CODE INTERPRETATION MECKLENBURG COUNTY Mechanical Code Enforcement Code Volume Reference: NC Mechanical Code (2002) Code Chapter Reference: 507.17 Subject: Performance Test Detail Effective Date: 1/1/2003 Prepared/Revision Date: 4/12/06 CODE: 507.17 Performance test. A performance test shall be conducted upon completion and before final approval of the installation of a ventilation system serving commercial food heat-processing appliances. The test shall verify the rate of airflow and proper operation as specified in this chapter. The permit holder shall furnish the necessary test equipment and devices required to perform the tests. INTERPRETATION: The hood/s (Type I only) test shall verify the rate of airflow and proper operation with these additional requirements: 1. All building exhausting equipment (i.e. misc. kitchen exhaust fans, bath fans, etc.) shall be energized and in operation during the performance test. 2. The cooking equipment under the hood/s shall be in place, up to operational heat levels and sufficient smoke/grease generating foods to simulate the desired cooking process. CODE INTERPRETATION 3. The MECKLENBURG COUNTY Mechanical Code Enforcement hood shall capture all exhaust. T-T Puffers (or equal) shall be used during the test to check for spillage of exhaust to the kitchen area. 4. The test shall also include the verifying of actual flow rates versus design flow rates. 5. The Designer or installer shall provide documentation detailing and certification of all test results including the status of the structures systems during the tests (i.e. temperatures, food cooked, fans, etc.) Prepared by: Consistency Team Approved by: Philip B. Edwards, M/P Code Administrator