ANSI/AIHA Z9.5–2012 Laboratory Ventilation A Publication by American Industrial Hygiene Association BY THE Copyright AIHA® ANSI/AIHA Z9.5 SUBCOMMITTEE For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ANSI/AIHA® Z9.5 – 2012 Laboratory Ventilation Secretariat American Industrial Hygiene Association Approved April 26, 2012 Copyright AIHA® For personal use only. Do not distribute. American National Standard Approval of an American National Standard requires verification by ANSI that the requirements for due process, consensus, and other criteria for approval have been met by the standard’s developer. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly and materially affected interests. Substantial agreement means much more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made toward their resolution. The use of American National Standards is completely voluntary; their existence does not in any respect preclude anyone, whether he or she has approved the standards or not, from manufacturing, marketing, purchasing, or using products, processors, or procedures not conforming to the standards. The American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any American National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American National Standards Institute. Requests for interpretations should be addressed to the secretariat or sponsor whose name appears on the title page of this standard. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than five years from the date of approval. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute. Published by American Industrial Hygiene Association 3141 Fairview Park Drive, Suite 777, Falls Church, VA 22042 www.aiha.org Copyright © 2012 by the American Industrial Hygiene Association All rights reserved. No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher. Printed in the United States of America. ISBN 978-1-935082-34-7 Stock Number: LVEA12-437 Copyright AIHA® For personal use only. Do not distribute. Contents Page Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii 1 Scope, Application and Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1. Scope and Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Laboratory Ventilation Management Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.1. General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2. Chemical Hygiene Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.3. Responsible Person . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.4. The Role of Hazard Assessment in Laboratory Ventilation Management . . . 8 2.5. Recordkeeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3 Laboratory Fume Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3.1. Design and Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.2. Laboratory Fume Hood Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.3. Hood Airflow and Monitoring (Design and Performance Specifications) . . . 22 4 Other Containment Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 4.1. Gloveboxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 4.2. Ductless Hoods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 4.3. Special Purpose Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 5 Laboratory Ventilation Systems Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5.1. Laboratory Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5.2. Laboratory Airflow Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 5.3. Supply Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 5.4. Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 6 Commissioning and Routine Performance Testing . . . . . . . . . . . . . . . . . . . . . . . 65 6.1. Performance specifications, tests, and instrumentation . . . . . . . . . . . . . . . . 65 6.2. Commissioning of Laboratory Ventilation Systems. . . . . . . . . . . . . . . . . . . . 73 6.3. Commissioning Fume Hoods and Different Types of Systems. . . . . . . . . . . 75 6.4. Ongoing or Routine Hood and System Tests . . . . . . . . . . . . . . . . . . . . . . . . 81 7 Work Practices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 7.1. General Requirements and Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 7.2. Posting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 7.3. Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 7.4. Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 8 Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 8.1. Operations During Maintenance Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . 84 8.2. Housekeeping Before and After Maintenance . . . . . . . . . . . . . . . . . . . . . . . 84 8.3. Safety for Maintenance Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 8.4. Work Permits and Other Communications . . . . . . . . . . . . . . . . . . . . . . . . . . 85 8.5. Records. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 8.6. Testing and Monitoring Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 8.7. Monitoring Fans, Motors, and Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 8.8. Critical Service Spares . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 8.9. Critical Service Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 8.10. Performance Monitoring Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 9 Air Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 9.1. Supply Air Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 9.2. Exhaust Air Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 9.3. Filtration for Recirculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 9.4. Testing and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Copyright AIHA® For personal use only. Do not distribute. Appendices Appendix 1 Definitions, Terms, and Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Appendix 2 Referenced Standards and Publications . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Appendix 3 Selecting Laboratory Stack Designs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Appendix 4 Audit Form for ANSI/AIHA Z9.5-2010 . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Appendix 5 Sample Table of Contents for Laboratory Ventilation Management Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Copyright AIHA® For personal use only. Do not distribute. Foreword (This foreword is not part of the American National Standard Z9.5–2012.) General coverage. This standard describes required and recommended practices for the design and operation of laboratory ventilation systems used for control of exposure to airborne contaminants. It is intended for use by employers, architects, industrial hygienists, safety engineers, Chemical Hygiene Officers, Environmental Health and Safety Professionals, ventilation system designers, facilities engineers, maintenance personnel, and testing and balance personnel. It is compatible with the ACGIH® Industrial Ventilation: A Manual of Recommended Practices, ASHRAE ventilation standards, and other recognized standards of good practice. HOW TO READ THIS STANDARD. The standard is presented in a two-column format. The left column represents the requirements of the standard as expressed by the use of “shall.” The right column provides description and explanation of the requirements and suggested good practices or examples as expressed by the use of “should.” Appendices 1 and 2 provide supplementary information on definitions and references. Appendix 3 provides more detailed information on stack design. Appendix 4 provides a sample audit document and Appendix 5 presents a sample table of contents for a Laboratory Ventilation Management Plan. Flexibility. Requirements should be considered minimum criteria and can be adapted to the needs of the User establishment. It is the intent of the standard to allow and encourage innovation provided the main objective of the standard, “control of exposure to airborne contaminants,” is met. Demonstrably equal or better approaches are acceptable. When standard provisions are in conflict, the more stringent applies. Response and Update. Please contact the standards coordinator at AIHA®, 3141 Fairview Park Drive, Suite 777, Falls Church, VA 22042, if you have questions, comments, or suggestions. As with all ANSI standards, this is a “work in progress.” Future versions of the standard will incorporate suggestions and recommendations submitted by its Users and others. This standard was processed and approved for submittal to ANSI by the Z9 Accredited Standards Committee on Health and Safety Standards for Ventilation Systems. Committee approval of the standard does not necessarily imply that all committee members voted for its approval. At the time it approved this standard the Z9 Committee had the following members: Thomas Smith, Chair Theodore Knutson, Vice Chair David Hicks, Secretariat Representative At the time of publication, the Secretariat Representative was David Hicks. Organization Represented . . . . . . . . . . . . . . . . . . . . . . . .Name of Representative ACGIH® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G. Knutson ASHRAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .T. Smith American Foundry Society . . . . . . . . . . . . . . . . . . . . . . . .R. Scholz ASSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P. Osley Global Finishing Solutions . . . . . . . . . . . . . . . . . . . . . . . .G. Raifsnider National Association of Metal Finishers . . . . . . . . . . . . . .K. Hankinson NIH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F. Memarzadeh NIOSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .M. Elliott OSHA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .L. Hathon iii Copyright AIHA® For personal use only. Do not distribute. Individual Members D.J. Burton S. Crooks L. DiBerardinis C. Figueroa S. Gunsel E. Pomer N. McManus D. O’Brien J. Price K. Paulson M. Rollins J. Sheehy Subcommittee Z9.5 on Laboratory Ventilation, which developed this standard, had the following members: Steve Crooks, Chair James Coogan, Vice Chair L. DiBerardinis D. Walters (*) D.J. Burton D. Hitchings T.C. Smith V. Neuman J.M. Price G. Knutson G. Sharp S. Hauville R.A. (Bob) Henry M. Tschida C.J. McAfee R.A. DeLuca P. Pinkston K. Kretchman S. Lengerich P. Carpenter (Technical Resource) A. Kolesnikov (Observer) * retired during the standard’s development * Contributing member of Z9.5 subcommittee but not a voting member of the full Z9 Committee at the time of standard approval. iv Copyright AIHA® For personal use only. Do not distribute. AMERICAN NATIONAL STANDARD ANSI/AIHA Z9.5–2012 American National Standard for Laboratory Ventilation Requirements of the Standard 1 Scope, Application and Purpose 1.1 Scope and Application This standard applies to the ventilation in most laboratories and is written for all laboratory ventilation stakeholders. An emphasis is placed on those with legal responsibilities and liability for providing a safe laboratory. However, users/operators, industrial hygienists, other safety and environmental professionals will also find the standard written for their needs. The standard cannot establish strict liability in all cases but does attempt to fix accountability in many relationships that exist with its context. Please note that such relationships are defined throughout the standard and generally encompass the following: administration - occupant; employer - employee; management - staff; owner - occupant; owner - tenant; teacher - student; designer - owner, etc. This standard does not apply to the following types of laboratories or hoods except as it may relate to general laboratory ventilation: • • • • animal facilities, biosafety cabinets, explosives laboratories, high containment facilities (e.g., BSL 3, BSL 4, facilities operating under “chemical surety plans,” etc.), • laminar flow hoods and isolators (e.g., a clean bench for product protection, not employee protection), and • radioisotope laboratories. General laboratory safety practices are not included except where they may relate to the ventilation system’s proper function or effectiveness. Clarification and Explanation of the Requirements Laboratories conduct teaching, research, quality control, and related activities and should satisfy several general objectives, in addition to being suited for the intended use they should • be energy efficient without sacrificing safety, compliance, or space condition requirements, • be safe places to work, • comply with environmental, health, and safety regulations, and • meet any necessary criteria for the occupants and technology involved in terms of control of temperature, humidity, and air quality. Appendix 2 offers several references providing information, guidelines or specific requirements for • • • • laboratory animals – AAALAC, biosafety cabinets – NSF, biohazardous materials – ABSA, and CDC, flammables, pyrophoric and explosives – NFPA, ISEE, and IMC, • high containment facilities – CDC, ISPE, and USAMRICD, • laminar flow hoods and isolators – NSF and CETA, • radioactive materials – NRC, and • special environmental requirements for product protection such as contamination control from particulates – CETA and IEST. This standard does not apply to comfort considerations unless they have an effect on contaminant control ventilation. 1 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 1.2 Purpose The primary purpose of this standard is to establish minimum requirements and best practices for laboratory ventilation systems to protect personnel from physical harm and overexposure to harmful or potentially harmful airborne contaminants generated within the laboratory. The standard’s requirements also aim to protect property where relevant. In light of significant efforts and initiative to reduce greenhouse gases, the standard also confronts energy considerations, especially where there is a potential to impact worker health and safety. This standard: • informs the designer of the requirements and conflicts among various criteria relative to laboratory ventilation, • informs the user of information needed by designers, and • sets forth ventilation requirements that will, combined with appropriate work practices, achieve acceptable concentrations of air contaminants. Thus, this standard provides insight on how inadequate ventilation or other ventilation system deficiencies can impact safety and containment. However, this standard cannot provide designers and users with everything needed for conducting hazard assessments. Designers and users are thereby cautioned to not misconstrue the purpose of this standard as addressing comprehensive hazard control for particular hazards posed by all operations that may occur in a laboratory room. See Section 2.4. Persons responsible for laboratory operations and those working within laboratories may not be aware of how ventilation can impact environment, health and safety. On the other hand, ventilation system design professionals cannot be expected to be fully aware of all the particular hazards posed by every type of operation that may occur in a laboratory. 2 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 2 Laboratory Ventilation Management Plan 2.1 General Requirements Management shall establish a Laboratory Ventilation Management Plan (LVMP) to ensure proper selection, operation, use, and maintenance of laboratory ventilation equipment. An LVMP shall be implemented to ensure proper operation of the lab ventilation systems, help protect laboratory personnel working with potentially hazardous airborne materials, provide satisfactory environmental air quality and maintain efficient operation of the laboratory ventilation systems. The LVMP shall provide guidelines and specifications for • commissioning to verify proper performance prior to occupancy and use of the laboratory hoods, • description of training programs for ensuring proper use, testing and maintenance of the laboratory hoods, • design of laboratory ventilation systems, • maintenance procedures for providing and documenting reliable operation, • periodic confirmation that the ventilation system is used properly, • selection of appropriate laboratory hoods, • specification of monitors to continuously verify proper operation of the laboratory hoods, and • standard procedures for routine testing. Laboratory workers and other building occupants depend on proper operation of the ventilation systems to provide safe, comfortable and productive environments for work with hazardous materials. The ventilation systems comprise numerous sub-systems and individual components including air handling units, exhaust fans, airflow controls, chemical fume hoods, biological safety cabinets and other local exhaust devices. Ensuring safe and efficient operation of laboratory ventilation systems requires careful management of the systems from design to operation. An LVMP provides the framework for keeping the systems operating to satisfy the primary functional requirements of building personnel. Management participation in the selection, design, and operation of laboratory ventilation systems is critical to the overall success of the effort. The program should be supported by top management. A sample Table of Contents for a Laboratory Ventilation Management Plan is included in Appendix 5. Management should understand that ventilation equipment is not furniture, but rather it is part of installed capital equipment. It must be interfaced to the building ventilation system. An effective LVMP should satisfy several general objectives. It should; • define the responsibilities of departments and personnel responsible for ensuring proper operation of the systems, • describe how the systems are to be commissioned, tested and maintained, • provide a description of the systems and define the functional requirements, • provide specifications for design and operation of the laboratory hood systems, and • result in safe, dependable and efficient operation of the laboratory ventilation systems. 3 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 2.1.1 Exposure Control Devices Adequate laboratory fume hoods, special purpose hoods, or other engineering controls shall be used when there is a possibility of employee overexposure to air contaminants generated by a laboratory activity. There are numerous exposure control devices including: • • • • • biological safety cabinets, gloveboxes, aboratory fume hoods, local exhaust hoods, and other ventilated enclosures Exposure control devices are available in a wide variety of designs with different capabilities and limitations. Selecting the appropriate exposure control device is important to ensuring adequate protection for the laboratory worker. OSHA requires that, employers are responsible for ensuring that exposure control devices are functioning properly and implementing feasible control measures to reduce employee exposures if the exposures exceed the PELs (§29 CFR 1910.1450(e)(3)(iii)). Furthermore, if an employer discovers through their hazard assessment efforts or employee feedback, that exposure control devices are not effectively reducing employee exposures, it is the employer's responsibility to adjust controls or replace engineering controls as necessary. OSHA does not promulgate specific control device testing protocols The capture and/or containment of the selected exposure control device shall be considered adequate if, in combination with prudent practice, laboratory worker exposure levels are maintained below published or inhouse exposure limits or below those limits identified in applying or using published exposure limits. If exposure limits [e.g., Occupational Safety and Health Administration Permissible Exposure Limits (OSHA PELs), National Institute for Occupational Safety and Health Recommended Exposure Limits (OSHA RELs), American Conference of Governmental Industrial Hygienists threshold limit values (ACGIH® TLVs® ), American Industrial Hygiene Association Workplace Environmental Exposure Limits (AIHA® WEELs®), German MAKs, (maximum admissible concentrations)] or similar limits used in prescribing and/or assessing safe handling do not exist for chemicals used in the laboratory, the employers should establish comparable in-house guidelines. Qualified industrial hygienists and toxicologists working in conjunction may be best suited to accomplish this need. OSHA specifically states the following requirements in regards to employee exposure monitoring: 1910.1450(d) Employee exposure determination The performance of an exposure control device is ultimately determined by its ability to control exposure to within applicable standards or other safe limits. 1910.1450(d)(1) Initial monitoring. 4 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 The employer shall measure the employee's exposure to any substance regulated by a standard which requires monitoring if there is reason to believe that exposure levels for that substance routinely exceed the action level (or in the absence of an action level, the PEL). 1910.1450(d)(2) Periodic monitoring. If the initial monitoring prescribed by paragraph (d)(1) of this section discloses employee exposure over the action level (or in the absence of an action level, the PEL), the employer shall immediately comply with the exposure monitoring provisions of the relevant standard. 1910.1450(d)(3) Termination of monitoring. Monitoring may be terminated in accordance with the relevant standard. 1910.1450(d)(4) Employee notification of monitoring results. The employer shall, within 15 working days after the receipt of any monitoring results, notify the employee of these results in writing either individually or by posting results in an appropriate location that is accessible to employees. Section 8.C.5 Testing and Verification of Prudent Practices in the Laboratory: Handling and Disposal of Chemicals, 1995 states the following with regards to exposure monitoring for fume hood users. “Perhaps the most meaningful method for evaluating hood performance is to measure worker exposure while the exposure control device is being used for its intended purpose. Where exposure limits and analytical methods exist, personal air-sampling devices can be worn by the user and worker exposure (both excursion peak and time-weighted average) can be measured using standard industrial hygiene techniques. The criterion for evaluating the device should be the desired performance (i.e., does the device contain chemical at the desired worker-exposure level?). A sufficient number of measurements should be made to define a statistically significant maximum exposure based on worst-case operating conditions. Direct-reading instruments are available for determining the short-term concentration excursions that may occur in laboratory hood use.” Measuring for an “overexposure” to chemicals implies a means of defining an unsafe limit and having an analytical means of determining when such limit is exceeded. Since neither are commonplace or practical, surrogates have been useful in empirical determinations. However, if an employee believes that he or she is overexposed to hazardous chemicals despite their use of an exposure control device, he or she should have an internal mechanism for resolving their concern (e.g., informing a supervisor). OSHA requires that any such employee is provided an opportunity to receive an appropriate medical examination. Other similar occurrences make it incumbent on the employer to protect the employee and ensure adequate control measures (§29 CFR 1910.1450(g)(1)(iiii). In the event an employer remains unresponsive to an employee’s complaint, the employee would be encouraged to seek other advice or external intervention (e.g., filing a complaint with OSHA.) In the European Union (EU,) Registration, Evaluation, Authorization and Restriction of Chemicals (REACH) is in effect and should be consulted as appropriate for hazard evaluation information impacting laboratories operating within the scope of this standard. 5 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Chemical “hazard determination” shall be conducted by chemical manufacturers and importers as required by the Occupational Safety and Health Administration's (OSHA) Hazard Communication standard, specifically, 29 CFR 1910.1200(d). This requires that manufacturers and importers of chemicals to identify chemical hazards so that employees and downstream users can be informed about these hazards. 2.1.2 Laboratory (Room) Ventilation Rate The specific room ventilation rate shall be established or agreed upon by the owner or his or her designee. Ventilation is a tool for controlling exposure. Contaminants should be controlled at the source. Potential sources should be identified and exposure control devices should be specified as appropriate to control emissions at the source. (See Sections 3 and 4) All sources and assumptions should be clearly defined and documented. An air exchange rate (air changes per hour) cannot be specified that will meet all conditions. Furthermore, air changes per hour is not the appropriate concept for designing contaminant control systems. Excessive airflow with no demonstrable safety benefit other than meeting an arbitrary air change rate can waste considerable energy. 2.1.3 Dilution Ventilation Dilution ventilation shall be provided to control the buildup of fugitive emissions and odors in the laboratory. The dilution rate shall be expressed in terms of exhaust flow in negatively pressurized laboratories and supply flow in positively pressurized laboratories. Control of hazardous chemicals by dilution alone, in the absence of adequate laboratory fume hoods, is seldom effective in protecting laboratory users. It is almost always preferable to capture contaminants at the source, than attempt to displace or dilute them by room ventilation. 6 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Nevertheless, dilution or displacement may remove contaminants not captured by a specifically applied device. The quantity of dilution (or displacement) ventilation required is a subject of controversy. Typical dilution ventilation rates can range from 4 to 10 air changes per hour depending on heating, cooling, and comfort needs and the number and size of exposure control devices. 2.2 Chemical Hygiene Plan The laboratory shall develop a Chemical Hygiene Plan according to the OSHA Laboratory Standard (29 CFR 1910.1450). Although some laboratories do not fall under the OSHA Standard, a Chemical Hygiene Plan or Laboratory Safety Standards (or manual) can establish proper work practices. Persons participating in writing the plan should be knowledgeable in industrial hygiene, laboratory procedures and chemicals, the design of the ventilation systems, and the system’s maintenance needs. The plan should be disseminated and become the basis for employee training. The plan shall address the laboratory operations and procedures that might generate air contamination in excess of the requirements of Section 2.1.2. These operations shall be performed inside exposure control devices adequate to attain compliance. In the event of large accidental releases in the laboratory room, away from exhausts and control systems, the laboratory owner should specify appropriate evacuation protocols. The plan may also include emergency ventilation modes. (See Section 5.2.3.) The plan shall address emergencies and accidents, as well as ordinary operation. 2.3 Responsible Person In each operation using laboratory ventilation systems, the user shall designate a “responsible person.” The responsible person may have the following duties: • Ensuring that existing conditions and equipment comply with applicable standards and codes, • Ensuring that testing and monitoring are done on schedule, 7 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • Maintaining adequate records, • Participating in the design (new construction or renovation) of the lab at the conception/ planning stage (preferably as an IH or EHS professional with laboratory ventilation experience), • Performing visual checks, • Training employees, and • Performing any other related task assigned by the employer. At a minimum, the responsible person should coordinate the above activities. 2.4 The Role of Hazard Assessment in Laboratory Ventilation Management 2.4.1 General Requirements Employers shall ensure the existence of an ongoing system for assessing the potential for hazardous chemical exposure. Much of this standard addresses a generic approach to exposure control. This is necessary because many of the chemical hazards in a laboratory are chronic in nature and an employee's ability to sense overexposure is subjective. Employers shall promote awareness that laboratory hoods are not appropriate control devices for all potential chemical releases in laboratory work. The practical limits of knowing how each exposure control device is being or may be used shall be considered when specifying design features, performance criteria (commissioning and routine monitoring), or when seeking energy savings. The responsible person as defined in Section 2.3 shall be consulted in making this judgment. Exposure control devices shall be functioning properly and specific measures shall be taken to ensure proper and adequate performance (refer to Section 2.1.1). The employer may determine that providing standard laboratory hoods tested to the ANSI/ASHRAE 110 standard and an “as installed” AI 0.1 rating are best for the types of chemical hazards and work being performed at the specific workplace. The assumption that follows is that users are trained to understand limitations of the hood's control ability and would not use it for work that, for example, should be performed in a glovebox. Alternatively, ensuring all hoods are capable of meeting an AI 0.1 rating may not be necessary, for example, if the only chemical being handled has an 8-hr time-weighted average (TWA) – TLV® exposure limit of 250 ppm. 8 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 The following briefly describes an approach used within laboratory ventilation management programs in assigning control measures given the ability (or inability) to assess specific day-to-day chemical exposure situations. Hazard assessments in general are geared toward identifying chemicals, their release potential (source), their transmission route (path), and their possible routes of entry into the body (receiver). It is critical that assessments be conducted in a competent manner such that the source-path-receiver “picture” is not misconstrued. The employer shall establish criteria for determining and implementing control measures to reduce employee exposure to hazardous chemicals. Particular attention shall be given to the selection of control measures for chemicals that are known to be extremely hazardous. Hazard assessments may incorporate results from tracer gas testing of engineering controls (example: ANSI/ASHRAE 110 fume hood testing) and transmission routes (example: exhaust reentry into building supply systems). The first step in the assessment is to identify what chemical(s) can be released including normally uncharacterized byproducts. After characterizing the inherent hazard potential (largely based on physical properties, toxicity, and routes of entry), the next step is to ascertain at least qualitatively, the release "picture." At what points within the "control zone" will chemicals be evolved and at what release rate? Will the chemical release have velocity? How has the maximum credible accidental release been accounted for? Finally, how many employees are/could be exposed and what means are available for emergency response? Due to the high cost of ventilation, the choice of hood and specification of airflow rates should be scrutinized to ensure adequate protection at minimum flow. 9 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 2.4.2 “Programming” and Control Objectives for New Construction, Renovation, or Program Evaluation The following items shall be considered and decisions made regarding each element's relevance following the hazard assessment process: • • • • • • • • • • • • • • • • • • • • • Acceptable exposure concentrations Adequate workspace, Air cleaning (exhaust pollution controls), Air supply diffusers and discharge temperature, Alarm system (local and central monitoring), Commissioning (level of formality to be applied), Containment (tracer gas containment "pass" criteria – e.g., AI 0.5, AI 0.1, AI 0.05, etc.), Decommissioning, Design sash opening and sash configuration (e.g., for laboratory fume hoods), Differential pressure and airflow between spaces and use of airlocks, etc., Diversity factor in Variable Air Volume (VAV) controlled laboratory chemical hood systems, Exhaust discharge (stack design) and dilution factors, Face velocity for laboratory chemical hoods, Fan selection, Frequency of routine performance tests, Hood location, Manifold or individual systems, Redundancy and emergency power, Recirculation of potentially contaminated air, Preventive maintenance, and Vendor qualification. Programming is a term commonly used in the context of a construction project whereby the needs of a user group are developed into the intended deliverables of the project. The idea here is that various scientific disciplines have different needs in terms of ventilation. Sets of design "templates" exist based on various types of laboratories. While the characterization of laboratories by "organic chemistry, analytical chemistry, biology, etc.," are generically understood by most designers, knowledge of the chemistry and biology and, therefore, potential hazards, are generally beyond the knowledge base of most designers. The overall goal of providing a safe workspace for the end users can be greatly enhanced by the use of a hazard assessment and system design team. Quality of system design and quality of performance are enhanced by utilizing the most appropriate skills and resources available to an organization. The Laboratory Ventilation Management Plan should describe specific responsibilities for each department involved in the design, installation, operation, and use of ventilation systems (Table 1 provides some guidance.) 10 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Table 1. Major Responsibilities Recommended for Ensuring an Effective LVMP Party Responsibility Employer, Management, Owner, etc. • Allocate sufficient resources. • Coordinate activities. • Ensure proper personnel training to design, install, commission, maintain and use exposure control devices and ventilation systems. • Implement the plan, do, check, act concepts prescribed in environment, health and safety management systems. • Provide leadership. • Remove barriers between departments. Laboratory User • Indicate and report performance problems. • Provide information on potentially hazardous materials. • Provide information on procedures, work habits, duration of use, changes in hazardous operations and materials, etc. • Utilize laboratory hoods in accordance with operating requirements and safety guidelines. • Work with Environmental Health and Safety to ensure appropriate safety systems. Environment Health and Safety Engineering Maintenance Purchasing Space Planning • • • • • • Assist laboratory users with recognition and evaluation of hazards. Conduct routine safety audits. Determine suitable control strategies. Establish control objectives and safety requirements. Maintain records of performance. Provide training for users of laboratories. • Analyze design options in consideration of hazard assessment findings. • Ensure system capability to provide safe, dependable and efficient operation. • Ensure proper design, installation, and commissioning of systems. • Maintain up-to-date system documentation. • Conduct preventive maintenance and repair. • Ensure proper functioning of systems. • Ensure system dependability. • Ensure equipment is not purchased without EHS approval. • Ensure safety and engineering issues are considered in any space allocation decisions. Note to Table 1: The responsible person could be from any one of the above parties. 11 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 2.5 Recordkeeping Complete and permanent records shall be maintained for each laboratory ventilation system. Only permanent records will allow a history of the system to be maintained. Records shall include: Records should be maintained to establish a performance history of the system that can be used to optimize operation. Records should be kept for at least the life of the system or until the system is altered. • As-built drawings; • Commissioning report; • Equipment replacement or modifications Testing and Balance reports; • Inspection and routine test reports; • Periodic performance and operation reports • Maintenance logs; • Reported problems; • System modifications, and • Written Laboratory Ventilation Management Plan. 3 Laboratory Fume Hoods A laboratory fume hood is a box-like structure with typically one open side, intended for placement on a table, bench, or floor. The bench and the hood may be one integral structure. The open side is provided with a sash or sashes that move vertically and/or horizontally to close the opening. Provisions are made for exhausting air from the top or back of the hood and adjustable or fixed internal baffles are usually provided to obtain proper airflow distribution across the open face. Other terms used for a fume hood include laboratory hood, laboratory chemical hood, and fume cupboard. Although not technically correct, the term fume, as used today and historically in the context of defining fume hoods; includes both gases (vapors) and aerosols (i.e. particulates, mists, fumes, smoke, etc.). Laboratory fume hoods are often appropriate for aerosol applications. However, because of the internal turbulence, particulates, mists, etc., can deposit on the interior surfaces. For certain applications, this may preclude the use of a fume hood. Fume hoods have been a major tool in laboratory ventilation. However, a fume hood is not universally applicable to all situations. In many cases, an enclosing hood (e.g., glovebox, biosafety cabinet, ventilated enclosure) 12 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 or a local exhaust hood (snorkel, tight fitting canopy hood, or specially designed hood) may provide as good or better control and require less volumetric flow. 3.1 Design and Construction The design and construction of laboratory fume hoods shall conform to the applicable guidelines presented in the latest edition of ACGIH® Industrial Ventilation: A Manual of Recommended Practice for Design, and the most current codes, guidelines, and standards and any other applicable regulations and recommendations (see Appendix 2). It is the intent of the standard to establish design parameters and performance criteria without limiting new and innovative designs. Although construction varies among models and manufacturers, the following are recognized as good design features: • Airfoils or other designs that reduce leakage and airflow eddies at the front edge of the work area should be provided at the front edge of the bench. Airfoils should not interfere with the hood’s ability to meet the criteria of performance testing defined in this standard. • Airfoils, beveled edges or other sidewall design that reduces leakage and airflow eddies at the side walls should be provided at the side posts. • Baffle design should provide for the capture of materials generated within the hood and distribute flow through the opening to minimize potential for escape. • Cupsinks should be protected by having a vertical lip around the sink’s circumference of at least ¼ in. (0.635 cm) or eliminated if not needed. • Utilities (e.g., valves and switches) should be located at readily accessible locations outside the hood. If additional utilities are required, other than electrical, they may be located inside the hood provided they have outside cutoffs and can be connected and operated without potentially subjecting the hood operator to exposure from materials in the hood or other unsafe conditions. • Work surfaces should be recessed at least ¼ in. (0.635 cm) below the front edge of the bench or surface; sides and back should be provided with a seamless vertical lip at least ¼ in. (0.635 cm) high to contain spills. However, excessively deep recesses can increase the turbulence at the work surface and induce reverse flow. 13 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA Z9.5–2003 3.1.1 Sashes The laboratory fume hood shall be equipped with a safety-viewing sash at the face opening. Typical sashes available include the following: • Combination vertical raising and horizontal sliding sashes, • Horizontal sliding sashes, and • Vertical raising sash or sashes. Refer to Figure 1 for diagrams of different sash configurations. Sashes shall not be removed when the hood is in use. Sashes should be constructed of transparent shatterproof material suitable for the intended use. The force to open the sash shall be reasonable for the size and weight of the sash. Typically, a five foot hood with a vertical rising sash should require approximately five pounds of force to operate the sash. An additional one pound of force may be required for each additional linear foot of fume hood width. The sash should remain stationary when force is removed unless automatic closing to the designed operating sash opening is required. 3.1.1.1 Design Opening The design opening of a laboratory hood is the open area at the face of the hood, which the design team assumed when determining the ventilation requirements of the exhaust system. Where the design sash opening area is less than the maximum sash opening area, the hood shall be equipped with a mechanical sash stop. A means of communicating when openings are in excess of the design sash opening area shall be provided. The Chemical Hygiene Plan shall clearly instruct the hood users to position the sash so that the opening is no greater than the design opening while using the hood for protection. Sash-limiting devices (stops) shall not be removed without resizing or redesigning the exhaust system if the design opening is less than full opening. The responsible person, or the design team, should determine the design opening of the hood and the position of the sash-limiting device based on the needs of the hood user. Operating the hood with a larger opening than the design opening results in a reduced capture velocity (face velocity) and may significantly and adversely affect the performance of the hood. Administrative controls, training, mechanical sash stops, alarms or other means are important for ensuring that the fume hoods and exhaust systems can provide the protection for which they were designed. Operating the sash at an incorrect position can jeopardize the protection otherwise afforded the hood users and those in the adjacent area. The Chemical Hygiene Plan should indicate the proper circumstances for overriding the sash stop. 14 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 3.1.1.2 Vertical Sashes Vertical sashes shall be designed and operated so as not to be opened more than the design opening when hazardous materials are being used within the hood The vertical raising sash can usually be opened for fullface opening in the open position. If this is greater than the design opening, control at the full open position may be compromised. 3.1.1.3 Horizontal Sashes Horizontal sashes shall be designed so as not to be opened more than the design opening width when hazardous materials are being generated in the hood. The horizontal sash should be designed to allow free movement of the sash. Accumulation of debris or other materials in the sash track can impede movement. The sash track can be designed to minimize this potential by hanging the sash from overhead. In any event, periodic maintenance is recommended to ensure proper sash management. If three or more sash panels are provided, one panel should be no more than 14 in (35 cm) wide if it is to serve as a safety shield narrow enough for a person to reach around to manipulate equipment. Caution is advised when using a horizontal panel as a shield in front of the hood operator as high concentrations can accumulate behind the sash panel and escape along the Users’ arms protruding through the opening or escape when their arms are withdrawn. 3.1.1.4 Combination Sashes If a combination sash provides horizontally moving panels mounted in a frame that moves vertically, the above requirements in Sections 3.1.1.2 to 3.1.1.3 shall apply. A combination sash has the advantages and disadvantages of both types of sashes. The combination vertical raising and horizontal sliding sash, commonly referred to as a combination sash, is a combination of the vertical sash described in Section 3.1.1.2 and horizontal sash in Section 3.1.1.3. The combination sash may be raised to full vertical sash opening. In the closed vertical position, the horizontal sliding panels can be opened to provide access to the interior hood chamber. Care should be taken in determining the design opening of a combination sash. Remember to include the area beneath the airfoil sill and through the bypass if one exists. 15 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 3.1.1.5 Automatic Sash Closers All users shall be trained in good work practices, including the need to close the sash when not in use. All users of VAV systems shall be trained in the proper uses of the sash, the energy consequences of improper use, and the need to close the sash when the operation does not require its use. Automatic sash positioning systems shall have obstruction sensing capable of stopping travel during sash closing operations without breaking glassware, etc. 3.2 Laboratory Fume Hood Types 3.2.1 Auxiliary Supplied Air Hoods Auxiliary air hoods have a portion of the total volume of exhausted air provided through a plenum located above and outside of the hood Face. Auxiliary air hoods shall meet the requirements in Section 3.3. The supply plenum shall be located externally and above the top of the hood face. The auxiliary air shall be released outside the hood. The supply jet shall be distributed so as not to affect containment adversely. The auxiliary air shall not disrupt hood containment or increase potential for escape. Good work practice and energy stewardship (for VAV systems) requires the user to close the sash when the hood is not in use. A well implemented chemical hygiene plan and proper administrative actions can ensure that the sash is properly positioned. Monitoring of user compliance may be possible with some VAV systems where the Building Automation System allows trending of the sash position and feedback to management (and subsequently to the user.) If the user feels it is his/her responsibility to close the sash and the culture is that they do close the sash, then an automatic sash closer may not be necessary. On the other hand, if the user does not close the sash and management tolerates this non-compliance, safety could be jeopardized, energy consumption may increase and an automatic sash closer may be advantageous. With or without automatic closers, users should understand the importance of the closed sash, and integrate proper sash operation into work procedures. Auxiliary supplied air hoods are not recommended unless special energy conditions or design circumstances exist. The information in this section is provided because many auxiliary air hoods are currently in use. The intent is not to discourage innovative design but current experience indicates these requirements are necessary. The rationale for using auxiliary supplied air hoods is that auxiliary air need not be conditioned as much (i.e., temperature, humidity) as room supply air, and that energy cost savings may offset the increased cost of installation, operation, and maintenance. However, if not all the air from the auxiliary plenum is captured at the hood face, the anticipated energy savings is not realized. With respect to temperature and humidity, workers may experience discomfort if it is necessary to spend appreciable time at the hood. If auxiliary air hoods are designed and operated properly, worker protection at the face may be enhanced 16 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Figure 1 — Diagrams of different sash opening configurations. 17 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 because the downward airflow at the breathing zone suppresses body vortices. However, if the design and operation are improper, contamination control may be compromised. In addition, the air quality and condition inside the hood may be significantly different from the room air and these conditions may compromise the work conducted inside the hood. For retrofit projects, auxiliary air may be installed more cheaply with less disruption than by upgrading the main air supply system. If auxiliary air is conditioned to the same extent as room air, most of the potential energy advantages are lost while the disadvantages remain and the total system becomes more expensive to install, operate, and maintain. With a worker (or reasonable proportioned manikin) at the full open hood face, the hood should capture more than 90% of the auxiliary jet airflow when either the auxiliary air is at least 20°F (-6.7°C) warmer or cooler than room air. This does not apply if the auxiliary air is designed to be conditioned the same as room air. 3.2.2 Bypass Hoods Bypass hoods have a route for air entering the hood (the bypass mechanism) which opens as the sash closes. Bypass hoods shall meet the requirements in Section 3.3. The bypass mechanism shall be designed to minimize potential ejection of liquid or solid material outside the hood in the event of an eruption inside the hood. Bypass mechanisms should be designed so the bypass opens progressively and proportionally as the sash travels to the full closed position. The face velocity at the hood opening should not exceed three times the nominal face velocity with the sash fully open. Excessive velocities, greater than 300 fpm (1.5 m/s), can disrupt equipment, materials, or operations in the hood possibly creating a hazardous condition. The hood exhaust volume should remain essentially unchanged (<5% change) while the sash moves through its range of opening and closing. This is important to the design of the exhaust system. 18 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 3.2.3 Conventional Hoods Conventional hoods shall meet the requirements in Section 3.3. Conventional hoods have the hood exhaust volume remain nearly unchanged as the sash position varies from full open to the closed position. However, as the sash is lowered, the face velocity will increase. In the fully closed position, airflow would be through the airfoil only. With the sash partially open, the hood will have very high face velocity. 3.2.4 Floor-Mounted Hoods Floor-mounted hoods shall meet the requirements in Section 3.3. Floor-mounted hoods are used when the vertical working space of a bench hood is inadequate for the work or apparatus to be contained in the hood. The base of the hood should provide for the containment of spills by means of a base contiguous with the sidewalls, and a vertical lip sufficient to contain spills inside the hood, often at least 1 in. (2.54 cm) or equivalent. The lip can be replaced by a ramp to allow wheeled carts to enter the hood. The hood should be furnished with distribution ductwork or interior baffles to provide uniform face velocity. Doors and panels on the lower portion should be capable of being opened for the installation of apparatus. If the lower doors are kept closed during operation, the hood and exhaust system design and operation may be similar to a bench top laboratory fume hood and the effectiveness of the control should be equivalent if all the provisions of Section 3.3 are implemented. However, in many floor-mounted hoods, the closed lower sash may cause significant turbulence and the hood may not perform as well as a bench-top hood. If the lower panels are opened during operations, the hood loses much of its effectiveness, even if face velocities comply with Section 3.3. The design and task-specific applications of floor mounted (walk-in) hoods may make it difficult to comply with the work practices of Section 7 of this standard. 19 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Hence, consideration should be given to preparation and implementation of written standard operating procedures (SOPs) for use of floor-mounted hoods. For example, if manipulations below waist height are necessary, special provisions may be necessary such as armports or small openings strategically located at necessary access points. Small rooms with one wall constituting a supply plenum and the opposite wall constituting an exhaust plenum should not be called a floor-mounted hood. In such instances, workers are intended to be inside the hood and exposure control provisions are drastically different. This standard does not apply to such rooms. 3.2.5 Perchloric Acid Hoods Perchloric acid hoods are specifically designed to safely handle certain types of perchloric acid work and shall be used for such work. Perchloric acid hoods shall be used for handling anhydrous perchloric acid (> 85% concentration.) Perchloric acid is a strong acid, distinguished by the fact that it is the only mineral acid that is not constituted as a gas dissolved in water. As a result, the vapor phase above a solution of perchloric acid is devoid of perchlorate at temperatures below about 150°C. Its oxidation power is readily controlled by management of concentration and temperature, factors conducive to its use both as a process reagent and a catalyst. Perchloric acid digestions and other procedures performed at elevated temperatures should be done in perchloric acid hoods. Aqueous solutions of perchloric acid – The vapor pressure of 72% perchloric acid at 25°C is 6.8 mm Hg. For comparison sake, the vapor pressure of 70% nitric acid, a more widely used acid, is 49 mm Hg at 20°C. This simply means that the nitric acid would evaporate faster. When a bottle of 70% perchloric acid is merely opened, it cannot evaporate quantities presenting a risk of making contact with incompatible organic compounds. 20 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 All procedures conducted in a perchloric acid hood shall be reviewed by the responsible person and immediate supervisor. All procedures using a perchloric acid hood shall be performed by trained personnel, knowledgeable and informed about the hazards and properties of these substances, provided with appropriate protective equipment after suitable emergency contingency plans are in place. The process of diluting 60–70% perchloric acid or handling dilute aqueous solutions of perchloric acid at room temperature presents little hazard of accumulating pure perchloric acid in hood ducts. The institutional/corporate responsible person (e.g., Safety Officer/Chemical Hygiene Officer) should be notified before procedures requiring a perchloric acid hood are performed. The design of a perchloric acid hood shall include: • All inside hood surfaces shall use materials that will be stable and not react with perchloric acid to form corrosive, flammable, and/or explosive compounds or byproducts. • All interior hood, duct, fan, and stack surfaces shall be equipped with water washdown capabilities. • All ductwork shall be constructed of materials that will be stable to and not react with perchloric acid and/or its byproducts and will have smooth cleanable seamless joints. • No part of the system shall be manifolded or joined to non-perchloric acid exhaust systems. • No organic materials, including gaskets, shall be used in the hood construction unless they are known not to react with perchloric acid and/or its byproducts. • Perchloric acid hoods shall be prominently labeled “Perchloric Acid Hood, Organic Chemicals Prohibited.” Perchloric acid hoods shall be periodically washed down thoroughly with water to remove all residues in the hood, duct system, fan, and stack. The complications of wash-down features and corrosion resistance of the exhaust fan might be avoided by using an air ejector, with the supplier blower located so it is not exposed to perchloric acid. The frequency of wash down depends on the procedures inside the hood. Many procedures require daily wash down 21 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 3.2.6 Variable Air Volume (VAV) Hoods VAV hoods shall meet the requirements in Section 3.3 Variable exhaust flow from a laboratory hood has implications for room ventilation which shall be addressed according to Section 5. Additional commissioning requirements are necessary for these systems (See Section 6). The VAV hood is a conventional hood equipped with a VAV control system so designed that the exhaust volume is varied in proportion to the opening of the hood face. VAV controls applied to by-pass hoods have been noted in many facilities. These situations appear to be design errors as VAV controls applied to by-pass hoods largely defeats the purpose. It is recommended that VAV hoods be equipped with emergency overrides that permit full design flow even when the sash is closed. 3.3 Hood Airflow and Monitoring (Design and Performance Specifications) 3.3.1 Face Velocity The average face velocity of the hood shall be sufficient to contain the hazardous chemicals for which the hood was selected by following guidance in Section 2.4 and as generated under asused conditions. An adequate face velocity is necessary but is not the only criterion to achieve acceptable performance and shall not be used as the only performance indicator. Hood containment shall be verified as appropriate for the hazard being controlled (See Section 2.1.1). Face velocity had been used historically as the primary indicator of laboratory hood performance for several decades. However, studies involving large populations of laboratory fume hoods tested using a containment-based test like the ANSI/ASHRAE Standard 110, “Method of Testing the Performance of Laboratory Fume Hoods,” reveal that face velocity alone is an inadequate indicator of hood performance. In one published study, approximately 17% of the hoods tested using the method had "acceptable" face velocities in the range of 80–120 fpm, but "failed" the tracer gas containment test with control levels exceeding a control level of 0.1 ppm. Some of these tests were “As Installed” while others were “As Used.” See Section 6 on commissioning and routine performance testing for additional information. Exposure assessments involve industrial hygiene measurement of actual exposure potential to chemicals being worked with. This is accomplished through air sampling in the breathing-zone of hood user. Design face velocities for laboratory fume hoods in the range of 80 –100 fpm (0.40 – 0.50 m/s) will provide adequate face velocity for a majority of fume hoods. 22 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Factors including the design of the hood, the laboratory layout, and cross-drafts created by supply air and traffic all influence hood performance as much as or more than the face velocity. Tracer gas containment testing is a reliable method for evaluating hood containment and is recommended in commissioning or in further applications as needed. Most tracer gas containment test methods, including the ANSI/ASHRAE 110 “Method of Testing Performance of Laboratory Fume Hoods” have certain limitations that must be observed. The ANSI/ASHRAE 110 method is a static test, under controlled conditions, and at low face velocities [<60 fpm (0.30 m/s)] may not adequately reflect containment under dynamic (realworld) conditions as room and operator dynamics have significant effect on containment at these low face velocities. Hoods with excellent containment characteristics may operate adequately below 80 fpm (0.40 m/s) while others may require higher face velocities. It is therefore inappropriate to prescribe a range of acceptable face velocities for all hoods. Face velocity can be divided into ranges with differing characteristics as shown below: Containment must be verified quantitatively in this range and compliance with use restrictions, etc. enforced. Room and operator dynamics have significant effect on hood performance at low face velocities. Therefore, it is important to understand the effects of dynamic challenges on hood performance so that standard operating procedures and user restrictions can be established. Operating a hood below 60 fpm (0.30 m/s) is not recommended since containment cannot be reliably quantified at low velocities and significant risk of exposure may be present. 60–80 fpm (0.30–0.40 m/s): Hoods with excellent containment characteristics operating under relatively ideal environmental conditions (i.e., room design characteristics) and with prudent operating practices can provide adequate containment in this velocity range although at an increased level of risk. Effective administrative controls should be in place. 80–100 fpm (0.40–0.50 m/s): Most hoods can be operated effectively with relatively low risk in this velocity range although containment should still be quantitatively 23 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 verified. Proper operator training and enforcement of administrative controls are still highly recommended. This is the range recommended for a majority of laboratory fume hoods. 100–120 fpm (0.50–0.60 m/s): This velocity range has similar characteristics as 80–100 fpm (0.40–0.50 m/s) but at significantly higher operating costs. Containment may be slightly enhanced in this range and hoods that do not contain adequately in the 80–100 fpm (0.40–0.50 m/s) range may be improved by operating in this range. 120–150 fpm (0.60–0.75 m/s): Although most hoods can operate effectively in this range, performance is not significantly better than at the lower ranges of 80–100 fpm (0.40–0.50 m/s) and 100–120 fpm (0.50–0.60 m/s). The operating cost penalty imposed by high face velocities in this rage is severe. Consequently, the high face velocities are not recommended. >150 fpm (>0.75 m/s): Most laboratory experts agree that velocities above 150 fpm (0.75 m/s) at the design sash position are excessive at operating sash height and may cause turbulent flow creating more potential for leakage. 3.3.2 Laboratory Hood Minimum Flow Rate The flow rate of Constant Volume hoods and the minimum flow rate of Variable Air Volume hoods shall be sufficient to prevent hazardous concentrations of contaminants within the laboratory fume hood. In addition to maintaining proper hood face velocity, laboratory hoods shall maintain a minimum exhaust volume to ensure that contaminants are properly diluted and exhausted from a hood. The following considerations shall be taken into account (as applicable) when setting the minimum hood flow rate for each hood: • Control of ignition sources within the hood(a), • Design of the hood, the materials used in the hood and the anticipated maximum generation rates(a), (a) A specific concern when choosing to minimize hood flow rates is the potential for fire or explosion if an ignition source were to exist within a vapor’s lower and upper flammable or explosive limits. Scenarios that could generate vapors in such quantities include: • Flammable liquids spill onto the work surface, or • Flammable vapors or gases released by any other means. Before selecting the minimum flow rate the user should calculate the maximum credible concentration that might be reached at locations where an ignition source may be present. Assign a minimum flow rate or other control measure capable of maintaining this concentration at the chosen safety factor percentage of the LFL for the materials used. Typically cited percentages range from 10% to 25% of the LFL (LEL). This calculation should be made for any new materials introduced for which the previous calculation 24 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • Potential for increased hood interior corrosion. (b) • Effect on exhaust stack discharge velocity (c), • Fume hood density (d), • Need to affect directional airflows (e), and the • Operating range of the hood exhaust equipment and the associated control system. (f) may not address (e.g., a flammable material with a higher generation rate or lower LFL.) A small body of empirical research and theoretical calculations(1–7) supports a range of values for the minimum flow for spill conditions and situations involving the use of typically used quantities of solvents. At least two empirical studies measured concentrations of contaminants resulting from simulated chemical spills in a hood. Their conclusions regarding minimum flow rate for the scenarios they studied, correspond roughly to the high and low ends of the range mentioned below in the brief discussion on energy savings. Additionally, extensive experience in Europe on European hood designs using European hood testing procedures provide some support for the low end of the range. Designers may choose to increase minimum hood flow rates in order to maintain flammable vapor duct concentrations below code required levels (See Section 5.4.1). (b) A secondary concern involves the potential for corrosion of the hood interior from the use of highly corrosive operations* that may dictate the use of a fume hood minimum flow rate near the higher end of the recommended range. (c) As stated in the exhaust stack discharge section of this standard, exhaust fan systems typically have some minimum design exhaust stack velocity. The minimum flow rate selected for the hood may affect design and operation of the exhaust system. Designers need to coordinate these issues. (d) In situations where the minimum hood flow drives the airflow rate for the laboratory, the minimum flow affects energy consumption. A higher value for the minimum flow requires more power to move and condition the air. Depending on the airflow rates involved, this situation occurs usually when the hood density exceeds values in the range from 2% to 10% of the floor space in the room. (For example one or more 30x72 inch bench top fume hoods in a 750 ft2 (75 m2) lab.) In situations where some other consideration sets the flow rate for the room, the minimum hood flow does not affect energy use. 25 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Where attempting to save energy in typically higher hood density installations, minimum fume hood flow rates in the range of 150 to 375 hood air changes per hour (ACH) have been used to control vapor concentrations inside hood interiors.(1–7) Minimum hood flow rates might be selected within the above range if the user complies with provisions in the left hand column. An exception being where a written hazard assessment indicates otherwise. (e) Designers may choose to increase minimum hood flow rate if the ventilation equipment and the airflow control system cannot regulate room air flows at the values required to effectively pressurize the room (See Section 5.2.1). (f) The expression “within the operating range” includes accuracy expectations at the minimum hood air change rate selected to prevent hazardous concentrations* of contaminants within the hood: +/- 10%. --------------------------------------------------Ventilation system designers shall coordinate the operating range of the fume hood flow rate with the operating ranges of the other air supply and exhaust devices in the room. If a hood is taken completely out of service, the flow may be reduced further or shut off so long as other ventilation needs are unaffected. For the purposes of establishing a value for the internal volume of the hood used in determining the flow rate corresponding to the desired value of hood air changes per hour, the internal hood volume is approximated and hereby defined as the total internal hood work surface area times the internal height of the hood. Section References 1. Sharp, G.P.: “A Review of U.S. and European Empirical Research, Theoretical Calculations, and Industry Experience on Fume Hood Minimum Flow Rates.” International Institute of Sustainable Laboratories (I2SL) E-Library, http://www.i2sl.org/elibrary/ index.html, 2009. 2. Braun, K.O. and K.J. Caplan: “Evaporation Rate of Volatile Liquids, Final Report, 2nd edition. EPA Contract Number 68-D80112”, PACE Laboratories Project 890501.315. Washington, D.C.: U.S. Dept. of Commerce, NTIS, December 1989. 26 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 3. Klein, R.C., C. King, and P. Labbie: Solvent vapor concentrations following spills in laboratory chemical hoods. Chem. Health Safe. 11(2):4–8 (2004).4. Harnett, P.B.: Empirical data and modeling of a flammable spill in a chemical fume hood do not support the need for fire suppression within the chemical fume hood ductwork. Chem. Health Safe. 10(4):11–14 (2003). 5. Parker, A.J. and P.J. DiNenno: “Evaluation of Fixed Extinguishing System Effectiveness in Continuously Exhausting Chemical Fume Hoods.” Prepared for Merck & Co. by Hughes Associates, September 2001. 6. Labconco Corp.: Development of the Labconco Protector® Xstream® High Performance Laboratory Fume Hood. Kansas City, MO: Labconco Corporation, 2009. 7. Ventilation Test according to DIN 12 924 Part 1: Fume Cupboard DIN 12 924 TA 1500 x 900 – 900, Fume hood Test report by Waldner Laboreinrichtungen GmbH & Co. for mc6 - Bench Mounted Fume Cupboard: Test Report No.159, May 2000. 3.3.3 Flow-Measuring Device for Laboratory Fume Hoods All hoods shall be equipped with a flow indicator, flow alarm, or face velocity alarm indicator to alert users to improper exhaust flow. The purpose of the flow-measuring device is to provide the hood user with continuous information about the hood’s airflow. One method is to measure the total volume flow through the hood. Another method is to measure the face velocity. One popular method for measuring total volume flow is the Hood Static Pressure measuring device (See ACGIH’s® Industrial Ventilation: A Manual of Recommended Practices for Operation and Maintenance), which can be related to flow. This method measures static suction in the exhaust duct close to the hood throat and, if there are no adjustable dampers between the hood and the measuring station, is related to the flow volume. Other methods include various exhaust volume or flow velocity sensors. The flow-measuring device shall be capable of indicating that the air flow is in the desired range, and capable of indicating improper flow when the flow is high or low by 20%. The means of alarm or warning chosen should be provided in a manner both visible and audible to the hood user. The alarm should warn when the flow is 20% low, that is, 80% of the set point value. 27 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Tissue paper and strings do not qualify as the sole means of warning. Some manufacturers may require calibration that is more frequent. 4 Other Containment Devices 4.1 Gloveboxes 4.1.1 General Description and Use Gloveboxes shall not be used for manipulation of hazardous materials with the face or other panels open or removed nor with the gloves removed. If the potential combinations of material properties with planned manipulations are so complex the hazard cannot be estimated, a glovebox may or may not be suitable. A hazard evaluation shall be employed in such complex cases. Gloveboxes shall be used when the properties of the hazardous materials, the planned manipulations, or a credible accident would generate hazardous personal exposures if the work were done in an ordinary laboratory hood. If gloves are removed it is not a glovebox but becomes a special enclosure requiring evaluation of effectiveness of containment. Laboratory-scale gloveboxes, for which this standard applies, should have a maximum internal chamber volume of 50 ft3 (1.4 m3) (single-sided access) or 100 ft3 (2.8 m3) (double-sided access) respectively (passthrough chambers excluded). Larger gloveboxes may occasionally be found in laboratory settings but are beyond the scope of this standard. For additional guidance, see the latest edition of the American Glovebox Association Society’s standard for additional advice Guideline for Gloveboxes (AGS-G001.) Gloveboxes may be used for any laboratory manipulations that can be conducted under the restraints imposed by working with gloves through armholes. Gloveboxes may be used when the manipulated substances must be handled in a controlled (e.g., inert) atmosphere or when they must be protected from the external environment. 4.1.1.1 Location There are no special requirements for location beyond those already noted for hoods. Gloveboxes shall be located as dictated by workflow, space requirements and other needs within the laboratory. Glovebox containment is unaffected by airflow cross drafts which create challenges for open face hoods. Since manipulations through glove ports are somewhat difficult, however, it is advisable to avoid high traffic areas and to allow ample aisle space. 28 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 4.1.2 Design, Construction, and Selection A hazard assessment as required in Section 2.4 shall be done to select the appropriate glovebox. Positive pressure gloveboxes shall not be used with hazardous materials without a written risk assessment. Depending upon the nature of the hazard controlled, a glovebox may be constructed of material with favorable characteristics such as fire rating, radiation shielding, nonporous and/or impervious surfaces, corrosionresistance for the intended use, and easily cleaned. Interior corners should be covered. For additional guidance see: Interior cracks, seams, and joints shall be eliminated or sealed. STANDARDS OF PRACTICE FOR THE DESIGN AND FABRICATION OF GLOVEBAGS(AGS-G002) STANDARDS OF PRACTICE FOR THE APPLICATIONS OF LININGS TO GLOVEBOXES(AGS-G003) STANDARDS OF PRACTICE FOR THE SPECIFICATIONS OF GLOVES FORGLOVEBOXES (AGS-G005) STANDARDS OF PRACTICE FOR THE DESIGN and FABRICATION OF NUCLEAR APPLICATION GLOVEBOXES (AGS-G006) 4.1.3 Utilities Utility valves and switches shall be in conformance with applicable codes. When control of utilities from inside the glovebox is required, additional valves and switches shall be provided outside the glovebox for emergency shutoff. 4.1.4 Certain applications require that all valves be located inside of the glovebox containment and all lines exterior to the box be 100% welded. Ergonomic Design Ergonomics shall be a significant consideration in the design, construction, and/or selection of gloveboxes. Frequency of use shall dictate the extent to which ergonomic principles will be applied. Proper application of ergonomic principles shall be met by referring to the latest edition of, Guideline for Gloveboxes, AGS-G001. Frequent use versus infrequent use may dictate the extent to which ergonomics principles will be applied. 29 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 4.1.5 Provision for Spills The design of the glovebox shall provide for retaining spilled liquids so the maximum volume of liquid permitted in the glovebox will be retained. A system for draining the spilled liquid into a suitable sealed container shall be provided if the properties of the spilled liquid or other circumstances prevent cleanup by working through the gloves. 4.1.6 Exhaust Ventilation Containment gloveboxes shall be provided with exhaust ventilation to result in a negative pressure inside the box that is capable of containing the hazard at acceptable levels. See Sections 4.1.11 through 4.1.14 for ventilation recommendations for specific glovebox types. Gloveboxes shall be exhausted to the outside unless the provisions described in ANSI Standard Z9.7 and Section 5.3.6.2 of this standard are met. 4.1.7 Exhaust Air Cleaning The air or gas exhausted from the glovebox shall be cleaned and discharged to the atmosphere in accordance with the general provisions of this standard and any pertinent environmental regulations. Air-cleaning equipment shall be sized for the maximum airflow anticipated when hazardous agents are exposed in the glovebox and the glovebox openings are open to the extent permitted under that condition. If the air-cleaning device (ACD) is passive (i.e., a HEPA filter or activated carbon) provision shall be made for determining the status of the ACD, as noted in Section 9.3. If the ACD is active (i.e., a packed-bed wet scrubber), instrumentation shall be provided to indicate its status. If the glovebox is sealed tightly when closed, a pressure relief valve might be required to prevent excessive negative pressure in the glovebox, depending on the choice of air-cleaning equipment and exhaust blower. Any ACD should be selected and applied according to the manufacturer’s specifications, with attention to airflow rate, and other operating parameters that can affect performance for the contaminants of interest. The ACD should be located as close as is practical to the glovebox to minimize the length of contaminated piping or the need for maintaining high transport velocity. The ACD shall be located to permit ready access for maintenance. Provision shall be made for maintenance of the ACD without hazard to 30 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 personnel or the environment and so as not to contaminate the surrounding areas. 4.1.8 Exhaust Ducting Exhaust piping shall be in accordance with the principles described in the latest editions of the ACGIH® Industrial Ventilation Manual, ANSI/AIHA® Z9.2, and the ASHRAE Handbook Fundamentals. All piping within the occupied premises shall be under negative pressure when in operation. Materials shall be resistant to corrosion by the agents to be used. 4.1.9 Monitoring and Alarms A glovebox pressure monitoring device with a means to locally indicate adequate pressure relationships to the user shall be provided on all gloveboxes. Ergonomics principles indicate that the total number and types of alarms should be minimized. If audible alarms are not provided, documented training for users in determining safe pressure differentials shall be required. Alarms should be clearly distinguished from each other. Pressure monitoring devices shall be adjustable (i.e., able to be calibrated if not a primary standard) and subject to periodic calibration at least annually. 4.1.10 Decontamination A written decommissioning plan following the procedures outlined in the latest edition of ANSI/AIHA® Z9.11 Laboratory Decommissioning shall be developed. Before the access panel(s) of the glovebox are opened or removed, the interior contamination shall have been reduced to a safe level. If the contaminant is gaseous, the atmosphere in the box shall be adequately exchanged to remove the potentially hazardous gas. This can be affected by exhausting the box through its ventilation system, and where necessary providing an air inlet that is filtered if required. Safe level is relative to the contaminant involved. Analytical techniques for determining surface contamination (mass/unit area, counts per minute/unit area) are helping to provide increasingly sensitive but not always specific risk information. Correlating surface contamination with exposure potential remains more of an art than a science. Use caution if gases or vapors may condense or deposit on surfaces. Decontamination may still be required. 31 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 If the contaminant is liquid, any liquid on surfaces shall be wiped with suitable adsorbent material or sponges until visibly clean and dry. Used wipes shall be placed in a suitable container before being removed from the glovebox. Many liquids and some solids have vapor pressures that might cause hazardous concentrations of vapor. A combination of the contamination reduction procedures discussed above might be necessary. If the contaminant is a powder or dust, all internal surfaces shall be cleaned and wiped until visibly clean. The exterior surfaces of the gloves also shall be wiped clean. Certain direct-reading instruments (e.g., combustible gas indicators) may lend themselves to such an assessment. Neutralizing reagents should be used, if available. Precautions to prevent hazards to personnel and contamination of the premises shall be made if the ducting is to be opened or dismantled. If there is any uncertainty about the effectiveness of contamination reduction procedures, personnel involved in opening the panels of the glovebox shall be provided with appropriate PPE or clothing. The exhaust piping from the glovebox to the ACD may be contaminated, especially if a hazardous particulate is involved. Nonessential personnel should be excluded from the decontamination area. The contamination in the general work area should be reduced before use. For more information see (1) EPA 402-R-97-016, Multi-Agency Radiation Survey and Site Investigation Manual. (2) ANSI/AIHA® Z9.11 Laboratory Decommissioning. 4.1.11 High Containment Glovebox A high containment glovebox shall conform to all the mandatory requirements of Sections 4.1.1 through 4.1.11, and • Shall be provided with one or more airlock pass-through ports for inserting or removing objects or sealed containers without breaching the physical barrier between the inside and outside of the glovebox; • Shall maintain negative operating static pressure within the range of -0.5 to -1.5 in.wg (-125 Pa to -374 Pa) such that contaminant escape due to “pinhole-type" leaks is minimized. • Shall maintain dilution of any flammable vapor–air mixtures to <10% of the applicable lower explosive limit. • Shall prevent transport of contaminants out of the glovebox. Examples include gloveboxes used for controlling exposures to unknown materials or acutely hazardous and highly volatile materials where any exposure may be harmful. Care should be exercised when placing certain hazardous liquids in an evacuated airlock or interior of a glovebox when a decrease in pressure could affect the boiling point of the liquid causing it to go to a gaseous state. Meeting the above requirements will depend on whether the glovebox is continuous flow or is sealed. The minimum exhaust flow rate is usually based on a glove being breached or an access door being intentionally opened. The air velocity into the open gloveport or door should be 125 ± 25 linear fpm (0.635 ± 0.13 m/s). 32 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 4.1.12 Medium Containment Glovebox A medium containment glovebox shall conform to all the mandatory requirements of Sections 4.1.1 through 4.1.10, is not provided with passthrough airlocks, and shall be provided with sufficient exhaust ventilation to maintain an inward air velocity of at least 100 fpm (0.51 m/s) through the open access ports, and create a negative pressure of at least 0.1 in.wg (25 Pa) when access ports are closed. Examples include gloveboxes designed to prevent overexposure to acutely hazardous materials that are not highly volatile and/or where allowable exposure levels have been established and personnel exposure can be verified to be below the established allowable levels. 4.1.13 Special Case Containment Glovebox A special case containment glovebox shall be designed for special situations, does not necessarily conform to the provisions of this standard, but has been tested for the intended use and found adequate for that purpose. For example, a positive pressure is maintained in a glovebox used to build desiccant assemblies. The desiccant requires a very dry environment and the positive pressure pushes moisture away rather than allowing it to enter. There is also an exhaust fan which creates a negative pressure in the stack from the box. 4.1.14 Controlled Atmosphere Containment Glovebox An isolation and containment glovebox shall be a controlled atmosphere containment glovebox required for special atmosphere work when either the controlled atmosphere and/or the contained agents are hazardous. Examples include applications where an inert atmosphere is necessary to protect the work or when it provides an added measure of safety. 4.1.14.1 Design and Construction Design and construction, and materials shall conform to the requirements for high, medium, or special case containment gloveboxes as necessary. Refer to the AGS-1998-001Guideline for Gloveboxes for more details on construction. If the controlled atmosphere gas is hazardous, the airlocks shall be provided with a purge air exhaust system that, by manipulation of valves, creates a purge flow of room air sufficient to provide at least 5 air changes per minute, with good mixing, to the interior space of the airlock. 33 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 4.1.14.1 Operation Operation of an isolation and containment glovebox shall conform to high, medium, or special case containment requirements as necessary and the airlock purge system shall be operated for sufficient time to dilute any hazardous gas in the airlock to safe concentrations before the outer door is opened. For the empty airlocks, a purge time of 3 min. at 5 air changes per minute with good mixing would reduce an atmosphere of 100% to less than 1 ppm. If an object in the airlock has cavities that would trap gas, or if the gas might be adsorbed in the object, more time would be required: Such time should be determined by sampling the exhaust stream upstream of the ACD. Care shall be exercised when placing certain hazardous liquids in an evacuated airlock or interior of a glovebox when a decrease in pressure could affect the boiling point of the liquid, causing it to go to gaseous state. 4.1.15 Testing and Maintenance An overall operation and maintenance program shall be documented for each application of the glovebox to provide users with necessary information on periodic maintenance and testing of glovebox system components. 4.2 Components such as air locks, gloves, air cleaning devices, etc., require periodic inspection and/or performance testing. Some components may also require more detailed operating instructions for users and specific maintenance procedures for maintenance technicians than is normally found for most laboratory ventilation systems. Ductless Hoods Ductless hoods shall meet the general requirements of Sections 3.1 and 3.3 as applicable. A Hazard Evaluation and Analysis shall be conducted as directed in ANSI/AIHA® Z9.7 and Section 2.1.1.4. Compliance with the general requirements of Sections 2, 3.3, and 5.3.6.2 shall be evaluated by qualified persons. Ductless hoods that do not meet the requirements specified in Sections 9.3 and 9.4 shall be used only for operations that normally would be performed on an open bench without presenting an exposure hazard. Ductless hoods have limited application because of the wide variety of chemicals used in most laboratories. The containment collection efficiency and retention for the air-cleaning system used in the ductless hood must be evaluated for each hazardous chemical. As referenced in ANSI/AIHA® Z9.7, the hazard evaluation and analysis serve to ensure proper air quality, effective occupant protection, and satisfactory system performance. Air-cleaning performance monitoring is typically limited for many hazardous materials. Chemical-specific detectors located downstream of adsorption media or pressure drop indicators for particulate filters are necessary for systems recirculating treated air from the ductless hood back into the laboratory. 34 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Ductless hoods shall meet the performance standards for contaminant removal established by the owner. Ductless hoods may be appropriate if the contaminant is particulate and provision is made for changing filters without excessive contamination of the laboratory or potential exposure to personnel changing the filters. See Sections 9.3 and 9.4. Ductless hoods shall have signage prominently posted on the ductless hood to inform operators and maintenance personnel on the allowable chemicals used in the hood, type and limitations of filters in place, filter changeout schedule, and that the hood recirculates air to the room. Adsorption media such as activated charcoal are not efficient for fine particles and are predominately used for adsorbing certain gases or vapors. Many gases and vapors of low molecular weight will be stripped from the adsorption media and reenter the room air on continued flow of clean air through the ductless hood. When this happens, the ductless hood only serves to protect the worker at the hood face and to spread the contaminant release into the room air during a longer time span and at a lower concentration. See Section 4.2.2. Where multiple air contaminants challenge the ductless hood air-cleaning system, the collection efficiency and breakthrough properties of the air filtering media are complicated and are dependent on the nature of the specific mixture. Enhanced breakthrough of components should be especially considered as a part of the Hazard Evaluation and Analysis. See Section 4.2.2. Also the warning properties (i.e. odor, taste) of the chemical being filtered must be adequate to provide an early indication that the filtration media are not operating properly. 4.2.1 Airborne Particulates Ductless hoods that utilize air-cleaning filtration systems for recirculating exhaust air contaminated with toxic particulates shall meet the requirements of Section 9.3.1. 4.2.2 Gases and Vapors Ductless hoods utilizing adsorption or other filtration media for the collection or retention of gases and vapors shall be specified for a limited use and shall meet the requirements of Section 9.3.2. Each application of the ductless hood must be evaluated prior to use. For each chemical that may be used in the hood its retention capacity must be known and be appropriate for the intended use. Ductless hoods employing filters for removing gases and vapors shall have written documentation (records) that the manufacturer has approved the specific application of the hood prior to usage. There is currently no national consensus standard for testing and performance of gas/vapor adsorbent filters used in ductless hoods. Although widespread experience with its use is lacking, there is one standard that may be worth considering assuming that it is made 35 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 more widely available. • Standard AFNOR NF X 15-211 The manufacturer shall provide a list of chemicals approved to be used in the hood with their retention capacities. Proper disposal of unused and used (contaminated) adsorption filters shall be considered as part of the decision to use ductless hood employing such. According to Tronville and Rivers, progress toward standards for gaseous contaminant filters for general-ventilation service has been very slow. Many factors influence the efficiency and service life of adsorptive and chemisorptive filters for gaseous contaminants. Standards writers must choose a few test contaminants to represent the behavior of filters on the hundreds of contaminants that may be of interest. A major problem is to relate the performance of a filter at the low gaseous contaminant concentrations present in real HVAC systems to the performance at the relatively high test concentrations necessary for reasonable test durations. ASHRAE is developing a standard comprising three parts, now at the ‘proposed’ stage: • For laboratory tests on granular adsorptive media • For laboratory tests on complete filter cells • For field tests in installed filters (4, 5 and 6). ASTM has for many years maintained standards on many aspects of activated carbon, the most used filter medium. Standards 7, 8, 9 and 10 deal with the mass of contaminant a carbon can absorb before it becomes saturated, and no longer of use. Paolo Tronville, Richard D. Rivers, International standards: filters for buildings and gas turbines, Filtration & Separation, Volume 42, Issue 7, September 2005, Pages 39-43, ISSN 0015-1882, DOI: 10.1016/S0015-1882(05)70623-6. (http://www.sciencedirect.com/science/article/ B6VJM-4H7BN0H-13/2/9888f01240f365fa2 efeb29972982d6d) Other reference standards for performance testing include ANSI/ASME N510, ANSI/ASHRAE 52.2, and ASHRAE 2001 Handbook – Fundamentals. 36 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 4.2.3 Handling Contaminated Filters Contaminated filters shall be unloaded from the air-cleaning system following safe work practices to avoid exposing personnel to hazardous conditions and to ensure proper containment of the filters for final disposal. Airflow through the filter housing shall be shut down during filter changeout. 4.2.4 Testing and Maintenance All of the requirements of Sections 6.3, 6.4, and 8.0 for containment and airflow testing and all of the requirements of Sections 9.2 and 9.3.2 for air cleaning performance shall be followed. 4.3 Special Purpose Hoods Special laboratory chemical hoods shall be designed in accordance with ANSI/AIHA® Z9.2 and the latest edition ACGIH®’s Industrial Ventilation: A Manual of Recommended Practice. Special purpose hoods are defined as any not conforming to the specific types described in this standard. Special hoods may be used for operations for which other types are not suitable (e.g., enclosures for analytical balances, for histology processing machines, gas vents from atomic absorption, or gas chromatography equipment). Other applications might present opportunities to achieve contamination control with less bench space or less exhaust volume (such as special mixing stations, sinks, evaporating racks, heat sources, or ventilated work tables). Additional information on special exhaust system design and operation can be found in Semiconductor Exhaust Ventilation Guidebook by Jeff Burton and “Development of a Program for Performance Evaluation of University Specialty Local Exhaust Systems for Compliance with the OSHA Lab standard” (Hallock et. al., Appl. Occup. Env. Hyg. 11(3):170–77 (1995). 37 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5 Laboratory Ventilation System Design 5.1 Laboratory Design 5.1.1 Spatial Layout Laboratory designers shall consider effects on safety when establishing floor plans and spatial layout. The laboratory ventilation system affects contamination control. Spatial layout, in terms of physical barriers, and the flow of personnel and material also affects contamination control. Laboratory design should address these issues from consistent view. One useful design concept is a progression of spaces from ‘clean to dirty’ or ‘low to high hazard.’ This can lead to placement of barriers between office space and a laboratory corridor, or to an ante-room between the corridor and the laboratory. The location of laboratory chemical hoods and other hoods or vented openings with respect to open windows, doorways, and personnel traffic flow directly influences the containment ability. Cross currents, drafts, and spurious air currents from these sources may decrease a hood’s containment ability. Users should be aware that cross drafts may disturb capture efficiency even when the sash is partially closed. Laboratory designers should consider how hood location affects path of egress from the laboratory. Designers should consider arranging exhaust devices, and gathering heat producing equipment in ways that reduce the energy expense associated with safe ventilation and effective heating and cooling. 5.1.2 Noise Ventilation system designers shall consider acoustical emission when selecting air moving devices. (fans) Generation of excessive noise shall be avoided in laboratory ventilation systems. Fan location and noise treatment shall provide for sound pressure level (SPL) in conformance with local ambient noise criteria. The acoustic character of the ventilation system should help create a pleasant working environment. Sound from the ventilation system should not interfere with laboratory operations. It may be used to mask undesirable noise such as vehicular traffic, noisy equipment, or low discourse. The primary references for design criteria and methods will be found in ASHRAE publications listed below. Chapter 7 on Sound and Vibration from the ASHRAE 2005 Handbook – Fundamentals 38 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Chapter 47 on Sound and Vibration Control from ASHRAE 2007 Handbook – HVAC Applications Noise associated with mechanical ventilation and exhaust systems generally originates with fans, duct or damper vibration, and air noise caused by excessive air velocity or turbulence. Therefore, the primary design focus should be on preventing excessive noise generation. Where possible, it is good practice to locate high static pressure fans remote from occupied spaces. Use good duct design procedures. Avoid abrupt duct turns without turning vanes, change duct dimensions gradually, and generally follow procedures given in the latest ASHRAE Handbooks chapters on duct design. The careful use of vibration isolators, inertia blocks, and suitable fan speed and outlet velocities is indicated. Variable volume systems have found wide application in laboratories. However it is important to be aware that variable sound levels may focus unwanted attention on the ventilation system. Frequently laboratories have large and numerous fans, and then special care must be taken to comply with location regulations and good practice with regard to noise contamination of adjoining properties. NOTE: Such regulations vary but provide for sound pressure level (SPL) in the range of 50 dBA and limit the increase in SPL above background levels when the ventilation systems are operating. System design should provide for control of exhaust system noise (combination of fan-generated noise and air-generated noise) in the laboratory. Systems should be designed to achieve an acceptable SPL and frequency spectrum [room criteria, (RC), or noise criteria (NC)] as described in the ASHRAE 2007 Handbook – HVAC Applications. The recommended range for hospital laboratories is 50 – 35; higher RC ranges might be acceptable for other types of laboratories. NC curves above 55 might result in unacceptable speech interference in the laboratory. Use of porous or flammable sound-absorbing interior lining of exhaust ductwork usually is unacceptable. Ventilation designers may also consider the sound caused by operation of ventilation control devices, especially when installed in an open ceiling. 39 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.2 Laboratory Airflow Management 5.2.1 Differential Pressure and Airflow Between Rooms As a general rule, airflow shall be from areas of low hazard to higher hazard unless the laboratory is used as a barrier facility, such as a Clean Room, or an isolation or sterile laboratory, or other special-type laboratories. When flow from one area to another is critical to emission exposure control, airflow monitoring devices shall be installed to signal or alarm that there is a malfunction. Air shall be allowed to flow from laboratory spaces to adjoining spaces only if • There are no extremely dangerous and life-threatening materials used in the laboratory; • The concentrations of air contaminants generated by the maximum credible accident will be lower than the exposure limits required by 2.1.1. ‘Space pressurization’ or ‘directional airflow’ between spaces is one of many tools available to limit exposure to laboratory hazards. Effectively applied, it opposes migration of air contaminants; it does not eliminate it. Air moves between spaces in response to many phenomena, including thermal effects, movement of people and direct drafts from the ventilation system. Effective pressurization overcomes many of those drivers, most of the time. In a laboratory with ordinary construction, and a properly functioning ventilation system, air can move briefly the wrong direction. (Very special techniques for construction and operation can eliminate migration. Such facilities are outside the scope of this standard.) Safety professionals and users should understand pressurization as an imperfect secondary barrier, and consider it in the context of other exposure control measures. This includes consideration of ordinary work practices, distribution and storage of materials, and operation of the primary barriers. It also includes consideration of emergencies, and accidents. Pressure within a Lab Room or other space is defined as the differential pressure between that space and adjacent space(s). This differential pressure causes air to flow in the desired direction, which is typically from areas of relatively low (risk of) contamination and in the direction of increasing (risk of) contamination. The resulting Transfer Air (TA) flow occurs at all the openings in the room boundary: space around the doors, gaps between wall, floor and ceiling materials and penetrations for ducts, pipes and wires. This directional air flow through the envelope reduces the likelihood of air contaminants moving in the wrong direction. In most laboratories a negative pressure (containment) tends to prevent contaminants from migrating outside the room. In other applications such as Clean Rooms or Sterile Laboratories a positive pressure (barrier) tends to prevent contamination by air from outside the Room. The flow rate of Transfer Air depends on the differential pressure and the effective leakage area around the doors and through envelope. If the room envelope is tightly sealed, the leakage area is small, and there is very little Transfer Air flow for a given pressure. If the room is not so tight, the leakage area is larger, and more Transfer Air flows for the same differential pressure. 40 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 When a door to the laboratory is open, the effective leakage area is very large. The differential pressure and the desired containment are lost. Net airflow may continue in the intended direction as a result of the airflow offset, but the average velocity is very low. It is impractical to maintain a differential pressure across an open door. Air is likely to move both directions through the large opening, which is one reason contaminants may migrate, despite proper ventilation. The quantity of Transfer Air is also generally equivalent to the “airflow offset” which is defined as the volumetric difference between Supply Air (SA) to the space and Exhaust (or Return) Air (RA) flows driven by the mechanical ventilation systems. The desired directional airflow between rooms shall be identified in the design and operating specifications. For a building with laboratories or other critical spaces it is recommended that an “airflow map” of the building be produced. This floor plan indicates the Transfer Air Volume through each boundary, or the required relative pressure relationship between across it. It should also show the Supply Air Volume, the Exhaust (or Return) Air Volume for each space. The flow rates must balance for each room (TA=SA-EA) and for large common areas such as corridors. These air volumes are summed to size fans and other mechanical equipment. Ventilation system designers use several approaches to control laboratory pressurization. Methods include flow offset control, direct pressure control and combinations of those two. ASHRAE (Applications Handbook 2007, Page 14–12) describes each method in detail and compares them, indicating the circumstances that favor each one. Flow offset control is the most commonly applied approach and is illustrated in the following example. A lab designer chooses a value for the offset between supply and exhaust. For example, the lab Exhaust Air volume is 1000 L/s (2118 CFM) and the Supply Air Volume is 900 L/s (1906 CFM). This is defined as a “-100 L/s (-212 CFM) offset.” This -100 L/s offset draws 100 L/s of Transfer Air into the room. If the flows were reversed (Supply greater than Exhaust) the offset would be+100 L/s (+212 CFM). 41 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Flow control accuracy is crucial to the performance of a pressurization system based on the airflow offset. Designers explicitly specify the accuracy needed for the mechanical flows in and out of the room after quantifying the effect of inaccuracy on the flow offset and resulting pressurization. The leakage of the room envelope is just as important. The quantity of offset air to maintain a desired room pressure depends on the effective leakage area of the room, through the doors and envelope. In some projects, delivering an effective pressurization system includes specifying and testing the tightness of the room envelope. The construction process may explicitly include steps to adjust the observed leakage area. Rooms that leak too much are far more common than rooms that are too tight. Sometimes it is necessary to seal the envelope more carefully before the room can be effectively pressurized. Typically, the leakage area is not known. Designers rely on their experience and published design resources, (ASHRAE Handbook Fundamentals, 2005, Page 27.23) to estimate it. Then during the construction, TAB and Commissioning Phase, air flow and pressure measurements confirm the design. If necessary, the Transfer Air Volume can be adjusted and the sealing of critical rooms can be corrected to produce the desired Room Pressure Differential. When rooms are constructed very tightly, the low room leakage means that small changes in the room offset air volume cause significant changes in the differential pressure to the adjacent spaces. Controlling a very tight room by volumetric offset requires especially precise and stable volumetric air flow control. If the room envelope is too tight for volumetric offset, direct pressure control is a practical alternative. In special cases designers open a hole in the envelope and fit it with an air balancing device to control the volume of transfer air, and in some cases, a HEPA filter to prevent contamination. Such measures only apply to special high containment laboratories or barrier facilities that employ rigorous construction methods for the structure, envelope, seals, penetrations and finishes. 42 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.2.1.1 Ante-rooms and Airlocks When health and safety professionals are concerned with containing contaminants during use and operation of the doors to the room, designers shall evaluate the application of airlocks and ante-rooms. An ante-room (or vestibule) stands between the laboratory and the adjacent corridor. This can improve the effectiveness of the pressurization system, reducing the likelihood that entry and exit by personnel will cause contaminants to move in the wrong direction. An airlock shall consist of a vestibule or small enclosed area that is immediately adjacent to the laboratory room and having an airtight door at each end for passage. Airlocks shall be applied in such a way that one door provides access into or out of the laboratory room, and the other door of the airlock provides passage to or from a corridor (or other non-laboratory area). Airlock doors shall be arranged with interlocking controls so that one door must be fully closed before the other door may be opened. An airlock is distinguished from a more common vestibule or ante-room by the interlocked, airtight doors. Airlocks are utilized to prevent undesirable airflow from one area to another in high hazardous applications, which are generally outside the scope of this standard. 5.2.1.2 Critical Air Balance If the direction of airflow between adjacent spaces is deemed critical, provision shall be made to locally indicate and annunciate inadequate airflow and improper airflow direction. 5.2.2 Diversity A designer, applying the concept of ventilation load diversity, shall consider the following issues: • Capacity of any existing equipment; • Expansion considerations; • Maintenance department’s ability to perform periodic maintenance • Minimum and maximum ventilation rates for each laboratory; • Quantity of hoods and researchers; • Requirements to maintain a minimum exhaust volume for each hood on the system; • Sash management (sash habits of users); • Thermal loads; Diversity is a system design concept that can justify sizing components for a total load that is less than the sum of the individual peak demands. A system that is designed with full flow capacity for all hoods is designed for 100% Usage Factor or 100% diversity. Both existing and new facilities can benefit from applying diversity to the HVAC design if individual laboratory chemical hoods are used at different times of day. Diversity may allow existing facilities to add laboratory chemical hood capacity without adding new mechanical equipment. In new construction, diversity allows the facility to reduce capital equipment expenditures and space requirements by downsizing equipment and other infrastructure. 43 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • • • • Type, size, and operating times of facility; Type of laboratory chemical hood controls; Type of ventilation system, and Use patterns of variable volume hoods. The following conditions shall be met in order to design a system diversity: • Acceptance of all hood-use restrictions by the user groups. Designers must take into account the common work practices of the site users. • A training plan must be in place for all laboratory users to make them aware of any limitations imposed on their freedom to use the hoods at any time. • An airflow alarm system must be installed to warn users when the system is operating beyond capabilities allowed by diversity. • Restrictions on future expansions or flexibility must be identified. 5.2.3 Lab users can undermine diversity assumptions if they leave fume hood sashes open. Common approaches for ensuring diversity include VAV hoods, sash management aids such as building management system trending and automated sash closers, and hood use detection. Designing with diversity may limit the number of hoods in use or limit the sash openings, thus creating potential for overexposures to personnel, and prevention of future expansion opportunities. Therefore, diversity should be applied carefully in all situations. Certain diversity approaches may be undesirable for certain circumstances: • Sash management is difficult to predict and often unreliable. Dependence on historical sash management patterns may be insufficient for any given facility. Turnover among laboratory users may reduce the future commitment to sash management. The use of building management systems to monitor sash management may help, but this requires significant commitment by operating personnel to effectively regulate the users. Automatic sash closers—designed to improve sash management habits—may be overridden and lose their effect on diversity. • Laboratories with extremely high use patterns— such as teaching labs—may be candidates for full-flow or very high-usage factor designs. Laboratory Ventilation—Emergency Modes A hazard assessment (see Section 2.4) shall be performed to identify credible emergency conditions that may occur. Each laboratory room should be evaluated with respect to the potential for hazardous chemical spills, accidental gas release, or a fire occurrence. When the type and quantity of chemicals or compressed gases that are present in a laboratory room warrant a special, emergency ventilation mode, the room shall be equipped with provision(s) to initiate emergency notification and emergency ventilation. If the type and quantity of chemicals and gas present could pose a toxicity or fire hazard if accidentally spilled, released, or ignited, the room occupants should have a means to signal for an appropriate emergency response as well as initiate appropriate emergency ventilation. The means to signal an emergency may be a dedicated switch or pull station, or it may be a phone. The signal may come from automatically monitored Eye Wash Stations of Emergency Showers. Naturally, the benefit of such provisions is limited to incidents that an occupant is present to observe. Emergency situations (see current version of NFPA 92A) that shall be anticipated and the appropriate ventilation system responses shall include: 44 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • CHEMICAL EMERGENCY – A means such as a clearly marked wall switch, posted emergency phone number, or other readily accessible device shall be provided to enable the room occupants to initiate appropriate emergency response. For rooms served by VAV ventilation systems, the Chemical Emergency mode of operation shall maximize the room ventilation (air change per hour) rate. For rooms served by 2-state ventilation systems that utilize a reduced ventilation level for energy savings, the Chemical Emergency mode of operation shall apply the maximum ventilation rate. The intent of the chemical emergency provision is to utilize the ventilation system to maximize the dilution and removal of chemical fumes and vapors, and prevent migration of such fumes and vapors to other building areas. This response is intended to address a serious chemical spill or related incident that has the potential for releasing large amounts of hazardous fumes or vapors within the room. In addition to initiating the emergency ventilation modes, it is desirable that the emergency situation be simultaneously indicated to appropriate facility personnel at one or more designated locations. Operation of the room ventilation system in a chemical emergency mode shall not reduce the room ventilation rate, room negative pressurization level, or hood exhaust airflow rate. • FIRE – Any manual or automatic means of detecting fire (such as a pull station or smoke detector) in a laboratory room shall also activate an appropriate fire emergency mode of operation for the room and/or building ventilation system. The selected fire emergency mode shall operate all supply and exhaust equipment in the room in a manner that promotes egress, retards the spread of fire and smoke, and complies with applicable fire safety codes and standards. The intent of the fire emergency ventilation mode is to promote safe egress. This means apply negative pressurization in the room of fire origin in order to retard the spread of smoke and toxic fire gases to other parts of the facility but do not pressurize to the extent that the force needed to open the door is excessive. (Also refer to the current versions of NFPA 92A and NFPA 45.) The common practice of cutting off supply air to a fire zone does not apply to some laboratories. The combination of a high exhaust rate and no supply can depressurize a room so far that some occupants would be unable to open the doors. The initial design of the laboratory ventilation system must include analysis of flow rates, pressure levels and forces on the door to ensure that egress is possible. 45 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Note: There are other failures and abnormal events (e.g. drop out of supply fans due to freeze stat alarms) that can cause excessive space pressure differences. Each of these scenarios should be identified and addressed in the design of the supply air, exhaust air, and smoke management system so that safe laboratory and building egress is maintained under all conditions. Depending on the chemicals used, the risk of fire may be heightened upon a spill or gas release. Such situations may justify initiating a fire alarm and summoning the local fire department to respond even if a fire has not started. 5.3 Supply Air 5.3.1 Supply Air Volume If laboratories are to be maintained with a negative pressurization and directional airflow from the corridor into the laboratory, supply air volume shall be less than the exhaust from the laboratory. When laboratories are to be maintained with a positive pressurization and directional airflow, supply air volume shall be more than the exhaust from the laboratory. To maintain the desired space pressurization, the supply air volume shall respond to applicable dynamic events including: • • • • changes in desired ventilation rate, flow changes in VAV exhaust devices, temperature control demands, and temporary deficit of exhaust system capacity. In general, return air is not used in laboratories with hazardous chemicals or biological hazards. The difference between the air supplied by the ventilation system and that exhausted is the Transfer Air described in Section 5.2.1. It serves to resist the escape of airborne hazardous materials from the laboratory room. Energy recovery systems should be evaluated to reduce the energy needed to condition a large outside air intake. The ventilation rate selected for a laboratory depends on the following concerns: • control of the thermal and psychrometric environment (ASHRAE Laboratory Design Guide,) • dilution and displacement of contaminants not captured by exposure control devices, • effective operation of exposure control devices, such as laboratory hoods (See Sections 3 and 4,) and • space pressurization (See Section 5.2.1.) Typically, the air flow rate is selected to satisfy the concern requiring the greatest flow. This rationale applies from room to room during the design process, and may apply from moment to moment in an active ventilation control system. 46 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 From a practical point of view, the ventilation designer may restrict the range of air flow rates based on the capability of the ventilation equipment and associated control system. The laboratory ventilation system shall be designed to remove and dilute air contaminants in accordance with the Laboratory Ventilation Management Plan. Current information about the costs of ventilation indicates that it costs approximately $3 to $9 per cfm-year. This cost includes the energy required to move and condition the supply and exhaust air. The costs can vary based on geography and depend on the cost of energy for given area. Minimizing airflow reduces energy use and operating costs. The quantity of dilution (or displacement) ventilation required is a subject of controversy. Numerous studies make it clear that the air flow rate is just one factor affecting contaminant levels in the room. Frequently, other factors have been shown to make a bigger difference than some changes in the air flow rate. These factors include the mechanical arrangement of the supply and exhaust devices, thermal effects, occupant movement and the motion and location of doors. (Manning, et al. 2000, ASHRAE Transactions, DA00-14-3: Analysis of Air Supply Type and Exhaust Location in Laboratory Animal Research Facilities Using CFD Klein, et al. 2009, JCHAS, Laboratory air quality and room ventilation rates Smith and Yancey-Smith, 2009, JCHAS, Specification of Airflow Rates in Laboratories) The ventilation rate must also satisfy the general codes and standards that apply to the occupancy class. These studies do not show that the flow rate does not matter. On the contrary, they have shown that the flow rate certainly does affect contaminant levels, but that there is no air change rate that is always appropriate. Usually a laboratory ventilation system surpasses the codes and standards that apply to the building in general. For example, the OA ventilation per person usually exceeds the requirements of ASHRAE Standard 62.1. 47 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.3.2 Supply Air Distribution Supply air distribution shall be designed to keep air jet velocities less than half, preferably less than one-third of the capture velocity or the face velocity of the laboratory chemical hoods at their face opening. For most laboratory chemical hoods, this requirement will mean 50 fpm (0.25 m/s) or less terminal throw velocity at 6 ft (1.8 m) above the floor. For laboratories with very small volumes of hood exhaust this may be achieved by correct selection and placement of conventional aspirating supply diffusers. For rooms with greater supply air requirements, either perforated ceilings or special large-capacity radial diffusers may be necessary. These special laboratory diffusers systems are preferable from a safety viewpoint to auxiliary air hoods because the ventilation air can also be used to sweep gases and vapors from the room into the laboratory chemical hoods. The large capacity radial diffusers are available from several manufacturers designed specifically for laboratory use. These diffusers have capacities of up to 100 cfm (47.2 L/s) per square foot of diffuser and come in 1ft 1ft (0.3 m 0.3 m), 2 ft 2 ft (0.6 m 0.6 m), 1 ft 4 ft (0.3 m 1.2 m), and 2 ft 4 ft (0.6 m 1.2 m) sizes with nonaspirating design and omnidirectional radial flow patterns. Supply air diffusers where practical should be located close to the personnel corridor and entry door to the laboratory and far from the major exhaust devices. This location promotes unidirectional flow, sweeping contaminants into the exhaust devices and helping further protect the corridor from airborne hazardous materials. The ideal arrangement locates hoods and exhaust devices away from entry doors and exit corridors and locates supply air diffusers close to entry doors and exit corridors. 5.3.3 Supply Air Quality Supply systems shall meet the technical requirements of the laboratory work and the requirements of the current version of ANSI/ASHRAE Standard 62.1. Additional design information can be obtained using Computational Fluid Dynamics (see Memarzadeh, 1996). The outside air should be drawn from the least contaminated location available. Wind studies are often used to select relative placement of air intakes and exhaust 48 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.4 Exhaust 5.4.1 Exhaust System Classification Designers shall review existing regulations and code requirements for the project location. International Mechanical Code (IMC) – Section 510 – Hazardous Exhaust Systems: In cases where Section 510 of the International Mechanical Code applies, designers shall consult the current version of IMC 510. Many building codes based on the IMC define Hazardous Exhaust Systems in a way that sometimes includes laboratory exhaust systems. In the past, the designation has been an obstacle to HVAC designers. Since 2006, revisions to the IMC make that designation less of a burden. In particular, the code more readily permits manifolding, and usually eliminates the need for fire suppression. Most states have adopted this section into their state mechanical code. Section 510.2 of this code provides a definition based decision process to determine whether Section 510 applies to their design. The exceptions in Section 510.4 serve to more readily permit manifolding of laboratory exhaust, when appropriate. The exception in Section 510.7 addresses an exemption for laboratory ducts from requirements for automatic suppression. The laboratory definition and exception language for laboratories are changes that were first published in the 2004 Supplement to the International Codes and the 2006 International Mechanical Code. These changes were made to support safety and efficiency in general, and to permit manifolding where appropriate. 5.4.2 Exhaust System Ductwork 5.4.2.1 Design Laboratory exhaust system ductwork shall comply with the appropriate sections of current versions of the Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA) standards. Systems and ductwork shall be designed to maintain negative pressure within all portions of the ductwork inside the building when the system is in operation. It is permissible to locate exhaust fans in a normally unoccupied enclosed space such as a roof penthouse when the fan discharge ductwork is well sealed and the enclosed space is adequately ventilated. 49 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Exhaust ductwork shall be designed in accordance with the current versions of ANSI/AIHA® Z9.2, the ASHRAE Handbook – Fundamentals, and NFPA 45. Branch ducts shall enter a main duct so that the branch duct centerline is on a plane that includes the centerline of the main duct. For horizontal main ducts, branch ducts shall not enter a main duct on a plane below the horizontal traverse centerline of the main duct. Horizontal runs of branch ducts shall be kept at a minimum. Longitudinal sections of a duct shall be a continuous seamless tube or of a continuously welded formed sheet. Longitudinal seams that are formed mechanically shall be utilized only for light duty systems with no condensation or accretion inside the duct. Spiral ducts may be one gauge lighter than the required gauge of longitudinal seam duct, except the spiral duct gauge shall always meet the abrasive wear resistance requirements. Traverse joints shall be continuously welded or flanged with welded or Van Stone flanges. (When nonmetallic materials are used, joints shall be cemented in accordance with the manufacturer’s procedures.) If the duct is coated with a corrosion-resistant material, the coating shall extend from the inside of the duct to cover the entire face of the flange. Flange faces shall be gasketed or beaded with material suitable for service. When nonmetallic materials are used, joints cemented in accordance with the manufacturer’s procedures may be considered equivalent to welding. If condensation within the duct is likely, all horizontal duct runs shall be sloped downward at least 1 in. per 10 ft in the direction of the airflow to a suitable drain or sump. Exhaust duct sizes should be selected to ensure sufficiently high airflow velocity to retard condensation of liquids or the adherence of solids within the exhaust system. 50 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Exhaust airflow volume shall be sufficient to keep the temperature in the duct below 400°F (204°C) under all foreseeable circumstances. In some cases, accumulation of solid material within the duct system may be prevented by providing water spray nozzles in the duct at frequent intervals and sloping the duct down to an appropriate receptor (e.g., a wet dust collector). This temperature limit applies in case of ignition of a spill of flammable liquid that in turn requires an estimate of the maximum credible accident that would generate heat. All duct connections to the exhaust fan shall be consistent with good ventilation design practice. As an alternative, the duct connections may be made by means of inlet and outlet boxes. If circumstances such as space limitations prevent the implementation of the preceding requirements, then applicable speed and power corrections shall be made by applying the “System Effect Factor" (see AMCA 201-90). Where optimum duct connections cannot be made due to space or other limitations, suitable alternative means shall be substituted to compensate for the space limitations. If adequate duct connections cannot be provided at the fan, the fan shall be equipped with inlet and outlet boxes furnished by the fan manufacturer. The manufacturer shall furnish performance curves for the fan with the inlet and outlet box(es) as part of the fan. If neither adequate connections nor inlet/outlet boxes are present, the fan speed and power requirements represented in the fan rating table shall be corrected by the “System Effect Factor.” If variable air volume (VAV) laboratory chemical hoods are used, satisfying this criterion might require a heat sensor arrangement to signal the VAV controls system to increase the exhaust airflow. An alternative solution would be to provide a higher temperature exhaust system design or a high-temperature combustion flue design for the portions of the exhaust system in which temperatures might exceed 400°F (204°C) in conjunction with the current version of NFPA 86. For good inlet and outlet duct design refer to the Air Movement and Control Association’s Fan Application Manual Part 1, the ACGIH® Laboratory Ventilation Manual, and the ASHRAE Handbook – Fundamentals. An adequate outlet duct connection has the same requirements as an air inlet duct except it need be only 3 diameters in length and no vortex breaker is necessary. Transition fittings at the inlet and outlet should have a 15° or less included angle in any plane. 51 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.4.2.2 Materials Exhaust system materials shall be in accordance with the current version of ACGIH’s Industrial Ventilation: A Manual of Recommended Practice, the ASHRAE Handbook – Fundamentals, and NFPA 45. Computation of this factor requires data on the fan’s “blast area” and must typically be obtained from the manufacturer. Exhaust system materials shall be resistant to corrosion by the agents to which they are exposed. Exhaust system materials shall be noncombustible if perchloric acid or similar oxidizing agents that pose a fire or explosive hazard are used. Solid metal ductwork has good fire characteristics but in some cases has inferior corrosion resistance for some chemicals. Solid plastic ductwork generally has good corrosion resistance but may not be acceptable to the local fire authority. An economical material that can be used when appropriate and if proper care is used in installation and maintenance is a metal duct with a protective coating. However, because of the thin coatings generally used, pinhole defects in the coating may be relatively common, which would eventually lead to a very small amount of leakage. Any mechanical damage or scratching of the coating in installation or maintenance would have to be immediately and properly repaired or the bare metal revealed in the scratch will be eaten away. Owner’s representatives must spend more time and money during installation to make sure contractor coats all exposed metal during initial installation and similar care must be exercised whenever the coated exhaust duct is modified during renovations. 5.4.3 Manifolds 5.4.3.1 Combined Exhaust Systems Two or more exhaust systems may be combined into a single manifold and stack, if the conditions of 5.4.3.2 are met. Manifold exhaust systems frequently have significant advantages over individual (single-hood/single-fan) systems and are encouraged. Exhaust systems may combine all lab exhaust, or may segregate general room exhaust from fume hood exhaust. This decision can affect options for heat recovery and air cleaning. 52 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Manifold and individual systems have the following characteristics: Manifold Systems: Advantages: • Contaminant concentrations from individual hoods are diluted by the air from all the other hoods on the manifold before being released into the atmosphere. • Energy recovery is financially feasible. • Fan maintenance costs are reduced. • Fewer stacks to locate in ideal location (5.4.5, 5.4.6, Appendix 3). • First costs are lower. • High mass of discharge makes it less susceptible to wind. • Operating costs are lower. • Opportunity to install redundant fans is increased and may only require one additional fan (i.e., cost to provide redundancy is reduced.) • Opportunity to install emergency power is increased while the cost is reduced. • Opportunity to utilize diversity is increased. • Opportunity to efficiently utilize VAV controls is increased. • Opportunity to provide additional capacity for future expansion is increased. • Shaft space for ductwork is reduced. • The number of roof penetrations and potential leaks are reduced. Disadvantages: • Changing the application of a single hood (i.e., from a standard laboratory chemical hood to radioisotope hood or perchloric acid hood) is difficult. • Controls for system static pressure, capacity control, etc., are more complex than individual systems. • Fan failure affects all hoods on the system and redundancy is required. • May be difficult to apply in existing buildings. • The ability to provide treatment (i.e., scrubbing, filtering, etc.) for an individual exhaust source requires an in-line scrubber and additional static 53 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 pressure for the entire manifold or in the specific hood branch. Individual Systems: Advantages: • Changing the application of a single hood (i.e., from a standard laboratory chemical hood to radioisotope hood or perchloric acid hood) is easily accomplished. • Fan failure affects only a single hood. • Less complex system. • The ability to provide treatment (i.e., scrubbing, filtering, etc.) for an individual exhaust source is easily accomplished. Disadvantages: • • • • • • • • • • • • • Applying diversity is difficult. Energy recovery is not financially feasible. First costs are higher. Impossible to locate all stacks in ideal location (5.4.5, 5.4.6, Appendix 3). Low mass of discharge makes it more susceptible to wind Operating costs are higher. Providing redundancy is difficult due to space limitations and is more expensive. Providing emergency power is difficult and more expensive. Providing future capacity for expansion requires additional ductwork, equipment, and utilities. Maintenance costs are higher. Requires a larger number of roof penetrations and roof leak potential is increased. Shaft space requirements are higher. There is no dilution of the source effluent before releasing it to the atmosphere. 54 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Large Systems: Large and/or diverse systems that have several types of hoods often benefit from a hybrid approach where a manifold is designed to handle a majority of the hoods and individual exhaust systems are installed for those that cannot or should not be manifolded such as perchloric acid or radioisotope hoods. Adverse Chemical Reaction Potential: Contrary to popular belief, the probability of two or more reagents from different sources combining in the manifold to produce an explosion is extremely small but should be evaluated for special cases involving large quantities of materials. Consider the minimum manifold with two hoods connected to a single fan: Reagent A is spilled in Hood A, covering the entire work surface and producing maximum evaporation and duct concentration while Reagent B is similarly spilled in Hood B. Reactive chemistry experts attempting to devise worst-case binary reaction assure us that although these two chemicals, when mixed in liquid or solid form, will certainly explode, when mixed in concentrations less than 10,000 ppm (1%) in air, it is unlikely that an explosive reaction can be initiated or sustained (Hitchings, unpublished data). The last statement notwithstanding, assuming that a reaction can be initiated, the result would be only a slight adiabatic temperature increase in the duct. The ability of chemicals from different sources to form toxic products is similarly limited by low concentrations that become lower and lower the closer they get to the fan in manifold systems. 55 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.4.3.2 Manifold Requirements Laboratory chemical hood ducts may be combined into a common manifold with the following exceptions and limitations: Flow regulating devices that are pressure-independent devices also allow changes to be made in the system without the need to rebalance the entire system. Each control branch shall have a flow-regulating device to buffer the fluctuations in pressure inherent in manifolds. Manifolding of perchloric acid hoods is discouraged because nonvertical ductwork is implied by connecting one or more hoods together and nonvertical ducts are difficult to wash down properly using duct-mounted spray heads. Perchloric acid hoods shall not be manifolded with nonperchloric acid hoods unless a scrubber is installed between the hood and the manifold. Where there is a potential for ductwork contamination from hood operations as determined from the Hazard Assessment of Section 2.4, radioisotope hoods shall not be manifolded with nonradioisotope hoods unless an appropriate air-cleaning system is provided between the hood and the manifold: HEPA filter and/or carbon bed filters for gases. Installing in-line filtration is impractical in most situations because it increases the overall static pressure for the entire system unless a booster fan is installed with the HEPA filters, which increases a leak potential. Manifolding of radioisotope hoods is discouraged due to the potential contamination of the entire exhaust system in the event of HEPA filtration failure and the possibility of pressurizing the exhaust manifold with the booster fan. HEPA filters only cover radioactive dust, not radioactive gases. Systems that use heavy digestions or other operations that could cause condensation in the duct may not be appropriate for a manifold system. The high potential of condensation imposes drainage problems throughout the system rather than just for the hoods that may have high condensation. 56 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.4.3.3 Compatibility of Sources Exhaust streams that contain concentrations of flammable or explosive vapors at concentrations above the Lower Explosion Limit (LEL) as well as those that might form explosive compounds (i.e., perchloric acid hood exhaust) shall not be connected to a centralized exhaust system. Exhaust streams comprised of radioactive materials shall be adequately filtered to ensure removal of radioactive material before being connected to a centralized exhaust system. Biological exhaust hoods shall be adequately filtered to remove all hazardous biological substances prior to connection to a centralized exhaust system. 5.4.3.4 Exhaust System Reliability Unless all individual exhausts connected to the centralized exhaust system can be completely stopped without creating a hazardous situation, provision shall be made for continuous maintenance of adequate negative static pressure (suction) in all parts of the system. This requirement could be satisfied by one or both of the following provisions: • Multiple operating fans so the loss of a single fan does not result in loss of total system negative static pressure. • Spare centralized system exhaust fan(s) that will rapidly and automatically be put into service upon failure of an operating fan by repositioning isolation dampers and energizing the standby fan motor. Emergency backup power should be provided to all exhaust fans and the associated control system. As an alternative, if the hood is completely turned off, the hood shall be emptied and decontaminated and provisions shall be implemented to prevent the hood from back-drafting. Before considering complete shutdown of the hood, the following considerations should be investigated: • Notification to occupants • Room air balance, and • Use of other chemicals in the space Under these conditions, the exhaust volume is independent of the sash position. The VAV hood shall be provided with an emergency switch that allows the hood exhaust volume to return to the maximum. Note this requires careful planning for a system with less than 100% diversity (See Section 5.1.2). If the maximum exhaust volume of the variable air volume hoods in one room exceeds 10% of the room air supply volume, and if the laboratory is designed for 57 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 controlled airflow between the laboratory and adjacent spaces, automatic flow control devices should be provided to reduce the supply air volume by the same amount that hood exhaust volume is reduced. At present, this system requires sophisticated testing equipment and training of maintenance personnel. 5.4.3.5 Biological Safety Cabinets Biological safety cabinets manifolded with chemical laboratory chemical hoods shall have either: 1) A thimble connection (also known as a canopy connection), or Thimbles allow the exhaust flow to continue exhausting airflow from the room when the biological safety cabinet is off thus avoiding continuous dust loading of the biological safety cabinet filters. Secondly, this prevents the exhaust system from becoming positively pressurized by the internal fans in the biological safety cabinets in the event that the exhaust system should fail. 2) An air flow control device and an interlock/alarm for these devices shall be installed between the cabinet outlet and the exhaust manifold. Where Hazard Evaluation and Analysis determines that the installation calls for direct connection (hard ducted) of the biological safety cabinet (e.g., Class II–Type B) to an exhaust manifold system to allow work with toxic chemicals or radionuclides, interlocks and alarms shall be provided to prevent the biological safety cabinet from operating its normal starting mode or to immediately warn the operator in the event of an exhaust system failure (CDC-NIH, 1999). Thirdly, continuous exhaust through the thimble connection may be important for room air balance as well as removing the heat load of laboratory equipment. For direct (hard ducting) of Class II Type B cabinet, the exhaust flow balance is critical for the needed inflow velocity of the biological safety cabinet. Where the installation calls for direct connection of the biological safety cabinet (e.g., Class II–Type B), interlocks and alarms should be provided to prevent the biological safety cabinet from shutting down and to immediately warn the operator in the event of an exhaust system failure. Thimble connections can be improperly designed and are sometimes difficult to balance and draw in a small amount of room air. However, they are recommended over the direct connection and operation interlock design so that worker and product protection are maintained even in the event of an exhaust system failure. Interlocks, if activated during an exhaust system failure involving radioactive materials, could cause worker or product exposure. A non-manifolded dedicated exhaust system connection directly vented to the atmosphere may be needed for work with these types of hazardous materials. 58 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Constant volume control devices maintain a constant exhaust rate from all types of biological safety cabinets regardless of changes in exhaust system static pressure. Refer to NSF 49 for testing and certification of biological safety cabinets. 5.4.3.6 Static Pressure The static pressure in the exhaust system shall be lower than the surrounding areas throughout the entire length, with the exception noted in Section 5.3.1.1. This prevents contaminated air from leaking out of the duct into the building. 5.4.3.7 Fire Dampers Fire dampers shall not be installed in exhaust system ductwork (NFPA 45). The accidental activation of a fire damper will shut off airflow from one or more laboratory chemical hoods and may cause worker injury or exposure. The activation of a fire damper caused by a fire in a laboratory chemical hood will shut off airflow from that hood making it impossible to remove the combustion products from the hood and forcing the hood to become positively pressurized. This condition makes it likely that the fire will escape the fire-resistant hood into the laboratory. With the exhaust flow from one or more hoods shut off, the laboratory may become positively pressurized with respect to the corridor, encouraging the spread of the combustion products, and perhaps the fire, from the laboratory to adjoining spaces. 5.4.3.8 Fire Suppression Fire sprinklers shall not be installed in laboratory chemical hood exhaust manifolds. Studies of actual exhaust systems have demonstrated that the spray cone produced by sprinkler heads can actually act as a damper and reduce or prevent airflow in the duct past the sprinkler head (Hitchings and Deluga, personal communication). Like a fire damper, this may produce a lack of flow at one or more laboratory chemical hoods at the moment when it is needed most. 59 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.4.3.9 Continuous Operation Exhaust systems shall operate continuously to provide adequate ventilation for any hood at any time it is in use and to prevent backflow of air into the laboratory when the following conditions are present: A “motorized damper” may need to be provided at the fan to isolate the system from a stack effect. • Chemicals are present in any hood (opened or unopened). • Exhaust system operation is required to maintain minimum ventilation rates and room pressure control. • There are powered devices connected to the manifold. Powered devices include, but are not limited to: biological safety cabinets, in-line scrubbers, motorized dampers, and booster fans. 5.4.3.10 Constant Suction, Redundancy and Emergency Power Manifolds shall be maintained under negative pressure at all times and be provided with at least two exhaust fans for redundant capacity. Emergency power shall be connected to one or more of the exhaust fans where exhaust system function must be maintained even under power outage situations. 5.4.4 The manifold fans and controls should be designed so that sufficient static pressure is available to each connected exhaust source for all conditions that do not exceed the system diversity. Since each critical connected source (i.e., laboratory hoods) should have continuous performance monitors, exceeding system capacity should also result in flow alarms. Exhaust Fans Each fan applied to serve a laboratory exhaust system or to exhaust an individual piece of laboratory equipment (e.g., a laboratory chemical hood, biosafety cabinet, chemical storage, etc.) shall be adequately sized to provide the necessary amount of exhaust airflow in conjunction with the size, amount, and configuration of the connecting ductwork. In addition, each fan’s rotational speed and motor horsepower shall be sufficient to maintain both the required exhaust airflow and stack exit velocity and the necessary negative static pressure (suction) in all parts of the exhaust system. If flammable gas, vapor, or combustible dust is present in concentrations above 20% of the Lower Flammable Limit, fan construction shall 60 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 be as recommended by the current version of AMCA’s 99-0401, Classifications for Spark Resistant Construction. Laboratory exhaust fans shall be located as follows: • Physically outside of the laboratory building and preferably on the highest level roof of the building served. This is the preferred location since it generally minimizes risk of personnel coming into contact with the exhaust airflow. • In roof penthouse or a roof mechanical equipment room that is always maintained at a negative static pressure with respect to the rest of the facility, and provides direct fan discharge into the exhaust stack(s). Under most operating conditions, centrifugal fans will leak small amounts of system gases at the fan shaft. Also, fan discharge ducts typically are under positive pressure and any air leaks would discharge into the room. Locating laboratory exhaust fans as required helps ensure that any leakage will be effectively removed and will not migrate within the building. It is permissible to locate exhaust fans in a normally unoccupied enclosed space such as a roof penthouse when the fan discharge ductwork is well sealed and the enclosed space is adequately ventilated. All laboratory exhaust fans shall include provisions to allow periodic shutdown for inspection and maintenance. Such provisions include: • Isolation dampers on the inlet side of all centralized exhaust system fans that have individual discharge arrangements or their own individual exhaust stacks. • Isolation dampers on both the inlet and outlet sides of all centralized exhaust system fans that discharge into a common exhaust stack or plenum. • Ready access to all fans, motors, belts, drives, isolation dampers, associated control equipment, and the connecting ductwork. • Sufficient space to allow removal and replacement of a fan, its motor, and all other associated exhaust system components and equipment without affecting other mechanical equipment or the need to alter the building structure. The requirements for inspection access and serviceability are intended to ensure that laboratory exhaust systems can be kept and maintained in proper operating condition. If a centralized exhaust system has multiple fans and a fan replacement is necessary, the process should not require disconnecting piping or removing other building encumbrances that might lead to an indefinite postponement of the required work. See Section 8.1, Operations During Maintenance Shutdown, for necessary requirements and guidance. 61 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.4.5 Discharge of Contaminated Air The discharge of potentially contaminated air that contains a concentration more than the allowable breathing air concentration shall be • direct to the atmosphere unless the air is treated to the degree necessary for recirculation (see Section 9.3), • discharged in a manner and location to avoid reentry into the laboratory building or adjacent buildings at concentrations above 20% of allowable concentrations inside the laboratory for routine emissions or 100% of allowable concentrations for emergency emissions under wind conditions up to the 1%-wind speed for the site, and • in compliance with applicable federal, state, or local regulations with respect to air emissions 5.4.6 The in-stack concentrations of contaminants allowed under such regulations typically range from 100 to 1000 times higher than safe breathing concentrations. The 1% wind speed is the value exceeded at the site only 1% of time, according to historical weather records. Exhaust Stack Discharge The exhaust stack discharge shall be in accordance with the current version of ASHRAE Handbook – HVAC Applications, and the chapter or section dealing with Building Air Intake and Exhaust Design. In any event the discharge shall be a minimum of 10 ft (3 m) above adjacent roof lines and air intakes and in a vertical up direction. Necessary measures must be taken to protect the laboratory building and adjacent buildings from toxic materials reentry. The 10 ft (3 m) height above the adjacent roof line called for by this standard is primarily intended to protect maintenance workers from direct exposure from the top of the stack. However, this minimum 10 ft (3 m) height may be insufficient to guarantee that harmful contaminants won’t enter the outside air intake of the building or of nearby buildings. After initial installation, the exhaust stack is unchanged for the lifetime of the hood. It is uncertain that the lifetime hood usage can be accurately projected. In most cases, consistent discipline in safe hood procedures cannot be assured. Accordingly, it is prudent to use conservative guidelines in the location and arrangement of the hood discharge. The basic challenge in locating the hood discharge is to avoid re-entrainment of effluent into any building air intake or opening and to minimize exposure of the public. The selection of stack height is dependent on the building geometry and airflow pattern around the build- 62 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ing and is as variable as meteorological conditions. An excellent resource is Chapter 44 of the ASHRAE 2007 Handbook – HVAC Applications. Among the factors to consider in establishing stack configuration, design, and height are: toxicity, corrosivity, and relative humidity of the exhaust, meteorological conditions, geometry of the building, type of stack head and cap design, adjacency of other discharged stacks and building intake, discharge velocity, and receptor population. Exhaust stack discharge velocity shall be at least 3000 fpm (15.2 m/s) is required unless it can be demonstrated that a specific design meets the dilution criteria necessary to reduce the concentration of hazardous materials in the exhaust to safe levels (See Section 2.1) at all potential receptors. A discharge velocity of 2500 fpm (12.7 m/s) prevents downward flow of condensed moisture within the exhaust stack. It is good practice to make the terminal velocity at least 3000 fpm (15.2 m/s) to encourage plume rise and dilution. Aesthetic conditions concerning external appearance shall not supersede the requirements of Sections 5.4.5 and 5.4.6. In case there is a conflict, the requirements of Section 5.3.4 take priority. Some solutions that may be used are: Any architectural structure that protrudes to a height close to the stack-top elevation (i.e., architectural structure to mask unwanted appearance of stack, penthouses, mechanical equipment, nearby buildings, trees or other structures) shall be evaluated for its effects on re-entrainment The air intake or exhaust grilles shall not be located within the architectural screen or mask unless it is demonstrated to be acceptable. These factors affect the dilution of the exhaust stream and the plume trajectory. High discharge velocity and temperature increase plume rise, but high velocity is generally less effective than increased stack height. • An evaluation of the stack design that will account for the effects of problem structures should be undertaken. The evaluation should provide estimates of the expected concentration levels of exhaust contaminants at surrounding air intakes. Appropriate physical modeling (wind tunnel, mockup or water flume) or numerical modeling using appropriate methods (Computational Fluid Dynamics or other advanced numerical methods) should be undertaken as discussed in Chapter 44 of the ASHRAE 2007 Handbook – HVAC Applications. The limitations of the technique utilized should be understood and evidence should be provided that the results are conservative or accurate for the case being modeled. When physical modeling is used, procedures discussed in the EPA Guideline for Modeling of Atmospheric Diffusion (Office of Air Quality Planning and Standards, EPA600/8-81-009, April 1981) should be employed. • Treatment of the discharge gas may permit a lower and esthetically acceptable stack. The technology of gas-treating equipment is outside the scope of this standard except as described in 63 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Section 9.2. • Appendix 3 is provided to assist the designer in understanding stack height determination and evaluation methods. 5.4.7 Recirculation of Room Exhaust Air Non-laboratory air or air from building areas adjacent to the laboratory is permitted as part of the supply air to the laboratory if its quality is adequate. In many laboratory settings, the laboratory is purposely kept at a slight negative differential pressure with respect to adjacent building spaces. In this situation, air flows from the adjacent spaces into the laboratory through building cracks and doorways, at least when open. This may be highly desirable; if not, this flow can be reduced, but not completely eliminated, by use of double-door anterooms, with corresponding consumption of interior space and some hindrance to traffic. 5.4.7.1 General Room Exhaust Air exhausted from the general laboratory space (as distinguished from laboratory chemical hoods) shall not be recirculated to other areas unless one of the following sets of criteria is met: 1) Criteria A Some laboratories have no general exhaust, so there is no flow to consider recirculating. Devices that are intended to provide heating and/or cooling by recirculating the air within a laboratory space (i.e., fan coil units) are exempt from this requirement • The concentration of air contaminants generated by maximum credible accident will be lower than short-term exposure limits required by 2.1.1; • There are no extremely dangerous or lifethreatening materials used in the laboratory; and • The system serving the laboratory chemical hoods is provided with installed redundancy, emergency power, and other reliability features as necessary, or 2) Criteria B • Provision of 100% outside air, whenever continuous monitoring indicates an alarm condition; • Recirculated air is treated to reduce contaminant concentrations to those specified in 2.1.1; and 64 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • Recirculated air is monitored continuously for contaminant concentrations or provided with a secondary backup air-cleaning device that also serves as a monitor (via a HEPA filter in a series with a less efficient filter, for particulate contamination only). Refer to Section 9.3.1. 5.4.7.2 Hood Exhaust Exhaust air from laboratory hoods shall not be recirculated to other areas. Hood exhaust air meeting the same criteria as noted in Section 5.4.7.1 shall only be recirculated to the same work area where the hood operators have control of the hood work practices and can monitor the status of air cleaning. For most laboratories, recirculation of laboratory chemical hood air should be avoided. Laboratory chemical hood air usually contains significant amounts of materials with differing requirements for removal. Providing air-cleaning equipment to permit safe recirculation represents a high capital and operating cost, especially when redundancy and monitoring requirements are considered. Refer to the current version of NFPA 45 for its position on recirculation of laboratory chemical hood air when using flammables. 6 Commissioning and Routine Performance Testing 6.1 Performance specifications, tests, and instrumentation 6.1.1 Specifying Laboratory Fume Hood Performance Test specifications used for selecting a hood, in commissioning or in routine testing, shall refer to the applicable ANSI/ASHRAE 110 defined performance tests or to a test standard recognized to be equivalent. Specification and procurement of laboratory fume hoods shall be based on “As Manufactured” ANSI/ASHRAE 110 defined performance tests conducted on a representative hood (or prototype hood) that demonstrate Some “single purpose” laboratories might find it practical to recirculate laboratory chemical hood air; the requirements are similar to those in Section 5.3.7.1 criteria B. See Section 4.2 for more information. ANSI/ASHRAE 110 defines three different test scenarios, “As Manufactured, As Installed and As Used.” ”As Manufactured” tests, usually performed at the hood manufacturer’s facility, are conducted to determine whether the hood is adequately designed to provide 65 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 adequate hood containment. The performance tests to be witnessed, referenced or otherwise shall include • • • • • • • airflow visualization tests, auxiliary air velocity tests (if applicable,) cross drafts velocity tests, exhaust flow measurements, face velocity tests, hood static pressure measurement, and tracer gas containment tests The tests shall be conducted under constant volume conditions where exhaust and air supply flow are stable and exhibit no more than 5% variation from set-point. the required level of performance. In addition, the tests are conducted to determine appropriate operating specifications. It is only necessary to perform these tests on one hood for each unique hood design or mode. Credible catalog data on the fundamental performance and capabilities of a hood as it comes from the manufacturer are useful. The designer can then specify the unit with confidence that it will perform as per the manufacturer’s catalog data. It is recommended that the manufacturers’ tests be conducted or witnessed by the laboratory owner and design professional, and/or independent third party. The containment tests should be conducted over the range of possible operating configurations afforded by the hood design (i.e., sash position, baffle configurations, etc.) and at different target face velocities or exhaust flow rates to determine operational boundary conditions and hood limitations. Proper containment of a laboratory fume hood is affected by a number of factors including design of the hood, design of the laboratory, and design and operation of the ventilation systems. Controlled tests enable elimination of one variable: design of the hood. Therefore, performance problems encountered after installation can be attributed to other factors. Where possible, containment tests should be conducted according to methods described in the most recent ANSI/ASHRAE 110 standard equal to or more challenging than the standardized test. ANSI/ASHRAE 110 does not specify a face velocity. The standard yields a performance rating in the form of AM yy, AI yy, or AU yy where, AM means “as manufactured,” AI means “as installed,” and AU means “as used.” The symbol yy represents the average 5-minute concentration of tracer gas measured in the breathing zone of a mannequin used to simulate a hood user. The ANSI/ASHRAE 110 standard recommends a gas generation rate of 4 L/m. However, other generation rates (i.e., 1 L/m or 8 L/m) can be specified by the design professional or responsible person 66 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 (2.3) when deemed appropriate. Testing at different operating configurations will help to identify operational limitations or worst-case operating conditions. This information helps the design professional in their work and can then be relayed to the hood users to ensure proper work practices that minimize potential for exposure. 6.1.2 Performance Tests The following performance tests shall be conducted as indicated and as prescribed in the commissioning plan, laboratory ventilation management plan, or as directed by the responsible person. 6.1.2.1 Airflow Visualization Tests Airflow visualization tests shall be conducted as described in the ANSI/ASHRAE 110–1995, Method of Testing Performance of Laboratory Fume Hoods. The tests shall consist of small-volume generation and large-volume generation smoke to identify areas of reverse flow, stagnation zones, vortex regions, escape, and clearance. Visible escape beyond the plane of the sash when generated 6 in. (15.2 cm) into the hood shall constitute a failure during the performance test. Smoke tests are valuable because they indicate the direction of airflow through the opening and within the hood enclosure when the smoke plume is visible. Smoke particles are rapidly diluted to the extent where they may not be visible even though significant concentrations may exist in the invisible plume. Smoke tests should be used only as an indication of flow direction and absence of visible smoke should not be interpreted as an absence of smoke. Users of smoke should note that smoke tubes and candles can be caustic and detrimental to the user, test equipment, and apparatus in the hood. Attempts to improve airflow patterns should be attempted by adjusting the baffles and slot widths, redirecting room air currents, or changing the opening configuration by moving the sash panels. Closure of the sashes resulting in an opening smaller than the design opening may represent a “restricted use” condition. Often the most devastating area for reverse flow is behind the airfoil sill on bench-top-mounted hoods. An improperly designed airfoil or lack of an airfoil will cause reverse flow along the work surface within 6 in. (15.2 cm) of the sash plane. Reverse flow in this region is particularly worrisome as the wake zone that develops in front of a hood user could overlap with the reverse flow zone. Dynamic challenges should be evaluated. 67 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 6.1.2.2 Auxiliary Air Velocity Tests For auxiliary air hoods, the face velocity shall be measured with the auxiliary air turned off unless room pressurization would change significantly to affect exhaust flow. Where exhaust flow would be affected by turning off the auxiliary airflow, auxiliary air must be redirected from the hood opening so as not to interfere with flow into the hood while conducting the face velocity traverse. The velocity of the auxiliary air exiting the auxiliary air plenum shall be measured to determine the magnitude and distribution of air supplied above the hood opening. The average auxiliary air velocity shall be determined from the average of grid velocities measured across the plenum outlet. Hood face velocity is usually defined as air speed in a direction normal to the plane of the hood face opening. For auxiliary air hoods in standard operation, the directional component of the air velocity is not normal to the hood face plane. Accurate determination of the flow direction and derivation of the horizontal and vertical components of the velocity vector require very sophisticated instrumentation because of the low air speeds involved. Hence, measuring the hood’s face velocity with the auxiliary air shut off is an acceptable measure of hood exhaust volume, if turning off the auxiliary air does not upset the room air balance enough to reduce significantly the volume extracted by the hood exhaust system. Face velocity measurements should be determined with the supply air off or with special devices designed to eliminate the effect of the auxiliary air at the hood face. For example, supply air from the auxiliary air plenum can be temporarily redirected away from the sash opening by use of a portable baffle, hand held or otherwise placed beneath the supply air discharge without blocking off the supply air flow. NOTE: The 90% capture efficiency should be tested by material balance by introducing a tracer gas into the auxiliary airstream and sampling the hood exhaust. Flow volume and sampling should be in accordance with EPA methods 1, 2, and 17 (40 CFR 60, Appendix A) or by other methods mutually agreed on by all parties. The auxiliary air supply plenum located above the top of the hood face and external to the hood should be designed to distribute air across the width of the hood opening so as not to affect containment. Excessive auxiliary air velocity can interfere or overcome air flowing into the hood opening and cause escape from the hood. The downflow velocities should be measured approximately 6 in. (15.2 cm) above the bottom edge of the sash positioned at the design opening height. 68 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 6.1.2.3 Cross-Draft Velocity Tests Cross-draft velocity measurements shall be made with the sashes open and the velocity probe positioned at several locations near the hood opening to detect potentially interfering room air currents (cross drafts). Record measurement locations. Over a period of 10–30 sec., cross-draft velocities shall be recorded approximately 1 reading per second using a thermal anemometer with an accuracy of +5% at 50 fpm (0.25 m/s) or better. The average and maximum cross-draft velocities at each location shall be recorded and not be sufficient to cause escape from the hood. Cross draft velocities shall not be of such magnitude and direction as to negatively affect containment. More test locations may be required or can be useful for determining cross-draft velocities past the hood opening. Vertical and horizontal components of crossdraft velocities should be measured at each location. Increasing face velocity may not make the hood more resistant to cross drafts. However, increasing face velocity may: • Increase the required volume of room air supply and increase difficulties with ensuring proper room air distribution. • Increase exhaust of expensive conditioned air. Excessive cross-draft velocities (>50% of the average face velocity) have been demonstrated to significantly affect hood containment and should be identified and alleviated. Ideally, cross-draft velocities should be less than 30%. If the supply tracks the exhaust, measure the cross drafts at the maximum conditions. 6.1.2.4 Exhaust Flow Measurements The volumetric flow exhausted from a laboratory fume hood shall be determined by measuring the flow in the exhaust duct using industry-approved methods. See the current version of ACGIH®’s Industrial Ventilation: A Manual for Recommended Practice, or ANSI/ASHRAE 41.2–1987 (RA 92), for measuring flow. The hood exhaust flow should be adjusted to achieve the target average face velocity at the design opening and to achieve the specified flow with the sash closed. Typically, exhaust flow can be predicted from the area of the opening multiplied by the design face velocity. However, infiltration of air into the hood through openings other than the face may require approximately 5–10% more exhaust flow than calculated. The exhaust flow and variance from the calculated flow should be determined to enable proper specification of flows for design of the ventilation systems. Failure to determine the total exhaust flow required to achieve the desired average face velocity may result in under sizing of the exhaust system or improper specification of supply volume to achieve required lab pressurization or differential airflow. 69 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Calculation of exhaust flow from face velocity measurements multiplied by hood face area is not a measurement of exhaust flow and due to the reasons stated above, true exhaust flow can vary significantly from the calculated exhaust flow. In addition, the accuracy of face velocity measurements can affect the accuracy of the average face velocity used to calculate exhaust flow. Face velocities measured at the plane of the sash opening using hot-wire anemometers or pressure grid assemblies can be subject to significant error due to turbulence at the opening and direction of airflow over the probes where average face velocities could vary from actual by 5–20%. 6.1.2.5 Face Velocity Tests Once adequate performance has been established for a particular hood at a given benchmark face velocity using the methods described herein, that benchmark face velocity shall be used as a periodic check for continued performance as long as no substantive changes have occurred to the hood or other aspects that affect hood performance. Substantive changes include: changes in hood setup; hood face velocity control type, set point, range, and response time; exhaust system static pressure, control range and response time; the hood operating environment including lab/furniture geometry, supply air distribution patterns, and volume; and room pressure control range and response time. Face velocity measurements shall be made with the sash in the Design Sash Position. The Design Sash Position is the maximum opening or configuration allowed by user standards, SOPs, or the Chemical Hygiene Plan, whichever is applicable, and used in the design of the exhaust system to which the hood is connected. The face velocity of a combination sash is sometimes determined with the sash closed and the horizontal windows open. For "set-up" conditions, the determination of the actual face velocity may not be unique. The face velocity of combination sash hoods should identify the sash position where the tests were conducted. The sash position at which benchmark face velocity is measured shall be recorded with the face velocity measurement and reproduced each time measurements are taken. It is important to use the same sash position for successive periodic performance measurements. A decrease in the average face velocity below 90% of the benchmark velocity shall be corrected prior to continued hood use. This magnitude of decrease may impair performance. Face velocity increases exceeding 20% of the benchmark shall be corrected prior to continued use. An increase in individual hood average face velocity not exceeding 20% of the benchmark face velocity will probably not significantly alter hood performance and is acceptable with no corrective action. It should be noted, however, that there is an unnecessary increase in operating cost with increased face velocities. Increases exceeding 20% and the accompanying 70 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 increase in supply flow rates may degrade performance due to increased impingement and cross-draft velocities. In addition, an increase in face velocity at the measured hood may indicate a decrease in face velocity at other hoods in the exhaust systems. In constant volume systems, the face velocity will increase with reduced sash height. Although the face velocity could be three times or more than the design face velocity, the hood performance does not usually deteriorate because the hood opening is reduced (which often improves performance) and the lowered sash acts as a partial barrier. Supply and exhaust system capacities should be observed in the event of hood face velocity increases as volume shifting may occur, depriving other hoods of adequate airflow. Periodic dynamic testing should be performed when significant changes have occurred or to evaluate the response of a VAV system. The average face velocity alone is inadequate to describe hood performance. Face velocity is not a measure of containment but only the speed of air entering the face opening. Hood performance should be determined from tests of hood containment. Average face velocity should only be used as an indicator of proper system operation. Refer to section 3.3.1, for information about analysis of face velocity data and recommended criteria. The average face velocity shall be determined by the method described in the current version of ANSI/ASHRAE 110 Method of Testing Performance of Laboratory Fume Hoods. Face velocity measurements shall be made by dividing the hood opening into equal area grids with sides measuring no more than 12 in. (30.5 cm). The tip of the probe shall be positioned in the plane of the sash opening and fixed (not handheld) at the approximate center of each grid. Grid measurements around the perimeter The accuracy of face velocity measurements can be affected by numerous factors including instrument accuracy, measurement technique, hood aerodynamics, room air conditions (cross drafts), and exhaust flow stability. Average face velocities and grid velocities can be significantly affected by turbulence (temporal variation) and direction through the opening (spatial variation). Multiple readings taken over time at each grid location are recommended to provide more accurate velocity measurements. Cross drafts can also bias face velocity data by creating turbulence at the opening and variations in face velocity readings. 71 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 of the hood opening shall be made at a distance of approximately 6 in. (15.2 cm) from the top, bottom, and sides of the opening enclosure. Multiple readings at each grid point will help determine more accurate average face velocities when turbulent air is present at the hood opening. Multiple readings can be acquired with the use of time constants for meters so equipped or use of a data logger or data acquisition system attached to a computer. The average face velocity shall be the average of the grid velocity measurements. Manufacturers have been defining the sash plane somewhat subjectively, thus making it difficult for users to compare face velocity data and AM containment test results. This definition from ANSI/ASHRAE 110 aims to lessen the subjectivity in AM as well as AI and AU testing. Each grid velocity shall be the average of at least 10 measurements made over at least 10 seconds. The plane of the sash shall be defined as the exterior surface of the outer most glass panel. 6.1.2.6 Hood Static Pressure Measurements The hood static pressure shall be measured above the outlet collar of the hood at the flows required to achieve the design average face velocity. For test method, refer to current version of ANSI/ASHRAE 41.3. Hood static pressure is a measure of the resistance imposed on the exhaust system by the hood. Determination of hood static pressure is required to ensure proper system design. Typical hood static pressures range from 0.1 to 0.75 in.wg (25 to 187 Pa) at face velocities between 80 to 120 fpm (0.41 to 0.61 m/s). However, the hood static pressure will depend on the hood design and exhaust flow. 6.1.2.7 Tracer Gas Containment Tests The tracer gas containment tests shall be conducted as described in the ANSI/ASHRAE 110–1995, Method of Testing Performance of Laboratory Fume Hoods or by a test recognized to be equivalent. A control level for 5-minute average tests at each location conducted at a generation rate of 4 L/m shall be no greater than 0.05 ppm for "as manufactured” tests and 0.10 ppm for “as installed” (AM 0.05, AI 0.1). Escape more than the control levels stated above shall be acceptable at the discretion of the design professional in agreement with the responsible person (2.4.2). The “as used” 0.10 ppm level or more is at the discretion of the responsible person (2.3). Tracer gas tests enable the ability to quantify the potential for escape from a laboratory fume hood. The test data need to be made available by the manufacturer for each specific model and type of hood so a potential buyer can verify proper containment or compare one manufacturer’s hood containment against another. Values for control level may not be suitable for establishing hood safety, as the tracer gas test methods may not adequately simulate actual material use, risk, or generation characteristics. In addition, the tracer gas test does not simulate a live operator, who may increase potential for escape due to operator size, movements near the hood opening, or improper hood use. 72 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Hood containment should be evaluated at different mannequin heights to represent workers of different height. AM 0.05 can be achieved with a properly designed laboratory fume hood. It should not be implied that this exposure level is safe. Safe exposure levels are application specific and should be evaluated by properly trained personnel (SEFA 1-2002). 6.1.3 Test Instrumentation All test instrumentation utilized for the tests prescribed throughout this section shall be in good working order and shall have been factory calibrated within 1 year of the date of use. (See 8.6.1, Air Velocity, Air Pressure, Temperature and Humidity Instruments) 6.2 Commissioning of Laboratory Ventilation Systems 6.2.1 Commissioning Process All newly installed, renovated, or moved hoods shall be commissioned to ensure proper operation prior to use by laboratory personnel. 6.2.2 Commissioning tests are conducted to ensure that laboratory ventilation systems operate according to design specifications and are capable of meeting control objectives under resulting operating conditions. The extent of the commissioning process depends on the complexity of the systems along with the anticipated risk associated with work to be conducted in the laboratory. Commissioning Authority The commissioning process shall be overseen by a responsible person or commissioning authority. The commissioning authority should be someone who represents the interests of the system owner and should be knowledgeable in the design and operation of laboratory ventilation systems. In addition, the commissioning authority should be experienced with collection and analysis of test data. The commissioning authority may develop the commissioning plan in conjunction with information provided by potential equipment suppliers and contractors, owner personnel, and project design professionals. A commissioning team consisting of personnel directly involved in the design, installation, and use of the new 73 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 or renovated systems should assist the commissioning authority. A commissioning team might include: • • • • • • • • • 6.2.3 Chemical Hygiene Officer Commissioning Consultant; Health and Safety Personnel; Hood Performance Tester; HVAC Controls Expert; HVAC Design Engineers; Laboratory Managers; Maintenance Engineers, and Principal Researchers or Hood Users; TAB (Testing, Adjusting and Air Balance) Leader. Commissioning Plan A written commissioning plan shall accompany design documents and be approved by the commissioning authority in advance of construction activities. The commissioning plan shall be available to all potential suppliers and contractors prior to bid along with the other project documents. The conceptual design phase of the project generally includes a statement of performance objective and criteria for establishing proper operation of proposed systems. The statement of performance provides an operational definition of performance that can be measured after installation and startup to validate or verify proper operation. The commissioning plan describes the tests that will be conducted to verify proper operation of the systems. A commissioning plan shall address operation of the entire ventilation system where the hoods, laboratories, and associated exhaust and air supply ventilation systems are considered subsystems. The plan shall include written procedures to verify or validate proper operation of all system components and include: • Laboratory Fume Hood Specification and Performance Tests • Preoccupancy Hood and Ventilation System Commissioning Tests • Preoccupancy Laboratory Commissioning Tests For example, an operational definition for proper performance of a new hood system might include: the new hood operated with the vertical sliding sash at a height of 28 in. (71.1 cm) must have an average face velocity between 80–120 fpm (0.41 to 0.61 m/s) and provide containment below a control level of AU 0.1 ppm as determined by methods described in the ANSI/ASHRAE 110–1995, Method of Testing Performance of Laboratory Fume Hoods. A laboratory fume hood system includes all associated subsystems such as the hoods, ducts, dampers, automated controls, filtration, fan, motor, and exhaust stacks. In laboratories, the air supply system is considered part of the hood system when operation can affect hood performance. 74 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 It is imperative that the commissioning plan be completed and that is part of the project design documents. It should not be developed after the bid process or signing of contracts because it may substantially impact the individual contractor laboratory costs and scheduling. If it is developed after the bid date, whatever requirements it imposes on a contractor could be contested as being invalid since it was not available at the time of bid. Design changes made subsequent to construction must be reflected in a revised commissioning plan. 6.2.4 Commissioning Documentation Preliminary and final commissioning documents shall be issued to the appropriate party(s) by the Commissioning Authority. The documents should detail the status of the ventilation systems relative to maintaining a safe facility environment. The documents shall include: The document should clearly indicate, based upon the ventilation system functionality, which laboratory rooms and equipment (i.e., chemical laboratory hoods, biosafety cabinets, etc.) are ready for safe use, any areas or equipment that are not safe for use or occupancy, and other safety-related ventilation system details. • • • • Commissioning Test Data; Copy of Test and Balance Report; Design Flow Specifications; Laboratory and System Drawings for Final System Design; • List of Ventilation System Deficiencies uncovered and the details of how (and if) they were satisfactorily resolved. Operational deficiencies and other problems uncovered by the commissioning process shall be communicated to the responsible party (i.e., installer, subcontractor, etc.) for prompt correction. 6.3 Commissioning Fume Hoods and Different Types of Systems 6.3.1 Laboratory Fume Hoods If practical, the exhaust flowrate from hoods shall be tested by measuring the flow in the duct by the hood throat suction method or by flow meter. Unreasonable delays or unsatisfactory follow-up should be communicated to the owner as well as any contractors in the tier to which this subcontractor is responsible. See the current edition of the ACGIH®– Industrial Ventilation: A Manual of Recommended Practice. If a flowmeter is used, care should be taken to ensure that the element has not been compromised by chemical action or deposition of solids. 75 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 If flow measurement in the duct is not practical, velocity at the hood face or opening shall be measured at a sufficient number of points to obtain a realistic average velocity, and multiplied by the open area in the plane of the velocity measurements to obtain the flowrate. NOTE: Fine dust, for example, might adhere to the throat of a venturi meter and change its inside dimension, which is critical to the measurement. If the flowrate is more than 10% different from design, corrective action shall be taken 6.3.2 Single Hood CAV Systems Commissioning tests on single hood, constant air volume (CAV) systems shall consist of: • • • • Fan Performance Tests; Exhaust Duct Measurements; Hood Performance Tests; and Hood Monitor Calibration. Ensuring proper operation of a laboratory fume hood requires proper design, installation, and operation of all components of the exhaust systems and many times the air supply systems as well. Using a “top-down” approach, the fan should be adjusted to exhaust the specified volume of air. Fan Performance Tests shall include measurement of fan speed, fan static pressure, motor speed, and amp draw. The exhaust flow should be measured in the exhaust duct according the methods described in the current version of ANSI/ASHRAE 41.2 or as described above. Exhaust duct measurements shall consist of exhaust flow measurement and hood static pressure measurement. Fan performance and exhaust measurements should be conducted by a certified Test-and-Balance firm. Hood performance tests shall consist of tests described in Section 6.1.2. The hood monitor shall be calibrated and adjusted after hood performance has been determined as satisfactory. Safe operating points shall be clearly identified for the hood user. 6.3.3 Multiple Hood CAV Systems Commissioning of multiple hood, constant air volume systems shall include: • Fan Performance Tests; • Verification of proper test, adjustment, and balance of branch exhaust flow and static pressures (exhaust flow and static pressure for each branch shall be recorded after final balancing is complete); Multiple hood systems should be balanced using an iterative approach where dampers or controllers are adjusted until flow through each hood is in accordance with design specifications. Hood performance tests should follow completion of system balancing, measurement of branch exhaust flows, and branch static pressures. 76 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • Hood Performance tests as described above in Sections 6.1.2; and • Hood and System Monitor Calibration 6.3.4 Determine that sash position of one hood does not affect flow through another hood. VAV Laboratory Fume Hood Systems VAV hood systems shall be commissioned prior to use by laboratory personnel to ensure that all system components function properly and the system operates as designed under all anticipated operating modes (defined under the VAV section). Performance of laboratory fume hoods connected to variable air volume systems (VAV) can be affected by numerous factors associated with proper design, calibration, and tuning of the control systems. It is imperative that all components of the VAV system be in proper operating condition to ensure proper hood performance. The commissioning procedures for VAV systems shall include: Commissioning tests should be specified to verify that the VAV systems operate according to design specifications. Some of the data, such as sensor calibrations, can be acquired through the process of installing the VAV controls or through the Testing, Adjustment and Air Balance process (TAB). • Verification of VAV Sensor Calibration; • VAV Hood Performance Tests; • VAV Laboratory and Ventilation System Tests; and • Verification of System Diversity. Documentation collected outside the commissioning tests, such as manufacturer’s tests on system components, should be available in advance of commissioning tests for comparison with test data and inclusion with final commissioning documents. 6.3.4.1 VAV Sensor Calibration VAV sensors shall be capable of accurate measurement and control within 10% of actual at the design maximum and minimum flow conditions. Numerous sensors can be employed in a typical VAV laboratory fume hood systems such as sash position sensors and room differential pressure sensors, to name a few. The accuracy of the sensors depends on proper methods to measure the physical parameters and ability to adjust calibration. Sensors that report inaccurate information will not only be misleading when monitoring system operation but may result in unsafe hood and laboratory conditions. Part of the process of installing VAV controls and balancing system airflows should involve calibration of sensors and documentation of it. At a minimum, commissioning tests should test a representative sample of sensors to verify accurate reporting of information. 77 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 6.3.4.2 VAV Hood Performance Tests In addition to hood performance tests described for evaluation of CAV hood systems, commissioning tests on VAV hood systems shall include measurement of flow or face velocities at different sash configurations and VAV Response and Stability tests. Flow or face velocity measurements shall be conducted at a minimum of two separate sash configurations. In the majority of VAV hood systems, the purpose of the VAV control system is to adjust airflows to compensate for changes in sash configurations or system operating mode (occupied/unoccupied, night setback, etc.). The VAV control system must be capable of quick and precise adjustment of flows without experiencing major overshoot or undershoot (10% of steady-state value). VAV Response and Stability tests shall include continuous measurements and recording of flow while opening and closing the sashes for each hood (calibrated flow sensors or measurement of slot velocity within the hood can be used as an indicator of flow). Commissioning tests should be used to verify that VAV systems provide satisfactory control of airflows in response to sash movement or changes in operating modes. VAV Response shall be sufficient to increase or decrease flow within 90% of the target flow or face velocity in a manner that does not increase potential for escape. A response time of < 3 sec. after the completion of the sash movement is considered acceptable for most operations. Faster response times may improve hood containment following the sash movement. VAV Stability shall be sufficient to prevent flow variations in excess of 10% from design at each sash configuration or operating mode. 6.3.4.3 VAV Ventilation System Tests The VAV hood controls shall provide stable control of flow in the exhaust and supply ducts and variation of flow must not exceed 10% from design at each sash configuration or operating mode. On a plenum system determine what happens to exhaust flow when one fan is not operating. 6.3.4.4 Verification of System Diversity System diversity shall be verified prior to use of laboratory fume hoods. The tests shall be designed to verify that users will be alerted when system capacity is exceeded and unsafe conditions may exist. 78 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 6.3.5 Laboratory Airflow Verification Tests Tests to verify and commission the laboratory shall consist of: • Air supply measurements; • General room exhaust flow measurement (if applicable); • Room differential pressure measurement; and • Calculation of the difference between total area (laboratory, zone, etc.) supply and total exhaust. All ventilation system alarm and monitoring provisions associated with occupant safety shall be verified for proper functionality. The laboratory commissioning tests are used to ensure proper air supply and exhaust for each laboratory or zone. TAB data once verified can be substituted where appropriate. This includes local monitoring provisions for such items as hood airflow or room differential pressure as well as remote and central monitoring provisions for such parameters. 6.3.5.1 CAV Laboratory Room Tests These tests shall ensure that the ventilation system design airflow is being maintained within the allowable tolerance in: • All hood exhausts; • All other bench-top and equipment exhaust provisions that may be present; • The room general exhaust if present; • The room supply; and • Room air cross currents at the hood face opening. If a specific room differential pressure (dP) has been specified, the dP shall be measured to ensure that it is within its allowable range. If a room differential airflow is specified, actual room differential airflow shall be determined to ensure that is within allowable maximum and minimum limits and in the proper direction. If the room has more than one ventilation control mode (i.e., occupied/unoccupied, etc.), each individual mode shall be enabled and applicable parameters (i.e., room supply, room total exhaust, etc.) shall be performed for each separate mode. 79 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Room ambient conditions (temperature, humidity, air currents, etc.) shall also be measured to ensure they are being maintained under the conditions specified. 6.3.5.2 VAV Laboratory Room Tests These tests shall ensure proper performance of the VAV ventilation system and its associated controls such that: • The room general exhaust provides the specified range of airflow. • The room supply provides the specified range of airflow. • Room air cross currents at the laboratory hood face opening are within limits. If a specified room dP has been specified, the dP shall be measured to ensure that it is being controlled within its allowable range with all doors closed and at minimum and maximum room exhaust airflow. If a room differential airflow is specified, actual room differential airflow shall be determined to ensure that it is within allowable maximum and minimum limits and direction at minimum and maximum room exhaust airflow. If the room has more than one ventilation control mode (i.e., occupied/unoccupied, etc.) conditions shall be evaluated for each mode. Room ambient conditions (temperature, humidity, air currents, etc.) shall also be measured to ensure they are being maintained under the conditions specified. The VAV systems shall be capable of maintaining the offset flow required between exhaust and supply to achieve the desired area pressurization within the desired time specified. For most operations, 10 seconds will be an acceptable time to achieve the desired area pressurization but a Hazard Evaluation should be conducted to determine the acceptable time. 80 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 6.4 Ongoing or Routine Hood and System Tests Routine performance tests shall be conducted at least annually or whenever a significant change has been made to the operational characteristics of the hood system. A hood that is found to be operating with an average face velocity more than 10% below the designated average face velocity shall be labeled as out of service or restricted use and corrective actions shall be taken to increase flow. ANSI/ASHRAE 110–1995 may be used in the laboratory as an accepted test with specific values for the control levels (and the release rate if you depart from the standard). It also may be used for routine periodic testing, but it is somewhat expensive and other less rigorous tests may be adequate if conditions have not changed since commissioning tests. In addition to the hood tests, periodic testing at a minimum of 1-year intervals should ensure that: • All other room exhaust provisions are within specifications; • Room differential pressure is within specifications (if applicable); • Room differential airflow is within specifications (if applicable). Each hood shall be posted with a notice giving the date of the routine performance test, and the measured average face velocity. If it is taken out of service it shall be posted with a restricted use or out- of-service notice. The restricted use notice shall state the requisite precautions concerning the type of materials permitted or prohibited for use in the hood. Periodic tests concerning face velocity or hood exhaust volume are valid indications of hood operation provided no changes have been made in that hood structure, supply air distribution, or other factors listed above that affect hood performance. The hood sash should not be lowered below design position to increase face velocity during routine tests. A decrease in face velocity at the design opening may be indicative of a problem with operation of the exhaust system. 81 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 7 Work Practices and Training 7.1 General Requirements The user shall establish work practices that reduce emissions and employee exposures. The laboratory’s Chemical Hygiene Plan should discuss proper work practices. The user shall not modify the interior or exterior components of the hood without the approval of the Chemical Hygiene Officer, Responsible Person, or other appropriate authority in the organization. The following list concerns only those work practices that relate directly to hood performance and applies only when hazardous materials are to be used in the hood. Many work practices affect the overall safety and health in the laboratory. • The user shall not lean into the hood so that his/her head is inside the plane of the hood, as defined by the sash, without adequate respiratory and personal protection. • Equipment and materials shall not be placed in the hood so that they block the slots or otherwise interfere with the smooth flow of air into the hood. • All work shall be conducted at least 6 in. (15.24 cm) behind the plane of the sash (hood face). • The horizontal sash or panels shall not be removed. • The hood shall not be operated without the back baffles in place. • Flammable liquids shall not be stored permanently in the hood or the cabinet under the hood unless that cabinet meets the requirements the current editions of NFPA 30 and NFPA 45 for flammable liquid storage. During setup or hood maintenance, this provision is not necessary, provided there are no sources of chemicals in the hood and the hood is decontaminated. When large equipment must be placed in a laboratory chemical hood, placing the equipment on a stand to allow air to flow under the stand can reduce the significance of any airflow disturbance. Marking the work surface with a tape or other means, to indicate the 6 in. (15.24 cm) line, will assist the user in identifying the limits of usable space. In some cases, while the hood is empty, the sash could be removed for setup procedures. Although the storage of acids does not pose the same hazard as flammable solvents, the storage of acids under the hood should be in acid-resistant cabinets. Because of the high hazard associated with the storage of chemicals in front of the user at the hood, some laboratories prohibit the storage of flammable materials under the hood. Individual policies are often site specific; hence, the Chemical Hygiene Officer should always be consulted. In some laboratory design, the normal sash position is not full open. When the sash is raised above the design level, the hood could lose adequate control. 82 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • The sash or panels shall be closed to the maximum position possible while still allowing comfortable working conditions. • Hood users shall be trained to close the sash or panels when the hood is not in use. • The hood user shall not operate with the sashes opened beyond the design opening. • Pedestrian traffic shall be restricted near operating hoods. • Rapid movement within the hood shall be discouraged. • The hood shall not be operated unless verified it is working. 7.2 When a person walks past a laboratory chemical hood he or she sets up a wake that can aspirate contaminants from the laboratory chemical hood. Proper location of the hood and administrative controls are required to minimize this potential hazard. Posting Each hood shall be posted with a notice giving the date of the last periodic field test. If the hood failed the performance test, it shall be taken out of service until repaired, or posted with a restricted use notice. The intent is to ensure that those using the hood know its current status and where to get help or further information. The notice shall state the partially closed sash position necessary for safe/normal operation and any other precaution concerning the type of work and materials permitted or prohibited. Other information that should be posted may include flowrates, fan numbers, an indication that the system is VAV or less than 100% diversity and an emergency phone number. 7.3 Operating Conditions Hoods shall be in operation whenever hazardous volatile materials are being used or stored inside. 7.4 A hood that is more than 10% below the standard operating conditions, either because of inadequate face velocity, or poor distribution of the face velocity should be immediately reported to the responsible safety person. The hood should not be used unless specific conditions for safe use can be identified and posted such as its maximum sash opening. Hoods should only be turned off when all materials are removed from the interior and only if the hood does not provide general exhaust ventilation to the space. Training Hood users shall be trained in the proper operation and use of a hood. 83 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 8 Preventive Maintenance Inspection and maintenance shall follow a Preventive Maintenance (PM) Program developed by the user. PM programs should be “preventive” in nature. The written PM Program should identify potential hazards and problems associated with laboratory operations and designate appropriate PM procedures to minimize such hazards and problems. This could include, for example, routine inspection of fan belts to ensure that hood exhaust ventilation fans are turning at the designed speeds, that hoods are being cleaned to minimize buildup of hazardous chemicals in the hoods, evidence of tampering with performance equipment or blast gates, and so forth. The written program should identify standard operating procedures to be followed during PM activities. The “responsible person” identified in Section 2.3 should be involved in the development and operation of the PM program. Preventive maintenance shall be performed on a regularly scheduled basis. 8.1 Operations During Maintenance Shutdown Operations served by equipment being shut down for inspection or maintenance shall be safely discontinued and secured during such maintenance. “Secured” condition will vary from case to case. It might consist of ceasing operation, or requiring removal from the premises of all flammable and highly toxic materials. Lock-out/tag-out procedures shall be implemented. All ventilation equipment should be de-energized and labeled as such with appropriate signage before starting any repair work. Laboratory workers shall be notified in advance of inspection and maintenance operations. 8.2 Housekeeping Before and After Maintenance All toxic or otherwise dangerous materials on or in the vicinity of the subject equipment shall be removed or cleaned up before maintenance. Any hazardous materials and any other debris shall be cleaned up before operations resume. If possible, equipment to be removed should be decontaminated. If the maintenance activities involve contact with potentially contaminated parts of the system, these parts should be evaluated first by appropriate methods. 84 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 8.3 Safety for Maintenance Personnel Maintenance personnel shall be trained and required to use appropriate PPE (such as respirators, goggles or faceshields, gloves, and protective clothing) during parts of the work involving potential hazard. A procedure shall be established to notify hood users before any maintenance is to be performed so work in the hood can be halted during maintenance. 8.4 Work Permits and Other Communications A written work permit system or other equally effective means of communication shall be established whenever any PM or unscheduled maintenance; There may be situations in the United States where OSHA’s hazardous energy control standard (29 CFR1910.147) conceivably be applied to the situations being addressed in this section. • could affect the safety of maintenance personnel, hood users or others • could jeopardize the integrity of the experiments/procedures/etc., underway in the affected hood(s.) Such system(s) shall be designed to suit the circumstances and address the following: • a means to communicate when systems are returned to normal operations, • oversight by the responsible person as defined in this standard, • signed or otherwise endorsed and communicated by the person(s) to do the work, his/her supervisor, and communicated to any and all hood users and others affected by the work, • the nature of the work and the health and safety precautions, and Allowable variance from design conditions, or conditions determined otherwise satisfactory, shall be: • For air velocity, +10%; • For ventilation air pressure or differential pressure, +20%; For pneumatic control system air pressure, <5%; and • For electronic control system, +2% of fullscale values. 85 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • the date(s), time(s) and affected location(s) of the work. Records shall be maintained in accordance with the organizations records retention policy. 8.5 Records Records shall be maintained for all inspections and maintenance. If testing involves quantitative values (such as hood throat suction) the observed values shall be recorded. Inspection forms designed for the several categories of testing shall be provided and shall include the normal values for the parameters tested. 8.6 Testing and Monitoring Instruments 8.6.1 Air Velocity, Air Pressure, Temperature and Humidity Measurements Pressure instrumentation and measurement shall be in compliance with ANSI/ASHRAE 41.3–1989. Temperature instruments and measurement techniques shall be in compliance with ANSI/ASHRAE 41.1–1986 (RA 01). All Velocity Accuracy Below 100 fpm (0.51 m/s) 5 fpm (0.025 m/s) 100 fpm (0.51 m/s) and higher 5% of signal Pressure Accuracy 0.1 in.wg (25 Pa) 0% of signal Between 0.1 in. wg (25 Pa) and 0.5 in. wg (125 Pa) Interpolate linearly 0.5 in.wg (125 Pa) and higher Records should be kept for at least 1 year or until the next required test is performed. Instruments of a “primary standard” nature (i.e., standard pitot tubes, flow tube manometers, draft gauges, etc.) – if used with fluids for which they are designed and tested for leaks – require no further calibration. Performance measurement equipment can be used to determine many different system changes requiring attention (e.g., exhaust filtration loading, damper changes, fan operation, etc.) and provides real-time indication of system performance. Pressure indicating manometers can lose indicating fluids due to leaks or evaporation. These devices should be checked on a regular basis. Fluids should be refilled and the device re-leveled as needed. 5% of signal 86 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 instruments using electrical, electronic, or mechanical components shall be calibrated no longer than 12 months before use or after any possible damage (including impacts with no apparent damage) since the last calibration. The accuracy of a scale used for a given parameter shall meet the following requirements: Pitot-static tube measurements shall be in accordance with ANSI/ASHRAE’s Method of Test Measurement of Flow of Gas, 41.7–1984 (RA 00). Inclined manometers shall be selected so that the nominal value of the measured parameter is at least 5% of full scale. U-tube manometers shall not be used for pressures less than 0.5 in.wg (125 Pa). Pitot tubes other than standard shall be calibrated. Temperature measurement instrumentation shall have an accuracy of +0.5°F or +1°C over the entire measurement range. Humidity measurement instrumentation shall have an accuracy of +3.0% relative humidity over the entire measurement range. 8.6.2 Air Contaminant Monitors Air contaminant monitors shall be tested at least monthly or more often, if experience or manufacturer’s recommendations so indicate. Such testing shall include the sensing element, zero drift, and actuation of signals, alarms, or controls. Continuous air monitors shall be calibrated per manufacturer’s specifications or more frequently if experience dictates. 8.6.3 Tolerance of Test Results Allowable variance from design conditions, or conditions determined otherwise satisfactory, shall be: • For air velocity, +10%; • For ventilation air pressure or differential pressure, +20%; For pneumatic control system air pressure, <5%; and • For electronic control system, +2% of fullscale values. 87 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 8.6.4 Other Test Instruments Other instruments (such as voltmeters and tachometers) shall be checked for function and accuracy against a “known source” before use and follow manufacturer’s recommendation, when provided, for periodic calibration. 8.7 Monitoring Fans, Motors, and Drives 8.7.1 Visual Inspection Fans, blowers, drive mechanisms, and stack systems shall be visually checked at least semi-annually. Key problematic observations are abnormal noise or vibration, bearing noise, excessive temperature of motors, lubricant leaks, etc. Inspections should focus on key problematic issues with the fans, blowers, and drive apparatus looking for abnormal noise, vibration, bearing noise, excessive temperature, high amperage of motors, and signs such as lubricant leaks, etc. 8.7.2 V-belt Drives V-belt drives on non-redundant fans serving exposure control devices without performance monitoring equipment shall be stopped and inspected monthly for belt tension, signs of belt wear, sheave wear, checking, or excessive amperage pull on the motor. Stack inspection should include the following: • Ensuring that any tags, labels, etc., used to associate the stack and hood device(s) are legible, • Support structure such as guide wires, • That conditions surrounding the discharge haven’t changed resulting in re-entrainment of exhaust, and • The stack discharge velocity is still in accordance with design. Belt guard shall be reinstalled after any removal. This will probably require removing the belt guard. 8.7.3 Lubrication Blowers, drives, and other necessary components shall be lubricated at intervals and with lubricants recommended by the manufacturer. 8.8 The use of performance monitoring equipment (See Section 8.10) allows for maintenance as required rather than on any time-based interval. Critical Service Spares The ventilation system management plan shall address the need of providing for critical service issues and keeping spare parts on hand. Lead time for parts should be considered such that periodic inspection schedules are not affected. Maintenance supplies and spares should be planned considering factors such as: • Availability of spares or replacements, • Economic cost of facility being out of service, and • Potential health or safety risk of breakdown. 88 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 8.9 Critical Service Instrumentation All critical service instrumentation shall have contingency plans in place. For critical equipment of 100 horsepower (74.6 kW) or larger, consideration should be given to providing temperature and vibration sensors to give early warning of problems. Key instrumentation should include at least one spare performance monitoring device. 8.10 Performance Monitoring Equipment All hoods and exposure control devices shall be equipped with a flow indicator, flow alarm, or face velocity alarm indicator as applicable to alert users to improper exhaust flow. When these devices are marked and labeled so the hood operator can easily interpret the equipment reading and know when to shut down a hood and request maintenance. 9 Air Cleaning 9.1 Supply Air Cleaning Performance monitoring equipment allows the hood user to check and monitor the reliability of the hood system compared to normal. The performance equipment should be on an annual pm. The performance equipment should be calibrated and relabeled so the hood operator can readily understand the findings. Laboratory air supply systems seldom require air cleaning for health and safety reasons. Supply air cleaning usually is provided, however, for technical reasons, usually to reduce the contamination from atmospheric dust and dirt. See ASHRAE 1999 Handbook – HVAC Applications. 9.2 Exhaust Air Cleaning Air-cleaning systems for laboratory exhaust systems, where required, shall be designed or specified by a responsible person to ensure that air-cleaning systems will meet the performance criteria necessary for regulatory compliance. See the current version of ASHRAE Handbook—Fundamentals. Exhaust air might require cleaning for one or more reasons (See Sections 4.2 and 5.3). Air-cleaning equipment covers a wide range of physical and chemical mechanisms beyond the scope of this standard and its proper application is, in general, not included. Air-cleaning performance monitoring is typically limited for many hazardous materials. Chemical specific detectors located downstream of adsorption media, pressure drop indicators for particulate filters, and/or periodic stack sampling for contaminant emissions may be required to monitor for regulatory compliance. 89 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 9.3 Filtration for Recirculation Air-cleaning systems for recirculating general exhaust or hood exhaust from laboratories shall meet the design and installation requirements in the current version of ANSI/AIHA® Z9.7. Recirculation of process air shall be returned to the same room where the process is located and control of the process is supervised. In practical terms, recirculation of exhaust air usually is economical only if the air needs to be cleaned of low concentrations of: • Particulate material that can be removed by static (i.e., not self-cleaning) filters; • Gases and vapors that can be removed efficiently by adsorption media. Filter installations shall be tested for leaks and have all leaks repaired or the filter replaced before use. The flow rate through the filters shall be maintained at design specifications not to exceed 100% of the rated flow capacity of the filters. 9.3.1 Particulates Air-cleaning filtration systems for recirculating exhaust air contaminated with toxic particulates shall be filtered through a particulate filtration system specified following the standard performance and design criteria of the ASHRAE Systems and Equipment to meet the objectives described in General Requirements within the Laboratory Ventilation Management section of this standard. The properties and behavior of airborne particulates cover a wide range and may include dusts, fumes, mists, smoke, etc. Special caution should be taken when utilizing recirculating particulate air-cleaning systems when condensation or evaporation of hazardous particulate materials can take place in the air stream. See the Institute of Environmental Sciences Recommended Practice for Laminar Flow Clean Air Devices. The filter assembly should be provided with a damper and control that: • Indicate the static pressure differential separately across the primary and secondary filters and the pressure differential across both filters and the damper; • Actuate a damper motor (or allow manual activation) to open the damper from an initial partially closed position when filters are clean to a fullopen position when filters are fully loaded; and • Actuate a signal or alarm when the pressure drop across either the primary or secondary filter reaches 0.01 in.wg (2.5 Pa) more than the ratedloaded pressure drop. 90 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Also see the ASHRAE 2001 Handbook Fundamentals for additional information on the theory and need for application of air cleaning equipment for the emission control of hazardous materials from work operations. 9.3.2 Gases and Vapors Adsorption or other filtration media used for the collection or retention of gases and vapors shall be specified for a limited use. Specific hazardous materials to be collected, airflow rate, temperature, and other relevant physical properties of the system shall be incorporated into the selection of filtration media. The intent of this section is to specify the need to have a method for detecting filter breakthrough before a hazardous contaminant is released to the laboratory environment. Any method that provides early, accurate, and reproducible detection for the contaminants present is acceptable. Activated carbon and other adsorption media are available in a number of configurations as filter housings. Media may be sprayed onto another filtration media as a thin coat or be packed into thin panels less than 2 in. (5.1 cm) in depth. Also, deep- bed filters, typically cylindrical in shape and up to several feet in diameter and length, are utilized to provide adequate retention time for gas adsorption. A reliable and adequately sensitive monitoring system shall be utilized to indicate adsorbent breakthrough. The sensitivity of the monitoring system shall be a predetermined fraction of the TLV® or appropriate health standard of the contaminant being adsorbed but shall not be more than 25% of the TLV®. The breakthrough time of the contaminant, before the effluent reaches no more than 50% of the TLV®, shall be sufficient, based upon system capacity design to allow a work operation shut down or parallel filter switch-over, thus proving a fresh filter. For toxic gases and vapors, the filtration system shall be designed and sized for capacity to ensure adequate collection and retention for a worst-case scenario when in the event of a spill or other major release, adequate warning is provided for personnel to stop work or enact other emergency procedures. An important characteristic of adsorption media is that upstream layers perform the adsorption function; with the result that breakthrough of unadsorbed gas occurs rather quickly without gradual reduction of adsorption efficiency. Prediction of breakthrough in deep beds can be accomplished by periodic withdrawal of media samples from incremental depths of the bed, but this is impractical in the shallow beds used in panels or in smaller cylindrical cartridges. Saturation of the active adsorption sites occurs progressively through the layer of carbon and depends on the burden of adsorbate, which typically is variable. Therefore, breakthrough of contaminant on the downstream side of the carbon layer is difficult to predict. Other gas and vapor filtration systems use absorbents such as potassium permanganate that are impregnated onto the media that transform, oxidize, or otherwise treat the specific air contaminant to remove the hazardous material from the air stream. A particulate filter should be located upstream of the adsorption filter to serve as a pre filter to prevent particulate loading on the adsorption filter. 91 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 9.3.3 Handling Contaminated Filters When required, contaminated filters shall be unloaded from the air-cleaning system following safe work practices to avoid exposing personnel to hazardous conditions, to avoid contamination of downstream ductwork and to ensure proper containment of the filters for final disposal. Airflow through the filter housing shall be shut down during filter change-out. 9.4 Testing and Monitoring 9.4.1 Recirculation – Particulate Filter Systems Recirculation air filters shall be inspected and tested as per Section 9.3.1 before initial use and then at least once per year. Inspections and testing shall be done after any system maintenance or modification that disturbs the filter housing, filter seals, and/or filter media. 9.4.2 The Hazard Assessment should include recommended work practices and procedures to conduct filter change-outs when filters have been exposed to hazardous materials. Hazardous waste disposal requirements should be identified where needed. Care should be taken during filter replacement to minimize the release of hazardous materials from the filters. The most common and recommended practice employs the use of bag-in/bag-out systems. Another approach involving the careful introduction of encapsulants upstream of the filter just prior to shut down and filter changes has been described in various documents. An example is CAG-005–2007 Servicing Hazardous Drug Compounding Primary Engineering Controls. All air filters should be provided with differential pressure gauges. Gauges should be read at intervals of 1 week (or at other intervals, based on experience) and inspected visually at the same time. If the pressure differential equals or exceeds the rated maximum, the filters should be changed at the first opportunity. Recirculation – Adsorption and Absorption Filter Systems Recirculation systems that utilize activated carbon adsorption or chemical absorption filters shall be tested as per Section 9.3.2 at intervals no longer than 1 month initially and then based on experience with the particular installation and a schedule shall be prepared. 9.4.3 Air Pollution Control Equipment Air pollution control equipment shall be inspected visually at intervals no longer than 1 week and, if necessary, at shorter intervals. Specific tests and repairs shall be in accordance with the manufacturer’s recommendations or in compliance with applicable regulations. The variety of generic types of pollution control equipment, combined with the many different configurations on the market, make it inappropriate to set forth specific requirements. 92 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 APPENDIX 1 Definitions, Terms, and Units There are many terms and definitions associated with laboratory ventilation that have special meaning. The following are definitions of terms or units used in this document: A2.1 adjacent roof line: For the purposes of determining the laboratory chemical hood stack height, the adjacent roof will be within 6 feet horizontally of the nearest outer point of the exhaust fan stack. This criterion is intended to protect maintenance workers from direct exposure to their breathing zone, hands, feet, and other parts of their body. Parts of the building that are within 6 feet horizontally of the exhaust fan stack are exempted if it would be impossible for a person to stand or cling to the surface in question. A2.2 air changes per hour (ACH): A common means for expressing a volumetric airflow through a room. Each ACH for a room is intended to represent an amount of air equal to the gross volume of the air passing through the room each hour. An ACH rate for a room can be converted to volumetric airflow by multiplying the ACH number times the gross volume of the room. For instance, for an ACH of 10, a room with a gross volume of 2400 cubic feet has a volumetric airflow of 400 cfm (10 2400 ÷ 60). The air change rate depends on exhaust flow for a negatively pressurized room and on supply flow for a positively pressurized room. This term does not reflect actual mixing factors and therefore does not indicate the effective air exchange rate in the room. See the ACGIH® publication, Industrial Ventilation Manual for further information on mixing factors. A2.3 air lock: An intermediate chamber between two dissimilar spaces with airtight doors or openings to each of the spaces. The doors are interlocked to ensure that there is always at least one of them closed. A2.4 auxiliary air hood: A laboratory chemical hood with an external supply air plenum at the top of the laboratory chemical hood. The auxiliary air plenum provides a makeup airstream comprised of unconditioned or only minimally conditioned outside air to substantially reduce the amount of con- ditioned room air exhausted by the laboratory hood. A2.5 bypass hood (constant air volume bypass laboratory hood): A laboratory hood design that incorporates an opening (bypass area) in the upper portion of the laboratory hood structure. When the movable sash is fully open, the sash blocks off this bypass area and all of the airflow into the laboratory hood must pass through the open face area. However, as the sash is being closed to reduce the open face area, at a specific point an amount of bypass area is being uncovered. The increase in the bypass area opening offsets the decrease in the face area opening, thus providing an alternate path (the uncovered bypass area) for air to flow into the laboratory hood. When utilized with a constant air volume ventilation system, the bypass area keeps the laboratory hood face velocity relatively constant and from increasing to an objectionably high value as the sash is lowered. A2.6 capture velocity: The air velocity at a point in space of sufficient magnitude to overcome room air currents and draw the air and any contaminants at that point into the hood. A2.7 chemical hygiene officer: An employee who is designated by the employer and who is qualified by training or experience to provide technical guidance in the development and implementation of the provisions of the Chemical Hygiene Plan. This definition is not intended to place restrictions on the position description or job classification that the designated individual shall hold within the employer's organizational structure. A2.8 constant air volume (CAV) ventilation system: A ventilation system designed to maintain a constant quantity of airflow within its ductwork. The airflow quantity is typically based upon the amount required to handle the most extreme conditions of outdoor-weather-related heat gain or loss and internal building loading. Although relatively simple, a constant volume ventilation system typically requires the maximum ongoing energy usage since the system always operates at maximum capacity. 93 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 A2.9 design sash position: The maximum open area of the hood face that achieves the desired face velocity during any work inside the hood that produces airborne contaminants. of the laboratory hood and discharges the exhaust directly into the room. Ductless laboratory hoods are of limited size and capacity in comparison to conventional ducted laboratory hoods. A2.10 dilution ventilation: Ventilation airflow that dilutes contaminant concentrations by mixing with contaminated air, as distinguished from capturing the contaminated air. A2.14 exhaust air: Air that is removed from an enclosed space and discharged to atmosphere. A2.11 discharge velocity: The speed of the exhaust air normally expressed in feet per minute (meters/second) at the point of discharge from a laboratory exhaust system. Since laboratory exhaust system fans may be configured to discharge into a vertical exhaust stack or may utilize fans specifically designed to discharge directly upward, the discharge velocity normally refers to the air velocity as it leaves the last element of the exhaust system. Since the top of an exhaust stack may be conical (or other type of configuration), the velocity of the exhaust air at the point of discharge may differ from the velocity of the air within the vertical stack itself. The term “stack velocity” is sometimes used when referring to the speed of the exhaust airstream as it is discharged into the outside air. A2.12 diversity factor: A percentage factor that is applied to establish the theoretical maximum exhaust airflow quantity that is required at any point in time. For example, in an exhaust system consisting of three hoods, the diversity factor would be 1/3 if at any point in time only 1 hood were being used. Applying a diversity factor to the theoretical maximum required capacity of an HVAC system is often considered in the design of a VAV system. Incorporating a diversity factor enables downsizing HVAC system components and thus results in a smaller capacity ventilation system. The overall intention of applying a diversity factor when designing a VAV ventilation system is to achieve a lower life cycle cost (e.g., lower system first cost and/or lower system energy costs). A2.13 ductless hood: A laboratory hood that is not connected to an exhaust system that discharges the laboratory hood exhaust outdoors. Rather, a ductless laboratory hood incorporates an exhaust fan and exhaust filters as an integral part A2.15 face velocity: The air velocity at the plane of and perpendicular to the opening of a laboratory chemical hood. A2.16 floor-mounted hood (walk-in hood): A larger-size laboratory hood with sash and/or door arrangement that enables access from the floor to the top of the hood interior. The name unfortunately is a misnomer and although the design and height of these hoods may allow it, users should not walk into any hood that may represent a significant exposure hazard. Walk-in laboratory hoods enable larger equipment and apparatus (e.g., equipment on carts, gas cylinders, etc.) to be more readily put in and set up within the laboratory hood. A2.17 glovebox: A controlled environment work enclosure providing a primary barrier from the work area. Operations are performed through sealed gloved openings to protect the user, the environment, and/or the product. A2.18 hazardous chemical – Encompasses 1) regulatory definitions such as found in 29 CFR 1910.1450 (which appears to almost mistakenly refer exclusively to health hazards) and 29 CFR 1910.1200 (which refers to both health and physical hazards), and 2) other accepted definitions such as offered by OSHA on its safety and health topics web page http://www.osha.gov/SLTC/hazardoustoxicsubstances/index.html. A2.19 HEPA: High Efficiency Particulate Air (filter) for air filters of 99.97% or higher collection efficiency for 0.3 m diameter droplets of an approved test aerosol (e.g., Emory 3004) operating at a rated airflow. A2.20 laboratory: It is difficult to provide a strict definition for laboratory. Some entire institutions are formally named “Laboratory.” The general concept for application of this standard is a facility in 94 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 which the amounts of chemicals handled are small [perhaps 22 or 44 lbs (10 or 20 kg), except for storage of supplies], where much of the work involves manual manipulation of small containers or benchtop apparatus, and where the work is not routine production of goods. When this standard is used as a reference document in specifying design and construction (or modification) of a facility, it is suggested that the parties involved in the activity agree whether the facility is to be considered a laboratory. The Occupational Safety and Health Administration, in 29 CFR 1910.1450 (subpart 2, paragraph 191.1450) [4], provides a definition of “laboratory” for regulatory purposes. A2.21 laboratory fume hood: a box-like structure with typically one open side, intended for placement on a table, bench, or floor. The bench and the hood may be one integral structure. The open side is provided with a sash or sashes that move vertically and/or horizontally to close the opening. Provisions are made for exhausting air from the top or back of the hood and adjustable or fixed internal baffles are usually provided to obtain proper airflow distribution across the open face A2.22 makeup air (replacement air): Any combination of transfer air and air provided by a ventilation system to replace air being exhausted from a laboratory hood, canopy hood, room, or space. A2.23 perchloric acid hood: A laboratory hood constructed and specifically intended for use with perchloric acid or other reagents that may form flammable or explosive compounds with organic materials of construction. A perchloric acid hood as well as its exhaust system must be constructed of all inorganic materials and be equipped with a water washdown system that is regularly used to remove all perchloric salts that may precipitate and collect in the laboratory hood and in the exhaust system. The exhaust fan must also be of a sparkresistant design to ensure against ignition of any perchlorate deposits in the exhaust system. A2.24 recirculation: Air removed or exhausted from a building area and ducted back to an air-handling system where it is mixed with outside fresh air. This air mixture is then conditioned and utilized for ventilation. Since air removed from a space is more often close to the temperature and humidity of the building interior than outside air, the recirculation process enables achieving a greater reduction in heating and cooling energy than if 100% outside air was utilized (also see return air). A2.25 reentry: The flow of contaminated air that has been exhausted from a space back into the space through air intakes or openings in the walls of the space. A2.26 replacement air: See makeup air. A2.27 responsible person: An individual who has the responsibility and authority for the design and implementation of the ventilation management plan. This person may be the Chemical Hygiene Officer or work in conjunction with the Chemical Hygiene Officer. A2.28 return air: Air being returned from a space to the ventilation fan that supplies air to a space. A2.29 room air balance: A general term describing the requirement that a laboratory room have the proper relationship with respect to the total exhaust airflow from the room and the supply makeup airflow. The relationship of these airflows also establishes the pressure differential between the laboratory room and adjacent rooms and spaces. A2.30 room ventilation: The volumetric airflow through a room expressed in terms of cfm or L/sec. A2.31 special purpose hood: An exhausted hood, not otherwise classified for a special purpose such as but not limited to capturing emissions from equipment such as atomic absorption gas chromatographs; liquid pouring, mixing, or weighing stations; and heat sources. These hoods might not meet the design description of various types of laboratory chemical hoods discussed here. They may be exterior hoods, receiving hoods, or enclosing hoods, as described in the latest ACGIH Industrial Ventilation: A Manual of Recommended Practice. 95 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 A2.32 – transfer air – air that moves between spaces in a building, driven by the ventilation system. A2.33 variable air volume—two-position ventilation system: A constant air volume ventilation system (sometimes also referred to as a “two-position variable air volume system”) that is designed to provide two separate levels of airflow. The higher level of airflow is provided when a facility is normally occupied such as during regular work hours. The lower level of airflow is utilized during unoccupied times (e.g., nighttime, holidays, etc.) when ventilation needs and internal loads require less airflow. A2.34 variable volume hood: A hood designed so the exhaust volume is varied in proportion to the opening of the hood face by changing the speed of the exhaust blower or by operating a damper or control valve in the exhaust duct. A2.35 variable air volume (VAV) ventilation system: A type of HVAC system specifically designed to vary the amount of conditioned air supplied and exhausted from the spaces served. The amount of air supplied and intended to meet (but not exceed) the actual need of a space at any point in time. In general, the amount of air that is needed by a space is determined by the required rate and the amount of airflow necessary to maintain comfortable conditions (temperature and humidity). A2.36 velocity: Magnitude and direction of air motion. As used in this standard, if the direction is omitted it is implied to be perpendicular to the plane of the airflow cross section. If the direction is important, it will be stated. A2.39 units and abbreviations: AAALAC – Association for Assessment and Accreditation of Laboratory Animal Care ABSA – American Biological Safety Association ACD – air-cleaning device AMCA – Air Movement Control Association ACGIH® – American Conference of Governmental Industrial Hygienists AGS – American Glovebox Society AIHA® – American Industrial Hygiene Association USAMRICD – United States Army Medical Research Institute of Chemical Defense ASME – American Society of Mechanical Engineers ASHRAE – American Society of Heating, Refrigerating and Air Conditioning Engineers AI – as installed AM – as manufactured AU – As used CAV – constant air volume CETA – Controlled Environment Testing Association CFD – computational fluid dynamics A2.37 volumetric airflow rate: The rate of airflow expressed in terms of volume (cubic feet or liters) per unit of time. These are commonly expressed as cubic feet per minute (cfm) in USCS units or liters per second (l/s) in SI units. (Also see room ventilation.) A2.38 Walk-in hood: See floor-mounted hood. cfm – cubic feet per minute dBA – (A scale) decibels dP – differential pressure fpm – feet per minute in.wg – inches water column (gauge) 96 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 IEST – Institute of Environmental Sciences and Technology PPE – personal protective equipment RC – room criteria curves ISEE – International Society of Explosives Engineers REL – Recommended Exposure Levels ISPE – International Society for Pharmaceutical Engineering SEFA – Scientific Equipment and Furniture Association JIC – joint industry codes (hydraulic equipment) SMACNA – Sheet Metal and Air Conditioning Contractors National Association MAK – maximum allowable concentration SPL – sound pressure level NFPA – National Fire Protection Association TA – Transfer Air NC – noise criteria curves TAB – testing, adjusting and air balancing NEC – National Electrical Code TLV® – Threshold Limit Value NFC – National Fire Code TWA – time weighted average NIOSH – National Institute for Occupational Safety and Health NSF – National Sanitation Foundation VAV – variable air volume WEEL® – Workplace Environmental Exposure Levels PEL – Permissible Exposure Limit 97 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 APPENDIX 2. Referenced Standards and Publications The following standards and associated publications, when referenced in this document, constitute provisions of this American National Standards Institute, Inc. At the time of publication, the editions indicated were the most current. However, since standards and associated publications are subject to periodic revision, parties to agreements based on this American National Standard are encouraged to ensure that they reference the current editions of these documents. ACGIH®: Industrial Ventilation: A Manual of Recommended Practice, 27th edition. Cincinnati, OH: American Conference of Governmental Industrial Hygienists, 2001. ACGIH®: Threshold Limit Values (TLV®) For Chemical Substances and Physical Agents. Cincinnati, OH: American Conference of Governmental Industrial Hygienists, 2012. AGS-G001–2007: Guideline for Gloveboxes, 3rd edition. Santa Rosa, CA: American Glovebox Society, 2007. AMCA 99–2010: Standards Handbook. Arlington Heights, IL: Air Movement and Control Association, 1986. AMCA 200-95 (RA 2007): Fan Application Manual, Part I, Fans and Systems: AMCA Classification for Spark Resistant Construction. Arlington Heights, IL: Air Movement and Control Association, 2007. ANSI/AIHA® Z9.2–2001: Fundamentals Governing the Design and Operation of Local Exhaust Systems. Fairfax, VA: American Industrial Hygiene Association, 2001. ANSI/AIHA® Z9.7–1998: Recirculation of Air from Industrial Process Exhaust Systems. Fairfax, VA: American Industrial Hygiene Association, 1998. ANSI/AIHA® Z9.11–2008: Laboratory Decommissioning. Fairfax, VA: AIHA®, 2008. ANSI/ASHRAE 41.1–1986 (RA 01): Standard Method for Temperature Measurement. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 1991. ANSI/ASHRAE 41.2–1987 (RA 92): Standard Methods for Laboratory Air Flow Measurement. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 1992. ANSI/ASHRAE 41.3–1989: Standard Method for Pressure Measurement. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 1989. ANSI/ASHRAE 41.7–1984 (RA 00): Method of Test Measurement of Flow of Gas. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 2000. ANSI/ASHRAE 52.1–1992: Gravimetric and DustSpot Testing Procedure for Testing Air-Cleaning Devices Used in General Ventilation for Removing Particulate Matter. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 1992. ANSI/ASHRAE 52.2–2007: Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 2007. ANSI/ASHRAE 62.1–2010: Ventilation for Acceptable Indoor Air Quality. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 2010. ANSI/ASHRAE 110–1995: Method of Testing Performance of Laboratory Fume Hoods. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers, 1995. ASHRAE 2009 Handbook – Fundamentals (Inch-Pound edition). Atlanta, GA: American Society of Heating, Refrigerating, and AirConditioning Engineers, Inc., 2009. 98 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ASHRAE 2011 Handbook – HVAC Applications (Inch-Pound edition). Atlanta, GA: American Society of Heating, Refrigerating, and AirConditioning Engineers, Inc., 2011. Braun, K.O. and K.J. Caplan: “Evaporation Rate of Volatile Liquids, Final Report, 2nd edition. EPA Contract Number 68-D8-0112”, PACE Laboratories Project 890501.315. Washington, D.C.: U.S. Dept. of Commerce, NTIS, December 1989. Controlled Environment Testing Association. CAG-005-2007, Servicing Hazardous Drug Compounding Primary Engineering Controls, Controlled Environment Testing Association, 1500 Sunday Drive, Suite 102, Raleigh, NC 27607, http://www.cetainternational.org/reference/CAG00 5-v15.pdf CDC-NIH: Biosafety in Microbiological and Biomedical Laboratories, Appendix A, CDC-NIH, 5th edition, Atlanta, GA: Centers for Disease Control and Prevention, 2009. EPA-600/8-81-009: Guideline for Modeling of Atmospheric Diffusion. Office of Air Quality Planning and Standards, April 1981. Harnett, P.B.: Empirical data and modeling of a flammable spill in a chemical fume hood do not support the need for fire suppression within the chemical fume hood ductwork. Chem. Health Safe. 10(4):11–14 (2003). “Hazard Communication,” Code of Federal Regulations. Title 29, Part 1910.1200, 1988. HVAC Duct Construction Standards: Metal and Flexible, Merrifield, VA: Sheet Metal and Air Conditioning Contractors’ National Association, 2005. IMC-2012: International Mechanical Code. Falls Church, VA: International Code Council, 2012. Institute of Environmental Sciences and Technology (IEST), Laminar Flow Clean Air Devices, IEST-RP-CC-002-86 Arlington Heights, IL, http://www.iest.org Ivany, R., M. First, and L.J. DiBerardinis: A New Quantitative Method for In-Place Testing of Laboratory Hoods. Am. Ind. Hyg. Assoc. J. 50(5):275–80 (1989). Klein, R.C., C. King, and P. Labbie: Solvent vapor concentrations following spills in laboratory chemical hoods. Chem. Health Safe. 11(2):4–8 (2004). Klein, R.C., et al.: Laboratory air quality and room ventilation rates. J. Chem. Health Safety 16(5):36–42 (2009). Kolesnikov, A., R. Ryan, and D.B. Walters: Use of Computational Fluid Dynamics to Optimize Airflow and Energy Conservation in Laboratory Hoods and Vented Enclosures. Washington, D.C.: EPA Labs for the 21st Century, January 2002. Kolesnikov, A., J. McNally, R. Ryan, and D.B. Walters: CFD-Driven Design of a Low AirFlow, Rapid Recovery System to Maximize Safety and Optimize Energy Efficiency. Durham, NC: EPA Labs for the 21st Century, October 2002. Labconco Corp.: Development of the Labconco Protector® Xstream® High Performance Laboratory Fume Hood. Kansas City, MO: Labconco Corporation, 2009. LEED: Leadership in Energy and Environmental Design. U.S. Green Building Council. Manning, A., et al.: Analysis of Air Supply Type and Exhaust Location in Laboratory Animal Research Facilities Using CFD. ASHRAE Transactions DA-00-14-3 (2000). Memarzadeh, F.: Methodology for Optimization of Laboratory Hood Containment, Volumes I and II. Bethesda, MD: National Institutes of Health, 1996. NFPA 30–2008: Flammable and Combustible Liquids Code. Quincy, MA: National Fire Protection Association, 2000. NFPA 45–2011: Standard on Fire Protection for Laboratories Using Chemicals. Quincy, MA: National Fire Protection Association, 2011. 99 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 NFPA 86–2007: Standards for Ovens and Furnaces. Quincy, MA: National Fire Protection Association, 2007. NFPA 92A–2009: Recommended Practice for Smoke Control Systems. Quincy, MA: National Fire Protection Association, 2009. NSF 49–2004: Class II (Laminar Flow) Biohazard Cabinetry. Ann Arbor, MI: National Sanitation Foundation, International, 2004. “Occupational Exposure to Hazardous Chemicals in Laboratories,” Code of Federal Regulations Title 29, Part 1910.1450, 1988. Parker, A.J. and P.J. DiNenno: “Evaluation of Fixed Extinguishing System Effectiveness in Continuously Exhausting Chemical Fume Hoods.” Prepared for Merck & Co. by Hughes Associates, September 2001. Petersen, R.L., B.C. Cochran, and J. LeCompte: “Specifying Exhaust Systems that Avoid Fume Reentry and Adverse Health Effects.” Symposium Paper at ASHRAE Summer Meeting, Honolulu, HI, June 23-26, 2002. To be published in 2002 ASHRAE Transactions. Ratcliff, M.A. and E. Sandru: Dilution Calculations for Determining Laboratory Exhaust Stack Heights. ASHRAE Transactions 105(1):Ch-99-7-2 (1999). SEFA-1-2002: Scientific Equipment and Furniture Association, 2001. Sharp, G.P.: “A Review of U.S. and European Empirical Research, Theoretical Calculations, and Industry Experience on Fume Hood Minimum Flow Rates.” International Institute of Sustainable Laboratories (I2SL) E-Library, http://www.i2sl.org/ elibrary/ index.html, 2009. Smith, T.C. and S.M. Crooks: Implementing a Laboratory Ventilation Management Program. Chem. Health Safety 3 : 12 (1996). Smith, T.C. and S. Yancey-Smith: Specification of Airflow Rates in Laboratories. J. Chem. Health Safety 16(5):27–35 (2009). Tronville, P. and R.D. Rivers: International standards: filters for buildings and gas turbines, Filtration & Separation, Volume 42, Issue 7, September 2005, Pages 39-43, ISSN 0015-1882, DOI: 10.1016/S0015-1882(05)70623-6. “Test Methods,” Code of Federal Regulations Title 40, Part 60, Appendix A, 1989. UMC–2012: Uniform Mechanical Code. Whittier, CA: International Conference of Building Officials and Los Angeles, CA: International Association of Plumbing and Mechanical Officials, 2012. U.S. Nuclear Regulatory Commission, U.S. Department of Energy, U.S. Environmental Protection Agency, and U.S. Department of Defense: Multi-Agency Radiation Survey and Site Investigation Manual (MARSSIM) (EPA 402-R-97016), 2001. Ventilation Test according to DIN 12 924 Part 1: Fume Cupboard DIN 12 924 TA 1500 x 900 – 900, Fume hood Test report by Waldner Laboreinrichtungen GmbH & Co. for mc6 - Bench Mounted Fume Cupboard: Test Report No.159, May 2000. 100 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 APPENDIX 3. Selecting Laboratory Stack Designs Necessary measures must be taken to protect the laboratory building and adjacent buildings from reingestion of toxic laboratory chemical hood exhaust back into a building air supply system. The 10 ft (3.05 m) minimum stack height called for in the body of this standard is primarily intended to protect maintenance workers from direct contamination from the top of the stack. However, the minimum height of 10 ft is not enough by itself to guarantee that harmful contaminants would not be reingested. Similarly, a minimum 3000 fpm (15.3 m/s) exit velocity is specified in the body of this standard, but this exit velocity does not guarantee that re-ingestion will not occur. This appendix describes general stack design guidelines and three analysis methods for determining an adequate stack design. The first analysis method is termed the "Geometric" method, which ensures that the lower edge of an exhaust plume stays above the emitting building and associated zones of turbulent airflow. The geometric method is fully described here and is accompanied by an example. The second analysis method, briefly described, predicts exhaust dilution at downwind locations. The dilution equations are not presented here but can be obtained from the ASHRAE Handbook HVAC Applications. A dilution criterion is presented in this appendix to judge the adequacy of the predicted dilutions in minimizing re-ingestion. The third analysis method described is wind tunnel or water flume modeling. General Guidelines Laboratory chemical hood exhaust stacks should have vertical, unobstructed exhaust openings. The Building Air Intake and Exhaust Design chapter of the ASHRAE Handbook – HVAC Applications describes appropriate rain protection devices. Goosenecks, flapper dampers, and rain caps are unacceptable as they deflect the exhaust sideways or downward, making it much more likely that re-ingestion will occur. The stack must reach high enough to ensure that the exhaust plume is sufficiently diluted when it reaches sensitive areas such as building air intakes, entrances, operable windows, and outdoor plazas. The appropriate stack height is a function of the plume height for the exhaust system being designed and the subsequent dispersion, or concentration levels at the aforementioned sensitive locations. The dispersion modeling process (numerical or physical modeling) is discussed in a later section. The plume rise should be calculated using the equations that compute plume rise versus downwind distance. If two exhaust systems give the same plume height at the same downwind distance, the dispersion and resulting concentration levels will be identical. It should be noted that by adding 5 to 10 ft to the stack height and decreasing the exit velocity, the same plume rise (and dilution) can be achieved which can lead to the fan energy savings. For a given exhaust flow rate, reducing the exit diameter with an exhaust nozzle is recommended to increase the exit velocity and rise or throw of the exhaust over the building. However, exit velocities much larger than 3000–4000 fpm (15.3 to 20.4 m/s) may result in high noise and vibration. Too small of a nozzle, or one with too rapid a decrease in area, could result in excessive pressure loss in the exhaust and the resulting combination of reduced flow due to fan system effect and reduced dilution and safety. Combining exhausts into a common stack, either by manifolding exhausts or with very close grouping of stacks, will enhance the rise of the exhaust plume. Close grouping of stacks can be used for specialty exhausts that cannot be manifolded because of their chemical nature. Manifolding or combining exhausts can generally give greater benefit than installing an exhaust nozzle on a stack serving a single laboratory chemical hood. Manifolding of exhausts can also provide some internal dilution of fume hood exhausts when the majority of chemical emissions are from an upset condition or large release from a single laboratory chemical hood. Such upset or large release conditions are the primary cause of odor complaints and potential health effects. However, this internal dilution is partially offset by the decreased atmospheric 101 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 dilution due to the larger plume size. Nevertheless, manifolding of exhausts is still beneficial and recommended. Variable exhaust flow rates, used to reduce energy costs, can periodically result in low exit velocities. Minimum exit velocities below 1500 fpm (7.65 m/s) are discouraged because for such low exit velocities, high winds can cause the exhaust to travel down the side of the stack instead of rising vertically. A dispersion modeling assessment can define the minimum exhaust velocity and volume flow needed to avoid fume reentry. If this assessment shows a higher exhaust velocity and/or volume flow is needed, there are other methods to achieve the desired dispersion: • Variable flow geometry • Induction of outdoor air • Staging of multiple fans on a common inlet plenum • Use of a control system and on-site weather station so that low velocities can be set during low wind and high velocities during high winds. Adding outdoor air to the exhaust is the most common approach because it provides the larger plume rise and some internal dilution. Air intake placement is as important as stack design. Intakes on the side of the building or at grade will usually provide greater protection from rooftop exhausts. Intakes on the roof may work if placed a sufficient distance from the exhausts. When only a single tall stack is present, an intake location near the base of the stack may be a good location. The advantage of this location is diminished if there are sources of toxic or odorous exhausts at other locations on the roof. Nearby intakes elevated above a laboratory exhaust stack should be avoided. Rooftop obstacles, such as parapets or architectural fences, and penthouses on the same roof as the hazardous exhaust stack can also act as adjacent buildings causing wind flow disturbances that reduce the rise of the exhaust. Note that it is the difference in roof heights that is particularly important when analyzing the adjacent building effect. First Stack Design Method—The Geometric Method The ASHRAE Handbook—HVAC Applications describes the geometric method. This simplified method is intended to be conservative, but there are limits on its applicability. The ASHRAE Handbook also describes those limits. The geometric method is designed for isolated rectangular buildings that do not have taller buildings, dense taller trees, or taller hills close to the laboratory building. Also air intakes on the emitting building should be no higher than the top of the physical exhaust stack opening. Provided these conditions are met, the geometric method can be applied as follows: 1) Calculate the length of the recirculation zone (R) downwind of the building for each of the four basic approach wind directions. For a given direction, R = (Bsmall 0.67) (Blarge 0.33), where Bsmall is the smaller of the building height and width, and Blarge is the larger of the two. As used here, the recirculation zone height is the height of the emitting building. Table A2 presents recirculation zone length for various building dimensions. 2) Calculate the plume rise (throw) due to exhaust momentum and add it to the stack height, to obtain the effective stack height. hf = 0.9[FmUH/U*]1/2 UHßj {} 2 Fm = Ve d 4 ßj = 1 3 + UH Ve is the final plume rise, where is the momentum flux, ft4/s2 (m4/s2) is the jet entrainment coefficient UH / U* = 2.5ln(H/z0) is the well-known logarithmic wind profile equation, 102 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Ve = stack exit velocity, fpm (m/s) d = stack diameter, ft (m) UH = wind speed at stack top, fpm (m/s) H = stack height above ground level, ft (m) U* = friction velocity, ft (m) of the basic approach wind directions. Table A3 shows flowrates required to meet the geometric method, given a 10 ft (3.5 m) stack height and a 3000 fpm (15.3 m/s) exit velocity (as per this standard), a 1%-wind speed of 15 mph (24 k/h), and various horizontal distances to clear. The horizontal distance is the distance between the stack and the downwind building edge plus the recirculation zone length. zo = surface roughness length, ft (m) The same method can be used to determine a taller stack that also complies. Table A1 describes various zo values for a range of sites. For example if zo equals 0.5 m and H = 11 m, substituting into the logarithmic wind profile equation gives UH/U* = 8.3. Example Calculation for the First Stack Design Method—The Geometric Method Table A1: Terrain Factors Terrain zo, ft (m) Flat, water, desert 0.03 (0.01) Flat, airport, grassland 0.16 (0.05) Suburban 2.0 (0.6) Urban 6.0 (2.0) A laboratory building is 100 ft (30.5 m) wide, 200 ft (61 m) long, and 60 ft (18.3 m) high. A manifolded laboratory exhaust with a flowrate of 10,000 cfm (4.7 m3/s) is located in the center of the roof. For wind approaching the 100 ft (30.5 m) wide side, Bsmall is 60 ft (18.3 m) and Blarge is 100 ft (30.5 m). The length of the recirculation zone is R = (600.67)(100 0.33) = 71 ft (21.7 m). The horizontal distance that must be cleared by the plume equals 100 ft (30.5 m) from the center to the edge of the building plus 71 ft (21.7 m) for the recirculation zone, or 171 ft (52.2 m). The required effective stack height to clear the building and recirculation zone is 171/5 (using the 5:1 slope) = 34.2 ft (10.4 m). 3) The effective height of the stack is the physical stack height plus the added plume rise due to momentum. The added stack height due to momentum is calculated next. The stack diameter is 2.06 ft (.63 m) based on a 3000 fpm (15.3 m/s) exit velocity and a 10,000 cfm (4.7 m3/s) flow rate. Using a 15 mph (24 k/h), 1320 fpm (6.7 m/s) 1%-wind speed, the added stack height = 3 °F 2.06 °F 3000/1320 = 14 ft (4.3 m). Given a physical stack height of 10 ft (3.05 m) based on the minimum required to meet this standard, the effective stack height is 14 + 10 ft = 24 ft (7.32 m). 4) The geometric method, as stated here, specifies that the bottom of an exhaust plume should clear the emitting building, including penthouses, and the recirculation zone downwind of the building. The bottom of the plume extends downward at a 5:1 slope (5 units horizontal and 1 unit downward) from the effective stack height (physical height plus added plume rise). This should be done for all four The required effective height computed above is 34.2 ft (10.4 m), which is not met with a 10 ft (3.05 m) physical stack height. The designer can increase the physical height to 20 ft (6.1 m). As an alternative, the designer can increase the momentum of the air by introducing outside air to the system. If the physical stack height remains at 10 ft (3.05 m), the diameter would need to increase to The 1%-wind speed is a high wind speed exceeded only 1% of the time. These wind speeds are available for numerous locations in the ASHRAE Handbook—Fundamentals, Chapter Climatic Design Information. 103 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Table A1 Length of Downstream Recirculation Zone (feet and meters) Each story is 15 ft (4.6 m) high Bldg. Dimensions 1 Story 2 Stories 3 Stories 4 Stories 5 Stories 6 Stories 7 Stories Height in Feet (meters) 15 ft (4.6 m) 30 ft (9.1 m) 45 ft (13.7 m) 60 ft (18.3 m) 75 ft (22.9 m) 90 ft (27.4 m) 105 ft (32.0 m) 50 ft (15.2 m) 22.3ft (6.8 m) 35.5 ft (10.8 m) 46.6 ft (14.2 m) 53.1 ft (16.2 m) 57.2 ft (17.4 m) 60.7 ft (18.5 m) 63.9 ft (19.5 m) 75 ft (22.9 m) 25.5 ft (7.8 m) 40.6 ft (12.4 m) 53.3 ft (16.2 m) 64.6 ft (19.7 m) 75.0 ft (22.9 m) 79.7 ft (24.3 m) 83.3 ft (25.4 m) 100 ft (30.5 m) 28.1 ft (8.6 m) 44.6 ft (13.6 m) 58.6 ft (17.9 m) 71.0 ft (21.6 m) 82.5 ft (25.1 m) 93.2 ft (28.4 m) 101.6 ft (31.0 m) 150 ft (45.7 m) 29.8 ft (9.1 m) 51.0 ft (15.5 m) 67.0 ft (20.4 m) 81.2 ft (24.7 m) 94.3 ft (28.7 m) 106.5 ft (32.5 m) 118.1 ft (36.0 m) 200 ft (61.0 m) 29.8 ft (9.1 m) 56.1 ft (17.1 m) 73.6 ft (22.4 m) 89.3 ft (27.2 m) 103.7 ft (31.6 m) 117.1 ft (35.7 m) 129.9 ft (39.6 m) 250 ft (76.2 m) 29.8 ft (9.1 m) 59.6 ft (18.2 m) 79.2 ft (24.1 m) 96.1 ft (29.3 m) 111.6 ft (34.0 m) 126.1 ft (38.4 m) 139.8 ft (42.6 m) 300 ft (91.4 m) 29.8 ft (9.1 m) 59.6 ft (18.2 m) 84.2 ft (25.7 m) 102.0 ft (31.1 m) 118.5 ft (36.1 m) 133.9 ft (40.8 m) 148.5 ft (45.3 m) 500 ft (152.4 m) 29.8 ft (9.1 m) 59.6 ft (18.2 m) 89.4 ft (27.2 m) 119.2 ft (36.3 m) 140.3 ft (42.8 m) 158.5 ft (48.3 m) 175.7 ft (53.6 m) 1000 ft (304.8 m) 29.8 ft (9.1 m) 59.6 ft (18.2 m) 89.4 ft (27.2 m) 119.2 ft (36.3 m) 149.0 ft (45.4 m) 178.8 ft (54.5 m) 208.5 ft (63.6 m) Length or Width Formula for figure is: Length of downstream recirculation zone is Bsmall(0.67) °F Blarge(0.33) where Bsmall is the smaller of height and width or length and Blarge is the larger of the two (from ASHRAE, 1997). Where Blarge is > 8 Bsmall, use Blarge = 8 Bsmall 3.5 ft (1.1 m), increasing flow rate to about 30,000 cfm (14.1 m3/s). Also, increasing to 30,000 cfm (14.1 m3/s) will increase in-stack dilution by a factor of 3:1. This in-stack dilution, whether achieved by manifolding exhausts in the building or by adding roof air, can be very valuable to achieving safe results. The other wind direction (aimed toward the long side of the building) should be checked, but for this example this wind direction is the worst case. High volume flow in itself is not a guarantee of adequate dilution. For a given source spill rate in kilograms/second, a higher exhaust volume flow Qe increases the in-stack dilution, but somewhat reduces the atmospheric dilution because the atmosphere is now presented with a larger volume of gas to disperse. Tables A2 and A3 assist in estimating a stack height that ensures that the plume avoids recirculation zones and the edge of the building. 104 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Table A2 Volume Necessary to Achieve Throw Off Edge of Building and Recirculation Zone, cfm and L/s Assume stack is 10 ft (3.0 m) high and fan exit velocity is 3000 fpm (15.2 m/s) with 15 mph (24.1 km/h) wind speed Distance to Edge of Feet to throw Building and Recirc. Zone horizontally Meters to throw horizontally Flow needed, cfm Flow needed, L/s 75 22.9 1,267 598.0 100 30.5 5,068 2392.0 150 45.7 20,272 9567.3 200 61.0 45,612 21526.5 250 76.2 81,088 38269.3 300 91.4 126,699 59795.3 Second Stack Design Method—The Numerical Method A more detailed analysis that accounts for dilution within the plume can be used if the required stack heights or flowrates are too large from the geometric method. Minimum dilution can be predicted using equations from the ASHRAE Handbook— HVAC Applications. The equations are not discussed in detail here. These equations apply only to intakes below stack top. The stack height used in these equations is the physical stack height only. “Effective stack height,” including the effect of plume rise, should not be used. The EPA screening dispersion model, SCREEN3, can also be used in certain situations to supplement the ASHRAE Handbook equations. The numerical methods are continually evolving. Designers are advised to consult current sources for specific calculations. The discussion here illustrates issues; it does not teach a design procedure. For the example case discussed above [10 ft (3.05 m) stack, diameter = 2.06 ft (0.628 m), exit velocity = 3000 fpm (15.24 m/s), flowrate = 10,000 cfm (4.7 m3/s), receptor at end of wake recirculation zone 171 ft (52.2 m) away], the predicted minimum dilution from the ASHRAE Handbook is 455:1. If the diameter is increased to 3.5 ft (1.07 m) associated with a larger flow rate of 30,000 cfm (14.1 m3/s), the minimum dilution decreases to 264:1. At first glance, the smaller flowrate stack that yields the larger dilution would seem to be preferred. However, the larger 30,000 cfm (14.1 m3/s), flowrate provides an internal dilution of 3:1 compared to the original 10,000 cfm (4.7 m3/s). When comparing the two cases, the larger flowrate case has a total dilution of 3 °F 264 = 792:1, which is better than the lower flowrate case and would provide lower chemical concentrations at an air intake for a given chemical release rate. Allowable spill rate to meet the 0.05 ppm at the receptor location would be 11.2 L/m of toxic vapor. The original design with d = 2.06 ft (0.63 m) has a higher dilution Dcrit of 455 but the reduced volume flow only allows a spill volume rate of 6.4 L/m. In effect, the factor of 3 volume flow increase in the stack with the fan allows about a factor of 1.75 increase in allowable spill rate. In conceptual terms, exit velocity and volume flow rate are "equal partners" in plume rise and the resulting increase in safety through greater dilution. However, in practical terms, exit velocities can only be increased by doubling or tripling while manifolding or adding roof air to the stack can easily result in a 10-fold increase in dilution. Dilution in the context of dispersion of laboratory exhaust is a deceptively difficult concept because one must account for both the dilution within the 105 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 exhaust system, De, which is present at the stack and the dilution from the stack to a downwind location, D. The concept can be simplified by normalizing D by the volume flow rate through the exhaust stack, Q. By normalizing D, only the dispersion, which occurs between the exhaust stack and the downwind location, needs to be considered. The normalized value can be presented in one of two ways, either as a normalized dilution or a normalized concentration value. A normalized dilution value can be obtained by multiplying D by the ratio of the actual volume flow rate and a standardized volume flowrate [i.e., 1000 cfm (4.7 m3/s) °F (Qact / Qstd)]. The result is a dilution value that is independent of the actual volume flowrate through the exhaust stack, making it possible to compare the effectiveness of various exhaust stacks with different volume flowrates, because all of the values are referenced to the same 1000 cfm (0.47 m3/s) volume flowrate. A normalized concentration value is obtained by applying the definitions of concentration and dilution provided in the ASHRAE Handbook—HVAC Applications, [C/m = 1/ (D * Q)]. The result is a normalized concentration value that is the ratio of the concentration present at the downwind location and the mass emission rate of the emitted chemical, expressed in units of µg/m3 per g/s. This value is completely independent of the volume flowrate through the exhaust stack, and thus can be used to readily compare the effectiveness of exhaust stacks with various volume flowrates. Another advantage of this method is that if the emission rate of a chemical is known, you can simply multiply the emission rate by the C/m value to obtain a pollutant concentration. This concentration can then be compared directly with established health and odor limits. Design Criteria When designing stacks with the numerical method, it is necessary to have a design criterion for selecting a stack design. Development of a dilution criterion can be difficult since the types and quantities of laboratory chemicals can vary significantly from laboratory to laboratory. As a starting place, it is suggested here to have the stack provide protection similar to what a laboratory chemical hood would provide a worker standing at the hood. As described in this standard, a laboratory chemical hood should have an ANSI/ASHRAE 110 test performed by a manufacturer, and the ANSI/ASHRAE 110 rating should be AM 0.05 or lower. This rating translates to the worker being exposed to 0.05 ppm or lower of tracer gas while 4 liters per minute (4 L/min.) of tracer gas are being emitted from within the laboratory chemical hood. The same 4 L/min. of tracer gas are being emitted from the laboratory chemical hood exhaust stack. The recommended design criterion is that the 0.05 ppm concentration also be the maximum concentration at the air intake. (The time constant for exposure concentrations mentioned in this standard is measuring over a 10-minute span of time.) The detailed calculations are not presented here, but it can be confirmed that the 4 L/min. emission rate and an allowable air intake concentration of 0.05 ppm corresponds to a normalized concentration design criterion of 750 µg/m3 per g/s or a 2800:1 dilution for a 1000 cfm (0.47 m3/s) flowrate exhaust, 280:1 for a 10,000 cfm (4.7 m3/s) flow rate, and a 93:1 dilution for a 30,000 cfm exhaust. These suggested design criteria is somewhat more lenient than the smaller criteria suggested in the ASHRAE Handbook—HVAC Applications, Chapter Laboratories, which has recommended that air intake concentrations should be less than 3 ppm due to an evaporating liquid spill in a fume hood and exhausted at a rate of 7.5 L/s. The ASHRAE criteria translate to a normalized concentration design criterion of 400 µg/m3 per g/s or a 5000:1 dilution for a 1000 cfm flowrate exhaust. For facilities with intense chemical utilization, design criteria specific for that facility can be developed using the chemical inventory. In the stack examples above, the 10,000 cfm (4.7 m3/s) case had a predicted dilution of 455:1, which meets the 280:1 criterion for a 10,000 cfm (4.7 m3/s) flowrate. The 30,000 cfm (14.1 m3/s) case had a predicted dilution of 264:1, which also meets the 93:1 criterion for this flowrate, by a larger margin than the 10,000 cfm (4.7 m3/s) stack. 106 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 Graphical Solution Referenced for the Second Stack Design Method Using the Halitsky Criteria Two graphical solutions can be consulted that show a solution to the dilution calculations. The first is Ratcliff and Sandru (ASHRAE Transactions, 105, part 1, paper Ch-99-7-1, 1999) and the second is Petersen, Cochran, and LeCompte (to be published in 2002 ASHRAE Transactions). The solutions in both papers are for a Halitsky Criteria spill, 0.028 ppm, rather than the criterion derived from the ANSI/ASHRAE 110 test specification. Quite a bit of expertise is required to interpret the graphs. As an example, in the second paper, one point calculated and shown on the graph is that a zero height stack with a flow of 50,000 cfm (23.5 L/s) and an exit velocity of 3000 fpm (15.24 m/s) would require an offset distance of 120 ft (36.6 m) to the nearest receptor site using the 0.028 ppm exposure limit at the receptor. These graphs were derived from Chapter 43 of ASHRAE 1999 Handbook—Applications Manual equations for critical wind speeds and dilutions. Zero-height stacks are quite common because stacks that end below parapet walls, below the height of adjacent penthouses, or that end below adjacent screen walls or screens will act as a zero-height stack. Receptor sites would include operable doors and windows, and any location where pedestrian access was allowed as well as to outside air intakes. Third Stack Design Method—Physical Modeling Using the Wind Tunnel or Water Flume If the stack heights determined from the first two methods described above are undesirable or if the geometry or topography of the building site makes simple analysis methods unreliable, a scale model of the building and surroundings should be physically modeled in an atmospheric wind tunnel or water flume. Physical modeling provides more accurate, and typically less conservative, predictions than the numerical or geometric methods. Physical modeling is the safest method to choose stack heights in new buildings or in buildings being retrofitted. Wind-tunnel modeling is often the preferred method for predicting maximum concentrations for stack designs and locations of interest when energy and equipment optimization is desired. It is the recommended approach because it gives the most accurate estimates of concentration levels in complex building environments. A wind-tunnel modeling study is like a full-scale field study, except it is conducted before a project is built. Typically, a scale model of the building under evaluation, along with the surrounding buildings and terrain within a 1000-ft radius, is placed in an atmospheric boundary layer wind tunnel. A tracer gas is released from the exhaust sources of interest, and concentration levels of this gas are then measured at receptor locations (i.e., air intakes, operable windows, etc.) of interest and converted to full-scale concentration values. Next, these values are compared against the appropriate health or odor design criteria outlined in Section 5.3.4 to evaluate the acceptability of the exhaust design. ASHRAE (2009) and Snyder (1981) provide more information on scale-model simulation and testing methods. Dilution criteria are still necessary to evaluate the results of physical modeling. The design criteria discussed above provide initial guidance. A more complete evaluation of appropriate design criteria should be conducted when the chemical usage is expected to exceed minimal levels. In addition, the design criteria should take into account the 20% factor outlined in Section 5.3.4. 107 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 APPENDIX 4. Audit Form for ANSI/AIHA® Z9.5–2012 ( ) 2.1.3 Dilution ventilation is provided to control the buildup of fugitive emissions and odors in the laboratory. Laboratory Ventilation 2.2 Chemical Hygiene Plan Audit item numbers refer to Standard paragraphs. Compliance with the Standard should only be claimed when all applicable provisions or elements of the Standard are met. Note: Mark (X) all those that genuinely apply. 2 Lab Ventilation Management Plan 2.1 General Requirements ( ) 2.2 The laboratory develops a Chemical Hygiene Plan according to the OSHA Laboratory Standard (29 CFR 1910.1450). ( ) The plan addresses the laboratory operations and procedures that might generate air contamination in excess of the requirements of Section 2.1.1. ( ) 2.1 Management has established a Laboratory Ventilation Management Plan (LVMP) to ensure proper selection, operation, use, and maintenance of laboratory ventilation equipment. ( ) These operations are performed inside a hood adequate to attain compliance. ( ) The LVMP has been implemented to ensure proper operation of the lab ventilation systems, help protect laboratory personnel working with potentially hazardous airborne materials, provide satisfactory environmental air quality and maintain efficient operation of the laboratory ventilation systems. ( ) 2.3 In each operation using laboratory ventilation systems, the user designates a “responsible person.” ( ) 2.1.1 Adequate laboratory chemical hoods, special purpose hoods, or other engineering controls are used when there is a possibility of employee overexposure to air contaminants generated by a laboratory activity. ( ) Laboratory worker chemical exposures are maintained below applicable published or inhouse exposure limits. ( ) Chemical “hazard determinations” are conducted by chemical manufacturers and importers as required by the Occupational Safety and Health Administration's (OSHA) Hazard Communication standard, specifically, 29 CFR 1910.1200(d). ( ) 2.1.2 The specific room ventilation rate is established or agreed upon by the owner or their designee. 2.3 Responsible Person 2.4 Roll of Hazard Assessments ( ) 2.4.1 Employers ensure an ongoing system for assessing the potential for hazardous chemical exposure. ( ) Employers promote awareness that laboratory hoods are not appropriate control devices for all potential chemical releases in laboratory work. ( ) The practical limits of knowing how each ventilation control is being used in the laboratory are considered when specifying design features and performance criteria. ( ) The responsible person defined in Section 2.3 is consulted in making these judgments. ( ) The employer establishes criteria for determining and implementing control measures to reduce employee exposures to hazardous chemicals; particular attention is given to the selection of control measures for chemicals that are known to be extremely hazardous. 108 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ( ) Laboratory chemical hoods are functioning properly and specific measures are taken to ensure proper and adequate performance. ( ) 2.4.2 The following items are considered and decisions made regarding each element's relevance following the hazard assessment process: ( ) Vendor qualification; ( ) Adequate workspace; ( ) Design sash opening and sash configuration (e.g. , for laboratory chemical hoods); ( ) Diversity factor in VAV-controlled laboratory chemical hood systems; ( ) Manifolded or individual systems; ( ) Redundancy and emergency power; ( ) Hood location; ( ) Face velocity for laboratory chemical hoods; ( ) The level of formality given to system commissioning; ( ) Tracer gas containment "pass" criteria; ( ) Alarm system (local and central monitoring); ( ) Air cleaning (exhaust pollution controls); ( ) Exhaust discharge (stack design) and dilution factors; ( ) Recirculation of potentially contaminated air; ( ) Differential pressure and airflow between spaces and use of airlocks, etc.; ( ) Fan selection; ( ) Frequency of routine performance tests; ( ) Preventive maintenance; and ( ) Decommissioning. equipped with a safety viewing sash at the face opening. ( ) Sashes are not removed when the hood is in use. ( ) 3.1.1.1 Where the design sash opening area is less than the maximum sash opening area, the hood is equipped with a mechanical sash stop. ( ) A means of communicating when openings are in excess of the design sash opening area is provided. ( ) The Chemical Hygiene Plan clearly instructs the hood users to position the sash so that the opening is no greater than the design opening while using the hood for protection. ( ) 3.1.1.2 Vertical sashes are designed and operated so as not to be opened more than the design opening when hazardous materials are being used within the hood. ( ) 3.1.1.3Horizontal sashes arfe designed so as not to be opened more than the design opening width when hazardous materials are being generated in the hood. ( ) 3.1.1.4 If a combination sash provides horizontally moving panels mounted in a frame that moves vertically, the above requirements are met. 2.5 Complete and permanent records are maintained for each laboratory ventilation system. ( ) 3.1.1.5 All users are trained in good work practices, including the need to close the sash when not in use. 3 Laboratory Fume Hoods ( ) All users of VAV systems shall be trained in the proper uses of the sash, the energy consequences of improper use, and the need to close the sash when the operation does not require its use. 3.1 Design and Construction ( ) 3.1 The design and construction of laboratory chemical hoods conform to the applicable guidelines presented in the latest edition of ACGIH® Industrial Ventilation: A Manual of Recommended Practice, and the most current codes, guidelines and standards, and any other applicable regulations and recommendations. ( ) 3.1.1 The laboratory chemical hood is ( ) Automatic sash positioning systems have obstruction sensing capable of stopping travel during sash closing operations without breaking glassware, etc. ( ) Automatic sash positioning allows manual override of positioning with forces of no more than 109 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 10 lbs (45 N) mechanical both when powered and during fault modes during power failures. emergency contingency plans are in place. In addition: 3.2 Hood Types ( ) 3.2.1 Auxiliary air hoods meet the requirements in Section 3.3. ( ) All inside hood surfaces use materials that will be stable and not react with perchloric acid to form corrosive, flammable, and/or explosive compounds or byproducts; In addition: ( ) The supply plenum is located externally and above the top of the hood face; ( ) The supply jet is distributed uniformly across the hood width; ( ) The auxiliary air does not disrupt hood containment or increase potential for escape. ( ) 3.2.2 Bypass hoods have a route for air entering the hood (the bypass mechanism) opens as the sash closes. ( ) The bypass mechanism shall be designed to minimize potential ejection of liquid or solid material outside the hood in the event of an eruption inside the hood. ( ) 3.2.3 Conventional hoods meet the requirements in Section 3.3. ( ) 3.2..4 Floor-mounted hoods meet the requirements in Section 3.3. ( ) 3.2.5 Perchloric acid hoods are specifically designed to safely handle certain types of perchloric acid work and are actually used for such work. ( ) Perchloric acid hoods are used for handling anhydrous perchloric acid (> 85% concentration.) ( ) All procedures conducted in a perchloric acid hood are reviewed by an immediate supervisor. ( ) All procedures using a perchloric acid hood are performed by trained personnel, knowledgeable and informed about the hazards and properties of these substances, and are provided with appropriate protective equipment after suitable ( ) All interior hood, duct, fan, and stack surfaces are equipped with water washdown capabilities; ( ) All ductwork is constructed of materials that will be stable to and not react with perchloric acid and/or its byproducts and will have smooth welded seams; ( ) No part of the system is manifolded or joined to nonperchloric acid exhaust systems; ( ) No organic materials, including gaskets are used in the hood construction unless they are known not to react with perchloric acid and/or its byproducts; ( ) Perchloric acid hoods are prominently labeled “Perchloric Acid Hood, Organic Chemicals Prohibited.” ( ) 3.2.6 VAV hoods meet the requirements in Section 3.3. ( ) Variable exhaust flow from a laboratory hood has implications for room ventilation which are addressed according to Section 5. 3.3 Hood Airflow and Monitoring ( ) 3.3.1 The average face velocity of the hood is sufficient to capture and contain the hazardous chemicals for which the hood was selected, and follows guidance in Section 2.4 and as generated under as-used conditions. ( ) An adequate face velocity is is not the only criterion to achieve acceptable performance and is not used as the only performance indicator. ( ) Hood containment is verified as appropriate for the hazard being controlled (e.g., visual meth- 110 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ods such as smoke, face velocity testing, exposure assessments, tracer gas containment testing, etc.) ( ) 4.1.1 Gloveboxes are not used for manipulation of hazardous materials with the face or other panels open or removed. ( ) 3.3.2 The flow rate of Constant Volume hoods and the minimum flow rate of Variable Air Volume hoods is sufficient to prevent hazardous concentrations of contaminants within the laboratory fume hood. ( ) In addition to maintaining proper hood face velocity, laboratory hoods maintain a minimum exhaust volume to ensure that contaminants are properly diluted and exhausted from a hood. ( ) The following considerations are taken into account (as applicable) when setting the minimum hood flow rate: hood interior corrosion, need to affect directional airflows, fume hood density, hood design, hood materials, generation or emission rates, exhaust parameters. ( ) The hood flow rate is set within the operating range of the hood exhaust equipment and the associated control system. ( ) Ventilation system designers coordinate the operating range of the fume hood flow rate with the operating ranges of the other air supply and exhaust devices in the room. 3.3.3 Flow Measuring Devices ( ) All hoods are equipped with a flow indicator, flow alarm, or face velocity alarm indicator to alert users to improper exhaust flow. ( ) The flow-measuring device is capable of indicating that the air flow is in the desired range, and capable of indicating alarms when the flow is high or low by 20%. ( ) The device is calibrated at least annually and whenever damaged. 4 Other Containment Devices 4.1 Gloveboxes ( ) 4.1.2 Materials: Interior cracks, seams, and joints are eliminated or sealed. ( ) 4.1.3 Utility valves and switches are in conformance with applicable codes. ( ) When control of utilities from inside the glovebox is required, additional valves and switches are provided outside the glovebox for emergency shutoff. ( ) 4.1.4 Proper application of ergonomic principles is met by referring to Chapter 5.10, “Guidelines for Gloveboxes,” AGS-G001–1998. ( ) 4.1.5 The design of the glovebox provides for retaining spilled liquids so the maximum volume of liquid permitted in the glovebox will be retained. ( ) 4.1.6 Containment gloveboxes are provided with exhaust ventilation to result in a negative pressure inside the box that is capable of containing the hazard to acceptable levels. ( ) 4.1.7 The air or gas exhausted from the glovebox is cleaned, and discharged to the atmosphere in accordance with the general provisions of this standard and pertinent environmental regulations. ( ) Air-cleaning equipment is sized for the maximum airflow anticipated when hazardous agents are exposed in the glovebox and the glovebox openings are open to the extent permitted under that condition. ( ) If the air-cleaning device (ACD) is passive, provision is made for determining the status of the ACD, as noted in Section 9.3. If the ACD is active, instrumentation is provided to indicate its status. ( ) The ACD is located to permit ready access for maintenance. ( ) Provision is made for maintenance of the ACD without hazard to personnel or the environment 111 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 and so not to contaminate the surrounding areas. ( ) 4.1.8 Exhaust piping is in accordance with the principles described in ACGIH® Industrial Ventilation: A Manual of Recommended Practices, ANSI/AIHA® Z9.2, and the ASHRAE 1997 Handbook − Fundamentals. ( ) All piping within the occupied premises is under negative pressure when in operation. ( ) Materials are resistant to corrosion by the agents to be used. ( ) 4.1.9 A glovebox pressure monitoring device with a means to locally indicate adequate pressure relationships to the user is provided on all gloveboxes. ( ) If audible alarms are not provided, documented training for users in determining safe pressure differentials is required. ( ) Pressure monitoring devices are adjustable and subject to periodic calibration. ( ) 4.1.10 A written decommissioning plan following the procedures outlined in the latest edition of ANSI/AIHA® Standard Z9.11 Laboratory Decommissioning is developed. ( ) Before the access panel(s) of the glovebox are opened or re moved, the interior contamination is reduced to a safe level. ( ) If the contaminant is gaseous, the atmosphere in the box is adequately exchanged to remove the potentially hazardous gas. ( ) If the contaminant is liquid, any liquid on surfaces is wiped with suitable adsorbent material or sponges until visibly clean and dry. ( ) Used wipes are placed in a suitable container before being removed from the glovebox. ( ) If the contaminant is a powder or dust, all internal surfaces are cleaned and wiped until visi- bly clean and the exterior surfaces of the gloves also are wiped clean. ( ) Precautions to prevent personnel hazard and contamination of the premises are made if the ducting is to be opened or dismantled. ( ) When there is any uncertainty about the effectiveness of the contamination reduction procedures, personnel involved in opening the panels of the glovebox are provided with appropriate Personal Protective Equipment or clothing. ( ) 4.1.11 A high containment glovebox conforms to all the mandatory requirements of 4.1.1 through 4.1.10, and ( ) Is provided with one or more air-lock passthrough ports for inserting or removing objects or sealed containers without breaching the physical barrier between the inside and outside of the glovebox. ( ) Maintains negative operating static pressure within the range of -0.5 to -1.5 in. wg (–124 to –373.5 Pa) such that contaminant escape due to “pinhole-type" leaks is minimized. ( ) Maintains dilution of any flammable vapor-air mixtures to <10% of the applicable lower explosive limit. ( ) Prevents transport of contaminants out of the glovebox. ( ) 4.1.12 A medium containment glovebox conforms to all the mandatory requirements of Sections 4.1.1 through 4.1.10, and is not provided with pass-through airlocks, and is provided with sufficient exhaust ventilation to maintain an inward air velocity of at least 100 fpm (0.51 m/s) through the open access ports, and creates a negative pressure of at least 0.1 in. w g (2.49 Pa) when access ports are closed. ( ) 4.1.13 Special case containment gloveboxes are tested for the intended use and found adequate for that purpose. 112 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ( ) 4.1.14 An isolation and containment glovebox is used to control special atmosphere work when either the controlled atmosphere and/or the contained agents are hazardous. ( ) Design and construction and materials conforms to the requirements for high, medium, or special case containment gloveboxes as necessary. ( ) If the controlled atmosphere gas is hazardous, the airlocks are provided with a purge air exhaust system that, by manipulation of valves, creates a purge flow of room air sufficient to provide at least 5 air changes per minute, with good mixing, to the interior space of the airlock. ( ) Operation of an isolation and containment glovebox conform to high, medium, or special case containment requirements as necessary and the airlock purge system is operated for sufficient time to dilute any hazardous gas in the airlock to safe concentrations before the outer door is opened. ( ) Care is exercised when placing certain hazardous liquids in an evacuated airlock or interior of a glovebox when a decrease in pressure could affect the boiling point of the liquid, causing it to go to gaseous state. 4.1.15 An overall operation and maintenance program is documented for each application of the glovebox to provide users with necessary information on periodic maintenance and testing of glovebox system components. 4.2. Ductless Hoods ( ) Ductless hoods meet the general requirements of Sections 3.1 and 3.3 as applicable. ( ) A Hazard Evaluation and Analysis is conducted as directed in ANSI/AIHA® Z9.7 and Section 2.1.1 of this Standard. ( ) Compliance with the general requirements of Sections 2, 3.3 and 5.3.6.2, are evaluated by qualified persons. ( ) Ductless hoods that do not meet the requirements specified in Sections 9.3 and 9.4 are used only for operations that normally would be performed on an open bench without presenting an exposure hazard. ( ) Ductless hoods have signage prominently posted on them to inform operators and maintenance personnel about the allowable chemicals used in the hood, type and limitations of filters in place, filter changeout schedule, and that the hood recirculates air to the room. ( ) 4.2.1 Ductless hoods utilizing air-cleaning filtration systems for recirculating exhaust air contaminated with toxic particulates must meet the requirements of Section 9.3.1. ( ) 4.2.2 Ductless hoods utilizing adsorption or other filtration media for the collection or retention of gases and vapors are specified for a limited use and meet the requirements of Section 9.3.2. ( ) Ductless hoods employing filters for removing gases and vapors have written documentation (records) that the manufacturer has approved the specific application of the hood prior to usage. ( ) The manufacturer provides a list of chemicals approved to be used in the hood with their retention capacities. ( ) Proper disposal of unused and used (contaminated) adsorption filters is considered as part of the decision to use ductless hood employing such. ( ) 4.2.3 Contaminated filters are unloaded from the air-cleaning system following safe work practices to avoid exposing personnel to hazardous conditions and to ensure proper containment of the filters for final disposal. ( ) Airflow through the filter housing is shut down during filter change-out. ( ) 4.2.4 All of the requirements of sections 6.3, 113 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 6.4, 6.5.3.1 and 8.0 for containment and airflow testing and all of the requirements of sections 9.2 and 9.3.2 for air cleaning performance shall be followed. 4.3 Special Purpose Hoods ( ) 4.3 Special laboratory chemical hoods are designed in accordance with ANSI/AIHA® Z9.2 and ACGIH® Industrial Ventilation: A Manual of Recommended Practices. 5 Laboratory Ventilation System Design mizes the room ventilation (air changes per hour) rate and, if appropriate, increases negative room pressurization. ( ) For rooms served by CAV ventilation systems that utilize a reduced ventilation level for energy savings, the chemical emergency mode of operation ensures that the room ventilation and negative pressurization are at the maximum rate. ( ) Operation of the room ventilation system in a chemical emergency mode does not reduce the room ventilation rate, room negative pressurization level, or hood exhaust airflow rate. 5.1 Lab Design 5.2 Lab Airflow Management ( ) 5.1.1 Laboratory designers consider effects on safety when establishing floor plans and spatial layout. ( ) Laboratory chemical hoods are located so their performance is not adversely affected by cross drafts. ( ) Windows in laboratories with hoods shall be fully closed while hoods are in use (emergency conditions excepted). ( ) 5.1.2 Generation of excessive noise is avoided in laboratory ventilation systems. ( ) Fan location and noise treatment provide for SPL in conformance with local ambient noise criteria. ( ) 5.1.4 When the type and quantity of chemicals or compressed gases that are present in a laboratory room could pose a significant toxic or fire hazard, the room is equipped with provision(s) to initiate emergency notification and initiate the operation of the ventilation system in a mode consistent with accepted safety practices. ( ) A hazard assessment is performed to identify the credible emergency conditions that may occur. ( ) For rooms served by VAV ventilation systems, the chemical emergency mode of operation maxi- 5.2.1. ( ) As a general rule, airflow is from areas of low hazard to higher hazard and exceptions are documented. ( ) When flow from one area to another is critical to emission exposure control, airflow-monitoring devices are installed to signal or alarm a malfunction. ( ) Air is allowed to flow from laboratory spaces to adjoining spaces only if: ( ) There are no extremely dangerous and lifethreatening materials used in the laboratory; ( ) The concentrations of air contaminants generated by the maximum credible accident will be lower than the exposure limits required by 2.1.1. ( ) The desired directional airflow between rooms is identified in the design and operating specifications. ( ) 5.2.1.1 Airlocks are utilized to prevent undesirable airflow from one area to another in high hazardous applications, or to minimize volume of supply air required by Section 5.1.1. ( ) Airlocks are applied in such a way that one door provides access into or out of the laboratory room, and the other door of the airlock provides passage to or from a corridor (or other non-laboratory area). 114 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ( ) Airlock doors are arranged with interlocking controls so that one door must be fully closed before the other door may be opened. ( ) 5.2.1.2 If the direction of airflow between adjacent spaces is deemed critical, provision is made to locally indicate and annunciate inadequate airflow and improper airflow direction. ( ) 5.2.2 The following issues are evaluated in order to design for diversity: ( ) Use patterns of hoods; ( ) Type, size, and operating times of facility; ( ) Quantity of hoods and researchers; ( ) Sash management (sash habits of users); ( ) Requirements to maintain a minimum exhaust volume for each hood on the system; ( ) Type of ventilation system; ( ) Type of laboratory chemical hood controls; ( ) Minimum and maximum ventilation rates for each laboratory; ( ) Capacity of any existing equipment; ( ) Expansion considerations; ( ) Thermal loads; and ( ) Ability to perform periodic maintenance. ( ) The following conditions are met in order to design a system diversity: ( ) Acceptance of all hood-use restrictions by the user groups, which take into account the common work practices of the site users. ( ) When the type and quantity of chemicals or compressed gases that are present in a laboratory room could pose a significant toxic or fire hazard, the room is equipped with provision(s) to initiate emergency notification and initiate the operation of the ventilation system in a mode consistent with accepted safety practices. ( ) Emergency situations (see current version of NFPA 92A) that are anticipated and the appropriate ventilation system responses are provided, as follows: ( ) For a CHEMICAL EMERGENCY – A means such as a clearly marked wall switch, , or other readily accessible device is provided to enable the room occupants to initiate appropriate emergency notification and simultaneously activate the ventilation system’s chemical emergency mode of operation if one exists. ( ) For rooms served by VAV ventilation systems, the Chemical Emergency mode of operation maximizes the room ventilation (air change per hour) rate. ( ) For rooms served by 2-state ventilation systems that utilize a reduced ventilation level for energy savings, the Chemical Emergency mode of operation applies the maximum ventilation rate. ( ) A training plan is in place for all laboratory users to make them aware of any limitations imposed on their freedom to use the hoods at any time. ( ) Operation of the room ventilation system in a chemical emergency mode does not reduce the room ventilation rate, room negative pressurization level, or hood exhaust airflow rate. ( ) An airflow alarm system is installed to warn users when the system is operating beyond capabilities allowed by diversity. ( ) For FIRE – Any manual or automatic means of detecting fire (such as a pull station or smoke detector) in a laboratory room also activates an appropriate fire emergency mode of operation for the room and/or building ventilation system. ( ) Restrictions on future expansions or flexibility are identified. 5.2.3 Lab Ventilation – Emergency Modes ( ) A hazard assessment (see Section 2.4) is performed to identify credible emergency conditions that may occur. ( ) The selected fire emergency mode operates all supply and exhaust equipment in the room in a manner that promotes egress, retards the spread of fire and smoke, and complies with applicable fire safety codes and standards. 5.3 Supply Air 115 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 5.3.1 Supply Air Volume ( ) If laboratories are to be maintained with a negative pressurization and directional airflow from the corridor into the laboratory, supply air volumes are less than the exhaust flowrate from the laboratory. ( ) When laboratories are to be maintained with a positive pressurization and directional airflow, supply air volume is more than the exhaust from the laboratory. ( ) To maintain the desired space pressurization, the supply air volume responds to applicable dynamic events including: • • • • changes in desired ventilation rate, flow changes in VAV exhaust devices, temperature control demands, and temporary deficit of exhaust system capacity. ( ) The laboratory ventilation system is designed to remove and dilute air contaminants in accordance with the Laboratory Ventilation Management Plan. ( ) The ventilation rate also satisfies the general codes and standards that apply to the occupancy class. 5.3.2 Supply Air Distribution and Quality ( ) Supply air distribution is designed to keep air jet velocities less than half, preferably less than one-fourth of the capture velocity or the face velocity of the laboratory chemical hoods at their face opening. ( ) In cases where Section 510 of the International Mechanical Code applies, designers consult the most current version of IMC 510. 5.4.2 Exhaust System Ductwork ( ) Laboratory exhaust system ductwork complies with the appropriate sections of current versions of the Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA) standards. ( ) Systems and ductwork are designed to maintain negative pressure within all portions of the ductwork inside the building when the system is in operation. ( ) Exhaust ductwork is designed in accordance with the current versions of ANSI/AIHA® Z9.2, the ASHRAE Handbook – Fundamentals, and NFPA 45. ( ) Branch ducts enter a main duct so that the branch duct centerline is on a plane that includes the centerline of the main duct. ( ) For horizontal main ducts, branch ducts do not enter a main duct on a plane below the horizontal traverse centerline of the main duct. Horizontal runs of branch ducts shall be kept at a minimum. ( ) Longitudinal sections of a duct are a continuous seamless tube or of a continuously welded formed sheet. ( ) Longitudinal seams that are formed mechanically are utilized only for light duty systems with no condensation or accretion inside the duct. ( ) Supply systems meet the technical requirements of the laboratory work and the requirements of the latest version of ANSI/ASHRAE Standard 62.1. ( ) Spiral ducts can be one gauge lighter than the required gauge of longitudinal seam duct if the spiral duct gauge always meets the abrasive wear resistance requirements. 5.4 Exhaust System Classification ( ) Traverse joints are continuously welded or flanged with welded or Van Stone flanges. 5.4.1 ( ) Designers reviews existing regulations and code requirements for the project location. ( ) When nonmetallic materials are used, joints are cemented in accordance with the manufactur- 116 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 er’s procedures. NFPA 45. ( ) If the duct is coated with a corrosion-resistant material, the coating extends from the inside of the duct to cover the entire face of the flange. ( ) Exhaust system materials are resistant to corrosion by the agents to which they are exposed. ( ) Flange faces are gasketed or beaded with material suitable for service. ( ) If condensation within the duct is likely, all horizontal duct runs are sloped downward at least 1 in. per 10 ft in the direction of the airflow to a suitable drain or sump. ( ) Exhaust airflow volume are sufficient to keep the temperature in the duct below 400°F (204°C) under all foreseeable circumstances. ( ) All duct connections to the exhaust fan are consistent with good ventilation design practice. As an alternative, the duct connections may be made by means of inlet and outlet boxes. ( ) If circumstances such as space limitations prevent the implementation of the preceding requirements, then applicable speed and power corrections are made by applying the “System Effect Factor" (see AMCA 201-90). ( ) Where optimum duct connections cannot be made due to space or other limitations, suitable alternative means are substituted to compensate for the space limitations. ( ) If adequate duct connections cannot be provided at the fan, the fan is equipped with inlet and outlet boxes furnished by the fan manufacturer. ( ) The manufacturer furnishes performance curves for the fan with the inlet and outlet box(es) as part of the fan. ( ) If neither adequate connections nor inlet/outlet boxes are present, the fan speed and power requirements represented in the fan rating table are corrected by the “System Effect Factor.” ( ) Exhaust system materials chosen in accordance with the current version of ACGIH’s® Industrial Ventilation: A Manual of Recommended Practice, the ASHRAE Handbook—Fundamentals, and ( ) Exhaust system materials are noncombustible if perchloric acid or similar oxidizing agents that pose a fire or explosive hazard are used. 5.4.3 Manifolds ( ) Laboratory chemical hood ducts are combined into a common manifold with the following exceptions and limitations: ( ) Each control branch has a flow-regulating device to buffer the fluctuations in pressure inherent in manifolds. ( ) Perchloric acid hoods are not manifolded with nonperchloric acid hoods unless a scrubber is installed between the hood and the manifold. ( ) Where there is a potential for ductwork contamination from hood operations as determined from the Hazard Assessment of Section 2.4, radioisotope hoods are not manifolded with nonradioisotope hoods unless an appropriate air-cleaning system is provided between the hood and the manifold: HEPA filter and/or carbon bed filters for gases. ( ) Exhaust streams that contain concentrations of flammable or explosive vapors at concentrations above the Lower Explosion Limit (LEL) as well as those that might form explosive compounds (i.e., perchloric acid hood exhaust) are not connected to a centralized exhaust system. ( ) Exhaust streams comprised of radioactive materials are adequately filtered to ensure removal of radioactive material before being connected to a centralized exhaust system. ( ) Biological exhaust hoods are adequately filtered to remove all hazardous biological substances prior to connection to a centralized exhaust system. ( ) Unless all individual exhausts connected to the centralized exhaust system can be completely 117 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 stopped without creating a hazardous situation, provision is made for continuous maintenance of adequate negative static pressure (suction) in all parts of the system. devices connected to the manifold, and powered devices include, but are not limited to: biological safety cabinets, in-line scrubbers, motorized dampers, and booster fans. ( ) As an alternative, if the hood is completely turned off, the hood is emptied and decontaminated and provisions are implemented to prevent the hood from back-drafting. ( ) Manifolds are maintained under negative pressure at all times and be provided with at least two exhaust fans for redundant capacity. ( ) A VAV hood is provided with an emergency switch that allows the hood exhaust volume to return to the maximum. ( ) Biological safety cabinets manifolded with chemical laboratory chemical hoods have either: (1) A thimble connection or (2) An air flow control device and an interlock/alarm for these devices installed between the cabinet outlet and the exhaust manifold. ( ) Where Hazard Evaluation and Analysis determines that the installation calls for direct connection (hard ducted) of the biological safety cabinet (e.g., Class II–Type B) to an exhaust manifold system to allow work with toxic chemicals or radionuclides, interlocks and alarms are provided to prevent the biological safety cabinet from operating its normal starting mode or to immediately warn the operator in the event of an exhaust system failure (CDC-NIH, 1999). ( ) The static pressure in the exhaust system is lower than the surrounding areas throughout the entire length, with the exception noted in Section 5.3.1.1. ( ) Fire dampers are not installed in exhaust system ductwork (NFPA 45). ( ) Fire sprinklers are not installed in laboratory chemical hood exhaust manifolds. ( ) Exhaust systems operate continuously to provide adequate ventilation for any hood at any time it is in use and to prevent backflow of air into the laboratory when the following conditions are present: Chemicals are present in any hood (opened or unopened), exhaust system operation is required to maintain minimum ventilation rates and room pressure control, there are powered ( ) Emergency power is connected to one or more of the exhaust fans where exhaust system function must be maintained even under power outage situations. 5.4.4 Fans ( ) Each fan serving a laboratory exhaust system or to exhaust an individual piece of laboratory equipment (e.g., a laboratory chemical hood, biosafety cabinet, chemical storage, etc.) is adequately sized to provide the necessary amount of exhaust airflow in conjunction with the size, amount, and configuration of the connecting ductwork. ( ) In addition, each fan’s rotational speed and motor horsepower are sufficient to maintain both the required exhaust airflow and stack exit velocity and the necessary negative static pressure (suction) in all parts of the exhaust system. ( ) If flammable gas, vapor, or combustible dust is present in concentrations above 20% of the Lower Flammable Limit, fan construction is as recommended by the most current version of AMCA’s 99-0401, Classifications for Spark Resistant Construction. ( ) Laboratory exhaust fans are located as follows • Physically outside of the laboratory building and preferably on the highest level roof of the building served. (This is the preferred location since it generally minimizes risk of personnel coming into contact with the exhaust airflow.) • In roof penthouse or a roof mechanical equipment room that is always maintained at a negative static pressure with respect to the rest of the facility, and provides direct fan discharge into the exhaust stack(s). 118 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ( ) All laboratory exhaust fans include provisions to allow periodic shutdown for inspection and maintenance. Such provisions include: • Isolation dampers on the inlet side of all centralized exhaust system fans that have individual discharge arrangements or their own individual exhaust stacks. • Isolation dampers on both the inlet and outlet sides of all centralized exhaust system fans that discharge into a common exhaust stack or plenum. • Ready access to all fans, motors, belts, drives, isolation dampers, associated control equipment, and the connecting ductwork. • Sufficient space to allow removal and replacement of a fan, its motor, and all other associated exhaust system components and equipment without affecting other mechanical equipment or the need to alter the building structure. Design. ( ) In any event the discharge is a minimum of 10 ft (3 m) above adjacent roof lines and air intakes and in a vertical up direction. ( ) Exhaust stack discharge velocity is at least 3000 fpm (15.2 m/s) (unless it can be demonstrated that a specific design meets the dilution criteria necessary to reduce the concentration of hazardous materials in the exhaust to safe levels (see Section 2.1) at all potential receptors.) ( ) Esthetic conditions concerning external appearance do not supersede the requirements of Sections 5.4.5 and 5.4.6. ( ) Any architectural structure that protrudes to a height close to the stack-top elevation (i.e., architectural structure to mask unwanted appearance of stack, penthouses, mechanical equipment, nearby buildings, trees or other structures) is evaluated for its effects on re-entrainment. 5.4.5. Discharge of Contaminated Air ( ) The discharge of potentially contaminated air that contains a concentration more than the allowable breathing air concentration is: ( ) The air intake or exhaust grills are not located within the architectural screen or mask unless it is demonstrated to be acceptable. 5.4.7 Recirculation • direct to the atmosphere unless the air is treated to the degree necessary for recirculation (see Section 9.3), • discharged in a manner and location to avoid reentry into the laboratory building or adjacent buildings at concentrations above 20% of allowable concentrations inside the laboratory for routine emissions or 100% of allowable concentrations for emergency emissions under wind conditions up to the 1%-wind speed for the site, and in compliance with applicable federal, state, or local regulations with respect to air emissions 5.4.6 Exhaust Stack Discharge ( ) The exhaust stack discharge is in accordance with the current version of ASHRAE Handbook – HVAC Applications, and the chapter or section dealing with Building Air Intake and Exhaust ( ) Air exhausted from the general laboratory space (as distinguished from laboratory chemical hoods) is not recirculated to other areas unless one of the following sets of criteria is met: 3) Criteria A • The concentration of air contaminants generated by maximum credible accident will be lower than short-term exposure limits required by 2.1.1; • There are no extremely dangerous or lifethreatening materials used in the laboratory; and • The system serving the laboratory chemical hoods is provided with installed redundancy, emergency power, and other reliability features as necessary, or 119 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 4) Criteria B • Provision of 100% outside air, whenever continuous monitoring indicates an alarm condition; • Recirculated air is treated to reduce contaminant concentrations to those specified in 2.1.1; and recirculated air is monitored continuously for contaminant concentrations or provided with a secondary backup air-cleaning device that also serves as a monitor (via a HEPA filter in a series with a less efficient filter, for particulate contamination only; refer to Section 9.3.1) and exhaust air from laboratory hoods shall not be recirculated to other areas. ( ) Hood exhaust meeting the same criteria as noted in Section 5.4.7.1 is only recirculated to the same work area where the hood operators have control of the hood work practices and can monitor the status of air cleaning. 6. Commissioning and Routine Performance Testing 6.1 Specifying Laboratory Fume Hood Performance ( ) Test specifications used for selecting a hood, in commissioning or in routine testing, refer to the applicable ANSI/ASHRAE 110 defined performance tests. or to a test standard recognized to be equivalent. ( ) Specification and procurement of laboratory fume hoods are based on “As Manufactured” ANSI/ASHRAE 110 defined performance tests conducted on a representative hood (or prototype hood) that demonstrate adequate hood containment. ( ) The performance tests to be witnessed, referenced or otherwise include: • • • • airflow visualization tests, auxiliary air velocity tests (if applicable,) cross drafts velocity tests, exhaust flow measurements, • face velocity tests, • hood static pressure measurement, and • tracer gas containment tests ( ) The tests are conducted under constant volume conditions where exhaust and air supply flow are stable and exhibit no more than 5% variation from set-point. 6.1.1 Performance Tests ( ) The following performance tests are conducted as indicated and as prescribed in the commissioning plan, laboratory ventilation management plan, or as directed by the responsible person. 6.1.1.1 Airflow Visualization Tests ( ) Airflow visualization tests are conducted as described in the ANSI/ASHRAE 110–1995, Method of Testing Performance of Laboratory Fume Hoods. ( ) The tests consist of small-volume generation and large-volume generation smoke to identify areas of reverse flow, stagnation zones, vortex regions, escape, and clearance. ( ) Visible escape beyond the plane of the sash when generated 6 in. (15.2 cm) into the hood constitutes a failure during the performance test. 6.1.1.2 Auxiliary Air Velocity Tests ( ) For auxiliary air hoods, the face velocity is measured with the auxiliary air turned off unless room pressurization would change significantly to affect exhaust flow. Where exhaust flow would be affected by turning off the auxiliary airflow, auxiliary air is redirected from the hood opening so as not to interfere with flow into the hood while conducting the face velocity traverse. ( ) The velocity of the auxiliary air exiting the auxiliary air plenum is measured to determine the magnitude and distribution of air supplied above the hood opening. ( ) The average auxiliary air velocity is determined from the average of grid velocities mea- 120 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 sured across the plenum outlet. measurements are taken. 6.1.1.3 Cross-Draft Velocity Tests ( ) A decrease in the average face velocity below 90% of the benchmark velocity is corrected prior to continued hood use. ( ) Cross-draft velocity measurements are made with the sashes open and the velocity probe positioned at several locations near the hood opening to detect potentially interfering room air currents (cross drafts). Record measurement locations. ( ) Over a period of 10–30 sec., cross-draft velocities are recorded approximately 1 reading per second using a thermal anemometer with an accuracy of +5% at 50 fpm (0.25 m/s) or better. ( ) The average and maximum cross-draft velocities at each location are recorded and not be sufficient to cause escape from the hood. ( ) Cross draft velocities are not of such magnitude and direction as to negatively affect containment. 6.1.1.4 Exhaust Flow Measurement ( ) The volumetric flow exhausted from a laboratory fume hood is determined by measuring the flow in the exhaust duct using industry-approved methods. 6.1.1.5 Face Velocity Tests ( ) Once adequate performance has been established for a particular hood at a given benchmark face velocity using the methods described above, that benchmark face velocity is used as a periodic check for continued performance as long as no substantive changes have occurred to the hood or other aspects that affect hood performance. ( ) Face velocity measurements are made with the sash in the Design Sash Position. The Design Sash Position is the maximum opening or configuration allowed by user standards, SOPs, or the Chemical Hygiene Plan, whichever is applicable, and used in the design of the exhaust system to which the hood is connected. ( ) The sash position at which benchmark face velocity is measured is recorded with the face velocity measurement and reproduced each time ( ) The average face velocity is determined by the method described in the current version of ANSI/ASHRAE 110 Method of Testing Performance of Laboratory Fume Hoods. ( ) Face velocity measurements are made by dividing the hood opening into equal area grids with sides measuring no more than 12 in. (30.5 cm). ( ) The tip of the probe is positioned in the plane of the sash opening and fixed (not handheld) at the approximate center of each grid. ( ) Grid measurements around the perimeter of the hood opening are made at a distance of approximately 6 in. (15.2 cm) from the top, bottom, and sides of the opening enclosure. ( ) The average face velocity is the average of the grid velocity measurements. ( ) Each grid velocity is the average of at least 10 measurements made over at least 10 seconds. ( ) The plane of the sash is defined as the exterior surface of the outer most glass panel. 6.1.1.6 Hood Static Pressure Measurement ( ) The hood static pressure is measured above the outlet collar of the hood at the flows required to achieve the design average face velocity. 6.1.1.7 Tracer Gas Containment Tests ( ) Ttracer gas containment tests are conducted as described in the ANSI/ASHRAE 110–1995, Method of Testing Performance of Laboratory Fume Hoods or by a test recognized to be equivalent. ( ) A control level for 5-minute average tests at 121 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 each location conducted at a generation rate of 6 L/m is no greater than 0.05 ppm for "as manufactured” tests and 0.10 ppm for “as installed” (AM 0.05, AI 0.1). ( ) Escape of emissions more than the control levels stated above are acceptable at the discretion of the design professional in agreement with the responsible person (2.4.2). ( ) The “as used” 0.10 ppm level or more is at the discretion of the responsible person (2.3). ( ) Face velocity increases exceeding 20% of the benchmark are corrected prior to continued use. 6.1.2 Test Instrumentation ( ) All test instrumentation utilized for the tests prescribed throughout this section are in good working order and have been factory calibrated within 1 year of the date of use. (See 8.6.1 Air Velocity, Air Pressure, Temperature and Humidity Instruments) along with the other project documents. ( ) A commissioning plan addresses operation of the entire ventilation system where the hoods, laboratories, and associated exhaust and air supply ventilation systems are considered subsystems. ( ) The plan includes written procedures to verify or validate proper operation of all system components and include: • Laboratory Fume Hood Specification and Performance Tests • Preoccupancy Hood and Ventilation System Commissioning Tests • Preoccupancy Laboratory Commissioning Tests 6.2.4 Commissioning Documentation ( ) Preliminary and final commissioning documents are issued to the appropriate party(s) by the Commissioning Authority. The documents include: 6.2 Commissioning of Laboratory Ventilation Systems 6.2.1 Commissioning Process ( ) All newly installed, renovated, or moved hoods are commissioned to ensure proper operation prior to use by laboratory personnel. 6.2.2 Commissioning Authority ( ) The commissioning process is overseen by a responsible person or commissioning authority. 6.2.3 Commissioning Plan ( ) A written commissioning plan accompanies design documents and is approved by the commissioning authority in advance of construction activities. • • • • Commissioning Test Data; Copy of Test and Balance Report; Design Flow Specifications; Laboratory and System Drawings for Final System Design; • List of Ventilation System Deficiencies uncovered and the details of how (and if) they were satisfactorily resolved. ( ) Operational deficiencies and other problems uncovered by the commissioning process are communicated to the responsible party (i.e., installer, subcontractor, etc.) for prompt correction. 6.3 Commissioning Fume Hoods and Different Types of Systems 6.3.1 Laboratory Fume Hoods ( ) The commissioning plan is available to all potential suppliers and contractors prior to bid ( ) If practical, the exhaust flowrate from hoods 122 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 are tested by measuring the flow in the duct by the hood throat suction method or by flow meter. ( ) If flow measurement in the duct is not practical, velocity at the hood face or opening are measured at a sufficient number of points to obtain a realistic average velocity, and multiplied by the open area in the plane of the velocity measurements to obtain the flowrate. ( ) If the flowrate is more than 10% different from design, corrective actions are taken. 6.3.2 Single Hood CAV Systems ( ) Commissioning tests on single hood, constant air volume (CAV) systems consist of: • • • • Fan Performance Tests; Exhaust Duct Measurements; Hood Performance Tests; and Hood Monitor Calibration. ( ) Fan Performance Tests include measurement of fan speed, fan static pressure, motor speed, and amp draw. ( ) Exhaust duct measurements consist of exhaust flow measurement and hood static pressure measurement. ( ) Hood performance tests consist of tests described in Section 6.1.2. • Verification of proper test, adjustment, and balance of branch exhaust flow and static pressures (exhaust flow and static pressure for each branch shall be recorded after final balancing is complete); • Hood Performance tests as described above in Sections 6.1.2; and • Hood and System Monitor Calibration. 6.3.4 VAV Laboratory Fume Hood Systems ( ) VAV hood systems are commissioned prior to use by laboratory personnel to ensure that all system components function properly and the system operates as designed under all anticipated operating modes (defined under the VAV section). ( ) The commissioning procedures for VAV systems include: • Verification of VAV Sensor Calibration; • VAV Hood Performance Tests; • VAV Laboratory and Ventilation System Tests, and • Verification of System Diversity. 6.3.4.1 VAV Sensor Calibration ( ) VAV sensors are capable of accurate measurement and control within 10% of actual at the design maximum and minimum flow conditions. 6.3.4.2 VAV Hood Performance Tests ( ) The hood monitor is calibrated and adjusted after hood performance has been determined as satisfactory. ( ) Safe operating points are clearly identified for the hood user. 6.3.3 Multiple Hood CAV Systems ( ) Commissioning of multiple hood, constant air volume systems include: • Fan Performance Tests; ( ) In addition to hood performance tests described for evaluation of CAV hood systems, commissioning tests on VAV hood systems include measurement of flow or face velocities at different sash configurations and VAV Response and Stability tests. ( ) Flow or face velocity measurements are conducted at a minimum of two separate sash configurations. ( ) VAV Response and Stability tests include continuous measurements and recording of flow while opening and closing the sashes for each hood 123 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 (calibrated flow sensors or measurement of slot velocity within the hood can be used as an indicator of flow). ( ) VAV Response is sufficient to increase or decrease flow within 90% of the target flow or face velocity in a manner that does not increase potential for escape. 6.3.4.3 VAV Ventilation System Tests ( ) The VAV hood controls provide stable control of flow in the exhaust and supply ducts and variation of flow do not exceed 10% from design at each sash configuration or operating mode. 6.3.4.4 Verification of System Diversity ( ) System diversity is verified prior to use of laboratory fume hoods. ( ) The tests are designed to verify that users will be alerted when system capacity is exceeded and unsafe conditions may exist. ( ) VAV Stability is sufficient to prevent flow variations in excess of 10% from design at each sash configuration or operating mode. 6.3.5 Laboratory Airflow Verification Tests ( ) Tests to verify and commission the laboratory consist of: • Air supply measurements; • General room exhaust flow measurement (if applicable); • Room differential pressure measurement; and • Calculation of the difference between total area (laboratory, zone, etc.) supply and total exhaust. ( ) All ventilation system alarm and monitoring provisions associated with occupant safety are verified for proper functionality. 6.3.5.1 CAV Laboratory Room Tests ( ) These tests ensure that the ventilation system design airflow is being maintained within the allowable tolerance in: • All hood exhausts; • All other bench-top and equipment exhaust provisions that may be present; • The room general exhaust if present; • The room supply; and • Room air cross currents at the hood face opening. ( ) If a specific room differential pressure (dP) has been specified, the dP is measured to ensure that it is within its allowable range. ( ) If a room differential airflow is specified, actual room differential airflow is determined to ensure that is within allowable maximum and minimum limits and in the proper direction. ( ) If the room has more than one ventilation control mode (i.e., occupied/unoccupied, etc.), each individual mode is enabled and applicable parameters (i.e., room supply, room total exhaust, etc.) are performed for each separate mode. ( ) Room ambient conditions (temperature, humidity, air currents, etc.) are also measured to ensure they are being maintained under the conditions specified 6.3.5.2 VAV Laboratory Room Tests ( ) These tests ensure proper performance of the VAV ventilation system and its associated controls such that: • The room general exhaust provides the specified range of airflow. • The room supply provides the specified range of airflow. • Room air cross currents at the laboratory hood face opening are within limits. ( ) If a specified room dP has been specified, the dP is measured to ensure that it is being controlled within its allowable range with all doors 124 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 closed and at minimum and maximum room exhaust airflow. ( ) If a room differential airflow is specified, actual room differential airflow is determined to ensure that it is within allowable maximum and minimum limits and direction at minimum and maximum room exhaust airflow. 7 Work Practices ( ) Hood users are trained in the proper operation and use of hood. ( ) The user establishes work practices that reduce emissions and employee exposures. ( ) If the room has more than one ventilation control mode (i.e., occupied/unoccupied, etc.) conditions are evaluated for each mode. ( ) The user does not modify the interior or exterior components of the hood without the approval of the Chemical Hygiene Officer, Responsible Person, or other appropriate authority in the organization. ( ) Room ambient conditions (temperature, humidity, air currents, etc.) are measured to ensure they are being maintained under the conditions specified. ( ) The following work practices are followed when hazardous materials are used in the hood: ( ) VAV systems are capable of maintaining the offset flow required between exhaust and supply to achieve the desired area pressurization within the desired time specified. 6.4 Ongoing or Routine Hood and System Tests ( ) Routine performance tests are conducted at least annually or whenever a significant change has been made to the operational characteristics of the hood system. ( ) A hood that is found to be operating with an average face velocity more than 10% below the designated average face velocity is labeled as out of service or restricted use and corrective actions are taken to increase flow. ( ) Each hood is posted with a notice giving the date of the routine performance test, and the measured average face velocity. ( ) If it is taken out of service, it is posted with a restricted use or out- of-service notice. ( ) The restricted use notice states the requisite precautions concerning the type of materials permitted or prohibited for use in the hood. ( ) The user does not lean into the hood so that his/her head is inside the plane of the hood, as defined by the sash, without adequate respiratory and personal protection. ( ) Equipment and materials are not placed in the hood so that they block the slots or otherwise interfere with the smooth flow of air into the hood. ( ) All work is conducted at least 6 inches behind the plane of the sash (hood face). ( ) The horizontal sash or panels are not removed. ( ) The hood is not operated without the back baffles in place. ( ) Flammable liquids are not stored permanently in the hood or the cabinet under the hood unless that cabinet meets the requirements of NFPA 30 and NFPA 45 for flammable liquid storage. ( ) The sash or panels are closed to the maximum position possible while still allowing comfortable working conditions. ( ) Hood users are trained to close the sash or panels when the hood is not in use. ( ) The hood user does not operate with the sashes opened beyond the design opening. 125 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 ( ) Pedestrian traffic is restricted near operating hoods. ( ) 8.3 Maintenance personnel are trained and required to use appropriate PPE during work involving potential hazards. ( ) Rapid movement within the hood is discouraged ( ) The hood is not operated unless it is verified that it is working. ( ) Rapid movement of the sash or panels is discouraged. ( ) 7.1 Each hood is posted with a notice giving the date of the last periodic field test. ( ) If the hood failed the performance test, it is taken out of service until repaired, or a restricted use notice is posted on the hood. ( ) The notice states the partially closed sash position necessary for safe/normal operation and any other precaution concerning the type of work and materials permitted or prohibited. ( ) 7.2 Hoods are in operation whenever hazardous volatile materials are being used or stored inside. 8 Preventive Maintenance ( ) Inspection and maintenance follow a written I&M Program developed by the user. ( ) Preventative maintenance is performed on a regularly scheduled basis. ( ) 8.1 Operations served by equipment being shut down for inspection or maintenance are safely discontinued and secured during such maintenance. ( ) Laboratory workers are notified in advance of inspection and maintenance operations. ( ) 8.4 A written work permit system is established whenever the integrity of a potentially contaminated ventilation system is to be breached. ( ) Such work permits are designed to suit the circumstances, and at least address the following factors: ( ) The permit system is overseen by a Responsible Person, as defined in this standard, and is signed by the person(s) to do the work, their supervisor, and any other supervisors affected by the work; ( ) The nature of the work, and the health and safety precautions, aredescribed; ( ) The time and place of the work are described; ( ) The same persons who signed the permit (or their counterparts on a different shift) sign off when the work is complete; ( ) Completed work permits are filed by an appropriate management function and retained for a minimum of 3 years or as specified by individual organizational policy. ( ) 8.5 Records are maintained for all inspections and maintenance. ( ) If testing involves quantitative values, the observed values are recorded. ( ) Inspection forms designed for the several categories of testing are provided and include the normal values for the parameters tested. ( ) 8.2 All toxic or otherwise dangerous materials on or in the vicinity of the subject equipment is removed or cleaned up before maintenance. ( ) 8.6.1 Pressure instrumentation and measurement are in compliance with ANSI/ASHRAE 41.3. Temperature instruments and measurement techniques are in compliance with ANSI/ASHRAE 41.1. ( ) Any hazardous materials and any other debris are cleaned up before operations resume. ( ) All instruments using electrical, electronic, or mechanical components are 126 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 calibrated no longer than 12 months before use or after any possible damage (including impacts with no apparent damage) since the last calibration. ( ) 8.7.3 Blowers, drives, and other critical machine elements are lubricated at intervals and with lubricants recommended by the manufacturer. ( ) The accuracy of a scale used for a given parameter meets the following requirements: ( ) 8.8 Ventilation system management plan addresses the need to provide critical service issues and keep spare parts on hand. ( ( ( ( ( ( ( ( ) Velocity − fpm Accuracy ) Below 100 (5 m/s) 5 fpm (0.25 m/s) ) 100 (5 m/s) and higher 5% of signal ) Pressure − in. wg Accuracy ) 0.1 in. wg (25 Pa) 10% of signal ) 0.5 in. wg (125 Pa) and higher 5% of signal ) Between 25 and 125 Pa, interpolate linearly. ) Pitot-static tube measurements are in accordance with ANSI/ASHRAE 41.7– 1984 (RA 91). ( ) Inclined manometers are selected so that the nominal value of the measured parameter is at least 5% of full scale. U-tube manometers should not be used for pressures less than 0.5 in. wg. ( ) 8.9 All critical service instrumentation has contingency plans in place. 9 Air Cleaning ( ) 9.2 Air-cleaning systems for laboratory exhaust systems, where required, are designed or specified by a Responsible Person to ensure that air-cleaning systems will meet the performance criteria necessary for regulatory compliance. ( ) 9.3 Air-cleaning systems for recirculating general exhaust or hood exhaust from laboratories meet the design and installation requirements of ANSI/AIHA® Z9.7. ( ) Pitot tubes other than standard are calibrated. ( ) 8.6.2 Air contaminant monitors are tested at least monthly or more often, if experience or manufacturer¹s recommendation indicates. ( ) Such testing includes the sensing element, zero drift, and actuation of signals, alarms, and controls. ( ) Continuous air monitors are calibrated per manufacturer¹s specifications or more frequently if experience dictates. ( ) Recirculation of process air is returned to the same room where the process is isolated and control of the process is supervised. ( ) 9.3.1 Air-cleaning filtration systems for recirculating exhaust air contaminated with toxic particulates are filtered through a two-stage particulate filtration system specified as following the standard performance and design criteria of the ASHRAE systems and equipment to meet the objectives of 2.4.1. ( ) 8.6.3 Other instruments (such as voltmeters and tachometers) are checked for function and accuracy against a “known source” before use and follow manufacturer’s ( ) Filter installations are tested for leaks and have all leaks repaired or the filter recommendation, when provided, for periodic calibration. ( ) The flowrate through the filters is maintained at design specifications and does not exceed 100% of the rated flow capacity of the filters. ( ) 8.7.1 Fans, blowers, and drive mechanisms are visually inspected weekly. ( ) 8.7.2 V-belt drives are stopped and inspected monthly for belt tension and signs of belt wear or checking. replaced before use. ( ) 9.3.2 Adsorption or other filtration media used for the collection or retention of gases and vapors are specified for a limited use. ( ) Specific hazardous materials to be collected, 127 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 airflow rate, temperature, and other relevant physical properties of the system are incorporated into the selection of filtration media. ( ) A reliable and adequately sensitive monitoring system is utilized to indicate adsorbent breakthrough. The sensitivity of the monitoring system is a predetermined fraction of the TLV® or appropriate health standard of the contaminant being adsorbed but is not more than 25% of the TLV®. ( ) The breakthrough time of the contaminant, before the effluent reaches no more then 50% of the TLV®, is sufficient, based upon system capacity design to allow a work operation shut down or parallel filter switch-over, thus proving a fresh filter. ( ) For toxic gases and vapors, the filtration system is designed and sized to ensure adequate collection and retention for a worst case scenario when in the event of a spill or other major release. ( ) Adequate warning is provided for personnel to stop work or enact other emergency procedures. unloaded from the air-cleaning system following safe work practices to avoid exposing personnel to hazardous conditions and to ensure proper containment of the filters for final disposal. ( ) Airflow through the filter housing is shut down during filter change-out. ( ) 9.4.1 Recirculation air filters are inspected and tested as per Section 9.3.1 except that provisions are mandatory. ( ) 9.4.2 Activated carbon beds or panels are tested as per Section. 9.3.2 at intervals no longer than 1 month initially and then, based on experience with the particular installation, a schedule is prepared. ( ) 9.4.3 Air pollution control equipment is inspected visually at intervals no longer than 1 week and, if necessary, at shorter intervals. ( ) Specific tests and repairs are in accordance with the manufacturer’srecommendations or are in compliance with applicable regulations. ( ) 9.3.3 When required, contaminated filters are 128 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 • Minimum Design and Operating Specifications APPENDIX 5 Sample Table of Contents for Laboratory Ventilation Management Plan Section IV – System Design and Operation Foreword Purpose Scope • Systems Safety • Laboratory Design Minimum Specifications • Laboratory Ventilation Systems Minimum Specifications PART A – Standards and Procedures Section I Facility Organization • Roles and Responsibilities Section II – Characterizing Hazardous Procedures • Categorizing Laboratory Hazards and Procedures • Effluent Characteristics • Hazard Information Summary Section III – Selection and Performance of Hoods • Laboratory Hoods ° Chemical Fume Hoods ° Biological Safety Cabinets ° Ventilation Balance Enclosures ° Laminar Flow Fume Hoods ° Snorkels ° Canopies ° Ventilation Enclosures ° Gloveboxes Section V – Operational Tests and Maintenance • • • • Recommended Performance Criteria Installation and Commissioning Procedures Routine Test Procedures Maintenance Management Procedures Section VI – Proper Work Practices • Personnel Training Programs • Verifying and Maintaining Work Practices PART B – Laboratory Hood Systems Information Design Drawings Basis of Design Operating Specifications TAB and Commissioning Reports Test and Maintenance Data 129 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA® Z9.5–2012 130 Copyright AIHA® For personal use only. Do not distribute. ANSI/AIHA STANDARDS American National Standard for ANSI/AIHA Z9.5–2012 Laboratory Ventilation BY THE ANSI/AIHA Z9.5 SUBCOMMITTEE Every laboratory will benefit from this outline of laboratory ventilation requirements and practices. Chapters include performance tests, air cleaning, preventive maintenance, and work practices. Five appendices covering definitions, terms and units are included. Those involved in laboratory management, including chemical hygiene officers, campus and institutional health and safety staff, industrial hygienists, and environmental health and safety staff will benefit from this standard. STOCK NUMBER: LVEA12-437 A Publication by American Industrial Hygiene Association Copyright AIHA® For personal use only. Do not distribute.