Uploaded by Exile Dummy 2

Assignment1 ME141-2 C1 FERRER

advertisement
FERRER, John Emmanuel E.
Assignment 1
ME141-2/C1
CN#12
3.2 A simple saturation ammonia compression system has a high pressure of 1.35 MN/m2
and a low pressure of 0.19 MN/m2. Find per 400,000 kJ/h of refrigerating capacity, the
power consumption of the compressor and COP of the cycle.
Vapor Compression Cycle
LIQUID LINE
DISCHARGE LINE
CONDENSER
β„Ž2 = 1710.92
β„Ž3 = 346.48
π‘˜π½
π‘˜π‘”
HIGH PRESSURE SIDE
β„Ž1 = 1417.69
EXPANSION DEVICE
β„Ž4 = 346.48
π‘˜π½
π‘˜π‘”
π‘˜
π‘˜π‘”
COMPRESSOR
Suction Line
EVAPORATOR
EXPANSION LINE
π‘˜π½
π‘˜π‘”
LOW PRESSURE SIDE
Pressure-Enthalpy Diagram of Ammonia
3
2
P
4
β„Ž3 = β„Ž4 = 346.48 π‘˜π½
/π‘˜π‘”
1
β„Ž1 = 1417.69
π‘˜π½ β„Ž = 1710.92 π‘˜π½
2
π‘˜π‘”
π‘˜π‘”
Given Data:
P1 = 0.19 MN/m2 = 0.19 MPa = 1.9 bar
P2 = 1.35 MN/m2 = 1.35 MPa = 13.5 bar
Ref. Capacity = 400,000 kJ/h
Getting for enthalpies:
Interpolate
β„Ž1 = β„Ž π‘Žπ‘‘ 1.9 π‘π‘Žπ‘Ÿ
1434.4−β„Ž1
1.7441−1.9
π’Œπ‘±
values,
=
→
𝒉
=
πŸπŸ’πŸ‘πŸ•.
πŸŽπŸ•
𝟏
1434.4−1437.2
1.7441−1.9074
π’Œπ’ˆ
𝑠1 = 𝑠 π‘Žπ‘‘ 1.9 π‘π‘Žπ‘Ÿ
Interpolate
values,
361.2−β„Ž
5.9336−𝑠1
5.9336−5.9025
13.139−13.5
1.7441−1.9
π’Œπ‘±
= 1.7441−1.9074 → π’”πŸ = πŸ“. πŸ—πŸŽπŸ‘πŸ— π’Œπ’ˆπ‘²
π’Œπ‘±
Interpolate values, 361.2−366.1 = 13.139−13.522 → π’‰πŸ‘ = π’‰πŸ’ = πŸ‘πŸ”πŸ“. πŸ–πŸ π’Œπ’ˆ
Pressure Enthalpy Chart for R717(Ammonia):
According to chart, h2 = 1730 kJ/kg
Solution:
π‘Š = π‘š(β„Ž2 − β„Ž1 )
π‘„π‘œ = π‘šπ‘žπ‘œ → π‘š =
π‘„π‘œ
π‘žπ‘œ
π‘žπ‘œ = β„Ž1 − β„Ž4
π‘˜π½
Finding the value of qo, π‘žπ‘œ = β„Ž1 − β„Ž4 = 1437.07 − 365.82 = 1071.25 π‘˜π‘”
The value for Qo in kJ/min, π‘„π‘œ =
𝑄
6666.67
π‘˜π½
β„Ž
400000
60 π‘šπ‘–π‘›
π‘˜π½
= 6666.67 π‘šπ‘–π‘›
π‘˜π‘”
The value for m, π‘š = π‘žπ‘œ = 1071.25 = 6.22 π‘šπ‘–π‘›
π‘œ
a.) Getting the value of Power Consumption (W):
π‘Š = π‘š(β„Ž2 − β„Ž1 ) = 6.22
π‘˜π‘”
π‘˜π½
π‘˜π½
π’Œπ‘±
π’Œπ‘±
(1730
− 1437.07 ) = πŸπŸ–πŸπŸ. 𝟎𝟐
= πŸ‘πŸŽ. πŸ‘πŸ•
𝒐𝒓 π’Œπ‘Ύ
min
π‘˜π‘”
π‘˜π‘”
π’Žπ’Šπ’
𝒔
b.) Getting the value of COP:
β„Ž1 −β„Ž4
𝐢𝑂𝑃 = β„Ž
2 −β„Ž1
=
π‘˜π½
π‘˜π½
−365.82
π‘˜π‘”
π‘˜π‘”
π‘˜π½
π‘˜π½
1730 −1437.07
π‘˜π‘”
π‘˜π‘”
1437.07
= πŸ‘. πŸ”πŸ”
______________________________________________________________________
3.4 In a vapor compression cycle saturated liquid Refrigerant 22 leaving the condenser
at 40°C is required to expand to the evaporator temperature of 0°C in a cold storage plant.
(a) Determine the percentage saving in network of the cycle per kg of the refrigerant if an
isentropic expander could be used to expand the refrigerant in place of the throttling
device.
(b) Also determine the percentage increase in refrigerating effect per kg of refrigerant as
a result of use of the expander. Assume that compression is isentropic from saturated
vapor state at 0°C to the condenser pressure.
Vapor Compression Cycle
LIQUID LINE
CONDENSER
DISCHARGE LINE
β„Ž2 = 432
πŸ’πŸŽβ„ƒ
β„Ž3 = 249.08
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
HIGH PRESSURE SIDE
EXPANSION DEVICE
β„Ž1 = 405.36
π‘˜π½
π‘˜π‘”
COMPRESSOR
Suction Line
β„Ž4 = 249.08
π‘˜π½
π‘˜π‘”
EVAPORATOR
EXPANSION LINE
πŸŽβ„ƒ
LOW PRESSURE SIDE
Pressure-Enthalpy Diagram of Ammonia
3
40℃
2
P
4
β„Ž3 = β„Ž4
1
0℃
β„Ž1
β„Ž2
Given Data:
T1 = 0⁰C
T3 = 40⁰C
Enthalpies:
π‘˜π½
π‘˜π‘”
π‘˜π½
𝑠1 = 𝑠𝑔 π‘Žπ‘‘ 0℃ = 1.7518
π‘˜π‘”πΎ
β„Ž1 = β„Žπ‘” π‘Žπ‘‘ 0℃ = 405.36
β„Ž3 = β„Ž4 = β„Žπ‘“ π‘Žπ‘‘ 40℃ = 249.08
𝑃3 = 𝑃2 = 15.335 π‘π‘Žπ‘Ÿ
π‘˜π½
π‘˜π‘”
Pressure Enthalpy Chart for R22:
According to chart, h2 = 432 kJ/kg
3.6 A standard vapor compression cycle using Freon 22 operates on simple saturation
cycle at the following conditions:
Refrigerating capacity 15 TR
Condensing temperature 40°C
Evaporating temperature 5°C
Calculate:
(a) Refrigerant circulation rate in kg/s.
(b) Power required by the compressor in kW.
(c) Coefficient of performance.
(d) Volume flow rate of the refrigerant at compressor suction.
(e) Compressor discharge temperature.
(f) Suction vapor volume and power consumption per ton of refrigeration.
Refrigeration engineers assume that if this Freon 22 compressor is used with R 134a, its
capacity would fall by about 40%. Examine this assumption by doing cycle analysis for
R134a with the same compressor.
Vapor Compression Cycle
LIQUID LINE
CONDENSER
DISCHARGE LINE
β„Ž2 = 430
πŸ’πŸŽβ„ƒ
β„Ž3 = 249.08
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
HIGH PRESSURE SIDE
EXPANSION DEVICE
β„Ž1 = 407.11
π‘˜π½
π‘˜π‘”
COMPRESSOR
Suction Line
β„Ž4 = 249.08
π‘˜π½
π‘˜π‘”
EVAPORATOR
EXPANSION LINE
πŸ“β„ƒ
LOW PRESSURE SIDE
Pressure-Enthalpy Diagram of R22
40℃
3
2
P
4
1
5℃
β„Ž3 = β„Ž4
β„Ž1
β„Ž2
Given Data:
T1 = 5⁰C
T3 = 40⁰C
Qo = 15 TR = 15(211 kJ/min) = 3165 kJ/min
Getting Enthalpies:
Solving h1, v1 and s1 by interpolation,
4−5
406.77 − β„Ž1
0.0416 − 𝑣1
1.7460 − 𝑠1
=
=
=
4 − 6 406.77 − 407.45 0.0416 − 0.0391 1.7460 − 1.7432
π‘˜π½
β„Ž1 = β„Žπ‘” @ 5℃ = 407.11
π‘˜π‘”
π‘š3
𝑣1 = 𝑣𝑔 @ 5℃ = 0.0404
π‘˜π‘”
π‘˜π½
𝑠1 = 𝑠𝑔 @ 5℃ = 1.7446
π‘˜π‘”πΎ
π‘˜π½
β„Ž3 = β„Ž4 = β„Žπ‘“ @ 40℃ = 249.08
π‘˜π‘”
𝑃3 = 15.335 π‘π‘Žπ‘Ÿ
Pressure Enthalpy Chart for R22:
π΄π‘π‘π‘œπ‘Ÿπ‘‘π‘–π‘›π‘” π‘‘π‘œ π‘β„Žπ‘Žπ‘Ÿπ‘‘, β„Ž2 = 430
π‘˜π½
π‘˜π‘”
Solution:
a.) Refrigerant circulation rate in kg/s
π‘„π‘œ = π‘š(β„Ž1 − β„Ž4 ) → π‘š =
π‘š=
π‘˜π½
3165 min
407.11
π‘„π‘œ
β„Ž1 − β„Ž4
π‘˜π½
π‘˜π½
− 249.08
π‘˜π‘”
π‘˜π‘”
= 20.03
π‘˜π‘”
π’Œπ’ˆ
= 𝟎. πŸ‘πŸ‘πŸ‘πŸ–
π‘šπ‘–π‘›
𝒔
b.) Power required by the compressor in kW
π‘Š = π‘š(β„Ž2 − β„Ž1 ) = 0.3338
π‘˜π‘”
π‘˜π½
π‘˜π½
(430
− 407.11 ) = πŸ•. πŸ”πŸ’ π’Œπ‘Ύ
𝑠
π‘˜π‘”
π‘˜π‘”
c.) Coefficient of Performance
π‘˜π½
π‘˜π½
β„Ž1 − β„Ž4 407.11 π‘˜π‘” − 249.08 π‘˜π‘”
𝐢𝑂𝑃 =
=
= πŸ”. πŸ—πŸŽπŸ’
π‘˜π½
π‘˜π½
β„Ž2 − β„Ž1
430
− 407.11
π‘˜π‘”
π‘˜π‘”
d.) Volume flow rate of the refrigerant at compressor suction
π‘˜π‘”
π‘š3
π’ŽπŸ‘
𝑉1 = π‘šπ‘£1 = 0.3338
(0.0404 ) = 𝟎. πŸŽπŸπŸ‘πŸ“
𝑠
π‘˜π‘”
𝒔
e.) Compressor discharge temperature
π‘»πŸ = πŸ“πŸ“β„ƒ
f.) Suction vapor volume and power consumption per ton of refrigeration.
π‘š3 1000 𝐿
𝑳
𝑉1 = 0.0404
(
)
=
πŸ’πŸŽ.
πŸ’
π‘˜π‘” 1 π‘š3
π’Œπ’ˆ
7.64 π‘˜π‘Š
π’Œπ‘Ύ
π‘Š=
= 𝟎. πŸ“πŸŽπŸ—πŸ‘
15 π‘‘π‘œπ‘›π‘ 
𝒕𝒐𝒏𝒔
Refrigeration engineers assume that if this Freon 22 compressor is used with R
134a, its capacity would fall by about 40%. Examine this assumption by doing cycle
analysis for R134a with the same compressor.
Vapor Compression Cycle
LIQUID LINE
CONDENSER
DISCHARGE LINE
β„Ž2 = 420
πŸ’πŸŽβ„ƒ
β„Ž3 = 256.41
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
HIGH PRESSURE SIDE
EXPANSION DEVICE
β„Ž1 = 401.49
π‘˜π½
π‘˜π‘”
COMPRESSOR
Suction Line
β„Ž4 = 256.41
π‘˜π½
π‘˜π‘”
EVAPORATOR
EXPANSION LINE
πŸ“β„ƒ
LOW PRESSURE SIDE
Pressure-Enthalpy Diagram of R134a
40℃
3
2
P
4
1
5℃
β„Ž3 = β„Ž4
β„Ž1
β„Ž2
Given Data:
T1 = 5⁰C
T3 = 40⁰C
Qo would fall by 40% = 15TR(0.4)=6TR
Qo =15TR – 6TR = 9TR = 9TR(211 kJ/min) =1899 kJ/min
Getting Enthalpies:
Solving h1, v1 and s1 by interpolation,
4−5
400.92 − β„Ž1
0.06039 − 𝑣1
1.7250 − 𝑠1
=
=
=
4 − 6 400.92 − 402.06 0.06039 − 0.05644 1.7250 − 1.7240
π‘˜π½
β„Ž1 = β„Žπ‘” @ 5℃ = 401.49
π‘˜π‘”
π‘š3
𝑣1 = 𝑣𝑔 @ 5℃ = 0.0584
π‘˜π‘”
π‘˜π½
𝑠1 = 𝑠𝑔 @ 5℃ = 1.7245
π‘˜π‘”πΎ
π‘˜π½
β„Ž3 = β„Ž4 = β„Žπ‘“ @ 40℃ = 256.41
π‘˜π‘”
𝑃3 = 1.0166 π‘€π‘ƒπ‘Ž
Pressure Enthalpy Chart for R134a:
π΄π‘π‘π‘œπ‘Ÿπ‘‘π‘–π‘›π‘” π‘‘π‘œ π‘β„Žπ‘Žπ‘Ÿπ‘‘, β„Ž2 = 420
π‘˜π½
π‘˜π‘”
Solution:
a.) Refrigerant circulation rate in kg/s
π‘„π‘œ = π‘š(β„Ž1 − β„Ž4 ) → π‘š =
π‘š=
π‘˜π½
1899 min
401.49
π‘„π‘œ
β„Ž1 − β„Ž4
π‘˜π½
π‘˜π½
− 256.41
π‘˜π‘”
π‘˜π‘”
= 13.09
π‘˜π‘”
π’Œπ’ˆ
= 𝟎. πŸπŸπŸ–πŸ
π‘šπ‘–π‘›
𝒔
b.) Power required by the compressor in kW
π‘Š = π‘š(β„Ž2 − β„Ž1 ) = 0.2182
π‘˜π‘”
π‘˜π½
π‘˜π½
(420
− 401.49 ) = πŸ’. πŸŽπŸ’ π’Œπ‘Ύ
𝑠
π‘˜π‘”
π‘˜π‘”
c.) Coefficient of Performance
π‘˜π½
π‘˜π½
β„Ž1 − β„Ž4 401.49 π‘˜π‘” − 256.41 π‘˜π‘”
𝐢𝑂𝑃 =
=
= πŸ•. πŸ–πŸ‘πŸ–
π‘˜π½
π‘˜π½
β„Ž2 − β„Ž1
420
− 401.49
π‘˜π‘”
π‘˜π‘”
d.) Volume flow rate of the refrigerant at compressor suction
π‘˜π‘”
π‘š3
π’ŽπŸ‘
𝑉1 = π‘šπ‘£1 = 0.2182
(0.0584 ) = 𝟎. πŸŽπŸπŸπŸ•
𝑠
π‘˜π‘”
𝒔
e.) Compressor discharge temperature
π‘»πŸ = πŸ’πŸ‘β„ƒ
f.) Suction vapor volume and power consumption per ton of refrigeration.
π‘š3 (1000 𝐿)
π‘³πŸ‘
𝑉 = (0.0584 ) (
) = πŸ“πŸ–. πŸ’
π‘˜π‘”
1 π‘š3
π’Œπ’ˆ
4.04 π‘˜π‘Š
π’Œπ‘Ύ
π‘Š=
= 𝟎. πŸ’πŸ’πŸ–πŸ—
9 π‘‘π‘œπ‘›π‘ 
𝒕𝒐𝒏𝒔
3.8 A R134a machine operates at –15°C evaporator and 35°C condenser temperatures.
Assuming a simple-saturation cycle, calculate the volume of the suction vapor and power
consumption per ton of refrigeration and COP of the cycle. Calculate the same if the
system has a regenerative heat exchanger with the suction vapor leaving at 20°C from
the heat exchanger.
Vapor Compression Cycle
LIQUID LINE
CONDENSER
DISCHARGE LINE
β„Ž2 = 420
πŸ‘πŸ“β„ƒ
β„Ž3 = 249.01
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
HIGH PRESSURE SIDE
EXPANSION DEVICE
β„Ž1 = 389.63
π‘˜π½
π‘˜π‘”
COMPRESSOR
Suction Line
β„Ž4 = 249.01
π‘˜π½
π‘˜π‘”
EVAPORATOR
EXPANSION LINE
−πŸπŸ“β„ƒ
LOW PRESSURE SIDE
Pressure-Enthalpy Diagram of R22
35℃
3
2
P
4
1
−15℃
β„Ž3 = β„Ž4
β„Ž1
β„Ž2
Given Data:
T1 = -15⁰C
T3 = 35⁰C
Getting Enthalpies:
Solving h1, v1 and s1 by interpolation
−16 − (−15)
389.02 − β„Ž1
0.12551 − 𝑣1
1.7379 − 𝑠1
=
=
=
−16 − (−14) 389.02 − 390.24 0.12551 − 0.11605 1.7379 − 1.7363
π‘˜π½
β„Ž1 = β„Žπ‘” @ − 15℃ = 389.63
π‘˜π‘”
π‘š3
𝑣1 = 𝑣𝑔 @ − 15℃ = 0.12078
π‘˜π‘”
π‘˜π½
𝑠1 = 𝑠𝑔 @ − 15℃ = 1.7371
π‘˜π‘”πΎ
Solving h3 = h4 and P3 by interpolation
34 − 35
247.54 − β„Ž
0.86263 − 𝑃
=
=
34 − 36 247.54 − 250.48 0.86263 − 0.91185
π‘˜π½
β„Ž3 = β„Ž4 = β„Žπ‘“ @35℃ = 249.01
π‘˜π‘”
𝑃3 = 0.88724 π‘€π‘ƒπ‘Ž
Pressure Enthalpy Chart for R134a:
β„Ž2 = 426
π‘˜π½
π‘˜π‘”
Solution:
a.) Volume of the Suction Vapor
π‘˜π½
1 π‘šπ‘–π‘›
211
βˆ™
π‘„π‘œ
π‘šπ‘–π‘› 60 𝑠 = 0.025 π‘˜π‘”
π‘š=
=
β„Ž1 − β„Ž4 (389.63 − 249.01)
𝑠
𝑉1 = π‘šπ‘£1 = 0.025(0.12078) = πŸ‘. πŸŽπŸπŸ—πŸ“ × πŸπŸŽ
−πŸ‘
π’ŽπŸ‘
𝒔
b.)
π‘Š = π‘š(β„Ž2 − β„Ž1 ) = 0.025(426 − 389.63) = 𝟎. πŸ—πŸŽπŸ—πŸπŸ“ π’Œπ‘Ύ
c.) COP
π‘˜π‘—
β„Ž1 − β„Ž4 (389.63 − 249.01) π‘˜π‘”
𝐢𝑂𝑃 =
=
= πŸ‘. πŸ–πŸ”πŸ”πŸ’
π‘˜π‘—
β„Ž2 − β„Ž1
(426 − 389.63)
π‘˜π‘”
With Heat Exchangers:
Vapor Compression Cycle
β„Ž3 = 249.01
β„Ž2 = 468
π‘˜π½
π‘˜π‘”
CONDENSER
π‘˜π½
π‘˜π‘”
πŸ‘πŸ“β„ƒ
β„Ž1 = 420.34
π‘˜π½
π‘˜π‘”
HEAT
EXCHANGER
β„Ž6 = 389.63
β„Ž4 = 218.3
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
EVAPORATOR
−πŸπŸ“β„ƒ
EV
β„Ž5 = 218.3
π‘˜π½
π‘˜π‘”
COMPRESSOR
Pressure Enthalpy Diagram of R134a
35℃
4’
P
2’
3
6
1
−15℃
5
20℃
β„Ž4 = β„Ž5
β„Ž3
β„Ž6
β„Ž1
β„Ž2
Given Data:
β„Ž1 = β„Ž@20℃(π‘ π‘’π‘π‘’π‘Ÿβ„Žπ‘’π‘Žπ‘‘π‘’π‘‘ π‘‘π‘Žπ‘π‘™π‘’) = 420.34
𝑠1 = 𝑠@20℃(π‘ π‘’π‘π‘’π‘Ÿβ„Žπ‘’π‘Žπ‘‘π‘’π‘‘ π‘‘π‘Žπ‘π‘™π‘’) = 1.8864
𝐾𝑗
π‘˜π‘”πΎ
𝑣1 = 𝑣@20℃(π‘ π‘’π‘π‘’π‘Ÿβ„Žπ‘’π‘Žπ‘‘π‘’π‘‘ π‘‘π‘Žπ‘π‘™π‘’) = 0.2304
β„Ž3 = β„Žπ‘“ @35℃ = 249.01
π‘˜π½
π‘˜π‘”
Heat Balance for Heat Exchanger:
β„Ž3 + β„Ž6 = β„Ž1 + β„Ž4
249.01 + 389.63 = 420.34 + β„Ž4
β„Ž4′ = 218.3
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
π‘š3
π‘˜π‘”
Pressure Enthalpy Chart for R134a:
β„Ž2′ = 468
π‘˜π½
π‘˜π‘”
Solution:
a.) Volume of suction vapor
π‘˜π½ 1 π‘šπ‘–π‘›
211
∗
π‘„π‘œ
π‘˜π‘”
π‘˜π‘” 60 𝑠
π‘š=
=
= 0.02053
β„Ž6 − β„Ž5 389.63 − 218.3
𝑠
π’ŽπŸ‘
𝑉 = π‘šπ‘£1 = 0.02053(0.2304) = πŸ’. πŸ•πŸ‘πŸŽπŸπŸ × πŸπŸŽ
𝒔
πŸ‘
b.)
π‘Š = π‘š(β„Ž2 − β„Ž1 ) = 0.02053(468 − 420.34) = 𝟎. πŸ—πŸ•πŸ–πŸ“ π’Œπ‘Ύ
c.) COP
389.63 − 218.3
= πŸ‘. πŸ“πŸ—πŸ’πŸ–
β„Ž2 − β„Ž1
468 − 420.34
______________________________________________________________________
𝐢𝑂𝑃 =
β„Ž6 − β„Ž5
=
3.10 A simple saturation cycle using Freon 22 is designed for a load of 100 TR. The
saturated suction and discharge temperatures are 5°C and 40°C respectively. Calculate:
(a) The mass flow rate of refrigerant.
(b) The COP and isentropic horsepower.
(c) The heat rejected in the condenser.
Use the following data:
t
P
hf
hg
⁰C
bar
kJ/kg
kJ/kg
5
5.836
205.9
407.1
40
15.331
249.53
416.4
Specific heat of vapor is 0.65 kJ/(kg.K).
sf
kJ/(kg.K)
1.02115
1.16659
sg
kJ/(kg.K)
1..7447
1.69953
vg
m3/kg
0.0404
Vapor Compression Cycle
LIQUID LINE
DISCHARGE LINE
CONDENSER
β„Ž2 = 433.5
πŸ’πŸŽβ„ƒ
β„Ž3 = 249.53
π‘˜π½
π‘˜π‘”
π‘˜π½
π‘˜π‘”
HIGH PRESSURE SIDE
EXPANSION DEVICE
β„Ž1 = 407.1
π‘˜π½
π‘˜π‘”
COMPRESSOR
Suction Line
β„Ž4 = 249.53
π‘˜π½
π‘˜π‘”
EVAPORATOR
EXPANSION LINE
πŸ“β„ƒ
LOW PRESSURE SIDE
Pressure-Enthalpy Diagram of R22
3
40℃
2
P
4
β„Ž3 = β„Ž4
1
5℃
β„Ž1
β„Ž2
Given Data:
RE = 100 TR = 100(211 kJ/min) = 21100 kJ/min
π‘˜π½
π‘˜π‘”
π‘˜π½
𝑠1 = 𝑠𝑔 @5℃ = 1.7447
π‘˜π‘”
π‘š3
𝑣1 = 𝑣𝑔 @5℃ = 0.0404
π‘˜π‘”
β„Ž1 = β„Žπ‘” @5℃ = 407.1
β„Ž3 = β„Ž4 = β„Žπ‘“ @40℃ = 249.53
𝑃3 = 15.331 π‘π‘Žπ‘Ÿ
π‘˜π½
π‘˜π‘”
Pressure Enthalpy Chart for R22:
β„Ž2 = 433.5
π‘˜π½
π‘˜π‘”
Solution:
a.) The mass flow rate of refrigerant
π‘˜π½
1 π‘šπ‘–π‘›
(21100 min) ( 60 𝑠 )
𝑅𝐸
π’Œπ’ˆ
π‘š=
=
= 𝟐. πŸπŸ‘πŸπŸ–
π‘˜π½
β„Ž1 − β„Ž4
𝒔
(407.1 − 249.53)
π‘˜π‘”
b.) The COP and isentropic horsepower
𝐢𝑂𝑃 =
β„Ž1 − β„Ž4 407.1 − 249.53
=
= πŸ“. πŸ—πŸ”πŸ–πŸ”
β„Ž2 − β„Ž1
433.5 − 407.1
π‘Š = π‘š(β„Ž2 − β„Ž1 ) = 2.2318(433.5 − 407.1) = 58.0268 π‘˜π‘Š (
1 β„Žπ‘
) = πŸ•πŸ•. πŸ•πŸ–πŸ‘πŸ— 𝒉𝒑
0.746 π‘˜π‘Š
c.) The heat rejected in the condenser.
π‘„π‘˜ = π‘š(β„Ž2 − β„Ž3 ) = 2.318(433.5 − 249.53) = πŸ’πŸπŸ”. πŸ’πŸ’ π’Œπ‘Ύ
Download