provided its lighting should be of a standard comparable with a laboratory, office or workshop as appropriate to allow preparation by the presenter. 5.10 Areas with display screen equipment The lighting for the display screen equipment (DSE) in educational and conference spaces needs to be appropriate for all tasks performed at that location and for the duration of the task, e.g. reading from screen or printed text, writing on paper, keyboard work. For these spaces the lighting criteria and system should be chosen in accordance with activity area, task type and type of interior from the schedule in section 5.2. The display screen (whether desk mounted, on the speaker’s lectern, or part of the wall display for interactive teaching) and, in some circumstances, the keyboard may suffer from reflections causing discomfort glare. It is therefore 5.9 Lighting for particular applications 59 necessary to select, locate and arrange the luminaires, and to control daylight so as to avoid high brightness reflections. The designer will need to determine the offending mounting zone and choose equipment with suitable mounting positions or distributions which will cause no disturbing reflections. 5.10.1 Luminaire luminance limits with downward flux Lighting can lower the contrast of the presentation on display screens by either causing veiling reflection by the illuminance incident on the displays surface or by luminance from luminaires, windows and bright surfaces reflected in the display. Based on the intended context of use BS EN ISO 9241-307(47) gives requirements for the visual qualities of displays concerning unwanted reflections. This paragraph describes luminance limits for luminaires that may be reflected in display screen equipment for normal viewing directions. Table 5.4 gives the limits of the average luminaire luminance at elevation angles of 65° and above from the downward vertical, radially around the luminaires for work places where display screens, which are vertical or inclined up to 15° tilt angle, are used. The effect of higher luminance on the display screen is determined in part by the display usage. In Table 5.4, ‘Case A’ refers to positive polarity and normal requirements concerning colour and details of the displayed information (e.g. when used in office, school etc.) and ‘Case B’ applies to negative polarity and/or higher requirements concerning colour and details of the displayed information (e.g. when used for computer aided design (CAD), colour inspection etc.). Some tasks or activities may require different lighting treatment such as lower luminance limits, special shading, individual dimming and so, according to the task. Table 5.4 Average luminance limits of luminaires that can be reflected in flat screens (adapted from BS EN 12464-1(44), Table 4) Display screen type Luminaire luminance limit for stated screen ‘high state’ luminance High (> 200 cd/m²) Medium (< 200 cd/m²) Case A ≤ 3000 cd/ m² ≤ 1500 cd/ m² Case B ≤ 1500 cd/m² ≤ 1000 cd/m² Note: for old type CRT screens luminaire luminance limits are 200 cd/m² for negative and 500 cd/m² for positive polarity 5.10.2 Selection of the appropriate limit To help establish whether the correct choice of luminance limit has been made the designer can use the methodology(50) below and the flowcharts given in Appendix A1. First the designer will need to determine the size of the offending light source (luminaire or window, see Figure 5.23. The visual size of the light source or the subtended angle (θ ) can be calculated using the equation: ( d/2 θ = 2 arctan ——— s1 + s2 ) (5.1) where θ is the subtended angle or visual size of light source (°), d is the distance of the light source in the direction of the display screen (m), s1 is the viewing distance (m) and s2 is the distance between the light source and the display screen. Then the solid angle (Ω ) delimited by a cone of apex angle θ can be calculated using the equation: Ω = 2 π (1 – cos (θ /2)) where Ω is the solid angle in steradians. (5.2) 60 Fig. 5.23 Lighting Guide 5: Lighting for education Calculation of visual size in degrees (the luminaire and distance are not to scale but enlarged to show the angle clearly) Luminaire d s2 θ s1 Display screen The visual size of a luminaire is highly dependent on the luminaire, the direction of viewing and the distances between the luminaire, the screen and the viewer. A 1° source is about the size of a circular downlight or a fluorescent troffer viewed crosswise. Other luminaires may be nearer to 3–5°. The visual size of a window is also variable. Studies of student positions in typical classrooms indicate window sizes of, typically, 10° and 15°. The tables given in Appendix A1 use a 95% satisfaction criterion, that is to say by this method of calculation and luminance limit, 95% of users would not experience problems with display screen equipment veiling reflections. 5.10.3 An alternative approach As screen technology is developing at a faster rate than that of conventional lighting it is far more appropriate to define the performance of the screen that is required, rather than compromise the lighting comfort of the user of a space by restricting the available light. Given that in most learning spaces the computer screen is not the main disseminator of knowledge, it seems inappropriate to limit the lighting designer’s choices for lighting the speaker, teacher or pupil simply due to poor application of display screen technology. To do so would recreate the ‘cave’ effect inadvertently produced in many offices and classrooms of the 1980s and 1990s. Most luminaire manufacturers issue accurate information on the luminance of their equipment at angles above 65° from the downward vertical. Once the lighting designer has reached a lighting solution that provides for the performance, efficiency and comfort of the users of a learning space, the screen brightness limitations suited for use in that space should be defined. For instance, it should be possible to require suppliers of laptop or desktop computers screens for classroom use to provide screens capable of a minimum of 3000 cd/m2 with a matt finish and available tilt of not more than 35°, rather than limit the luminaires to 200 cd/m2, based on an inadequate knowledge at the time of the lighting design as to what display screens may be used. Given also that, on average, screens are replaced every 5 years, whereas luminaires may last in excess of 15 years, this approach makes sense in both economic and sustainability terms in order to provide a good quality lit environment. Lighting control for both the electric lighting and daylighting should still be provided. 5.11 Laboratories, workshops and other practical learning spaces Rooms used for practical work, i.e. laboratories, workshops, art rooms, food technology/catering, electronics, craft rooms and similar applied learning spaces, involve visual needs and tasks that are the same as those found in industry. This is particularly so if the room contains fixed equipment, e.g. a workshop with lathes and other machine tools. Lighting for particular applications 61 The reader should consult the Code for Lighting(8) for advice on laboratories, workshops and textiles rooms. However, many rooms used for practical work have to serve a wide variety of purposes and the visual needs may be different for each. In recent years there have been considerable changes in the way traditional subjects have been taught. Teaching spaces are increasingly becoming more flexible in use with functions ranging from industrial to office environments. The computer is no longer confined to special rooms — personal and laptop computers may be used almost anywhere. A very large range of activities are to be found in design and technology departments and they may change throughout the course of a year. The illuminance over the working plane (0.85 m above the floor) should be above 500 lux, and UGR 19. The UGR may be raised to 22 for preparation areas and the illuminance should be raised to 750 lux for art rooms in specialist art colleges. If work involving accurate judgement of colour (e.g. art, dyeing etc.) is to be done, the lamps should be of Ra = 80 or better in most educational buildings, but in specialist art and textile colleges/faculties Ra = 90 would be more appropriate. Visual tasks such as sewing will require local task lighting. In all these spaces the teacher occupies no fixed position but spends time at the benches, machines and worktables as needed. The main requirement is for good supervision with the ability to determine detail and texture being important in most subjects, hence good modelling is required with some flexibility to control the direction of light and to reduce or omit daylight when necessary. In most rooms there may be a teaching wall from where more formal presentations will take place with the students sitting or standing by their machines, benches or tables, but in some establishments presentations and discussions take place in separate spaces with only practical work carried out in specialist rooms. These separate spaces may be lecture rooms, classrooms, seminar rooms or small group rooms, and the design of these spaces should follow the advice given in earlier chapters. Laboratories in tertiary education and research will generally have fixed furniture (see Figure 5.24) but in schools and colleges may take a less formal arrangement with movable tables and fixed wall benches or service pillars so that a variety of layouts can be provided. In both cases, as with design and technology, there is usually a teaching wall. As with other teaching rooms in schools, it is a requirement that they are primarily daylit, but here it is more important that sunlight can be excluded because of disability glare and the danger of rendering experimental flames invisible. Fig. 5.24 A typical laboratory showing a fixed arrangement, teaching wall and workstations situated close to daylight (photograph courtesy of Thorn Lighting) 62 Lighting Guide 5: Lighting for education Where fast moving machinery is in use care should be taken to avoid stroboscopic effects by use of high frequency control gear. Where dust or moisture risk exists the lighting should be a minimum of IP44. In specialist laboratories in higher education it may be necessary to provide luminaires of IP65 with a clean room classification. In this case advice should be sought in line with good practice in the clean room/pharmaceutical industries covered in SLL Lighting Guide LG1: Industry(51). In laboratories some processes may need terminating before evacuation. It is therefore necessary to have adequate high risk emergency task lighting in those specific locations where a visual task must be performed prior to evacuation. Lighting to the escape routes, or open areas from laboratories and workshops will be required to ensure safe passage past any risks from machinery or other hazards. 5.12 Libraries Fig. 5.25 Lighting coordinated with library shelving to provide sufficient vertical illuminance to the lowest shelf (photograph courtesy of Thorn Lighting) In libraries the designer needs to allow for two main tasks: (a) finding the correct book, and (b) reading or study. In addition, there are a number of other considerations such as lighting for using computers and accent lighting for display purposes. Lighting in each case calls for a different approach. Physically finding a book (rather than looking it up on a computer database) requires vertical illuminance on the spine of the book and, in the worst case, this may be just above floor level. Therefore, 200 lux on a vertical plane at just above floor level is required and the designer should remember that the library user will create a shadow when in the vicinity of the shelving, hence light from more than one direction is important. Use of floor finishes with a relatively high reflectance can help. For computer and reading based tasks 300 lux is suitable for most users and in some libraries that are open to the wider adult community this may be raised to 500 lux for reading tasks by the addition of local task lighting where appropriate, such as at planned reading desks. However, it would not be acceptable to light the entire space to a higher level for a few users who may be present only occasionally. Lighting for students with impaired vision needs careful design and suitable aids to reading should be considered. It should be borne in mind that for some impairments higher illuminance, in itself, may not be the solution. Care should be taken to incorporate daylight were practical, protecting valuable reading matter where necessary from heat or ultraviolet damage but maximising energy savings and providing a higher quality of reading light as far as practicable. Lighting for particular applications 5.13 Sports halls and gymnasia Fig. 5.26 It is possible to provide daylight to sports halls with careful design; electric lighting should cater for many differing uses (photograph courtesy of Thorn Lighting) 63 It is generally considered that daylight is beneficial in sports halls and gymnasia. However, windows and roof lights are frequently excluded except at high level because the sun and sky can cause both disability and discomfort glare to users who are moving quickly and often with an upward field of view. Also there is a risk of damage to glazing from some sports. Reflected glare from shiny surfaces and particularly floors can also be a nuisance. If daylight is provided, screening facilities for use when necessary should be available. There should be little objection to the use of natural lighting within sports halls providing it is well considered and appropriate. The provision of high quality internal spaces with attractive daytime environments is a significant aspect in attracting user groups. There are considerable benefits in terms of environmental sustainability and potentially lower running costs in being able to complement electric lighting with natural daylighting. However, using natural light in a sports hall requires very careful consideration because of difficulties in controlling glare and ensuring reasonably constant and uniform levels of lighting. Appropriate lighting is vital in sports halls to allow activities to take place that often demand difficult visual tasks, for instance tracking a fast moving shuttlecock against a similar colour background. The design issues are complex and optimising natural daylight and integrating it with well designed electric light requires that the form, fabric, internal layout and systems of a building are considered holistically. For natural lighting generally, north light is considered most appropriate. To enhance the visual environment, it is suggested that luminaires with both upward and downward light should be utilised. There should be some control to keep glare to a minimum and the light distribution should provide adequate light on vertical surfaces. Lamps and luminaires should have wire guards or other impact-resistant protection. Sports halls and gymnasia in schools are often used for non-sporting events, including examinations, and therefore consideration must be given to the lighting required for these events and supplementary arrangements provided if necessary. Control strategies should be such as to make it difficult simply to switch ‘all on’ lighting because it is easy to do so; scene switching should be clear and functional. Because of the high mounting of the luminaires, maintenance of the lighting installation will be difficult unless special access facilities are provided. The use of long life lamps in these circumstances should be examined. Reference should be made to Lighting Guide LG4: Sports lighting(49). 64 Lighting Guide 5: Lighting for education 5.14 General purpose halls, drama and dance studios Very often there will be a need for a large space within an educational building to cater for activities ranging from examinations to drama. The design will depend on the range of activities. Blackout will almost certainly be required for drama use, as will a degree of flexibility in the lighting dependent on the range of uses envisaged and the budget. If the budget is limited, a general lighting installation of luminaires that provide both upward and downward light should be used. The installation should meet the most stringent requirements in terms of activity, allowing the luminaires to be simply controlled to provide some flexibility. To complement this there should be a system of wiring that allows supplementary theatre lighting equipment to be installed when needed. For teaching of GCSE, A-level and degree level drama courses, a good standard of stage and drama studio lighting will be required (see Figure 5.27). Fig. 5.27 Floor trap with sockets (on stage if fixed stage) Mounting positions for (upper) theatre and (lower) drama room lighting Stage may be whole width of hall or be platform only Rear stage barrel for back lighting Dimmer racks Socket for control desk for setting-up lighting Possible proscenium arch location Wall sockets high up on wall Socket for control board during performance Pre-wired lighting barrels across entire room Window should have full blackout facilities Sound and light control desk Front stage barrel (deep stages may require one or more intermediate barrels) Front of stage barrel to light those on fore stage Lighting for particular applications Fig. 5.28 Dance studios should use daylight whereas drama may require complete blackout (photograph courtesy of Cundall Light4) 5.15 Lighting for whiteboards and projection screens 65 In halls likely to be used for concerts, theatrical and dance productions it may be necessary to arrange for an adaptable stage lighting system to be installed so that each event can be appropriately lit. Lighting barrels will need to be placed above and in front of the stage so that stage lights can be positioned to light the faces of people performing on all areas of the stage. To achieve this, lighting needs to come from about 45° above and 45° to either side of any position on stage. This will involve using wall mounted brackets and additional lighting power and control connections. Where there is a fixed stage, floor-traps with stage lighting sockets should be located on either side for side-lighting dance, and for special effects lighting. The lighting installed in spaces for music recital or performance should be carefully considered in terms of the noise the luminaire components and controls may make. Resistive or inductive components should be mounted outside of the space or within sound insulating enclosures. High level, wall mounted and stage sockets should all be wired back to a dimmer position on one side of the stage. For larger halls there may be a need to provide an additional dimmer position at the back of the hall for controlling the lighting during a production. Drama and dance studios are used primarily for the teaching of drama with some need for small dance class use. Whilst windows and daylight are still required to allow flexibility of use for these rooms there may be a need for full blackout facilities during lessons. Drama lessons are used to teach group skills, focusing on social and personal development, where general mood lighting across the whole studio is needed, as well as performance and stage craft skills, such as set and lighting design, where full theatre lighting is needed for performance use in any area of the room. To achieve this there needs to be a basic structure of lighting points across the space for locating lights in any part of the room. Often the most convenient solution is to place a series of pre-wired lighting barrels at intervals across the width of the room. The lighting sockets should all be wired back to a dimmer position located in one corner of the room. The vast majority of educational spaces now use whiteboards (normally with a gloss finish) and, in an increasing number of cases, interactive whiteboards. Inherent in these technologies are surface finishes prone to veiling reflection and, in the latter case, projected images that may struggle to compete with high luminance sources (most commonly sunlight, but in some cases electric or general ambient daylight). It is therefore essential that all whiteboards be treated carefully. Note that gloss whiteboards cannot satisfactorily be used as projection screens as the high gloss will cause veiling reflections from the projector. To keep reflections to a minimum, whiteboards should be mounted vertically on walls perpendicular to the window wall. They are best lit by ceiling mounted luminaires (see Figure 5.29) or those specifically designed for the purpose (see Figure 5.30). Where older black chalkboard surfaces are still in use, the illuminance on the surface should average 500 lux, with a uniformity of 0.7; this may be reduced in the case of lighter colour boards to maintain an average luminance across the board available to the eye of 80–160 cd/m2. Effective reflectance for coloured boards are: whiteboard 85%, blackboard 5–10%, green/blue 20%, yellow/green 30%. Where a separate whiteboard luminaire, or luminaires, are fitted they should have a manual override switch positioned local to the board for ease of use. Care should also be taken to avoid excessive luminance on the interactive media board. In some cases, those based on plasma technology, luminance in excess of 200 cd/m2 may cause problems. In the case of modern close projection systems the luminance may be considerably higher than those imposed for 66 Lighting Guide 5: Lighting for education laptops and other display screen equipment; in some cases luminance up to 6000 cd/m2 may be acceptable but the designer is strongly advised to investigate the performance of the actual screen to be used. Fig. 5.29 Whiteboard luminaires need to be carefully positioned Whiteboard luminaire must be installed within the shaded area to avoid reflections in the board to the nearest viewer 0 0 Where students may sit close to an interactive whiteboard the board light may need to be switched off to reduce glare Fig. 5.30 Specific whiteboard lighting positioned to reduce glare and with matt projection screen mounted separately (photograph courtesy of Thorn Lighting) 5.16 Lighting and visual aids Visual aids are often used for teaching, most commonly interactive whiteboards and computer based projectors as well as television and video equipment. For the use of these teaching aids it may be necessary to provide a lower level of lighting so that the presentation can be seen comfortably and clearly. Curtains or window blinds will need to be chosen carefully to match the capabilities of the existing equipment and in some cases blackout blinds that fit into slots surrounding the window reveals may be used. Care should be taken to make sure lighting controls and blinds are easy to use to avoid the common ‘blinds closed, lights on’ mentality. Specification of suitable high brightness projectors should enable most daylit spaces to retain some natural light contribution at all times. Sufficient light should be provided to enable notes to be taken during the presentation, and an illuminance over the seating areas within the range 15–30 lux is suitable. High luminance elements from luminaires within the field of view may under certain conditions make the viewing of the presentation difficult and care should be taken, perhaps specifying a required shielding angle, Lighting for particular applications 67 to make sure a glare-free view of the screen is possible. Also, light should not fall onto the projection screen and it should not be possible to see reflected images of luminaires or windows on the screen surface of television monitors. 5.17 Lighting for pupils with visual and hearing impairments Lighting must take into account the different needs of children with special educational needs (SEN) and disabilities. Children with impaired vision, for example, need lighting levels that enhance their sight. Those with hearing impairment need clear visibility for lip-reading and signing, for orientation and using signage and wayfinding. Safety is a key factor; poor visibility and poor surface contrast may contribute to accidents. Input from a lighting specialist is recommended where there are complex visual needs. A school’s orientation and any natural shading on the site should be considered at the outset, including the location of spaces that generate the most heat and the need for and detailing of shading devices. The Royal National Institute for the Blind (RNIB) and similar organisations can advise on specialist environments for children with visual or multiple impairments. Designs should avoid glare, silhouetting, reflections, shadows and any other interference that causes visual confusion. For instance, a teacher’s or child’s face could be in shadow against a window or bright or highly reflective surfaces, or have shadows cast by electric lighting. Good tonal contrast is important. There will be times when teachers will want to change the mood of a space to create a more calming or stimulating environment. Window blinds and electric dimming can help, as can local controls. 5.17.1 Daylighting Daylighting is important for all schools, and children with limited mobility in particular benefit from a connection to the outdoors and a view out. However, some pupils with SEN may be particularly sensitive to glare from direct or reflected sunlight, so it is important to be able to control natural light entering the space. This may also be particularly important when providing the right visual conditions for viewing whiteboards and projection screens. The window wall should be light in colour. A brightly lit outdoor view through a window can be glaring against a dark wall — a particular hazard at the end of a corridor. A minimum average daylight factor of 4–5% is considered the optimum (on the working plane) for schools with children with SEN and disabilities; an acceptable uniformity ratio should be maintained by providing a minimum point daylight factor of 2% up to 0.5 m from the wall and avoiding under-lit areas furthest from windows. This applies to learning, circulation and assembly spaces. In deep spaces lit by windows in one wall only, ceilings may need to be higher than average with high levels of light reflectance may be required. Where there is a number of children with visual impairment or sensitivity to light, or where there are conflicting needs, specialist lighting advice may be needed. 5.17.2 Electric lighting Light fittings must be low-glare, with strict avoidance of mains frequency flicker and unwanted noise. It may be necessary to avoid visible light sources, over changing-beds or therapy couches, for example. Uplighters and use of coloured light synchronised to particular time cues or events during the day may be more suitable for some children with autism. Automatic sensors that switch off lighting when no movement is detected may not be suitable for children who are less mobile. Switches may be useful in teaching children how to use them. 5.18 Local task lighting Without doubt there has to be a fundamental change in the use of light in all buildings. No longer is it ecologically sound to light for the neediest user as a blanket measure. The approach must be one of allowing sufficient light for the normal users and the most common task. In addition, the designer should allow for the needs of any other users of the same space through the use of additional task lighting. This task lighting can be by the provision of controls, for instance 68 Lighting Guide 5: Lighting for education the setting of the normal scene in a classroom to 300 lux, but allowing a scene that increases this to 500 lux if required. Alternately, the designer could allow for the lower level using ambient lighting, including daylight, and top-up this level local to a particular task; for instance, by providing an ambient 200 lux vertical illuminance in a library with desk mounted reading lighting to 500 lux at reading positions. Careful design of task luminaires is needed, especially in cases of SEN students. For all students it will be necessary to ensure power leads are kept out of reach by careful cable management and routing through desks. It will be necessary to limit the temperature of any luminaire components available to touch or likely to be in advertently touched, perhaps whilst leaning over a book. Where luminaires are used in close proximity to students it will be necessary to limit surface temperatures to below that which will cause skin damage. Local task lighting should be dimmable and controlled such that the lighting distribution does not extend beyond the intended task and removing the possibility of glare to other users or equipment. Local switching will be required, preferably linked to a room override function to ensure lighting is switched off when not required. 5.19 Exterior lighting Fig. 5.31 External lighting should guide, welcome and provide a sense of safety whilst satisfying the need for good quality CCTV images and minimal light nuisance (photograph courtesy of Cundall Light4) When considering the external lighting the designer should take the opportunity to consider not only the functional requirements of external lighting but also the amenity aspects and the benefits that good exterior lighting can bring. Advantage should be taken where appropriate to provide landscape illumination wherever possible and to add a sense of visual enhancement to interesting architecture, sculptures or building structures. Overall, though, lighting to educational buildings will be for safety and security. Entrances should be treated in the same way as entrances to leisure centres or retail outlets. The designer should ensure they provide an attractive, welcoming appearance to all the entrances, access routes and surrounding areas for staff and students alike. Environmental planning will also require the lighting designer to be mindful of the light nuisance that may be caused. Although difficult to alleviate totally, it can be reduced considerably by careful consideration of the product design and positioning of luminaires. Exterior lighting should at the very least provide both pedestrians and vehicular traffic with good visual guidance around the site. Lighting for particular applications 69 In addition to the visual tasks it should also be designed to provide pedestrians with a ‘psychologically safe’ environment. Colour rendering, installation efficacies and maintenance issues must all be considered as well as the luminaire positioning relative to CCTV and local residences. 5.19.1 General performance See Table 5.5. Exterior lighting should comply with minimum lamp and gear efficacy targets of 80 lm/W for colour rendering light sources less than Ra = 60 requirements for and with 70 lm/W for light sources greater than Ra = 60. exterior spaces Where there is increased use by those with disabilities, the designer may decide to increase these levels appropriately but only in zones specifically designed to ease disabled access. Table 5.5 General performance requirements for exterior spaces (source: BS EN 12464-2(52)) Type of area task or activity Em (lx) General circulation areas: — walkways exclusively for pedestrians — traffic areas for slowly moving vehicles (max 10 km/h, e.g. bicycles) — regular vehicle traffic (max 40 km/h) — pedestrian passages, vehicle turning, loading and unloading points Parking areas: — light traffic e.g. parking areas of schools — medium traffic e.g. parking areas of colleges or universities, office buildings, sports and multipurpose building complexes — heavy traffic e.g. parking areas of major conference venues, major sports and multi-purpose building complexes 5.19.2 Sports pitches Ra (min) Uo (min) GRL (max) 5 10 20 20 0.25 0.40 50 50 20 50 20 20 0.40 0.40 45 50 5 10 20 20 0.25 0.25 55 50 20 20 0.25 50 The designer should avoid the desire to over-specify sports pitch lighting in the view that it will extend community use. Generally all educational facilities will only require a maximum of Class III play(32), i.e. suitable for recreation or schools sports use including physical education. In cases of colleges or universities with specialist sports courses, the designer may need to increase this sensibly in line with the needs of the college. Where the establishment requires lighting to higher than Class III the design must provide the additional levels by luminaires on separate control circuits enabling a stepped switched approach and giving staff the ability to minimise energy use to the most appropriate level. Lighting controls for the higher levels should be accessible only to staff. Generally external sports areas are likely to have a multi-purpose use and the designer may need to satisfy a number of requirements. Furthermore the designer should consider the realistic quality of play, type of material used for Table 5.6 General performance requirements for exterior sports pitches to BS EN 12193(32) Type of area task or activity Basketball Football (outdoor) Handball (outdoor) Hockey (outdoor) Netball (outdoor) School sports Tennis (outdoor) Class Em (lx) III III III III III I II III III 75 75 75 200 75 750 500 200 200 Ra (min) 20 20 20 20 20 60 60 20 20 Uo (min) 0.50 0.50 0.50 0.70 0.50 0.70 0.70 0.50 0.60 GRL (max) 55 55 55 55 55 — — — 55 70 Lighting Guide 5: Lighting for education the playing surface and the range of visual acuity issues raised by extended community use. In such cases the designer may find the guidance levels offered by Sport England more applicable, see Table 5.7. Table 5.7 Multi-use games areas to Sport England standards Surface Game Em (lx) (principal playing area) Painted open textured macadam Principal sports Tennis, mini-tennis, basketball Secondary sports Netball Open textured macadam Principal sports Netball (AENA Category 1 and 2 courts) Secondary sports Tennis, mini-tennis, basketball Polymeric surfaced Principal sports Netball (AENA Category 3 court) Secondary sports Tennis, mini-tennis, basketball Principal sports Five a-side, football training, athletics training Sand filled/dressed synthetic turf Principal sports Hockey, football and five-a-side football Secondary sports Ra Uo GRL MF CCT 400 400 65 65 0.7 0.7 50 50 0.8 0.8 4000 4000 400 400 65 65 0.7 0.7 50 50 0.8 0.8 4000 4000 400 400 200 (full lighting and training) 65 65 — 0.7 0.7 0.7 50 50 — 0.8 0.8 — 4000 4000 — 350 (full lighting 200 (training) 0.7 Lacrosse, rugby training (not scrummaging), and athletics training 350 (full lighting 200 (training) 0.7 Note: in all cases overall minimum maintenance factor = 0.8, glare rating < 50, colour rendering value (Ra) > 65, colour temperature ≥ 4000 K 5.19.3 Light nuisance Fig. 5.32 Use of zero cut-off lanterns aimed from the perimeter inwards restricts to the minimum light nuisance (photograph courtesy of Thorn Lighting) In modern exterior design there is very little justification for poor control of light nuisance from any educational site, especially those that sit within the community. Whilst there are arguments for road lanterns using shallow bowl optical design, to compromise some upward light for maximum spacing and therefore better overall performance, the case for all other exterior lighting is not as strong. Particularly for educational premises, the designer should comply with the requirements of BS EN 12464-2(52) with respect to restricting light nuisance. Furthermore, there is little basis for the decision that new buildings in urban or Lighting for particular applications 71 suburban zones should be allowed to waste light more than those in rural districts. Hence, for all educational premises, the designer must aim for the minimum limits given against each zone for the technical parameters given in Table 5.8. The zones are defined in Table 5.9. For colleges and universities specialising in sports the use of zone E4 limits may be justified, subject to geographic location for the sports pitch lighting, provided suitable controls are installed to ensure the lighting does not remain on when not required. Except for high performance sports pitches in specialist colleges and universities, exterior lighting should maximise the use of zero cut-off lanterns, those luminaires that emit no upward light when normally installed. Table 5.8 Performance requirements to limit light nuisance (adapted from BS EN 12464-2(52) Table 2, by permission of the British Standards Institution) Parameter Application conditions Value of parameter for stated environmental zone E1 E2 E3 E4 Upward light ratio (ULR) Ratio of luminous flux incident on horizontal plane just above luminaire in its installed position, to total luminaire flux. 0 0–5 0–15 0–15 Illuminance in vertical plane (Ev ) (lux) Pre-curfew Post-curfew 2 0 5 1 10 2 10 2 Luminous intensity emitted Pre-curfew by luminaires (I ) (cd) Post-curfew 2500 0 7500 500 10 000 1000 10 000 1000 0 5 10 10 50 400 800 2800 Building facade luminance (Lb ) (cd/m2) Taken as the product of the design average illuminance and reflectance factor divided by π Sign luminance (Ls ) (cd/m2) Taken as the product of the design average illuminance and reflectance factor divided by π or for self-luminous signs the average luminance Table 5.9 Classification of environmental zones Zone Surrounding Lighting environment Examples E1 E2 E3 E4 Natural Rural Suburban Urban Dark Low brightness Medium brightness High brightness National parks and protected sites Industrial or residential rural areas Industrial or residential rural suburbs Town centres and commercial areas Table 5.10 Threshold Increment limitations from sports and road lighting installations (reproduced from BS EN 12464-2(52) by permission of the British Standards Institution) Threshold increment for stated road lighting/road classification No road lighting Road classification M5 15% based on adaptation luminance of 0.1 cd/m2 5.19.4 Road lighting 15% based on adaptation luminance of 1 cd/m2 M4/M3 15% based on adaptation luminance of 2 cd/m2 M2/M1 15% based on adaptation luminance of 5 cd/m2 Road lighting requirements are currently detailed in BS 5489-1(53) and BS EN 13201: Parts 2 and 3(54,55). Entrance and exit points will often connect with major traffic routes and the lighting should be graded, in order to avoid sharp contrast with the external roadway lighting. Roads lighting standards should be considered based on realistic vehicle speeds, pedestrian and cyclist usage. 72 Lighting Guide 5: Lighting for education 5.19.5 Car parking Guidance for all types of exterior lighting, including recommended illuminance levels, can be found in detail in BS 5489-1(53) and summarised in the lighting schedule (Table 5.5). On new installations it is advisable to ensure a that a ‘safe by design’ policy is initiated early in the project. This should include advice on CCTV together with the positioning and type of lighting required. The external lighting should include all entrance and exit points, and all pathways that link with buildings. All exterior luminaires should use high output, good colour quality, low energy lamps. Care should always be taken to avoid or minimise any light nuisance. All lanterns should be of zero upward light distribution. For smaller car parking areas, it may be possible to provide illumination from the periphery and also from buildings in the immediate vicinity. Larger areas will require columns to be located either centrally or on the boundaries of the car parking area. The location of the columns should take into consideration the parking bays. Where columns are used, their height and position relative to adjacent access roads must be taken into account. Access for maintenance purposes should also be considered and, wherever possible, the column height should be such as to allow on-site maintenance to be carried out without the need for specialist access equipment. 5.19.6 Pedestrian footways Footways that are not well illuminated from elsewhere must be provided with adequate illumination to ensure people’s safety during hours of use. Wall mounted luminaires from adjacent buildings or low-level luminaires can be provided in the absence of street lighting. If low-level luminaires are utilised, these must be of the vandal resistant type and incorporate long life, low energy lamps. If CCTV is operational, the minimum illuminance for the CCTV equipment must be taken into account, as well as care in the positioning of the luminaires. Particular attention should be given to routes that allow passage to plant rooms where maintenance staff may require access after dark. These access points, which may be at roof level, must also be adequately illuminated. Similar special consideration must be provided for routes to staff on-site residential areas, which may be in regular night-time use. 5.19.7 Security lighting There are many areas that pose security risks around educational sites, particularly from vandalism or theft. Attention should be given to areas of darkness that may encourage unauthorised persons to gain access or linger in the area. 5.20 Emergency lighting In all of the rooms covered by this Lighting Guide, large numbers of people may gather together. It is therefore necessary to provide emergency lighting, which is defined as lighting that will enable people to see their way out of a building in the event of the normal lighting failing. It must be stressed that it is not the function of emergency lighting to enable normal activities to continue within a building if the main power supply should fail; such lighting is referred to as standby lighting and is not normally provided in educational and conference premises. Certain elements of the Building Regulations put size limitations on rooms inferring that anti-panic lighting is not required. However, the designer must record a risk assessment for the space, specifically under the Regulatory Reform (Fire) Order(56) in England and Wales. It should be noted that where there is open access, public assembly, reconfigurable furniture and access after dark to people unfamiliar with the space the risk of injury on lighting power failure is likely to be significant and may be even greater if the likely influences of age, illness, alcohol or drugs are taken into account. 5.20.1 Escape route signage It is important that all exits, available for use in an emergency, are clearly signposted and are visible at all material times. The sign should be illuminated by normal and emergency lighting systems. If exits are not directly visible, route Lighting for particular applications Fig. 5.33 Example pictogram from BS EN 1838 73 indicator signs with an appropriate directional arrow should be used. The style and details of the safety signs are defined in BS 5499(57,58). ISO 3864(59) gives the internationally agreed formats of exit signs and safe condition signs. The designs consist of a rectangular or square shaped frame with a white pictogram on a green background. The green area must be more than 50% of the total area of the sign and the colour must conform to ISO 3864-1(59). As the pictograms can differ in style and content, it is important to consult the enforcing authority for a particular project on its interpretation prior to choosing the signs. The preferred style of escape signs is shown in Figure 5.33, which has been reproduced from BS 5499-4(57), BS EN 1838(60) and BS 5499-1(58). A summary of the requirements for safety signs is given in Table 5.11. Table 5.11 Summary of requirements for safety signs Parameter Requirement Viewing distance 100 × height of externally illuminated sign 200 × height of internally illuminated sign Minimum 2 m above floor 50% of design value in 5 s 100% of design value in 60 s 1 hour Mounting height Response time Minimum duration 5.20.2 Escape route illumination Escape lighting should provide adequate visual conditions and directions for safe passage on escape routes and allow occupants to reach escape routes from open areas. It should allow fire alarm call points, fire lighting equipment and safety equipment to be identified. It should allow hazards (stairs, intersections, slopes) and hazardous processes to be identified and made safe during evacuation. In general, students will be familiar with the site layout and the safety provisions. They should therefore be able to make an orderly evacuation during an emergency. However, in some educational buildings there may be activities and processes that are hazardous and have to be terminated before evacuation. These are referred to as high-risk areas. In most educational premises there is likely to be public access for extracurricular activities and adult education, therefore there are likely to be large numbers of people who will be unfamiliar with the premises, layout and escape procedures. Here, much anxiety and confusion may be alleviated by strategically placed escape signs. At least one sign must be visible from all parts of the premises at all material times. Such signs should permanently indicate the directions to exits from the premises or places of safety. Escape areas and routes must also be illuminated adequately and appropriately. In high-risk areas, a higher illuminance must be provided at positions where a visual task has to be performed prior to evacuation or where people have to pass by these dangers along the escape route. In all escape areas and spaces, the emergency lighting system should be so designed that the light it provides fills the occupied volume of the space used for evacuation. In addition, the design should be based on the minimum-light-output condition of the luminaire and should be based on direct light only. The contributions by room surface inter-reflections should be ignored. However, for lighting systems using indirect luminaires or uplights, where the luminaire works in conjunction with a surface, the first reflection is taken to be the direct light and subsequent reflections should be ignored. 5.20.3 Glare High contrast between a luminaire and its background may produce glare. In escape route lighting, the main problem will be disability glare, in which the brightness of the luminaire may dazzle and prevent obstructions from being seen, see Figures 5.34 and 5.35. Such glare may be created, for example, by the 74 Lighting Guide 5: Lighting for education Glare zone 60° 60° Contributory Line of sight Fig. 5.34 Glare in direction of escape 180° Table 5.12 Luminaire mounting heights and maximum luminous intensity Mounting height above floor level, h (m) 180° Fig. 5.35 beam of a twin spot emergency floodlight seen against a very dark background or placed at the end of a corridor. The disability glare level to which an individual is subjected is related to the luminous intensities of the luminaires in the visual field. The glare can be minimised by restricting the luminous intensity of all luminaires in the field of view. The sensitive field of view is taken to be in the zone 60° to 90° (in elevation) for level routes/areas and the whole of the lower hemisphere for nonlevel routes/areas, as shown in Figures 5.34 and 5.35. The maximum permissible luminous intensity of an individual luminaire in the glare zone is related to mounting height, and the limits are shown in Table 5.12. The limits have to be calculated for the maximum emergency lighting lumen output. Glare on stairs 5.20.4 Luminaire locations h 2.5 ≤ h 3.0 ≤ h 3.5 ≤ h 4.0 ≤ h 4.5 ≤ h < < < < < Maximum luminous intensity, Imax (cd) Escape routes and open areas 2.5 3.0 3.5 4.0 4.5 High-risk task area lighting 500 900 1600 2500 3500 5000 1000 1800 3200 5000 7000 10000 At points/places of emphasis, position a luminaire at or within 2 m measured horizontally: (a) at each exit door intended for use in emergency (b) near stairs so that each flight of stairs receives direct light (c) near any change in level (d) at mandatory emergency exits and safety signs (e) at each change of direction (f) at each intersection of corridors (g) outside and near each final exit (h) near each first aid post (i) near each piece of fire fighting equipment (j) near each alarm and call point (k) in lift cars (l) in toilets, lobbies and closets over 8 m2 (m) in toilets, lobbies and closets less than 8 m2 without borrowed light (n) in control and plant rooms (o) in motor generator rooms use self-contained luminaires (p) each side of automatically closing doors (q) immediately outside the exit from the premises to the place of safety. Note: if (h), (i) and (j) is not an escape route or area, a minimum of 5 lx on the floor should be provided. Lighting for particular applications 75 5.20.5 Choice of systems Emergency lighting systems are usually powered from batteries or generators that are automatically triggered by a detection system as soon as the mains system fails. The system duration or category is defined by the period the system is able supply power to the load, usually given as 1 or 3 hours. In most educational premises 1 hour duration is sufficient, however for premises used by those with limited mobility longer durations may be required. Emergency lighting power systems in educational premises may be integral or centrally powered; using whichever system makes sense primarily from a safety point of view. The designer must consider the environmental impact of emergency lighting batteries, lamps and power use, though as a secondary consideration to that of safety. Consideration of LED emergency solutions may offer reduced quantities of batteries, extended battery life, extended light source life and reduced parasitic power. However, the designer should research carefully the claimed performance of LED systems and understand the issues until the performance of such systems is regulated by suitable European standards. 5.20.6 Classification of systems There are a number of ways that emergency luminaires can operate: — Non-maintained (NM): the lamp is only lit when the mains fail and is operated by an emergency power source. — Maintained (M): the lamp is lit at all material times and is powered by the mains supply under normal conditions. In an emergency, when the mains fail, an emergency power source cuts in to power the lamp. In all cases, where a battery is present, it is charged by the mains supply. Where the public are present, ‘maintained’ exit signage should be used. 5.20.7 Planning schemes Fig. 5.36 If this equipment is sited along an escape route it will require 1 lux from luminaires positioned within 2m horizontal distance The emergency escape luminaires may be stand-alone bulkhead units or integrated recessed, surface, pendant luminaires or uplights, but close attention should be paid to the positioning and mounting of these luminaires. Luminaires placed too low, especially along corridors, may be obscured by the movement of people and be subject to vandalism. If placed too high, for example direct on a very high ceiling, the luminaires may be obscured by layering of smoke in the event of fire. As a general rule, they should be placed at least 2 m above floor level and as close to this height as possible. In schemes where provision is planned for smoke layering at ceiling level (creating a smoke reservoir), consultation with the fire service is advisable and consideration should be given to mounting the luminaires below this zone by using, for example, pendant luminaires. These luminaires, however, should be at least 2.2 m above the floor level. Note that the positions of the escape luminaires can, by themselves, give the first indication of the escape route. Escape luminaires should therefore be sited at, or near, positions where it is necessary to emphasise potential hazards on the route or the location of safety equipment. ‘Near’ is taken to be within 2 m measured horizontally. The illuminance on the escape route at these positions should be at least 1 lx. If these positions are not on the escape route or in an escape area, they should be illuminated to at least 5 lx on the floor. 76 Lighting Guide 5: Lighting for education 5.20.7.1 Escape route lighting See Table 5.13 and Figure 5.37. Escape routes must be clearly defined and permanently unobstructed. Table 5.13 Requirements for escape route lighting Item Value Route size Design illuminance: — on centre line ≤ 30 m long, up to 2 m wide (each 2 m wide strip if route is wider) — on centre band Diversity Disability glare 0·5 lx Fig. 5.37 1 lx 0·5 lx 1m 2m Escape route lighting 5.20.7.2 Anti-panic (escape area) lighting Response time Minimum duration Colour rendering Minimum design value of 1 lx, on the floor along the centre line of the route Minimum design value 0.5 lx, on the floor of the centre band (i.e. at least 50% of the route width Illuminance on centre line < 40 (max./min.) Intensity limits: level routes from γ = 60° to 90° at non-level routes at all angles (γ) in the lower hemisphere Design value within 5 s of supply failing 1 hour Lamp Ra ≥ 40 See Tables 5.14 to 5.16 and Figures 5.38 and 5.39. These are open or reconfigurable areas including teaching spaces, sports/assembly/examination halls and cafeteria. It should be noted that there have been changes to the law governing fire safety in a number of countries. In the UK, the Regulatory Reform (Fire Safety) Order 2005(56) makes it the legal responsibility of building designers and owners/occupiers to risk-assess their premises for fire safety. This risk assessment would include emergency lighting for all areas, but in particular it should be noted that areas smaller than 60 m2, but which may be open to the public after dark, may require anti-panic emergency lighting. Recent practice in schools has been to suggest one luminaire near the exit door providing only partial illuminance to the room; this is not acceptable. 0·5 lx 0·5 m Fig. 5.38 0·5 m Escape area lighting Fig. 5.39 Emergency task spotlighting Table 5.14 Requirements for escape area lighting Item Value Area size Generally ≤ 60 m2 except in places of public assembly or where a sufficient risk is identified Minimum design value 0.5 lx on empty floor excluding 0.5 m wide perimeter band < 40 (max./min.) Intensity limits: level routes from γ = 60° to 90° 50% design value in 5 s and 100% design value in 60 s 1 hour Lamp Ra ≥ 40 Design illuminance Diversity Disability glare Response time Minimum duration Colour rendering Lighting for particular applications 77 Table 5.15 Requirements for lighting in fixed seated areas (i.e. areas in auditoria, sports halls, conference rooms, lecture theatres having fixed seating) Item Value Area size Design illuminance ≤ 60 m2 Minimum design value of 0.1 lx on a plane 1 m above floor/pitch line over seated areas; gangways should be treated as clearly defined routes < 40 (max./min.) Intensity limits: level routes from γ = 60° to 90° Design value in 5 s 1 hour Lamp Ra ≥ 40 Diversity Disability glare Response time Minimum duration Colour rendering Table 5.16 Requirements for lighting in high risk task areas (i.e. area where hazardous activity occurs that is to be made safe or terminated or where people may pass by) Fig. 5.40 Fixed seating area table Item Value Area size Design illuminance As defined by task size, location and plane Minimum 10% of maintained illuminance on the reference plane but at least 15 lx > 0.1 (min./average) Intensity limits: level routes from γ = 60° to 90° Design value in 5 s or faster if the risk requires it Period for which the risk to people exists Lamp Ra ≥ 40 Uniformity Disability glare Response time Duration Colour rendering 5.20.8 Installation, testing and maintenance The success of an emergency lighting system depends not only on the design, planning and selection of the correct equipment, but also on the satisfactory installation and maintenance of the equipment throughout its service life. It is vital that the designer specifies equipment that is fit for the purpose. Consideration should be given to the choice of products so that they are serviceable when installed and, if installed in places where access for maintenance will be restricted, will require virtually no servicing during their product life. Regular maintenance, servicing and testing of the emergency lighting installation is very important if it is to be operative when the need arises. The emergency lighting system should be installed as instructed by the designer of the scheme and also in accordance with the equipment manufacturer’s instructions. The designer usually provides a schedule of installation, including scheme plans and wiring/piping drawings in which the location of equipment, placing of protection devices and the choice and routing of wiring/piping are set out. The schedule or drawings may also give the sequence of fixing and connections, particularly of complex systems, that the installer should follow. All such schedules and drawings should be added to the log book on completion of the installation. These should be updated with information of all scheme modifications made during the life of the installation. Maintenance and servicing of the installation should be made regularly. This work should be carried out by a competent person*, appointed by the owner/occupier of the premises. The designer should provide a maintenance schedule that lists and gives details of replacement luminaire components such as lamp type, battery, fuses, cleaning and topping-up fluids. Caution should be exercised in servicing, as unenergised circuits may suddenly become energised automatically. Prime movers and generators will almost always be started without warning in an emergency or auto test, since a sensor remote from the plant enclosure initiates the sequence of operations. * A competent person is someone who has the necessary knowledge, training, experience and abilities to carry out the work (MSLL or equivalent qualification). 78 Lighting Guide 5: Lighting for education 5.20.9 Luminaires The luminaires must be suitable for the environmental conditions in which they are expected to function. Luminaires and signs should be cleaned at regular intervals that may coincide with the time of inspection. Any defects noted should be recorded in the log book and rectified as soon as possible. The cleaning interval is dependent on the atmospheric dirt in the installation. Serviceable components should be replaced by an approved part at the end of the recommended component service life. Self-luminous signs, such as a tritium-activated phosphor-coated signs, should be replaced at the specified end of service life. Note that these signs contain residual radioactive material and their disposal must be carried out by an authorised contractor. Photoluminescent signs must be placed such that they are externally lit at all times to ensure that the photo luminescent material is fully charged at all times. 5.20.10 Service schedule Inspection and maintenance should be carried out in accordance with a systematic schedule. A typical planned inspection/servicing schedule is as follows: — Check that defects recorded in the log book have been corrected. — Clean the exterior of luminaires and signs. — Check correct operation of luminaires and internally illuminated signs by operating the test facility. — Check correct operation of engine driven generator(s) and carry out the manufacturer’s recommended maintenance. — Check fuel tanks and oil and coolant levels and top up as necessary. — Check level of electrolyte in batteries of central battery systems and generator starter batteries. — Check that all indicator lamps are functioning. — Record data in the log book. — Check egress path to determine whether architectural and furniture changes have rendered the emergency lighting system ineffective. — Check egress path for obstructions that hinder escape during an emergency. Instructions issued by manufacturers should also be observed and added to the service schedule. Routine inspection and testing should be carried out at the intervals specified below. Records should be kept of the tests and the results obtained. Where self-testing or remote testing features are being used, those responsible for emergency lighting systems should verify that the tests have been conducted on schedule and have given satisfactory results. Details of routine testing are given in BS EN 50172(61). 5.20.11 Self-testing and remote testing systems An increasing trend is for emergency lighting to incorporate some form of selftesting facility, or for the luminaires to incorporate a remote monitoring feature. The electrical test should verify that any self-testing system performs as intended, and without impairing the integrity of the lighting design. Where selftesting or remote monitoring systems are used as the basis of compliance with section 12 of BS 5266-1(46), visual inspection of the installed equipment should be carried out at least annually to verify that it is in good mechanical condition. BS EN 62034(62) gives details of automatic test systems for battery powered emergency escape lighting. Lighting for particular applications 79 5.20.11.1 Daily It should be verified that the charging supply to the central battery systems is indicating normal operation. The emergency lighting record log book or monitoring system should be checked in order that recorded faults may be rectified. 5.20.11.2 Monthly A short-duration test should be performed, by simulating a failure of the general lighting power supply, to verify that all emergency luminaires are operating. This applies for both self-contained and centrally supplied systems. The duration of the function test should be as brief as possible, so as not to discharge batteries unduly or damage the lamps. Engine-driven generators should be checked for automatic starting and to ensure that they energise the emergency lighting system correctly. 5.20.11.3 Annually A full duration test of all systems should be performed, to verify that the emergency lighting provides its design output for the full design duration. The duration test should be arranged to occur at a point in time where the time needed to recharge batteries has the least impact on the occupation of the building. The signs and luminaires are cleaned if required. 5.20.12 Initial inspection certificate A model certificate can be found in BS 5266-1(46). 5.20.12.1 Maintenance schedule A maintenance schedule should be prepared as indicated in the service schedule. 5.20.12.2 Log book Record keeping is an important aspect of maintenance and recording the system condition. A log book should be kept on the premises in the care of a competent person appointed by the owner/occupier of the premises and should be readily available for examination by any duly authorised person. The log book should contain the following information: — date of any completion certificate, including any certificate relating to alterations — a complete set of plans and emergency lighting layouts for the building; a full set of schematics will be required where central battery and generator systems are employed — a schedule of plant and equipment requiring maintenance, including information regarding the frequency of testing — instructions that highlight planned maintenance tasks and give guidance on the execution of these tasks — a schedule of recording the outcome of all maintenance inspections and tests carried out, defects and remedial action — manufacturers’ installation and instruction manuals for each individual item of the system, and — a schedule detailing the quantity of each spare component (e.g. lamp, battery, fusing) to be stored on site to enable quick replacement of failed components; contact details for each manufacturer should also be included. Further guidance can be found in BS 5266(46), BS EN 1838(60) and ISO 30061/CIE S 020(63). 80 Lighting Guide 5: Lighting for education 6 Checklist for lighting design The designer should check systematically that all the factors relevant to the design of the lighting installation have been taken into account. In the following checklist the headings below indicate the areas to be considered and the most commonly occurring questions. In any specific situation there may be other questions which need to be considered. 6.1 Task/activity lighting (a) (b) (c) (d) Objectives: — Safety requirements: What hazards need to be seen clearly? What form of emergency lighting is needed? Is a stroboscopic effect likely? — Task requirements: Where are the tasks to be performed in the interior? What planes do they occupy? What aspects of lighting are important to the performance of these tasks? Are optical aids necessary? — Appearance: What impression is the lighting required to create? Constraints: — Statutory: Are there any statutory requirements that are relevant to the lighting installation? — Financial: What is the budget available, and what is the relative importance of capital and running costs including maintenance? — Physical: Is a hostile or hazardous environment present? Are high or low ambient temperatures likely to occur? Is noise from control gear likely to be a problem? Are mounting positions restricted, and is there a limit on luminaire size? — Historical: Is the choice of equipment restricted by the need to make the installation compatible with existing installations? Specification: — Source of recommendations: What is the source of the lighting recommendations used? How authoritative is this source? — Form of recommendations: Have all the relevant lighting variables been considered, e.g. design maintained illuminance, uniformity, illuminance ratios, surface reflectances and colours, light source colour, colour rendering group, limiting glare index, veiling reflections? — Qualitative requirements: Have the aspects of the design which cannot be quantified been carefully considered? General planning: — Daylight and electric lighting: What is the relationship between these forms of lighting? Is it possible or desirable to provide a control system to match the electric lighting to the daylight available? — Protection from solar glare and heat gain: Are the windows designed to limit the effects of solar glare and heat gain on the occupants of the building? Do the window walls have suitable reflectance? — Choice of electric lighting system: Is general, localised or local lighting for task or display most appropriate for the situation? Does obstruction make some form of local lighting necessary? — Choice of lamp and luminaire: Does the light source have the required lumen output, luminous efficacy, colour properties, lumen maintenance, life, run-up and re-strike properties? Is the proposed lamp and luminaire package suitable for the application? Is air handling heat recovery appropriate? Will the luminaire be safe in the environmental conditions? Will it withstand the environmental conditions? Does it have suitable Checklist for lighting design 81 maintenance characteristic and mounting facilities? Does it conform to BS 4533(64)/BS EN 60598-1(65) or other appropriate standard? Does the luminaire have an appropriate appearance and will it enable the desired effect to be created? Are reliable photometric data available? (e) 6.2 Lighting and energy efficiency — Maintenance: Has a maintenance schedule been agreed? Has a realistic maintenance factor been estimated based on the agreed schedule or, if not, have the assumptions used to derive the maintenance factor been clearly recorded? Is the equipment resistant to dirt deposition? Can the equipment be easily maintained, is the equipment easily accessible, and will replacement parts be readily available? — Control systems: Are control systems for matching the operation of the lighting to the availability of daylight and the pattern of occupancy appropriate? Is a dimming facility desirable? Have manual switches or local override facilities been provided, are they easily accessible and is their relationship to the lighting installation understandable? — Interactions: How will the lighting installation influence other building services? Is it worth recovering the heat produced by the lamps? If so, have the air flow rates been checked in relation to the operating efficacy of the lamps? Detailed planning: — Layout: Is the layout of the installation consistent with the objectives and the physical constraints? Has allowance been made for the effects of obstruction by building structure, other services, machinery and furniture? Has the possibility of undesirable high luminance reflections from specular surfaces been considered? Does the layout conform to the spacing-toheight ratio criteria? — Mounting and electrical supply: How are the luminaires to be fixed to the building? What system of electricity supply is to be used? Does the electrical installation comply with the latest edition (including any subsequent amendments) of BS 7671: Requirements for electrical installations. IEE Wiring Regulations. Seventeenth edition(66)? — Calculations: Have the design maintained illuminance and variation been calculated for appropriate planes? Has an acceptable maintenance programme been specified? Have the most suitable calculation methods been used? Has the glare rating been calculated? Have up-to-date and accurate lamp and luminaire through-life photometric data been used? — Verification: Does the proposed installation meet the specification of lighting conditions? Is it within the financial budget? Is the power density within the recommended range? Does the installation fulfil the design objectives? A lighting installation should meet the lighting requirements of a particular space in an energy efficient manner. An estimation of the energy requirements of a lighting installation needs to be made according to BS EN 15193: Energy performance of buildings. Energy requirements for lighting(22). It gives a methodology for a numeric indicator of energy performance of buildings. This indicator can be used for single rooms on a comparative basis only, as the benchmark values given in BS EN 15193 are intended for complete buildings. It is important not to compromise the visual aspects of a lighting installation simply to reduce energy consumption. Light levels as set in BS EN 12464-1(44) are minimum average illuminance values, and need to be obtained. Therefore, to achieve the required energy performance, consideration of 82 Lighting Guide 5: Lighting for education appropriate lighting systems, equipment, controls and the use of available daylight is essential. Energy efficiency calculations may also be required to prove compliance with local building regulations, such as Building Regulations Part L(18) for England and Wales. An energy efficiency checklist would include questions such as: 7 Lighting maintenance — Does the lighting design exceed 55 luminaire lumens per circuit watt for the teaching, office, industrial and storage spaces? — Do areas other than these also exceed 55 luminaire lumens per circuit watt, including display lighting where practical? — Are full lighting controls for daylight harvesting installed in all rooms that receive daylight? — Is manual on/off with absence override detection fitted to all interior luminaires? — Are lighting controls commissioned appropriately to the patterns or daylight and use? — Does the exterior lighting comply to a minimum of 80 lm/W for colour rendering light sources Ra < 60 and with 70 lm/W for light sources with Ra > 60? — Are suitable daylight and time controls fitted to all exterior lighting? — Is high frequency (HF) gear used for all luminaires? — Where dimming gear is fitted do the ballasts use > 0.5 W when no light is emitted? (From the year 2017, any new luminaire ballasts should use zero power when no light is emitted). In both lecture and conference spaces it is essential for the lighting equipment to be properly maintained. Lamps that have failed or are flickering not only fail in their function, but convey the impression to audience and lecturer alike that nobody cares. It is important that lamps that have failed be replaced promptly, and with lamps of precisely the same type and colour. In raked lecture theatres, access to the luminaires is often difficult from below. This is a point that the designer must bear in mind. It is strongly advisable for a group replacement scheme to be used, in which all of the lamps are replaced at set intervals. The reader is referred to the SLL Code for Lighting(8) on the maintenance of lighting systems. Other items such as blackout blinds, projection screens and lighting controls suffer damage relatively frequently. Any damage of this kind should be made good promptly. It can largely be avoided by using simple controls with clear instructions adjacent to the item concerned and using equipment of sufficiently robust construction to withstand the onslaughts of daily use. During the life of a lighting installation the amount of light it produces will diminish. This reduction is caused mainly by dirt building-up on the lamps, the luminaires or, in the case of natural lighting, on the windows. There will also be a reduction caused by dirt build-up on the internal surfaces of the rooms, diminishing their reflectance. Lamp light output will also reduce with ageing, some light sources losing more output than others. These reductions in lighting levels will need to be minimised if energy and money are not to be wasted, and to achieve this it is important to pay attention at the design stage to the proper maintenance of the lighting installation and of the building itself. This aspect should be discussed in advance with the users of the building to ensure that they are aware of the proposed maintenance strategy and its implications and obtain their cooperation. 82 Lighting Guide 5: Lighting for education appropriate lighting systems, equipment, controls and the use of available daylight is essential. Energy efficiency calculations may also be required to prove compliance with local building regulations, such as Building Regulations Part L(18) for England and Wales. An energy efficiency checklist would include questions such as: 7 Lighting maintenance — Does the lighting design exceed 55 luminaire lumens per circuit watt for the teaching, office, industrial and storage spaces? — Do areas other than these also exceed 55 luminaire lumens per circuit watt, including display lighting where practical? — Are full lighting controls for daylight harvesting installed in all rooms that receive daylight? — Is manual on/off with absence override detection fitted to all interior luminaires? — Are lighting controls commissioned appropriately to the patterns or daylight and use? — Does the exterior lighting comply to a minimum of 80 lm/W for colour rendering light sources Ra < 60 and with 70 lm/W for light sources with Ra > 60? — Are suitable daylight and time controls fitted to all exterior lighting? — Is high frequency (HF) gear used for all luminaires? — Where dimming gear is fitted do the ballasts use > 0.5 W when no light is emitted? (From the year 2017, any new luminaire ballasts should use zero power when no light is emitted). In both lecture and conference spaces it is essential for the lighting equipment to be properly maintained. Lamps that have failed or are flickering not only fail in their function, but convey the impression to audience and lecturer alike that nobody cares. It is important that lamps that have failed be replaced promptly, and with lamps of precisely the same type and colour. In raked lecture theatres, access to the luminaires is often difficult from below. This is a point that the designer must bear in mind. It is strongly advisable for a group replacement scheme to be used, in which all of the lamps are replaced at set intervals. The reader is referred to the SLL Code for Lighting(8) on the maintenance of lighting systems. Other items such as blackout blinds, projection screens and lighting controls suffer damage relatively frequently. Any damage of this kind should be made good promptly. It can largely be avoided by using simple controls with clear instructions adjacent to the item concerned and using equipment of sufficiently robust construction to withstand the onslaughts of daily use. During the life of a lighting installation the amount of light it produces will diminish. This reduction is caused mainly by dirt building-up on the lamps, the luminaires or, in the case of natural lighting, on the windows. There will also be a reduction caused by dirt build-up on the internal surfaces of the rooms, diminishing their reflectance. Lamp light output will also reduce with ageing, some light sources losing more output than others. These reductions in lighting levels will need to be minimised if energy and money are not to be wasted, and to achieve this it is important to pay attention at the design stage to the proper maintenance of the lighting installation and of the building itself. This aspect should be discussed in advance with the users of the building to ensure that they are aware of the proposed maintenance strategy and its implications and obtain their cooperation. Management of lecture and conference spaces 83 The designer should pay specific attention to the life and lumen prediction graphs for each light source, especially when considering LEDs. Across the range of light sources there are a number of different life measures for instance that vary from 90% lumen output to 50% failure of a batch of lamps. For LEDs, until there is international agreement on this fast developing technology, the designer should consult Guidelines for the specification of LED lighting products(45), which has been produced by a joint committee representing the SLL, the Institution of Lighting Engineers, the Lighting Industry Federation, the Professional Lighting Designers’ Association, the International Association of Lighting Designers, and the Highway Electrical Manufacturers and Suppliers Association. 8 Management of lecture and conference spaces For the purposes of managing lecture theatres there are three categories: (a) those supposedly devoted to a single subject or single department of an educational institution, e.g. the ‘nuclear physics’ theatre (b) those in common use by a wide variety of departments in an educational institution; often very heavily used (c) those in research institutes, professional institutions, museums, galleries and so on; usually relatively lightly used. In practice, all lecture theatres are on occasions used for purposes other than those intended, sometimes on a hire basis. 8.1 Visual clutter Fig. 8.1 A large lecture theatre kept clear of clutter though the wall behind the lecture station is relatively busy in design terms (photograph courtesy of Thorn Lighting) Mention has already been made in section 5.3.3.3 of the need to keep lecture rooms free of visual clutter, which means keeping them free of unwanted paraphernalia that serves only to distract the attention of the audience from the speaker. It is an essential part of managing a lecture theatre or conference room to see that unwanted paraphernalia is kept out, see Figure 8.1 below. Lecture theatres of category (a) are particularly prone to these intrusions; wall charts, glass cased specimens and glazed portraits of the great men of the subject serve to distract rather than inspire. Such items should only be permanently displayed if there is a real need to refer to them frequently, e.g. the periodic table in a chemistry lecture theatre. The absence of visual clutter is also welcome in lecture rooms and classrooms, where it can be equally distracting. Management of lecture and conference spaces 83 The designer should pay specific attention to the life and lumen prediction graphs for each light source, especially when considering LEDs. Across the range of light sources there are a number of different life measures for instance that vary from 90% lumen output to 50% failure of a batch of lamps. For LEDs, until there is international agreement on this fast developing technology, the designer should consult Guidelines for the specification of LED lighting products(45), which has been produced by a joint committee representing the SLL, the Institution of Lighting Engineers, the Lighting Industry Federation, the Professional Lighting Designers’ Association, the International Association of Lighting Designers, and the Highway Electrical Manufacturers and Suppliers Association. 8 Management of lecture and conference spaces For the purposes of managing lecture theatres there are three categories: (a) those supposedly devoted to a single subject or single department of an educational institution, e.g. the ‘nuclear physics’ theatre (b) those in common use by a wide variety of departments in an educational institution; often very heavily used (c) those in research institutes, professional institutions, museums, galleries and so on; usually relatively lightly used. In practice, all lecture theatres are on occasions used for purposes other than those intended, sometimes on a hire basis. 8.1 Visual clutter Fig. 8.1 A large lecture theatre kept clear of clutter though the wall behind the lecture station is relatively busy in design terms (photograph courtesy of Thorn Lighting) Mention has already been made in section 5.3.3.3 of the need to keep lecture rooms free of visual clutter, which means keeping them free of unwanted paraphernalia that serves only to distract the attention of the audience from the speaker. It is an essential part of managing a lecture theatre or conference room to see that unwanted paraphernalia is kept out, see Figure 8.1 below. Lecture theatres of category (a) are particularly prone to these intrusions; wall charts, glass cased specimens and glazed portraits of the great men of the subject serve to distract rather than inspire. Such items should only be permanently displayed if there is a real need to refer to them frequently, e.g. the periodic table in a chemistry lecture theatre. The absence of visual clutter is also welcome in lecture rooms and classrooms, where it can be equally distracting. 84 Lighting Guide 5: Lighting for education 8.2 Lecture attendants The term ‘lecture attendant’ refers to those individuals who actually assist in the performance of lectures. The job of such lecture attendants is to see that the lecturer’s needs are fulfilled, e.g. that the lights are raised or lowered at the right time, the sound is correct and so on. To do this, it is necessary for the attendant to give undivided attention to assisting the lecturer and to avoid distraction. Where there is a control booth or room for the lecture assistant, care should be taken that stray light and sound do not distract the audience from the presentation and that the assistant, who may be visible, does not cause distraction to the lecturer. To limit light nuisance, the assistant should be provided with a carefully shielded task light. Care should be taken to see that light from the audience area does not cause glare to the assistant, either on their equipment or within their view field of view of the lecture theatre. 8.3 Communication between lecturer and projectionist or projector In the majority of lectures in which images are shown, a laptop computer under the direct control of the lecturer is used. In these cases often the lecturer has complete control of the room and the controls available to them should be clearly marked, sufficiently distinct to be visible in near-darkness. The controls available to the lecturer should also include an on/off switch for any projector, as it often happens that there are long periods when projection is not required and the fan noise may distract and annoy the audience. Lighting controls are similar; it is best if they can be operated directly by the lecturer, but again the controls must be simple and clearly marked. Some duplicate controls for the lights should be provided near the main entrance door(s). There are occasions when control of the projection, sound and lighting has to be in the hands of an attendant, for example when a large array of demonstrations is presented or for a full day’s conference containing many different presenters and media. In this case the lecturer should have a speaker’s screen showing an image and perhaps speaker’s notes of the slide that the audience is currently viewing. There should also be a controller for advancing the presentation, though commonly these are now wireless. 8.4 Projection rooms and booths The traditional projection room adjacent to a lecture room is nowadays used more often as a control room than a projection room. Experience shows that such a room is essential in any lecture theatre seating more than 150. Besides housing the projection equipment, it may also be needed to house sound amplifying equipment, lighting controls, image recording and projection equipment, and possibly controls for the air conditioning system. A projection booth within a lecture theatre is not recommended unless situated where there is no risk of distraction or difficulty of access once an audience is seated. 8.5 Preparation and equipment rooms The multiplicity of audio/visual aid techniques of recent years have now converged normally to a single projector and sound system with, in some cases, an interactive screen. The need for separate lockable equipment rooms is less than before but some form of storage should be provided for the relevant cables and power extensions often required by visiting presenters. In large lecture theatres there should ideally be a large equipment room adjacent to and on the same floor as the demonstration area, which can be used to house items needed for only part of the presentation. The lighting in these rooms needs to be sufficient for safe set-up and removal of these items, which may include fine detail tasks, but should be suitably shielded from the main space so as to limit distraction to the audience. This can normally be achieved either through lighting controls in the equipment room, or by a suitable lobby between rooms. Lighting control sensors in these rooms should be positioned carefully to detect fine movement possibly shadowed by the body of the technician. Lighting costs 85 8.6 Problems for visiting lecturers The main problem facing the visiting lecturer is unfamiliarity with the lighting controls, and seeing that the audio/visual aids chosen will work satisfactorily on the apparatus provided, for instance that the presenter’s laptop computer connects to the projector. Reference has already been made to the necessity for lighting and projector controls to be clearly marked. They should be few in number and should be grouped separately from other controls. A control panel resembling a complex computer interface does nothing to ease the lecturer’s task unless it is blatant in its simplicity of operation. 8.7 Lectures involving demonstrations Access to the theatre/room from cars or vans is required. Demonstration equipment intended to be seen by large numbers of people must itself be large, and may obstruct the view of some members of the audience of either the projection screen or the lecturer. This is particularly the case in lecture rooms and conference rooms as distinct from raked lecture theatres. To avoid this problem the presentation area should be devoid of any fixed furniture, using loose tables or benches combined with the provision for additional theatrical style lighting where required. 9 Lighting costs 9.1 General The cost of lighting can be divided into three parts: (a) the capital cost of the equipment, including its installation, (b) the running costs, which include both maintenance and the cost of energy, and (c) the environmental or sustainability costs. It is important that all aspects are considered when the lighting is being designed. In terms of capital cost, the amount will be small compared to the total cost of the building and yet lighting has a major effect on its appearance and operation, and economies need to be considered carefully to ensure that they are not false economies. Energy and maintenance costs are a continuing burden on the operation of any educational building and need to be taken into account at the design stage to ensure that they can be kept at an acceptable level. The sustainability costs will include items such as recycling and replacement, for instance the cost of obtaining raw materials, transport and manufacture of replacement luminaires and that or returning the failed components to a recycling point and converting them into re-usable materials. For many buildings, the capital and running cost elements may be borne by different bodies, which can result in conflict. It is important therefore that the lighting designer produces a scheme which takes a balanced view of energy and cost efficiency, considering the true life cycle costs. 9.2 Emergency lighting 10 Equipment 10.1 Lamps Emergency lighting, by its very nature, introduces additional running costs. Even as a safety system it is important to consider the technologies used and make rational decisions about the life cycle costs. For instance the provision of traditional 8 W bulkheads for emergency lighting may introduce significant maintenance and environmental costs in lamp and battery replacement compared to well designed LED emergency lighting fittings, which have a longer light source life and use less battery material. Testing and maintenance of emergency lighting is essential and the designer should consider carefully the cost to building managers of the testing and regular maintenance visits necessary. The use of self-test and central test emergency products may negate the need to provide staff to test emergency systems and may regulate the number of maintenance visits to just those when components are reported as faulty. Where such self-test systems are used the provision of training and operation manuals that are simple to understand is essential. Characteristics of the main lamp types are summarised in Table 10.1. Lighting costs 85 8.6 Problems for visiting lecturers The main problem facing the visiting lecturer is unfamiliarity with the lighting controls, and seeing that the audio/visual aids chosen will work satisfactorily on the apparatus provided, for instance that the presenter’s laptop computer connects to the projector. Reference has already been made to the necessity for lighting and projector controls to be clearly marked. They should be few in number and should be grouped separately from other controls. A control panel resembling a complex computer interface does nothing to ease the lecturer’s task unless it is blatant in its simplicity of operation. 8.7 Lectures involving demonstrations Access to the theatre/room from cars or vans is required. Demonstration equipment intended to be seen by large numbers of people must itself be large, and may obstruct the view of some members of the audience of either the projection screen or the lecturer. This is particularly the case in lecture rooms and conference rooms as distinct from raked lecture theatres. To avoid this problem the presentation area should be devoid of any fixed furniture, using loose tables or benches combined with the provision for additional theatrical style lighting where required. 9 Lighting costs 9.1 General The cost of lighting can be divided into three parts: (a) the capital cost of the equipment, including its installation, (b) the running costs, which include both maintenance and the cost of energy, and (c) the environmental or sustainability costs. It is important that all aspects are considered when the lighting is being designed. In terms of capital cost, the amount will be small compared to the total cost of the building and yet lighting has a major effect on its appearance and operation, and economies need to be considered carefully to ensure that they are not false economies. Energy and maintenance costs are a continuing burden on the operation of any educational building and need to be taken into account at the design stage to ensure that they can be kept at an acceptable level. The sustainability costs will include items such as recycling and replacement, for instance the cost of obtaining raw materials, transport and manufacture of replacement luminaires and that or returning the failed components to a recycling point and converting them into re-usable materials. For many buildings, the capital and running cost elements may be borne by different bodies, which can result in conflict. It is important therefore that the lighting designer produces a scheme which takes a balanced view of energy and cost efficiency, considering the true life cycle costs. 9.2 Emergency lighting 10 Equipment 10.1 Lamps Emergency lighting, by its very nature, introduces additional running costs. Even as a safety system it is important to consider the technologies used and make rational decisions about the life cycle costs. For instance the provision of traditional 8 W bulkheads for emergency lighting may introduce significant maintenance and environmental costs in lamp and battery replacement compared to well designed LED emergency lighting fittings, which have a longer light source life and use less battery material. Testing and maintenance of emergency lighting is essential and the designer should consider carefully the cost to building managers of the testing and regular maintenance visits necessary. The use of self-test and central test emergency products may negate the need to provide staff to test emergency systems and may regulate the number of maintenance visits to just those when components are reported as faulty. Where such self-test systems are used the provision of training and operation manuals that are simple to understand is essential. Characteristics of the main lamp types are summarised in Table 10.1. Lighting costs 85 8.6 Problems for visiting lecturers The main problem facing the visiting lecturer is unfamiliarity with the lighting controls, and seeing that the audio/visual aids chosen will work satisfactorily on the apparatus provided, for instance that the presenter’s laptop computer connects to the projector. Reference has already been made to the necessity for lighting and projector controls to be clearly marked. They should be few in number and should be grouped separately from other controls. A control panel resembling a complex computer interface does nothing to ease the lecturer’s task unless it is blatant in its simplicity of operation. 8.7 Lectures involving demonstrations Access to the theatre/room from cars or vans is required. Demonstration equipment intended to be seen by large numbers of people must itself be large, and may obstruct the view of some members of the audience of either the projection screen or the lecturer. This is particularly the case in lecture rooms and conference rooms as distinct from raked lecture theatres. To avoid this problem the presentation area should be devoid of any fixed furniture, using loose tables or benches combined with the provision for additional theatrical style lighting where required. 9 Lighting costs 9.1 General The cost of lighting can be divided into three parts: (a) the capital cost of the equipment, including its installation, (b) the running costs, which include both maintenance and the cost of energy, and (c) the environmental or sustainability costs. It is important that all aspects are considered when the lighting is being designed. In terms of capital cost, the amount will be small compared to the total cost of the building and yet lighting has a major effect on its appearance and operation, and economies need to be considered carefully to ensure that they are not false economies. Energy and maintenance costs are a continuing burden on the operation of any educational building and need to be taken into account at the design stage to ensure that they can be kept at an acceptable level. The sustainability costs will include items such as recycling and replacement, for instance the cost of obtaining raw materials, transport and manufacture of replacement luminaires and that or returning the failed components to a recycling point and converting them into re-usable materials. For many buildings, the capital and running cost elements may be borne by different bodies, which can result in conflict. It is important therefore that the lighting designer produces a scheme which takes a balanced view of energy and cost efficiency, considering the true life cycle costs. 9.2 Emergency lighting 10 Equipment 10.1 Lamps Emergency lighting, by its very nature, introduces additional running costs. Even as a safety system it is important to consider the technologies used and make rational decisions about the life cycle costs. For instance the provision of traditional 8 W bulkheads for emergency lighting may introduce significant maintenance and environmental costs in lamp and battery replacement compared to well designed LED emergency lighting fittings, which have a longer light source life and use less battery material. Testing and maintenance of emergency lighting is essential and the designer should consider carefully the cost to building managers of the testing and regular maintenance visits necessary. The use of self-test and central test emergency products may negate the need to provide staff to test emergency systems and may regulate the number of maintenance visits to just those when components are reported as faulty. Where such self-test systems are used the provision of training and operation manuals that are simple to understand is essential. Characteristics of the main lamp types are summarised in Table 10.1. 86 Table 10.1 Summary of lamp types Lamp type Format Nominal size Power range (W) Control gear Efficacy (lm/W) Colour rendering group Colour appearance (K) Dimming options Suitable for central control system Linear fluorescent T16 (T5) (16 mm diam.) T16 (T5) miniature (16 mm diam.) T26 (T8) (26 mm diam.) Various Various 600–1500 mm 14–80 Electronic 60–95 1A–1B Yes Yes 150–530 mm 4–13 Electronic/magnetic 35–65 3 2700–4000 6000 (limited options) 3500 No No 600–1800 mm 18–70 Electronic/magnetic 55–95 1A–1B Yes Yes Various Various 16–120 18–70 Electronic Electronic 64–88 64–76 1B 1B 3000–4000 6000 (limited options) 3000–4000 3000–4000 Yes Limited Yes Yes Various 20–2000 Electronic/magnetic 70–115 1A–2B Very limited Yes; not suitable for frequent switching Linear fluorescent Linear fluorescent Compact fluorescent Compact fluorescent amalgam Metal halide* Various 3000–4000 6000 (limited options) 50–1000 Electronic/magnetic 65–125 4 2000 Very limited No (up to 150 for 600/1000 W lamps) * Metal halide and SON lamps can take several minutes to run up to full output and, immediately after being switched off, can take several minutes to re-strike. Some low wattage options can be run at reduced output on special electronic control gear but dimming range is limited and colour variations can occur. Lighting Guide 5: Lighting for education Single ended tubular, double ended and reflector High pressure sodium* SON tubular Equipment 87 10.2 Control gear A wide range of lamps require control gear of some kind to ensure correct running and starting of the lamp. This gear in various lamps controls either the voltage or the current and may itself operate at differing voltages and frequencies. 10.2.1.1 General principles Where available the designer should specify the most appropriate and efficient control gear for all lighting. In general this would imply high frequency (HF) or electronic control gear for all luminaires. Control gear should comply with the minimum targets set by the Energy-using Products Directive(17) for lighting. 10.2.1.2 Electromagnetic control gear for fluorescent light sources Generally electromagnetic gear used in fluorescent circuits is considered inefficient when compared to high frequency circuits, and causes user discomfort through 100 Hz flicker. In all teaching/learning buildings high frequency control gear should be used as standard except where a suitable case can be made on health and safety grounds or if alternative technologies are developed that remove the problem of flicker and improve the sustainable case for this technology. 10.2.1.3 Electronic control gear for fluorescent light sources Operating fluorescent lamps at high frequency has a number of advantages and most modern control gear is now of this type. Most electronic ballasts for fluorescent lamps are integrated into a single package that performs a number of functions including limiting the amount of harmonic distortion, controlling the amount of radio frequency interference, and protecting the ballast against high voltage mains peaks. Where high frequency ballasts are used with in-built protection fuses there will be no need to fit additional fused terminal blocks. In some ballasts it is possible to dim the lamp by use of an additional control signal, either analogue or digital signals. The designer should look carefully at the features and benefits that the various types offer, weighing up the true cost or energy implications. For instance, while it may be beneficial to dim rather than switch a luminaire in response to daylight, offering considerable energy savings in some installations, the parasitic power absorbed by the ballast and control system must be taken into account. 10.2.1.4 Electronic gear for HID light sources There are many types of high intensity discharge (HID) lamp, with different electrical requirements and a limited range of frequencies in which they can be operated. Also many lamp types do not show a significant gain in efficiency when operated on high frequencies. However, it is possible to gain a number of benefits from electronic gear for HID lamps. These include increased lamp life, elimination of visible flicker, better system efficacy, less sensitivity to fluctuations in mains voltage or temperature and the possibility of dimming with some lamp types. Not all these benefits are possible for all lamp types and all control gear combinations. However, the availability and quality of electronic gear available for HID lamps is rapidly increasing. 10.2.1.5 Transformers for low voltage light sources Many tungsten–halogen lamps are designed to run on low voltages the most common of which is 12 volts. Thus they need a device to reduce the supply voltage. The traditional way to do this was by using a transformer. As well as reducing the voltage, the transformer also isolates the lamp supply from the mains. This means that even under a fault condition the voltage in the secondary circuit will not rise significantly above the nominal output voltage and so it will always be safe to touch the conductors on the low voltage side. In all educational buildings transformers for halogen lamps should be of the electronic type with a minimum circuit efficacy of 22 lumens per circuit watt (lm/W) for a ‘pass’ rating, 29 lm/W for ‘good’ and 36 lm/W for ‘excellent’. 10.2.2 Drivers for LEDs LEDs need to be run at a controlled current to ensure proper operation. To provide this drivers are used. Most drivers take mains power and provide a 88 Lighting Guide 5: Lighting for education constant current output. However, it is possible to control some drivers so that output current is varied so that the LED may be dimmed. In more complex systems it is possible to dim three separate channels separately, so that when red, green and blue LEDs are used together it is possible to make colour changes. Most LED drivers can maintain their constant current output over a range of voltages so it is often possible to connect a number of LEDs in series on one driver. The designer should take care to avoid flicker inherent in cheaper LED drivers. For LED circuits to be considered efficient they should meet or exceed the same efficacy targets for other lighting. 10.3 Lighting controls Wherever practical lighting controls should be included to provide scene setting functionality where required and energy saving where users are unlikely to switch off lighting when not required. In daylit spaces lighting should be circuited according to the amount of daylight likely to occur in the area lit by the luminaire. Luminaires in daylight zones should then be switched, according to the daylight present. Preference must be given to systems that dim according to daylight and hence also provide for constant illuminance control from the luminaires. 10.3.1 Options for control There are a number of factors that need to be considered in any control system; these are the inputs to system, how the system controls the lighting equipment and what is the control process that decides how a particular set of inputs will impact on the lighting. Thus for a control system to function it must have input devices such as switches, presence detectors, timers and photocells. Control processes may consist of a simple wiring network through to a computer-based control system. The system may control luminaires in a number of ways, from simply switching them on and off to dimming the lamp and, in more complex systems, causing movement of spotlights and colour changes. 10.3.2 Input devices Lighting controls require a number of inputs to make them function, broadly they are classified as follows. 10.3.2.1 Manual inputs These vary from simple switches used to turn the lights on though dimmer switches and remote control units that interface to a control system to lighting control desks that are used in theatres. The point of these units is to allow people to control the lighting and care is always needed in the application of such devices to ensure that users of the system can readily understand the function of any such control. 10.3.2.2 Presence detectors Most presence detectors are based on passive infrared (PIR) detectors. However some devices are based on microwave or ultrasonic technology. PIR devices monitor changes in the amount of infrared radiation that they are receiving. The movement of people in a space will be detected by them and this can be signalled to a control system. Thus if a device detects the presence of a person this can be used to signal the control system to switch the lights on, but if no persons have been detected for some time this can be used to signal that the lights can be turned off. It is strongly recommended that these detectors, when used in educational spaces, should be used for absence detection with a manual override for teaching staff. This enables sufficient flexibility for teaching purposes, but also offers the maximum energy savings. In order to achieve an excellent efficiency rating in an educational building, more than 60% of luminaires need to be controlled for daylight and absence using controls within the parasitic power limitations set in the Energyusing Products Directive(17). 10.3.2.3 Timers Most computerised control systems have timers built in so that they can turn the lighting on or off at particular times. However, there are also a large number of Equipment 89 time switches available that can turn lamps on and off at given times. Timers for external lighting are available that change the time at which they operate throughout the year, so that the lamps are switched at dawn and dusk. Timers should be carefully considered and only those used that respond also to ambient conditions or time of year and so offer maximum energy savings. 10.3.2.4 Photocells There are many different types of photocells used to control lighting. The simplest to use are those that switch on at one illuminance value and switch off at another and are often used outdoors for car park, security and amenity lighting. Some photocells communicate the illuminance value detected to a central control system, which uses the information to adjust the lighting in some way. Some photocells are mounted on ceilings with shields around them so that they only receive light reflected from the working plane; this allows them to act like luminance meters and, provided the reflectance of the working plane remains constant, they can be set to provide constant illuminance. Photocell control should be considered essential for all teaching spaces as considerable daylight will be available. They should also be fitted to all external lighting and to lighting elsewhere in the space where daylight is sufficient. As their use in occupied spaces may lead to nuisance switching the designer should consider the use of dimming luminaires where this is more appropriate. 10.3.3 Control processes and systems In the case of simple control systems these are generally configured as some form of automated switching in the power supply to a luminaire or group of luminaires. However, more complex systems are generally configured as a network of devices including luminaires, sensors and control inputs. In most systems the devices are physically connected using some form of cabled network or based on the local area network (LAN). There are several systems in common use for lighting systems and care needs to be taken to specify the correct type for each component in the system. The most common systems offer differing levels of functionality and speed of response. The designer should consider carefully the needs of the controls system, for instance the speed of response and number of channels available would make the DMX512 protocol an obvious choice for theatre, drama and some conference rooms, whereas DSI or DALI would be more appropriate for classrooms. In all cases a control strategy needs to be developed and this should consider primarily the efficiency savings possible and the comfort needs of the occupants. Too complex a system will often render the system inoperable to all but the most determined user. 10.3.4 Recommended minimum controls provision The minimum controls provision recommended for various types of space are given in Table 10.2 below. 10.4 Disposal of used lighting equipment The WEEE Regulations(25) make business users, manufacturers and retailers of electrical and electronic equipment (EEE) responsible for making sure their goods do not end up in landfill or incineration, where the toxic chemicals, metals and associated solders, glues and plastics can cause environmental and health problems. Original equipment manufacturers (OEMs) now have cradle-to-grave responsibility for their electrical products, having to pay for the treatment and recycling of all affected products. The designer should ensure that any equipment they specify is suited to recycling and that the producer, who may be the wholesaler, electrical contractor, importer or OEM, complies with the WEEE Regulations. The installer who removes old equipment, or purchases new, should ensure that all obsolete luminaires or other EEE is dealt with accordingly. 90 Lighting Guide 5: Lighting for education Table 10.2 Recommended minimum controls provision Type of space Description Recommended minimum controls Owned space A space such as a small room for one or two people who control the lighting, e.g. a cellular office or tutorial room. Shared space A multi-occupied area, e.g. classroom, common room, an open-plan office or craft area. Temporarily owned space A space where people are expected to operate the lighting controls while they are there, e.g. a lecture or meeting room. Occasionally visited space A space where people generally stay for a relatively short period of time when they visit the space, e.g. a storeroom or toilet. A space where individual users require lighting but are not expected to operate the lighting controls, e.g. a corridor or atrium. Manual switch by the door with absence* override. Separate circuit for daylight dimming, or switching, of luminaires close to the window in daylight spaces. Manual switch by the door with absence* override. Separate circuits for daylight dimming or switching of luminaires in appropriate zones according to the amount of daylit for daylight spaces. Local manual control with absence* override. Sensor(s) should be suitably mounted to pick up the movement of occupants and speaker. Manual on with absence* override. Presence detection may be acceptable provided sensors use no more than 0.5 W. Time switching, or manual on with absence* override, or presence provided individual sensors use no more than 0.5 W. Separate circuits for daylight dimming or switching of luminaires in appropriate zones according to the amount of daylight for daylit spaces. Time switching, scene setting or central switching by a responsible person. Un-owned space Managed space A space where lighting is under the control of a responsible person, e.g. a conference room, theatre or sports hall. Separate circuits for daylight dimming or switching of luminaires in appropriate zones according to the amount of daylight for daylit spaces. * Absence sensors should be circuited such that they switch themselves off and hence use zero power when the lighting is off. 11 Glossary The definitions and explanations given in this glossary are intended to help readers to understand this Lighting Guide. They are based on BS EN 12665: Light and lighting. Basic terms and criteria for specifying lighting(67), which should be consulted if more precise definitions are needed. adaptation The process by which the state of the visual system is modified by previous and present exposure to stimuli that may have various luminances, spectral distributions and angular subtenses. adjoining spaces Foyers, ante-rooms, lobbies and corridors immediately adjoining teaching spaces listed in this Lighting Guide. chromaticity The property of a colour stimulus defined by its chromaticity coordinates, or by its dominant or complementary wavelength and purity taken together. 100 Lighting Guide 5: Lighting for education Appendix A1: luminance limits and display screen equipment The following flowcharts offer suggestions to ensure that the luminance is appropriate to the type of display screen equipment in use, see section 5.10.2. They use a 95% satisfaction criterion, i.e. 95% of users would not experience problems with veiling reflections at the luminance limits indicated. Size of light source Brightness of light source DSE type DSE polarity Suggestion < 200 cd/m2 All types All polarities OK to use Negative Change display polarity or surface finish Positive OK to use Negative OK to use Positive OK to use Negative OK to use Positive Change display polarity Negative Change display polarity or surface finish Positive OK to use if LB > 400 cd/m2 or change finish Negative OK to use Positive OK to use Negative Change display polarity Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 700 cd/m2 or change finish Negative Change display polarity Positive OK to use Negative Change display polarity Positive OK to use if LB > 600 cd/m2 Negative Change display polarity or surface finish Positive OK to use if LB > 900 cd/m2 or change finish Negative Change display polarity Positive OK to use if LB > 300 cd/m2 Negative Change display polarity Positive OK to use if LB > 800 cd/m2 Glossy LCD 200–300 cd/m2 Matt LCD Project IWB Glossy LCD 300–500 cd/m2 Matt LCD Project IWB Angular diameter 15° Glossy LCD 500–1000 cd/m2 Matt LCD Project IWB Glossy LCD 1000–1500 cd/m2 Fig. A1.1 Evaluation and correction of glare in display screen equipment (DSE) for large light sources (15° angular diameter) such as large windows or atria Matt LCD Project IWB Abbreviations and symbols LB = background luminance on display screen (cd/m2); LCD = liquid crystal display; IWB = interactive white board; ‘Positive’ polarity means dark text on light background; ‘Negative’ polarity means light text on dark background Appendix A1: luminance limits and display screen equipment Size of light source 101 Brightness of light source DSE type DSE polarity Suggestion < 300 cd/m2 All types All polarities OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 200 cd/m2 or change finish Negative OK to use Positive OK to use Negative Change display polarity Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 400 cd/m2 or change finish Negative OK to use Positive OK to use Negative Change display polarity Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 500 cd/m2 or change finish Negative OK to use Positive OK to use Negative Change display polarity Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 700 cd/m2 or change finish Negative Change display polarity Positive OK to use Negative Change display polarity Positive OK to use if LB > 500 cd/m2 Glossy LCD 300–500 cd/m2 Matt LCD Project IWB Glossy LCD 500–700 cd/m2 Matt LCD Project IWB Angular diameter 10° Glossy LCD 700–1000 cd/m2 Matt LCD Project IWB Glossy LCD 1000–1500 cd/m2 Fig. A1.2 Evaluation and correction of glare in display screen equipment (DSE) for medium sized light sources (10° angular diameter) such as small windows or skylights Matt LCD Project IWB Abbreviations and symbols LB = background luminance on display screen (cd/m2); LCD = liquid crystal display; IWB = interactive white board; ‘Positive’ polarity means dark text on light background; ‘Negative’ polarity means light text on dark background 102 Lighting Guide 5: Lighting for education Size of light source Brightness of light source DSE type DSE polarity Suggestion < 500 cd/m2 All types All polarities OK to use Negative Change display polarity or surface finish Positive OK to use Negative OK to use Positive OK to use Negative OK to use Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 300 cd/m2 or change finish Negative OK to use Positive OK to use Negative OK to use Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 500 cd/m2 or change finish Negative OK to use Positive OK to use Negative Change display polarity Positive OK to use Negative Change display polarity or surface finish Positive OK to use if LB > 800 cd/m2 or change finish Negative OK to use Positive OK to use Negative Change display polarity Positive OK to use Glossy LCD 500–700 cd/m2 Matt LCD Project IWB Glossy LCD 700–1000 cd/m2 Matt LCD Project IWB Angular diameter 1° Glossy LCD 1000–1500 cd/m2 Matt LCD Project IWB Glossy LCD 1500–3000 cd/m2 Fig. A1.3 Evaluation and correction of glare in display screen equipment (DSE) for small light sources (1° angular diameter) such as luminaires Matt LCD Project IWB Abbreviations and symbols LB = background luminance on display screen (cd/m2); LCD = liquid crystal display; IWB = interactive white board; ‘Positive’ polarity means dark text on light background; ‘Negative’ polarity means light text on dark background INDEX Note: page numbers in italics refer to figures; page numbers in bold refer to tables. Index Terms Links A absence control 34 88 16–17 24 3 90 57–58 90 ante-rooms 57 58 84 anti-panic (escape area) lighting 76 76 77 architectural form and daylighting 13 23–24 24 access doors see entrances acoustic considerations adaptation, visual adjoining spaces architectural integration 4–5 architectural models 36–37 area lighting see exterior lighting area-weighted average reflectance 25 art rooms 39 artificial sky 37 60–62 assembly halls see auditoria atria 14 15 23 40 audience lighting 41–43 52 audio-visual presentation 49 auditoria 39 77 3 21 29 30 battery powered emergency lighting 75 78–79 biodynamic lighting 34 blackout arrangements 47 see also conference rooms; lecture theatres automatic controls see controls average illuminance awnings B blinds 66 28–29 see also external blinds; internal blinds ‘borrowed light’ 14 This page has been reformatted by Knovel to provide easier navigation. 93 24 Index Terms Links brise soleil 23 28 BS 5266-1 78 79 BS 5489-1 71 BS 5499 73 BS 8206-2 23 BS EN 1838 73 BS EN 5266 49 BS EN 12193 20 BS EN 12464 20 BS EN 13201 71 BS EN 15193 6 BS EN 50172 78 BS EN 62034 78 BS EN ISO 9241-307 59 BS ISO 3864 73 British Standards building fabric, and daylight design building facades 25 31 70 81 7 8 81 59 13 13–14 15 building obstructions 13 25 building orientation 13 67 3 6 canopies 29 30 canteens 40 building form see architectural form Building Regulations C capital costs 9 85 car parking 69 72 CCTV surveillance 72 ceiling heights 23 checklist for lighting design 80–81 chromaticity 90 CIE 1974 general colour rendering index 91 circadian system 10 circulation areas exterior 68–69 69 interior 39 57–58 classification of spaces 38 This page has been reformatted by Knovel to provide easier navigation. 25 8 Index Terms Links classrooms 51 colour interest 33 daylight design 27 depths and heights 23 design tools 40 5 electric lighting 17 natural lighting benefits 11–12 performance requirements 39 veiling reflections and glare 32 clean room classification 62 clerestory windows 14 climate-based daylight modelling colour appearance colour interest colour recognition 60 17–19 4 20 91 20 33 48 3 colour rendering 91 colour rendering index (CRI) 3 39–40 91 colour temperature 4 34 91 53–54 91 committee rooms common rooms 39 computer display screens see display screen equipment (DSE) computer modelling 36–37 computer projection 47 49 66–67 84 51–53 77 82 see also interactive whiteboards/display screens computer visualisation 36–37 concert halls 65 conference rooms 40 94 Construction (Design and Management) Regulations 2 contrast ambient/task lighting 40 definition 91 room surfaces 20 25 window walls 14 30 see also luminance distribution contrast rendering factor 91 control rooms 50–51 84 controls 34–35 88–89 blinds and shades 28 checklist 81 This page has been reformatted by Knovel to provide easier navigation. Index Terms Links controls (Cont.) conference rooms 52 configuration 89 control gear 87–88 daylight sensing 34 energy efficiency 5 input devices 35 88–89 integrated daylighting and electric lighting 17 internal blinds 15 lecture rooms/theatres 48 multi-purpose rooms 56–57 recommended minimum provision 90 special educational needs 67 correlated colour temperature (CCT) corridors costs 4 34 39 57 8–10 85 courtyards, daylighting 28 craft rooms 39 60–62 curtains 27 30 cut-off 91 cut-off angle 31 31 20–21 91–92 cylindrical illuminance 91 91 D dance studios 64–65 daylight design 4–5 committee/meeting rooms 53–54 daylight modelling 17–19 daylight quantity 24–26 lecture rooms 46–47 lighting controls 12 22–31 24–25 40 67 5 multi-purpose rooms 54 performance requirements 40 special educational needs 67 sports halls and gymnasia 63 daylight factor 11–17 24 92 daylight matching lamps daylight quality daylight sensing controls 34 26–28 34 35 This page has been reformatted by Knovel to provide easier navigation. Index Terms Links demonstration areas 39 demonstration equipment 85 design and technology areas 32 design checklist 43–44 49 39 60–62 92 80–81 design objectives and constraints 1–2 diffused lighting 92 dimmers 48 dining halls 40 direct lighting 92 directional lighting 21 22 disability glare 29 93 discharge light sources flicker 32 fluorescent lights 32 high frequency 32 86 87 discharge light sources high intensity discharge (HID) lamps 32 87 high pressure sodium lamps 41 86 metal halide sources 42 56 86 discomfort glare 29 36 93 display lighting 53 56 display screen equipment (DSE) 58–59 luminance limits 59 59–60 60 veiling reflections and glare 31 32 60 see also interactive whiteboards/display screens disposal of used equipment 89 drama studios 64 64–65 E Education (School Premises) Regulations 2–3 efficacy see luminance efficacy targets efficiency, energy see energy efficiency electric lighting 17 electrical supply 81 emergency lighting 75 electromagnetic control gear 87 electronic control gear 87 emergency escape lighting 31–35 78–79 72–79 anti-panic (escape area) lighting 76 costs 85 76 This page has been reformatted by Knovel to provide easier navigation. 77 100–102 Index Terms Links emergency escape lighting (Cont.) definition 92 laboratories and workshops 62 lecture rooms/theatres 49 emergency power supplies 75 end user needs and preferences 13 energy consumption 17 5 energy efficiency 5–8 design criteria classes 81–82 8 requirements 5–6 targets 6 Energy Performance in Buildings Directive (EPBD) Energy-using Products Directive entrance halls 6–8 7 40 57 49 58 6 5–6 39 entrances exterior lighting 68 to lecture rooms/theatres 47 environmental design 4–5 passive integration 10 see also daylight design EPBD (Energy Performance in Buildings Directive) 6 equipment disposal 89 equipment rooms 84 escape area lighting 76 76 77 escape route lighting 73–76 74 76 escape route signage 72–73 exhibition lighting 56 exit signs 49 72–73 68–72 69 external blinds 28 29 external building obstructions 13 25 25 external shades 28 29 29 exterior lighting external view 26–28 F facade design 13–14 fibre optic light distribution 16 fire risk assessment 76 flicker 32 flip charts 53 15 92 This page has been reformatted by Knovel to provide easier navigation. 76 30 Index Terms Links floodlighting 69–71 fluorescent lights 32 footways 72 86 87 foyers see entrance halls full height glazing 14 full spectrum fluorescent lighting 11 furnishings 48 52–53 games areas 69 69–70 general colour rendering index 91 G general lighting 3 general purpose halls 70 71 92 64–65 glare, definition 92 glare control daylighting 28–31 electric lighting 31 escape route lighting 73–74 74 lecture rooms/theatres 42 45 multi-purpose rooms 56 special educational needs 67 46 glazed roofs see rooflights glazing see windows gloss finishes 32 gymnasia 40 63 handicraft rooms 39 60–62 hazardous situations 62 73 natural lighting benefits 10 11–12 ultraviolet (UV) radiation 10 H 76 77 76 77 health issues hearing impairment 67 heliodon 37 high frequency discharge lamps 32 high intensity discharge (HID) lamps 32 87 high pressure sodium lamps 41 86 high risk task areas 62 73 horizontally stacked shading 15 This page has been reformatted by Knovel to provide easier navigation. Index Terms Links human visual system 3 I illuminance definition 93 recommended 19 19 39–40 uniformity 25 38 93 see also daylight factor; luminance immediate surrounding area independent schools 93 3 indirect lighting 19 information technology (IT) rooms 39 initial illuminance 93 inspection, emergency lighting 93 78–79 installation, emergency lighting 77 installed loading 93 integrated daylighting and electric lighting 17 34 35–36 interactive whiteboards/display screens 32 51 65–66 20 33 48 28–29 29 47 internal glazing 14 28 28 internal shades 28 29 29 interpretation booths 53 ISO 2603 53 IT (information technology) rooms 39 interior decoration colour interest conference rooms 52–53 lecture rooms/theatres 48 internal blinds K keystone effect 94 kitchens 40 L laboratories 39 lamp lumen maintenance factor 94 lamp survival factor 94 60–62 lamps choice of lamp and luminaire 34 41–42 This page has been reformatted by Knovel to provide easier navigation. 86 88 Index Terms Links lamps (Cont.) correlated colour temperature (CCT) 4 34 luminaire efficacy 6 8 31 31 31 41 45–51 94 83 shielding angles 91 see also discharge light sources; LEDs (light emitting diodes) language laboratories 39 lecture attendants 84 lecture rooms 39 lecture theatres 41–51 daylighting 40 definition 94 lighting and projection control 84 lighting maintenance 82 management 85 83–85 performance requirements LEDs (light emitting diodes) drivers 39 77 32 41 75 40 62 87–88 legal requirements 2–3 daylight design 17 energy efficiency 6–8 libraries 39 life cycle costs 9 light nuisance 70–71 light output ratio 94 light pipes 16 light pollution 70–71 light traps 49–50 light trespass 71 71 71 lighting controls see controls lighting energy numeric indicator (LENI) 6 7 lighting scenes 35 48 lightshelves 15 lightwells 14 lines of sight see sight lines lobbies 57 local lighting 94 localised lighting 67–68 58 94 see also task lighting log books, emergency lighting 79 louvre blinds 29 This page has been reformatted by Knovel to provide easier navigation. 94 Index Terms Links low voltage light sources 87 luminaires cut-off angle 31 31 91 emergency lighting 74 74 75 78 light output ratio 94 lighting fitting 95 maintenance factor 95 mounting height 56 60 100–102 selection checklist 58 80–81 spacing/height ratio 95 task lighting 68 see also lamps luminance definition 94 for display screen equipment 59 59–60 3 90 3–4 29 24–25 28 see also illuminance luminance adaptation luminance distribution daylighting modelling 33 36 task/ambient lighting luminaire efficacy targets 5 40 6 6 8 M machine rooms 32 mains ripple 32 maintained illuminance 39–40 93 maintenance 8 82–83 checklist 81 emergency lighting 77–79 maximum illuminance 93 mean cylindrical illuminance 20–21 meeting rooms 40 53–54 metal halide sources 42 56 microstructure prismatic materials 16 mnimum illuminance 93 modelling 36–37 modeling index 21 22 motion detectors see presence detectors This page has been reformatted by Knovel to provide easier navigation. 86 Index Terms Links mounting height 95 emergency lighting 74 75 luminaires 56 58 safety signs 73 multi-purpose halls 64–65 multi-purpose rooms 54–57 music practice rooms 39 musical performances 65 95 N natural lighting design considerations 12–17 learning and health benefits 11–12 see alsodaylight design natural ventilation 23 no-sky line 26 24 O offices 40 operational costs 9 85 orientation of building 13 67 outdoor learning 11 outdoor lighting 68–72 69 parking areas 69 72 passive integration 10 pedestrian footways 72 performance requirements 38 39–40 escape area lighting 76 77 exterior lighting 69 71 P photocell control 89 photoluminescent signs 78 planning submissions 16 power supplies for emergency lighting 75 78–79 practical work, rooms for 39 51 60–62 preparation rooms 39 58 84 presence detectors 88 This page has been reformatted by Knovel to provide easier navigation. 95 Index Terms Links presentation areas lecture rooms/theatres 43–44 teaching rooms 47–48 51 presentation walls 20 privacy problems 27 projection screens 65–67 29 see also computer projection psychological effects 10–11 R raked seating 42 reception areas 40 recycling 9 reflectance, definition 95 reflective surfaces 14 Regulatory Reform (Fire) Order (2005) 76 remote testing, emergency lighting 44 44 10 89 16 19 20 78–79 retractable screens 29 30 road lighting 71 71 roof overhangs 30 rooflights 14 daylight factor 24 daylight factor calculation 25 discomfort glare 30 lecture rooms 47 room depth 23 room function and daylight design 13 room index 95 15 30 26 26 room surfaces colour 20 33 reflectance 14 16 wall lighting 35 S safety signs 72–73 73 ‘scene setting’ controls 35 48 science laboratories 39 60–62 seasonal affective disorder (SAD) security lighting 10–11 72 This page has been reformatted by Knovel to provide easier navigation. 19 20 Index Terms Links self-luminous signs 78 self-testing, emergency lighting semi-direct lighting 78–79 95 service schedules, emergency lighting 78–79 servicing, emergency lighting 77–78 shading, and architectural form 23 shading systems 15 30 44 45 see also blinds; external shades; internal shades sight lines, lecture rooms/theatres signage, escape routes 46 72–73 sky luminance 29 30 23–24 28–31 36 40 67 skylights see rooflights solar design space planning 23 spacing/height ratio 95 special educational needs (SEN) 13 splayed reveals 30 sports halls 40 55 63 77 sports pitches 69 69–70 70 71 spotlights 45 50 56 staff rooms/offices 39 stage areas 49–50 56 staircases 39 57–58 74 stock rooms 39 stroboscopic effects 32 62 96 sunlight human exposure to 11 penetration into building 36 redirection systems 16 shading systems 15 see also solar design supplier registration 9 surface finishes 32 48 54 surface reflectance 14 16 19 20 9 9 85 95 sustainability issues swimming pools 5 40 switches see controls This page has been reformatted by Knovel to provide easier navigation. Index Terms Links T task lighting 67–68 and ambient lighting 5 design checklist 40 80–81 emergency 62 73 76 64–65 teaching rooms, definition 96 technical drawing rooms 39 television equipment 66 testing, emergency lighting 77 theatrical lighting 50 64 49–51 65 13 15 theatrical presentations thermal design, and daylight design timers 77 88–89 transformers, for low voltage light sources 87 U ultraviolet (UV) radiation 10 unified glare rating (UGR) 31 useful daylight illuminance (UDI) 39–40 18–19 V veiling reflections 32–33 96 ventilation 23 24 vertical shading 15 video equipment 66 view (outlook) 28 26–28 virtual daylight models 36 vision, human 3 visual acuity 96 visual aids 37 66–67 visual amenity 3–4 visual clutter 83 visual comfort 19 visual field 96 visual function 33 96 3 visual impairment 67 visual interest 3–4 4 3–4 4 see also colour interest visual lightness This page has been reformatted by Knovel to provide easier navigation. 19 47 Index Terms Links visual performance 96 W waiting areas 58 wall lighting 35 wall thickness, and daylight design 13 Waste Electrical and Electronic Equipment (WEEE) Regulations whiteboards 9 89 53 65–66 lighting design 32–33 luminaires 65–66 66 presentation walls 20 29 veiling reflections 32 see also interactive whiteboards/display screens window walls windows daylight design lecture rooms/theatres 14 30 4 30 13–14 14 47 view 26–28 wall contrast 14 30 39 60–62 see also rooflights; shading systems workshops This page has been reformatted by Knovel to provide easier navigation. 23 25–26