OPERATIONAL PROCEDURE O. P. NO. RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK RFST WATCH AREA FUEL OIL LOCAL CONTROL PANEL (FOLP) NOTES: 1. Observe all standard notes for the Oil King (SN. NO. SNOK). USER NOTES NOTE: Numbers refer to valves as numbered on diagrams DFOT and DOWT. I. VERIFY SYSTEM ALIGNMENT A. Verify fuel and oily waste drain tank levels, monitor fuel oil and oily waste tank liquid level indicators. Indicate liquid level in storage and service tanks on SD NO. TSDF. B. Ensure the following valves are shut: CPO BERTHING FT-V-131 1. Refueling main low point drain. 2. Refueling main stop to port forecastle. FT-V-2 3. Defueling discharge (locked). No. 1 AMR FT-V-85 4. Refueling main fill. FT-V-51 5. Receiving tank transfer valve. No. 1 AMR 4-78-1-F No. 1 AMR 4-78-2-F FT-V-87A FT-V-87B 6. Receiving tanks fill valve "CLOSE" indicator is illuminated and it’s actuator is aligned in the “AUTO” mode. CODE RFST/1796/020112 PAGE 1 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK No. 1 AMR 4-78-1-F No. 1 AMR 4-78-2-F FT-V-60 FT-V-62 7. Defueling discharge (locked). A/C Mach Pmp Rm FT-V-91 8. Refueling main fill. FT-V-17 9. Receiving tank transfer valve. A/C Mach Pmp Rm 5-308-1-F A/C Mach Pmp Rm 5-308-2-F FT-V-97A FT-V-97B 10. Receiving tanks fill valve "CLOSE" indicator is illuminated and it’s actuator is aligned in the “AUTO” mode. A/C Mach Pmp Rm 5-308-1-F A/C Mach Pmp Rm 5-308-2-F FT-V-122A FT-V-122B 11. Service tanks fill. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-116A FT-V-116B FT-V-76A FT-V-76B 12. Service tanks stripping suction cutout. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-123A FT-V-123B FT-V-126A FT-V-126B 13. Service tank stripping suction line stop (locked). 14. Transfer header bulkhead stops. CODE RFST/1796/020112 No. 1 ER FT-V-125 No. 2 ER FT-V-128 FT-V-52 FT-V-53 FT-V-54 FT-V-132 PAGE 2 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK No. 1 ER 1-FT-V-82 No. 2 ER 2-FT-V-82 16. Recirculation main cross-connect(s). FT-V-83 FT-V-88 FT-V-89 17. Transfer pump suction. 1-FT-V-66 2-FT-V-66 18. Purifier discharge cross-connect. FT-V-74 FT-V-75 19. Transfer pump discharge sample connection. 1-FT-V-79 2-FT-V-79 20. Transfer heater vent (locked). 1-FT-V-100 2-FT-V-100 21. Transfer pump suction from fill main. 1-FT-V-65 2-FT-V-65 22. Transfer heater bypass. 1-FT-V-98 2-FT-V-98 23. Transfer heater drain. 1-FT-V-101 2-FT-V-101 24. Purifier discharge sample/drain. 1-FT-V-115 2-FT-V-115 25. Fuel oil strainer vent and drain. 1-FT-V-110 1-FT-V-111 2-FT-V-110 2-FT-V-111 26. Heater water removal drain. 1-FT-V-102 2-FT-V-102 27. Heater water removal bypass strainer inlet, outlet and drain. 1-FT-V-103 1-FT-V-104 1-FT-V-105 2-FT-V-103 2-FT-V-104 2-FT-V-105 28. Diverting valve discharge to transfer pump suction. 1-FT-V-112 2-FT-V-112 15. Transfer pump discharge to recirculation main (locked). CODE RFST/1796/020112 PAGE 3 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK 29. Purifier inlet. No. 1 ER 1-FT-V-70 No. 2 ER 2-FT-V-70 30. Purifier outlet. 1-FT-V-73 2-FT-V-73 31. Emergency fuel supply from JP-5 system (locked). FT-V-77 32. Receiving tank transfer valve. No. 1 ER 4-174-1-F No. 1 ER 5-220-4-F FT-V-93 FT-V-95 33. Receiving tanks fill valve ”CLOSE“ indicator is illuminated and it’s actuator is aligned in the ”AUTO“ mode. No. 1 ER 4-174-1-F No. 1 ER 5-220-4-F FT-V-64 FT-V-119 II. ALIGN FUEL OIL TRANSFER SYSTEM A. Indicate designated service tank to be recirculated. CAUTION: FUEL OIL SHOULD NOT BE RECIRCULATED IN A SERVICE TANK WHILE FUEL OIL IS BEING DRAWN FROM THAT TANK. WHEN A SERVICE TANK ON SUCTION REQUIRES RECIRCULATING, SHIFT SUCTION TO FULL STANDBY SERVICE TANK. B. Open the designated service tank valve: 1. Service tanks stripping suction cutouts. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-123A FT-V-123B FT-V-126A FT-V-126B NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-116A FT-V-116B FT-V-76A FT-V-76B 2. Fill. CODE RFST/1796/020112 PAGE 4 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK No. 1 ER FT-V-125 No. 2 ER FT-V-128 C. When aligning No. 1 transfer system to recirculate an aft service tank, open transfer pumps suction from transfer main, transfer header bulkhead stop and aft service tank stripping suction. 1-FT-V-65 FT-V-53 2-FT-V-65 FT-V-132 D. When aligning No. 2 transfer system to recirculate a forward service tank, open transfer pumps suction from transfer main, transfer header bulkhead stop and forward service tank stripping suction. FT-V-53 1-FT-V-65 2-FT-V-65 FT-V-132 E. When aligning No. 1 transfer system for recirculating an aft service tank or No. 2 transfer system for recirculating to forward, open transfer purifiers discharge cross-connect valve. FT-V-74 FT-V-75 3. Unlock and open service tank stripping suction line stop. III. ALIGN PURIFIER OPERATING WATER TANK A. Ensure the following valves are shut: 1. Tank drain to bilge. CPW-V-384 CPW-V-508 2. Tank gauge glass drain. CPW-GG-3 CPW-GG-12 3. Bypass valve for freshwater fill. CPW-V-379 CPW-V-503 B. Open the following valves: CODE RFST/1796/020112 PAGE 5 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK No. 1 ER CPW-V-377 No. 2 ER CPW-V-501 2. Tank freshwater outlet. CPW-V-380 CPW-V-504 3. Purifier liquid seal supply. CPW-V-381 CPW-V-505 4. Purifier operating water supply. CPW-V-385 CPW-V-509 1. Tank freshwater inlet. C. Ensure the following valves are open: 1. Tank gauge glass cutouts. CPW-GG-1 CPW-GG-2 CPW-GG-10 CPW-GG-11 2. Control air to water supply valve. ALP-V-415 ALP-V-442 3. Control air to diverting valve from heater to purifier. ALP-V-422 ALP-V-443 4. Control air to diverting valve pressure gauge cutout. CA-V-21 CA-GA-1TI CA-V-22 CA-GA-2TI D. Ensure tank water level is between minimum and maximum levels. IV. PLACE TRANSFER SYSTEM IN OPERATION NOTE: Purifier must be aligned and primed at the unit prior to placing it in operation. NOTE: Water should discharge from the water discharge sight port to indicate that priming was successful in producing a water seal. A. Start and prime designated fuel oil purifier. 1. Ensure lube oil reservoir level is at operating range. CODE RFST/1796/020112 PAGE 6 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK CAUTION: DO NOT OVER TIGHTEN T HANDLE-HAND TIGHT ONLY. 2. Ensure the feed tube is secured in the paring disc (left hand thread). 3. Ensure bowl brake is released. 4. Ensure cover clamps are secured. 5. Check oily water drain tank level; ensure sufficient tank capacity to receive drains. 6. Ensure the following valves are open: No. 1 Purifier 1-FT-V-108 1-FT-GA-12HI 1-FT-V-109 1-FT-GA-12LO No. 2 Purifier 2-FT-V-108 2-FT-GA-12HI 2-FT-V-109 2-FT-GA-12LO b. Inlet pressure gauge cutouts. 1-FT-V-113 1-FT-GA-13TI 2-FT-V-113 2-FT-GA-13TI c. Outlet pressure gauge cutouts. 1-FT-V-114 1-FT-GA-14TI 2-FT-V-114 2-FT-GA-14TI 7. Open purifier outlet valve. 1-FT-V-73 2-FT-V-73 8. Ensure purifier drain valves to oily waste water drain tank are open (locked). OW-V-9 OW-V-11 OW-V-20 OW-V-84 OW-V-86 OW-V-62 No. 1 ER (5-174-2-F) OW-V-211 No. 2 ER (5-296-1-F) OW-V-214 a. Inlet strainer differential pressure gauge cutouts. 9. Ensure oily waste drain tank inlet is open. CODE RFST/1796/020112 PAGE 7 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK 10. Ensure water removal bypass valve is open one turn. No. 1 Purifier 1-FT-V-68 No. 2 Purifier 2-FT-V-68 11. When fuel oil transfer heater is required, open the following valves: a. Heater outlet. 1-FT-V-69 2-FT-V-69 b. Heater inlet. 1-FT-V-67 2-FT-V-67 12. When fuel oil transfer heater is not required, open heater bypass valve. 1-FT-V-98 2-FT-V-98 NOTE: When a cold (false) start is made, allow purifier to coast, without braking, to a complete stop. NOTE: After surface of motor has cooled to an ambient temperature not exceeding 50 C (125 F), a hot (true) start can be made. NOTE: Between multiple starts, allow one-half hour running time or one hour rest time (rest time includes deceleration time plus idle time). CAUTION: MORE THAN TWO STARTS WITHIN AN HOUR MAY DAMAGE MOTOR. CAUTION: IF PURIFIER DOES NOT COME UP TO SPEED WITHIN 8 MINUTES OR HAS EXCESSIVE VIBRATION NOISE, STOP IMMEDIATELY AND INVESTIGATE. TO DETERMINE SPEED, PLACE FINGER ON ROTATING CAP OF SPEED INDICATOR. BUTTON ON CAP SHOULD ROTATE AT 149 RPM. 13. Turn CLOSE WATER selector switch to ON position. 14. Depress purifier START pushbutton. The red "PURIFIER START" indicator should illuminate. NOTE: When the "PURIFIER RUN" light illuminates, the solenoid valve controlling the bowl closing water will be energized. The bowl will close in approximately 30 seconds. The purifier bowl is now ready for priming. 15. Prime the purifier as follows: CODE RFST/1796/020112 PAGE 8 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK a. When the bowl is up to speed, turn the spring loaded SHOOT/OFF/PRIME selector switch to the PRIME position. Hold the switch over in the PRIME position, against spring pressure, until water is seen flowing past the sightglass in the heavy phase discharge chamber. Release the switch when the priming is completed. NOTE: Water should discharge from the water discharge sight port to indicate that priming was successful in producing a water seal. B. Align and start the transfer pump as follows: 1. Ensure the following valves are open: No. 1 Xfr Pmp 1-FT-V-78 1-FT-GA-9TI No. 2 Xfr Pmp 2-FT-V-78 2-FT-GA-9TI 1-FT-V-81 1-FT-GA-10TI 1-FT-V-80 1-FT-PS-1TI 2-FT-V-80 2-FT-GA-10TI 2-FT-V-81 2-FT-PS-1TI No. 1 ER 1-FT-V-71 No. 2 ER 2-FT-V-71 3. Open purifier inlet valve. 1-FT-V-70 2-FT-V-70 4. Open transfer pump suction valve. 1-FT-V-66 2-FT-V-66 5. Open diverting valve discharge to suction side of transfer pump. 1-FT-V-112 2-FT-V-112 a. Suction pressure gauge cutouts. b. Discharge pressure gauge and pressure switch cutouts. 2. Ensure fuel oil purifier inlet diverting valve handwheel is in the fully counterclockwise position. CODE RFST/1796/020112 PAGE 9 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK CAUTION: HIGH FUEL OIL TEMPERATURE RISE MAY OCCUR ACROSS FUEL OIL TRANSFER PUMPS HANDLING NAVY DISTILLATE DURING PUMP STARTING PROCEDURE. CAUTION: PUMP MUST NOT BE OPERATED WITHOUT SUCTION. CAUTION: WHEN PUMP CANNOT BE PLACED ON THE TRANSFER LINE WITHIN 3 MINUTES AFTER INITIAL ROTATION DURING STARTING PROCEDURE, PUMP MUST BE STOPPED. 6. Start designated transfer pump as follows. a. Depress XFR PUMP START pushbutton. b. Verify XFR PUMP "PUMP RUNNING" indicator illuminates. c. Verify XFR PUMP discharge pressure is greater than 20 PSIG. C. Open fuel heater telltale drain cutout valve and check drain for presence of fuel. When no fuel is observed, shut telltale drain valve. No. 1 ER 1-FT-V-132 No. 2 ER 2-FT-V-132 CAUTION: FUEL OIL MUST BE FLOWING THROUGH HEATER BEFORE ENERGIZING. CAUTION: WHEN TRANSFERRING JP-5 FUEL, BE SURE TRANSFER HEATERS ARE BYPASSED. JP-5 FUEL DOES NOT REQUIRE HEATING. WARNING: THE TEMPERATURE OF FUEL OIL SHALL NEVER BE RAISED TO OR ABOVE ITS FLASH POINT (MINIMUM OF 140 F). D. Place designated heater in operation by depressing the heater ON pushbutton, verify "HEATER ON" indicator illuminates. CAUTION: IF PURIFIER SEAL IS LOST, SHUT PURIFIER INLET VALVE AND RE-PRIME PURIFIER. E. Place purifier in operation as follows: 1. Turn FUEL FORWARD switch to the START position until the green "FUEL FORWARD" indicator illuminates. CODE RFST/1796/020112 PAGE 10 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK 2. Verify "NO EFFLUENT" indicator is extinguished. Release FUEL FORWARD switch. 3. Ensure positive control air pressure to diverting valve. NOTE: Ensure purifier is discharging fuel oil at sufficient back pressure to prevent fuel oil from foaming, but not so great as to cause loss of fuel oil at waste water drain. 4. Adjust purifier outlet valve to obtain 25-30 PSIG purifier discharge pressure. 5. Adjust purifier inlet pressure by adjusting purifier inlet valve to obtain approximately 5-25 PSIG. No. 1 Purifier 1-FT-V-73 No. 2 Purifier 2-FT-V-73 1-FT-V-70 2-FT-V-70 F. Report to EOOW/PACC operator, "Commenced recirculating fuel oil in No. ___ service tank, using No. ___ fuel oil purifier." G. Align and place water removal bypass in operation as follows: MER 1 1-FT-V-102 MER 2 2-FT-V-102 2. Open strainer inlet and outlet valves. 1-FT-V-103 1-FT-V-104 2-FT-V-103 2-FT-V-104 3. Ensure orifice differential pressure gauge cutout valves are open. 1-FT-V-106 1-FT-V-107 1-FT-GA-11HI 1-FT-GA-11LO 2-FT-V-106 2-FT-V-107 2-FT-GA-11HI 2-FT-GA-11LO 1. Open heater water removal drain valve and allow water to drain, shut when fuel appears. CODE RFST/1796/020112 PAGE 11 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK 4. Open heater outlet 3-way valve to achieve 3 PSID across orifice. 5. Throttle strainer outlet to achieve 2 PSID across orifice. MER 1 1-FT-V-68 MER 2 2-FT-V-68 1-FT-V-104 2-FT-V-104 6. Observe purifier inlet and outlet pressure and adjust as necessary. H. Report to EOOW/PACC operator, "Water removal bypass in operation." V. OPERATING A. Ensure all operating parameters are normal. 1. Purifier operating data: a. Feed Pressure DESIGN DATA 5-25 PSIG b. Back Pressure 25-30 PSIG 2. Transfer pump operating data: a. Discharge Pressure 20-50 PSIG b. Discharge Low Pressure Alarm 20 PSIG c. Fuel oil pump strainer differential pressure Less than 5 PSID B. Five (5) minutes after recirculation initiation, then every thirty (30) minutes, sample and visually test (clear and bright) purifier discharge. C. Continue recirculating service tank until clear and bright sample is obtained. D. When designated service tank has been recirculated for required time, purifier does not require cleaning, and adjacent service tank requires filling, system alignment may be shifted from recirculation to transfer by performing Step VIII. CODE RFST/1796/020112 PAGE 12 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK E. When designated service tank has been recirculated for required time and system is to be secured, proceed to Step IX. VI. PLACING THE PURIFIER IN STANDBY NOTE: When the purifier is in standby, the purifier continues to operate at normal speed. WARNING: FAILURE TO EMPTY THE BOWL OF FUEL PRIOR TO PLACING THE PURIFIER IN STANDBY MAY CAUSE EXCESSIVE HEAT BUILDUP OF THE FUEL. A. When ordered, place the purifier in standby. 1. Turn the spring loaded FUEL FORWARD selector switch to the STOP/ALARM RESET position and release. 2. Verify the "FUEL FORWARD" indicator extinguishes. 3. Secure heater by depressing the HEATER OFF pushbutton; verify "HEATER ON" indicator extinguishes. 4. When heater inlet and outlet temperature equalize, secure transfer pump by depressing the XFR PUMP STOP pushbutton; verify XFR PUMP "PUMP RUNNING" indicator extinguishes. 5. Open purifier discharge line sample/drain valve, allowing the fuel in the purifier outlet to drain. 6. After the fuel has drained, shut purifier discharge line sample/drain valve. No. 1 Purifier 1-FT-V-115 No. 2 Purifier 2-FT-V-115 1-FT-V-115 2-FT-V-115 7. Turn the SHOOT/OFF/PRIME selector switch to the PRIME position and hold until water is seen flowing past the observation port. 8. Release the selector switch from the PRIME position and turn it to the SHOOT position and hold it there until the purifier shoots (2-3seconds). CODE RFST/1796/020112 PAGE 13 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK 9. Return the selector switch to the PRIME position until water is seen flowing past the observation port. 10. Release the SHOOT/OFF/PRIME selector switch. 11. Check after 5 minutes, and every 5 minutes there after, to insure purifier inlet and outlet housing and cover are cool to the touch (no discomfort when hand is placed on cover). 12. If the cover is not cool to the touch, repeat steps 8. and 9. (a hot cover will become cool within 10 seconds). 13. If cover continues to become hot, secure purifier. B. Report to EOOW/PACC operator, "No. in standby." ___ purifier running VII. SHOOTING THE BOWL NOTE: Periodic shooting of the bowl is required in 2 hour intervals to remove accumulated solids (sludge). A. Turn the FUEL FORWARD selector switch to STOP/ALARM RESET position and release. B. Verify "FUEL FORWARD" indicator extinguishes. C. Turn the SHOOT/OFF/PRIME switch to the PRIME position and hold until water is seen flowing past the observation port. D. Release selector switch from the PRIME position and turn it to the SHOOT position and hold it there until the purifier shoots (2-3 seconds). E. Return the selector switch to the PRIME position until water is seen flowing past the observation port. F. Release the SHOOT/OFF/PRIME selector switch. G. Resume purifying fuel by turning FUEL FORWARD selector switch to START. H. When the "FUEL FORWARD" indicator illuminates, release the FUEL FORWARD switch. I. Verify the "NO EFFLUENT" indicator is extinguished. CODE RFST/1796/020112 PAGE 14 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK VIII. SHIFT PURIFICATION FROM RECIRCULATION TO TRANSFER A. Place purifier in standby by performing step VI. B. Check the FCS equipment status on the FCS SCM workstation in control as follows: 1. Select the Acknowledge button and call up the acknowledge menu. Select the Equip screen. 2. On the FCS Equipment Status screen ensure the PLC Status section has one PLC in control with a "YES" indication and the other PLCs have a "NO" indication. 3. Ensure all status sections on the FCS Equipment show an Ok indication. 4. Return to the HOME page screen by selecting the HOME button. C. Activate the Fuel Control System for transfer of fuel oil as follows: 1. Select Compensating Tank Groups from the TRANSFER menu on the HOME page screen. 2. Ensure Fill valves for the tank groups are in MANUAL. 3. Ensure no flow arrows are indicated on the Compensating Tank Groups-Tranfer screen. 4. Select the TRANSFER button for the designated storage tank and verify "OUTWARD FLOW" arrow appears. 5. Select the RECEIVE button for the designated service tank and verify "INWARD FLOW" arrow appears. 6. Select the START button for TRANSFER. 7. Select OK on the Verify popup window to Start Transfer. 8. Select the OPEN button for the storage tank fill valve and verify the designated storage tank fill valve icon transitions from close to open. CODE RFST/1796/020112 PAGE 15 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK D. Indicate designated receiving tank(s) to be transferred from and service tank(s) to be transferred to on SD NO. TSDF. E. Ensure designated receiving tank in port flow limiting valve is open. NO. 1 AMR 4-78-1-F NO. 1 AMR 4-78-2-F NO. 1 ER 4-174-1-F NO. 1 ER 5-220-4-F FT-V-59 FT-V-61 FT-V-63 FT-V-118 A/C Mach Pmp Rm 5-308-1-F A/C Mach Pmp Rm 5-308-2-F FT-V-121A FT-V-121B F. When aligning transfer system, open transfer pump suction from fill main. No. 1 ER 1-FT-V-65 No. 2 ER 2-FT-V-65 G. When aligning transfer system to transfer from forward tanks, open fill main bulkhead stop. FT-V-52 H. When aligning transfer system to transfer from aft tank, open fill main bulkhead stop. FT-V-53 FT-V-54 FT-V-132 I. When aligning No. 1 transfer system for transferring to aft service tanks or No. 2 transfer system for transferring to forward, open transfer purifier discharge cross-connect valve. FT-V-74 FT-V-75 J. When aligning No. 1 transfer system for transfer to aft service tanks or No. 2 transfer system to transfer to forward service tanks open fill main bulkhead stop. FT-V-53 FT-V-132 CODE RFST/1796/020112 PAGE 16 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK K. Shut fill valve of service tank being recirculated. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-116A FT-V-116B FT-V-76A FT-V-76B L. Shut stripping suction cutout valve for service tank being recirculated. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-123A FT-V-123B FT-V-126A FT-V-126B M. Shut and lock service tank stripping suction line stop valve. No. 1 ER FT-V-125 No. 2 ER FT-V-128 N. Report to EOOW/PACC operator, "Secured recirculating No. ___ service tank; request EOOW/PACC operator shift No. ___ engineroom fuel oil service suction to TK A/B." O. Ensure all operating parameters are normal. CAUTION: FUEL OIL SHOULD NOT BE TRANSFERRED TO A SERVICE TANK WHILE FUEL OIL IS BEING DRAWN FROM THAT TANK. WHEN A SERVICE TANK ON SUCTION REQUIRES FILLING, SHIFT SUCTION TO FULL STANDBY SERVICE TANK. P. When designated engineroom fuel oil service suction reported shifted, open No. ___ service tank fill valve. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-116A FT-V-116B FT-V-76A FT-V-76B Q. Start designated transfer pump as follows: 1. Depress XFR PUMP START pushbutton. 2. Verify XFR PUMP "PUMP RUNNING" indicator illuminates. 3. Verify XFR PUMP discharge pressure is greater than 20 PSIG. CAUTION: FUEL OIL MUST BE FLOWING THROUGH HEATER BEFORE ENERGIZING. CODE RFST/1796/020112 PAGE 17 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK CAUTION: WHEN TRANSFERRING JP-5 FUEL, BE SURE TRANSFER HEATERS ARE BYPASSED. JP-5 FUEL DOES NOT REQUIRE HEATING. WARNING: THE TEMPERATURE OF FUEL OIL SHALL NEVER BE RAISED TO OR ABOVE ITS FLASH POINT (MINIMUM OF 140 F). R. Place heater in operation by depressing the HEATER ON pushbutton; verify "HEATER ON" indicator illuminates. S. Resume purifying fuel by turning FUEL FORWARD selector switch to the FUEL FORWARD position. T. When the "FUEL FORWARD" indicator illuminates, release the FUEL FORWARD switch. U. Verify the "NO EFFLUENT" indicator is extinguished. V. Report to EOOW/PACC operator, "Commenced transferring fuel oil from No. ___ fuel oil storage tank to No. ___ fuel oil service tank." W. Ensure all operating parameters are normal. X. Five (5) minutes after transfer initiation, then every thirty (30) minutes, sample and visually test (clear and bright) purifier discharge. Y. Monitor liquid level indicators; when designated service tank(s) is at 80% in-port (95% at-sea), and designated service tank is to be recirculated immediately after transfer, system alignment may be shifted from transfer to recirculation by performing OP NO. SFSS, Step VIII. IX. SECURE RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK NOTE: In order to properly secure the purifier after a purification cycle, a bowl cleaning operation must be performed. A. Secure recirculating fuel as follows: 1. Turn the FUEL FORWARD selector switch to the STOP/ALARM RESET position. 2. Verify the "FUEL FORWARD" indicator is extinguished. B. Secure designated heater by depressing the HEATER OFF pushbutton; verify "HEATER ON" indicator extinguishes. CODE RFST/1796/020112 PAGE 18 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK C. When heater inlet and outlet temperature equalize, secure designated transfer pump and purifier as follows: 1. Stop transfer pump as follows: a. Depress XFR PUMP STOP pushbutton. b. Verify XFR PUMP "PUMP RUNNING" indicator extinguishes. 2. Shut purifier inlet valve. No. 1 Purifier 1-FT-V-70 No. 2 Purifier 2-FT-V-70 CAUTION: DO NOT SHUT VALVES BEFORE PUMP IS STOPPED. 3. Shut transfer pump suction valve. No. 1 Xfr Pmp 1-FT-V-66 No. 2 Xfr Pmp 2-FT-V-66 D. Secure designated heater as follows: 1. When required, shut heater inlet and outlet valves. No. 1 Heater 1-FT-V-67 1-FT-V-69 No. 2 Heater 2-FT-V-67 2-FT-V-69 2. When required, shut heater bypass valve. 1-FT-V-98 2-FT-V-98 3. When required, shut water removal bypass strainer inlet and outlet valves. 1-FT-V-103 1-FT-V-104 2-FT-V-103 2-FT-V-104 E. Shut the following transfer system valves opened to fill designated service tanks: 1. Service tank fill valve. NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-116A FT-V-116B FT-V-76A FT-V-76B 2. Service tanks stripping suction cutout. CODE RFST/1796/020112 PAGE 19 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK NO. 1 ER 4-220-1-F NO. 1 ER 4-220-4-F NO. 2 ER 4-300-1-F NO. 2 ER 5-300-2-F FT-V-123A FT-V-123B FT-V-126A FT-V-126B 3. Shut and lock service tank stripping suction line stop. 4. Purifiers discharge cross-connect. No. 1 ER FT-V-125 No. 2 ER FT-V-128 FT-V-74 FT-V-75 F. Verify tank status, monitor fuel oil tank liquid level indicators. Indicate liquid level in storage and service tanks on SD NO. TSDF. G. Report to EOOW/PACC operator, "Completed recirculating fuel oil in No. ___ fuel oil service tank." H. Clean purifier as follows: 1. Turn the SHOOT/OFF/PRIME selector switch to PRIME position, and hold until water is seen flowing past the discharge chamber sightglass. 2. Release the SHOOT/OFF/PRIME selector switch. 3. Turn the CLOSE WATER selector switch to the OFF position. 4. Turn the SHOOT/OFF/PRIME selector switch to the SHOOT position, and hold it there until the purifier shoots (approximately 2-3 seconds). 5. Release the SHOOT/OFF/PRIME selector switch and wait 15 to20 seconds. 6. Again turn the selector switch to the SHOOT position, wait until the purifier shoots, and release. Wait 15 to 20 seconds, and repeat. 7. Repeat step 6 until purifier stops shooting. 8. Turn the CLOSE WATER selector switch back to the ON position. Wait 30 seconds. CODE RFST/1796/020112 PAGE 20 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK 9. Turn the SHOOT/OFF/PRIME selector switch to PRIME position and hold it there for approximately 1 minute, until water is seen flowing past the discharge chamber sightglass. 10. Release the SHOOT/OFF/PRIME selector switch and allow it to return to the center position. 11. Turn the CLOSE WATER selector switch to the OFF position. 12. Turn the SHOOT/OFF/PRIME selector switch to the SHOOT position and hold it there until the purifier shoots (approximately 2-3 seconds). 13. Release the SHOOT/OFF/PRIME selector switch and wait 15-20 seconds. 14. Again turn the selector switch to the SHOOT position, wait until the purifier shoots, and release. Wait 15-20 seconds and repeat. 15. Repeat the shoot/wait cycle a total of 5 times. 16. Depress the PURIFIER STOP pushbutton. 17. Shut purifier outlet valve. No. 1 Purifier 1-FT-V-73 No. 2 Purifier 2-FT-V-73 18. Shut the following purifier operating water tank valves: No. 1 ER CPW-V-377 No. 2 ER CPW-V-501 b. Tank freshwater outlet. CPW-V-380 CPW-V-504 c. Purifier liquid seal supply. CPW-V-381 CPW-V-505 d. Purifier operating water supply. CPW-V-385 CPW-V-509 a. Tank freshwater inlet. CODE RFST/1796/020112 PAGE 21 OF 22 USER NOTES RECIRCULATING FUEL OIL FROM SERVICE TANK TO SERVICE TANK NOTE: The purifier will coast to a stop in approximately 30 minutes. Using the brake will stop the purifier in approximately 8 minutes. Under normal circumstances it is not necessary to use the brake to stop the purifier. WARNING: WHERE EXPLOSIVE ATMOSPHERE EXISTS, NEVER USE BRAKE TO STOP FUEL OIL PURIFIER BOWL, ALLOW BOWL TO COAST TO STOP. 19. Report to EOOW/PACC operator, "No. cleaned and secured." CODE RFST/1796/020112 ___ purifier PAGE 22 OF 22