Uploaded by alberto7.solano

Pompe PVT Atex - Manuale EN - Rev.13 (1)

advertisement
EN
ORIGINAL INSTRUCTIONS
INSTALLATION, USE AND
MAINTENANCE MANUAL
Rev. 13
02-09-2020
PVT 200-280-400-700-1000 ATEX
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
REV. 13
02-09-2020
2020 – Jurop – Azzano Decimo (PN)
Reproduction, electronic storage and dissemination, even partial, are prohibited.
Jurop reserves the right to modify the products described in this manual without prior notice.
Any product names mentioned herein are the trademarks of their respective owners.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
2 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
Index
1.
General warnings
4
9.
Accessories
1.1
Introduction
4
9.1
Muffler: models and dimensions
1.2
Spare part request
4
9.2
Flushing kit
1.3
Warranty terms and conditions
4
SPARE PART DATA SHEET – PVT 200
1.4
Atex Directive
4
2.
Technical Data
2.1
ATEX classification
5
2.2
Arrangements PVT
6
SPARE PART DATA SHEET – PVT 280-400 HDR ATEX (COMPACT)
2.3
Dimensions PVT
6
SPARE PART DATA SHEET – PVT 700-1000 ATEX
2.4
Performances – Operation in vacuum mode
11
2.5
Performances – Operation in pressure mode
2.6
Noise
2.7
Usage Limitations
2.8
Lubrication
3.
Safety and accident prevention
3.1
General recommendations
3.2
Intended Use
3.3
Conveyed Fluid
4.
Installation
4.1
Compulsory accessory
4.2
Checking upon receipt
4.3
Storing in the warehouse
4.4
Handling and installation
4.5
Mounting
4.6
Vacuum – Pressure Line
4.7
Air injection cooling system
4.8
Overheating Alarm
4.9
Installing – Power Drive
5.
Start Up
5.1
Starting-up
5.2
Operating Suggestions
6.
Maintenance
6.1
Ordinary maintenance
6.2
Extraordinary maintenance
7.
Malfunctions:
troubleshooting
pag.
8.
Scrapping
pag.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
pag.
pag.
pag.
SPARE PART DATA SHEET – PVT 200 WITH GEARBOX ATEX
5
SPARE PART DATA SHEET – PVT 280-400 ATEX
SPARE PART DATA SHEET – PVT 700-1000 HDR ATEX (COMPACT)
pag.
pag.
pag.
pag.
3 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
1. General warnings
1.1.
Introduction
• This booklet contains the necessary instructions for a correct
installation, running, use and maintenance of the pump, as well as
some practical suggestions for a safe operating.
• The knowledge of the following pages will grant a long and
trouble-free operation of the pump.
• Following the instructions below contributes to limiting pump repair
expenses by extending its duration, as well as preventing hazardous
situations, thereby increasing its reliability.
• If the pump is driven by an hydraulic motor please refer to
manufacturer's specific manual.
• It is recommended to:
-
Read, understand and apply carefully the instructions before
running the pump.
Keep the booklet at hand and have it known to all operators.
• Below is a brief description of the symbols used in this manual.
Pic. 1.1
1.2.
• Use only genuine spare parts for maintenance and repairs. To
order spare parts, provide the following details:
ATEX CONFORMITY: this symbol comes before texts with
mandatory instructions on installation, use and maintenance of
ATEX certified compressors only. If the instructions preceded by
this symbol are not respected, all the essential requirements
defined in the Directive are not met and, therefore, the
manufacturer shall not be deemed responsible for any damages
resulting from the use of the compressor in potentially explosive
atmospheres.
EXAMPLE:
If these safety rules are not respected, operators can be injured
and the compressor or oilers damaged remarkably.
a) The model (see compressor tag):
PVT400
b) The serial number (see compressor tag):
J90001
c) A description of the parts (see parts list):
GASKET
d) The quantity (see parts list):
n°1 pc
e) Code number of the part (see parts list):
16807 084 00
1.3.
If these safety rules are not respected, the compressor or
system can be damaged.
Warranty terms and conditions
Suggestions for an environment friendly use of the compressor.
• Compliance with the installation, use and maintenance instructions
provided by this manual is crucial for the recognition of warranty
against defective parts.
Useful information for an easy usage and maintenance of the
compressor.
1.4.
• The graphic representations and photographs contained in this
manual are there to illustrate the product in the parts that make it up
and in specific operating phases. Though the model shown in the
manual may differ from the one purchased, the operating principle at
the base of the illustrated operating phase is the same.
• Each PVT could be used if the manufacturer’s plate indicating:
1.
2.
3.
4.
5.
6.
7.
Spare part request
ATEX Directive
• ATEX Directive 2014/34/UE defines the essential requirements
concerning equipment and protective systems intended for use in
potentially explosive atmospheres, which are defined as a mixture of
flammable substances in the form of gases, vapours, mists or dusts.
PVT decompressor with Ex marking are classified for use in potentially
explosive atmospheres as defined in ATEX Directive 2014/34/UE as
Group II, Category 2 and 3.
PVT Model; year of manufacture.
Serial number.
Max pressure.
Max speed.
Max flow (free air).
Power consumption.
ATEX marking (2014/34/UE); name of registered file.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
4 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
2. Technical Data
• PVT vacuum pumps are trilobe pumps specifically designed for suction plants (also high vacuum) that must convey gas free from polluting
substances such as suspended oil or water: this is made possible due to the lack of sliding parts and, therefore, of lubricating oil within the
compression chambers. In addition, PVTs are dry pumps that do not need any auxiliary cooling system, since they are provided with a built-in air
injection cooling system. The specific and accurate lobes profiles as well as shafts junction grant high volumetric efficiency and high flow rates
combined with minimized dimensions and vacuum rates up to 92%.












Trilobe rotary volumetric pump with synchronised phase helical gears.
No oil emission into the atmosphere.
Wear-proof operation, poor maintenance.
Clockwise or counter clockwise rotation on request.
Dynamically balanced rotors to reduce vibrations (A).
Splash lubricated bearings (B) and gears (C) in the front and rear boxes.
Internal combined seals (D): Y-seals and labyrinth seals with PTFE/cast iron rings with venting into the atmosphere.
High temperature seals and gaskets.
Side air injection cooling system with clapet valve (E). This valve opens only in vacuum functioning mode.
Injection muffler (compulsory accessory) and vacuum pump exhaust.
Overheating thermostat on the exhaust port (F).
Removable lifting points (G) and supporting feet (H).
2.1
Manufacturer and marking: ATEX classification
• Jurop SpA, via Crosera n°50, 33082 Azzano Decimo (PN), guarantees the accordance with ATEX 2014/34/UE rules for the following
decompressors: PVT200 Atex, PVT200 M Atex, PVT280 Atex, PVT400 Atex, PVT700 Atex, PVT1000 Atex. The marking affixed on the pump certify
the following classification:
II 2/2G Ex h IIB T3 X Gb/Gb
Therefore, the appliance is:
II
2/2 G
h
IIB
T3
X
Gb/Gb
Suitable for surface installations.
Category 2: it owns a high protection level. Device is intended for use inside and/or outside hazardous areas containing
explosive gases or vapours.
Ignition-protected:
protection by constructional safety;
protection by control of ignition source;
protection by liquid immersion.
Compatible with IIB explosion gases. Hydrogen and acetylene are not included.
Designed to be used with 200°C temperature class: the maximum temperature achieved by the surfaces in contact with the
explosive atmosphere.
Room temperature range for the use of the blower -40°C to +40°C. Follow instructions in the user’s manual.
Internal and / or external protection from sources of ignition in normal operational conditions and in foreseeable failure
conditions.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
5 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
2.2
PVT Arrangements
SX = Counter clockwise rotation
DX = Clockwise rotation
O = Horizontal ports
Standard
Upon request
V = Vertical ports
D = Right hand shaft
S = Left hand shaft
A = Upper shaft
B = Lower shaft
HDR = Hydraulic motor
Note: PVT200 M (with multiplier 3:1) is available only in the following arrangements: PVT DX-O-B and PVT SX-O-B.
2.3
PVT Dimensions
Multiplier (PVT200 only)
Code
Description
G147751100
PVT200 DX-O
MULTIPLIER
PVT200 SX-O
MULTIPLIER
G147851100
Note: PVT200 with multiplier weighs 210 kg.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
6 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
Direct drive system - HDR
Code
Description
G140851102
PVT200 DX-O-B
G630851102
PVT280 DX-O-B
G150851102
PVT400 DX-O-B
G130851102
PVT700 DX-O-B
G510851102
PVT1000 DX-O-B
F148151102
PVT200 DX-O-B-HDR
F638151102
PVT280 DX-O-B-HDR
F158151102
PVT400 DX-O-B-HDR
F138151102
PVT700 DX-O-B-HDR
Code
Description
G140951102
PVT200 SX-O-B
G630951102
PVT280 SX-O-B
G150951102
PVT400 SX-O-B
G130951102
PVT700 SX-O-B
G510951102
PVT1000 SX-O-B
F140951102
PVT200 SX-O-B-HDR
F630951102
PVT280 SX-O-B-HDR
F150951102
PVT400 SX-O-B-HDR
F138051102
PVT700 SX-O-B-HDR
PVT
A
B
C
D
E
F
H
I
K
L
M
200
280
400
700
1000
276
168
176
270
458
155
373
207
M 14
69
266
312
200
200
312
468
167
436
234
M 14
86
231
312
200
236
392
508
203
470
270
M 14
106
231
386
239
532
438
623
234
658
339
M 20
150
344
386
239
532
462
623
234
658
339
M 20
150
344
PVT
N
O
P*
Q
S
T
R
200
328
154
428
215
38 g6
280
350
241
531 (379)
280
50 g6
400
460
261
536 (395)
315
50 g6
700
422
385
828 (512)
364
70 g6
1000
630
385
828 (512)
364
70 g6
-0.009
-0.025
-0.009
-0.025
-0.009
-0.025
-0.010
-0.029
-0.010
-0.029
U
10
41
110
14
53.5
122
14
53.5
155
20
74.5
200
20
74.5
220
Weight
DN100 PN6
UNI EN 1092-1
DN100 PN10
UNI EN 1092-1
DN150 PN10
UNI EN 1092-1
DN175 PN10
UNI EN 1092-1
DN200 PN10
UNI EN 1092-1
160 Kg
192 Kg
240 Kg
640 Kg
780 Kg
* HDR Transmission. Dimensions in brackets refer to the compact model.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
7 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
Code
Description
G140951101
PVT200 SX-O-A
G630951101
PVT280 SX-O-A
G150951101
PVT400 SX-O-A
G130951101
PVT700 SX-O-A
G510951101
PVT1000 SX-O-A
F848051101*
PVT280 SX-O-A-HDR
F858051101*
PVT400 SX-O-A-HDR
* See the previous page to check the
dimensions of the compact hydraulic
version.
Code
Description
G140851101
PVT200 DX-O-A
G630851101
PVT280 DX-O-A
G150851101
PVT400 DX-O-A
G130851101
PVT700 DX-O-A
G510851101
PVT1000 DX-O-A
PVT
A
B
C
D
E
F
H
I
K
L
M
200
280
400
700
1000
276
168
176
270
458
259
373
207
M 14
69
266
312
200
200
312
468
301
436
234
M 14
86
231
312
200
236
392
508
337
470
270
M 14
106
231
386
239
532
438
623
444
658
339
M 20
150
344
386
239
532
462
623
444
658
339
M 20
150
344
PVT
N
O
200
328
154
38 g6
280
350
241
50 g6
400
460
261
50 g6
700
422
385
70 g6
1000
630
385
70 g6
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
R
-0.009
-0.025
-0.009
-0.025
-0.009
-0.025
-0.010
-0.029
-0.010
-0.029
8 / 40
S
T
10
41
110
U
14
53.5
122
14
53.5
155
20
74.5
200
20
74.5
220
Weight
DN100 PN6
UNI EN 1092-1
DN100 PN10
UNI EN 1092-1
DN150 PN10
UNI EN 1092-1
DN175 PN10
UNI EN 1092-1
DN200 PN10
UNI EN 1092-1
160 Kg
192 Kg
240 Kg
640 Kg
780 Kg
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
Code
Description
G140850103
PVT200 DX-V-S
G630850103
PVT280 DX-V-S
G150850103
PVT400 DX-V-S
G130850103
PVT700 DX-V-S
G510850103
PVT1000 DX-V-S
F148150103
PVT200 DX-V-S-HDR
F638150103
PVT280 DX-V-S-HDR
F158150103
PVT400 DX-V-S-HDR
F138150103
PVT700 DX-V-S-HDR
Code
Description
G140950104
PVT200 SX-V-D
G630950104
PVT280 SX-V-D
G150950104
PVT400 SX-V-D
G130950104
PVT700 SX-V-D
G510950104
PVT1000 SX-V-D
F138050104
PVT200 SX-V-D-HDR
F638050104
PVT280 SX-V-D-HDR
F158050104
PVT400 SX-V-D-HDR
F138050104
PVT700 SX-V-D-HDR
PVT
A
B
C
C1
C2
D
E
F
H
I
K
K1
K2
200
280
400
700
1000
52
-
264
316
212
270
381
80
430
168
-
M10
35
67
-
318.6
372
236
312
413
92
468
200
-
M10
35
67
-
318.6
372
236
392
448
92
508
200
-
M10
35
105
-15
745
-
-
438
642
234
339
623
M20
-
-
105
-15
745
-
-
462
642
234
339
623
M20
-
-
PVT
L
M
N
O
P*
Q
200
69
266
328
154
428
215
38 g6
R
280
86
231
350
241
531 (379)
275
50 g6
400
106
231
460
261
536 (395)
315
50 g6
700
150
344
422
385
828 (512)
364
70 g6
1000
150
344
630
385
828 (512)
364
70 g6
-0.009
-0.025
-0.009
-0.025
-0.009
-0.025
-0.010
-0.029
-0.010
-0.029
S
T
10
41
110
U
14
53.5
122
14
53.5
155
20
74.5
200
20
74.5
220
DN100 PN6
UNI EN 1092-1
DN100 PN10
UNI EN 1092-1
DN150 PN10
UNI EN 1092-1
DN175 PN10
UNI EN 1092-1
DN200 PN10
UNI EN 1092-1
Weight
160 Kg
192 Kg
240 Kg
640 Kg
780 Kg
* HDR Transmission. Dimensions in brackets refer to the compact model.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
9 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
Code
Description
G140950103
PVT200 SX-V-S
G630950103
PVT280 SX-V-S
G150950103
PVT400 SX-V-S
G130950103
PVT700 SX-V-S
G510950103
PVT1000 SX-V-S
Code
Description
G140850104
PVT200 DX-V-D
G630850104
PVT280 DX-V-D
G150850104
PVT400 DX-V-D
G130850104
PVT700 DX-V-D
G510850104
PVT1000 DX-V-D
PVT
A
B
C
D
E
F
H
I
K
L
M
200
280
400
700
1000
52
20
280
270
381
155
432
168
M14
69
266
67
11
335
312
413
167
479
200
M14
86
231
67
7
372
392
448
203
515
200
M14
106
231
105
15
745
438
641
234
432
239
M20
150
344
105
15
745
462
641
234
432
239
M20
150
344
PVT
N
O
200
328
154
38 g6
280
350
241
50 g6
400
460
261
50 g6
700
630
385
70 g6
1000
630
385
70 g6
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
R
-0.009
-0.025
-0.009
-0.025
-0.009
-0.025
-0.010
-0.029
-0.010
-0.029
10 / 40
S
T
10
41
110
U
14
53.5
122
14
53.5
155
20
74.5
200
20
74.5
220
Weight
DN100 PN6
UNI EN 1092-1
DN100 PN10
UNI EN 1092-1
DN150 PN10
UNI EN 1092-1
DN175 PN10
UNI EN 1092-1
DN200 PN10
UNI EN 1092-1
160 Kg
192 Kg
240 Kg
640 Kg
780 Kg
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
2.4
Performances – Operation in vacuum mode
ROOM CONDITIONS
Absolute reference pressure: 1013 mbar abs
Exhaust back pressure: 1013 mbar abs.
Ambient reference temperature: 20°C
Tolerance on flow rate and power: ±5%
• PVT200M performances are identical to PVT200 performances. The rotation speed of the PVT200M is 1/3 of the rotation speed showed on the
graphs.
FLOW [m³/h]
POWER [kW]
PVT 200
VACUUM RATE [%]
VACUUM RATE [%]
FLOW [m³/h]
POWER [kW]
PVT 280
VACUUM RATE [%]
VACUUM RATE [%]
VACUUM RATE [%]
VACUUM RATE [%]
FLOW [m³/h]
POWER [kW]
PVT 400
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
11 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
FLOW [m³/h]
POWER [kW]
PVT 700
VACCUM RATE [%]
VACUUM RATE [%]
FLOW [m³/h]
POWER [kW]
PVT 1000
VACUUM RATE [%]
2.5
VACUUM RATE [%]
Performances - Operating in pressure mode
ROOM CONDITIONS
Absolute reference pressure: 1013 mbar abs
Exhaust back pressure: 1013 mbar abs
Ambient reference temperature: 20°C
Tolerance on flow rate and power: ±5%
• PVT operations with exhaust pressure higher than 800 mbar rel. are allowed only in intermittent duty. PVT200M performances are identical to
PVT200 performances. The rotation speed of the PVT200M is 1/3 of the rotation speed showed on the graphs.
FLOW [m³/h]
POWER [kW]
PVT 200
PRESSURE [mbar]
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
PRESSURE [mbar]
12 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
POWER [kW]
FLOW [m³/h]
PVT 280
PRESSURE [mbar]
PRESSURE [mbar]
FLOW [m³/h]
POWER [kW]
PVT 400
PRESSURE [mbar]
PRESSURE [mbar]
FLOW [m³/h]
POWER [kW]
PVT 700
PRESSURE [mbar]
PRESSURE [mbar]
FLOW [m³/h]
POWER [kW]
PVT 1000
PRESSURE [mbar]
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
PRESSURE [mbar]
13 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
2.6.
Noise level
Noise power LwA of the pump alone and relative noise pressure LpA in free field at a distance of 7m from the pump.
Measures according to: UNI EN ISO 9614-2
Measure tolerance: ±2%
PVT 200
Rotation
Speed
Lw (A)
Noise power of the pump alone (without
drive transmission, suction group,
mufflers).
Lp (A)
Noise pressure of the pump alone at 7m in free
field (without drive transmission, suction group,
mufflers).
[dB(A)]
[dB(A)]
vac 50%
91
63
vac 80%
92
64
Δ press 600 mbar
97
69
vac 50%
92
64
vac 80%
93
65
Δ press 600 mbar
98
70
vac 50%
95
67
vac 80%
96
68
Δ press 600 mbar
100
72
vac 50%
96
68
vac 80%
97
69
Δ press 600 mbar
103
75
Vacuum/Pressure
[rpm]
3300
3600
3900
4200
PVT 200 with multiplier
Rotation
Speed
Lw (A)
Lp (A)
Noise power of the pump alone (without
drive transmission, suction group,
mufflers).
Noise pressure of the pump alone at 7m in free
field (without drive transmission, suction group,
mufflers).
[dB(A)]
[dB(A)]
vac 50%
92
64
vac 80%
93
65
Δ press 600 mbar
97
69
vac 50%
93
65
vac 80%
94
66
Δ press 600 mbar
98
70
vac 50%
96
68
vac 80%
97
69
Δ press 600 mbar
101
73
vac 50%
97
69
vac 80%
98
70
Δ press 600 mbar
104
76
Vacuum/Pressure
[rpm]
1100
1200
1300
1400
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
14 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
PVT 280 - 400
Rotation
Speed
Lw (A)
Lp (A)
Noise power of the pump alone (without
drive transmission, suction group,
mufflers).
Noise pressure of the pump alone at 7m in free
field (without drive transmission, suction group,
mufflers).
[dB(A)]
[dB(A)]
vac 50%
93
65
vac 80%
95
67
Δ press 600 mbar
115
87
vac 50%
95
67
vac 80%
96
68
Δ press 600 mbar
118
90
vac 50%
96
68
vac 80%
97
69
Δ press 600 mbar
121
93
vac 50%
98
70
vac 80%
99
71
Δ press 600 mbar
124
96
vac 50%
99
71
vac 80%
100
72
Δ press 600 mbar
126
98
vac 50%
100
72
vac 80%
101
73
Δ press 600 mbar
129
101
Vacuum/Pressure
[rpm]
2300
2500
2700
2900
3100
3300
PVT 700 - 1000
Rotation
Speed
Vacuum/Pressure
[rpm]
1200
1600
2000
2400
Lw (A)
Lp (A)
Noise power of the pump alone (without
drive transmission, suction group,
mufflers).
Noise pressure of the pump alone at 7m in free
field (without drive transmission, suction group,
mufflers).
[dB(A)]
[dB(A)]
vac 50%
98
70
vac 80%
99
71
Δ press 600 mbar
104
76
vac 50%
101
73
vac 80%
102
74
Δ press 600 mbar
106
78
vac 50%
104
76
vac 80%
106
78
Δ press 600 mbar
109
81
vac 50%
107
79
vac 80%
109
81
Δ press 600 mbar
113
85
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
15 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
2.7.
Usage limitations
RPM
Model
P2 (bar rel.) max
P2 -P1 (bar)
T2 (°C)
T2 - T1 (°C)
Max
Max
Max
1
1
160
130
/
0,8
160
130
0,8
1
1
160
130
0,8
/
1
160
130
Min
Max
Max continuos
Max intermittent
PVT 200
2500
4200
0,8
PVT 200 M
850
1400
0,8
PVT 280 - 400
1700
3300
PVT 700 -1000
1000
2400
P2: max continuos: pressure limit for continuos duty
P2 max intermittent: pressure limit for intermittent duty
P1: inlet relative pressure
P2: oulet relative pressure
Vacuum operation: MAX counter pressure discharge + 0.1 bar
T1: inlet air temperature
T2: oulet air temperature
Under pressure operation: MAX vacuum value suction - 0.1 bar
• Rotation speed: running at speed inferior to the minimum level
designed is allowed only for intermittent (not continuous) duty because
the pump may actually get warm quickly.
• Pressure mode: running at a pressure superior to 800 mbar is
allowed only for intermittent duty because the pump may get warm
quickly. (Operations at 1 bar are allowed for a maximum of 20 minutes.
After that period, the pump must be stopped or has to work at free air,
for 20 minutes further). However, never exceed the maximum pressure
of 1000 mbar (800 mbar for PVT200 M).
• Do not exceed the values of the table above.
• In order to avoid overpressures due to an accidental closing of the
valves or to obstructions on the pressure line, a pressure switch or any
2.8.
Room Temperature: -40 / +40 °C
other equal pressure device in compliance with ATEX Directive must
be installed as safety and controlling device (see page 7) with marking
Ex II 2G and temperature classes T3, T4, T5 or T6.
A pressure switch or any other equal pressure
device in compliance with ATEX Directive must
be installed as safety and controlling device with
marking Ex II 2G and temperature classes T3, T4,
T5 or T6.
• The temperature sensor supplied with the pump must be installed.
• Ambient temperature in service: Minimum -40°C; Maximum +40°C
Lubrication
Use synthetic gear oils: TENNEX FACTOR SYNT ISO 150. In case this oil is not available, it is possible to refill the level with a gear oil composed of
polyalphaolefine (PAO):
Room Temp.
Viscosity
Over -10°C
ISO VG 150
ENI
ESSO
SHELL
TOTAL
MOBIL
BLASIA SX
MOBIL
MORILINA S4 B
CARTER SH
Q8
EL GRECO
SHC 629
100
SHC 629
150
150
150
Synthetic lubricant for internal combustion engine is recommended for room temperature lower than 0°C. Use it if temperature is always under 0°C.
Room Temp.
Viscosity
-40°C – 0°C
SAE 0W-30
-20°C - 0°C
ENI
ESSO
SHELL
TOTAL
MOBIL
BP CASTROL
TEXACO HAVOLINE
Q8
iSint Tech
SUPER 3000LD
HELIX Ultra AS
QUARTZ 9000
SUPER 3000LD
EDGE
ULTRA
FORMULA ELITE
0W-30
0W-30
0W-30
0W-30
0W-30
0W-30
0W-30
5W-30
iSint
ULTRON
HELIX ULTRA
CLASSIC
SUPER 3000 X1
VISCO 5000 C
SYNTHETIC
EXCEL
5W-40
5W-40
5W-40
5W-40
5W-40
5W-40
5W-40
5W-40
SAE 5W-40
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
16 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
3. Safety and accident prevention
 Signals prescribing the use of Individual Protection Devices
(IPDs) such as, in this case, the use of gloves and ear
protectors.
 Signals indicating to pay particular attention to the dangers
related to the machine’s components, such as: risk of dragging
in the transmission equipment and contact with hot surfaces.
 Signals indicating specific parts of the machine for an easier
identification, such as: greasing points, oil tanks, etc.
Attention:
Observe the following instructions carefully.
3.1
General recommendations
• When transporting the pump, use proper slinging. Store the pump in
stable places.
• Installation and maintenance must be carried out with the unit
totally disengaged from its drive system and must be performed by
qualified personnel. All the operations such as installation, storage,
start up maintenance and repair, must be done in explosive
atmosphere absence.
Attention: all the operations must be done in
explosive atmosphere absence.
• Use adequate clothing (avoid ties, loose sleeves, necklaces and so
on) and suitable protection equipment (gloves, protection glasses,
boots...).
• Before each maintenance operation, stop the pump and restore the
atmospheric pressure.
• Make sure that all the parts of the unit are idle and cool, before
performing any maintenance operation.
• To prevent errors and hazardous situations, establish what each
operator is responsible for in the different maintenance operations
• Do not start the machine if the protection devices provided for
transmissions are removed. Replace damaged parts.
• Final manufacturer must make the transmission inaccessible by
means of a fixed guard or interlocked movable guard.
• Operators working nearby must avoid prolonged exposure to the
noise emitted by the aspirator, if not equipped with the proper earprotection devices. IPDs recommended: ear protectors.
• When the pump is running, some parts may reach very high
temperatures (above 70°C). Use all necessary precautions to avoid
contact.
• Avoid accidental suction of solids: solids may be projected at high
speed through the exhaust manifold and cause injures. During suction
use suitable filters.
• Pressure relief valve: point the air flux away from the operators.
• Do not use the aspirator over its designed limits: the machine may
be damage and the operator may be injured.
Do not exceed the power supply parameters
indicated in the technical tables (see par. 2.4 2.7).
• Based on the final use of the decompressor, the insertion in the
housing machine and the typology of the same, the designer of the
housing machine must apply safety signals (pictograms) to warn the
operator on the risk still present. These pictograms essentially refer to
three categories:
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
3.2
Intended use
• PVT pump are 3 lobe blowers specifically designed for vacuum
plants that must convey gas free from polluting substances, oil or
water: this is made possible due to the lack of sliding parts, and
therefore oil lubrication within the compression chambers.
• Before starting-up the pump, operators have to check the
compatibility between explosive atmosphere with maximum
compression values – allowed for compressor – and maximum
temperatures of exhaust, (see par. 2.6).
Attention: check
compatibility.
the
aspirated
material
• Operators must prevent the entry of liquid into the compressor
• An adequate safety filter with a filtering capacity equal to:


150 μm must be installed on the vacuum line of PVT200, 700 and
1000.
200 μm must be installed on the vacuum line of PVT280 and 400.
Attention: an adequate safety filter with a filtering
capacity equal to 150 μm (for PVT200-700-1000)
or 200 μm (for PVT280-400) must be installed on
the vacuum line.
• Liquids or solids infiltrations can seriously damage the
compressor.
Attention: liquids or solids infiltrations can
seriously damage the vacuum pump.
• Do not run the compressor over its designed operating limits (see
par. 2.4 - 2.7): it may break and transmission can be damaged.
3.3
Conveyed fluids
• The PVT pump is suitable for conveying filtered air. Before
conveying other kind of gases, verify compatibility with pumps’s
characteristics.
• Please contact Jurop’s Technical dept. if necessary.
17 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
4. Installation
4.1
Compulsory accessories
• The correct installation of the decompressors PVT requires the
following accessories:
 Suction silencer (for PVT Atex);
 Discharge silencer (for PVT Atex);
 Overheating alarm to connect to the thermostat on the exhaust
port;
 An adequate safety filter and/or secondary shutoff on the
vacuum line to avoid suction of foreign bodies or liquids.
 Safety filter with a filtering capacity equal to 150 μm (for
PVT200-700-1000) or 200 μm (for PVT280-400) must be
installed on the vacuum line, on the injection line and on
discharge line (if compressor has to generate pressure in the
tank). In this way it is possible to prevent the entrance of
materials with dimensions higher than a 0,15 mm (for PVT200700-1000) and 0,20 mm (for PVT280-400).
Attention: avoid the entrance of materials with
dimensions higher than a 0,15 mm (for PVT200700-1000) and 0,20 mm (for PVT280-400).
 Adequate overpressure safety valves.
4.2
Checking upon receipt
• When the goods are delivered, make sure that all parts listed on
the delivery note are in perfect condition and have suffered no damage
during shipping.
• Remove the parts of the packaging that can be dangerous if
sucked by the pump.
• Make sure the pump has its identification plate affixed on the front
cover. Pumps without such identification are to be considered
anonymous and potentially dangerous: in such an event, they must not
be used, otherwise the manufacturer will be deemed free from any
liability whatsoever.
4.3
• Do not lift the packaging or the machine when moving more than
50 cm from the ground. Proceed with the final lifting only near the
installation point.
• Harness the machine with suitable straps / chains near the main
body, paying attention to the position of the mass centre of gravity to
ensure the load stability.
Warning: do not stand under the machine when it
is lifted during the installation.
4.5
• All mounting operations must be carried out in absence of any
potentially explosive atmosphere:
Attention: all the operations must be carried out
in absence of explosive atmosphere.
• When the pump is installed it must be accessible for maintenance
and fitted, with vibration adsorbing pads, to a bearing frame or level
base (Max. admitted angle 3° in all the directions).
• The size of the frame must be suitable to support the pump weight
and avoid bending. It is recommended to install the pump on vibration
adsorbing pads to reduce the noise and vibrations produced during its
operation.
• Leave enough space around the pump to allow the free circulation
of air for cooling; avoid exposure to dirt and debris.
• Leave enough room to access the oil drainage, filling and checking
ports (see Fig. 4.1).
• The oil level control and drainage plugs are mounted correctly
during the final inspection in the factory. Do not change their position.
Legend
Storing in the warehouse
• If the pump will not be installed inside a short time after delivery:
- Remove the guards from the ports and spray a film of
protective oil over the inner surfaces of the body, rotors and
sides. Then attach again the guards;
- Store in a closed and dry place. Renew the preserving oil
periodically.
To temporarily store a used pump, follow the instructions below:
- Thoroughly clean the pump.
- Equip the pump with suitable anti-corrosion protection.
4.4
Mounting
L
Oil level (front and rear gearboxes)
SO
Oil drainage (front and rear gearboxes)
SS
Gearbox vent (front and rear gearboxes)
ST
Seals vent (front and rear gearboxes)
CO
Filler cap (front and rear gearboxes)
FD
Drainage hole
PVT – HORIZONTAL PORTS
Handling and installation
• Before each movement, verify that the lifting equipment has a
suitable capacity (check the weight of the decompressor, possibly
showed in this manual, in the paragraphs 2.3).
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
18 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
PVT – VERTICAL PORTS
PVT200 WITH GEARBOX
Fig. 4.1
• Oil levels, filler caps and oil drainages are individual for the front
and rear gearboxes.
Oil levels, filler caps and oil drainages are
individual for the front and rear gearboxes.
• The rotation direction of the vacuum pump determines the room
taken up by the injection system as well as the flow direction (see
Section 2.2 “Dimensions”). Any changes made to rotation direction or
to the assembly position must be agreed with our “Technical
Assistance”.
Any changes made to rotation direction or to the
assembly position must be agreed with our
Jurop.
• Ground the pump so that it does not accumulate static electricity
and make sure that paint does not hinder the way.
• Keep suction filter clean: obstructions may lead to noticeably
reduced performance.
• Keep injection filter clean: obstructions may reduce the air
injection cooling performance and cause overheating of the pump.
• Do not embed nor cover the pump.
• The base must not lead heat towards the machine while it is
running.
• In the event that the decompressor is electrically isolated, connect
it to the ground or make it equipotential with the housing machine.
Check that the paint does not prevent its passage.
4.6
• Remove the port guards before mounting. The pipes and
components of the whole line must be clean.
• Avoid constrictions and tight curves where they are not necessary.
• The exhaust pipes can reach high temperatures. Protect them
adequately from the operator reach.
• A clapet valve on suction pipe avoids rotation in the opposite
direction when the vacuum pump is stopped.
• Over-pressure safety relief valve on the vacuum line: install it
close to the vacuum pump. Valve relief flow rate must prevent the PVT
pump from exceeding a pressure of 1800 mbar or, in any case, the
maximum allowed by the system (see par. 2.7). Do not interpose
shutoff valves on the line between the pump and the safety relief valve.
• Manometer should be placed on a distance not superior to 350
mm from the compressor’s escape valve.
• If necessary apply:
 A second shutoff valve or suction filter. Liquids and materials
must never reach the pump;
 A venting valve on the suction line, controlled by the
thermostat: when the vacuum pump is overheating, this valve
will open up a direct connection with the atmosphere and
consequently the pump will suck fresh air from the outside for a
better cooling (a 2” valve can be enough for a good cooling
without losing too much vacuum rate). Install a silencer filter;
 A 4-way change-over valve to obtain alternatively vacuum or
pressure in the system (this is not required if the pump is used
only for vacuum or only for pressure).
• For use in potentially explosive atmospheres, all line components
with potential ignition sources must comply with ATEX Directive and be
marked at least Ex II 2G with temperature classes T3, T4, T5 or T6.
The installer must certify that the whole system is pursuant to ATEX
before the machine is first run in potentially explosive atmospheres. All
components of the vacuum line supplied by Jurop are not provided with
the ATEX certificate.
All line components with potential ignition
sources must comply with ATEX Directive and be
marked at least Ex II 2G with temperature classes
T3, T4, T5 or T6.
• All components of the vacuum line supplied by Jurop are not
provided with the ATEX certificate.
Both suction filter (pos. 7) and silencer (pos. 6)
must have a filtering capacity equal to 150 µm.
VACUUM – PRESSURE LINE COMPONENTS
Vacuum –Pressure Line
• See Fig. 4.2 e 4.3.
• The diameter of the vacuum and pressure line pipes must be
suitable for the pump’s flow rate (approximate average speed is 15-30
m/s).
• The weight or dimensions of the pipes must in no way stress the
vacuum pump body. Use high temperature resistant rubber sleeves.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
19 / 40
1
Vacuum Pump
2
Clapet Valve
3
4-way change-over valve (optional)
4
Overheating safety venting valve (optional)
5
Over-pressure safety relief valve
6
Over-pressure safety relief valve
7
Suction filter
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
Vacuum – Pressure Line – Vacuum operation
Vacuum – Pressure Line – Pressure operation
7
3
3
5
1
2
2
6
6
5
4
Fig. 4.2
1
4
Fig.4.3
• By turning the 4-way valve changeover by 90 deg. (from the
vacuum position), the pump can suck air from the exhaust silencer to
pressurize the tank. In this case, it is recommended to control the pump
speed in order to avoid dangerous overpressure on the line.
• In case of overheating while working in pressure mode, opening
the safety venting valve mounted on suction line will not cool down the
pump. For a proper cooling the pump drive system must be stopped.
• It is recommended to vent the vacuum tank and restore the
atmospheric pressure:
 Before servicing the vacuum pump or its drive system. The
pressure difference between inlet/outlet ports can make the
machine start turning automatically;
 Before starting the machine again: otherwise, it would require a
higher starting torque.
Vacuum rate control
• No special vacuum limits are designed for the suction port. It is
however important to reduce the vacuum rate below 200 mbar (vac.
rate < 20%) when the thermostat starts operating, thus indicating that
the pump is overheating.
• It is therefore important to install a gate, controlled by the
thermostat, that will allow the air which has been taken from the non
classified zone (EN 99/92/CE) to enter the pipe under vacuum.
• The valve and its control system must comply with the ATEX
Directive and be marked at least Ex II 2G with temperature classes T3,
T4, T5 or T6 if applied in the same area as the pump.
The valve and its control system must comply with
the ATEX Directive and be marked at least Ex II 2G
with temperature classes T3, T4, T5 or T6 if applied in
the same area as the pump.
In case of overheating while working in pressure
mode, opening the safety venting valve mounted
on suction line will not cool down the pump.
4.7
Pressure control
• The maximum pressure inside the line between vacuum pump and
tank must be limited by applying one of the following devices complying
with ATEX Directive and marked at least Ex II 2G with temperature
classes T3, T4, T5 or T6:
 An external pressure sensor on delivery line, which will stop
the machine and restore the balance between the pressures in
the system when the max. value allowed of 1.8 absolute bars
is exceeded;
 An over-pressure safety relief valve on delivery line. It must
discharge all the flow produced at the maximum operating
pressure allowed onto a non classified zone (EN 99/92/EC).
The maximum pressure inside the line between
vacuum pump and tank must be limited by
applying one of the following devices complying
with ATEX Directive and marked at least Ex II 2G
with temperature classes T3, T4, T5 or T6.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
Air injection cooling system
• Operating only in vacuum mode.
• Use only the specific - standard or side compact - air injection
muffler for PVTs.
• The minimum pipeline inner diameter (Di) of the injection system
must be:
MODEL
INNER DIAMETER
PVT 200
98 mm
PVT 280
110 mm
PVT 400
127 mm
PVT 700
160 mm
PVT 1000
190 mm
• The silencer should be mounted as close as possible to the
vacuum pump (max. 1-1.5 m) and in a position protected against debris
and water:
 Avoid tight curves;
 Avoid pumping nearby heat sources;
 Observe tilt angle of clapet valve.
20 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
• Check the muffler suction port for cleanliness every week.
Remove all the filth that obstructs the air flow
The injection silencers supplied by Jurop are not
provided with the Atex certificate. Suction filter
(for PVT Atex) with a filtering capacity equal to
150 μm must be used.
• Working conditions which cause a continuous activation of the
protection must not repeat over time. The operator must quickly detect
and solve the cause of the anomalous overheating based on the
indications found in chapter “Operation Anomalies, with the machine
stopped and in the absence of an explosive atmosphere.
• In any case, all operations must be carried out in compliance with
the safety requirements provided in the Machinery Directive.
• An inefficient AIR injection could cause the vacuum pump
overheating during the vacuum operation.
Attention: an inefficient AIR injection could cause
the vacuum pump overheating during the
vacuum operation.
• Max injection line vacuum value: - 0.1 bar. Measurement taken
near the pump injection vent.
45°
STANDARD AIR
INJECTION MUFFLER
Safety
thermostat
supplied
with
the
pumps/compressors is certified SIL 2 (IEC
61508). The installer must verify the overheating
protection system reliability and establish the
correct time interval for tests.
SIDE COMPACT AIR
INJECTION MUFFLER
Overheating alarm
MAX temperature at the exhaust: 160°C.
• PVT vacuum pumps are supplied with a safety system which
prevents the formation of sources of ignition caused by overheating:
 Temperature probe PT100 installed on the discharge manifold.
 Signal converter programmed to intervene at safety
temperature.
Caution: follow the indications to install the
probe and converter.
• Once the maximum operation temperature is reached, the outlet
contacts of the programmed converter change status and must cause
one of the following events:
 The machine will be stopped;
 A certified vacuum relief valve place in a safe zone – which is
compatible with the pump Atex classification – will be opened
for 2 minutes. If temperature does not fall below the threshold
value after that period, the machine will stop. The valve must
grant such an air flow in order to decrease the vacuum rate
below 20%.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
• Safety thermostat supplied with the pumps is certified SIL 2 (IEC
61508). The installer must verify the overheating protection system (eg.
Electro valves, pneumatic switches) reliability and establish the correct
time interval for tests.
CHECK
THE
FLOW
DIRECTION
AND
THE
CLAPET
VALVE
POSITIONING
Fig. 4.4
4.8
Attention: if maximum pressure or temperature
allowed are exceeded, pump can be damaged.
Check the cause and remove it.
Protection type “b2” UNI EN/ISO 80079-37:2016
• Reliability evaluation of the discharge temperature control system
comprising:
 (1) temperature probe (RTD-3 wires) PT100, 3 wires, ATEX.
 (2) programmed converter with built-in safety.
 (3) a contactor, i.e. final actuator to be defined in order to
obtain a SIF (Safety Instrumented Function) with a Functional
Safety of level SIL 2 or in accordance with IEC 61511 for “Low
demand mode of operation”.
• The converter (2) is certified in accordance with IEC 61511 for
“Low demand mode of operation” therefore the SIF will be defined only
for “Low demand mode of operation” even though (1) the temperature
probe also allows “High and continuous demand mode of operation”,
while (3) the final actuator can be for Low or for High and continuous
demand mode of operation.
• Based on the certificates of (1) and (2) and based on the
instructions provided for the installation it can be stated that:
a)
for (1) RTD-3 wires, in “Low stress” conditions and “Single
RTD 1oo1” configuration: PFDavg (1 year) = 1.58 E-03 ; PFDavg
(3 years) = 4.74 E-03 ; PFDavg (5 years) = 7.88 E-03 which implies
SIL 2 at 1 year, 3 and 5 years according to IEC 61511 for “Low
demand mode of operation”.
b)
for (2) converter with “relay output contacts in series
connection” and Alarm A and Alarm B trip amplifiers programmed
with the same configuration: PFDavg (1 year) = 2.86 E-04; PFDavg
(3 years) = 8.58 E-04; PFDavg (5 years) = 1.43 E-03; PFDavg (6
years) = 1.70 E-03 which implies a SIL 2 at 1 year, 3, 5 and 6 years
according to IEC 61511 for “Low demand mode of operation”.
c)
at least SIL2 is required to have a SIF SIL 2 for the (3) final
actuator. The coil of the final actuator must be supplied by means
of a power line which passes through the relay contacts of
D1073S. The relay contacts of D1073S are normally closed if there
are no alarms, therefore the coil of the actuator is energised
closing the relative contacts and operating the compressor. In case
21 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
Only for operations conducted with room
temperature between -10° and -40°C, Jurop (on
request) provide a second temperature converter
to hook up with safety thermostat.
4.9
A) Belt Drive
T MAX
CHECK BELT TENSION
DP MIN
of maximum temperature alarm, the relay contact of D1073S are
opened and the coil of the actuator is de-energised opening the
relative contacts and stopping the operation of the compressor.
d)
SIF: SIL 2: T-proof 3 years: PFDavg_SIF (3 years) =
PFDavg_(1) (3 years) + PFDavg_(2) (3 years) + PFDavg_(3) (3
years) = 4.74 E-03 + 8.58 E-04 + PFDavg_(3) (3 years) < 1 E-02
limit imposed to maintain SIL 2; i.e. (3) the final actuator must have
PFDavg_(3) (3 years) < 4.40 E-03 in order to guarantee a SIF SIL
2 for 3 years. Every 3 years, to guarantee the reset of the initial SIL
2 conditions of the SIF, the T-proof procedure of the various
products which compose the SIF must be performed, as indicated
in the relative functional safety manuals of these products.
• Furthermore, according to standard UNI/EN 80079-37:2016.
HFT: 1 The device must be safe with a single fault.
• To guarantee a compliant degree of reliability, the device must be
protected with a redundant system doubling the sensor, programmable
converter and actuator.
• Only for operations conducted with room temperature between 10° and -40°C, Jurop (on request) provide a second temperature
converter to hook up with safety thermostat. When working lowest
temperature is reached (+20°C), the output contacts of the thermostat
will change status. Pump could get in touch with flammable
atmosphere.
KEEP AXELS PARALLEL
ALINGN PULLEY GROVES
AND BELTS
Fig. 4.5
• Install a suitable pulley on the smooth shaft as close as possible
to the compressor in order to avoid excessive bending stress on the
drive shaft.
• Install a suitable pulley on the smooth shaft as close as possible
to the compressor. Taper lock pulley are suggested.
• Do not use driven or driving pulleys with a pitch diameter than
shown in the table below. Small pulleys require a high belt tension
which may cause premature wear to the bearing or transmission
damages.
• Let the air circulate freely to cool down the compressor. The
safety guards shall ensure adequate ventilation.
• A limited speed ratio allows a longer belts life while reducing
stress on the shafts. When possible, prefer:
 Pulleys with a pitch diameter bigger than the one indicated;
 Motors or power take-offs with a speed similar to the one of the
compressor.
Drive system – Power transmission
• For the machines of this series, the allowed power transmissions
are:
 Direct transmission;
 Oil hydraulic transmission (HDR).
• For use in potentially explosive atmospheres, all drive components
with potential ignition sources must comply with ATEX Directive and be
marked at least Ex II 2G with temperature classes T3, T4, T5 or T6.
Attention: For use in potentially explosive
atmospheres, all drive components with potential
ignition sources must comply with ATEX
Directive and be marked at least Ex II 2G with
temperature classes T3, T4, T5 or T6.
Max speed (rpm)
T. max (N)
L. max (mm)
Drive min. pulley p. diam. (mm)
N° groves
Belts
PVT 200
Model
4200
3000
50
180
4 x SPA
XPA
PVT 200 MOLT.
1400
3800
35
250
4 x SPB
XPB
PVT 280
3300
3500
45
180
4 x SPB
XPB
PVT 400
< 2800
5000
55
160
5 x SPB
SPBX
PVT 400
> 2800 (MAX 3000)
5000
55
180
5 x SPB
SPBX
PVT 700
2400
7500
70
250
4 x SPC
XPC
PVT 1000
2400
10500
80
250
5 x SPC
XPC
Min Pitch Diam.: minimum pitch diameter of the smaller pulley.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
22 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
B) Hydraulic Drive
• The PVT HDR pump is equipped with a fixed (without flushing valve) displacement high pressure motor suitable for open or closed type oil
circuits
Displacement Operating pres.
(cc/rev)
Max (bar)
Model
Max pres.
draining line
(bar)
Fluid
Filtration
Optimum
viscosity
Housing
Max viscosity
temperature
cSt
max °C (*)
1
HLP
20/18/13
15 - 30
1000
80
PVT200 HDR
30
420
PVT 280 HDR
40 (40)
410 (410)
1 (1)
HLP
20/18/13
15 - 30
1000
80 (80)
PVT400 HDR
60 (60)
420 (420)
1 (1.5)
HLP
20/18/13
15 - 30
1000
80 (90)
PVT700 HDR
110 (90)
420 (350)
1 (1)
HLP
20/18/13
15 - 30
1000
80 (80)
PVT1000 HDR
125 (125)
420 (400)
1 (2)
HLP
20/18/13
15 - 30
1000
80 (90)
(*)
()
Temperature of oil, used in the main cicuit.
HDR Transmission. The values in brackets refer to the compact model
• Oil flow and pressure: to be defined according to the vacuum
pump performance required, i.e. speed rotation and operating
pressure).
• Fluid: mineral oil for plumbing HLP (DIN51524).
• Filtration: oil contamination class ISO 20/18/13, ISO 4406.
• Check circuit connections: they must be applied in the same
rotation direction of the vacuum pump (see Fig. 4.6).
• Drainage: connect this line to the oil tank to make sure the motor
never operates without oil. Discharge into the tank under free surface
or bend the pipe into a U-shape.
DRAIN
(1)
Attention: avoid rotation in the opposite direction
to the pump stopping because that may damage
the motor.
• In order to check the rotation speed, an inductive sensor must be
applied on the front box (use the foreseen opening) and connected to
an adequate electronic revolution counter or the servicing holes on the
bell (if present) must be used.
• The inductive sensor must be powered at 12-24V DC from the rev
counter.
HDR pump
Z (number of teeth of the sensor gear)
PVT 200 … 700
4
PVT 1000
2
DRAIN
HDR pump
Drain thread
In/Out flange
G 7/8” - 14
SAE ¾” 6000psi
PVT 280 HDR
G 3/4
SAE ¾” 6000psi
PVT 400 HDR
M22x1.5
SAE ¾” 6000psi
PVT 700 HDR
M18x1.5
SAE 1¼” 6000psi
PVT 1000 HDR
M18x1.5
SAE 1¼” 6000psi
PVT 200 HDR
OIL
LEVEL
(1)
OIL TANK
COUNTER CLOCKWISE
ROTATION
• The machine/system manufacturer is responsible for dimensioning
the lines.
CLOCKWISE
ROTATION
(1) REFILL WITH OIL BEFORE FIRST START
Pic. 4.6
The machine/system manufacturer is responsible
for dimensioning the lines.
• Starting up: make sure that the system is well cleaned and pour
oil into tank and motor housing (this operation is necessary to lubricate
the inner bearings).
• Vent the circuit off and adjust the overpressure safety valve to the
lowest value possible.
• Check the oil tank level.
• Increase pressure and rotation speed until operating values are
reached.
• Avoid rotation in the opposite direction to the pump stopping
because that may damage the motor both with open and closed circuits
(see also Section “Vacuum-Pressure Line”). Protect the hydraulic
circuit against overpressures.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
23 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
REV. 13
02-09-2020
5. Start-up
5.1
Starting-up
1. Before washing the pump, be sure that it has cooled down. It
should be either run with free port (vac. rate 0%) for some
minutes or stopped;
• Check the oil level in the front and rear tanks.
• Check that all protection and safety devices as well as the
overheating alarm are correctly installed.
• Check that no obstacles obstruct the vacuum and pressure line or
the air injection cooling system.
• Check rotation direction: open all system valves and start running
at slow speed.
• Rotation in the wrong direction is allowed at low speed: line and/or
pump may be damaged.
Attention: do not carry out this operation on very
hot pumps (for example after a working day) until
they have cooled down.
2. Use 1-2 litres of water mixed with a non-flammable detergent with
passivating and protective properties. We suggest you use Henkel
Bonderite C-NE 5225, 5% concentration in water;
3. Use one of the sleeves on the suction line to introduce some
detergent;
4. Start the pump at low speed (app. 1000 rpm for PVT200-280400; 500 rpm for PVT200M and PVT700) leaving all suction
valves on the tank open in order to keep the vacuum rate low
(max vac. rate 10-20%). Pour in the detergent mix very slowly;
5. The detergent mix stays suspended in the air and so it will be
expelled through the exhaust silencer. Now the internal pump
components must be dried to prevent oxidation. Once the detergent
mix is finished, continue running the pump with free port for a few
minutes, then operate the vent and valves to increase the vacuum
rate up to MAX 50-60% for a couple of minutes. With this operation
the remaining water inside the pump will be completely dried by the
heated air while the detergent will protect it and prevent the cast
iron internal parts from oxidizing;
6. Washing the pump with this detergent guarantees a protection
after some days of inoperativity. If the pump is not used for more
than two weeks, after having washed and dried the inner parts as
described above, it is recommended to suck slowly 200 cc antirust and water-repellent protective oil (or, if not available, a very
fluid gear oil).
Attention: rotation in the wrong direction is
allowed at low speed: line and/or pump may be
damaged.
• Close the valves and increase operating pressure or vacuum rate.
• Check loading and operating speed for vibrations or unusual
noises.
• Check overheating alarm for efficiency.
5.2
Operating precautions
• The manufacturer declines all responsibility for damages caused if
these installation, operating and maintenance instructions are
disregarded.
• When the overheating alarm triggers because maximum operating
temperature has been reached:
1. Stop the vacuum pump and wait until it has cooled down;
2. if possible, in order to reduce the time needed for proper cooling,
run the pump at a vacuum rate lower than 30% - if working in
vacuum mode - or at an exhaust pressure lower than 200 mbar
rel. - if working in pressure mode - for the time necessary to
restore the alarm. To this purpose, provide an adequate opening
which is in communication with the atmosphere on the
suction/discharge line and is operated by a valve regulated by the
alarm system itself;
3. Work can be started again only when the temperature has
returned to normal values;
4. If the alarm often triggers during normal use, check the conditions
of use (temperature, pressures, and speed) as well as of the
system.
• When ambient temperatures are very low (like in winter for
example), exhaust temperatures are lower than usual and the
overheating alarm will not trigger even if you are working at high speed
and with high vacuum rates. We recommend not exceeding a
temperature difference of 130°C between incoming and outgoing air in
order to avoid anomalous deformation of the components and to
prevent the vacuum pump from being blocked. Avoid continuous duty
under such conditions even if the overheating alarm does not trigger.
• After operating in dusty environments, after accidental sucking of
liquids inside the pump or before a long inoperativity period it is
recommended to perform an internal wash-up of the pump:
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
Attention: do not carry out this operation on very
hot pumps (for example after a working day) until
they have cooled down.
• Do not suck fluids with ignition temperature lower than 250°C,
above all if the pump is not cold. Prevent the fluids which are used to
wash the internal parts of pump or vacuum line from accumulating.
Attention: avoid suction of fluids with ignition
temperature lower than 250°C.
• Do not convey the exceeding flow outlet towards the suction port.
• Control the air flow by adjusting the rotation speed: do not use the
safety relief valve to discharge the exceeding flow.
• Do not squeeze the hoses/pipes.
• When stopping the pump, avoid rotation in the opposite direction.
In fact, the difference in pressure between delivery and suction ports
can make the rotors turning. Use non-return valves on the line (see
Section “Vacuum – Pressure Line”).
• If the decompressor operates in vacuum or under pressure with a
capacity environment (such as a cistern) and is not equipped with the
“suction unit” accessory, it is advisable to intercept the working line of
the machine when it is stopped, to prevent contrary rotations until the
24 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
rebalancing of the pressures. The interception can take place through a
controlled valve or an automatic unidirectional valve (swing valve).
• Avoid starting the pump under load: motor and drive system can be
excessively stressed.
• Please contact Jurop Technical Service for use in high temperature
atmospheres under conditions approaching the limit values (high
speed, vacuum rate higher than that designed for continuous duty) or
for suction of air with traces of other gases and dusts.
Please contact Jurop Technical Service for use in
high temperature atmospheres under conditions
approaching the limit values.
• Use the vacuum pump in potentially explosive atmospheres only
with ambient temperature ranging from –40 / +40°C.
Attention: use the vacuum pump in potentially
explosive atmospheres only with ambient
temperature ranging from –40 / +40°C.
• With ambient temperature ranging from -20°C and -40°C, the
below preventative measures must be followed:
1. Start up the pump in a safe zone:
- Avoid fast increases of speed, they cause stress.
- Avoid higher starting torque.
- Do not start running the pump under load.
When starting from an idled equipment, it’s mandatory to limit
the ratio between torque at start Ms and maximum absorbed
torque M (Ms/M = 2.5 Max).
2. To avoid overloads, further speed changes must be achieved
by applying progressively a Ma torque. Limit ratio between
torque at start Ma and maximum absorbed torque M (Ma/M =
2.0 Max).
• When the ambient temperature is within the range from -40°C to
+40°C:
1. When selecting the transmission system do not oversize it.
Some common examples:
 Transmission using a clutch: apply the minimum safety factor
suggested by manufacturer. Please note that oversized
clutches engage very fast.
 Transmission using an electric motor: the power at shaft must
be commensurated with the absorbed power by the suction
unit. Please note that oversized motors supply a very high
torque at start.
2. Start: torque at start Ms/M = 2.5 MAX.
3. Further speed-up: Ma/M = 2.0 MAX.
M: maximum torque absorbed by the suction unit (pressure
Δp=1000 mbar).
Attention: with ambient temperature ranging from
-20°C and -40°C, start up the pump in a safe zone.
Torque
PVT200
PVT280
PVT400
PVT700
PVT100
M (Nm)
96
174
246
520
660
Ms (Nm)
240
435
615
1300
1650
Ma (Nm)
192
348
492
1040
1320
2. Warm up the machine in a safe zone at the minimum speed
(see par. 2.7) till temperature reach +20°C.
3. On request, Jurop provide a second temperature converter
(factory-adjusted), which advise you when working lowest
temperature is reached.
4. Working lowest temperature value is +20°C, both for the first
start-up and for the further after a rest period. Before entering in
a flammable atmosphere, verify discharge temperature.
• When the ambient temperature is within the range from -20°C to
-10°C, start is permitted in a classified zone if complying with following
precautions:
1. Avoid any start under load: during speed-up the suction unit
must work at no more than 20% vacuum rate or at no more
than 200 mbar gauge pressure.
2. Apply progressively the torque.
When starting from an idled equipment, it’s mandatory to limit
the ratio between torque at start Ms and maximum absorbed
torque M: (Ms/M = 2.5 Max).
3. To avoid overloads, further speed changes must be achieved
by applying progressively a Ma torque. Limit the ratio between
torque at start Ma and maximum absorbed torque M (Ma/M =
2.0 Max).
• When the ambient temperature is within the range -10°C to +40°C,
start is permitted in a classified zone if complying with following
precautions:
1. Apply progressively the torque.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
25 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
6. Maintenance
6.1. Ordinary maintenance
• Any interventions must be performed when the machine is cold, stopped and switched off.
• Installation and maintenance must be operated only by qualified personnel wearing the proper clothes and the necessary tools.
• Use suitable protection equipment (gloves, protection glasses, boots...).
• In the following table summarizes the main controls to be performed and the frequency of intervention.
Operating conditions
Maintenance Area
Vacuum line
OPERATING
Transmission / Pump
Vacuum line
STANDSTILL
Pump
Overall
Checking
8H
50H
500H
1000H
Check safety valve (non-return valve)
Working pressure
Rotating speed
Noise (also HDR motor)
Temperature
Clean filter and vacuum line shutoff
4-way changeover valve (optional): check and lubricate
Oil level
Change oil in front gearbox (*)
Change oil in rear gearbox (*)
Pump’s inner washing (**)
Chack transmission pulley
(*) The first oil change must be done inside 500 hours operation.
Following changes every 5000 hours or 12 months. In order to choose
the most suitable oil, see paragraph 2.8. (**) After operation in dusty
environments, after accidental sucking of liquids inside the pump or
before a long inoperativity period it is recommended to wash the pump
inside according to the procedure described at paragraph 5.2.
• Use synthetic gear oils: “TENNEX FACTOR SYNT ISO 150”.
• In case this oil is not available, it is possible to refill the level with a
gear oil composed of polyalphaolefine (PAO), see par. 2.8.
• It is recommended to refill the oil level always with the same type: avoid
mixing of various oil types.
• When changing the oil, also replace the washer on the drainage
plug.
Checking oil level rear and front gearbox
Dispose of used oil in accordance with the
current regulations.
• Check the oil level in both gearboxes (front/rear) when the pump is
still and cold. Oil sight, refill and drainage are showed in Fig. 4.1.
• Do not run the compressor with insufficient lubrication: that may
cause seals and internal transmission members to wear quickly and/or
the compressor to stop with possible breakdown of the drive system.
Possible risk of ignition for explosive atmosphere.
OPTIMAL LEVEL
MINIMUM LEVEL
• The oil level must not drop below minimum: internal components
may rapidly wear.
• The wearing of the internal lip seals will cause the level of oil in the
boxes to drop. We strongly recommend that you often check the oil
level - every day or at the latest every week - because frequent oil
refilling indicates wearing of seals.
Arrangement
PVT 200
PVT 200 Moltiplicatore
PVT 280-400
PVT 700-1000
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
Attention: possible risk of ignition for explosive
atmosphere.
Front Gearbox (shaft side)
Rear Gearbox
DX-O-B, SX-O-B, DX-O-A, SX-O-A
0,25 l
0,50 l
DX-V-S, SX-V-D (iniezione sotto)
0,60 l
0,90 l
DX-V-D, SX-V-S (iniezione sopra)
0,60 l
0,90 l
-
1,10 l
0,55 l
DX-O-B, SX-O-B, DX-O-A, SX-O-A
0,70 l
0,60 l
DX-V-S, SX-V-D (iniezione sotto)
1,20 l
0,90 l
DX-V-D, SX-V-S (iniezione sopra)
1,20 l
0,90 l
DX-O-B, SX-O-B, DX-O-A, SX-O-A
1,80 l
1,40 l
DX-V-S, SX-V-D (iniezione sotto)
5,00 l
3,75 l
DX-V-D, SX-V-S (iniezione sopra)
5,00 l
3,75 l
26 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
• Follow installer’s instructions for the checking and servicing of
vacuum –pressure line components (filters, safety valves, seals, etc.)
drive members (belts, hydraulic drive system, etc.) controlling and
adjusting devices (revolution counters, sensors, etc.).
• See Fig. 6.1.
Follow installer’s instructions for the checking and
servicing of vacuum –pressure line components,
drive members, controlling and adjusting devices.
Flushing-Kit (optional)
Fig. 6.1
• Use appropriate protective equipment (recommended IPDs: gloves
and googles).
• The flush kit is a specific tool for the maintenance of JUROP
vacuum pumps. The regular use of the kit helps reducing the repair
costs of the pump and increase its life span.
• It’s recommended to use the flush kit every week, possibly at the
end of the working week or at any time the need arises. Use
instructions:
1. Before doing this operation wait for the pump to cool down.
Connect, if not already done, the flush kit near the blower suction
manifold. The tank position must be possibly higher than the
connection of the same with the pump.
2. Start the pump at medium speed, under conditions of use close
to the free vent.
3. Open the ball valve in order to let the flushing fluid out. We
suggest some product like Henkel BONDERITE C-NE 5225: 5%
concentration in water.
4. Flush about 0,2 litre before turning the ball valve off.
5. Keep the blower running for one minute from the closing of the
valve, letting the fluid drain out the pump.
6. Turn the blower off.
7. Drain the flushing liquid (the FD cap, pic. 4.1) and dispose of it
according to local regulations.
• To order spare parts see spare parts list at the end of this manual.
6.2
• Clean the front flange (1) and remove it.
• Replace the sealing ring (3). Spread the seal lip with high
temperature grease 220°C NLGI2.
• Change the gasket (2) and fit the flange back on its seat. Do not
damage the sealing lip nor turn it upside-down when remounting.
• The housing seat of the tongue has sharp edges: pay attention.
Model
Gasket Code (2)
Y seal Code (3)
PVT200 GEAR.
1680708700
4022200412
PVT 280-400
1680708400
4022200425
PVT 700-1000
1680710500
4022200152
Replacing the front sealing ring (PVT200)
• Replace it immediately in case lubricant leaks or every 5 years.
Attention: Replace it immediately in case
lubricant leaks or every 5 years.
• See Fig. 6.2.
Extraordinary maintenance
• Except for the cases described below, extraordinary maintenance
on a PVT must be carried out by specialized personnel only; otherwise
the guarantee will be invalidated.
• Before starting any extraordinary maintenance operation, be sure
the pump stands still and follow the safety prescriptions as described in
Cap. “Safety and accident prevention”.
Follow the safety prescriptions as described in
Cap. “Safety and accident prevention”.
Replacing the front sealing ring
(PVT 200M, PVT280, PVT 400, PVT 700, PVT 1000)
• Replace it immediately in case lubricant leaks or every 5 years.
Fig. 6.2
• Remove the drive system.
• Unscrew the oil discharge plug (SO) and empty the front tank.
• Remove the front cover.
• Replace the sealing ring (3). Spread the seal lip with high
temperature grease 220°C NLGI 2.
• Change the gasket (2) and fit the front cover back in its place. Do
not damage the seal lip nor turn it upside-down when remounting.
• The housing seat of the tongue has sharp edges: pay attention.
• Refill with oil up to an adequate level by checking the oil level glass
(L). Read Section 4.4.
Attention: replace it immediately in case lubricant
leaks or every 5 years.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
27 / 40
Model
Gasket Code (2)
Y seal Code (3)
PVT 200
1680709600
4022200154
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
Common maintenance to PVT
Cleaning of rotors and body
• This operation is necessary to remove hard formations.
• Remove the pipes from the suction and exhaust ports.
• Clean the internal surface of pump body and rotors with solvents
and scrape without scratching.
Checking the clapet valve on the injection
• Regular checking to prevent the pump from sucking scraps and to
guarantee a correct functioning (See Sec. 4.6).
• Every year: replace ORs.
• Every 3 years or when performing a general overhaul of the pump:
replace clapet valve and related screws and bolts. The valve must
allow the flow towards the pump and block it in the opposite direction.
Tilt the clapet pivoting axle by 45° from the horizontal. (See Sec. 4.6).
Replacing the rock wool inside the compact air injection
muffler
Fig. 6.3
Cleaning the gearbox venting plugs (front / rear)
• Remove the gearbox venting plugs (SS position in Section 4.4)
and clean them to remove possible obstructions.
• Keep clean the space around the gearbox venting plugs. Replace
it, if necessary. Do not use in explosive atmosphere until venting plugs
cleaning or replacement.
Attention: do not use in explosive atmosphere
until venting plugs cleaning or replacement.
• If the internal rock wool inside the compact injection muffler
degrades, thus increasing the noise level of the pump, it can be
replaced. The spare part code of the rock wool is 40222 136 00 and the
quantity is reported on the table below.
Model
Rock wool (kg)
PVT 200 - 200M - 280 - 400
2,5
PVT 700
8,5
• Unscrew and remove the muffler cover.
• Extract the used rock wool inside the muffler.
• Clean the internal surfaces of the muffler with a solvent.
• Insert the new rock wool.
• Check the internal air injection duct for cleanness before fitting the
muffler cover back in its place.
• Screw the muffler cover.
Every 10.000 working hours: general overhauling
• In case of particularly hard formations, general overhaul of the
pump is recommended: rotors wash-up, seals check, replacement of
bearing and sealing ring, and lubricant replacement. The servicing
operations which require the pump to be completely disassembled
must be performed at a Service Centre authorised by Jurop.
The servicing operations which require the pump
to be completely disassembled must be
performed at a Service Centre authorised by
Jurop.
Cleaning the seals venting plugs
• Remove the seals venting plugs (ST position in Section 4.4) and
clean them with a solvent to remove possible obstructions.
• Do not use compressed air or solvents for the seals venting ducts
in the pump benches where the seals venting ports are screwed.
Internal seals can be damaged.
Do not use compressed air or solvents for the
seals venting ducts in the pump benches where
the seals venting ports are screwed. Internal
seals can be damaged.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
28 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
02-09-2020
7. Malfunctions: troubleshooting
PROBLEMS
Reduced performances
Cause
Solution
• Speed not correct
• Check and restore
• Pipes and/or filters clogged or leaking
• Check conditions and restore
• Pipes are undersized
• Check the maximum compressor performance
• Safety valves not adjusted
• Check and adjust correctly
Overheating
Cause
Solution
• Ambient temperature and/or suction or injected air temperature is too high.
• Reduce pressure or vacuum rate
• Inefficient air injection
• Check filter for cleanness, check condition of injection line and clapet valve.
• Pipes are undersized
• Check the effective vacuum or working pressure by measuring it near the suction
ports. Do not exceed operating limits.
Oil leaks
Cause
Solution
• Front sealing ring is worn
• Replace it
• Level indicators are broken
• Replace it
• Leaking from the sealing rings
• Check the pump tilt angle (max. 3°). Check seal venting valves for cleanness.
• If this is not enough to solve the problem, please contact the After Sales Service to
have the seals checked.
Unusual vibrations or noise (stop the vacuum pump)
Cause
Solution
• The rotors are getting in contact
• Temperature is over the max. working limits (T2 > 160°C and/or T2 – T1 > 130°C:
see Sec. 3.3.2). Stop the pump and let it cool down. Start again only after the alarm
has been reset.
• Rotors with hard formations on the surface
• Internal wash-up of the pump.
• If the problem still persists, remove the pipes and clean rotors and pump body.
• Suction of liquids or foreign bodies
• If they have caused the incrustations, pipes must be removed and rotors and pump
body cleaned.
• Not uniform power transmission
• Check operating conditions. Do not install joints with a too high angle.
8. Scrapping
• Recycling materials allow reducing the environmental impact and
respecting the environment.
• Before scrapping the machine, the following materials need to be
separated and suitably disposed of:
Do not dispose of in the environment. Dispose of
in compliance with the standards in force.
Material
Cast Iron
Steel
Alluminum
Bronze
Rubber
Gasket
Oil
PVT 200
79 %
13 %
6.8 %
0.0 %
0.1 %
0.1 %
0.6 %
PVT 280
74 %
17 %
7.8 %
0.3 %
0.1 %
0.1 %
1.1 %
PVT 400
70 %
22 %
7.1 %
0.2 %
0.1 %
0.1 %
0.9 %
PVT 700
78 %
14 %
6.9 %
0.2 %
0.0 %
0.0 %
0.5 %
PVT 1000
74 %
19 %
6.1 %
0.2 %
0.0 %
0.0 %
0.4 %
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
29 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 13
02-09-2020
INSTALLATION, USE AND MAINTENANCE MANUAL
PVT 200-280-400-700-1000 ATEX
9. Accessories
PVT 200-280
MODEL
PVT 400
PVT 700
INJECTION
PVT1000
EXHAUST
PVT1000
INJECTION
PVT700
EXHAUST
PVT700
PVT400 INJECTION
PVT400 EXHAUST
INJECTION
EXHAUST
PVT200-280
Mufflers: models and dimensions
PVT200-280
9.1.
PVT 1000
TYPE
EXHAUST
INJECTION
EXHAUST
INJECTION
EXHAUST
INJECTION
EXHAUST
INJECTION
FLANGE (UNI EN 1092-1)
DN100 PN6
DN100 PN6
DN125 PN6
DN125 PN6
DN175 PN10
DN175 PN10
DN175 PN10
DN175 PN10
CODE (IRON)
1414014600
1414014700
1414014200
1414014300
1414013800
1414013900
1414014000
1414014100
CODE (INOX)
1414014800
1414014900
1414014400
1414014500
-
-
-
-
46 kg
57 kg
52 kg
64 kg
108 kg
135 kg
193 kg
220 kg
WEIGHT
9.2.
Flushing kit (cod. 18920 031 E0)
Pos.
Code
1
2
3
4
5
6
1624042800
1673001000
1685100300
1687600000
4023125000
4024405400
Description
SPACER
FILTER LINK
WASHER DI 20
SIDE OIL TANK
BUSHING
VALVE G1/8
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
Q.ty
Pos.
Code
2
1
2
1
2
1
7
8
9
10
11
4026103013
4026357007
4026702004
4026904503
4026910103
4021102005
30 / 40
Description
SCREW TE M12X90 GALV.
WASHER M12 GALV.
CONNECTION DIR 6X1/8
PLUG M20X1,5
PLASTIC VENT 1"
PIPE RILSAN
Q.ty
2
2
1
1
1
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
21-04-2020
SPARE PART DATA SHEET – PVT 200 ATEX
PVT 200 ATEX
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
31 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
21-04-2020
SPARE PART DATA SHEET – PVT 200 ATEX
PVT 200 ATEX
Pos.
Code
1
2
3
4
5
6*
7*
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
1609000400
16100BDSB0
1610513800
1613034900
1613501300
1621508100
1621508200
1624035500
1624035600
1624035700
1624036000
1624036100
1624036200
1624036300
1624036900
1624040300
1624040700
1624040800
1624040900
1624041000
162404TQB0
162404TUB0
1627104700
1640102100
1640102200
1647001200
1651002RA0
1662500800
1680609100
1680709600
1680711600
16807X7VA0
1681008400
1681008500
1681008600
1685100200
16851ABUB0
1687508900
4022104501
Description
OIL LEVEL PLATE
FLANGE
FLANGE
SUPPORT
SUPPORT
ATEX DRIVE TRILOBE SHAFT
ATEX DRIVEN TRILOBE SHAFT
SPACER 60x45x18
SPACER 54x45x4
SPACER 85x73x3
RING SPACER
SPACER 85x76x7
DISK SPACER 13MM
DISK SPACER 3MM
COMPRESSOR SPACER
SEAL BUSHING
SEAL SPACER
FRONT SPACER 1
FRONT SPACER 2
REAR SPACER 1
BUSHING
BUSHING SPACER
INJECTION MANIFOLD
FRONT COVER
REAR COVER
OIL SPREADING WASHER
TIMING GEAR
BENCH
GASKET
GASKET
GASKET
GASKET
BLOCKING PLATE
BLOCKING WASHER
SAFETY WASHER
ALUMINIUM WASHER
CUPPER WASHER
BODY
OIL LEVEL PLUG 3/8”
Pcs
Pos.
Code
Description
Pcs
2
1
1
2
4
1
1
2
1
3
4
1
2
2
2
4
4
2
2
2
1
1
1
1
1
2
2
2
1
2
2
2
12
2
2
26
1
1
2
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77*
78*
4022200154
4022200313
4022200317
4022202806
4022203601
4023115046
4023115051
4023115053
4026102808
4026107111
4026120405
4026120407
4026120411
4026120413
4026120503
4026120506
4026120509
4026121817
4026155706
4026300018
4026308005
402630RB05
4026350505
4026350506
4026350706
4026359003
4026401101
4026401806
4026500911
4026510538
4026510545
4026701602
4026701603
4026701620
4026910006
4026910102
4027400413
4028249B10
4028249B06
SEALING RING 45X65x10 VITON
OR 2162 VITON
OR 108 VITON
SEALING RING 75x55x8 VITON
RING PTFE 65x58x3.8
BEARING NUP 209 ECJ C3
BEARING NJ 209 ECJ C3
BEARING NJ 2209 ECJ C4
SCREW M8x30
SCREW M8x30
SCREW M8x25
SCREW M8x35
SCREW M8x55
SCREW M8x70
SCREW M10x20
SCREW M10x30
SCREW M10x45
SCREW M10x80
SCREW M8x18
COMPENSATING RING
BOLT M8
RING NUT M45x1.5
WASHER GROWER M8 SQUARE SEC.
WASHER GROWER M10 SQUARE S.
WASHER GROWER M8 FLAT SEC.
ALUMINIUM WASHER
PIN 3x12
PIN 10x36
TAB 10x8x63
SEEGER I68
SEEGER I85
PLUG 3/8
PLUG ½
MAGNETIC PLUG 3/8
VENTING PLUG 3/8 WITHOUT FILTER
VENTING PLUG 3/8 WITH VALVE
CLAPET
ATEX THERMOSTAT
PT100 ATEX SENSOR
1
4
20
4
8
2
1
1
4
6
10
2
17
20
4
8
1
7
12
8
12
4
48
20
4
1
4
12
1
1
2
16
1
2
4
2
1
1
1
1892007600
SET GASKET PVT200
1
PVT 200 - HDR – Atex
Pos.
Code
H1*
H2
H3*
H4
H5
H6
H7*
1470106800
1610051700
1612505100
162404TQB0
1640501500
1680709700
4024107750
Description
PVT200 ATEX HDR JOINT
SERVICING FLANGE
ATEX HDR TRANSMISSION BOX
BUSHING
FRONT COVER FOR HDR MOTOR
GASKET
ATEX HDR MOTOR
Pcs
Pos.
Code
1
2
1
1
1
2
1
H8
H9
H10
H11
H12
H13
H14
4026103402
4026120301
4026120506
4026121711
4026350503
4026350506
4026350508
Description
SCREW M8x1x10
SCREW M6x12
SCREW M10x30
SCREW M12x40
WASHER GROWER M6 SQUARE
WASHER GROWER M10 SQUARE
WASHER GROWER M12 SQUARE
Pcs
1
8
4
4
8
4
4
The components marked with (*) have been especially redesigned or newly introduced into the supply in order to meet the Atex Directive.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
32 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
SPARE PART DATA SHEET – PVT 200 ATEX
21-04-2020
PVT 200 MULTIPLIER ATEX
Pos
Code
1
2
3
4
5
6
7
8
9
10
11
12
13
1610512300
161058B2B0
162404TQB0
1624082EB0
164058B8B0
165107ZZB0
16510802B0
1680708700
1680709600
1680795CB0
1685002400
1685100200
4022104501
Description
FLANGE
FRONT FLANGE
BUSHING
SPACER
FRONT COVER
DRIVING GEAR
DRIVED GEAR
FRONT FLANGE GASKET
GASKET
GASKET
SAFETY WASHER
WASHER 17X22X1.5
OIL LEVEL PLUG 3/8''
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
Q.ty
Pos
Code
1
1
1
1
1
1
1
1
1
1
1
5
2
14
15
16
17
18
19
20
21
22
23
24
25
26
4022200412
4023105008
4023105009
4026102808
4026121405
4026121406
4026121408
4026350505
4026401806
4026500911
4026501603
4026701620
4026910102
33 / 40
Description
Y-SEAL 45X65X8
BEARING 21309 E/C3
BEARING 22207 E/C3
SCREW TE 8.8 M8X30 ZINC.
SCREW TCEI 8.8 M8X20 ZINC.
SCREW TCEI 8.8 M8X30 ZINC.
SCREW TCEI 8.8 M8X35 ZINC.
WASHER GROWER 8 ZINC.
PIN 10X36
TAB 10X8X63
TAB 14X9X63
MAGNETIC PLUG 3/8
VENTIL PLUG 3/8
Q.ty
1
1
1
1
3
10
10
23
8
1
1
2
1
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
SPARE PART DATA SHEET – PVT 280 - 400 ATEX
REV. 12
21-04-2020
SIDE INJECTION (FLANK)
SIDE INJECTION
PVT 280 - 400 ATEX
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
34 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
SPARE PART DATA SHEET – PVT 280 - 400
21-04-2020
PVT 280 - 400 ATEX
Pos.
Code
1
16215026E0
1521506900
16215027E0
1521507000
1609000400
1610512200
1611000900
1613034900
1613501300
1613501200
1624027600
1624027800
1624030200
1624036300
1624039500
1624040100
1624040200
1624040400
1624040500
1624041200
1624041400
1624041300
16271001E0
1627104600
16271005E0
1627105600
1640102000
1640500800
1647001700
1651008800
1651008900
1662500700
1680613800
1680708200
1680708400
1680711500
1681009100
1681009200
1685100200
16851ABUB0
16851DBVB0
16875002E0
1687509000
4022104502
4022200313
4022200318
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
Description
ATEX DRIVE SHAFT PVT280 ATEX
ATEX DRIVE SHAFT PVT400 ATEX
ATEX DRIVEN SHAFT PVT280 ATEX
ATEX DRIVEN SHAFT PVT400 ATEX
OIL LEVEL PLATE
DRIVE SHAFT FLANGE
PHASE-ADJUSTING HUB
SUPPORT
SUPPORT (PVT280)
SUPPORT (PVT400)
FRONT SPACER
REAR SPACER
FRONT SEAL BUSHING
OIL SPREADING DISK SPACER
OIL SPREADING DISK SPACER
FRONT SEAL BUSHING
REAR SEAL BUSHING
SPACER
SPACER
BEARING BUSHING
ADJUSTING SPACER 0.10
ADJUSTING SPACER 0.50
INJECTION MANIFOLD PVT280
INJECTION MANIFOLD PVT400
SIDE INJECTION MANIFOLD PVT280
SIDE INJECTION MANIFOLD PVT400
REAR COVER
FRONT COVER
OIL SPREADING DISK
TIMING GEAR
ADJUSTING TIMING GEAR
BENCH
GASKET
GASKET
GASKET
GASKET
BEARING PLATE
BEARING PLATE
ALUMINIUM WASHER
CUPPER WASHER
CUPPER WASHER
HOUSING PVT280
HOUSING PVT400
OIL LEVEL PLUG ½”
OR 2162
OR 2043
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
Pcs
Pos.
Code
1
1
1
1
2
1
1
4
4
4
2
2
1
1
1
2
2
2
2
2
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
Chk
1
1
1
1
1
1
1
1
1
2
2
2
1
2
2
2
14
1
2
1
1
2
2
20
35 / 40
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
Description
Pcs
4022200320
4022200322
4022200425
4022202805
4022203600
4023105007
4023110060
4023110065
4026107110
4026120403
4026120503
4026120506
4026120511
4026121815
4026120513
4026120518
4026121819
4026155706
40261D2C10
4026306309
4026306310
4026306311
4026306509
4026306510
4026306511
4026350505
4026350506
4026359003
4026401101
4026401806
4026501607
4026501609
4026502003
4026502106
4026701602
4026701603
4026701621
4026910006
4026910102
4027400414
4028249B09
4028249B06
4028249B08
1612088IB0
4026121811
4026121812
OR 2200
OR 2175
SEALING RING 80x55x10 VITON
SEALING RING 85x65x10 VITON
ANELLO PTFE 70x63x3.8
BEARING 22209 E C3
BEARING NU 2210 ECJ C3
BEARING NU 2211 ECJ C3
SCREW M8x25
SCREW M8x20
SCREW M10x20
SCREW M10x30
SCREW M10x60
SCREW M10x60 (SIDE INJECTION FLANK)
SCREW M10x70
SCREW M10x100
SCREW M10x100 (SIDE INJ. FLANK)
SCREW M8x18
SCREW M12x30
RING NUT WASHER MB9
RING NUT WASHER MB10
RING NUT WASHER MB11
RING NUT M45x1.5
RING NUT M50x1.5
RING NUT M55x2
WASHER GROWER M8 SQUARE S.
WASHER GROWER M10 SQUARE
ALUMINIUM WASHER
PIN 3x12
PIN 10x36
TAB 14x9x80 (PVT280)
TAB 14x9x100 (PVT400)
TAB 14x9x50
TAB 16x10x56
PLUG 3/8
PLUG 1/2
MAGNETIC PLUG 1/2
VENTING PLUG 3/8 WITHOUT FILTER
VENTING PLUG 3/8 WITH VALVE
CLAPET
ATEX THERMOSTAT SIL 2
PT100 ATEX SENSOR (PVT280)
PT100 ATEX SENSOR (PVT400)
PLATE FOR CLAPET VANE
SCREW M10x40 GALV.
SCREW M10X45 GALV:
2
1
1
4
8
2
1
2
8
3
8
20
9
1
20
7
3
8
6
2
1
1
2
1
1
11
64
15
2
12
1
1
1
1
7
14
2
4
2
1
1
1
1
1
3
1
1892009500
1892007700
GASKET KIT PVT280
GASKET KIT PVT400
1
1
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
21-04-2020
SPARE PART DATA SHEET – PVT 280 - 400 ATEX
PVT 280 - 400 - HDR - ATEX
Pos.
Code
H1
14701006E0
1470106900
1610052600
1610512200
1612505200
1640501100
1680708400
4022200425
4023110060
4024107551
4024107553
4026103402
H2
H3
H4
H5
H6
H7
H8
H9
H10
Description
PVT280 ATEX HDR JOINT
PVT400 ATEX HDR JOINT
ATEX TRANSMISSION FLANGE
DRIVE SHAFT FLANGE
ATEX HDR TRANSMISSION BOX
FRONT COVER FOR HDR MOTOR
GASKET
SEALING RING 80x55x10
BEARING NU 2210 ECJ/C3
ATEX HDR MOTOR (PVT 280)
ATEX HDR MOTOR (PVT 400)
SCREW M8x1x10
Pcs
Pos.
Code
1
1
1
1
1
1
1
1
1
1
1
1
H11
H12
H13
H14
H15
H16
H17
H18
H19
H20
H21
4026120403
4026120610
4026121213
4026121711
4026350505
4026350508
4026350609
4026350611
4026359003
4026401806
4026701603
Description
SCREW M8x20
SCREW M12x35
SCREW M16x50
SCREW M12x40
WASHER GROWER M8 SQUARE
WASHER GROWER M12 SQUARE
WASHER GROWER M12 FLAT SEC.
WASHER GROWER M16 FLAT SEC.
ALUMINIUM WASHER
PIN 10x36
PLUG 1/2
Pcs
3
4
4
4
3
4
4
4
1
2
1
PVT280-400 HDR ATEX (COMPACT )
Pos
Code
Description
Q.ty
H1*
H2*
H3
H4
H5*
16110010E0
HDR JOINT
1
16401129E0
HDR FRONT COVER
1
16510027E0
GEAR
1
4022200383
OR 4487
1
4024107557
PVT280 HDR MOTOR
1
4024107553
PVT400 HDR MOTOR
1
H6
4026121214
SCREW TCEI M16X55 ZINC.
1
H7
4026121715
SCREW TCEI 8,8 M 12 X 60 ZINC.
4
H8
4026136205
SCREW M6X12
2
H9
40261D2C10
SCREW TE FLANG M12X30
6
H10
4026308007
NUT M12 ESAG. ZINC.
4
H11
4026312B06
WASHER IN RAME DA 18
1
H12
4026350508
WASHER GROWER 12 ZINC.
4
H13
4026350709
WASHER GROWER 12 ZINC.
4
H14
4026385C25
WASHER M16 ZINC.
3
H15
4026701670
PLUG M C/TESTA M18X1,5
1
The components marked with (*) have been especially redesigned or newly introduced into the supply in order to meet the Atex Directive.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
36 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
21-04-2020
SPARE PART DATA SHEET – PVT 700 - 1000
PVT 700 - 1000 ATEX
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
37 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
21-04-2020
SPARE PART DATA SHEET – PVT 700 - 1000
PVT 700 - 1000 ATEX
Pos.
Code
1
2
3
4
1610513700
161104EAB0
1613501700
1621508300
1521506200
1621508400
1521506100
1624038800
1624038900
1624039000
1624039100
1624039300
1624039400
1624041500
1624041600
1624041700
1624041800
1624041900
1624042000
162404TSB0
162404TWB0
1627104800
1627105500
1627104900
1640501400
1640501600
1647001600
1647002000
165104E6B0
165104E7B0
1662500900
1680710500
1680710600
1680711700
1680711800
1680711900
16807D1WB0
1681008900
1681009300
1684002600
1685002700
1685100200
16851ABUB0
1687509200
1687509900
4022104504
4022200152
4022200305
4022200327
4022200328
4022200329
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
Description
Pcs
Pos.
Code
Description
Pcs
SHAFT FLANGE
PHASE ADJUSTING HUB
SUPPORT
ATEX DRIVE TRILOBE ROT. PVT700
ATEX DRIVE TRILOBE ROT. PVT1000
ATEX DRIVEN TRILOBE ROT. PVT700
ATEX DRIVEN TRILOBE ROT. PVT1000
SPACER
FRONT SPACER
ADJUSTING SPACER 0.50 MM
ADJUSTING SPACER 0.10 MM
DISK SPACER
DISK SPACER
FRONT SEAL BUSHING
REAR SEAL BUSHING
BEARING BUSHING
SPACER
SPACER
SPACER
BUSHING
SPACER
INJECTION MANIFOLD (PVT700)
INJECTION MANIFOLD (PVT1000)
90° MANIFOLD
FRONT COVER
REAR COVER
OIL DISK
FRONT OIL DISK
TIMING GEAR
ADJUSTABLE TIMING GEAR
BENCH
GASKET
GASKET
GASKET
GASKET
GASKET PVT700
GASKET PVT1000
BEARING FLANGE
BEARING FLANGE
BALANCING PLUG
SAFETY WASHER
ALUMINUM WASHER
COPPER WASHER
HOUSING PVT700
HOUSING PVT1000
OIL SIGHT GLASS
80x100x10 VITON SEAL
OR 3256
OR 3275
OR 119
OR 3237
1
1
4
1
1
1
1
2
1
Chk
Chk
1
1
2
2
2
1
4
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
2
1
2
2
2
2
12
8
1
2
1
1
4
1
1
2
28
2
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91*
92*
4022202807
4022203603
4023105014
4023110096
4023110097
4026101301
4026101813
40261D3C10
4026120506
4026120719
4026121711
4026121720
4026121808
4026121818
4026121823
4026155807
4026171211
4026190103
4026306313
4026306314
4026306315
4026306513
4026306514
4026306515
4026308007
4026350506
4026350508
4026350509
4026350713
4026359000
4026359003
4026401208
4026402011
4026501403
4026501408
4026510552
4026510558
4026701602
4026701603
4026701604
4026701622
4026904510
4026910008
4026910104
4027400415
4028249B09
4028249B07
SEAL 110x90x12 VITON
SEAL PTFE 100x91x4
BEARING 22213 E C3
BEARING NU314 ECJ C3
BEARING NU315 ECJ C3
SCREW M6x10
SCREW M20x50
SCREW M16X50
SCREW M10x30
SCREW M14x100
SCREW M12x40
SCREW M12x90
SCREW M10x25
SCREW M10x90
SCREW M10x140
SCREW M10x20
SCREW M12x80
EYE BOLT M20
RING NUT WASHER MB13
RING NUT WASHER MB14
RING NUT WASHER MB15
RING NUT M65x2
RING NUT M70x2
RING NUT M75x2
BOLT M12
WASHER GROWER M10
WASHER GROWER M12
WASHER GROWER M14
WASHER GROWER M20
ALUMINUM WASHER
ALUMINUM WASHER
PIN 6x24
PIN 14x55 M8
TAB 20x12x80
TAB 20x12x140
SEEGER I102
SEEGER I120
PLUG G 3/8
PLUG G 1/2
PLUG G 3/4
MAGNETIC PLUG G 3/4
PLUG M22x1.5
VENTING PLUG G 3/4 WITH FILTER
VENTING PLUG G 1/2 WITH VALVE
CLAPET VALVE
ATEX THERMOSTAT
PT100 ATEX TEMPERATURE SENSOR
4
8
2
1
2
3
4
6
8
28
20
9
12
4
11
8
8
4
2
1
1
2
1
1
16
21
44
24
4
17
7
1
12
2
1
1
4
1
5
7
2
1
4
2
1
1
1
1892007400
1892007500
GASKET KIT PVT700
GASKET KIT PVT1000
1
1
The components marked with (*) have been especially redesigned or newly introduced into the supply in order to meet the Atex Directive.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
38 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
REV. 12
SPARE PART DATA SHEET – PVT 700 - 1000
21-04-2020
PVT 700 - 1000 HDR - Atex
Pos.
Code
H1*
H2*
H3
H4*
H5
H6
H7
H8*
1470106400
1610051800
1610051900
1612504700
1640501700
1680701400
1680709700
4024107555
4024107556
Description
ATEX COUPLING PVT700 HDR
HDR TRANSMISSION FLANGE
FLANGE
HDR MOTOR MOUNTING FLANGE
FRONT COVER HDR TRANSMISSION
GASKET
GASKET
ATEX HDR MOTOR (PVT700)
ATEX HDR MOTOR (PVT1000)
Pcs
Pos.
Code
1
1
1
1
1
1
1
1
1
H9
H10
H11
H12
H13
H14
H15
H16
H17
4026103402
4026120301
4026120712
4026121212
4026121214
4026350503
4026350509
4026350611
4026401806
Description
SCREW M8x1x10
SCREW M6x12
SCREW M14x45
SCREW M16x45 GALV.
SCREW M16x55 GALV.
WASHER GROWER M6
WASHER GROWER M14
WASHER GROWER M16
PIN 10x36
Pcs
1
8
8
4
4
4
8
8
4
The components marked with (*) have been especially redesigned or newly introduced into the supply in order to meet the Atex Directive.
PVT 700-1000 HDR ATEX (COMPACT)
Pos.
Code
H1*
1611001600
1611002000
1611001700
1611002100
1640501700
1651011800
4022200346
4022200347
4022200356
4024107554
4024107557
4026120718
4026171302
H2*
H3
H4*
H5
H6
H7*
H8
Description
HDR JOINT (PVT700)
HDR JOINT (PVT1000)
MOTOR MOUNTING FLANGE (PVT700)
MOTOR MOUNTING FLANGE (PVT1000)
HDR FRONT COVER
HDR GEAR
O-RING 4562 VITON
O-RING 4550 VITON (PVT700)
O-RING 4700 VITON (PVT1000)
HDR MOTOR (PVT700)
HDR MOTOR (PVT1000)
SCREW TCEI M14X90 ZINC. (PVT700)
SCREW TCEI M14X30 ZINC. (PVT1000)
Pcs
Pos.
Code
1
1
1
1
1
1
1
1
1
1
1
8
8
H9
4026121713
4026103212
4026121922
4026135407
4026186C00
40261D3C10
4026350509
4026350709
4026350711
4026359006
4026385C33
H10
H11
H12
H13
H14
H15
H16
H17
Description
SCREW TCEI M12X50 ZINC. (PVT700)
SCREW TCEI M16X50 ZINC. (PVT1000)
SCREW TCEI M22X70 ZINC.
STUD SCREW M8X14
SCREW TCEI M12X1X20
SCREW TE FLANG M16X50
WASHER GROWER 14 ZINC.
WASHER A GROWER 12 ZINC. (PVT700)
WASHER GROWER 16 ZINC. (PVT1000)
WASHER 13,5X18X1,5
WASHER M22
Pcs
4
4
1
2
2
6
8
4
4
2
1
The components marked with (*) have been especially redesigned or newly introduced into the supply in order to meet the Atex Directive.
Jurop SpA
Via Crosera n° 50
33082 Azzano Decimo, PN (Italy)
39 / 40
TEL. +39 0434 636811 FAX. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
Model
Issue date
Revision No.
Revision date
Filled out by
Viewed by
PVT ATEX SERIES
03-11-2010
13
02-09-2020
U.T.
A.T.
Jurop SpA
Via Crosera, 50
33082 Azzano Decimo, PN (ITALY)
Tel. +39 0434 636811
Fax. +39 0434 636812
http://www.jurop.it
e-mail: info@jurop.it
Jurop SpA reserves the right to modify the products described in this manual without prior notice.
40 /
Download