HIGH VOLTAGE PRODUCTS Shunt reactor switching High voltage circuit-breakers Hitachi's circuit-breakers are well suited for switching of shunt reactors and are type tested for this switching duty according to IEC 62271-110. Nevertheless, to reduce stress on both the reactor and the circuitbreaker, safeguard their long service life and minimize the probability of re-ignitions, Hitachi highly recommends point-onwave switching of reactor circuit-breakers. 1. Introduction Shunt reactors are used for reactive power management in power systems. They are installed at substation level for reactive power control and voltage regulation on main bus, and for reactive power compensation on long transmission lines or cables. Sometimes they are also connected on the tertiary winding of power transformers for the same purposes. This paper explains the reactor switching duty for circuit-breaker and the advantages of applying point-on-wave (POW) switching for this application. Recommendations are based on: ● IEC, IEEE, CIGRE standard and technical reports ● Technical aspects of reactor switching duty 2. Reactor switching duty for circuit-breakers De-energization of a shunt reactor leads to voltage transients with very short rise time and frequency in the range of several kHz. Such transients are due to interaction between the inductance of the reactor and the stray capacitance on the reactor side, post the current interruption, and are generally not harmful [1]. Generally, the latest generation of circuit-breakers have very low value chopping currents, thus the inductive current in each pole is interrupted in the vicinity of a natural current zero. Moreover, this may vary based on the specification and design of the reactor and may create higher chopping current. Consequently, the transient recovery voltage (TRV) across the contact gap will vary in magni- 2/4 HITACHI ENERGY | GENERAL TECHNICAL INFORMATION| SHUNT REACTOR SWITCHING tude but it will have very short rise time and frequency in range of several kHz. The fast-rising transients can lead to a breakdown of the contact gap and, hence, reappearance of the current through arcing as shown in Fig. 1. This happens in a very short time, less than a quarter cycle post current interruption, and it is known as a “re-ignition”. The re-ignition will lead to steep voltage transient with high magnitude and frequency in the range of kilohertz, known as “re-ignition overvoltage”, which may affect the dielectric integrity and electrical lifetime of the circuit-breaker and/or the reactor [2], [3]. Dielectric strength of circuit-breaker (UDS) Current Steep voltage across contact gap (UCB) UCB > UDS Re-ignition resulting into another current loop Source voltage Fig. 1: Example of circuit-breaker re-ignition during reactor de-energization 3. Type testing and results IEC standards [4], [5] define the type testing procedures for circuitbreakers intended for reactor switching duty. This test is mainly to obtain the corresponding circuit-breaker characteristic parameters such as chopping current and voltage withstand capability. With the test circuit used, the results are most relevant for the specific nominal current magnitude and transient recovery voltage (TRV) shape applied to the circuit-breaker. For every installation, the TRV shape as well as the chopping current will differ based on the design, connection configuration and specification of the reactor. It will also be impacted by the stray capacitances at site. Consequently, the stresses on the circuit-breaker and the reactor will be different from that imposed during the type testing. Therefore, it is challenging to anticipate the impact of these variations on expected life cycle duration of the breaker or the reactor. To minimize this impact, IEC, IEEE and CIGRE study committees recommend application of point-on-wave (POW) switching [1], [2], [3]. Alternatively, other methods such as surge arresters can be used to suppress the TRV peak [6]. Nevertheless, the preferred solution needs to be evaluated for each installation [7]. for reducing the probability of re-ignitions and consequently re-ignition over-voltages by ensuring sufficient gap between arcing contacts at the time of current interruption when the TRV appears. This is achieved by separating the arcing contacts well before the natural current zero where the arc is expected to be quenched. The time difference between contact separation and current interruption is known as "arcing time”. The range of arcing times that will minimize the probability of re-ignitions is known as "re-ignition free window" and is shown in Fig. 2 [1], [5]. It shall be derived for individual phases based on the circuitbreaker characteristics obtained from the type test, considering the reactor specification and its connection configuration. This is well explained in IEC and IEEE guidelines [2], [3]. An additional benefit of point-on-wave switching is minimizing the asymmetry of inrush currents during reactor energization. With that, the probability of protection mal-operation will be reduced. The mechanical and dielectric characteristics of the circuit-breaker as specified in [8] also need to be furnished for successful application of point- on-wave switching. 4. Point-on-Wave switching of reactor breakers Point-on-wave switching (controlled switching) is the technique of controlling circuit-breaker operations to occur at a specified point on the reference voltage in each phase. For reactor breakers, it is used 2GHV065591 en B Released Public (Original document) | Shunt reactor switching High voltage circuit-breakers HITACHI ENERGY | GENERAL TECHNICAL INFORMATION | SHUNT REACTOR SWITCHING Re-ignition free window Dielectric strength of circuit-breaker TRV Current Source voltage Minimum arcing time for specific reactor configuration Fig. 2: Re-ignition free window for point-on-wave controlled de-energizaiton of shunt reactor 5. References [1] CIGRE TB 757: Guidelines and best practices for the commissioning and operation of controlled switching projects. [2] IEC/TR 62271-306: High-voltage switchgear and controlgear Part 306: Guide to IEC 62271-100, IEC 62271-1 and other IEC standards related to alternating current circuit-breakers. [3] IEEE Std C37.015™: IEEE Guide for the Application of Shunt Reactor Switching. [4] IEC 62271-100: High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers. [5] IEC 62271-110: High-voltage switchgear and controlgear - Part 110: Inductive load switching. [6] CIGRE TB 546: Protection, Monitoring and Control of Shunt Reactors. [7] CIGRE Green Book: Switching Equipment. Springer, 2019. [8] IEC/TR 62271-302: High-voltage switchgear and controlgear Part 302: Alternating current circuit-breakers with intentionally nonsimultaneous pole operation. 2GHV065591 en B Released Public (Original document) | Shunt reactor switching High voltage circuit-breakers 3/4 FACEBOOK.COM/HASHTAG/HITACHIENERGY INSTAGRAM.COM/HITACHIENERGY TWITTER.COM/HITACHIENERGY YOUTUBE.COM/C/HITACHIENERGY Hitachi Energy Switzerland AG High Voltage Products Brown Boveri Strasse 5 8050 Zurich / Switzerland Hotline 24 hours service: hitachienergy.com/contact-us e-mail: contact-us@hitachienergy.com hitachienergy.com ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Energy company. © Hitachi Energy 2021 . All rights reserved. Specifications subject to change without notice. 2GHV065591 en B Released Public (Original document) | Shunt reactor switching High voltage circuit-breakers LINKEDIN.COM/COMPANY/HITACHIENERGY