2022 International Conference on Computational Intelligence and Sustainable Engineering Solutions (CISES) | 978-1-6654-8004-8/22/$31.00 ©2022 IEEE | DOI: 10.1109/CISES54857.2022.9844359 1st International Conference on Computational Intelligence and Sustainable Engineering Solution(CISES2022) Transient Switching Study for 120 MVAr Variable Shunt Reactor at 220 kV Substation Ayyaj Maner Project Engineering Adani Electricity Mumbai Mumbai, India ayyaj.maner@adani.com Sonu Karekar In-charge Netwotk Development Adani Electricity Mumbai Mumbai, India sonu.karekar@adani.com Amol Salunkhe Testing and Protection Adani Electricity Mumbai Mumbai, India amol.salunkhe@adani.com Raiju Hassan Network Development Adani Electricity Mumbai Mumbai, Inida raiju.hassan@adani.com Mahesh Ambardekar Head Project and Engineering Adani Electricity Mumbai Mumbai, Inida mahesh.ambardekar@adani.com Arvindkumar Sharma COO, Transmission Adani Electricity Mumbai Mumbai, India arvind.kumar.sharma@adani.com Abstract— This paper describes transients switching study carried out for variable shunt reactor (VSR) connected to 220 kV Grid at 220/33 kV Adani Electricity Mumbai Ltd (AEML) Gorai substation. The study model developed in the PSCAD. It includes a model for VSR, Sf6 CB, other substation equipments. Inrush currents due to uncontrolled switching and transient recovery voltage peak due to forced 5A current chopping corresponding to lowest 48 MVAr (40%) and highest 120 MVAr (100%) reactive power were determined. Based on the analysis, controlled switching device (CSD) was proposed for point on wave switching strategy for 120 MVAr VSR and operational methodology is devised. Reactive shunt compensation (bus reactors) were placed at various locations in study model and the effect on system voltages were observed. Further, the possibility of physical installation of bus reactors, i.e. space availability at substation, was also explored. Keywords — variable shunt reactor, inrush current, controlled switching, transient recovery voltage. A single VSR is always advantageous compared to, traditional fixed type shunt reactor for stabilizing the voltage for a range of loading conditions in the system. 31 Steps are considered for VSR where 1st tap provides 40% reactive power of rated one and 29th tap provides the 100% reactive power. Taps can be changed remotely to meet continuous compensation of reactive power as load varies and therefore securing voltage stability of grid. Some other key benefits are elimination of voltage jumps resulting from switching of traditional fixed type reactors, flexible for load pattern, reduced footprint of substation etc [1]. I. INTRODUCTION Mumbai Metropolitan Region (MMR), the financial capital of the country, having a mix of diversified electrical requirements ranging from households to commercial complexes, corporate Offices, data /IT Centers to industrial establishments like refineries, BARC, Port, Airport, etc. Presently the average demand of MMR is around 3500 MW. Considering importance of the region, it is necessary to provide 24x7 quality power supply to all the consumers. However, there has been consistent complaints with respect to voltage dips in and around interconnected substations of the 400/220/100 kV Kalwa S/s. by various utilities viz. M/s. HPCL, M/s. TATA, M/s. AEML & other consumers. To identify the reasons and remedial measures, the Director (Operations), MSETCL, formulated a working group comprising of members from various utilities under his leadership. A series of meetings of the working group were conducted for identifying the reasons and remedial measures thereof. It noted the reasons for frequent high magnitude voltage dips that consumer being affected was due to number of system fault occurrences in network associated with high fault currents; failure of switchgear & protection system to clear the fault instantly. Remedial measures were proposed by working group to reduce the fault current. Further group study also revealed that during winter MMR demand was lowest and system voltages were highest. 978-1-6654-8004-8/22/$31.00 ©2022 IEEE Committee report recommends the installation of bus reactors in Adani Electricity 220kV Network at Gorai S/s, will result in significant reduction in high system voltages during off peak condition. In view of installation of 120 MVAr reactor at 220 kV level; transient switching study of reactor is carried out in PSCAD and presented in this paper. Mainly there are two concerns seen while switching the reactor, which are briefly elaborated. First is the inrush current is relatively dependent on the CB pole closing instant and linearity characteristics of the reactor core [2]. Uncontrolled switching of shunt reactor may cause high magnitude inrush current [3]. It may lead to serious damages if not appropriately managed. Second is current chopping phenomena, observe while interrupting the small inductive current that leads to overvoltage across the circuit breaker terminals and shunt reactor [2]. It is due to trapped energy in the reactor. The voltage appears across the circuit breaker is termed as transient recovery voltage (TRV) which can be dangerous and risk of reignition if the peak value exceeds the rated one [4]. Controlled switching device (CSD) normally recommended to use alongwith circuit breaker for extending closing or opening command at optimum time instant on voltage or current waveform to eliminate the harmful 183 Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on April 12,2023 at 19:26:47 UTC from IEEE Xplore. Restrictions apply. 1st International Conference on Computational Intelligence and Sustainable Engineering Solution(CISES-2022) transients produced due to uncontrolled random switching [5]. 1500.0 II. MODEL IN PSCAD 1000.0 geographic information systems A. Model for VSR For switching study, 220 kV Gorai Substation is modeled alongwith its connectivity with external network represented one bus away from substation [6]. Gorai is the GIS substation with two bus system configuration with 10 bays which includes two underground cables of 9.1 km each, hybrid transmission line-1 (OH 11.6 km + Cable 0.055 km), hybrid transmission line-2 (OH 9.17 km + Cable 0.055 km), two 125 MVA transformer, one 120 MVAr VSR (proposed), two Bus PT and B/C. 500.0 Ln=1.284H 0.0 0 cross linked polyethylene 220 kV 3000.0 Frequency 50 Hz Core Type Three limb Reactive Power 120 MVAr (Tap position 29) Ψ (V.s) Voltage Rating 48 MVAr (Tap position 1) 126 A Total losses ( at 220 kV) 190 kW 78 kW Lair=0.3H 2000.0 1000.0 Ln=3.21H 0.0 0 Per phase Capacitance (winding to ground) Reactor Bushing Capacitance 500 1000 1500 i (Amp) 3.2 ηF Fig. 2. Instantaneous flux-current saturation curve of 48 MVAr shunt reactor 250 pF 853660.7 [ohm] Ia 0.0032 [uF] 3Iph2Rcu = PTot - Pfe 0.000250 [uF] Variable shunt reactor model is represented by RLC circuit shown in Fig. 3 [6]. Copper losses (Pcu) and iron losses (Pfe) are determined using equation (1) considering two scenarios first, PTot 190 kW at 314.9 A and second, PTot 78 kW at 126 A. Pfe as a constant. 0.4480 [ohm] 853660.7 [ohm] ------ equation (1) and 3Vph2 / Rfe = Pfe = PTot - Pcu Per phase copper resistance (Rcu) is calculated initially using equation (1) then iron loss (Pfe) & hence iron resistance (Rfe) is calculated using phase voltage (Vph). Ib 0.0032 [uF] 0.000250 [uF] Pcu = 3Iph2Rcu 1500 Fig. 1. Instantaneous flux-current saturation curve of 120 MVAr shunt reactor 4000.0 314.9 A 1000 i (Amp) TECHNICAL DATA OF VSR Nominal Current 500 To study the inrush current of reactor during energization requires an instantaneous flux–current saturation curves (Fig. 1 and Fig. 2) of reactor iron core [7]. Typical values provided by manufacturer are converted in to pu and then it used in nonlinear inductance element in PSCAD. It is approximated into two segments. VSR bay is modelled in detail includes 55 meter 220kV XLPE cable portion from GIS Bay to VSR, circuit breaker, transformer bushing and other high voltage equipment. Technical details of variable shunt rector are given in Table 1. TABLE I. Ψ (V.s) Lair=0.77H 0.4480 [ohm] 853660.7 [ohm] 0.0032 [uF] 0.000250 [uF] Ic 0.4480 [ohm] Fig. 3. VSR Model A bay is a power line within an electrical substation which connects a circuit (such as a power line or transformer) to a busbar Each bay typically includes circuit breakers, disconnectors, instrument transformers and surge arresters. It is suggested not to tag all these individual components. 184 Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on April 12,2023 at 19:26:47 UTC from IEEE Xplore. Restrictions apply. 1st International Conference on Computational Intelligence and Sustainable Engineering Solution(CISES-2022) B. Model for CB and Bay Equipment P = 1.29 Q = 15.68 P is in Watt Q is in MVAr V is in kV 0.5 [ohm] 0.001 [mH] Bus 0.0005 [uF] BRKA A V 1.18 [ohm] P = -0.6945 Q = 15.82 A V A V BRK 3.21 [H] Ia P = 0.07962 Q = 47.96 V = 220 2079430 [ohm] 3.21 [H] Ib 1.18 [ohm] P = -0.5166 Q = 15.78 Fig. 4. Model of circuit breaker A V Electric arc model [2] is considered for circuit breaker. Reactor switching produces transients of high frequency, bay equipments were represented by capacitance with respect to ground (Table II). For three phases in one bus GIS, manufacturer provided the capacitance 62pF per meter for the bus. The capacitance of disconnecting switches and circuit breakers does not vary greatly from the values per meter for the bus [8]. TABLE II. 2079430 [ohm] 2079430 [ohm] 3.21 [H] Ic 1.18 [ohm] Fig. 6. Steady State load flow of 48 MVAr Reactor B. Uncontrolled energization Current waveforms during uncontrolled energization of VSR with 100% capacity i.e. 120 MVAr reactive power at time instants ta =120 ms, tb=119 ms, tc = 121 ms are presented in Fig. 7. CAPACITANCE TO GROUND [8] Reactor Current (kA) GIS equipment Ia Capacitance (pF) Ib Ic 1.00 Disconnector 62 Current Transfomer 200 Potential Transformer 80 0.50 0.00 -0.50 III. SIMULATIONS OF SWITCHING TRANSIENTS -1.00 Switching transient is simulated on 100% rating of reactor (120 MVAr at highest tap) and 40% rating of reactor (48 MVAR at lowest tap). Fig. 7. Reactor Current Iamax = 969.5A , Ibmax= 841.4A , Icmax= 837.4A A. Steady State load flow Initially load flow is carried out to confirm the steady state losses and measurands, results of load flow shown in Fig. 5 and Fig. 6. Current waveforms during uncontrolled energization of with 40% capacity i.e. 48 MVAr reactive power at time instants ta =120 ms, tb=119 ms, tc = 121 ms are presented in Fig. 8. Magnitude of Inrush current are lower in case with 48 MVAr compared to 120 MVAr. P = 3.226 Q = 39.23 P is in Watt Q is in MVAr V is in kV A V x 0.150 1.283 [H] 0.448 [ohm] A V P = -1.74 Q = 39.57 BRK A V 0.250 Ib Ic 0.40 853660.7 [ohm] Ib 0.200 Reactor Current (kA) Ia P = 0.1915 Bus Q = 120 V = 220 t (sec) Simulation shows that transient inrush current with amplitude of 3.07 p.u. and high DC component can last up to 4 seconds (Fig. 9) 853660.7 [ohm] Ia 0.100 0.30 1.283 [H] 0.20 0.10 0.448 [ohm] 0.00 P = -1.295 Q = 39.48 A V Ic -0.10 853660.7 [ohm] -0.20 1.283 [H] -0.30 -0.40 0.448 [ohm] x Fig. 5. Steady State load flow of 120 MVAr Reactor 0.100 0.150 t (sec) 0.200 0.250 Fig. 8. Reactor Current Iamax = 391.7 A, Ibmax=340.5 A, Icmax= 338.7 A 185 Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on April 12,2023 at 19:26:47 UTC from IEEE Xplore. Restrictions apply. 1st International Conference on Computational Intelligence and Sustainable Engineering Solution(CISES-2022) Reactor Current (kA) 1.00 Ia Ib Ct is total capacitance parallel with the breaker (F) Ic For the SF6 breaker , λ ϵ [ 4 - 17×104 ], 0.75 0.50 Modern SF6 breakers have a relatively low arc voltage and do not tend to significantly chop current [5]. 0.25 0.00 Note: 5 A max chopping current is assumed to study the TRV peak in this study model. -0.25 -0.50 -0.75 -1.00 x 0.0 1.0 2.0 t (sec) 3.0 4.0 Transient Recovery Voltage (kV) 5.0 400 TRVA TRVB TRVC 300 Fig. 9. Uncontrolled Switching of VSR 200 100 C. Controlled energization Switching of reactor at voltage peak time instant using control switching device (CSD) significantly reduces the inrush currents in each phase. Current waveform at optimum switching instant is shown in Fig.10 for 120 MVAr reactive power and in Fig.11 for 48 MVAr reactive power. 0 -100 -200 -300 -400 x 0.120 0.130 0.140 t (sec) 0.150 Reactor Current (kA) 0.50 Ia Ib Fig. 12. Voltage across circuit breaker (TRV) at 120 MVAr Reactive Power Ic Transient Recovery Voltage (kV) 0.40 0.30 400 0.20 TRVB TRVC 300 0.10 0.00 200 -0.10 100 -0.20 0 -0.30 -100 -0.40 -200 -0.50 x TRVA 0.110 0.120 0.130 0.140 0.150 -300 t (sec) -400 x Fig. 10. Reactor Current Iamax=466.8 A, Ibmax=467.5 A, Icmax= 468.8 A 0.120 0.130 t (sec) 0.140 0.150 Reactor Current (kA) 0.40 Ia Ib Fig. 13. Voltage across circuit breaker (TRV) at 48 MVAr Reactive Power Ic 0.30 0.20 TABLE III. PEAK TRANSIENT RECOVERY VOLTAGE ACROSS CICUIT BREAKER (KV) 0.10 0.00 Reacti ve Power (MVA r) -0.10 -0.20 -0.30 -0.40 x 0.110 0.120 0.130 0.140 0.150 t (sec) Fig. 11. Reactor Current Iamax=190.3 A, Ibmax=190.1 A, Icmax= 191.1 A D. Deenergization of VSR Current chopping phenomena can be seen while interrupting the small reactor current that leads overvoltage across the circuit breaker terminals and shunt reactor [2]. Phase B U1max U1max (Ich = (Ich = 0A) 5A) Phase C U1max U1max (Ich = (Ich = 0A) 5A) 120 351.2 360.4 347.5 356.8 351.4 360.7 48 346.1 366.8 341.0 362.3 347.3 368.1 IV. RESULT Simulation Results are summarized below. A. Voltage appears across the circuit breaker immediate after current interruption is termed as transient recovery voltage which may result in damages of interrupter and nearby connected equipments. Magnitude of Transient recovery voltage peak largely depends on the magnitude of chopping current which described in equation (2) [9]. Ich = λ * √ Ct Peak TRV across Circuit Breaker (kV) Phase A U1max( U1max Ich = (Ich = 0A) 5A) Inrush Current Peak Table IV shows the magnitude of inrush current which is recorded during uncontrolled switching and controlled switching of reactor at 40% and 100% reactive power. It can be understood that magnitude of inrush current significantly reduced with controlled switching compared to uncontrolled random switching. ------ equation (2) Ich is chopping current (A) TABLE IV. λ is the chopping number (AF-0.5) Reactive Power Identify applicable funding agency here. If none, delete this text box. PEAK INRUSH CURRENT (AMP) Peak Inrush Current (Amp) Uncontrolled Switching Controlled Switching 186 Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on April 12,2023 at 19:26:47 UTC from IEEE Xplore. Restrictions apply. 1st International Conference on Computational Intelligence and Sustainable Engineering Solution(CISES-2022) (MVAr) Ia Ib Ic Ia Ib Ic 120 969.5 841.4 837.4 466.8 467.5 468.8 48 391.7 340.5 338.7 190.3 190.1 191.1 seen increasing with increase in chopping current value. Hence it is adviced to switch OFF the variable shunt reactor at lowest tap position (1st tap – 48 MVAr reactive power) for SF6 breakers (Modern) using CSD. V. CONCLUSION This paper describes transient switching study carried out for 120 MVAr VSR connected to 220 kV Adani Electricity Mumbai Network for voltage control. Simulation was performed for steady state load flow, uncontrolled switching, controlled switching for VSR at its 40% and 100% reactive power. Study shows that the magnitude of inrush current is considerably reduced to its nominal current level almost with controlled switching. Further the magnitude of TRV peak can be seen higher for forced 5A chopping current, compared to zero current chopping. TRV peak mainly depends on chopping current value. Pre-determined switching of VSR using controlled switching device (CSD) significantly reduces the inrush current, overvoltage and risk of reignition. Operational methodology for switching of VSR is devised and 220 kV grid voltage regulation at typical loading conditions also studied. B. Transient Recovery Voltage Peak Table III shows the recorded value of transient recovery voltage peak can be seen around 351 kV without chopping and 360.7 kV with forced 5A current chopping. TRV peak can be observed below the breaker’s maximum withstand voltage 375 kV. It can be seen that 55 meter 220kV XLPE cable portion used to connect 220kV GIS and reactor contributes to limit the TRV across CB and helps to reduce the shunt reactor overvoltage from 1.12 p.u. to 1.04 p.u. for a 120 MVAr capacity during deenergization. C. Bus Voltage Control Table IV shows the 220 kV Gorai bus voltage regulation with and without VSR at typical off peak loading conditions in AEML network. Simulations shows that the bus voltage of Gorai substation is reduced by 3.03 kV and 1.37 kV respectively to 120 MVAr and 48 MVAr reactive power compensation using VSR. TABLE V. ACKNOWLEDGMENT The authors like to mention special thanks to engineering, testing & protection team of AEML-T for providing data for the work presented in this paper, as well as network team for their support and providing the access of simulation software used in this paper. 220 KV VOLTAGE (KV) AT GORAI S/S 220 kV Grid Voltage (kV) at Gorai S/s Reactive Power (MVAr) Without VSR (kV) With VSR (kV) 120 236.84 233.81 48 236.84 235.47 a. REFERENCES [1] [2] PSSE used for Voltage regulation study. [3] D. Point on Wave (PoW) Switch 1) PoW switch is used to extend the open or close control command at a pre-determined point on voltage waveform for preventing inrush current and overvoltage transients. Command is extended to the phase for which voltage peak either negative or positive occurring first, then after command extend to remaining two phases with delay of 60 deg (A-C-B) [5]. 2) Further PoW helps to reduce the probability of reignition by ensuring well separation of contacts of a circuit breaker from each other before the current is interrupted. It involves identifying right instant to open the breaker so that its contacts will part just after a current zero; an arc that will extinguish less than a half-cycle later at the next current zero [5]. [4] [5] [6] [7] [8] E. Operational methodology. 1) Inrush current magnitude is observed less at lowest tap position therefore it is adviced to switch ON the variable shunt reactor at lowest tap position (1st tap – 48 MVAr reactive power). Fine tunned CSD further helps to reduce the inrush current significantly. 2) Transient recovery voltage is observed less at lowest tap position for low chopping current value and TRV can be [9] Wikipedia, Variable Shunt Reactor, WEB: https://en.wikipedia.org/w/index.php?title=Variable_shunt_reactor&o ldid=1073705973 Župan, Alan & Filipović-Grčić, Božidar & Filipović-Grčić, Dalibor. (2016). Transients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor. Electric Power Systems Research. 138. 5057. 10.1016/j.epsr.2015.12.010. Uglešić, Ivo & Filipović-Grčić, Božidar & Bojić, Srećko. (2013). Transients Caused by Uncontrolled and Controlled Switching of Circuit Breakers. "IEEE Standard Requirements, Terminology, and Test Code for Shunt Reactors Rated Over 500 kVA," in IEEE Std C57.21-2008 (Revision of IEEE Std C57.21-1990) , vol., no., pp.1-101, 1 Aug. 2008, doi: 10.1109/IEEESTD.2008.4586406. D. Goldsworthy, T. Roseburg, D. Tziouvaras and J. Pope, "Controlled Switching of HVAC Circuit Breakers: Application Examples and Benefits," 2008 61st Annual Conference for Protective Relay Engineers, 2008, pp. 520-535, doi: 10.1109/CPRE.2008.4515078. PSCAD, documentation, WEB: https://www.pscad.com/knowledgebase/download/kb-document-256.pdf Župan, Alan & Filipović-Grčić, Božidar & Uglešić, Ivo. (2017). Modelling of variable shunt reactor in transmission power system for simulation of switching transients. 10.23919/MIPRO.2017.7973495. "IEEE Guide for the Application of Transient Recovery Voltage for AC High-Voltage Circuit Breakers," in IEEE Std C37.011-2011 (Revision of IEEE Std C37.011-2005) , vol., no., pp.1-97, 28 Nov. 2011, doi: 10.1109/IEEESTD.2011.6093699. S. Qiuqin, M. Yong, X. Tianxi, L. Yang, Z. Zhicheng and T. Fengbo, "Analysis and characterization of the shunt reactor switching overvoltages interrupted by SF6 circuit breakers with chopping current," 2014 International Conference on Power System Technology, 2014, pp. 1234-1237, doi: 10.1109/POWERCON.2014.6993528. 187 Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on April 12,2023 at 19:26:47 UTC from IEEE Xplore. Restrictions apply. 1st International Conference on Computational Intelligence and Sustainable Engineering Solution(CISES-2022) 188 Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on April 12,2023 at 19:26:47 UTC from IEEE Xplore. Restrictions apply.