Power System Analysis Lecture 9: Transformers Announcements • Please read Chapter 3 • HW 4 is 4.32, 4.41, 5.1, 5.7, 5.14; this one must be turned in on Sept 22 (hence there will be no quiz that day) 1 Three Line Models Long Line Model (longer than 200 miles) l tanh sinh l Y ' Y 2 use Z ' Z , l 2 2 l 2 Medium Line Model (between 50 and 200 miles) Y use Z and 2 Short Line Model (less than 50 miles) use Z (i.e., assume Y is zero) 2 Power Transfer in Short Lines •Often we'd like to know the maximum power that could be transferred through a short transmission line V1 + - I1 I1 Transmission Line with Impedance Z S12 + S21 - V2 * V1 V2 * S12 V1I1 V1 Z with V1 V1 1 , V2 V2 2 Z Z Z 2 S12 V1 V1 V2 Z Z 12 Z Z 3 Power Transfer in Lossless Lines If we assume a line is lossless with impedance jX and are just interested in real power transfer then: 2 P12 jQ12 V1 V1 V2 90 90 12 Z Z Since - cos(90 12 ) sin 12 , we get V1 V2 P12 sin 12 X Hence the maximum power transfer is P12Max V1 V2 X 4 Limits Affecting Max. Power Transfer • Thermal limits – – – – limit is due to heating of conductor and hence depends heavily on ambient conditions. For many lines, sagging is the limiting constraint. Newer conductors limit can limit sag. For example, in 2004 ORNL working with 3M announced lines with a core consisting of ceramic Nextel fibers. These lines can operate at 200 degrees C. Trees grow, and will eventually hit lines if they are planted under the line. 5 Other Limits Affecting Power Transfer • Angle limits – while the maximum power transfer occurs when line angle difference is 90 degrees, actual limit is substantially less due to multiple lines in the system • Voltage stability limits – as power transfers increases, reactive losses increase as I2X. As reactive power increases the voltage falls, resulting in a potentially cascading voltage collapse. 6 Example 5.8 765.0 kV 0.0 Deg 816.7 kV -11.4 Deg 847.3 kV -19.5 Deg 857.8 kV -27.3 Deg A A A MVA MVA MVA A A A MVA MVA MVA A A A MVA MVA MVA A A A MVA MVA MVA A A MVA MVA slack 9000 MW -2912 Mvar 9000 MW 0 Mvar 7 Transmission Line Series Compensation • One way to increase the transmission capacity of a transmission line that is limited by its reactance is to add series compensation – Capacitors are placed in series with the transmission line (covered in Example 5.10) Image shows BPA series capacitors in a 500 kV line Image: https://www.bpa.gov/news/newsroom/Pages/Chief-engineers-reunite-reminisce-for-BPAs-75th.aspx Transmission Line Series Compensation • Amount of series compensation is expressed as a percentage of the total line reactance (e.g., 50%) • The series capacitance is usually setup so that it can be bypassed sometimes – There can be excessive reactive power generation on the system during light loads, like at night • There can be a concern with sub-synchronous interactions (SSI) fn XC 1 f0 XL LC Example 5.10 765.0 kV 765.0 kV slack 2200.0 MW YES -0.2 Mvar YES Line Angle Difference: -21.4 Deg 2200 MW 0 Mvar Transformers Overview • Power systems are characterized by many different voltage levels, ranging from 765 kV down to 240/120 volts. • Transformers are used to transfer power between different voltage levels. • The ability to inexpensively change voltage levels is a key advantage of ac systems over dc systems. • In this section we’ll development models for the transformer and discuss various ways of connecting three phase transformers. 11 Transmission to Distribution Transfomer 12 Transmission Level Transformer 13 Ideal Transformer • First we review the voltage/current relationships for an ideal transformer – – – no real power losses magnetic core has infinite permeability no leakage flux • We’ll define the “primary” side of the transformer as the side that usually takes power, and the secondary as the side that usually delivers power. – primary is usually the side with the higher voltage, but may be the low voltage side on a generator step-up transformer. 14 Ideal Transformer Relationships Assume we have flux m in magnetic material. Then 1 N1m d 1 2 N 2m d 2 d m d m v1 N1 v2 N2 dt dt dt dt d m v1 v2 v1 N1 a = turns ratio dt N1 N2 v2 N2 15 Current Relationships To get the current relationships use ampere's law mmf H idL N1i1 N 2i2' H length N1i1 N 2i2' B length N1i1 N 2i2' Assuming uniform flux density in the core length N1i1 N 2i2' area 16 Current/Voltage Relationships If is infinite then 0 N1i1 N 2i2' . Hence i1 N2 or ' N1 i2 i1 N2 1 i2 N1 a Then v1 i 1 a 0 v 2 1 0 i2 a 17 Impedance Transformation Example •Example: Calculate the primary voltage and current for an impedance load on the secondary a v1 i 0 1 v1 a v2 i1 0 v2 1 v2 Z a 1 v2 aZ v1 a2 Z i1 18 Real Transformers • Real transformers – – – have losses have leakage flux have finite permeability of magnetic core • Real power losses resistance in windings (i2 R) core losses due to eddy currents and hysteresis 19 Transformer Core losses Eddy currents arise because of changing flux in core. Eddy currents are reduced by laminating the core Hysteresis losses are proportional to area of BH curve and the frequency These losses are reduced by using material with a thin BH curve 20 Effect of Leakage Flux Not all flux is within the transformer core 1 l1 N1m 2 l 2 N 2m Assuming a linear magnetic medium we get l1 ≜ Ll1i1 l 2 ≜ Ll 2i 2' di1 dm v1 r1i1 Ll1 N1 dt dt ' v 2 r2i 2 Ll 2 di2' d m N2 dt dt 21 Effect of Finite Core Permeability Finite core permeability means a non-zero mmf is required to maintain m in the core N1i1 N 2i2 m This value is usually modeled as a magnetizing current m N 2 i1 i2 N1 N1 i1 N2 im i2 N1 m where i m N1 22 Transformer Equivalent Circuit Using the previous relationships, we can derive an equivalent circuit model for the real transformer This model is further simplified by referring all impedances to the primary side r2' a 2 r2 re r1 r2' x2' a 2 x2 xe x1 x2' 23 Simplified Equivalent Circuit 24 Calculation of Model Parameters • The parameters of the model are determined based upon – – – nameplate data: gives the rated voltages and power open circuit test: rated voltage is applied to primary with secondary open; measure the primary current and losses (the test may also be done applying the voltage to the secondary, calculating the values, then referring the values back to the primary side). short circuit test: with secondary shorted, apply voltage to primary to get rated current to flow; measure voltage and losses. 25 Transformer Example Example: A single phase, 100 MVA, 200/80 kV transformer has the following test data: open circuit: 20 amps, with 10 kW losses short circuit: 30 kV, with 500 kW losses Determine the model parameters. 26 Transformer Example, cont’d From the short circuit test 100 MVA 30 kV I sc 500 A, R e jX e 60 200kV 500 A 2 Psc Re I sc 500 kW R e 2 , Hence X e 602 22 60 From the open circuit test 200 kV 2 Rc 4M 10 kW 200 kV R e jX e jX m 10, 000 20 A X m 10, 000 27 Residential Distribution Transformers Single phase transformers are commonly used in residential distribution systems. Most distribution systems are 4 wire, with a multi-grounded, common neutral. 28