Ventilation Topic 1 1. The Need to Ventilate Mines Ventilation is the process of conducting an adequate flow of pure, fresh air along airways, working places and service points underground. The main aims of ventilation can be summarized as follows: 1. 2. 3. 4. to provide air for mine workers and equipment, to dilute the concentration of explosive and toxic gases, fumes and radon to environmentally safe levels and to remove them from the mine, to dilute the concentration of airborne dust to physiologically acceptable levels and to remove it from the mine and to provide a thermally acceptable environment in which persons can work without undue discomfort or any danger of heat exhaustion and to remove heat from the mine as may be necessary. 2. Air for Breathing The average composition of ordinary air by volume is: Nitrogen Oxygen Carbon Dioxide Argon and other rare gases 78.09% 20.95% 0.03% 0.93% The above figures do not take water vapour into account, which is always present in amounts varying from 1% to 6% by volume. Since oxygen is essential for human life, it stands to reason that a change in the composition of the air could cause discomfort and even death below certain O2 percentages. Respiration Breathing is the most basic of human functions and involves removing oxygen from inhaled air and returning carbon dioxide in return. The amount of air breathed and the amount of oxygen retained depends largely upon the level of muscular activity. During hard work a person absorbs about three litres of oxygen per minute compared to 0.3 l per minute required by a sleeping person. A considerable oxygen deficiency can be tolerated: 21% - normal 17% - person still works comfortably, but breathing is faster and deeper 14% - symptoms like dizziness, buzzing in the ears, rapid heart action and headaches start to appear 6% - death These figures assume that the oxygen deficiency is due to displacement of oxygen by a gas such as methane or the absorption of oxygen by the oxidation process of metals and minerals. If the deficiency is due to carbon dioxide, the effects on a person are more severe. Carbon dioxide acts as a stimulant which regulates human breathing. When the percentage of carbon dioxide in atmospheric air (normally 0.03%) is increased to about 3%, the breathing rate is doubled. At 5% the rate of breathing is quadrupled and laboured but death will usually not occur until all the oxygen has been depleted. 1 To avoid this, each person working underground should be supplied with at least 0.015m 3/s of fresh 3 air and 0.1 m /s of air should ideally be supplied. 3. Gases and Fumes Prolonged exposure to sufficient concentrations of certain gases will disable or kill a person. These are known as toxic gases and can be divided into four groups: 1. 2. 3. 4. asphyxiant gases irritant gases narcotic gases protoplasmic gases 1. Asphyxiant gases If the oxygen supply to the bloodstream and the tissues of the body decreases or fails, asphyxiation results. The may occur in two forms: simple asphyxia occurs when sufficient air is breathed, but the air has an oxygen deficiency; chemical asphyxia occurs when a substance present in the air prevents oxygen from being utilized by the body (e.g. carbon monoxide). 2. Irritant gases These gases irritate and inflame tissue in contact with them. Inflammation of the lungs leads to pulmonary oedema (fluids are produced in the lungs, causing suffocation). Nitrous fumes and hydrogen sulphide act in this way. 3. Narcotic gases Gases such as chloroform and ether which act on the nervous system, after having been absorbed in the blood and transported to the tissue, are narcotic gases. If large quantities are absorbed, the normal coma will terminate in death. 4. Protoplasmic poisons After absorption by the body, these gases destroy the living cells in contact with them. Examples include fumes of metals such as mercury and lead. Explosive gases Some gases encountered in a mine, although safe to breathe may be explosive. Four conditions must exist underground to cause a gas explosion: 1. 2. 3. 4. the gas must be produced, the gas concentration must reach an explosive level, a flame or spark must ignite the gas and there must be sufficient oxygen present in the atmosphere. If one of these factors is absent, the explosion will not occur. Some Less Common Gases in Mines 1. Hydrocyanic Gas (HCN) Also known as hydrogen cyanide or prussic acid, this gas affects people in a way similar to H2S, only it is far more poisonous. Even a gas mask is not proof against it as it can be absorbed through the skin. 2 It is a colourless gas with a smell resembling that of bitter almonds. It is slightly lighter than air. The gas occurs in mines only when acid water comes into contact with cyanide in sand which has been used for sand-filling. 2. Chlorine (Cl2) This is heavy, greenish-yellow irritant gas with a pungent odour. It is extremely poisonous. A concentration of 0.005% can prove fatal and 0.001% is given as the MAC value. It causes coughing, smarting of the eyes, tightness of the chest and vomiting. As in the case of nitrous fumes, oedema (waterlogging) of the chest may occur several hours after exposure. Several chemical tests are available for chlorine, but in practice they are not necessary as the gas is easily recognised by its smell. The gas only occurs in mines where liquid chlorine is used to disinfect drinking water. 3. Aldehydes These are a series of organic compounds with a general formula C nH2nO. The lowest member of the series is CH2O (formaldehyde). Several aldehydes, with formaldehyde predominating, are present in exhaust gases from diesel engines. They have a pungent smell and are intensely irritating to the eyes, mucus membranes and the skin. At high concentrations they can be suffocating. Aldehydes can be detected by the human nose at concentrations far below that necessary to cause irritation and thus no test is required. Headings Under Which Mine Gases are Studied source properties - colour, taste, smell, relative density (RD), solubility, combustibility, toxicity effects on humans detection legal safety Source: To associate the presence of a gas with a particular condition. Properties: To ascertain whether the gas is: detectable by physical means, lighter or heavier than air, can be diluted or rendered harmless by means of water, is combustible or not, is poisonous or not. Effects on Humans: Enables action to be taken in the event of gassing underground. Detection: Enables use of correct instruments and procedures in gas detection. Legal Aspects: The dangerous effects of these gases are only apparent once the legal limits have been exceeded. 3 Relative Density The ratio of the mass of a given volume of gas to that of an equal volume of air. The following table reveals important source properties of various gases encountered in the mines. 4 5 A further summary of gases are provided in the table below. Approx. Name of Relative Symbol Explosive Range Gas Density in Air Allowable For 8 Hrs (TLV) Amount in Air Danger to Life N2 0.97 Non-explosive - Above 88% CO 0.97 12 to 72% 30 ppm 0.1% (30 Min.) - 1.00 Non-explosive - - H2S 1.18 4 to 44% 10 ppm 500 ppm NO2 1.23 Non-explosive 3 ppm 100 ppm Methane CH2 0.55 5 to 15% Visible cap 25% (Def 02) Oxygen O2 1.10 Non-explosive - Below 12% Hydrogen H2 0.07 4 to 74% - 25% Ammonia NH3 0.6 Non-explosive 100ppm 2500ppm(30min) Nitrogen Carbon Monoxide Air Hydrogen Sulphide Nitrous Fumes 6 Characteristics Colourless, tasteless, odourless Colourless, tasteless, odourless Colourless, tasteless, odourless Colourless, smell of bad eggs Reddish brown colourdelayed effect Colourless, tasteless, odourless Colourless, tasteless, odourless Colourless, tasteless, odourless Colourless, Acrid Biting taste, strong pungent odour The following gases and their concentrations in ambient air would affect humans in various ways such as: Carbon monoxide (CO) 0.02% - Slight poisoning symptoms in two hours (Canary – no reaction) 0.05% - Headache and discomfort in one hour 0.1% - Giddiness in half an hour - Helplessness in one hour - Death in two hours - (Canary – No distress in 12 to 15 minutes) 0.2% - Serious effects in 30 minutes - (Canary – Serious effects in 3 minutes) 0.5% - Man – Serious effects in 5 to 7 minutes - Death in 15 minutes 1.0% - Man – Immediate danger Hydrogen Sulphide Low concentrations - Headaches - Irritates eyes and nose - Impairs sense of smell 0.05% - Kills canary in 30 seconds 0.1% - Quickly causes unconsciousness 0.2% - Kills man in a few minutes To summarise some of the important gases dealt with in this section of mine ventilation the following is given: Hydrogen 4 to 74% - Explosive range Colourless Odourless Lightest gas Can occur with methane Methane 5 to 15% - Explosive range 10% - Most violent explosion would occur > 15% - Burns in this range Colourless Odourless Lighter than air The following fresh air supply would be required by man in the different conditions encountered: a) b) c) d) Required Shallow gold mine Deep gold mine Factories 3 = 0.015 m /s 3 = 0.08 m /s 3 = 0.14 m /s 2 = 1.5 l/s/m or 7.5 l/s/person The effect of carbon dioxide inhalation would have the following effects on human breathing: a) b) c) 0.03% - Normal breathing 3% - Breathing rate doubled 5% - Breathing rate quadrupled 7 The effect of oxygen and the lack thereof in ambient air would be the following: a) b) c) d) 21% 17% 14% 6% - Normal ambient concentration - Breath deeper and faster - Dizziness, buzzing in the ears and a rapid heart rate - Death The following air requirement could be set for human work performed: a) b) Hard work Sleeping - 3 litres per minute - 0.3 litres per minute Nitrous fumes have the following combinations: NxOy a) Nitric Oxide b) Nitrogen dioxide c) Nitrogen Trioxide d) Nitrogen tetroxide 8 Ventilation Topic 2 Tutorial 1 Gas Calculation The questions below are designed to enable calculation of the concentrations in the question set. 3 A diesel vehicle travels along an airway. The total gas emission is 0.2 m /s. The exhaust gases contain 1500 ppm of carbon monoxide and 750 ppm of oxides of nitrogen. The cross-sectional area of 2 the airway is 9 m and the air velocity is 3 m/s. What is the concentration of carbon monoxide and oxides of nitrogen in the air after complete mixing is the vehicle travels at : a) 8 km/h in the opposite direction to the air, b) 6 km/h in the same direction as the air and, c) at the same speed as the air and in the same direction? 9 Ventilation Topic 3 Ventilation Requirements At the start of the Industrial Revolution, mines were generally shallow and ventilation of the workings was not a serious consideration. As mines became deeper, this situation changed. Empirical Guidelines for Ventilation in South Africa Gold Mines 10 A wide range of conditions exists under which gold is mined. For this reason it is difficult to specify an overall air quantity. Typical values range from 3 to 6 kg/s per 1000 t of rock mined per month. Main surface fan pressures of up to 9 kPa are used. This means that single shaft systems may transport up to 700 m3/s of air and have electric power consumption for the main fans of about 8 MW. Base Metal Mines Base metal mines vary enormously in mining method, degree of mechanisation, depth and many other factors. Most are highly mechanised and thus if a standard of 60 -65 m3/s of air per MW of rated diesel capacity is adequate and if it is assumed that only 50% of the air arrives at the working place, then about 120 -130 m3/s/MW should be supplied. Depending on the mining method, between 30 000 and 60 000 t/month can be produced from 1 MW of installed diesel capacity. The following example calculation would be the requirement for trackless equipment utilisation in an underground mining situation: Trackless equipment: LHD 1 x 100 kW diesel power unit 11 Quantity requirement: The method of calculating the amount of ventilation air required for an operational fleet in a “multi— heading” mining development system is the one used by the MSHA (Mine Safety and Health Administration, USA) where: Qt Qt Q1 Q2 Qn = = = = = 100% x Q1 + 75% x Q2 + 50% x Qn Total air quantity required Permissible volume rate for largest rated unit (diesel) Permissible volume rate for second largest rated unit (diesel) Combined permissible volume rate for each additional diesel unit. Using the MSHA formula and the example fleet as given above, the required quantity for the mine is: Qt = = (100 x 0.07) + (0 x 0.07 x 0.75) + (0 x 0.07 x 0.5) 7.0 m³/s (Section requirement) There will be 1 diesel units operating in the heading therefore the ventilation requirements are as calculated above. If more diesel units are to be operated in the ramp system, the air requirements need to be adjusted accordingly. Coal Mines Because of the possibility of methane related problems, minimum ventilation requirements are specified by law. The following list is taken from the old Mines and Works Act which is still in force via the Minerals Act: 10.8.1 10.8.2 10.8.3 10.8.4 10.8.5 25 l/s x maximum tons per shift less than 200 persons per ventilation district longwall face ventilation velocity at least 0.25 m/s air velocity in airways at least 0.25 m/s 2 ventilation in advance headings at least 300 l/s/m 12 Ventilation Practice in Mines To ensure adequate ventilation of a mine, provision is made for suitable pathways (called airways) for the air to enter the workings. Once the air has passed through the workings, airways are required to allow it to leave the mine. Most mines have ascensional ventilation of the workings - the fresh air is conveyed directly to the lowest working places by means of a downcast system and then ascends through the rest of the mine. This is generally more satisfactory than descentional ventilation in which air descends through the workings and is then taken to surface from the lowest reaches of the mine via an upcast shaft. 13 Air always flows along the path of least resistance, but this may not be where it is required for use. To prevent the air from returning directly to surface along upper levels connecting downcast and upcast shafts, ventilation doors or airlocks are installed. An airlock consists of two doors arranged so that when one is opened the other can be kept closed to prevent airflow. If a small volume flow rate of air is required continuously in a given level, then an opening of reduced size, called a regulator, is made in the ventilation door or door frame. Although general airflow can be made to pass directly through the main working places, there will usually be several places where auxiliary ventilation will be required (such as development ends, hoist chambers, shaft loading stations, etc.). The provision of such ventilation requires an additional fan and a suitable route for the air. This route is generally a ventilation duct. Ventilation of Main Working Places Stopes A normal stope connects two levels, of which the lower usually acts as the intake airway and the upper as the return airway. The distribution of air in a stope is controlled by closing the bottom and top of the stope as far as possible, leaving openings only near the faces and other areas where people may be working. This will direct most of the air towards the face 14 Development Ends Three main systems can be used to ventilate the working face in a development end. A) Forcing systems The fresh air from the through ventilation is forced into the end through a ventilation duct by a fan and returns via the development end. The intake to the duct must extend well into the upstream portion of the intake airstream (at least 5 m) in order to prevent recirculation of used air. The fan should be situated in that part of the duct which extends into the fresh air so that it is accessible after blasting when the roadway itself should not be entered. The intake and delivery ends of the duct should be fitted with wire screens to prevent any extraneous material from being drawn into the fan. The duct should be maintained in good condition in order to deliver as much air as possible to the development end. The delivery end of the duct must be kept as close as possible to the face (< 12-m to the face). The end of the duct may be damaged by blasting if it is too close to the face. One method of avoiding damage is to remove the last section or two of the ventilation duct before blasting and replace them at the time of loading, or to use a flexible, retractable duct. B) Exhaust Systems Air from near the working face of the end is exhausted through a ventilation duct and is replaced by fresh air drawn along the roadway. The duct must discharge the return air well beyond the entrance to the development end (at least 5 m), on the downstream side to prevent the air re-entering the end. This system is not commonly used because fresh air drawn along the roadway tends to enter the exhaust ventilation duct directly and very little of it actually reaches the face due its low velocity. This situation is exacerbated by the fact that the intake of the return duct cannot always be kept right up to the face as it may be damaged by the blast. Shaft sinking operations often use this type of ventilation method to allow for re-entry period limitations. 15 C) Overlap Systems Force overlap system Exhaust overlap system In exhaust overlap systems, an auxiliary duct forces fresh air from the roadway onto the face in addition to an exhaust ventilation duct. The length of the auxiliary duct commonly varies from 6 to 60 m. The distance from the face to the intake end of the exhaust duct is generally kept within 15 m (but usually 5 m) of the face. It is important that the exhaust duct and the auxiliary forcing duct overlap by at least 5 m. A common length of overlap is 10 m. This ensures that the air entering the auxiliary forcing duct is fresh air coming up the roadway and not air returning from the face. It is essential to ensure that the volume flow rate of air being exhausted from the face is at all-time greater (2 - 4 times) than the volume flow rate of air being forced onto the face by the auxiliary duct. This prevents short-circuiting of air. The drives of the fans must also be interlocked so that if the main exhaust fan stops, the in-bye forcing fan also stops. 16 The following law requirement is enforced via the South African Mining law: This permission supersedes all previous permissions granted in this regard. RE-ENTRY INTERVALS In terms of Regulations 2.10.10 and 10.10.2 in force in terms of Schedule 4 of the Mine Health and Safety Act, 1996 (Act no 29 of 1996) the intervals which must expire before persons are allowed to reenter the workings of your mine in which blasting has taken place are fixed as follows: 1. NIL RE-ENTRY INTERVAL No interval of re-entry needs to be observed in all workings in which through ventilation has been established and which are ventilated by air, which does not become contaminated by blasting fumes. Should the air in any of the workings become contaminated by blasting fumes, the general reentry interval, as set out in paragraph 2 below must be observed in those workings. 2. GENERAL RE-ENTRY - REGULATION 10.10.2 (For Blasting once in 24 Hours) A general minimum re-entry interval of three (3) hours after the blast in all ventilation districts must be observed, with the exception of the workings mentioned in paragraph 1 above and other workings where special re-entry intervals have been set in terms of this permission. Blasting more than once in 24 hours for certain stoping sections will be allowed provided that the minimum re-entry interval of three (3) hours is maintained and that an air quality as specified in 3.1 c) of this permission is maintained at all times. 3. THIRTY MINUTE RE-ENTRY INTERVAL - REGULATION 10.10.1(a) (For blasting more than once in 24 Hours) The following provisions must be made applicable to all multi-blast development ends or shafts being sunk: 3.1 Minimum Air Quantities Required (Relative to the Air Density at the working face) a) The minimum quantity of air forced must not be less than 0,3 cubic metres per second for every square metre of face area, for all multi-blast development ends. b) The quantity of air exhausted from the development end must not be less than twice more than the quantity of air supplied by the force column referred to in paragraph a) above, the minimum force: exhaust ratio of 1:2 must be maintained at all times. c) The air supplied must be of a quality as prescribed in Regulation 10.6.6 and also applies to conditions on re-entry. Dust measurement results with a tyndallometer must be less than an AQI of 1.0 taken over a 2-minute period. 3.2.1 Ventilation Arrangements 3.2.1 Horizontal Development, Inclines, Declines and Raises. a) An exhaust-overlap system of ventilation must be used for every end being multi-blasted. b) The intake of the exhaust column must be carried to a point not exceeding 30 metres from the face. c) The discharge end of the force column providing the quantity of air prescribed must not be more than twelve metres from the face of the development end being blasted. d) The minimum overlap distance between the exhaust column intake and the force column intake points must be at least 9 metres and not exceeding 15 metres. e) Fans in the exhaust column must be positioned in such a manner that the exhaust column remains under negative pressure thus ensuring that no exhaust fumes leak back into the intake air flowing to the face. f) To prevent open circuit exhaust fans from recirculating a volume of at least 0.6m /s/m , of through ventilation, at these fan sites, must be maintained at all times. 3 17 2 g) The exhaust fans in an exhaust-overlap system, which are the primary source of ventilation, must be interlocked with all other electrical appliances and equipment in the end being multi-blasted. This is to ensure that in the event of the exhaust fans stopping that all other electrical appliances and equipment will also shut down. h) No butterfly valves to be positioned in any exhaust column in development ends. i) In a raise the exhaust column must be kept within 30 m of the face at all times and on the face side of any ore-pass connection. j) The force fan must be positioned only in the overlap section of the ventilation system. k) A water blast or other similar dust allaying mechanism must be operated during the blast and re-entry period at a discharge point not exceeding 15 metres from the face. l) If, at any stage, blasting fumes from the end being multi-blasted contaminates any working places in the vicinity, then multi-blasting must cease and conventional time lasting (as per paragraph 2) must be followed until conditions have been rectified for multi-blasting. The ends so contaminated must also of necessity be on conventional time blasting. m) The dust and fumes from blasting operations must be exhausted directly to surface via an established smoke way and must not contaminate any place where persons may be required to work or travel 3.2.2 Shafts a) The bank area must be kept clear of blasting fumes and the shaft must remain downcasting, in the bank area, at all times. b) The force column delivery must at least be to the bottom deck of the stage during blasting. 3.3 Waiting Place in terms of Regulations 2.10.6 and 8.10.33 a) Blasting must be carried out from a place of safety demarcated by the manager. This position must be sign posted as “Waiting Place” and also act as a contraband control point. b) The blasting times must be recorded and the re-entry interval must be specified and posted on the waiting place signboard and other relevant conspicuous places. c) Blasting initiation must be conducted electronically. 18 3.4 Miscellaneous a) Continuously operating flammable gas measuring instruments must be used at all drilling sites (inclusive of cover/diamond/prospect drilling sites). 3.5 Returns to Department of Minerals and Energy (Mine Health and safety Inspectorate) a) All returns must be sent to this Regional Office. b) These returns must be submitted on a monthly basis per multi-blasted development end. c) The following is a listing of the minimum information that will required in the returns : Mine Information i) ii) iii) iv) Name of Mine Shaft complex, section and development end identification. Development end cross sectional area in m 2. A sketch plan of the working place showing all ventilation arrangements and volume flow rates. Ventilation Appliances (before blasting) i) ii) iii) iv) Force column delivery quantity; force column distance from the face. Exhaust column intake quantity and distance from face. Water blast or dust allaying mechanism, distance from face. Exhaust-overlap distance. Environmental Conditions on Re-Entry (30 minutes after blast) – at a point 3 metres from the intake of the exhaust column (face side). I. II. Concentrations of, oxides of nitrogen, carbon monoxide and amount of flammable gas in the atmosphere. Concentrations of dust by means of tyndallometer readings. Your attention is also drawn to the requirements of Regulations 8.11, 10.1.1, 10.3.1, 10.6.3, 10.6.5, 10.10.3, 10.10.4 and 10.10.6. All regulations mentioned above are in force in terms of Schedule 4 of the Mine Health and Safety Act, 1996 (Act no 29 of 1996). This permission may be amended or withdrawn at any time should such action be considered necessary. All persons concerned must be made fully conversant with the terms of this permission, copies of, which must be readily available to them. Forces Causing Airflow in Mines To cause airflow in mines a difference in pressure between the intake and return shafts is essential. This pressure difference can be caused by either natural or mechanical ventilation Natural Ventilating Pressure Single Shaft In a mine with only one shaft, there will be a natural flow of air as long as that temperature of the workings is markedly higher than that on surface. Warm air rises and a convection current is set up 19 within the shaft which is sufficient to ventilate small, shallow workings. By the late seventeenth century it was recognised that two interconnected shafts (or a shaft and an adit) provided a flow of air and reduced the risk of suffocation. Twin Shafts Where the two shafts are of unequal depth, in winter air will flow down the shallow shaft and up the deep one because the temperature in the shallow shaft will be lower than that in the deep shaft. In summer the temperature in the shallow shaft will usually be higher than that in the deep shaft and so the direction of the air current will be reversed. With two shafts of equal depths, the direction of the air current may be determined by the direction of the prevailing wind or by one shaft being wetter (and therefore cooler) that the other. Natural ventilation in most modern mines results because the air in the downcast shaft is cooler and denser than the air in the upcast. The unequal densities, although influenced by other factors, are due mainly to the transfer of heat from the underground rock to the mine atmosphere. With the exception of very shallow mines, underground air temperatures approach rock temperature and remain fairly constant. Consequently, the temperature, density and total weight of the air column in the upcast shaft will not fluctuate to any great extent. The density and total weight of the air column in the downcast shaft, however, fluctuates with surface air temperature. Since a density change in either of the columns will cause a change in the natural ventilating pressure, this pressure may vary from a maximum in one direction, to zero, to a maximum in the opposite direction depending on whether the surface air temperature is lower than, equal to or greater than the underground air temperature. This results in an unpredictable volume flow rate which may vary from a maximum in one direction to some value in the opposite direction. In some instances, natural ventilation may maintain underground air quality standards, but generally is alone is not a dependable means for continuous and effective ventilation. Thus additional ventilation has to be provided by mechanical means. There is still today a mine in Zimbabwe (Blanket mine) utilising natural ventilation to ventilate the whole mine. This is only possible because of its workings depth below surface (800mbc) and the intake shafts positions. A) Natural ventilation in a twin shaft system where the shafts are of unequal depth. 20 B) Natural ventilation in a twin shaft system where the shafts are of unequal depth Mechanical Ventilation A fan takes in air at one pressure and raises this air to a higher pressure, i.e. it increases the pressure of the air on its delivery side to a value above the pressure of the air on its intake side. Due to this induced pressure difference, the air is able to overcome the resistance of the circuit through which it is flowing. Usually the main fan (or fans) is situated at the top of the upcast shaft or return opening. Its main advantages are: (1) (2) (3) The working environment’s pressure is slightly less than the outside atmosphere pressure, because the fan creates a negative pressure within the mine. When the fan stops, underground pressure builds up to atmospheric pressure and this increase slows down the liberation of strata gases and gas emissions from the goaf, and prolongs the time required for the gas to fill active workings. Through the use of discharge evasée, velocity pressure can be recovered enabling power savings No heat is added to the air supply underground The disadvantages are: (1) (2) (3) (4) It can only be applied if all the return air flows in the upcast shaft. Foul air goes through the fan, making repair or maintenance difficult. Corrosive fumes and particles cause corrosion on the fan blades and reduce effective air passage area and can throw the fan out of balance. Natural ventilation pressure is reduced It is difficult to hoist men and materials in the upcast shaft due to safety requirements In shallow mines having fractured rock, in areas of contiguous mining where there may be ground fractures into abandoned mines, and in mines with old workings outcropping on the surface, the most advantageous position for the fan is at the top of the downcast shaft or intake opening. Some of the disadvantages are: 21 (1) (2) (3) access to the shaft is difficult, requiring special airlocks, etc.: it is difficult to transport men, material or ore in the shaft heat is added to the downcast air. From the thermodynamical point of view, the best location is at the bottom of the upcast shaft. Because the fan adds heat to the air in the upcast shaft, natural ventilation is increased. The other advantages are: (1) (2) no heat is added to the air breathed by miners the downcast shaft is left clear for hoisting The disadvantages are: (1) (2) (3) the fan handles foul air it is not accessible during fires any leakages across doors above the fan results in recirculation of foul air. The following paper is provided for further reading and to indicate the relevance of ventilation systems. 22 23 24 25 26 27 Ventilation Topic 4 Fluid Mechanics Fluid mechanics consists of two fields of study: fluid statics and fluid dynamics. Fluid statics deals with stationary fluid bodies such as the hydrostatic pressures associated with water acting against a dam wall. The fundamental equation associated with this field describes the pressure exerted by a column of incompressible fluid of height ‘H’ and density‘w’: p=wgH [1] where: g = gravitational acceleration 2 9.79 m/s in Johannesburg Fluid dynamics deals with fluids subjected to a shear force and which deform continuously, moving relative to the rest of the fluid body. In a flowing liquid each particle changes its position with a certain velocity. The magnitudes and directions of the particle velocities may vary with position as well as time. This may be illustrated using streamlines. These are imaginary lines in a fluid, the tangents of which give the direction of flow at that point. Generally speaking, there are three types of flow as can be visualised from the above drawing, namely plug, laminar and turbulent flow. Plug Flow Plug flow is a type of laminar flow and only occurs with yield stress materials moving at low velocities. The central part of the fluid moves as a plug with the same particle velocities. A shearing effect is only present at the pipe wall. The velocity profile therefore has a flat centre portion as shown in the diagram below. Laminar Flow In laminar flow the flow pattern is smooth with fluid layers travelling straight or in gently curving lines parallel to the conduit axis. The velocity of each layer increases towards the middle of the stream until a maximum velocity is attained at the centre. In this type of flow there is only one component of fluid velocity: a longitudinal component. Here the fluid shear stress resistance is caused by the sliding action only and is independent of the roughness of the pipe. 28 Turbulent Flow Turbulent flow only occurs at high velocities or at low fluid viscosities and is characterised by chaotic motion of fluid particles. This random movement results in two components of velocity: a longitudinal and a transverse component. The longitudinal velocity attempts to make the fluid flow parallel to the conduit axis, while the transverse component attempts to move the fluid in a direction normal to the pipe axis. Types of Fluid Newtonian Fluids In this type of fluid, viscosity is constant and is only influenced by changes in temperature and pressure. Examples include gas, oil and water. Non-Newtonian Fluids The viscosity of this type of fluid is proportional to the magnitude of shear stress. Examples include drilling mud and cement slurries. FLUID MECHANICS Fluid mechanics consists of two fields of study: Fluid statics, and fluid dynamics. Fluid statics deals with stationary fluid bodies, i.e. the hydrostatics of a dam acting against the dam wall. The basic equation of fluid statics is that the pressure exerted by a column of height 'H' of an incompressible fluid of density 'w' can be expressed as: P=wgH (1) Where: w - fluid density H - column height 2 g - gravitational acceleration = 9.79 m/s at altitude of Johannesburg Fluid dynamics deals with fluids subjected to a shear force, and which deform continuously, moving relative to the rest of the fluid body. In a flowing liquid each particle changes its position with a certain velocity. The magnitudes and directions of the velocities of all the particles may vary with position as well as time. This may be illustrated by using streamlines. Streamlines are imaginary lines in a fluid, the tangents of which give the direction of flow at that point. In laminar flow the fluid particles move along smooth paths such that the movement of all particles on the same path is identical. This type of flow is associated with very low velocities and highly viscous fluids. 29 Turbulent flow is characterised by fluid particles moving in irregular paths and colliding with one another in a haphazard manner. Most practical flow problems of interest to the mining engineer are related to turbulent flow. Whether a particular set of conditions will lead to laminar or turbulent flow is determined by its REYNOLD'S NUMBER Reynolds number: R wvD Where: 3 w - density (kg/m ) v - velocity (m/s) D - pipe diameter (m) - dynamic viscosity (Ns/m ) 2 R < 2 000: laminar flow; pressure directly proportional to velocity R > 4 000: turbulent flow; pressure proportional to the square of velocity 2 000 < R > 4 000: laminar or turbulent flow depending on the roughness of the pipe and upstream turbulence of the fluid. 30 THE LAWS OF FLUID DYNAMICS Airflow is analysed as it passes through a fixed region in space defined by a control surface. The properties of the air are examined as it enters and leaves the volume bounded by the control surface. Laminar & Turbulent flow - the REYNOLDS NUMBER of a fluid determines whether laminar or turbulent flow will predominate. THE LAW OF CONSERVATION OF MASS This law states that the mass flow entering the control surface must equal the mass flow rate leaving the control surface, i.e.: M1=M2 Or W1A1V1=W2A2V2 This is the CONTINUITY EQUATION; Where: M = mass flow rate w = density A = flow area measured normal to the direction of flow V = flow velocity If the air is of constant density, then: A1V1=A2V2 Or Q1=Q2 where Q is the volume flow rate Equation (2) is known as the CONTINUITY EQUATION. 31 THE LAW OF CONSERVATION OF MOMENTUM Newton's second law of motion states that the force 'f'’ to accelerate a body must be equal to the product of the mass 'm' of the body and its acceleration 'a', i.e. F = ma (N) If this law is applied to an ideal (frictionless), incompressible (constant-density) fluid, EULER'S LAW of conservation of momentum is obtained. PROOF- EULER'S LAW Let a fluid move steadily through an imaginary fixed volume element xyz (Figure below) Consider the flow across plane yz (in the x - direction) If pressures P1 and P2 act on the opposite surfaces, the corresponding forces are: P1y z And P2y z These are surface forces. In addition to these, the fluid may be subjected to body or mass forces. If: B denotes the mass force per unit mass in the x direction and w denotes the constant density of the fluid, the corresponding mass force is: Bwxyz 32 The resultant force on the fluid is thus: F = P1yz – P2yz + Bwxyz The fluid flows in with a velocity V and out with velocity V . If x is very small, the acceleration will be constant and is represented by: 1 2 a = (V - V ) / t 1 2 Where: t = the time for the fluid to flow through distance x Since the mass of the fluid element is m = wxyz, Newton's Law (F=ma) yields: P yz – P yz + Bwxyz = wxyz(V - V ) / t 1 2 1 2 which simplifies to: P - P + Bwx = wx(V - V ) / t 1 2 1 2 The mean velocity over the distance x is: (V + V ) / 2 = x / t 1 2 Substituting for x / t in the main equation yields: P1 P2 +Bwx =w (V22- V21) 2 This is EULER'S EQUATION for the x - direction, also known as the MOMENTUM EQUATION. 33 Ventilation Topic 5 Fluid Mechanics - Bernoulli’s Equation Bernoulli’s Equation and Compressible Fluids Assume that a fluid may be considered incompressible if its density does not change by more than 5%. If it is assumed further that the relationship between static pressure and density is linear, then the acceptable change in static pressure is also 5%. To find the limit of acceptability of the Bernoulli equation in terms of air velocity, that part of the equation stating that: 2 P = ½ wV may be used. The absolute pressure of atmospheric air is about 105 Nm-2, 5% of which is 3 -2. 5 x 10 Nm 2 With w = 1 kg.m-3 for air, the dynamic pressure 1/2 wv equals 5% of the absolute pressure when: 2 3 V = 5 x 10 x 2 or 100 m/s. Bernoulli’s equation therefore gives rise to appreciable errors for air velocities greater than 100 m/s when air is at about atmospheric pressure. As these velocities are not exceeded in mine airways, the equation can be used when dealing with air, even though it is a compressible fluid. To find the limit in terms of height, that part of the equation stating: P=wgH may be used. The value of H that results in a 5% change in absolute pressure is obtained by substituting: 3 P = 5 x 10 Nm w = 1 kg.m-3 -2 g = 9.8 m.s -2 This gives: H = 510 m. It is now apparent that for air at about atmospheric pressure with height changes of less than about 500 m and velocity changes which do not exceed 100 m/s, the application of Bernoulli’s equation should not produce unduly great errors. In the majority of mine ventilation applications, very little error will be introduced. For extended surveys of shafts, the height limit will be exceeded and other methods will be employed. Bernoulli’s Equation and Non-Frictionless Fluids The Bernoulli and Euler equations are only valid for ideal or frictionless fluids. Real fluids are subjected to shear resistance against relative movement of their layers. 34 Consider a fluid volume xyz subjected to a shear force ‘s’ acting on two opposite faces a distance ‘y’ apart (see diagram 1 at the end of these notes). The quotient of the force ‘s’ and the area of the plane parallel to its direction of action (area xz) is the shear stress: Shear stresses give rise to a continuous movement of the one face relative to the other. If the velocity of the one layer relative to the other is dV, then the rate of shear strain is dV/y. Newton postulated that: The factor of proportionality, , is called the coefficient of dynamic viscosity and is expressed in -2 -1 -1 N.s.m or kg.m .s . Viscosity depends on temperature. This is to be expected since the shear stress (of which viscosity is a measure) results from molecular motion within the fluid and temperature is a measure of the degree of molecular motion. The variation of viscosity with temperature is shown in figure 2 at the end of these notes. Note that the viscosity of gases is proportional to temperature while the viscosity of liquids is inversely proportional. In many real fluids the effects of shear stresses are small and Bernoulli’s concept of the ideal fluid is reasonably accurate for most practical cases concerning the relationship between pressure and velocity changes in a fluid. The Navier-Stokes equation is similar to Euler’s equation but it allows for viscous forces. This equation is rather complex and has been applied successfully to real fluid flow in only a few simple cases. 5. PROOF OF BERNOULLI'S EQUATION If the x - direction is taken as vertically upwards (Figure above), where P1 & V1 are at height H1 and P2 & V2 are at height H2 the distance x = H2- H1 35 The force B per unit mass is now due to gravity and corresponds to the weight per unit mass of the fluid column between H1 and H2. The weight per unit mass is g, therefore: B = -g as the weight is directed downwards, opposite to the direction of P1 Substituting x = H2- H1and B = -g into Euler's equation yields: 2 2 P1- P2- gw(H2- H1) = w(V1 - V2 ) / 2 Or 2 2 P1+ w(V1 / 2) + gwH1= P2+ w(V2 / 2) + gwH2 This is BERNOULLI'S EQUATION for the ideal, incompressible fluid in terms of pressure. Air is both compressible and non-frictionless (non-ideal). 5.1 BERNOULLI'S EQUATION and compressible fluids A fluid may be considered incompressible if it's density does not change by more than 5%. Assuming a linear relationship between static pressure and density, the acceptable change in static pressure is also 5%. Bernoulli's equation may be used if air is near atmospheric pressure and: the height does not change by more than 510 m and velocity changes do not exceed 100 m/s 5.2 BERNOULLI'S EQUATION and non-frictionless fluids 36 Bernoulli's equation and Euler's equation are only valid for ideal or frictionless fluids. In reality, however, fluids are subjected to shear resistance against relative motions of their layers. Consider a fluid volume xyz subjected to a shear force 'S' acting on two faces a distance 'y' apart (Figure above) The shear stress is thus: If the velocity of one face relative to the other is dV, the rate of strain is dV/y. Thus: Where: = coefficient of dynamic viscosity (Ns/m or kg/ms) 2 In many real fluids, the effects of shear forces are small and Bernoulli's equation may be applied. 37 6. THE BERNOULLI EQUATION & MINE VENTILATION 6.1.1 For an ideal fluid: 2 P1+ ½ w1v1 + w1g1H1= constant [1] where: P1 2 ½ w1v1 w1g1H1 - represents static pressure (SP) represents velocity pressure (VP) represents potential energy 6.1.2 For a non-ideal fluid: P1 w1V12 +w1g1H1 P2 w2 V22 w2 g2 H2 PL 2 2 [2] Where: PL is the sum of all friction losses if H 0 P1 w 1V1 2 P2 w2 V22 PL 2 [3] 2 6.2 Absolute Pressure & Gauge Pressure 38 The absolute pressure inside the column is 110 - 0.4 = 109.6 kPa The absolute pressure inside the column at: x1 is 109.6 kPa x2 is 100.6 kPa P = 9 kPa 6.3 Pressure Loss (PL) From equation [3] P = P + 1/2w v 1- (P2+ 1/2w v ) [4] [5] 2 L 1 1 2 2 2 PL = { (SP) + (VP)1} - { (SP)2+ (VP)2} 1 6.3.1 Constant diameter column (VP)1= (VP)2 (constant diameter) PL= (SP)1- (SP)2 [6] PL = (+700) - (+200) = 500 Pa 39 Note: (TP)1 = (VP)1+ (SP) = 200 + 700 = 900 Pa (TP)2 = (VP)2+ (SP)2 = 200 + 200 = 400 Pa PL = (TP)1- (TP)2 = 900 - 400 = 500 Pa [7] 6.3.2 Variable diameter column PL = (TP)1- (TP)2 = 600 - 500 = 100 Pa Note: (SP)1= 500 (SP)2= 200 PL(SP)1- (SP)2 6.4 Fan Total Pressure (FTP) The effect of adding a fan is as follows: 2 2 P1+ ½ w1v1 + FTP = P2+ ½ w2v2 + PL [8] 40 FTP = (P2+ ½ w2v2 ) - (P1+ ½ w1v1 ) + PL 2 2 [9] FTP = (SP2+ VP2) - (SP + VP ) + PL [10] FTP = (TP)2 - (TP)1+ PL [11] 1 1 6.5 Boundary Conditions at Extremities of Columns 6.5.1 Column intakes From equation [7]: PL = (TP)1- (TP)2 but PL = 0 and (TP)1 =0 thus 0 = 0 - (TP)2 (TP)2 =0 but (VP) = 200 Pa and (TP)2 (SP)2 2 = (VP)2+ (SP)2 = (TP)2- (VP)2 = 0 - 200 = -200 Pa Therefore, at the intake: (TP) = 0 (SP) = - (VP) assuming no shock losses As an example of entry losses affecting pressures within the duct, consider the previous example but this time make allowance for an entry loss of 75% of the velocity pressure Inlet shock losses = 0.75 x 200 = 150 Pa PL (TP)2 = (TP)1 - (TP)2 = (TP)1 - PL 41 but (TP)1 (TP)2 =0 = 0 - 150 = -150 Pa (VP)2 (TP)2 (SP)2 = 200 Pa = (SP)2+ (VP)2 = (TP)2- (VP)2 = (-150) - (200) = -350 Pa 6.5.2 Column deliveries (SP) = 0 (VP) = w V 2 2 (TP) = (SP) + (VP) (TP) = (VP) thus at the delivery: (TP) = (VP) (SP) = 0 6.5.3 The global pressure change Consider air being drawn into a column at point 1 by a fan and delivered from point 2: From equation [10]: FTP = (SP2+ VP2) - (SP1+ VP1) + PL = (TP)2- (TP)1+ PL but point 1 in an intake and point 2 is a delivery (TP)1 = 0 (TP)2= (VP)2 42 So FTP = (TP)2- (TP)1+ PL = (VP)2- 0 + PL = (VP)2+ PL 6.6 Fan Pressures 6.6.1 Fan total pressure a) FTP = (TP)2 - (TP)1 = 600 - (-240) = 840 Pa b) FTP = (SP)2- (SP)1 = 410 - (-430) = 840 Pa 6.6.2 Fan static pressure (FSP) FSP = (SP)2- (TP)1 = 410 - (-240) = 590 Pa The effect of a fan at the inlet of a column 43 J = facing gauge FTP = (TP)2 - (TP)1 = 800 – 0 = 800 Pa The measurement may be accomplished with a facing gauge at point 2. or: FTP = (SP)2- (SP)1 = 600 - (-200) = 800 Pa Using a side gauge The effect of a fan at the outlet of a column FTP = (SP)2- (SP)1 = 0 - (-800) = 800 Pa using a side gauge or: FTP = (TP)2- (TP)1 = 200 - (-600) = 800 Pa using both side and facing gauges 6.7 Evasées This is a device which is fitted to the discharge of a system and is used to convert the wasted velocity pressure into useful static pressure. This is done by enlarging the area at the discharge of the system, thus decreasing the air velocity and hence the velocity pressure. This reduction in velocity pressure represents a gain in static pressure. 44 At the discharge this 100 Pa is 'wasted'. An evasée could be fitted to reduce the velocity pressure from 100 Pa to 50 Pa. Now (VP) at A = 100 Pa B = 50 Pa loss in (VP) = 50 Pa but (TP) = (SP) + (VP) From the previous equation it is clear that whatever is lost in (VP) should be gained in (SP) so that the (TP) will remain unaltered. loss in (VP) = 50 Pa so gain in (SP) = 50 Pa A certain amount of this 'saving' is used to overcome friction and shock losses within the evasée. Assuming that these losses amount to 10 Pa, then: theoretical gain in (SP) = 50 Pa actual gain in (SP) = 50 - 10 Pa = 40 Pa 45 The efficiency of the evasée can be calculated by: Evasée efficiency = actual (SP) gain x 100 theoretical (SP) gain = 40 x 100 50 = 80% A static pressure measurement at the discharge of any column will read zero as all of the static pressure is used up in overcoming the friction of the system. But between A and B there is a gain is (SP). The (SP) is thus greater at B than at A. Since the (SP) at B is 0, the (SP) at A must be negative. This is always the case when an evasée is fitted to the discharge of a system. Note: I. VP is constant as long as the column diameter is constant and decreases as soon as the diameter increases in the evasée. II. A negative static pressure is obtained at the evasée inlet (A) of 40 Pa. There is then a gain in SP of 40 Pa and the SP at the end of the column equals zero. III. The friction losses between A and B are 10 Pa. In order to measure this loss due to friction in the evasée it would be necessary to measure TP at A and the TP at B and obtain the difference. TP is measured using a facing gauge. IV. The benefit of using evasées is that the fan pressure decreases by an amount equal to the regain in SP at the evasée. Consequently, a larger quantity of air will flow through the system. 46 6.7.1 Shock / entry losses for ventilation columns Often quoted as a percentage of velocity pressure: Straight inlet Flanged inlet 90% - circular pipes 50% - circular pipes 70% - rectangular pipes Inlet cone: 5 - 25% - depending on angle and length Flared cone: 3 -15% - depending on radius 47 Ventilation Topic 7 7. Airflow in Airways Air density: Wits: Klerksdorp & OFS: Sea level: 3 0.96 kg/m 3 1.00 kg/m 3 1.20 kg/m Elementary Laws of Airflow 1. For air to flow from one point to another, there must be a difference in pressure between these points. This is known as ventilating pressure. 2. Air flows from high pressure to low pressure. 3. The larger the ventilating pressure, the greater the quantity of air that will flow. 4. Resistance to airflow reduces the pressure (this is used to overcome the resistance). 5. If the pressure difference between two points remains the same, and the resistance between the points is increased, the quantity of air flowing between the points will decrease Factors creating resistance to airflow 1. 2. 3. 4. 5. 6. Skin factors (rougher increases R) Area normal to direction of flow (smaller area increases R) Distance (greater distance increases resistance) Shock losses (sudden changes in area increase resistance) Obstructions to airflow (increase resistance) Changes in direction (increase resistance) 7.1 Pressure Loss in Laminar Flow This pressure loss is due to the viscous resistance of air (shear stress generated when layers flow over one another) · Circular ducts: Hagen-Poiseuilles Equation P = 32Lv 2 D 48 Where: P: pressure loss (Pa) : dynamic viscosity of air (Pa.s) L: airway length (m) v: mean air velocity (m/s) D: airway diameter (m) 7.2 Pressure Loss in Turbulent Flow Due to shear stresses which are caused by the frictional resistance of the airway wall. · For circular airways: D'Arcy's Equation P = 4 fwLv 2D 2 Where: P: pressure loss (Pa) f : friction factor [ ] w: air density · Non-circular - use equivalent diameter (De) = 4A C Where: A: cross-sectional area of airway (m 2) C: perimeter of the airway (m) 7.3 Reynold's Number · For circular ducts Re = wvD = vD = w 49 Where: Re: Reynold's number [ ] (dimensionless) 2 : kinematic viscosity of air (m /s) NB: 1) Re < 2 000 2 000 < Re < 4 000 Re > 4 000 laminar transitional turbulent 2) of air increases with temperature · For non-circular ducts D = 2a b A+b Where: a: breadth b: width 7.4 D'Arcy's Friction Factor & Reynold's Number 7.4.1 Laminar Compare Hagen-Poiseuille & D'Arcy Equation 32 Lv = 4 fwLv 2 D 2D 2 f = 16 WvD f = 16/Re this only applies to laminar flow 7.4.2 Turbulent The friction factor (f) is a function of Re and relative roughness e. Relative roughness = e D where e: average height of surface irregularities 50 Required data can not be obtained from the graph below The Stanton and Nikuradse diagram (after Schlichting) 7.5 Atkinson's Equation P = KCLV2 A since v = Q/A P = KCLQ2 A3 X W 1.2 Where: 2 4 K: Atkinson's friction factor (Ns /m ) C: perimeter of airway (m) L: Length of airway (m) A: Area of airway (m 2) To account for density P = KCLV2 X W A (1.2 = density of air at msl [mean sea level]) 1.2 7.5.1 D'Arcy's friction factor and Atkinson's friction factor for a non-circular duct 4fwLV 2C K CLV2 2(4A) A X W 1.2 k = 0.6f 51 7.5.2 The resistance of an airway P = RQ 2 R = KCL Q = AV P = KCLQ2 W 3 A laminar: turbulent: models: 1.2 P = RQ 2 P = RQ n P = RQ 7.5.3 Typical values of the friction factor (K) 52 7.6 Losses of Pressure Due to Other Causes Two cases: I. II. change of direction (bend) change in cross-sectional area P = (1/2 wv ) 2 53 Where : loss factor Another method entails calculation of the equivalent length, for example: 45(short radius bend) in a 0.5 m duct. Treat as a straight duct, but increase the length to account for the increased resistance due to the bend. L =n for a 45bend, n = 18 D the increase in length is L = 18 x diameter = 18 x 0.5 = 9 m increase in length Obstructions retard the flow of air in the following manner: 1. By causing a reduction in the cross-sectional area, and consequently an increase in the air velocity 2. By disrupting the flow pattern of air, causing eddy currents which result in a loss of Pressure Measures to reduce the loss factor, , include: 1. Rounding off sharp corners and inserting guide vanes 2. Limiting angles by which the conduit increases or decreases it's cross-sectional area to 7 3. Rounding corners and inserting guide vanes in junctions 4. Chamfering the horizontal take-off from the shaft 5. Providing cages with fairings and close fitting doors. 7.7 Air Power WD = PAL Power =PAL t but volume / t = Q = AL t Power = PQ Or Power KCLQ2 w Q =KCLQ3 w A3 1.2 NB Power is proportional to Q 3 54 Bends 55 The table below indicates the different values of for different bends and conditions 56 Ventilation Tutorial 3 Airflow PROBLEMS – AIRFLOW QUESTION 1 (a) Describe the mechanism of pressure loss in: (i) Laminar flow, and (ii) Turbulent flow. (b) Describe two ways in which obstructions retard the flow of air in airways. (c) What are the units of Reynold’s number, resistance, and the friction factor (K). QUESTION 2 Calculate the air density in a shaft given the following information: Reynold’s number 37000 Air velocity 7 m/s Shaft diameter 6.9 m Dynamic viscosity of air 0.0016 Pa.s QUESTION 3 Calculate the pressure required to overcome friction when 50 cubic metres per second of air at a density of 1.2 kg per cubic metre flows through a 300 m length of 3m * 3m roadway. QUESTION 4 A 200 m long raise has been developed using a 2 m diameter raise borer. If the Reynolds Number is 2 000 000 and the surface roughness is one centimetre, what is the expected pressure loss in the raise for an airflow of 45 cubic metres per second? QUESTION 5 What is the resistance of the roadway in Question 3? QUESTION 6 Calculate the pressure loss when 4 cubic metres per second of air flows through a duct having a resistance of 9.3 (usual units for resistance). QUESTION 7 Calculate the air power expended when 4 cubic metres per second of air flows through a duct having a resistance of 40. QUESTION 8 Plot the system resistance curves of the ducts dealt with in Question 6 and 7. 57 Ventilation Topic 8 Ventilation Networks A mine normally consists of a large number of interconnected airways of various shapes, sizes and lengths. In order to facilitate calculation, complex networks can be subdivided into branches, junctions and meshes. Branch : Junction: Mesh: the airway between two junctions a point where three of more airways meet a closed path traversed through the network The following picture indicates the branches, junctions and meshes in an underground mine layout. 8.1 Solving Ventilation Networks The following methods are available: 58 I. II. III. IV. equivalent resistances direct analysis ventilation analogues iterative techniques 8.2 Equivalent Resistances Airways are in series or parallel 8.2.1 Roadways in series QT = QA = QB The total pressure in the system is the sum of the pressure loss in airways A and B: PT= PA + PB 2 since P = RQ , this can be written as follows: 2 2 2 RTQT = RAQA + RBQB but QT = QA = QB RT = RA + RB 8.2.2 Graphical representation of roadways in series Plot the resistance curve of the airways: AB BC CD 2 3 RAB = 0.066 Ns /m 2 3 RBC = 0.045 Ns /m 2 3 RCD = 0.012 Ns /m 59 The curve for each airway may be plotted by following the series laws and referring to quantity and pressure: i.e. PT = P1 + P2 QT = Q1 = Q2 To plot the system resistance curve of AD: Use a table: You know R, choose Q and calculate P Because the quantity of air in each airway is equal, any quantity line can be selected and the pressure required by airway 1 can be added to the pressure required by airway 2 (both on the same quantity line) to obtain the total pressure required by both airways. A point can then be plotted and other points can be obtained in the same way until sufficient points are obtained to plot a system curve representing both airways together. This is shown below. 60 The dotted curve is the combined curve for the two airways in series. 8.2.3 Roadways in parallel Parallel roadways are side by side and have a common inlet and return PT = PA = PB QT = QA + QB since P = RQ 2 2 2 2 2 RTQT = RAQA = RBQB And QB = ( RAQA / RB) and QT = ( RAQA2 / RT) Substitution yields: (RAQA / RT) = QA + (RAQA / RB) (RA / RT) = 1 + (RA / RB) 2 2 dividing by RA : 1 / (RT) = 1 / (RA) + 1 / (RB) 61 8.2.4 Graphical representation of roadways in parallel Airways in parallel can be solved by plotting the system resistance curves for airway. This is done by following the laws for quantity and pressure: PT = PS = P2 QT = Q1 + Q 2 Because the pressures are all equal, any pressure line can be selected and the quantity in airway one added to the quantity in airway two (both on the same pressure line) to obtain the total quantity in both airways. A point can now be plotted and the other points can be obtained in the same way until sufficient points have been obtained to plot a system curve. 8.3 Networks: Roadways in Series and Parallel In order to solve complex networks, the system may be simplified by observing an order of operation: I. parallel airways first I. begin with the smallest parallel circuit II. solve the resultant series circuit 62 9. REGULATORS & BOOSTER FANS 9.1 Regulators Regulators are openings of specific size which are used to control airflow. This is achieved by limiting the area through which air flows, thereby increasing the overall resistance of the systems and reducing the volume of air in circulation. Regulators have the effect of “using up” pressure that would otherwise have been used in overcoming friction. Case 1 PL = 500 Pa Over the length of airway, a pressure drop of 500 Pa is experienced due to friction. Case 2 PL = 500 Pa In the same airway, the installation of a regulator results in only 200 Pa being available to overcome friction. 300 Pa is used up by the regulator. The total pressure drop remains 500 Pa. The quantity of air flowing through the system in case 2 may be determined as follows: PQ And 2 P1 = P2 2 2 Q1 Q2 2 2 Q2 = Q1 x P2 P1 Q2 = Q1 x ( P2 / P1 ) 63 Q2 = 30 x (200 / 500) 3 Q2 = 18.97 m /s The pressure drop is the same, but the overall resistance is increased because the quantity of air flowing through the system has decreased: P = RQ2 Resistance: case 1 R=P 2 Q R = 500 2 (30) = 0.55 Ns/m Resistance: case 2 8 R = 500 2 (18.97) = 1.39 Ns/m 8 Size of regulator required: Ar = 1.1 Q (w / P) Where: 2 Ar - area of regulator (m ) Q - quantity of air flowing through the regulator (m 3/s) (i.e. Q2) P - pressure used up by regulator 3 w - air density (kg/m ) 64 A regulator works as a sharp-edged orifice. The actual flow through a regulator is less due to losses and the contraction of the airstream after exit from the orifice. The coefficient of discharge, Cd allows for these effects: Q = Cd Ar (2 H g) 3 Where Q: volume flow rate (m /s) 2 Ar: area of the regulator (m ) H: pressure producing the flow (metres of air column) if Cd = 0.64, then Q = 0.64 x Ar (2 H g) from the above: Ar = . Q . 0.64 (2 P g / w g) = 1.105 Q (w / P) 65 9.2 Booster Fans Underground booster fan installed through a wall in a haulage As regulators are used to decrease the quantity of air flowing in an airway, booster fans are designed to assist the main surface fan with the in-mine pressure drop that occurs. The sketch shows air distribution in a section of a mine. The pressure loss between A and C is 800 3 Pa. The mine has to increase the quantity of air flowing in ABC to 35 m /s. This is to be achieved by installing a booster fan. 9.2.1 Determination of the duty of a booster fan Pressure drop AC = Pressure drop ABC as these are parallel airways. This pressure is supplied by fans in another part of the system. 66 At present, 800 Pa of pressure is required to cause 20 m 3/s of air to flow. An unknown pressure 3 “P2” is required to cause 35 m /s to flow. P2 2 = P 1 x Q2 2 Q1 2 = 800 x (35) 2 (20) = 2 450 Pa There is already a pressure difference of 800 Pa across ABC due to the action of other fans. booster fan pressure = 2 450 - 800 = 1 650 Pa 3 The quantity of air handled by the booster fan must be a total of 35 m /s at a minimum pressure of 1650 Pa. 3 The duty of the booster fan is thus 35 m /s at 1 650 Pa Note: How can AC have a pressure drop of 800 Pa when the pressure drop in ABC is 2 450 Pa and the two airways run in parallel? The answer is simple: The booster fan adds pressure to the air and there is thus a “fan pressure gain” in ABC. The pressure losses due to friction in ABC are 2 450 Pa and the pressure gain due to the booster fan is 1 650 Pa. The difference is 800 Pa. 67 Ventilation Tutorial 5 Regulators & Booster Fans QUESTION 1 The pressure loss in the above airway is 720 Pa and the air density is 1,058 kilograms per cubic metre. What size regulator would be required to reduce the air quantity to 30 cubic metres per second? QUESTION 2 The pressure drop over the parallel airways shown in the sketch below is 900 Pa. The air density is 1,15 kilograms per cubic metre. Determine the size of the regulator required to reduce the quantity of air flowing in airway B to 60 cubic metres per second. QUESTION 3 The sketch below shows how air is distributed in a section of a mine. The pressure loss A-C is 900 Pa. It is desired to increase the quantity flowing in ABC to 30 cubic metres per second by installing a booster fan. Determine the duty of the required booster fan. 68 Ventilation Topic 10 Fan Types 10. FAN TYPES 10.1 General Description Main ventilation fans are usually placed at the top of the upcast shaft. This has the following advantages: 1. The working environment is maintained at a slightly lower pressure than the atmosphere. If the fan fails, natural ventilation will occur until the pressure underground has built up to normal atmospheric pressure. 2. Discharge evasées may be fitted, converting velocity pressure into static pressure and thereby enabling power savings. 3. No heat is added to the underground air. The disadvantages include: 1. The fan must handle foul air, making repair and maintenance difficult. Corrosion may become a serious problem. 2. Natural ventilation is reduced 3. It becomes difficult to use the upcast shaft for hoisting of materials. An alternative to this layout requires the placement of the fan at the top of the downcast shaft. 69 This presents the following disadvantages: 1. Access to the shaft is very difficult 2. Hoisting of men, materials and ore is difficult. 3. Heat is added to the downcast air. Placing the fan at the bottom of the upcast is generally the optimal solution. 1. Although the fan still produces heat, no heat is added to the air breathed by miners 2. The up-cast shaft is clear for hoisting. Disadvantages: 1. the fan handles foul air 2. the fan is not accessible during fires 3. re-circulation of foul air is likely unless a complex system for preventing this is installed. 10.1.1 Types of Fans Natural ventilating pressure is not sufficient to force ventilation to flow through modern large scale mines. In order to overcome this, various types of fans have been devised. The compression ratio of a fan is the discharge absolute pressure divided by the inlet absolute pressure. If this ratio is less than 1.1, the device may be referred to as a fan. If the ratio is greater than this value, the device is referred to as a compressor. This means that the pressure increase due to a fan is limited to 10 kPa, if the fan inlet is at atmospheric pressure. Fan outlet pressure is usually between 200 Pa and 7.5 kPa. A fan is a rotating machine drawing air in one side and delivering it at a higher pressure at the other. Mechanical energy is thus converted into potential energy. 70 i) Axial flow fans the direction of airflow is parallel to the axis of the shaft ii) Centrifugal fan or Radial flow fan air enters the fan parallel to the axis and is discharged radially 71 10.1.2 Mine Fans i) Main fans These are responsible for ventilating the bulk of the mine. They may be axial or radial but are usually 3 radial. They are electrically driven and commonly move quantities of air ranging from 12 m /s to 3 320 m /s. 72 The surface main fan installation above includes two centrifugal fan installations. One fan is generally switched off and acts as a stand-by system in case of maintenance or emergency. It can be clearly seen that the two fans are connected in parallel in this specific system. Another view of the same fan installation is the following: The following surface fan installation is given to illustrate an axial fan. 73 The surface fan installation above is that of an axial main fan system. Note the grass surrounding the installation. This could become dangerous in case of a fire in that a fire could ultimately damage the motor and electrical equipment. ii) Auxiliary fans Such fans are used to ventilate areas where air would not naturally enter. Examples of these areas include development ends and some stopes. Auxiliary fans commonly have diameters of 400 mm, 570 mm or 760 mm. 10.1.3 Fan Parts Principle component: impeller- hub - blades - mounted on shaft driven directly/ indirectly by motorconcealed by housing inlet cone outlet evasée guide vanes to control the direction of air through the cone. 74 10.2 Axial Flow Fans The impeller consists of two or more blades. Higher pressure machines generally have a higher number of blades. Shape and pitch of the blades vary considerably. The general configuration consists of short stubby blades on a large hub. The size of the hub is important as it prevents re-entry of air at the centre of the fan, thereby preventing pressure loss. Some fans have adjustable pitch. This means that the pitch may be mechanically altered once the fan has been stopped. Variable pitch refers to adjustment via a lever. This may occur during operation in some models. For this type of variability, the clearance between the blades and the housing needs to be very small. Accurate machining is required, increasing the cost. Fans may have two or more sets of blades mounted behind one another on the same shaft (multistage fans). These can produce higher pressure than is possible with a single stage fan. Air leaving an axial flow fan has a rotary motion, which represents a loss of energy. This can be corrected with guide vanes (stationary blades) or by using a multi-stage fan with a contra-rotating second impeller. In some cases, guide vanes may also be adjustable. 10.3 Centrifugal Fans (Rotary Fans) 75 Here the impeller consists of a hollow "wheel" or runner with a large number of blades orientated around the circumference. The blades are generally short and have a high width to height ratio. These fans may be arranged in three ways: I. radially II. forward curved III. backward curved 76 When the impeller rotates, air between the blades is thrown outwards, leaving the impeller at right angles to the axis before being forced to the outlet by the fan casing. Air moves into the fan to replace the evacuated air. These fans may have single or double inlets. 10.4 Fans Used in Auxiliary Ventilation 10.5 Effects of Reversal of Direction I. Axial flow fan: will deliver reduced quantity in the opposite direction at greatly reduced pressure and efficiency (). II. Centrifugal: will deliver reduced volume in the same direction at reduced pressure and . 77 Ventilation Topic 11 Fan Characteristics Measures of Fan Pressure Fan pressure is expressed in terms of pressure rise through the fan as follows: 1. Fan total pressure is the difference between the total pressures at the fan discharge and intake. 2. Fan pressure is the fan total pressure minus the fan velocity pressure. 3. Fan velocity is the velocity pressure corresponding to the average velocity at the fan discharge. The average velocity is calculated by dividing the volume flow rate of air by the area of the fan discharge orifice. Fan static pressure is often regarded as a measure of useful fan pressure. The total pressure developed by a fan depends on the volume flow rate through it. When intake and discharge are fully open, the fan total pressure is equal to the fan velocity pressure and the fan static pressure is zero. As the volume flow rate decreases, the fan velocity pressure decreases while the fan total pressure and consequently the fan static pressure increase. Theoretically, the fan total pressure should reach a maximum value when the intake and/or discharge are closed (i.e. when there is no airflow through the fan). Due to friction and shock losses, the fan total pressure reaches a maximum at a point in the range of the volume flow rate. The position of this point being dependant on the design of the fan in question. A graph of fan pressure against the volume flow rate of air is known as the fan characteristic and is determined by the laboratory work described below. The shape of the curve varies with the type of fan. A typical characteristic curve is shown overleaf. Fan Tests Reasons for testing fans 1. To check whether the fan performance complies with the manufacture’s specifications. This must be done as soon as possible after installation. 2. To check the fan performance after an overhaul. 3. To obtain performance figures which may not be readily available. Examples include performance at different pitch settings and ranges not covered by existing curves. 4. To determine whether the fan is still performing satisfactorily. Prolonged use may have resulted in inefficiency due to wear or accumulations of dirt on various parts. Measurements Required to Assess Fan Performance A collection of curves for a particular fan applies only for: a) a given air density, b) a specified fan speed and c) a particular pitch setting (if the fan has adjustable pitch blades or guide vanes. These measurements should all be specifies on the graph. 78 Air density is measured at the fan intake and is obtained from whirling hygrometer and barometer readings, using psychrometric charts. The fan speed is measured by means of an accurate rev-counter or stroboscope. The curves are produced using the following data: 1. quantity handled by the fan, 2. pressure produced by the fan and 3. input power. Quantities are measured with a vertical manometer. The input power is measured with a watt-meter in preference to the ammeter and voltmeter generally found on the control panel of the fan. General method To obtain different points on the characteristic curve of the fan, the resistance against which the fan is working is altered in stages. The quantity, pressure and input power are recorded at each stage. Such tests are conducted in laboratories. Manometers may be employed to measure fan pressure. They are used differently, depending on the location of the fan in the duct. 11.1.1 Forcing fan at duct inlet 11.1.2 Fan in column i) FTP 79 ii) FTP NB duct of uniform diameter iii) FSP 11.1.3 Exhaust fan at pipe outlet 11.2 Calculation of Power and Efficiency The electric power consumed by a three-phase AC motor is described by the following equation: W = EI pf 3 80 Where W : power (kW) E : voltage (kV) I : current (A) Pf : power factor (0.9) Power delivered at the shaft = motor output power Power delivered to fan = fan input power = motor output x drive efficiency Power added to air by the fan = air power W a = PQ 1000 Where: Wa: air power (kW) 3 Q: volume flow (m /s) P: pressure (Pa) Air power can also be calculated by multiplying fan input by fan efficiency. Using the sketch, it can be seen that: Motor efficiency = motor output power = b x 100% power input to motor a Drive efficiency = fan output power = c x 100% motor output power b 81 Fan efficiency = air power fan input power = Overall efficiency = air power Power input to motor d x 100% c = d x 100% a For example: 3 A fan ventilating a mine handles 85 m /s of air at a pressure of 750 Pa. The fan is driven by a 3-phase AC motor which consumes 65 A from a 1 000 V supply; the pf is 0.9. The motor efficiency is 95% and the drive efficiency is 92%. Calculate: a) the input power b) motor output power c) fan input power d) fan efficiency e) overall fan efficiency Answer: a) a) input power: W = EI pf 3 = 1x 65 x 0.9 x 1.73 = 101 Kw b) motor output power: = 101 x 0.95 = 96 kW c) c) fan input power: = 96 x 0.92 = 88 kW d) d) fan efficiency: = air power fan input power = PQ / 1000 88 = 63.75 88 = 72% 82 e) Overall efficiency: = air power input power = 63.75 / 101 = 63% Fans with belt drives The speed of a belt driven fan can be altered by changing the diameter of either the motor pulley or the fan pulley. Fan speed varies: inversely with the diameter of the fan pulley directly with the diameter of the motor pulley Fan speed = motor speed x motor pulley diameter fan pulley diameter Example: A fan runs at a speed of 12.3 rps. The fan pulley diameter is 195 mm and the motor pulley diameter is 150 mm. Determine the pulley sizes required to increase the fan speed to 18 rps. From the sketch it can be seen that the fan speed may be increased by either: decreasing the fan pulley diameter increasing the motor pulley diameter 83 I. new = old x old fan speed new fan speed = 195 x 12.5 18.0 = 133.25 mm II. new = old x new fan speed old fan speed = 150 x 18 12.3 = 219.5 mm 11.4 Characteristic Curves Quantity on the x axis is plotted against: pressure power efficiency In order to calculate the efficiency of the fan, air power must first be determined: W a = PQ 1000 Efficiency is determined by the following expression: = W a x 100 input power Example table 84 2 The resistance of the system is calculated to be 33.95 Ns .m -3 Determine: 1. the fan operating point 2. fan efficiency 3. fan power The fan operating point is given by the intersection of the system resistance curve and the fan characteristic curve. 3 1. FOP = 4.7 m /s 2. = 62.5% 3. Power = 5.665 kW 11.5 Natural Ventilating Pressure i) NVP assisted (SOP = System Operating Point) 2 2 P = RQ P = RQ - NVP ii) NVP opposed 2 2 P = RQ P = RQ + NVP 85 11.6 The Stall Zone This is the section of the characteristic curve in which both fan pressure and volume increase simultaneously, as opposed to normal conditions where volume flow decreases as pressure increases. If the fan is operating in the stall zone, air tends to separate from the blade surfaces, leading to excessive vibration and possibly damage to the fan if continued for long periods. A fan should never be operated in the stall zone. The stall zone is very marked in some fans, but hardly noticeable in others. Characteristics of a fan in the stall zone: vibrates excessively whines input amps show rapid oscillation quantity and pressure difference Situation remedied by: recirculating some of the air through the system (e.g. allowing some leakage to occur across an airlock) altering the characteristics of the mine so that the fan operates on a different part of its curve. 11.7 Typical Power Characteristics I. Overloading power characteristic If the power curve increases continuously as volume increases (i.e. if the volume is too high due to air short-circuiting) power requirements may be too high and the fan will burn out. 86 ii) Non-overloading power characteristics If the maximum power requirement occurs neither at maximum volume nor pressure, but in between, the power requirements will rise to a point as volume flow increases, but start decreasing once this point has been reached 11.8 Fan Evasées 11.8.1 Fitting a fan evasée to the discharge of a fan: improved fan performance no change in system resistance The magnitude of the improvement in performance is dependant on the characteristics of the evasée. Example: 2 2 An 85% efficient evasée with an inlet area of 0.5 m and an outlet area of 1.2 m is to be fitted to the discharge of an axial flow fan. Plot the new characteristic curve. The prevailing air density is 3. 1.2 kg/m 3 Choose any quantity, say 4 m /s 2 2 VP at inlet: v w = (4/0.5) x 1.2 = 38 Pa 2 2 87 VP at outlet: 2 2 0.5v w = (4/1.2) x 1.2 = 7 Pa 2 38 - 7 = 31 Pa loss in VP = 31 Pa theoretical gain in SP Actual gain = 85% of 31 Pa = 26 Pa 3 The actual gain in SP must now be added to the fan curve at Q = 4 m /s to obtain a new curve. 3 Another point must now be plotted. Try Q = 6 m /s Actual regain in SP = (VPin - VPout) x 100 2 2 = 1/2 w (vin - vout ) x 0.85 2 2 = 1/2 (1.2)[(6/0.5) - (6/1.2) ] x 0.85 = 61 Pa etc. 11.8.2 Fitting an Evasée to a system discharge reduced system resistance curve no change in fan curve Once again, the magnitude of the resistance reduction depends on the characteristics of the evasée. 88 Example: 2 2 An 80% efficient evasée with an inlet area of 0.5 m and an outlet area of 1.2 m is fitted to the discharge of a vent column. The density of the air is 1.0 kg/m3. Plot the new system resistance curve. 3 Assume 8 m /s flows through the system. 2 VPin = ½ wv = 128 Pa 2 VPout = ½ wv = 22 Pa Theoretical SP regain = 106 Pa actual SP regain = 0.8 x 106 = 85 Pa The actual SP regain is now subtracted from the system resistance curve in order to obtain a point on the system resistance curve. 3 At 8m /s, old P = 600 Pa 2 -3 R old = 9.38 Ns .m new P = 600 – 85 = 515 Pa 2. -3 R new = 8.05 Ns m 89 2 Use Rnew in the formula P = RQ to plot new curve The system and evasée are considered as a single unit and are represented by the new system resistance curve. 11.9 Fan Laws Fan characteristics curves are valid for a specific speed and specific air density. Fan laws may be used to predict the outcome of changes. 1. Varying speed, but constant air density Q n 2 P n 3 W n = 2. Varying density, constant speed Q=Q P w W w = Where: Q: quantity n: speed P: pressure W: power : efficiency w: density Both of these entities may change simultaneously. 90 Situation 1: n1 = 10 rps 3 w1 = 1.2 kg/m 3 At design point: Q1 = 115 m /s P1 = 1.37 kPa W 1 = 225 kW 1 = 70% Situation 2: n1 changes to 13.3 rps w1 changes to 1.04 kg/m 3 Q2 varying speed = Q1 x varying density n2 x n1 P2 = P1 x ( n2) ( n1) W2 = W1 x ( n2) ( n1) 2 = 1 x 1 2 3 1 x w2 w1 x w2 w1 x Therefore: 3 Q2 = 152.95 m /s P2 = 2.04 kPa W 2 = 458.76 kW 2 = 70% 91 1 92 93 94 12. FANS IN SERIES AND PARALLEL 12.1 Fans in series The figure below is given to illustrate multiple development end auxiliary ventilation. Each column could have more than one fan installed, either one after the other or spaced at regular intervals along the column. Fans that installed one behind the other so that each fan handles the same quantity of air are said to be in series. They may be directly behind one another or installed some distance apart. Provided they handle the same quantity of air, they are in series. Both fans will handle the same quantity of air, but each fan will add its own pressure, according to its capabilities. The total amount of pressure added by the fans is the sum of the individual pressures added by each fan. 95 The above picture illustrates a development end being ventilated by either a force or an exhaust ventilation column and fan or both systems together. 96 Fan laws for fans in series are thus as follows: QT = Q1 = Q2 PT = P1 + P2 If the performance curves of both fans and the resistance of the system in which they operate is known, a combined performance curve of both fans can be obtained. 12.2 Fans in parallel Fans installed side-by-side in such a way that they draw air from the same source and deliver it to the same place are said to be in parallel. In such a configuration, each fan must produce the same amount of pressure as the other as they have common intakes and discharges (as with parallel airways). Thus the total amount of pressure added by both fans equals the amount of pressure added by each fan. 97 The ventilation column above clearly illustrates the use of bends in a force or exhaust ventilation system 98 The above picture illustrates the use of a force and exhaust ventilation system. Each fan will handle a different quantity of air, depending on its characteristics. The quantity of air handled by fans in parallel is the sum of the individual quantities handled by both fans. The fans laws for fans in parallel may be written as follows: QT = Q1 + Q2 PT = P1 = P2 The following pages provide the student with an overview of fans, their characteristics, basic calculations and graphical illustrations. 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 VENTILATION ENGINEERING FANS & AIRFLOW Test Date: Time: Venue: Total: 2001 11h30 - 13h30 CM4 70 marks Instructions ANSWER ALL QUESTIONS This test accounts for 25% of the final course mark 1. List the four classes (with any sub-classes) of toxic gases, providing an example of each and indicating the effect of the gas on the body. [10] 2. In twin shaft systems, natural ventilating pressure can result in significant airflows through the mine. Briefly discuss the factors which determine the direction in which NVP acts (i.e. from downcast to upcast or upcast to downcast). [4] 3. How much fresh air is required to ensure that a source of 0.0005 m3/s of methane to ensure that permissible levels are not exceeded? [3] 4. A fluid with a density of 1.1 kg/m3 flows at a velocity of 18 m/s along a conduit of 0.25 m in radius. The coefficient of dynamic viscosity is 0.0016 Pa.s. What flow conditions predominate? [3] 5. A 200m long, straight airway of 1.5 m diameter interconnects with a 45(short radius) bend. From the perspective of airway resistance, what is the equivalent length of the airway and the bend? [2] 6. A fan runs at speed of 10 rps with a motor pulley diameter of 100 mm and a fan pulley diameter of 500 mm. The speed must be increased to 15 rps. Calculate the pulley sizes required if: a) only the fan pulley is changed b) only the motor pulley is changed c) both pulleys are changed [9] 122 7. A mine ventilation fan circulates a volume of 105 m3/s of air under a pressure of 725 Pa. The three phase motor is connected to a 380 V power supply and consumes 65 A. The efficiencies of the drive and the motor are 92% and 95% respectively. The power factor is 0.9. a) What is the input power? b) What is the motor output power? c) What is the fan efficiency? d) What is the efficiency of the whole unit? [6] 8. A haulage is 300 m long and is 3m high by 3m wide. The air density underground is approximately 1.15 kg/m3. If K = 0.0031 Ns2/m4, what is the air power required to convey a quantity of 50 m3/s along the airway? [3] 9. What are the units of Reynold’s Number? [1] 10. Given the following data, complete the table and plot the characteristic curve of the fan in question: a) If the system resistance is 33 Ns2.m-8, determine the fan operating point. [10] b) Due to a fall go ground in an R.A.W., the system resistance increases to 350 Ns2.m-8. Plot the new curve. Will the fan be capable of operation at this new point? On inspection of the fan, what symptoms would you expect to observe if the fan was operating on this part of its characteristic curve? How could this situation be remedied? [11 123 11. Explain the difference between sensible and latent heat, giving an example for the sources of each. [3] 12. Determine the total amount of heat added to air passing over a heater bank at a barometric pressure of 85 kPa. The flow rate is 10 m3/s. Inlet air has a temperature of 13C and a relative humidity of 90%. Outlet air has a temperature of 30C. The humidity ratio at both points is 0.0097 kg/kg. [5] END Given formulae 124 MEMO Mark breakdown Gases & Fumes Gas calc Ventilation practice Fluid mechanics - Bernoulli Airflow in airways Vent networks Fan types Regulators and booster Fan characteristics Q1 What size regulator would be required to reduce the air quantity in an airway from 80 m3/s to 20 m3/s if the air density is 1.1 kg/m3 and the pressure loss is 500 Pa? [5] Ans: P1 = P2 Q12 Q22 500 = P 6400 400 P = 31.25 Pa P used up by regulator must be 500 - 31.25 = 468.75 A = 1.2 Q (w/P) = 1.2 x 20 x (1.1/468.75) = 1.162 m2 (1.065 also acceptable) Gases & Fumes 1. List the four classes (with any sub-classes) of toxic gases, providing an example of each and indicating the effect of the gas on the body. [10] Ans 1. Asphyxiant gases If the oxygen supply to the bloodstream and the tissues of the body decreases or fails, asphyxiation results. The may occur in two forms: 125 simple asphyxia occurs when sufficient air is breathed, but the air has an oxygen deficiency; chemical asphyxia occurs when a substance present in the air prevents oxygen from being utilized by the body (e.g. carbon monoxide). 2. Irritant gases These gases irritate and inflame tissue in contact with them. Inflammation of the lungs leads to pulmonary oedema (fluids are produced in the lungs, causing suffocation). Nitrous fumes and hydrogen sulphide act in this way. 3. Narcotic gases Gases such as chloroform and ether which act on the nervous system, after having been absorbed in the blood and transported to the tissue, are narcotic gases. If large quantities are absorbed, the normal coma will terminate in death. 4. Protoplasmic poisons After absorption by the body, these gases destroy the living cells in contact with them. Examples include fumes of metals such as mercury and lead. Q2. In twin shaft systems, natural ventilating pressure can result in significant airflows through the mine. Briefly discuss the factors which determine the direction in which NVP acts (i.e. from downcast to upcast or upcast to downcast). [4] unequal depth - air down shallow shaft and up deep shaft as T in shallow lower than that in deep. In Summer, T in shallow may be higher and direction will reverse. equal depth - Direction determined by prevailing wind or by one shaft being wetter thus cooler modern mines air in downcast = cooler & denser than in upcast. Fluctuations in downcast column may lead to complete reversal of NVP. 126 Q3 How much fresh air is required to ensure that a source of 0.0005 m3/s of methane to ensure that permissible levels are not exceeded? [3] answer: permissible level = 1% (10 000 ppm) Q = Q1 x 10^6 MAC - N Q = quantity of fresh air required (m3/s) Q1 = quantity of gas (m3/s) MAC = max allowable concentration (ppm N = conc of gas in normal air = 0.0005 x 10^6 10 000 - 0 = 0.05 m3/s Q4 3 A fluid with a density of 1.1 kg/m flows at a velocity of 18 m/s along a conduit of 0.25 m in radius. The coefficient of dynamic viscosity is 0.0016 Pa.s. What flow conditions predominate? [2] answer: R = wvD μ = 1.1 x 18 x 0.5 0.0016 = 6187.5 = Turbulent flow Q5 A 200m long, straight airway of 1.5 m diameter interconnects with a 45(short radius) bend. From the perspective of airway resistance, what is the equivalent length of the airway and the bend? [3] 127 Answer: L=n D for a 45bend, n = 18 i.e. L = 18 x 1.5 = 27 m Total length = 227 m Q6 A fan runs at speed of 10 rps with a motor pulley diameter of 100 mm and a fan pulley diameter of 500 mm. The speed must be increased to 15 rps. Calculate the pulley sizes required if: d) only the fan pulley is changed e) only the motor pulley is changed f) both pulleys are changed [9] answer: fan speed = motor speed x motor pulley diameter fan pulley diameter original fan speed = 10 = motor speed x 100 / 500 motor speed = 50 rps new fan speed = 15 = 10 x 100 / new fan pulley new fan pulley = 66.6 mm or new fan speed = 15 = 10 x new motor pulley / 500 new motor pulley = 750 mm 128 Q7 A mine ventilation fan circulates a volume of 105 m3/s of air under a pressure of 725 Pa. The three phase motor is connected to a 380 V power supply and consumes 65 A. The efficiencies of the drive and the motor are 92% and 95% respectively. The power factor is 0.9. e) What is the input power? f) What is the motor output power? g) What is the fan efficiency? h) What is the efficiency of the whole unit? [7] Answer 7a: W = EI pf 3 = .38 x 65 x 0.9 x 3 = 38.5 Kw Answer 7b: Input power x efficiency of motor Answer 7c: Air power [2] = 38.5 x .95 = 36.6 kW [1] = p x Q / 1000 = 105 x 725 / 1000 = 76.125 kW Fan input power = motor output x drive efficiency = 36.6 x .92 = 33.7 kW Fan efficiency = air power / fan input power x 100% = 76.125 / 33.7 x 100 = 233.67 % [3] Answer 7d: Overall fan efficiency = air power / motor input power x 100% = 76.125 / 38.5 x 100 = 197.73% [1] 129 Q8 A haulage is 300 m long and is 3 m high by 3 m wide. The air density underground is approximately 1.15 kg/m3. If K = 0.0031 Ns2/m4, what is the air power required to convey a quantity of 50 m3/s along the airway? [3] answer: P = KCLQ2 x w A3 1.2 = 0.0031 x 12 x 300 x (50)2 x 1.15 3 9 1.2 = 36.68 Pa Q9 What are the units of Reynold’s Number? [1] Answer: dimensionless Q10 Given the following data, complete the table and plot the characteristic curve of the fan in question: a. If the system resistance is 33 Ns2.m-8, determine the fan operating point. [10] b. Due to a fall go ground in an R.A.W., the system resistance increases to 350 2 -8 Ns .m . Plot the new curve. Will the fan be capable of operation at this new point? On inspection of the fan, what symptoms would you expect to observe if the fan was operating on this part of its characteristic curve? How could this situation be remedied? [11] 130 Answer: [2] If the system resistance is 33 Ns2.m-3, determine the fan operating point. Q = 5.15 m3/s P = 875 Pa Eff = 78% [8] Due to a fall go ground in an R.A.W., the system resistance increases to 350 Ns2.m-8. Plot the new curve. Will the fan be capable of operation at this new point? On inspection of the fan, what symptoms would you expect to observe if the fan was operating on this part of its characteristic curve? How could this situation be remedied? no - stall zone. [6] Symptoms: Vibrates Whines Input amps show rapid oscillation [3] Remedy: Allow some leakage across an airlock (re-circulation) Altering characteristic of mine so that fan operates on different part of curve. [2] 131 Q11 i) Explain the difference between sensible and latent heat, giving an example for the sources of each. [3] ii) Determine the total amount of heat added to air passing over a heater bank at a barometric pressure of 85 kPa. The flow rate is 10 m3/s. Inlet air has a temperature of 13C and a relative humidity of 90%. Outlet air has a temperature of 30C. The humidity ratio at both points is 0.0097 kg/kg. [5] Ans (i) Sensible Heat Any heat which is added or taken away from the air and resulting in a change in the temperature of the air is called sensible heat. This is the heat added by lights. solar radiation, conduction, machinery, heaters, etc. Latent Heat When heat added to or removed from a substance results in a phase change with a temperature change is called latent heat. A latent heat process always involves a change in the amount of water vapour present in air. Latent heat is added to air from sources such as the human body, outside air being introduced into an air-conditioned space and any other appliance which involves water (kettles, evaporators etc.) (ii) 3 Flow rate = 10m /s From chart: 3 Specific volume of air at intake: 0.982 m /kg, mass flow rate: 10/.982 = 10.1823 kg/s [2] Sigma heat at pt 1. = 37.5 kJ/kg at pt 2. = 55.0 kJ/kg S = 17.5 kJ/kg [2] Total heat added = 17.5 x 10.1823 = 178.207kW And Q=MaCaTa = 10 x 1.005 x (30 – 13) = 170 W 132 [1] Heat & Refrigeration Topic 1 Deep Level Mining 1.Introduction to Psychrometry Psychrometry is concerned with the thermodynamic properties of mixtures of air and water vapour. This is of particular importance in mine ventilation as air undergoes large changes in moisture content as it flows through a mine. Information on the thermodynamic properties of air is vital in understanding phenomena as diverse as the flow of air in an upcast shaft and the interaction between heated air and chilled water sprays. Air Air is mixture of many gases. The principle components are Nitrogen, Oxygen, Argon and Carbon dioxide. Omitted from this list is water vapour. The term “air” is frequently used to describe a mixture of the above gases and water vapour, but some confusion exists as it is also employed to describe just the above gases. In order to avoid this confusion, the terms “air” and “dry air” may be adopted, where the former includes water vapour. Gas relationships Calculations of the properties of gases are effected using the mol. This is the quantity of a gas which is numerically equal to the molecular mass of the gas. Thus a mol of oxygen (which has a molecular mass of 32) has a mass of 32 g, and a mol of carbon dioxide, with a molecular mass of 44.01 has a mass of 44.01 g. A mol of any gas contains a fixed number of molecules, given by L, the Avogadro constant (6.02283 x 1026 molecules per mol). Gas Laws Boyle's Law If a constant mass of gas is kept at a constant temperature, then its pressure is inversely proportional to its volume: P1V1 = P2V2 = P3V3 =…. etc. 133 A certain mass of air occupies a volume of 16 m 3 when the pressure is 100 kPa. If the temperature of the air remains constant, what volume will the same mass of air occupy at a pressure of 80 kPa? Charles' Law If a given mass of gas is kept at a constant pressure, the volume of the gas is directly proportional to its absolute temperature: V1 = V2 = V3 T1 T 2 T3 3 8 m /s of air at 26C dry bulb enters an underground hoist chamber. The pressure of the air remains constant and there is no change in the amount of water vapour in the air. If the air leaves the chamber at 33C dry bulb, what is the volume of the air leaving the hoist chamber? The Universal Gas Law and the Ideal Gas Relationship Combining Boyle's and Charles' Laws yields the Universal Gas Law: P1V1 P2V2 T1 T2 P3V3 T3 As the pressure of real gases tends to zero, their behaviour approximates that of ideal gases1. The behaviour of ideal gases is described by the ideal gas relationship: PV = mRT Where: P = absolute pressure (kPa) 3 V = volume (m ) m = mass of gas (kg) R = gas constant (kJ/kg K) T = absolute temperature (K) 134 Avogadro’s hypothesis states that at a given pressure and temperature, the number of molecules per unit volume is constant. Applying this fact to the above equation yields the Universal Ideal Gas Equation: PV m R* T M Where: M = molecular mass R* = universal gas constant (kJ/kg mol K). This has a numerical value of 8.31436 kJ/kg mol K The ratio m/M (= n) is the number of mols of the gas and the universal ideal gas equation is PV = nR*T Gases of interest in mine ventilation: Table 1 Gasses and their mol mass Gas Mixtures The universal ideal gas equation applies both to pure gases and to mixtures of gases. In order to apply the equation to mixtures of gases, Dalton’s law of partial pressures is required. This states that the pressure exerted by a mixture of gases present in a given volume, and at a given temperature is equal to the sum of the pressures exerted by the individual components of the mixture if each alone occupied the volume at the same temperature. For k gases, the universal ideal gas equation can be written as follows: (P1 + P2 +...+ Pk)V = (n1 + n2 +...+ nk)R*T 135 The composition of a gas mixture can be expressed in terms of mole fractions (x i) for each component (i) xi = ni = ni . n (n1 + n2 +...+ nk) 2. Psychrometric Properties The gas constant for a gas or gas mixture is R or R*/M (where R* is the universal gas constant and M is the molecular mass). For standard dry air, the gas constant has the value: 8.31436 28.9664 = 0.287035 kJ/kg K Dry air may have a composition which differs appreciably from the standard. The air may also have a water vapour component. In order to predict changes in air, it is necessary to factor these differences into calculations. This is done by means of psychrometric equations. 1. Moisture Content (r) This is the mass of water vapour associated with a unit mass of dry air. r mw M wPw M w P w m a M aP a . M a P P w P is the absolute pressure, which is equal to the sum of the dry air pressure and the water vapour pressure. 2. Specific Volume () This is the volume occupied by the air expressed per unit mass of dry air. v = = R* T = ma Ma Pa R* T . Ma (P - Pw) 136 3. Density (w) The mass of air (dry air plus water vapour) per unit volume. In contrast to the first two properties, density is the mass of dry air and water vapour per unit volume. 4. Enthalpy (H) This property is measured in J/kg. It was once known as total heat or total energy. H = Ha + H w The enthalpy of dry air is given by: Ha = Cpa tdb = 1.005 tdb Where tdb is the dry bulb temperature (C) and Cpa is the thermal capacity at constant pressure for dry air (1.005 kJ/kgC). The enthalpy of the water vapour component (Hw) is the enthalpy of the water vapour associated with a unit mass of dry air. For the purposes of most mine ventilation calculations, Hw may be approximated by the following empirical relationship: H’w = 1.80 tdb + 2 501 (J/kg) This is the linear equation form. Two other equations in the quadratic and cubic related forms could be used as provided in the textbook (p. 442 EESAM handbook). Use of the linear equation expression results in an enthalpy expressed per unit mass of dry air. 137 5. Sigma Heat (S) This property is the enthalpy of the air less the enthalpy of the water vapour associated with the unit mass of dry air. The latter is calculated as if the water vapour was present as liquid at the wet bulb temperature. Sigma heat is expressed per unit mass of dry air: S = H - rH’wl [kJ/kg] Where: H’wl = 4.18 twb and r = moisture content 6. Relative Humidity () Relative humidity is the ratio of the actual vapour pressure to the saturated vapour pressure at dry bulb temperature: = Pw x 100% P”ws Where: P”ws = 0.6105 Exp. (17.27 tdb / 237.3 + tdb) [kPa] Pw is usually given 7. Dew point temperature (tdp) This is the temperature to which air must be cooled for condensation to begin. At this point the air becomes saturated. As there is no change in moisture content during the cooling process, the vapour content remains constant. The dew point is thus the temperature at which the saturated vapour pressure is equal to the actual vapour pressure. Dew point can be obtained from tables relating saturated vapour pressure to temperature. tdp 237.3 x ℃ 17.27 x 138 Where: 3. Psychrometric charts In order to determine the properties of an air-water mixture, the following information is required: barometric pressure (kPa) wet bulb temperature (C) dry bulb temperature (C) The procedure for analysis is as follows: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Get wet bulb temperature Find appropriate chart (pressure related) Determine state of air-water mixture Plot starting point using wet & dry bulb temperatures Read off apparent specific humidity Read off apparent specific volume Calculate: apparent density = 1 / apparent specific volume Read off vapour pressure Calculate relative humidity Calculate enthalpy Calculate sigma heat content Calculate dew point The mass of dry air is given by: M=Qxw Or M = Q / As an example, figure 1 below is provided whereby all the information could be determined from such a chart. Please note that this information only relates to the 100 kPa barometric pressure level. All psychrometric charts are available in Barrenburg’s book for psychrometry. 139 Special softwares for PC’s are also available from suppliers as well as within software packages such as Environ 2.5 and the latest windows based VUMA package. The intension here is not to use such packages but rather to familiarise the student with the parameters and related formula and actually calculate the psychrometric values of importance. 140 Figure 1: Psychrometric chart at a pressure of 100 kPa Please note: Pages 459 to 463 (E.E.S.A.M.) are to be studied as examples when using psychrometric calculated data. Air mass flow and heat flow calculations are important in this context. The following important steps are to be followed in order for the student to be able to read the psychrometric charts. 141 142 143 144 145 146 147 148 149 The following is the first page of Barrenburg psychrometric charts as an example. The student should familiarise him/ herself with the use of these charts. 150 Example of the sigma-heat chart found in Barrenburg’s book of charts 151 Another example of the enthalpy chart also found in Barrenburg’s book of charts 152 4. Heat Sources 1. Natural Sources of Heat 1.1 Heat transfer from rock strata The temperature of virgin rock increases with depth below the earth’s surface as a result of the flow of heat from the interior of the planet (Where does this interior heat originate?). The temperature of the rock at depth is thus reliant on the thermal conductivity of the rock and on the long-term average surface temperatures. Whenever the rock surface in an excavation is at a higher temperature than the ventilating air, heat will flow from the rock into the air (Heat flows from hot to cold as airflow would occur from a high pressure to a low pressure). This may occur by convection (fissure water) or conduction. 1.2. Oxidation of rock strata The oxidation of certain minerals, such as pyrite, is an exothermic reaction and results in the release of substantial amounts of heat. Mt. Isa mine in Australia has experienced difficulties as a result of this, but fortunately, the problem does not occur in South African gold mines. 2. Autocompression This phenomenon is not strictly speaking a source of heat. It applies to compressible fluids and results in an increase in temperature when potential energy is converted into enthalpy (enthalpy is total heat). Autocompression is important in the design of mine ventilation systems as such systems rely heavily on circulating fluids (i.e. chilled water) to remove excess heat within the mine. The enthalpy increase associated with autocompression serves to reduce the amount of heat that the fluid is able to remove. The increase in enthalpy due to autocompression is typically 9.79 kJ/kg for every 1 000 m. Therefore, the temperature increase effect as air or any fluid changes elevation is independent of the frictional impact. The steady flow equation gives the following: H2 – H1 = (Z1 – Z2)g +q12 [J/kg] Where: H = Enthalpy (J/kg) 153 Z = height above datum point (m) 2 g = Gravitational acceleration (m/s ) and q = surrounding heat (J/kg) The subscripts 1 and 2 refer to the inlet and outlet positions respectively. The increase in temperature is sometimes referred to as the adiabatic laps rate. When ignoring external heat influences (q = 0), and calculating the temperature difference between two vertically different positions, the equation through manipulation of equalities become: T ( Z1 Z2) g Cp ℃ 3. Artificial Sources of Heat These are sources of heat arising from normal day to day activities taking place in the mine. 3.1 Electrical machinery Hoist room with electric motors, etc. In many mines, electricity is the principle source of power. All equipment either converts this energy into heat energy or useful work. In the thermodynamic sense, “useful work” involves increasing the potential energy of an object or fluid by lifting it to a higher elevation against the force of gravity. 154 Keeping this definition in mind, it becomes apparent that fans and lamps convert all the electrical energy supplied to them into heat. Winches, hoists, locomotives and other motors convert a greater or lesser amount of their electrical energy into heat, depending on the application and efficient design. Increases in enthalpy and heat dissipated would differ in each specific design because of differences in motor power utilised and the application required (Refer to pages 598 to 605 in EESAM for example calculations). Loco on maintenance 3.2 Diesel equipment Underground diesel operated machinery 155 As with electrically powered machinery, heat is dissipated when the diesel engine is not employed in “useful work”(as defined above). LHDs and similar vehicles seldom traverse large gradients and thus the greater portion of energy consumed by the engine is release as heat. To provide an example, internal combustion diesel engines compares to about one third of the efficiency of that of electrical equipment. Therefore, diesels will produce about three times more heat than a mechanically similar electrical powered machine. The range of heat production could be between 30 to 500 kW depending upon the equipment rated power and work load performed. A calculation could easily be done once the diesel fuel consumption and fuel calorific value is known. Underground diesel LHD operating 3.3 Compressed Air This represents a safe and convenient source of power for rock drills, pumps and fans. The principle difference between this and other sources of energy is that the exhaust air enters the mine’s ventilation with a low enthalpy (the air has provided mechanical power). This acts as a source of coolth and may cancel the heat generated by the device. Rock drills may release a negative amount of heat (-3 kW) as a result of this phenomenon. 156 3.4 People People working underground People function by internally combusting various foodstuffs. This results in the emission of heat. Typical values are: at rest 90 - 115 W light work rate 200 W moderate work 275 W hard work rate 470 W For a shift of 1000 workers, this may result in a substantial source of heat. 157 3.5 Explosives Explosives being put into the drilled hole Large amounts of heat are liberated when explosives are used. There is no evidence to suggest that the heat liberated during blasting is completely removed during the re-entry period. This heat most probably enters the broken rock and is released over a long period of time: ammon gelignite 4650 kJ/kg ammon dynamite 4030 kJ/kg anfex 3820 kJ/kg 4. Heat & Psychrometry Sensible Heat Any heat which is added or taken away from the air, resulting in a change in the temperature of the air is called sensible heat. This is the heat added by lights. solar radiation, conduction, machinery, heaters etc. Sensible heat is removed by passing the air over a colder surface. In a pure sensible heating process, no water is evaporated or condensed and thus the humidity ratio of the air does not change. Sensible heating takes place along a horizontal line on the psychrometric chart. 158 Air at the intake of an electric heater bank of a plant at sea is at a temperature of 15C with a relative 3 humidity of 90%. 8 m /s of air pass over the heater bank. After the bank, the air is at a temperature of 30C. The humidity ratio at both points is 0.0097 kg/kg. The amount of heat added to the air can be determined by calculation or from psychrometric charts. The specific volume of air at the intake (from 3 the psychrometric chart) is 0.829m /kg and the mass flow rate is 8 / 0.829 or 9.65 kg/s. The total heat can be calculated using the formula: q = MCT = 9.65 x 1.012 x (30 - 15) = 146.5 kW (Use a psychrometric chart to verify this. Note the barometric pressure at sea level 101.3kPa). Latent Heat When heat is added to or removed from a substance and results in a phase change without a temperature change, it is called latent heat. A latent heat process always involves a change in the amount of water vapour present in air. Adding latent heat to air implies an increase in the humidity ratio (evaporation) whilst removing latent heat reduces the humidity ratio (condensation). Latent heat is added to air from sources such as the human body, outside air being introduced into an airconditioned space and any other appliance which involves water (kettles, evaporators etc.) Consider a humidifier with electric elements for water heating. This is a process where only, the absolute humidity (or moisture content) of the air is increased. Air passing through such a system has an initial temperature of 30C and a final temperature of 30C. The initial relative humidity is 37% and the final relative humidity is 50%. There is no sensible heat increase as the dry bulb temperature remains constant. The initial absolute humidity is 0.0097 kg/kg and the final absolute humidity is 0.0134 kg/kg. 0.0037 kg of water has thus been added to each kilogram of air passing over the humidifier. If the amount of air is 9.65kg, the total amount of water added to the air is 9.65 x 0.0037 = 0.03571 kg. To evaporate one kg of water requires 2 450 kJ, thus 0.03571 x 2 450 = 87.5 kW is required (Verify this using a psychrometric chart). Heat - Geothermal Gradients The quartzites of the Wits system are good conductors (Thermal conductive values of between 5 to 7 W/mK) and therefore rock temperatures do not increase rapidly with depth in the central Wits area (Geothermal gradient). In the Free State (and some other areas), the quartzites are overlain by Karoo shales and Ventersdorp Lavas which are not good conductors of heat (Generally < 4 W/mK). The VRT in these areas increases more rapidly with depth. The earth constantly drifts on crustal plates. These plates are relatively thin, i.e. 90km in thickness, with relation to the earth’s radius or diameter. Mining activity (depth) only takes place in a very small upper-layer portion in the drifting plates. The geothermal flow of heat emanating from the earth’s core and passing through that skin layer has an average value of 0.05 to 0.06W/m2. The heat flux can naturally differ and therefore be much higher depending on the geological region, thereby referring to thermal conductivity of the local strata. The mean heat flow of continents and oceans are 0.065 and 0.101 W/m2 respectively, which when weighted yield a global mean of 0.087 W/m2. More than half of the Earth’s heat loss comes from oceanic lithosphere (Pollack et al, 1993). The heat flow in geological terms are generally expressed in units of milli-watt per square metre (mW/m2) The data collected by Pollack et al constituted some 10,337continental measurements and 9,684 oceanic measurements. Figure 3 depicts the measurement stations around the world from which the data was complied. 159 Figure 3 Geographic distribution of heat flow measurement sites From measurement done by Jones (Jones, 1988, p. 3252) the Witwatersrand Basin heat flow has a mean value of 0.051 W/m2 (standard deviation [SD] of 6mW/m2).The heat flow in the Witwatersrand Basin is higher than the worldwide mean for Archaean cratons which is 0.041 W/m2 (sd of 11 W/m2). The reason (Jones, 1988) for the excess heat flow in the Witwatersrand Basin is because of radioactive heat produced in the basin’s strata which measures about 0.0075 W/m2. Measurements from borehole data were also listed (p. 3248) as compiled from various sites around South African mining operations. The heat flow was determined to be between 0.041 W/m2 (Avondrust AR1 borehole) and 0.072 W/m2 (Hartebeesfontein-HB5d-borehole). Further discussions on thermal gradients are provided in sub-section 2.5.6. Table 3 indicates some international heat flow values as given by Jones (1988, p.3255) Table 3. International heat flow trends (Jones, 1988) 160 When Fourier’s law is then applied to a heat flux value of say 0.06 W/m 2 for each square metre of land surface to indicate the variation in temperature, , with respect to depth, D, then 𝑑𝜃 𝑑𝐷 = 0.06 𝑘 ℃/m Eq.2.2.2 The increase of virgin rock temperature (VRT) with depth is known as the geothermal gradient. The inverted use of equation 2.2.2 is also often used thereby providing integer values in units of m/°C. The inverted use of the equation is then referred to as the geothermal step 𝑑𝐷 𝑑𝜃 . However, in normal mining terms, geothermal gradient is the general expression used (C/m) (McPherson, 1992). Watermeyer and Hoffenberg (1932, pp. 595 – 597) explained that in the coal mines of Great Britain the geothermal gradient averages a rise of 0.556C for every 21 m in depth (0.0265C/m), whereas on the Witwatersrand in South Africa, the gradient is more forgiving, i.e. 0.556C for every 67 m in depth (0.0083C/m). This rather flat geothermal gradient of the Witwatersrand area is because of the high thermal conductivity of the strata. Table 4 indicates some relevant thermal gradient values for different geological areas in South Africa Table 4 Mean thermal gradients VRT calculation As a rough estimate, the following linear related formula could be applied to determine the VRT at depth. Care should be taken not to generalise these two equations as the geology at different locations within the Witwatersrand do change rapidly and would influence the VRT accordingly. The best method of VRT determination is to measure it in-situ, preferably within a freshly opened up area. Witwatersrand area: 18 + (9.3 x d) Free State area: 20 + (14.5 x d) Where: d = depth [km] 161 The following graph shows the VRT with relation to depth for various countries/areas over the world. The graph above was constructed with data available. Some of the lines in the graph for the different regions were extrapolated further than actual data available, i.e. Hungary, Bushveld complex, etc. These data points indicating VRT values should ultimately be measured to verify or correct the extrapolated values obtained. The VRT values for the Witwatersrand and Free State for instance are only valid up to a depth of around 3500 mbc. 5. Heat - Mixing Airstreams Use: Sigma heat content Moisture content (S) (r) If two airstreams A and B mix to form airstream C, the sigma heat content of the mixture (Sc) can be calculated from: Sc = (MA x SA) + (MB x SB) (MA + MB) 162 Note: 1. (MA x SA) = total kW heat from A 2. (MB x SB) = total kW heat from B 3. (1.) + (2.) = total kW heat in C 4. (MA + MB) = total mass flow in C 5. Sc = sigma heat content of C Similarly the moisture content of the mixture (rc) can be calculated from: rc = (MA x rA) + (MB x rB) (MA + MB) Where: 1. 2. 4. 5. 6. (MA x rA) = the total moisture from A (MB x rB) = the total moisture from B (1.) + (2.) = the total moisture in C (MA + MB) = the total mass flow in C rc moisture content of the mixture C Once sc and rc have been determined, the temperature of the mixture can be read off at the INTERSECTION of these two lines on the relevant psychrometric chart. 6. Heat - Mixing Airstreams: The straight line method Procedure: 1. Plot the temperature of A 2. Plot the temperature of B 3. The temperature of C lies on the straight line between these two points, closer to the point with the higher mass of air. The exact position of the “mixture point” is determined by the inverse ratio of the mass of either original point to the total mass. (This ratio is multiplied by the distance between the original two points) 163 Total mass flow = 62.6 + 29.4 = 92.0 kg/s B’s proportion = 29.4 / 92.0 = 0.32 A’s proportion = 62.6 / 92.0 = 0.68 Therefore C lies (1 - 0.68) x length AB from A or C lies (1 - 0.32) x length AB from B Note: C lies closer to A because A has the larger mass Example 3 3 42.8 m /s of air at a temperature of 25.0/27.2 C is mixed with 23.3 m /s of air at temperature of 31.7/32.5 C. The barometric pressure is 115 kPa. Determine the temperature of the mixture. The answer is provided in the note below. 7. Heat Impacts & Acclimatisation 164 Effect of Heat on Workers Production Experiments conducted by COMRO (now Miningtek) show that a worker’s production is affected by heat and air velocity. At wetbulb temperatures of less than 27.2C, a person’s work output is not affected, even in environments with low air velocities. The combined effect of wetbulb temperature and air velocity is shown below: Table 5 Heat & Productivity relationship Effect of Heat on Health Physiological Effect As the temperature of work rate increases, the body tries to compensate by sweating more. The evaporation of sweat has a cooling effect. Under extremely hot conditions, little cooling results. Working at a high rate leads to: cramps heat exhaustion heat stroke Psychological Effect More mistakes are made when people work under hot conditions. Errors lead to accidents and low morale. 165 Why people are acclimatised Acclimatised men work harder in hot conditions with a greatly reduced chance of heat stroke. The need for acclimatisation of underground workers in deep, hot mines has been recognised for some time 7.2 Practical aspects of human heat stress (Chapter 21, Environmental Engineering in SA Mines - EESAM) 7.3 Heat Balance of a Working Man (Chapter 20, Environmental Engineering in SA Mines) 166 8. Refrigeration The Refrigeration Cycle Refrigeration is the process of cooling. Heat is removed from a substance at one temperature level and then discharged at a higher temperature level. The removal of this heat produces a condition called “cold”. This term, together with “hot”, is relative and makes no reference to the absolute amount of heat in a substance. A refrigeration machine uses mechanical work to absorb heat at one temperature and to reject heat to a sink at a higher temperature. Work is thus expended to produce coolth, a phenomenon in accordance with the laws of thermodynamics which state that work and heat are mutually convertible. Large cooling plants are used to cool water either on surface or underground. This water is then circulated to working places to be used as service water, or it is used to bulk-cool downcast air. It may also be circulated through the sections of the mine and used to cool the air in water-to-air heat exchangers. There are several types of refrigeration system available. This course will describe the commonly used vapour compression system. In machines of this type, a substance known as the refrigerant circulates continuously. It enters the evaporator as a liquid and is evaporated, the heat required for this being obtained from the substance being cooled. The resultant vapour then enters the compressor, where it is compressed to a higher pressure and then discharged to the condenser. Here the refrigerant is cooled and then condensed to a liquid, the latent heat released being transferred to the circulating condenser water. The liquid refrigerant then leaves the condenser and passes through an expansion valve before once again entering the evaporator. The Pressure-Enthalpy (P-h) Diagram This is a useful means for examining and analysing the operation of a vapour compression system. The diagram shows the various properties of the refrigerant 167 The main features are: the sub-cooled or liquid region: lines of constant temperature in this region will be vertical, extending upwards from the saturated liquid line. the wet region: this represents the condition of the refrigerant while undergoing a change of phase from liquid to vapour during the addition of latent heat at any given pressure. When a liquid changes into a vapour or vice versa at a constant pressure, the temperature remains constant while latent heat is added or removed. Temperature lines in this region are therefore horizontal. the super-heated region Single stage compression On leaving the condenser, the refrigerant is at point A. The liquid then passes through the expansion valve where the pressure is reduced from the condenser pressure to the evaporator pressure (A to B). No work is done during this process and thus the enthalpy remains constant. The refrigerant leaving the expansion valve consists of a mixture of saturated liquid at condition F and saturated vapour at condition C. This mixture condition is given by point B. Heat is now added to the liquid refrigerant by the evaporator, causing it to evaporate so that the refrigerant leaves the evaporator as a vapour, point C on the saturated vapour line. An ideal compression is represented by a line of constant entropy (line CE). 168 Due to inefficiencies in the compressor, further heat is added and the compression path follows line CD. Point D represents the condition of hot gas as it enters the condenser from the compressor. In order to cool the gas, cooling must first be provided to reduce its temperature to the saturation point at L. Further cooling causes the gas to condense until the final liquid state is reached at point A. Cycle Variations In order to improve efficiencies and performance, several modifications to the vapour compression cycle can be made. These include using economisers with multi-stage compressors and sub-cooling the refrigerant when it leaves the condenser. 1. Sub-cooling Sub-cooling of the liquid refrigerant from the condenser may be obtained from an external cooling medium such as air, water or some other fluid at a temperature below that of the liquid refrigerant. When sub-cooling occurs, the amount of flash gas produced after the expansion valve is reduced. Thus less refrigerant has to be circulated for a fixed cooling duty. The nett benefit of sub-cooling is to increase the refrigeration effect without affecting the work of compression. This benefit is usually small. 2. Economisers The properties of some refrigerants are such that in large cooling plants, several stages of compression are necessary to cover the pressure change from the evaporator to the condenser. When two or more stages of compression are used, the gas can be cooled after each stage by the addition of flash gas from the corresponding expansion valve. The same number of expansion valves and stages of compression are required. Flash gas from the first expansion valve after the condenser is separated from the remaining liquid refrigerant in the economiser and is piped back to enter the compressor between the first and second stages. This arrangement enables the hot gas from the first stage of compression to be cooled by the flash gas. The liquid refrigerant in the economiser is circulated to the evaporator in the usual manner. The result of this process is an increased refrigeration effect. 169 A liquid boils at constant temperature, provided the pressure remains the same. The heat added to the liquid is utilised in increasing the internal energy of the molecules until they no longer can remain in their liquid state, thus the molecules burst free to form a vapour or a gas. If the pressure is raised, additional heat is required to vaporize the fluid. Therefore, the boiling temperature will increase. 170 - Do example 1 on page 616 (EESAM) - Performance of a refrigeration cycle COP definition The coefficient of Performance of a cooling plant is defined as the ratio of the cooling duty to the input power, i.e. the ratio of what is got out to what is put in. Steady flow energy equation. Compressor: W 12 = H2 – H1 (J/kg) Condenser: q23 = H3 – H2 (J/kg) Exp. Valve: O = H4 – H3 (J/kg) Evaporator: q41 = H1 – H4 (J/kg) And: W 12 + q23 + q41 = 0 W 12 = mechanical energy added to compressor. q23 = Heat exchange in condenser q41 = Heat added to refrigerant H = Enthalpy. Thus: W 12 + q41 = -q23 Properties of refrigerants Page 622 (EESAM) Ideal refrigerant: a) b) c) d) e) f) g) h) Cheap Not affect the compressor lubricant Non-corrosive Non-toxic Non-flammable Non-explosive Leakages easily detectable Must have a high latent heat of evaporation so that flow rates can be kept as low as possible 171 The vapour compression cycle (McPhersons, 1993) The following is a brief description of the components of a refrigeration plant: 1) Compressor The compressor is the device where mechanical work is input to the system Types of compressors: a) Reciprocating b) Screw and c) Centrifugal types. 2) Evaporator The evaporator is a heat exchanger. It is typically of the shell-and-tube type. In large units, the refrigerant liquid is on the outside of the tubes while the medium to be cooled, i.e. water, passes through the tubes. Within the evaporator, the pressure remains relatively low, therefore the boiling point of the refrigerant is low, i.e. R12 boils at 4C at a pressure of 351 kPa. The heat required to maintain the boiling point is extracted from the liquid passing on the other side of the tube walls. Therefore, the liquid is cooled. The refrigerant is now vaporised and passes on to the compressor. 3) Condenser The refrigerant vapour comes from the compressor at a relatively high pressure and temperature. The condenser could be of a similar heat exchanger type used for the evaporator, i.e. shell-and-tube type, Heat is now removed from the refrigerant by water or air and the refrigerant cools and condenses back to a liquid state. The pressure is high therefore the condensing temperature is relatively high, i.e. R12 at a pressure of 1217 kPa condenses at 50C. 172 4) Expansion valve The fourth component, the expansion valve, duty is to reduce the pressure of the refrigerant back to the evaporator condition. At the exit from the expansion valve, the refrigerant is at a low pressure and corresponding low boiling point and the cycle repeats. Measure of plant performance COP = useful cooling effect (evaporator heat transfer) work input from compressor = q41 W 12 Thus: q41 q23q41 COP = . The area under the ideal Ts diagram represents heat. Thus q41 = area 41 ab -q23 = area 23 ba -q23 - q41 = area 1234 Now: W 12 = area 1234 And Cannot COP = area 41ab area 1234 = T1 Sa - Sb Sa - Sb = T1 or T 2-T1 T4 T3 T4 Example: Evaporator Temp = 4C Condenser Temp = 50C What is the maximum possible co-efficient of performance of this unit? COP = 273,15 +4 50 - 4 = 6,025 173 Actual COP COP actual is lower than ideal COP. REASON: a) In actual compressors and expansion valves there is an increase in entropy. b) As refrigerant passes through a condenser and evaporator there is a slight change in pressure and temperature. c) Point 1 on the diagram lies between the two phase region (liquid and vapour). The pressure of liquid droplets would cause some erosion of the compressor impeller. A few degrees of super hear are imparted to the vapour before it leaves the evaporator. COP = q41 W12 = H1 - H4 H2 - H1 Cycle efficiency = actual COP Carnot COP Example Water flow rate: 50 l /s Water inlet temp: 20C Water outlet temp: 10C Evaporator Refrigerant Pressure: 363 kPa refr. inlet Temp: 7 C refr. inlet Temp: 65 C Compressor (A) Refer to Pressure-Enthalpy diagram (R12) Analyse the performance characteristic of the unit. t evap = t4 = 5 C can be measured t cond = t 3 = 45 C B) Temperature of refrigerant entering compressor = 7C. Thus 7-5 = 2C of superheat Point 1 = 7C Point 2 = 65C Etc. Thus: Compressor. Inlet Compressor. Outlet and inlet Condenser. Outlet Evaporator. Inlet H1 = 356 kJ/kg H2 = 386 kJ/kg H3 = 244 kJ/kg H4 = 244 kJ/kg 174 (C) Carnot COP = T4 t3 – t4 = 273,15 + 5 45 - 5 = 6,954 = H1 - H4 H2 H1 = 356 – 244 386 – 356 Actual COP = 3,733 3,733 x 100 6,954 = 53,7% Cycle eff: = (D) Useful cooling effect (or evap. Duty, qevap) qevap = Mw,evap Cw Tw,evap (kW) (kW) = 50 x 4,187 x (20-10) = 2093,5 kW or (E) qevap = MR (H1 – H4) MR = 2093,5 356 - 244 = 18,69 kg/s (G) Condenser duty: -qcond = qevap + W 12 = 2093,5 + 560,7 = 2654,2 Kw -qcond = Mw,cond Cw Tw,cond 175 Tw,cond = 2654,2 140x4,187 = 4,53 C The overall co-efficient of performance is: Overall COP = heat transfer in evap Total energy consumption of refr unit Some pictures indicating refrigeration plants on surface and underground Underground plant (3,5 MW capacity)(E.E.S.A.M) Surface refrigeration plant installation (38 MW capacity) 176 Surface plant machine room Diagrammatic illustration of the full refrigeration cycle 177 9. Cooling Plant (Further calculations) The following measurements were obtained from a plant with a single-stage compressor. The refrigerant used is Refrigerant 12. Evaporating pressure: Condensing pressure: Compressor inlet temperature: Compressor outlet temperature: 363 kPa (abs) 225 kPa (abs) 7C 65C Flow rate: 140 l/s The following measurements were obtained from a plant with a single-stage compressor. The refrigerant used is Refrigerant 11. plant room barometric pressure: 100 kPa evaporating pressure: =54 kPa vacuum = 46 kPa (abs) condensing pressure: =125 kPa gauge = 225 kPa (abs) compressor inlet temperature: compressor outlet temperature: =3.4C =70C The evaporator duty is calculated from measurements made in the chilled water circuit and is 1 600 Kw Calculation of performance and duty: All enthalpy, temperature and specific volume can be read directly from the chart. Refrigeration effect: = HC – H B = 224.5 - 76 = 148.5 kJ/kg 178 Heat exchange at condenser: = HD - H A = 260.5 - 76 = 184.5 kJ/kg Work of compression: = HD - H C = 260.5 - 224.5 = 36.0 kJ/kg Ideal work of compression: = HE - H C = 253.0 - 224.5 = 28.5 kJ/kg Compressor efficiency: = HE - HC x 100 HD - HC = 28.5 x 100 36.0 = 79.2% Percentage flash gas: = HB - HF x 100 HC - HF = 39 x 100 187.5 = 21% Coefficients of performance (COP) Carnot C.O.P. = T1 . T2 - T1 = 273.15 + 3.20 48.0 - 3.20 = 6.2 The Carnot COP is the ratio of cooling duty to the input power (the ratio of what has gone out to what is put in) as mentioned before. The Carnot cycle is one in which heat is absorbed and rejected at constant temperature, and where both compression and expansion processes occur adiabatically. This cycle is the most efficient possible, hence the maximum possible COP is the Carnot COP. 179 Actual C.O.P. = refrigeration effect work of compression = 148.5 36.0 = 4.1 Actual COP is always less than Carnot COP Cycle efficiency = Actual C.O.P. x 100 Carnot C.O.P. = 4.1 x 100 6.2 = 66% Power/cooling ratio = work of compression refrigeration effect = 36.0 148.5 = 0.24 Refrigerant mass flow through evaporator = Mr = evaporator duty refrigeration effect = 1 600 148.5 = 10.8 kg/s Inlet volume flow rate = Mr x vc = 10.8 x 0.36 3 = 3.89 m /s Power consumed by compressor = Mr (HD - HC) = 10.8 x 36.0 = 389 kW 180 10. Cooling Plant DUTY From the first law of thermodynamics, the energy change of the water must equal the energy change of the air, due allowance being made for evaporation. The energy balance is approximated by: q = Mw.Cpw.tw = Ma.Sa In this equation only partial allowance is made for evaporation and a small additive term is omitted from the right hand side. The magnitude of this correction is 3 to 4% and its omission is generally justified. Assume that a heat ‘imbalance’ of greater than 10% is unacceptable, requiring instruments to be checked and readings to be re-taken. WATER EFFICIENCY From the second law of thermodynamics, the water cannot leave the tower at a temperature lower than that of the entering air wet-bulb temperature. The wet-bulb temperature of the air leaving the tower cannot exceed the temperature at which the water enters the tower. two > twbi twbo < twi W = (twi - two)/(twi - twbi) i.e.: (actual) / theoretical max. THERMAL CAPACITY FACTOR (R) This is the ratio of the thermal capacity of the water stream to that of the air stream. R = (Mw.Cpw)/(Ma.C’a) 181 For a particular installation, the water efficiency depends on the flow rates and temperature conditions that are imposed on the installation. R is the parameter used to measure these conditions. C’a is the EQUIVALENT SPECIFIC HEAT OF HUMID AIR for a process in which the moisture content of the air varies. It is evaluated from the wet-bulb temperature and the sigma heats associated with the inlet air and inlet water conditions. C’a = (Swi - Sai)/( twi - tai) (Specific heat of water = specific heat of air at that temperature) FACTOR OF MERIT This is a means of quantifying the basic performance characteristics of a heat exchanger. The factor of merit is the value of the water efficiency when R = 1 The factor of merit is determined using figure 23.13 (EESAM p 635) if R (thermal capacity ratio) and the water efficiency are known. The factor of merit is dependent upon the design of the installation. It is fairly independent of water and air temperatures, the barometric pressure and (within reason) of water and airflow rates. Once the F-value of a cooling tower is known it is possible to reliably predict the performance of the tower under a wide range of operating conditions. 11. Cooling plant tutorial 1. Typical cooling tower problem (p 636, Q 1 & 2, EESAM) Barometric pressure: 112.5 kPa AIR CIRCUIT Quantity: Temperature inlet: outlet: 3 213 m /s 30/34 C 40.9/40.9 C 182 WATER CIRCUIT Flow rate: Temperature entering: leaving: 1. 536 l/s 43.4 36.1 Calculate the following performance characteristics of the tower: a) b) c) d) duty water efficiency thermal capacity ratio factor of merit 2. Predict the entering and leaving temperatures for the above tower when, as a result of the installation of two new refrigeration machines, the amount of heat to be rejected increases to 23 259 kW. Assume that the factor of merit (F), the air and water quantities and the inlet air temperature remain as given and calculated above. 11. Cooling towers, coils and calculations Q = Mw x Cpw x Tw (Water) Or Q = Ma x Sa (Air) If condensation occurs on the outside of the coils, m aS would give slightly incorrect answers as it does not take into account the heat removed from the system by the condensate (latent heat). A “rule of thumb” to be remembered is: If both calculations were done and the results differ by more than say 7%, use the “water side” calculation. What could be a prominent practical reason for deviation of the two calculated results? 183 Single heat exchanger (coil type) Another way of expressing heat transfer is the overall heat transfer coefficient U. q = UA (tma - tmw) (W) UA product is a measure of the effectiveness of an indirect heat exchanger. UA of a clean coil is between 10 – 25 KW/C. What does a decline in UA mean? 184 Direct heat exchanger: Cooling tower In a cooling tower, how does the heat transfer take place? Heat is transferred from the water to the air (cooling tower) by two methods (a) Convection (sensible heat), and (b) Evaporation (latent heat) Air to water (warm air @ cold/chilled water). Several common factors that influence the amount and efficiency of direct contact heat exchangers. (a) H2O flowrate. (b) H2O supply temp. (c) H2O mass flowrate. (d) Air condition at inlet 185 (e) Duration of contact (air to water) factor of the design. Between air and water Size and concentration of the droplets. Water and air efficiency: (EESAM, p. 634) For a perfect heat transfer in a cooling tower: Maximum thermal capacity of water = m w Cw (tw,in – tg,in) (J) Max thermal capacity of air stream = Ma (Sw.in – Sin) (J) Tower capacity factor (R) Factor of merit. Factor of merit is a measure of the basic performance of a unit (same as UA). (See EESAM, figure 23.13 p. 635). 186 Do EESAM, Example 5 page 636: INDIRECT HEAT EXCHANGE 187 EESAM, Chapter 19 (p. 465) (1) Heat Transfer (a) Conduction q = k A (t1 – t2)/b Heat flux rate = thermal cond x area x temp diff thickness Why does an insulation product / material have to attain a certain thermal conductive value? ( not > 0.05 WmK) The ability of a material to conduct heat. (2) Radiation q = hR A (t1 – t2) Fev Radioactive heat transfer (3) Convection (a) Boundary layer (Dominating effect of hear transfer) The faster the air velocity, the thinner the layer, the more heat is transferred. qc = hc A(t1 – t2) Graphs predicting hc (p 477) Overall heat transfer coefficient (U) r = A2 A3 A4 Kins Kpipe h2 L h4 = = = = = = = = hR = radius 2r2L 2r3L 2r4L Thermal conductivity of insulation material Thermal conductivity of pipe material connective heat transfer coefficient between fluid and inside pipe surface Length of pipe connective heat transfer coefficient between ambient air and the outside surface of the insulation. radiative heat transfer coefficient 0.95 (Constant) 188 A2 A3 2 A34 = A 3 A 4 2 A23 = Determine heat transfer coefficients from charts (pages 477 to 479) (a) hr (page 473) (b) h2 (c) h4 D4 = Inside pipe diameter + 2 (Pipe wall thickness) + Insulation material thickness Now the heat gain by fluid per length is: q = UA.(tdb - tw).L W/length q (heat flow) is now determined as UA, tdb and tw are known parameters. And q = Mf x Cf x t M = Qf x f kg/s t = q = Mf Cf q QF.p. f. C f . or 189 Insulated pipe section with indicating parameters Heat transfer at wet surfaces Do example 10 page 486 (1) Condensation takes place (i.e. latent heat transfer) So q = qc + qr + qL Latent heat of condensation: = 2501 - 2,3830 T 190 When do you think will condensation take place? Up to page 489: Pipe Sizing For a 2 m/s flow-rate For new pipes f = 0.0039, however because of the ageing process this factor could increase between 20 to 50%. UPVC (plastic type) f = 0.0032. For bends and pipe fittings the frictional pressure loss could be increased by 10% to allow for these additional pressure loss that would occur. Energy and temperature changes within water systems and Therefore H = Cw t H = g.Z (p 399.) (p 403 etc). t = gZ Cw or roughly pressure drop: P = w.g.Z = Frictional pressure drop 191 Auto-compression Page 403 (Know this relationship) Similar to page 407 for water systems 12. MINE COOLING SYSTEMS (Review) Three sets of heat transfers involved (a) Transfer of heat from work areas to evaporators of Refr, units. (b) Transfer of heat from evaporator to condensers in Refr, unit. (c) Transfer of heat from cond, to free atmosphere (Surface). Heat Exchanger A device that promotes the transfer of thermal energy from one solid or fluid system to another - Indirect heat exchangers - Direct heat exchangers Indirect heat exchanged across a solid medium that separates two fluids. Direct Direct contact between the two fluids. PERFORMANCE CALCULATIONS FOR INDIRECT HEAT EXCHANGERS (Review) Equilibrium heat gained by one fluid = heat lost by other fluid. Thus: rate of heat transfer Another way of expressing heat transfer is - Overall heat transfer co-efficient, U(W/m2 C) And difference between mean temp, of air and water. Temp of air and water avarg. in a logarithmic manner rather than a linear fashion, the more accurate formula is: UA is a measure of the effectiveness of an heat exchanger (similar to the pipe heat exchanged formula indicated previously). 192 2 h = heat transfer co-efficient (W/m C) x = thickness of tube walls Kt = thermal cond of tube material (W/mC) i = insider tube surface o = outside tube surface m = mean of inner to outer surface hfi & hFo = heat transfer co-efficient associated with fouling New tubes hFi & fFo = infinite 13. DIRECT HEAT EXCHANGERS Cooling Tower Range = tw,in – tw,out (C) Approach = tw,out – ta,in (2C is acceptable) Balance equation Ma (Sout - Sin) = Mw Cw (tw,in – tw,out) (W) The Perfect Tower - Water would leave at inlet air wet bulb temp - Air would leave at the incoming water temp tw.out = ta,in and 193 ta,out = tw,in Water efficiency w = actual heat loss from water theoretical max heat loss from water Similarly the air efficiency: DO Examples: Heat exchange across walls of pipes and ducts Pipe Sizing, Insulation etc. 1) Direct & Indirect heat exchange systems Definition of each 2) a) Why do we cool deep underground mines? To reduce the heat load in the mine b) Where do these heat load come from? 194 a) Rock (Primary source) b) Machinery (fans, diesel, sub-station, hoists, etc.) 195 Diesel machinery could induce heat to the surroundings by as much as 2 to 2.5 times its rated output power c) Fissure Water (Major contributor) d) Explosions 196 e) Men c) How do we now reduce the heat load? (Direct & Indirect types). 197 3) Direct heat exchangers (Cooling Towers & spray chambers type) Indirect heat exchangers (coils etc.) Performance calculations (a) Equilibrium: heat gain by one fluid = heat loss by the other fluid. Thus: So, either the water or the air circuit could easily be measured and used for the calculation. The water measurements are normally more accurate and the tendency therefore Typical Spray Chamber problem Barometric pressure: 115 kPa AIR CIRCUIT Quantity: temperature 3 inlet: outlet: 24.7 m /s 33.1/34.7 C 22.1/22.1 C WATER CIRCUIT Flow rate Temperature entering: leaving: 35.3 l/s 18.8 C 28.6 C 1. Calculate the following performance characteristics of the spray chamber: a) Duty b) Water efficiency c) Thermal capacity factor d) Factor of merit 198 Project: Refrigeration 1. Handing in date : 31 October 2001 2. Project to be done in readable own handwriting and not typed. 3. All calculations to be shown clearly. (hand-written) 4. Assumptions, if any, to be clearly indicated as such. Project Objective a) To understand a Refrigeration plant operation b) To understand the reticulation system Components etc. c) To demonstrate the students ability in performing some basic calculations involved in a refrigeration and reticulation system design. Project The following plant and chilled water distribution system is given. Plant information Compressor: Refrigerant inlet temperature: 6 C Refrigerant outlet temperature: 58 C Condenser: Water flow rate : 110/s Refrigerant Pressure: 1150Kpa Evaporation: Water inlet Temperature: 23.8 C Water outlet Temperature : 6,5 C Refrigerant Pressure : 380 kPa Water Flow-rate: 55 /s Use the chart supplied and analyse the unit Performance (show all calculations) The following information is provided for the mine distribution system 1) Pump efficiency =78%, Energy recovery unit efficiency =75% 2) Surface BAC (Direct contact system) This is the only direct contact energy exchange system in the system. (a) Duty =18MW 3) Pre- Cooling Tower (PCT) outlet water Temperature =21 ℃ with a factor of merit of 0,45 4) Surface BAC (Bulk air cooler) distance to return water dam 1 = 320 m 5) Surface BAC water flow = 395 l/s with a factor of merit of 0,5 6) Coils efficiency = 65% 7) PRV operating head = 210 m 8) Plant leaving water flow and temperature = 710 l/s at 4.5oC. 9) Shaft bottom BAC uses 90 l/s. 199 Determine: 1. 2. 3. 4. 5. 6. The temperature in each of the dams (1 – 5) All pipe sizes (The mean water velocity in each pipe is 2 m/s) The PCT Duty (MW) The overall plant capacity (MW) The return water flow rate to the PCT with the temperature The water temperature to the plant. Using the first horizontal intake level to the workings. what influence could full pipe insulation have on the coil arriving water temperature ? Indicate on your calculation sheet and on the flow sheet provided the temperatures as the water flows down and up the reticulation system. All reasonable assumption to be stated clearly. Where data is not given and is required in the calculation procedure, assumption must be made. Total project marks = 25 points. 200 201 202 203 204 205 206 207 208 209 210 211 212